The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its concentration will
not exceed a set limit.
The refrigerant R410A which is used in the air
conditioner is safe, without the toxicity or
combustibility of ammonia, and is not restricted by
laws to be imposed which protect the ozone layer.
However, since it contains more than air, it poses the
risk of suffocation if its concentration should rise
excessively. Suffocation from leakage of R410A is
almost non-existent. With the recent increase in the
number of high concentration buildings, however, the
installation of multi air conditioner systems is on the
increase because of the need for effective use of floor
space, individual control, energy conservation by
curtailing heat and carrying power etc.
Most importantly, the multi air conditioner system is
able to replenish a large amount of refrigerant
compared with conventional individual air conditioners.
If a single unit of the multi conditioner system is to be
installed in a small room, select a suitable model and
installation procedure so that if the refrigerant
accidentally leaks out, its concentration does not
reach the limit (and in the event of an emergency,
measures can be made before injury can occur).
In a room where the concentration may exceed the
limit, create an opening with adjacent rooms, or install
mechanical ventilation combined with a gas leak
detection device.
The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m³)
≤ Concentration limit (kg/m³)
The concentration limit of R410A which is used in multi
air conditioners is 0.3kg/m³.
NOTE 1 :
If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should
be as charged in each independent device.
e.g., charged
amount (10kg)
Room A Room B Room C Room D Room E Room F
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in
rooms A, B and C is 10kg.
The possible amount of leaked refrigerant gas in
rooms D, E and F is 15kg.
Outdoor unit
e.g.,
charged amount (15kg)
Indoor unit
Important
NOTE : 2
The standards for minimum room volume are as
follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the
adjacent room for ventilation of leaking refrigerant
gas (opening without a door, or an opening 0.15%
or larger than the respective floor spaces at the
top or bottom of the door).
Outdoor unit
Refrigerant piping
Indoor unit
(3) If an indoor unit is installed in each partitioned
room and the refrigerant tubing is interconnected,
the smallest room of course becomes the object.
But when a mechanical ventilation is installed
interlocked with a gas leakage detector in the
smallest room where the density limit is exceeded,
the volume of the next smallest room becomes the
object.
Refrigerant piping
Outdoor unit
Very
small
room
Small
room
Mechanical ventilation device - Gas leak detector
Medium
room
Large room
NOTE 3 :
The minimum indoor floor area compared with the
amount of refrigerant is roughly as follows:
(When the ceiling is 2.7m high)
40
Range below the
35
m²
density limit
of 0.3 kg/m³
30
(countermeasures
not needed)
25
20
15
10
5
Min. indoor floor area
0
102030
Total amount of refrigerant
Range above
the density limit
of 0.3 kg/m³
(countermeasures
needed)
Indoor unit
kg
Page 3
NOTE
A direct current motor is adopted for indoor fan motor in the Concealed Duct Standard Type air conditioner.
Caused from its characteristics, a current limit works on the direct current motor . When replacing the highperformance filter or when opening the service board, be sure to stop the fan. If an above action is executed
during the fan operation, the protective control w orks to stop the unit oper ation, and the check code “P12”
may be issued. However it is not a trouble. When the desired operation has finished, be sure to reset the
system to clear “P12” error code using the leak breaker of the indoor unit. Then push the operation stop
button of the remote controller to return to the usual operation.
The important contents concerned to the safety are described on the product itself and on this Service Man ual.
Please read this Service Manual after understanding the described items thoroughly in the following contents
(Indications/Illustrated marks), and keep them.
[Explanation of indications]
Indication
DANGER
WARNING
CAUTION
∗ Property damage : Enlarged damage concerned to property, furniture, and domestic animal/pet
Indicates contents assumed that an imminent danger causing a death or serious injury of
the repair engineers and the third parties when an incorrect work has been executed.
Indicates possibilities assumed that a danger causing a death or serious injury of the
repair engineers, the third parties, and the users due to troubles of the product after work
when an incorrect work has been executed.
Indicates contents assumed that an injury or property damage ( ∗) may be caused on the
repair engineers, the third parties, and the users due to troubles of the product after work
when an incorrect work has been executed.
Explanation
[Explanation of illustrated marks]
MarkExplanation
Indicates prohibited items (Forbidden items to do)
The sentences near an illustrated mark describe the concrete prohibited contents.
Indicates mandatory items (Compulsory items to do)
The sentences near an illustrated mark describe the concrete mandatory contents.
Indicates cautions (including danger/warning)
The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.
[Confirmation of warning label on the main unit]
Confirm that labels are indicated on the specified positions
(Refer to the Parts disassembly diagram (Outdoor unit).)
If removing the label during parts replace, stick it as the original.
D ANGER
Turn “OFF” the breaker before removing the front panel and cabinet, otherwise an electric
shock is caused by high voltage resulted in a death or injury.
During operation, a high voltage with 400V or higher of circuit (∗) at secondary circuit of the highvoltage transfor mer is applied.
Turn off breaker.
Execute discharge
between terminals.
Prohibition
If touching a high voltage with the naked hands or body, an electr ic shock is caused even if using an
electric insulator.
∗ : For details, refer to the electric wiring diagram.
When removing the front panel or cabinet, execute short-circuit and discharge between highvoltage capacitor terminals.
If discharge is not executed, an electric shock is caused by high voltage resulted in a death or injury.
After turning off the breaker, high voltage also keeps to apply to the high-voltage capacitor.
Do not turn on the breaker under condition that the front panel and cabinet are removed.
An electric shock is caused by high voltage resulted in a death or injury.
4
Page 5
Check earth wires.
Prohibition of modification.
Use specified parts.
Do not bring a child
close to the equipment.
Insulating measures
No fire
WARNING
Before troubleshooting or repair work, check the earth wire is connected to the earth
terminals of the main unit, otherwise an electric shock is caused when a leak occurs.
If the earth wire is not correctly connected, contact an electric engineer for rework.
Do not modify the products.
Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury.
For spare parts, use those specified (
If unspecified parts are used, a fire or electric shock may be caused.
∗: For details, refer to the parts list.
Before troubleshooting or repair work, do not bring a third party (a child, etc.) except
the repair engineers close to the equipment.
It causes an injury with tools or disassembled parts.
Please inform the users so that the third party (a child, etc.) does not approach the equipment.
Connect the cut-off lead cables with crimp contact, etc, put the closed end side
upward and then apply a water-cut method, otherwise a leak or production of fire is
caused at the users’ side.
When repairing the refrigerating cycle, take the following measures.
1) Be attentive to fire around the cycle. When using a gas stove, etc, be sure to put out fire
before work; otherwise the oil mixed with refrigerant gas may catch fire.
2) Do not use a welder in the closed room. When using it without ventilation, carbon
monoxide poisoning may be caused.
3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may
catch the inflammables.
∗∗
∗).
∗∗
Refrigerant
Check the used refrigerant name and use tools and materials of the parts which
match with it.
For the products which use R410A refrigerant, the refrigerant name is indicated at a
position on the outdoor unit where is easy to see. To prevent miss-charging, the route of the
service por t is changed from one of the former R22.
For an air conditioner which uses R410A, never use other refrigerant than R410A.
For an air conditioner which uses other refrigerant (R22, etc.), never use R410A.
If different types of refrigerant are mixed, abnormal high pressure generates in the refrigerating cycle and an injury due to breakage may be caused.
Do not charge refrigerant additionally.
If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in
the refrigerating cycle changes resulted in change of air conditioner characteristics or
refrigerant over the specified standard amount is charged and an abnormal high pressure is
applied to the inside of the refrigerating cycle resulted in cause of breakage or injury.
Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute
vacuuming, and then newly recharge the specified amount of liquid refrigerant. In this time,
never charge the refrigerant over the specified amount.
When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant
or air other than R410A into the specified refrigerant.
If air or others is mixed with the refrigerant, abnormal high pressure generates in the
refrigerating cycle resulted in cause of injury due to breakage.
After installation work, check the refrigerant gas does not leak.
If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire
such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
Never recover the refrigerant into the outdoor unit.
When the equipment is moved or repaired, be sure to recover the refr igerant with recovering device. The refrigerant cannot be recovered in the outdoor unit; otherwise a serious
accident such as breakage or injury is caused.
Assembly/Cabling
After repair work, surely assemble the disassembled parts, and connect and lead the
removed cables as before. Perform the work so that the cabinet or panel does not
catch the inner cables.
If incorrect assembly or incorrect cable connection was done, a disaster such as a leak or
fire is caused at user’s side.
5
Page 6
WARNING
Insulator check
Ventilation
Be attentive to
electric shock
Compulsion
After the work has finished, be sure to use an insulation tester set (500V mugger) to
check the resistance is 2M
metal section (Earth position).
If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s
side.
When the refrigerant gas leaks during work, execute ventilation.
If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the
refrigerant and the closed room full with gas is dangerous because a shortage of oxygen
occurs. Be sure to execute ventilation.
When checking the circuit inevitably under condition of the power-ON, use rubber
gloves and others not to touch to the charging section.
If touching to the charging section, an electric shock may be caused.
When the refrigerant gas leaks, find up the leaked position and repair it surely.
If the leaked position cannot be found up and the repair work is interrupted, pump-down
and tighten the service valve, otherwise the refrigerant gas may leak into the room.
The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking
stove though the refrigerant gas itself is innocuous.
When installing equipment which includes a large amount of charged refrigerant such
as a multi air conditioner in a sub-room, it is necessar y that the density does not the
limit even if the refrigerant leaks.
If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is
caused.
For the installation/moving/reinstallation work, follow to the Installation Manual.
If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric
shock or fire is caused.
ΩΩ
Ω or more between the charge section and the non-charge
ΩΩ
Check after rerair
Check after reinstallation
Put on gloves
Cooling check
After repair work has finished, check there is no trouble.
If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off
the power breaker.
After repair work (installation of front panel and cabinet) has finished, execute a test
run to check there is no generation of smoke or abnormal sound.
If check is not executed, a fire or an electric shock is caused. Before test run, install the
front panel and cabinet.
Check the following items after reinstallation.
1) The earth wire is correctly connected.
2) The power cord is not caught in the product.
3) There is no inclination or unsteadiness and the installation is stable.
If check is not executed, a fire, an electric shock or an injury is caused.
CAUTION
Be sure to put on gloves (
If not putting on gloves, an injury may be caused with the parts, etc.
(∗) Heavy gloves such as work gloves
When the power was turned on, start to work after the equipment has been
sufficiently cooled.
As temperature of the compressor pipes and others became high due to cooling/heating
operation, a burn may be caused.
∗∗
∗) during repair work.
∗∗
6
Page 7
•New Refrigerant (R410A)
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer.
1. Safety Caution Concerned to New Refrigerant
The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of
refrigerant, the refrigerating oil has been also changed. Therefore, be sure that water, dust, the former refrigerant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner with new refrigerant during installation work or service work. If an incorrect work or incorrect service is performed, there is a
possibility to cause a serious accident. Use the tools and materials exclusive to R410A to purpose a safe work.
2. Cautions on Installation/Service
(1) Do not mix the other refrigerant or refrigerating oil.
For the tools exclusive to R410A, shapes of all the joints including the service port differ from those of the
former refrigerant in order to prevent mixture of them.
(2) As the use pressure of the new refrigerant is high, use material thickness of the pipe and tools which are
specified for R410A.
(3) In the installation time, use clean pipe materials and work with great attention so that water and others do
not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc. Use the clean
pipes.
Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.)
(4) For the earth protection, use a vacuum pump for air purge.
(5) R410A refrigerant is azeotropic mixture type refrigerant. Therefore use liquid type to charge the refrigerant.
(If using gas for charging, composition of the refrigerant changes and then characteristics of the air condi-
tioner change.)
3. Pipe Materials
For the refrigerant pipes, copper pipe and joints are mainly used. It is necessary to select the most appropriate
pipes to conform to the standard. Use clean material in which impurities adhere inside of pipe or joint to a
minimum.
(1) Copper pipe
<Piping>
The pipe thickness, flare finishing size, flare nut and others differ according to a refrigerant type.
When using a long copper pipe for R410A, it is recommended to select “Copper or copper-base pipe without
seam” and one with bonded oil amount 40mg/10m or less. Also do not use crushed, deformed, discolored
(especially inside) pipes. (Impurities cause clogging of expansion valves and capillary tubes.)
<Flare nut>
Use the flare nuts which are attached to the air conditioner unit.
(2) Joint
The flare joint and socket joint are used for joints of the copper pipe. The joints are rarely used for installa-
tion of the air conditioner. However clear impurities when using them.
7
Page 8
4. Tools
(1) Required T ools for R410A
Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc.
Accordingly, the tools to be used are classified into the following three types.
1) Tools exclusive for R410A (Those which cannot be used for conv entional refrigerant (R22))
2) Tools exclusiv e for R410A, but can be also used for conventional refrigerant (R22)
3) Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
Conventional air
conditioner installation
Whether new equipment
can be used with
conventional refrigerant
When recharge of the refrigerant is required, charge the new refrigerant with the specified amount in the
procedure as described below .
Recover the refrigerant and check there is no refrigerant in the
equipment.
Connect the charge hose to the packed valve service ports at gas
side, liquid side, and balance side of the outdoor unit.
Connect the charge hose to vacuum pump adaptor.
Leave it as it is for 1 to 2 minutes and check the indicator of
the compound gauge does not return.
Set the refrigerant cylinder on the electron balance, connect
the charge hose to connecting ports of the cylinder and the
electron gauge, and then charge the liquid refrigerant from the
service port at liquid side. (Shield with the gauge manifold so
that refrigerant does not flow to gas side.)
Open the packed valves of the balance pipe fully at liquid and gas
sides, and then return the valve at gas side a little to the closed side.
Open fully PMV of the outdoor unit.
• Turn on power of the outdoor unit.
• Short CN30 on I/F P.C. board of the outdoor unit.
•
Turn off power of the outdoor unit within 2 minutes after short-circuiting.
Open fully the handle Low of the gauge manifold, and then turn on
the power of vacuum pump for vacuuming.
When the pressure has lowered until indication of the compound
gauge pointed -0.1MPa (-76cmHg), open fully the handle Low and
turn off the power of vacuum pump.
Never charge the refrigerant ov er the specified amount.
Q
Do not charge the additional refrigerant.
R
If charging refrigerant additionally when refrigerant gas
leaks, the refrigerant composition in the refrigerating
cycle changes resulted in change of air conditioner
characteristics or refrigerant over the specified standard amount is charged and an abnormal high
pressure is applied to the inside of the refrigerating
cycle resulted in cause of breakage or injury.
(Charge the refrigerant as below.)
4mm-hexagonal wrench is required.
6. Environment
Use “Vacuum pump method” for an air purge (Discharge of air in the connecting pipe) in installation time.
• Do not discharge flon gas into the air to protect the earth environment.
• Using the vacuum pump method, clear the remained air (Nitrogen, etc.) in the unit. If the air remains , the
Set the equipment so that liquid refrigerant can be charged.
Q
When using a cylinder with siphon pipe, liquid can be charged without inversing the cylinder.
R
[ Cylinder with siphon ][ Cylinder without siphon ]
Refrigerant
cylinder
Electronic
balance
Gauge manifold
OUTDOOR unit
Electronic
balance
Gauge manifold
cylinder
Refrigerant
OUTDOOR unit
Siphon
R410A refrigerant is consisted with HFC mixed refrigerant.
Therefore if the refrigerant gas is charged, the composition
of the charged refrigerant changes and characteristics of
the equipment changes.
pressure in the refrigerating cycle becomes abnormally high and an injury and others are caused due to burst.
9
Page 10
1.OUTLINE
1-1. Components Lineup in Super Modular Multi Using
Total indoor unit capacity codeBelow 6.4
Total indoor unit capacity codeOver 6.4, below 14.2
Total indoor unit capacity codeOver 14.2, below 25.2
Total indoor unit capacity codeOver 25.2
Max.
4 branches
Max.
8 branches
The following 3 types of T joint pipes are collected as 1 set.
• Balance pipe (Ø9.5) ×1
• Pipe at liquid side (Corresponded dia. Ø9.5 to Ø22.2) ×1
• Pipe at gas side (Corresponded dia. Ø15.9 to Ø38.1) × 1
Total indoor unit capacity code Below 14.2
Total indoor unit capacity code Over 14.2, below 25.2
Total indoor unit capacity code Below 14.2
Total indoor unit capacity code Over 14.2, below 25.2
Usage
* In 1 line after header branch, the maximum total capacity codes 6.0 can be connected.
* The capacity code is indicated as HP equivalent. For details, refer to “Selection of refrigerant pipe”
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BRN : BROWN
Symbol
FM
TA
TC1
TCJ
TC2
LM1, LM2
DM
FS
RY302
PMV
Flow selector
unit earth
RED
Closed end
connector
S(N)R(L)
Power supply
Single phase
220-240V 50Hz
220V 60Hz
Color identification
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
GRN : GREEN
Fan motor
Indoor temp sensor
Temp sensor
Temp sensor
Temp sensor
Lover motor
Drain pump motor
Float switch
Drain control relay
Pulse Motor Valve
Parts name
screw
DM
WHI
CN304
(GRY)
RED
CN67
(BLK)
WHI
CN66
(WHI)
CN44
(BLN)
FM
CN334
1 2 3 4 5
(BLU)
1 2 3 4 56
Motor drive
+
–
T10
6 5 4 3 21 2 3
RY302
RY303
Fuse
T6.3A
250V~
P301
5 4 3 2 1
5 4 3 2 1
~
~
CN68
(BLU)
1
2
3
1
2
3
BLK
1
2
3
1
2
3
1
2
3
1
2
1
CN50
(WHI)
2
1. indicates the terminal block, letter at inside
indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
CN32
(WHI)
1 2
4 51
(Fandrive)
circuit
CN61
(YEL)
CN333
(WHI)
Fuse
T3.15A
250V~
6 4 3 1 2 5
6 4 3 1 2 5
1 2 3 4 5 6
1 2 3 4 5
Power
supply
CN60
(WHI)
6 5
4 3 2 1
(Option)
U2U
1
Outdoor unit
PMV
circuit
U
U
1
LM2
1 2 3 4 5
1 2 3 4 5
CN82
(BLU)
Indoor control P.C. board
MCC-1402
DC20V
DC15V
DC12V
DC7V
CN81
(BLK)
1 2 3 4 5
BA
2
WHI
BLKWHIBLK
CN1
(WHI)
1 2
1 2
Wired remote
controller
CN40
(BLU)
1 2
1 2
BLU
Adaptor for wireless
remote controller
BLU
1 2
1 2
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
CN41
(BLU)
1 2 3
1 2 3
BLK
BLK
BLK
WHI
CN001
(WHI)
CN309
(YEL)
CN01
(WHI)
3 3
2 2
1 1
CN02
(BLU)
LM1
1 2 3 4 5
1 2 3 4 5
CN33
(WHI)
1 2 3
1 2 3
1 2
Network adaptor
(Option)
1 2
Network
adaptor
P.C. board
1 2
1 2
X Y
CN20
(BLU)
1 2 3 4 5
TR
MCC-1401
CN03
(RED)
31
321
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRN)
CN80
(GRN)
CN73
(RED)
CN70
(WHI)
FS
CN34
(RED)
121
2
121
2
121
2
121
2
33
1
PNL
2
3
1
EXCT
2
1
Filter input
2
MMU-AP0271H, AP0301H, AP0361H, AP0481H, AP0561H
TA
TCJ
TC2
TC1
Page 14
14
Color
indication
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
Indoor unit
Earth screw
Power supply
Single phase
220-240V 50Hz
220V 60Hz
FM
Flow selector
unit earth
screw
Closed end
connector
S(N)R(L)
CN039
(YEL)
WHI
121
2
RED
343
4
565
6
77
9
(BLK)
CN304
(GRY)
1
2
3
1
2
3
CN066
(WHI)
CN044
(BRW)
TR
Line Filter
1
Outdoor unit
1
2
3
1
2
3
1
2
3
1
2
1
2
U2U
P301
CN067
(BLK)
CN040
(BLU)
1 2
1 2
BLU
BLU
U
1
U
RY004
Fuse
T5.0A
250V~
CN041
(BLU)
1 2 3
1 2 3
BLK
BLK
BA
2
CN1
(WHI)
1 2
1 2
Remote controller
FAN
CN083
YX
(WHI)
RED
RY007
3 3
1 1
CN02
(BLU)
RC
BLK
9 8 7 6
9 8 7 6
ORN
5 4 3 2 1
5 4 3 2 1
HML UL
RY006
RY005
CN050
(WHI)
1 2 3 4 5
Network
1 2
1 2
adaptor
(Option)
CN01
(WHI)
2
MCC-1401
LM
BLU
YEL
RY002
CN074
(WHI)
DM
1 2 3
1 2 3
CN068
DP
(BLU)
RY001
Power supply
1 2
1 2
1 2 3
1 2 3
circuit
CN033
1 2 3
1 2 3
1 2 3
4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
Sub P.C. board
MCC-1520
1 2 3 4 5 6
1 2 3 4 5 6
1 1
2 2
CN03
(RED)
1. indicates the terminal block, letter at inside
indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
FS
LM
(GRN)
1 2 3
1 2 3
FS
(RED)
CN030
Indoor control P.C. board
CN075
(WHI)
CN02
(YEL)
CN01
(WHI)
TR
CN061
(YEL)
1 2 3 4 5 61 2 3 4 5 6
CN032
(WHI)
1 2
Fan drive
Symbol
FM
RC
TR
LM
TA
TC1,TC2,TCJ
RY001
RY002
RY004
RY005~007
FS
DM
PMV
PMV
6 4 3
1 2 5
6 4 3
1 2 5
1 2 3
4 5 6
1 2 3
4 5 6
CN060
(WHI)
1 2 3 4 5 6
Option
Fan motor
Running capacitor
Transformer
Louver motor
Indoor temp sensor
Temp sensor
Louver control relay
Drain control relay
Heater control relay
Fan motor control relay
Float switch
Drain pump motor
Pulse Motor Valve
2-1-3. 1-way Air Discharge Cassette Type (Compact type)
Model: MMU-AP0071YH, AP0091YH, AP0121YH
15
Color
indication
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
Indoor unit
Earth screw
220-240V 50Hz
220V 60Hz
Flow selector
WHI
RED
RED
S(N)R(L)
Power supply
Single phase
FM
unit earth
screw
Closed end
connector
WHI
RC
2
4
6
CN304
(GRY)
CN309
(YEL)
AC IN
CN066
(WHI)
BLU
121
343
565
CN301
(BLK)
Heater
1
2
3
1
2
3
TR
Line Filter
1
Outdoor
unit
1
2
3
1
2
3
1
2
3
1
2
U
U2U
CN067
(BLK)
CN044
(BRW)
1 2
1 2
BLU
BLU
1
BLU
U
RY004
Fuse
T5.0A
CN041
CN040
(BLU)
1 2 3
1 2
13
1 2
BLU
BLK
BLK
BA
2
CN1
(WHI)
1 2
1 2
Remote controller
FAN
CN083
(BLU)
YX
AI-NET
central control
terminal
(WHI)
BLK
RED
9 8 7 6
9 8 7 6
HML UL
RY007
CN050
(WHI)
1 2 3 4 5
MCC-1401
CN01
(WHI)
1 1
Network
2 2
adaptor
CN03
P.C. board
(RED)
ORN
5 4 3 2 1
5 4 3 2 1
RY006
RY005
Network
1 2
adaptor
(Option)
1 2
2 1
2331
BLU
YEL
RY002
CN074
(WHI)
DM
1 2 3
1 2 3
1 2 3
1 2 3
CN068
DP
(BLU)
RY001
Power supply
LM
2 1
2 1
1 2 3
1 2 3
circuit
1 2 3
1 2 3
1 2 3
4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
Sub P.C. board
MCC-1520
1 2 3 4 5 6
1 2 3 4 5 6
CN02
(BLU)
1. indicates the terminal block, letter at inside
indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
FS
2 1
2 1
LM
(GRN)
CN033
1 2 3
1 2 3
FS
(RED)
CN030
Indoor control P.C. board
CN075
(WHI)
CN02
(YEL)
CN01
(WHI)
TR
CN061
(YEL)
1 2 3 4 5 61 2 3 4 5 6
CN032
(WHI)
1 2
Fan drive
Symbol
FM
RC
TR
LM
TA
TC1,TCJ
RY001
RY002
RY004
RY005~007
FS
DM
PMV
PMV
6 4 3
1 2 5
6 4 3
1 2 5
1 2 3
4 5 6
1 2 3
4 5 6
CN060
(WHI)
1 2 3 4 5 6
Option
Fan motor
Running capacitor
Power transformer
Louver motor
Indoor temp sensor
Temp sensor
Flap motor control relay
Drain pump control relay
Heater control relay
Fan motor control relay
Float switch
Drain pump motor
Pulse Motor Valve
(BLU)
CN082
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRW)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
PMV
2
2
1
2
2
1
2
3
1
2
1
2
1
2
3
4
5
Parts name
121
121
121
33
PNL
EXCT
1
2
TA
TCJ
TC1
Filter
Page 16
16
Indoor unit
earth screw
220-240V 50Hz
FM
RC
Flow selector
R(L) S(N)
Power supply
single phase
220V 60Hz
1
2
313
4
4
5
5
6
6
P301
BLK
RY004
1
(GRY)
3
CN304
1
(YEL)
313
AC IN
CN066
(WHI)
CN044
(BRW)
unit earth
screw
Line Filter
Closed-end
connector
CN309
1
FUSE
T5.0A 250V~
313
(BLK)
CN067
1
2
1
CN040
2
EMG
TR
U1
U1 U2
Outdoor unitRemote Controller
CN041
(BLU)
(BLU)
2
1 2331 2 3 4 5
112
1
BLU
BLU
BLK
2
112
U2 A B
2
112
CN1
RED BLK ORN BLU YEL
FAN
CN083
(WHI)
9531
RY007
RC
BLK
3
1 1
531779
M LUL
H
RY006
RY005
CN050
(WHI)
CN01(WHI)
3
CN02
2
(BLU)
CN03(RED)
LM
2
112
3
113
RY001
Power supply
circuit
1 2 3 4 5 61 21 23 4 5 61 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
Sub P.C. board
MCC-1520
1 2 3 4 5 6
1 2 3 4 5 6
Network Adapter
2
112
112
X Y
(Option)
2
MCC-1401
CN068
(BLU)
RY002
CN074
(WHI)
DM
133
1
113
DM
3
1. Indicates the terminal bolock, letter.
Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate
the wiring at side.
3. indicate the control p.c. board.
LM
CN033
(GRN)
113
Control P.C. board
for Indoor unit
MCC-1403
CN061
CN075
(YEL)
(WHI)
CN02
(YEL)
CN01
(WHI)
TR
FS
FS
3
CN030
(RED)
CN032
DRIVE
FM
RC
TR
LM
TA
TC1,TC2,TCJ
RY001
RY002
RY005~007
FS
DM
PMV
(WHI)
FAN
Symbol
PMV
1 23456
1 23456
1 2 3 4 5 6
1 2 3 4 5 6
CN060
(WHI)
OPTION
PMV
CN082
(BLU)
212
212
1
2
1
2
313
1
2
3
1
2
1
2
1
2
3
4
5
1
1
1
2
PNL
EXCT
FILTER
TCJ
TC2
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRW)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
Parts name
Fan motor
Running capacitor
Transformer
Lover motor
Indoor temp sensor
Temp sensor
Louver control relay
Drain control relay
Fan motor control relay
Float switch
Drain pump motor
Pulse motor valve
TA
TC1
Color
indication
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
RED
WHI
Closed
end
connector
Indoor unit
Earth screw
S(N)R(L)
Power supply
Single phase
220-240V 50Hz
220V 60Hz
(BLK)
CN304
(GRY)
1
2
3
1
2
3
TR
Flow selector
unit earth
screw
T10A,250V~
Closed end
connector
Spark
killer
87
43F1
FAN
CN083
(WHI)
P301
1
RY004
2
3
1
CN309
2
(YEL)
3
CN067
(BLK)
1
2
3
1
2
YEL
CN066
(WHI)
CN044
(BRW)
EMG
1
Outdoor unit
REDREDF
RED
6
4
Fuse
T5.0A
OC
U
U2U
43F1
WHI
1 2 3 4
CN040
(BLU)
1 21 2
1 2
RC
U
2
1
Remote controller
5
43F1
3
RED
GRY
1 2 3 4
WHI
RED
REDWHI
RY007
CN041
(BLU)
1 2 3
13
1 2
1 2
GRY
9 8 7 6
9 8 7 6
5 4 3 2 1
HML UL
RY006
1 2 3 4 5
BA
CN01
(WHI)
3 3
2
1 1
CN1
CN02
(WHI)
(BLU)
WHI
RC
FM
42
RY002
RY005
CN050
(WHI)
Network adaptor
(Option)
MCC-1401
1 2
1 2
CN03
1 2
(RED)
1 2
X Y
F1F2F3F
BLU
ORN
BLK
(Option)
DP
1 2 3
1 2 3
DP
(BLU)
CN068
RY001
1 2 3
1 2 3
LM
(GRN)
CN033
1 2 3
1 2 3
FS
CN030
(RED)
TA
1 2
1 2
CN104
(YEL)
Indoor control P.C. board
Power
supply
circuit
CN074
(WHI)
1 2 3
1 2 3
1 2 3
4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
Sub P.C. board
MCC-1520
1 2 3 4 5 6
1 2 3 4 5 6
1. indicates the terminal block, letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
4. When attaching a drain pump, exchange CN030 connector with a connector
of the float switch.
5. A part is connected to the terminal block.
When exchanging to the outside static pressure necessary at the local site,
check the terminal No. and lead color of the fan motor in the below diagram,
and then exchange the lead wire indicated by the arrow mark ( ),
4
6. Pay attention to change static pressure because the outside static pressure of
BRN
H tap in 50 or 60Hz.
Wired for MMD-AP0481 only
(BRN Wire)
Motor over heating protection switch
CN075
(WHI)
1 2 3 4 5 61 2 3 4 5 6
T10
CN02
(YEL)
CN01
(WHI)
TR
BLK
WHI
GRY
RED
CN061
(YEL)
49F
TCJ
1 2
1 2
CN102
(RED)
CN032
(WHI)
1 2
Fan drive
TC1
TC2
1 2 3
1 2
1 2 3
1 2
CN101
(BLK)
CN060
(WHI)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
CN082
(BLU)
1 2 3 4 5 6
Option
BLU
ORN
Sold
BRN
separately
CN100
(BRN)
1
2
3
1
2
1
2
1
2
3
4
5
6
5
4
3
2
1
Symbol
FM
RC
TR
TA
TC1,TC2,TCJ
RY005~007
RY001
RY002
PMV
F
43F1
DM
FS
PNL
EXCT
Filter
6
5
5
5
2
2
4
1
1
3
3
3
2
4
4
1
6
6
Fan motor
Running capacitor
Transformer
Indoor temp sensor
Temp sensor
Fan motor control relay
Flap motor control relay
Drain control relay
Pulse Motor Valve
Fuse
Fan motor control relay
Drain pump motor
Float switch
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
Symbol
FM
RC
TR
TA
TC1,TC2,TC3
RY005~007
RY001
RY002
PMV
F1~3
43F1,43F2
DM
FS
Fan motor inside
wiring diagram
49F
Motor over heating
protection switch
Closed-end
connector
YEL
BLU
ORN
WHI
RED
WHI
RED
Indoor unit
earth screw
R(L) S(N)
Power supply
single phase
220-240V 50Hz
220V 60Hz
Parts name
Fan motor
Running capacitor
Transformer
Indoor temp sensor
Temp sensor
Fan motor control relay
Louver control relay
Drain control relay
Pulse motor valve
Fuse for fan motor
Fan motor control relay
Drain pump motor
Float switch
Model: MMD-AP0721H, AP0961H
TC1
TC2
TCJ
RED
RED
Spark Killer
7
7
8
WHI
RED
WHI
S.K
43F243F1
8
WHI
7
WHI
S.K
AC INRED
8
6
WHI
RED
RED
RED
T10.0A, 250V~
RED
P301
(BLK)
1
3
1
313
1
313
1
2
F1
F2
F3
Closed-end
connector
RY004
(GRY)
CN304
(YEL)
CN309
FUSE
T5.0A 250V~
CN067
(BLK)
CN066
(WHI)
CN044
(BRW)
EMG
TR
Line Filter
U1 U2 A B
U1 U2
Outdoor unit
T10.0A, 250V~
T10.0A, 250V~
5
43F1
3
YEL
FAN
CN083
(WHI)
95 3 1
RY007
CN040
CN041
(BLU)
(BLU)
21 2
1 2331 2 3 4 5
112
1
BLU
BLU
BLK
112
CN1
Remote Controller
5
43F2
3
WHI
RED
GRY
1 2 3 4
4P
(RED)
1 2 3 4
FAN3
WHI
RED
GRY
H
RCCO
BLK
2
5
RC
5 3 1779
M LUL
RY006
RY005
3
1 1
RED
RED
ORW
FM3
(Option)
133
1
RY002
CN050
(WHI)
2
112
CN01(WHI)
3
CN02
2
(BLU)
CN03(RED)
2
112
X Y
F1 F2 F3 F4
YEL
BLU
ORN
DM
DP
CN068
(BLU)
1 3
RY001
Network Adapter
(Option)
MCC-1401
6
43F2
4
WHI
RED
GRY
1 2 3 4
1 2 3 4
WHI
RED
GRY
CN074
(WHI)
4P
(BLU)
FAN2
LM
CN033
(GRN)
113
Power supply
circuit
1 2 3 4 5 61 21 23 4 5 61 2 3 4 5 6
3
1 2 3 4 5 6
1 2 3 4 5
1 2 3 4 5
Sub P .C. board
MCC-1520
1 2 3 4 5
1 2 3 4 5
ORW
RC
F1 F2 F3 F4
YEL
BLU
ORN
FM2
1. Indicates the terminal bolock, letter.
Sold separately
Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate
the wiring at side.
3. indicate the control p.c. board.
4. When installing the drain pump connector
the froat switch connector to CN030 connector.
A
5. Position is connected to terminal block when change to
static pressure. Exchange the lead wire of arrow
position after check the terminal number as figure
and lead wire's color of fan motor.
6. When midifiy the high tap, to care the static pressure are
differ by 50Hz or 60Hz.
FM
RC
TR
TA
TC1,TC2,TCJ
RY001
RY002
RY004
RY005~007
PMV
112 3
CN060
(WHI)
OPTION
Symbol
FS
3
CN030
(RED)
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRN)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
TA
1
212
TCJ
1
212
TC2
1
1
2
2
TC1
1
212
1
2
PNL
3
1
EXCT
2
1
FILTER
2
1
2
3
4
5
Fan motor
Running capacitor
Transformer
Indoor temp sensor
Temp sensor
Louver control relay
Drain control relay
Heater control relay
Fan motor control relay
Pulse motor valve
indication
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
Parts name
Color
Page 23
23
Indoor unit
earth screw
RED
WHI
RED
R(L) S(N)
Power supply
single phase
220-240V 50Hz
220V 60Hz
Flow selector
unit earth
screw
Closed-end
connector
WHI
1
3
GRN
2
4
FM
5
6
For AP0071BH,AP0091BH,AP0121BH
2
112
TR
U1 U2
A BX Y
U1 U2
Outdoor unit
2
112
CN1
Remote Controller
WHI
1
3
2
4
5
6
RED
RED BLK ORN BLU YEL
FAN
CN083
(WHI)
95 3 1
RC
GRN
FM
RED
3
1 1
5 3 1779
3
2
CN01(WHI)
CN02
(BLU)
CN03(RED)
112
2
Network
adapter
(Option)
1 1
2 2
CN03
(RED)
R301
(BLK)
AC IN
1
1
EMG
WHI
1
3
313
T5.0A 250V~
313
1
CN066
(WHI)
2
1
CN044
(BRW)
2
(GRY)
CN304
(YEL)
CN309
FUSE
(BLK)
CN067
MCC-1401
1. Indicates the terminal bolock.
Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate
the wiring at side.
3. indicate the control p.c. board.
RC
RY004
CN040
(BLU)
112
2
2
424
5
5
6
6
3
3
RED BLK ORN BLU YEL
FAN
CN083
(WHI)
CN041
(BLU)
1 2331 2 3 4 5
1
5 3 1779
95 3 1
M LUL
H
RY007
RY006
CN050
CN068
(BLU)
RY002
RY005
(WHI)
CN074
(WHI)
Color
indication
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
133
1
113
3
3
CN033
(GRN)
113
RY001
Control P.C. board
Power supply
circuit
CN075
MCC-1520
(WHI)
CN02
(YEL)
CN01
(WHI)
TR
Symbol
1 2 3 4 5 6 1 21 23 4 5 61 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
Sub P.C. board
1 2 3 4 5 6
1 2 3 4 5 6
FM
RC
TR
TA
TC1,TC2,TCJ
RY001
RY002
RY004
RY005~007
PMV
112 3
CN030
for undoor unit
MCC-1403
CN061
(YEL)
(RED)
PMV
1 23456
1 23456
3
CN032
(WHI)
FAN
DRIVE
1 2 3 4 5 6
1 2 3 4 5 6
CN082
(BLU)
CN060
OPTION
(WHI)
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRW)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
PMV
Parts name
Fan motor
Running capacitor
Transformer
Indoor temp sensor
Temp sensor
Louver control relay
Drain control relay
Heater control reley
Fan motor control relay
Pulse motor valve
1. Indicates the terminal bolock, letter.
Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate
the wiring at side.
3. indicate the control p.c. board.
FS
3
CN030
112 3
MCC-1403
CN061
(YEL)
(RED)
CN032
(WHI)
FAN
DRIVE
FM
RC
TR
LM
TA
TC1,TC2,TCJ
RY001
RY002
RY005~007
PMV
PMV
1 23456
1 23456
1 2 3 4 5 6
1 2 3 4 5 6
CN060
(WHI)
OPTION
Symbol
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRW)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
PMV
CN082
(BLU)
TA
1
212
TCJ
1
212
TC2
1
1
2
2
131
3
1
2
PNL
3
1
EXCT
2
1
FILTER
2
1
2
3
4
5
Fan motor
Running capacitor
Transformer
Lover motor
Indoor temp sensor
Temp sensor
Louver control relay
Drain control relay
Fan motor control relay
Pulse motor valve
TC1
Parts name
Color
indication
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
Compressor
Pulse motor valve
2-way valve coil
4-way valve coil
Compressor case thermo.
Pipe temp. sensor (Inlet)
Pipe temp. sensor (Outlet)
Heat exchange temp. sensor
Air temp. sensor
Oil temp. sensor
Liquid temp. sensor
Case heater, 230V, 26W
Fan motor (DC)
Low pressure sensor
High pressure sensor
High pressure switch
Magnet switch
Overcurrent relay
ORN
YEL
WHI
RY503
RY502
RY504
RY506
RY507
RY508
RY509
RY516
RY517
Except 5HP, 6HP
PMV2
RED
BRN
BLU
ORN
YEL
6 5 4 3 2 1
6 5 4 3 2 1
CN301
(WHI)
RY518
Accumulator
Pressure
Pressure
Sensor
Sensor
PS
PD
RED
BLK
WHI
RED
BLK
1
2
3
4
5
6
CN800
1
2
3
4
5
6
7
8
9
CN802
Flash
CR
510CR518
1
PNK
3D
Noise filter
P.C. board
MCC-1366
WHI
4 3 1
4 3 2 1
CN501
(RED)
MCC-1429
CN30
4
33221
4
PNK
PNK
PNK
SV3ESV
WHI
4 3 2
4 3 2 1
CN500
(WHI)
Interface Control P.C. Board
(Srvice)
RY510
1 2
CN321
(RED)
1 2
BRN
heater
L1L2L3N
Power supply
terminal
Option
Board
4 3 2 1
4 3 2 1
CN508
(RED)
431ON2
SW11
431ON2
SW06
CN31
CN32
RY521RY511
1 2
CN323
(WHI)
1 2
BLK(PNK)
4WV1
Parts layout
Fan IPDU
MCC-896
Power supply
MCC-1439
Option
Option
Board
Board
4 3 2 1
4 3 2 1
4 3 2 1
4 3 2 1
CN509
CN510
(BLK)
(WHI)
31ON2
4
SW13
SW12
1
431ON2
ON
SW07
SW08
SW05SW04
SW06
D603D602D601D600D604
SW01
SW02 SW03
CR521CR511
CN307(WHI)
4 3 2 1
CN317
(BLU)
2 1
ORN
ORN
BLK(PNK)
Comp2
U1U2U3U4U5U
Connecting terminal
MG-
SW
for fan
OCR
Comp. IPDU
No.1
MCC-1502
ON
SW30
431ON2
SW09
CN305(RED)
7 5
BLU
6
MCC-1429
Comp. IPDU
MCC-1502
Option
Board
4 3 2 1
455 3 2 1
CN513
(BLU)
SW14
431ON2
SW10
5 3 13 2 17
3
BLK BLK
RED
ORN
Comp1
Interface
control
P.C. board
(I/F)
No.2
CN506(BLK)
1 2
1 2
PNK
RED
1 25
1 2
CN18
(RED)
CN21
WHI
BLU
BLU
GRY
GRY
GRY
3 1
3 1
CN17
(BLK)
T
S
R
CN07
WHI
YEL
BLU
1
331
CN502
(BLU)
CN501
(RED)
3 4
53 41 25
3 4 5
BLU
WHI
BLK
3 4
3 4 5
CN03
CN02
CN01
Reactor
PTC Themistor
BLK
WHI
RED
+–
313
1
5
5
GRY
3
3
RED
1
1
BLU
YEL
3 1
3 1
CN17
(BLK)
BLK
T
WHI
S
RED
R
CN20
WHI
RED
RED
Mg-SW OCR
1
2
4
3
5
6
A1 A2
2
4
6
Option
Board
63H1
63H2
4 3 2 1
1 3
T6.3A
FUSE
T6.3A
FUSE
4
332
4
BLK
GRY
N
380-415V 50Hz
1 3
1 3
1 3
CN306
CN308
(WHI)
CN502
CN503
(PNK)
CN504
CN505
(GRN)
CN507
CN514
CN515
(GRN)
CN516
(RED)
CN523
CN521
CN511
(GRN)
CN100
CN400
(WHI)
CN325
(YEL)
Power Supply
3phase
380 60Hz
BLU(BLK)
313
(BLU)
(WHI)
313
212
(WHI)
212
212
(YEL)
313
(BLK)
313
313
313
(YEL)
212
(WHI)
4 4
313
2 2
313
(BLK)
CN402
CN401
CN600(WHI)
5 5
4 4
313
2 2
1. The two-dot chain line indicates wiring at the local site, and the dashed line indicates
2. , , and indicate the terminal blocks and the numerals indicate the terminal numbers.
3. indicates P.C. board.
TD1
(YEL)
BLU(BLK)
1
BLU(BLK)
TD2
(RED)
BLU(BLK)
1
BLK
TS1
BLK
(GRY)
1
BLK
TE1
BLK
(BLK)
1
BLK
TO
BLK
(BLK)
1
BLU(BLK)
TK1
(BLK)
BLU(BLK)
1
BLU(BLK)
TK2
(BLU)
BLU(BLK)
1
BLU(BLK)
TK3
(BLU)
BLU(BLK)
1
BLU(BLK)
TK4
(GRN)
BLU(BLK)
1
BLK
TL
BLK
(WHI)
1
Option
board
1
BLU
BLU
1
Transformer
WHI
RED
1
PNK
RED
BLU
WHI
BLK
Earth screw
RED
L1
WHI
L2
BLK
L3
GRY
N
accessories sold separately and service cables, respectively.
* Be sure to fix the electric parts cover surely with two screws.
(Otherwise water enters into the box resulting in a trouble.)
4 3 2 1
CN512
(BLU)
31ON2
4
431ON2
T6.3A
FUSE
1
21
1
RED
WHI
3 1
L1L2L3
3 1
ORN
FM
RED
WHI
BLK
WVU
FAN IPDU
P.C. Board
MCC-896, 897
CN25
(WHI)
1
3
BLK
WHI
CM2
RED
YEL
BLU
YEL
–
+
CN01
(WHI)
BLU
3 1
3 1
CM1
CN26
(BLU)
RED
WHI
BLK
GRY
W
V
U
BLU
YEL
BLK
5
5
WHI
4
4
BLU
3
3
RED
2
2
PNK
1
1
CN25
(WHI)
1 1
2 2
3 3
BLK
WHI
RED
YEL
BLU
BLK
WHI
BLK
5 41
5 4
CN06
(WHI)
IPDU Board (2)
CN11
CN10
CN09
CN22
CN23
313
1
5
5
4
4
3
3
2
2
1
1
3 1
3 1
CN26
(BLU)
W
CN11
V
CN10
U
CN09
CN22
CN23
YEL
YEL
+– +–
Noise filter
P.C. board
MCC-1366
CN21
CN01
CN17
CN18
CN02
CN19
CN03
CN20
CN04
CN23(BLU)CN22(WHI)
1 3
1 3
1 3
1 3
PNK
RED
BLU
5 41
3 2
5 4
3 2 1
MCC-1502
CN15 CN13
YEL
BLU
CN500
(WHI)
Power supply
P.C. board for FAN
MCC-1439
CN503
(WHI)
CN504 CN505(RED)
BLK
PNK
RED
BLU
WHI
3 2
5 41
3 2 1
5 4
CN06
(WHI)
IPDU P.C. Board (1)
MCC-1502
CN13
CN15
BLK
BLK
BLK
RED
RED
RED
WHI
BLK
BLK
PNK
RED
BLU
WHI
BLK
3 2
3 2 1
CN18
(RED)
CN03
CN02
CN01
CN08
WHI
Reactor
Page 26
3.PARTS RATING
3-1. Indoor Unit
4-way Air Discharge Cassette Type
ModelMMU-AP0091H0121H0151H0181H0241H0271H0301H
Fan motorSWF-230-60-1
Drain pump motorADP-1409
Float switchFS-0218-102
TA sensorLead wire length : 155mm
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B25YGTFEDM-B40YGTF
Louver motor (panel)MP24GA
ModelMMU-AP0361H0481H0561H
Fan motorSWF-200-90-1
Drain pump motorADP-1409
Float switchFS-0218-102
TA sensorLead wire length : 155mm
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B60YGTF-1
Louver motor (panel)MP24GA
2-way Air Discharge Cassette Type
ModelMMU-AP0071WH0091WH0121WH0151WH0181WH
Fan motorAF-230-53-4GAF-230-39-4B
Running condenser for fan motorAC 400V, 1µFAC 450V, 2µF
Running capacitor for fan motorAC 400V, 1.0µFAC 450V, 2.0µF
Drain pump motorPJD-05230TF-1
Float switchFS-0208-608
Control P.C. board transformerTT-13
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B25YGTFEDM-B40YGTF
TA sensorLead wire length : 268mm
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
ModelMMU-AP0241WH0271WH0301WH0481WH
Fan motorAF-200-53-4FAF-200-92-4B
Running condenser for fan motorAC 450V, 2.5µFAC 450V, 3µFAC 450V, 5µF
Running capacitor for fan motorAC 450V, 2.5µFAC 450V, 3.5µFAC 500V, 5µ F
Drain pump motorPJD-05230TF-1
Float switchFS-0208-608
Control P.C. board transformerTT-13
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B40YGTFEDM-B60YGTF-1
TA sensorLead wire length : 268mm
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
26
Page 27
1-way Air Discharge Cassette (Compact type) Type
ModelMMU-AP0071YH0091YH0121YH
Fan motorAF-200-22-4N-1
Running capacitor for fan motorAC 400V, 1µF
Drain pump motorPJD-05230TF-1
Float switchFS-0208-602
Control P.C. board transformerTT-13
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B25YGTF
TA sensorLead wire length : 818mm
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
ModelMMU-AP0151SH0181SH0241SH
Fan motorAF-200-34-4D
Running capacitor for fan motorAC 450V, 1.5µ FAC 500V, 2.5µF
Drain pump motorPJD-05230TF-2
Float switchFS-0208-603
Control P.C. board transformerTT-13
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B40YGTF
TA sensorLead wire length : 155mm Vinyl tube
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 s i ze lead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
Concealed Duct Standard Type
ModelMMD-AP0071BH0091BH0121BH0151BH0181BH
Fan motorICF-280-120-2
Drain pump motorADP-1409
Float switchFS-0218-102
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B25YGTFEDM-B 4 0 YGTF
TA sensorLead wire length : 618mm
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 s i ze lead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
ModelMMD-AP0241BH0271BH0301BH0361BH0481BH0561BH
Fan motorICF-280-120-1ICF-280-120-2
Drain pump motorADP-1409
Float switchFS-0218-102
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B40YGTFEDM-B60YGTF-1
TA sensorLead wire length : 618mm
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 s i ze lead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
27
Page 28
Concealed Duct High Static Pressure Type
ModelMMD-AP0181H0241H0271H0361H0481H
Fan motorSTF-200-160-4BSTF-200-160-4ASTF-200-260-4CSTF-200-260-4B
Running condenser for fan motorAC 500V, 4µFAC 400V, 8µFAC 450V, 6µFAC 400V, 8µF
Drain pump motorADP-1409
Float switchFS-0218-102-6
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B40YGTFEDM-B60YGTF-1
TA sensorLead wire length : 1200mm
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
ModelMMD-AP0721H0961H
Fan motorSTF-200-370-4A
Running condenser for fan motorAC 450V, 12µF
Drain pump motorADP-1409
Float switchFS-0218-102-6
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-BAOYGTF-1
TA sensorLead wire length : 818mm
TC1 sensorØ4 size lead wire length : 2000mm Vinyl tube (Blue)
TC2 sensorØ6 size lead wire length : 2000mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 2000mm Vinyl tube (Red)
Under Ceiling Type
ModelMMC-AP0151H0181H0241H0271H0361H0481H
Fan motorSWF-280-60-1SWF-280-60-2SWF-280-120-2
Driving motor for horizontal grilleMP24GA1
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B40YGTFEDM-B60YGTF-1
TA sensorLead wire length : 155mm Vinyl tube
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
High Wall Type
ModelMMK-AP0071H0091H0121H0151H0181H0241H
Fan motorICF-280-120-3
Driving motor for horizontal grilleMT8-3-6
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B25YGTFEDM-B40YGTF
TA sensorLead wire length : 818mm Vinyl tube
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
28
Page 29
Floor Standing Cabinet Type
ModelMML-AP0071H0091H0121H0151H0181H0241H
Fan motorAF-200-19-4FAF-200-45-4FAF200-70-4K
Running condenser for fan motorAC450V, 1.2µFAC400V, 1.8µFAC450V, 2µF
TransformerTT13
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B25YGTFEDM-B40YGTF
TA sensorLead wire length : 818mm Vinyl tube
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
Floor Standing Concealed Type
ModelMML-AP0071BH0091BH0121BH0151BH0181BH0241BH
Fan motorAF-200-19-4GAF-200-70-4K
Running condenser for fan motorAC450V, 1.5µFAC450V, 1µFAC450V, 2µF
TransformerTT-13
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B25YGTFEDM-B40YGTF
TA sensorLead wire length : 818mm Vinyl tube
Ø4 size lead wire length : 2000mm Vinyl tube (Blue)
Floor Standing Type
ModelMMF-AP0151H0181H0241H0271H0361H0481H0561H
Fan motorAF-200-37RAF-200-63T
Running condenser for fan motorAC500V, 3µFAC500V, 3.5µFAC500V, 4µF
TransformerTT-13
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B40YGTFEDM-B60YGTF-1
Driving motor for vertical flapMT8-3-9
AF-200-110M -1
AF-200-160H-1
TA sensorLead wire length : 1200mm Vinyl tube
TC1 sensor
Pulse motor valve coilVPV-MOAJ524C0HAM-MD12TF-3DC12V
2-way valve coilVPV-122DQ1
VPV-122DQ 1SV2, SV3C, SV3D, SV3E
2-way valve
High-pressure SWACB-JB215OFF : 3.73MPa, ON : 2.9MPa
Pressure sensor
(For high pressure)
Pressure sensor
(For low pressure)
Fan motorMF-230-600-2DC280V, 600W
Case heaterAC240V, 26W × 3
Compressor case the rmoUS-622KX TM Q O - SSO F F : 125 °C, ON : 90°C × 2
High-pressure SWSCB-JB215OFF : 3.73MPa, ON : 2.9MPa
Pressure sensor
(For high pressure)
Pressure sensor
(For low pressure)
Fan motorMF-230-600-2DC280V, 600W
Case heaterAC200V, 26W × 3
Compressor case the rmoUS-622KX TM Q O - SSO F F : 125 °C, ON : 90°C × 2
They are provided at front,
rear, left, and right sides.
Fixing leg
3-5-2. Indoor Unit
[4-way Air Discharge Cassette Type]
Earth screw
It is included in the electric parts box.
Air outlet (Discharge)
Hot air is discharged when cooling
operation is performed.
Cold air is diacharged when heating
operation is performed.
Power source hole
Refrigerant pipe
connecting hole
Connecting valve is included inside here.
Air outlet/Air outlet flap
Select air blow direction in cooling or heating operation each.
2-way discharge/3-way discharge
2-way discharge or 3-way discharge can be selected
according to the shape or arrangement of the room.
For details, consult with the dealer which you have
purchased the air conditioner.
Clip
The clip is to open/close the air inlet grille.
[2-way Air Discharge Cassette Type]
Air outlet/Air outlet flap
Select air blow direction in cooling or heating operation each.
Earth screw
It is included in the electric parts box.
Center panel
Air inlet
Air in the room is sucked from here.
Air filter
Removes dust and trash.
(Air filter is provided in the air grille.)
Air inlet grille
Air in the room is sucked from here.
SET DATA
CODE No.
UNIT No.
SETTING
R.C. No.
TEST
UNIT
CL
SET
Wiress remote controller
(Sold separately)
Air filter
Removes dust and trash.
(Air filter is provided in the center panel.)
33
Page 34
[1-way Air Discharge Cassette Type]
Air outlet/Air outlet flap
Select air blow direction in
cooling or heating operation each.
Earth screw
It is included in the electric parts box.
Air inlet grille
Air in the room is sucked from here.
Air filter
Removes dust and trash.
(Air filter is provided in the air inlet grille.)
Earth screw
It is included in the electric parts box.
Air outlet/
Air outlet flap
Select air blow direction in cooling
or heating operation each.
Air inlet grille
Air in the room is sucked from here
Air filter
Remo ves dust and trash.
(Air filter is pro vided in the air inlet grille.)
[Concealed Duct Type]
Air outlet flange
Discharge duct is
connected.
Air filter
Removes dust and trash.
(Air filter is provided in the air inlet grille.)
Earth screw
It is included in the electric
parts box.
Air inlet
Air in the room is
sucked from here
[Concealed Duct, High Static Pressure Type]
Air inlet
Suction duct is connected.
Air outlet
Discharge duct is connected.
Earth screwDrain pan
Earth screws are provided in the
electric parts box.
CODE No.
SET DATA
UNIT No.
SETTING
R.C. No.
TEST
UNIT
CL
SET
Wiress remote controller
(Sold separately)
34
Page 35
3-6. Parts Name of Remote Controller
Operation section
• Using a remote controller, maximum 8 indoor units can be operated.
• After the operation contents have been once set up, the remote controller can be operated by pushing ON/
OFF buttons only.
Display section
In the display example, all indicators are displayed for the explanation.
In reality only, the selected contents are indicated.
• When turning on the leak breaker at the first time, [SET DATA] flashes
on the display part of the remote controller. While this display is
flashing, the model is being automatically confirmed. Accordingly, wait
for a while after [SET DATA] display has disappeared, and then use
the remote controller.
1
Central control
8
2
CODE No.
4
3
5
SET DATA
SETTING
TEST
UNIT No.
R.C. No.
6
7
1
SET DATA display
Displayed during setup of the timer.
10
Set up temperature display
The selected set up temp. is displayed.
SET DATA
SETTING
SET
10
12
14
TEST
CL
UNIT No.
R.C. No.
UNIT
11
13
CODE No.
Display
section
Operation
section
9
2
Operation mode select display
The selected operation mode is displayed.
3
CHECK display
Displayed while the protective device works or a
trouble occurs.
4
Timer time display
Time of the timer is displayed. (When a trouble
occurs, the check code is displayed.)
5
Timer SETIN setup display
When pushing the Timer SETIN button, the
display of the timer is selected in order of
[OFF] → [OFF] repeat OFF timer →
[ON] → No display.
6
Filter display
If “FILTER ” is displayed, clean the air filter.
7
TEST run display
Displayed during a test run.
8
Flap position display
Displays flap position.
9
SWING display
Display ed during up/down movement of the flap.
11
Remote controller sensor display
Displayed while the sensor of the remote
controller is used.
12
PRE-HEAT display
Displayed when the heating operation starts or
defrost operation is carried out.
While this indication is displayed, the indoor
fan stops or the mode enters in LO W.
13
No function display
Displayed if there is no function even if the
button is pushed.
14
Air volume select display
The selected air volume mode is displayed.
(AUTO)
(HIGH)
(MED.)
(LOW)
15
Stand by display
Displayed when unit cannot start cooling
operation because other indoor units are being
heating operation.
35
Page 36
Operation section
Push each button to select a desired operation.
• The details of the operation needs to be set up once, afterward, the air conditioner can be used by pushing
button only.
1
7
8
2
3
9
4
5
1
Air volume select button
Selects the desired air volume mode.
2
Timer set button
TIMER SET button is used when the timer is set
up.
3
Check button
The CHECK button is used for the check operation. During normal operation, do not use this
button.
4
Fan button
FAN button is used when a fan which is sold on
the market or etc. is connected.
• If “No function” is displayed on the remote
controller when pushing the FAN button, a fan
is not connected.
SET
CL
6
UNIT
10
8
When the button is pushed, the operation
starts, and it stops by pushing the button
again.
When the operation has stopped, the operation lamp and all the displays disappear.
9
Operation select button
Selects desired operation mode.
10
Set up temperature button
Adjusts the room temperature.
Set the desired set temperature by pushing
button
or .
5
Filter reset button
Resets (Erases) “FILTER ” display.
6
UNIT and AUTO flap button
Select a unit No.
UNIT
Automatic swing or adjust flap angle
7
Operation lamp
Lamp is lit during the operation. Lamp is off
when stopped.
Although it flashes when operating the protection
device or abnormal time.
OPTION :
Remote controller sensor
Usually the TEMP. sensor of the indoor unit senses
the temperature. The temperature on the surrounding of the remote controller can also be sensed.
For details, contact the dealer from which y ou have
purchased the air conditioner.
36
Page 37
3-7. Correct Usage
2
4
LOW MED. HIGH
AUTO
When you use the air conditioner for the first time or when you change the SET DATA value, follow the procedure below. From the next time, the operation displayed on the remote controller will start by pushing the
button only.
Preparation
Turn on the main power switch and/or the leakage breaker.
• When the power supply is turned on, a partition line is displayed on the display part of the remote controller.
* After the power supply is turned on, the remote controller does not accept an operation for approx. 1 minute,
but it is not a f ailure.
REQUIREMENT
• While using the air conditioner, operate it only with button without turning off the main power
switch and the leak breaker.
1
3
UNIT
CL
SET
1
Push button.
The operation lamp goes on, and the operation starts.
2
Select an operation mode with the “MODE” button.
One push of the button, and the display
changes in the order shown on the right.
• In HEAT mode, if the room temperature reaches to
the set temperature, the outdoor unit stops and the air
flow becomes LOW and the air volume decreases.
• In the defrost mode, the fan stops so that cool air is not discharged and PRE-DEF is displa yed.
3
Select air volume with “FAN ” button.
One push of the button, and the display
changes in the order shown on the right.
• When air volume is “AUTO ”, air volume differs according to the temperature difference between set
temp. and room temp.
• In DRY mode, “AUTO ” is displayed and the air volume is LOW.
• In heating operation, if the room temperature is not heated sufficiently with VOLUME “LOW ” operation,
select “MED. ” or “HIGH ” operation.
Cooling only model
DRYCOOLFAN
Heat-pump model
HEATDRYCOOLFAN
(Dehumidity)
4
Determine the set up temperature by pushing the “TEMP. ” or “TEMP. ” button.
Stop
Push button.
The operation lamp goes off, and the operation stops.
37
Page 38
3-8. Automatic Operation (Auto Changeover)
When you set the air conditioner in mode or switch over from AUTO operation because of some settings
change, it will automatically select either cooling, heating, or fan only operation depending on the indoor temperature.
Start
1
Push this button to start the air conditioner.
2
Mode select button (MODE)
Select Auto.
3
Temperature button
Set the desired temperature.
• In case of cooling, start the operation after approx. 1 minute.
• In case of heating, the operation mode is selected in accordance with the room temperature and operation
starts after approximately 3 to 5 minutes.
• When you select the Auto mode, it is unnecessary to set the fan speed. The FAN speed display will show
AUTO and the fan speed will be automatically controlled.
• After the heating operation has stopped, FAN operation may continue for approx. 30 seconds.
• When the room temperature reaches the set temperature and the outdoor unit stops, the super low wind is
discharged and the air volume decreases excessively. During defrost operation, the fan stops so that cool
air is not discharged and “HEAT READY” is displayed.
• If the Auto mode is uncomfortable, you can select the desired conditions manually.
button
NOTE
When restarting the operation after stop
• When restarting the operation immediately after stop, the air conditioner does not operate for approx. 3
minutes to protect the machine.
Stop
Push button.
Push this button again to stop the air conditioner.
38
Page 39
3-9. TIMER Operation
OFF
(OFF timer)(Repeat OFF timer)
No display
(ON timer)
OFFON
A type of timer operation can be selected from the following three types .
OFF timer: The operation stops when the time of timer has reached the set time.
Repeat OFF timer : Every time, the operation stops after the set time has passed.
ON timer: The operation starts when the time of timer has reached the set time.
Timer operation
1
UNIT
2
1
Push TIMER SET button.
• The timer display (type) changes for ev ery
push of the button.
• SET DATA and display flashes.
2
Push to select “SET TIME”.
For every push of b utton, the set time increases in the unit of 0.5 hr (30 minutes).
The maximum set time is 72.0 hr.
For every push of button, the set time decreases in the unit of 0.5 hr (30 minutes).
The minimum set time is 0.5 hr.
3
Push SET button.
• SET DATA display disappears and display goes on.
(When ON timer is activated, time is displayed, and after time of the timer has been up, displays other
than ON disappear.)
SET
3
CL
4
Cancel of timer operation
4
Push CL button.
• TIMER display disappears.
• When the operation stops after the timer reached the preset time, the Repeat OFF timer resumes the
operation by pushing button and stops the operation after the time of the timer has reached the
set time.
NOTICE
39
Page 40
3-10. Re-Installation
DANGER
Ask the dealer or an installation professional to re-install the air conditioner to a new place
or move it to another place and to observe the following items.
If the air conditioner is inappropriately by installed by yourself, it may cause electric shock
or fire.
Do not install the air conditioner in the following places
• Do not install the air conditioner in any place within 1 m from a TV, stereo, or radio set. If the unit is installed in
such place, noise transmitted from the air conditioner affects the operation of these appliances .
• Do not install the air conditioner near a high frequency appliance (sewing machine or massager for business
use, etc.), otherwise the air conditioner may malfunction.
• Do not install the air conditioner in a humid or oily place, or in a place where steam, soot, or corrosive gas is
generated.
• Do not install the air conditioner in a salty place such as seaside area.
• Do not install the air conditioner in a place where a great deal of machine oil is used.
• Do not install the air conditioner in a place where it is usually exposed to strong wind such as in seaside area
or on the roof or upper floor of a building.
• Do not install the air conditioner in a place where sulfureous gas generated such as in a spa.
• Do not install the air conditioner in a vessel or mobile crane. Be careful with noise or vibrations
• Do not install the air conditioner in a place where noise by outdoor unit or hot air from its air outlet annoys
your neighbors.
• Install the air conditioner on a solid and stable foundation so that it prevents transmission of resonating,
operation noise and vibration.
• If one indoor unit is operating, some sound may be audible from other indoor units that are not operating.
3-11. Troubles and Causes
CAUTION
If any of the following conditions occur, turn off the main power supply switch and immediately contact the
dealer :
• The operation lamps flash at short intervals (5 Hz) even though you have tried turning off the power
supply and turning on again after 2 or 3 minutes.
• Switch operation does not work properly.
• The main power fuse often blows out, or the circuit breaker is often activ ated.
• A foreign matter or water fall inside the air conditioner.
• Any other unusual conditions are observed.
40
Page 41
3-12. Information
Confirmation before operation
• Turn on the power switch 12 hours before starting
the operation.
• Make sure whether earth wire is connected.
• Make sure the air filter is connected to the indoor
unit.
Heating capacity
• A heat pump system which absorbs heat from
outside of the room and then discharges heat into
the room is adopted for heating. If the outside
temperature falls, the heating capacity decreases .
• When the outside temperature is too low, it is
recommended to use this air conditioner together
with other heating equipment.
Defrost during heating operation
• In heating operation, if there is frost on the outdoor
unit, the operation changes automatically to the
defrost operation (Approx. 2 to 10 minutes) to
increase the heating efficiency.
• During defrost operation, the fan of the indoor unit
stops.
3-minutes protection
Protective device (High pressure switch)
This device stops automatically an operation when
excessive force is applied on the air conditioner.
If the protective device works , the operation stops
and the operation lamp flashes.
When the protective device works, the indication
and the check code are displayed on the
display section of the remote controller. In the
following cases, the protective device may work.
In cooling operation
• The suction port or discharge port of the outdoor
unit is closed.
• A strong wind continuously blows to the discharge
port of the outdoor unit.
In heating operation
• Dust or waste adheres excessively to air filter of
the indoor unit.
• The discharge port of the indoor unit is closed.
If the protective device works, turn off the main
power switch, solve the cause, and then start the
operation again.
• When restarting the operation just after the
operation has been stopped or the main power
switch has turned on, the outdoor unit does not
work for approx. 3 minutes in order to protect the
air conditioner.
Power failure
• If a power failure occurred during operation, all
operations stop.
• When the power is returned after a power f ailure,
the operation lamp notifies the power-ON by
flashing operation lamp on the remote controller.
• When restarting the operation, push
button again.
Fan rotation in stopped unit
• In heating operation even in the stopped indoor
unit, the fan rotates once for several minutes per
approx. an hour when the other indoor unit is
operating to protect the air conditioner.
Cooling/Heating operation of Super
Modular Multi system air conditioner
• Although each indoor unit can be individually
controlled in the Super Modular Multi system air
conditioner, the cooling oper ation and the heating
operation cannot be simultaneously performed in
the multiple indoor units which are connected to
an outdoor unit.
• If the cooling operation and the heating operation
are simultaneously performed, the indoor unit
which executes cooling operation stops, and on
the operation section lights up. On the other hand,
the indoor unit which executes heating operation
continues running. In a case that the manager of
the air conditioner has fixed the operation to
cooling or heating, an operation other than that set
up is unavailab le. If an operation other than that
set up is executed, on the operation section
lights up and the operation stops.
Characteristics of heating operation
• The wind is not out just after starting an operation.
The hot wind starts to blow 3 to 5 minutes after
(Time differs according to indoor/outdoor temperature.) the indoor heat exchanger has warmed up.
• During operation, the outdoor unit may stop if the
outside temperature rises.
41
Page 42
3-13. Adjustment of Air Direction
To increase the cooling/heating efficiency ,
be sure to make proper use of the discharge
flap for cooling or heating operation.
As the characteristics of air, cool air collects at
lower levels, and hot air collects at higher levels.
Set t h e flap so that air blows out horizontally.
If cooling operation is performed with the flap blowing air
downwards, the air outlet or surface of the flap will be
wet with dew, and dewdrop may fall down.
CAUTION
[4-way Air Discharge Cassette Type]
In cooling operation
• Use the discharge
flap with horizontal
set point.
• When the air conditioner stops, the flap (adjustment plate of up/down air direction) directs downward automatically.
• When the heating operation is in READY states, the flap (adjustment plate of up/down wind direction) directs
upward. The swinging starts after HEAT READY status cleared, SWING is displayed on the remote controller even if the heating operation is in READY status.
How to set up the air direction
1
Push during operation.
The air direction changes for every push of the button.
In heating operation
• Use the discharge
flap with downward
set point.
In HEAT operation
Direct the flap (adjustment plate of up/down air
direction) downward. If directing at upward, hot
air may not come to the foot.
In COOL/DRY operation
Direct the flap (adjustment plate of up/down air
direction) upward. If directing it downward, the
dew may from on the surface of the air discharge port and may drop down.
Initial setup
1, 2, 34
In FAN operation
Initial setup
How to start swing
2
Push , set the flap (adjustment plate of up/down
air direction) direction to the lowest position, and then
push
SWING is displayed and the up/down wind direction is
automatically selected.
again.
How to stop swing
3
Push SWING/WIND again while the flap is swing.
• The flap stops at a position when you push. After then, if pushing , the air direction descends from
the highest position.
• In COOL/DRY operation, the flap does not stop as it directs downward. If stopping the flap as it directs
downward during swing oper ation, it stops after moving to the 3rd position from the highest position.
SET
Initial setup
Display when stopping the swing
Fan/Heat
operation
UNIT
CL
In all modes
Series of
operation
Cool/Dry
operation
4 Auto flap button
• Push
Then the indoor unit No. in a group control is displayed.
For the displayed indoor unit, set up the air direction.
• If the unit No. is not displayed, all the indoor units are operated at the same time.
• Every pushing
UNIT
UNIT
to set up the air direction individually in each indoor unit.
, the display is e xchanged as follows:
UNIT
42
No
display
Unit No.
Unit No.
1-4
1-1
Unit No.
1-2
Unit No.
1-3
Page 43
2-way/3-way air discharge
2-way discharge or 3-way discharge can be selected according to the shape or arrangement of the room.
For details, consult with the dealer which you have purchased the air conditioner.
NOTES
• If cooling operation is executed under condition of downw ard blowing, the cabinet or surface of the horizontal flap gets wet with dew and may drop.
• During heating operation under condition of horizontal blowing, unevenness of temperature may increase
in the room.
• Never handle the horizontal flap directly with hands, otherwise a trouble is caused. Use the flap operation
switch on the remote controller to change direction of the horizontal flap. The horizontal flap does not stop
even if pushing the horiz ontal flap. Adjusting the stop position, push the switch.
[2-way Air Discharge Cassette Type]
In cooling operation
Use the air outlet flap with horizontal set point.
Setup of air direction and swinging
1, 2
SET
Heating operation
Use the air outlet flap with downward set point.
UNIT
CL
3
1
Push during operation.
• is displayed and the air direction is auto-
matically exchanged upward/downw ard.
When a remote controller operates the multiple
indoor units, an indoor unit is selected and air
direction can be individually set up.
2
Push again during swinging of the
flap.
• You can stop the flap at the desired position.
43
3
Auto flap button
• Push
individually in each indoor unit. Then the indoor
unit No. in a group control is displayed. For the
displayed indoor unit, set up the air direction.
• If the unit No. is not displayed, all the indoor
units are operated at the same time.
• Every pushing
changed as follows:
UNIT
No
display
Unit No.
UNIT
to set up the air direction
, the display is ex-
UNIT
Unit No.
1-1
1-4
Unit No.
1-2
Unit No.
1-3
Page 44
[1-way Air Discharge Cassette Compact Type]
<Up/Down air direction adjustment>
In cooling operation
In cooling operation, use the air outlet flap with
horizontal set point so that cool air diffuses the whole
room.
<Left/Right air direction adjustment>
When you change the blowout direction to left/right,
direct the vertical grille inside of the air outlet flap to
desired direction.
<Setup of air direction and swing>
Refer to that of 2-way Air Discharge Cassette Type.
In heating operation
In heating operation, use the air outlet flap with
downward set point so that the hot air is spread to
the floor.
[Under Ceiling Type]
<Up/Down air direction adjustment>
In cooling operation
In cooling operation, use the air outlet flap with
horizontal set point so that cool air diffuses the whole
room.
<Left/Right air direction adjustment>
When you change the blowout direction to left/right,
direct the vertical flap inside of the air outlet flap to
desired direction.
In heating operation
In heating operation, use the air outlet flap with
downward set point so that the hot air is spread to
the floor.
44
Page 45
[Concealed Duct Standard Type]
When using a air outlet port unit (sold separately), adjust the air direction as follows:
In cooling operation
In cooling operation, use the air outlet flap with
horizontal set point so that cool air diffuses the whole
room.
[High Wall Type]
In heating operation
In heating operation, use the air outlet flap with
downward set point so that the hot air is spread at
the foot.
<Up/Down air direction adjustment>
In cooling operation
In cooling operation, use the air outlet flap with
horizontal set point so that cool air diffuses the whole
room.
<Left/Right air direction adjustment>
When you change the blowout direction to left/right,
direct the vertical flap inside of the air outlet flap to
desired direction.
In heating operation
In heating operation, use the air outlet flap with
downward set point so that the hot air is spread to
the floor.
45
Page 46
[Floor Standing Cabinet Type]
In cooling operation
In cooling operation, use the air outlet flap with
horizontal set point so that the cold air diffuses in
whole room.
In heating operation (For Heat-pump model only)
In heating operation, use the air outlet flap with
downward set point so that the hot air blo ws at the
foot.
[Floor Standing Type]
<Adjustment of air direction upward/downward>
In cooling operation
In cooling operation, move the flap with hands and use it with horizontal
air outlet point so that the cold air diffuses in whole room.
In heating operation (For Heat-pump model only)
In heating operation, move the flap with hands and use the air outlet flap
with downward set point so that the hot air blo ws at the foot.
<Adjustment of air direction rightward/leftward>
Lift up the vertical flap lightly, direct it toward the desired direction, and lower it.
In this case, do not use the Swing function.
2
In this case, do not use the
swing function.
1
46
Page 47
3-14. Air Conditioner Operations and Performance
3 minutes protection function
3-minutes protection function prevents the air conditioner from starting for initial 3 minutes after the main power
switch/circuit breaker is turned on f or re-starting the air conditioner .
Power failure
P o wer failure during operation will stop the unit completely.
• To restart the operation, push the START/STOP button on the remote controller.
• Lightning or a wireless car telephone operating nearby may cause the unit to malfunction. Turn off the main
power switch or circuit breaker and then turn them on again. Push the START/STOP button on the remote
controller to restart.
Heating characteristics
Preheating operation
The air conditioner will not deliver warm air immediately after it is turned on. Warm air will start to flow out after
approximately 5 minutes when the indoor heat exchanger warmed up.
Warm air control (In heating operation)
When the room temperature reaches the set temperature, the fan speed is automatically reduced to prevent to
blow cold draft. At this time, the outdoor unit will stop.
Defrosting operation
If the outdoor unit is frosted during the heating operation, defrosting starts automatically (for approximately
2 to 10 minutes) to maintain the heating capacity.
• The fans in both indoor and outdoor units will stop during the defrosting operation.
• During the defrosting operation, the defrosted water will be drained from the bottom plate of the outdoor unit.
Heating capacity
In the heating operation, the heat is absorbed from the outside and brought into the room. This way of heating
is called heat pump system. When the outside temperature is too low, it is recommended to use another heating
apparatus in combination with the air conditioner.
Attention to snowfall and freeze on the outdoor unit
• In snowy areas, the air inlet and air outlet of the outdoor unit are often covered with snow or frozen up.
If snow or freeze on the outdoor unit is left as it is, it may cause machine failure or poor warming.
• In cold areas, pay attention to the drain hose so that it perfectly drains water without water remaining inside for
freeze prevention. If water freezes in the drain hose or inside the outdoor unit, it may cause machine failure or
poor warming.
Air conditioner operating conditions
For proper performance, operate the air conditioner under the following temperature conditions:
Cooling operation
Dry operation
Outdoor temperature : –5°C to 43°C
Room temperature: 21°C to 32°C (Dry valve temp.), 15°C to 24°C (Wet valve temp.)
CAUTION
Outdoor temperature : 15°C to 43°C (Maximum suction air temp. 46°C)
Room temperature: 17°C to 32°C
Room relative humidity – less than 80 %. If the air conditioner operates
in excess of this figure, the surface of the air conditioner may cause dewing.
Heating operation
If air conditioner is used outside of the above conditions, safety protection may work.
Outdoor temperature : –15°C to 15°C (Wet valve temp.)
Room temperature: 15°C to 28°C (Dry valve temp.)
47
Page 48
3-15. Maintenance
Suction grille
Button
For maintenance, be sure to turn off the main power switch.
W ARNING
• Please do not intend to do the daily
maintenannce and/or Air Filter cleaning by
yourself.
Otherwise, you ma y contact with re volving fan or
active electrity when you insert your hands into the
unit during running of the air conditioners.
Do not handle the buttons with wet
hands; otherwise an electric shock
may be caused.
CAUTION
<Daily maintenance>
Cleaning of air filter
1
If is displayed on the remote controller,
maintain the air filter.
2
Clogging of the air filter decreases cooling/
heating efficiency.
• After cleaning, push button. displa y disap-
pears.
1,
2
[4-way Air Discharge Cassette Type]
• When using an elevator panel, move down the suction port with the elevator remote controller.
CODE No.
1
Open the suction port.
• Slide the clip of the suction port to inside and
open the suction port slowly while holding it.
2
Take out the air filter.
• Push the extrusion of the air filter to inside and
pull out it to take out the air filter.
3
Cleaning with water or vacuum cleaner
• If dirt is heavy, clean the air filter by tepid water
with neutral detergent or water.
• After cleaning with water, dry the air filter
sufficiently in a shade place.
4
Mount the air filter.
5
Close the suction port.
• Close the suction port, slide the clip outward,
and then fix it surely.
6
Push .
• display disappears.
Cleaning of oil guard filter
• Clean the oil guard filter once per 2 weeks.
• Clean the oil guard filter by tepid water with neutral
detergent or water.
• After cleaning with water, rinse and dry the oil guard
filter sufficiently in a shade place.
Strap to
1
prevent falling
Air filter
3
Suction grille
Button
Information
• The oil guard filter does not surely collect oil soot
though it has an excellent endurance against oil
soot.
• The cleaning interval for the oil guard filter is
calculated under environmental condition of oil soot
density 3.5mg/m3.
Adjust cleaning interval according to conditions of
adhered oil soot or dirt.
2
Push
5
48
Page 49
Cleaning of discharge louver
The air outlet flap can be removed to clean if necessary.
1
Remove the air outlet flap.
• Holding the both ends of the air outlet flap,
remove it with sagging the center downward.
2
Clean the air outlet flap with water.
• If dirt is heavy, clean the air outlet flap by tepid
water with neutral detergent or water.
1
3
Mount the air outlet flap.
• First push in the one side, and insert the
opposite side with sagging the center downward.
Be careful to direction when mounting
the louver.
Set the surface with printed mark upward, and
mount the flap so that the arrow mark of the
printed mark directs outward.
[2-way Air Discharge Cassette Type]
• Hold the center panel and pull it toward you and
pull down it slowly downward. (The center panel
can move either leftward or rightward. Remov e it
after confirmation.)
2
2
Insert in the flap sagging
down the center downward.
1
3
[1-way Air Discharge Cassette Compact T ype]
1 . Push [PUSH] at the center and left/right of the
suction port to open the suction port.
Insert
2. Take out the air filter by lifting up it once and then
• Take off the fall-preventing straps at the both sides.
• Pull down the air filter to take out it.
For AP0631, AP0481, and AP0561 types, hold
[ ]
the claw of the air filter and pull down it.
pull it downward.
REQUIREMENT
• Insert the air filter of 1-way Air Discharge Cassette
Compact Type surely into the specified position.
CAUTION
After cleaning, be sure to attach the fall-preventing straps of the center panel; otherwise an injury is caused
by falling.
49
Page 50
[Concealed Duct Standard Type]
• Slide [Click] of the suction panel toward arrow direction and then open the panel downward. Turn the lever at
the bottom side of the main unit to take out the air filter.
Clamp
Stepped screw
Pull out filter downward
[Concealed Duct High Static Pressure Type]
• Cleaning method differs according to the mounted air filter type.
For cleaning method, please contact the dealer.
• The cleaning method differs depending on the type of attached air filter.
Please ask the constructor or the dealer which you purchased the air conditioner.
while holding the frames.
<Before cooling season>
Cleaning of drain pan
• For cleaning of the drain pan, contact the dealer. (If the drain pan or drain port is clogged with dust, water
is disabled to drain. In some cases, water overflows from the drain pan and it may wet wall or floor.
Be sure to clean the drain pan before the cooling season.)
[Under Ceiling Type]
1
Open the suction grille.
• Hold “knob” of the inlet grille, push it rearward (OPEN),
and then open the inlet grille quietly while holding it.
2
Take out the air filter.
• Push knobs of the air filter to remove the claws of the
inlet grille. Remove the air filter by pulling it toward y ou.
3
Suck dust by a vacuum cleaner or clean with water.
• When dirt is heavy, it is effective to clean the filter with
tepid water with dissolved neutral detergent or cold water.
• After cleaning the filter with water,
dry the filter completely in the shade.
4
Mount the air filter.
5
Close the inlet grille.
• Close the inlet grille, slide the “knob”
toward you, and then fix it surely.
6
Push .
Inlet grille knob
Pull out inlet grille
while pushing hook.
Air filter
Inlet grille
Hinge
Inlet grille
Inlet grille
fixing knob
Slide
• display disappears.
50
Inlet grille knob
Air filter
Inlet grille
Page 51
[High Wall Type]
/
<Air inlet grille>
Wipe it with a dried soft cloth.
• If dirt of the main unit is not cleaned even if wiped with
a dried soft cloth, wipe it completely squeezed cloth
which was rinsed with tepid water below 40°C.
Air inlet grille
Air in the room is sucked from here.
<Air outlet grille/Air outlet flap>
• If using a metal brush or hard sponge for maintenance of the front panel, the surface is scratched and
coating of the front panel may be pealed.
• Use neutral detergent for kitchen to clean a heavy dirt
and then rinse the grille or flap with water .
Suck dust by a vacuum cleaner or clean with water.
• After cleaning the filter with water, dry the filter completely
in the shade.
Air filter
Removes dust and trash.
(Air filter is provided in the air inlet grille.)
Attachment air filter
Air outlet grille
Air outlet flap
[Floor Standing type]
Cleaning of drain pan
• For cleaning of the drain pan, contact the dealer. (If the drain pan or drain port is clogged with dust, water
is disabled to drain. In some cases, water overflows from the drain pan and it may wet wall or floor.
Be sure to clean the drain pan before the cooling season.)
<Attachment/detachment of the air filter>
• Pull the air filter downward and take out toward you.
• Insert the air filter into the indoor unit and push in it.
Suck dust by a vacuum cleaner or clean with water.
• When dirt is heavy, it is effective to clean the filter with
tepid water with dissolved neutral detergent or cold water.
• After cleaning the filter with water, dry the filter completely
in the shade.
51
Page 52
[Floor Standing Cabinet Type]
Air outlet / Air outlet flap
Air filter
Removes dirt or dust.
(It is included in the inlet grille.)
Air inlet glille
• Before you clean the air conditioner, be sure to
turn off the circuit breaker or the main power
switch.
• Clean the air filter every two weeks. If the air filter
is clogged with dust, the performance of the air
conditioner will deteriorate.
[Floor Standing Concealed Type]
Air outlet
Drain receiver (With strainer)
Air filter
Removes dirt or dust.
(It is included in the inlet grille.)
Front panel (Lower side)
• Clean the drain pan or the drain receiver. If the
drain pan or the drain receiver is clogged with
dust, water may o verflow causing getting wet on
the floor.
<How to remove front panel>
• Push down hook of the air filter on the front panel
(Lower side)
• Pull the air filter toward you to remove it.
• This model is a concealed type. Therefore conceal other parts than the air outlet and the air filter.
Be sure not to touch the electric parts box, the surrounding lead wires, the refrigerant pipes, etc. directly with
the hands.
52
Page 53
Cleaning of the main unit/remote controller
• Wipe them with soft and dry cloth.
• If heavy dirt adheres to the main unit, wipe out it
with a cloth dampened with tepid water. For the
• Do not use benzene, thinner, polishing powder, or
similar solvents for cleaning. These may cause a
crack or deformation.
remote controller, use a dry cloth.
Benzene
Thinner
Chemical
floor-cloth
I will wipe soft
and dry cloth!
Polishing
powder
<If you do not use the unit for more than 1 month>
• Operate the fan for half a day to dry inside of the main unit sufficiently.
• Turn off the main power switch.
• Clean the air filter and then remount it as before.
<Before cooling season (Concealed Duct High Static Pressure Type)>
Cleaning of drain pan and drain receiver (With strainer)
Do not use.
Use after drying
when it has not been
used for a long time!
CAUTION
Clean the drain pan and the drain receiver (strainer)
If the drain pan or the drain receiver chokes with dust, water overflows or ceiling or floor gets wet.
REQUIREMENT
For cleaning of the drain pan or drain receiver, contact the dealer which you purchased the air conditioner .
53
Page 54
3-16. How to Use the Air Conditioner Efficiently
To save the charges for electricity and to gain comfortable cooling/heating operation
Clean the air filter frequently
• If the air filter is clogged, cooling/heating efficiency
decreases.
Don’t forget
periodical
check!
Do not cool/heat the room excessively
W ARNING
Do not expose your body in cool air for a
long time; otherwise it causes worse
condition or health loss.
Close window or door often
• Close window or door often so that cool/hot air
does not out of the room.
Close windows
and doors often!
Evenness of room temperature
• Using a discharge louver, adjust air direction.
Exposing yourself for a long time in blowing air
exerts a bad influence upon your health.
• It is unhealthy; especially tak e care of children or
aged persons.
• Recommended set temperature
26 to 28°C
Cool
Heat
22 to 24°C
Don’t cool
excessively!
54
Page 55
3-17. When the Following Symptoms are Found
Check the points described below before asking repair servicing.
Symptom
Outdoor unit• White misty cold air
or water is out.
• Sometimes, noise
“Pushu !” is heard.
Indoor unit•“Swish” sound is
heard sometimes.
• Slight “Pishi!” sound
is heard.
• Discharge air smells.
• The operation lamp
flashes
•“STANDBY”
indication is lit.
Check again.
• Sound or cool air is
output from the
stand by indoor unit.
• When power of the
air conditioner is
turned on, “Ticktock”
sound is heard.
Cause
• Fan of the outdoor unit stops automatically and performs defrost
operation.
• Solenoid valve works when defrost operation starts or finishes.
• When the operation has started, during the operation, or immediately
after the operation has stopped, a sound such as water flows may be
heard, and the operation sound may become larger for 2 or 3 minutes
immediately after the operation has started. They are flowing sound of
refrigerant or draining sound of dehumidifier.
• This is sound generated when heat exchanger, etc. expand and
contract slightly due to change of temperature.
• Various smell such as one of wall, carpet, clothes, cigarette, or
cosmetics adhere to the air conditioner.
• Flashes when power is turned on again after power failure, or when
power switch is turned on.
• When cooling operation cannot be performed because another indoor
unit performs heating operation.
• When the manager of the air conditioner has fixed the operation to
COOL or HEAT, and an operation contrary to the setup operation is
performed.
• When fan operation stopped to prevent discharge of hot air.
• Since refrigerant is flowed temporarily to prevent stay of oil or
refrigerant in the stand by indoor unit, sound of flowing refrigerant,
“Kyururu” or “Shaa” may be heard or white steam when other indoor
unit operates in HEAT mode, and cold air in COOL mode may be
blow-out.
• Sound is generated when the expansion valve operates when power
has been turned on.
Operates or stops automatically.
Does not operate.
Silent
Air is not cooled or warmed sufficiently.
It is not a failure.
It’s strange.
• Is the timer “ON” or “OFF”?
• Is it a power failure?
• Is the power switch turned off?
• Is the power fuse or breaker blown?
• Has the protective device operated? (The operation lamp goes on.)
• Is the timer “ON”? (The operation lamp goes on.)
• Are COOL and HEAT selected simultaneously? (“STANDBY” indica-
tion is lit on the display column of the remote controller.)
• Is the suction port or discharge port of the outdoor unit obstructed?
• Are any door or window open?
• Is the air filter clogged with dust?
• Is discharge louver of the indoor unit set at appropriate position?
• Is air selection set to “LOW” “MED”, and is the operation mode set to
“FAN”?
• Is the setup temp. the appropriate temperature?
• Are COOL and HEAT selected simultaneously? (“STANDBY” indica-
tion is lit on the display column of the remote controller.)
When the following symptoms are found, stop the operation immediately, turn off the power switch, and contact
the dealer which you have purchased the air conditioner.
• Activation of switch is unstable.
• Fuse or breaker is blown periodically.
• Foreign matters or water entered by mistake .
• When if activation cause of the protective device has been removed, the operation is not performed.
• Other unusual status occurred.
55
Page 56
4.REFRIGERANT PIPING SYSTEMATIC DRAWING
4-1. In verter Unit (5, 6, 8, 10, 12HP)
Model: MMY-MAP0501HT, MAP0601HT, MAP0801HT,
(PMV1)
MMY-MAP1001HT, MAP1201HT
(8,10,12HP)
(PMV2)
Propeller fan
M
Fan motor
Sensor
(TE1)
(Right side)
Air heat exchanger
at outdoor side
(Left side)
Air heat exchanger
at outdoor side
(8,10,12HP)
(PMV1)
Sensor
(TL)
Check
joint
Liquid
tank
Strainer
Pulse motor
valve (PMV)
(5,6HP)
Strainer
Sensor
(TE1)
Solenoid valve (SV5)
Solenoid valve
(SV3D)
Solenoid valve
(SV41)
Capillary tube
Check valve
High-pressure
sensor
Check joint
Capillary tube
Strainer
Capillary tube
Strainer
High-pressure
switch
Sensor
(TD1)
Capillary tube
Solenoid
valve
(SV3E)
(Right side)
Air heat exchanger
at outdoor side
(Left side)
Air heat exchanger
at outdoor side
Oil
separator
Check
valve
Capillary
tube
Sensor
(TK3)
Strainer
Check
(Inverter)
valve
Compressor 1
Sensor
(TK1)
Sensor
(TK4)
Solenoid valve
Check
valve
Solenoid
valve
(SV3C)
Strainer
Check
valve
Capillary tube
Sensor
(TK2)
Oil tank
4-Way valve
(SV2)
Capillary tube
Solenoid valve
High-pressure
Sensor
(TD2)
(Inverter)
Compressor 2
Capillary tube
(SV42)
switch
Sensor
(TO)
Sensor (TS1)
Low-pressure
sensor
Check joint
Accumulator
Balance pipe
servise valve
Liquid side
servise valve
StrainerStrainer
Gas side
servise valve
Strainer
Check
valve
Solenoid
valve
(SV3A)
56
Solenoid
valve
(SV3B)
Check
valve
Page 57
4-2. Explanation of Functional Pa rts
Functional part name
Solenoid valve1. SV3A
2. SV3B
3. SV3C
4. SV3D
5. SV3E
6. SV2
7. SV4 (n)
8. SV5
4-way valve
Pulse motor valve PMV1, 2
Oil separator
Temp. sensor1. TD1
TD2
2. TS1
3. TE1
4. TK1, TK2,
TK3, TK4
5. TL
6. TO
Pressure sensor1. High pressure
sensor
2. Low pressure
sensor
HeaterCompressor case
heater
Accumulator case
heater
Balance pipe
Functional outline
(Connector CN324: Red)
1) Collects oil in the oil tank during OFF time.
2) Supplies oil reserved in the oil tank during ON time.
(Connector CN313: Blue)
1) Returns oil supplied in the balance pipe to the compressor.
(Connector CN314: Black)
1) Pressurizes oil reserved in the oil tank during ON time.
(Connector CN323: White)
1) Reserves oil in the oil separator during OFF time, and supplies oil during ON time.
(Connector CN323: White)
1) Turns on during operation and balances oil between compressors.
(Hot gas bypass) (Connector CN312: White)
1) Low pressure release function
2) High pressure release function
3) Gas balance function during stop time
(Start compensation valve of compressor) (Connector CN311: Blue)
1) For gas balance start
2) High pressure release function
3) Low pressure release function
(Connector CN310: White) (for Heating model only)
1) Preventive function for high-pressure rising in heating operation
(Connector CN317: Blue)
1) Cooling/heating exchange
2) Reverse defrost
(Connector CN300, 301: White)
1) Super heat control function in heating operation
2) Liquid line shut-down function while follower unit stops
3) Sub-cool adjustment function in cooling operation
1) Prevention for rapid decreasing of oil (Decreases oil flowing to the cycle)
(NOTE) MMU-AP0071YH to AP0121YH type air conditioners ha ve no TC2 sensor.
Functional part name
Pulse Motor Valve PMV
Temp. sensor1. TA
2. TC1
3. TC2
4. TCJ
(Connector CN082 (6P): Blue)
1) Controls super heat in cooling operation
2) Controls under cool in heating operation
3) Recovers refrigerant oil in cooling operation
4) Recovers refrigerant oil in heating operation
(Connector CN104 (2P): Yellow)
1) Detects indoor suction temperature
(Connector CN100 (3P): Brown)
1) Controls PMV super heat in cooling operation
(Connector CN101 (2P): Black)
1) Controls PMV under cool in heating operation
(Connector CN102 (2P): Red)
1) Controls PMV super heat in cooling operation
2) [MMU-AP0071 to AP0121YH only]
Controls PMV under cool in heating operation
Functional outline
Sensor
(TC1)
58
Page 59
5.COMBINED REFRIGERANT PIPES SYSTEMATIC
DRAWING
5-1. Normal Operation (COOL Mode / DEFROST Mode)
PMV1 PMV2
TL
Liquid
tank
Header unit
(MMY-MAP1001H)
FM
TE1
SV5
TK3
TK4
SV2
OS
SV3C
TK2
Oil tank
Pd sensor
SV3D
SV41SV42
HPHP
TD1
1
Compressor
TK1
SV3E
4-Way valve
Ps sensor
TD2
2
Compressor
TO
TS1
Accumulator
PMV1 PMV2
TL
Liquid
tank
Follower unit
(MMY-MAP1001H)
FM
TE1
SV5
TK3
TK4
SV2
OS
SV3C
TK2
Oil tank
Pd sensor
SV3D
SV41SV42
HPHP
TD1
1
Compressor
TK1
SV3E
TO
4-Way valve
TS1
Ps sensor
Accumulator
TD2
2
Compressor
SV3A
SV3B
Balance pipe
Liquid pipe
Gas pipe
Gas pipe
Liquid pipe
PMV
TC2
Strainer
TCJ
StrainerStrainer
PMV
TC1
TC2
TCJ
StrainerStrainer
PMV
TC1
TC2
TCJ
Indoor unit
High-pressure gas or condensate liquid refrigerant
Evaporative gas refrigerant (Low-pressure gas)
NOTE
An outdoor unit which is connected with indoor/outdoor communication
lines is the “Header unit”, and the other unit is called “Follower unit”.
SV3A
StrainerStrainer
PMV
TC1
TC2
TCJ
(Example: 20HP system)
SV3B
Strainer
TC1
59
Page 60
5-2. Normal Operation (HEAT Mode)
PMV1 PMV2
TL
Liquid
tank
Header unit
(MMY-MAP1001H)
FM
TE1
SV5
TK3
TK4
SV2
OS
SV3C
TK2
Oil tank
Pd sensor
SV3D
SV41SV42
HPHP
TD1
1
Compressor
TK1
SV3E
4-Way valve
Ps sensor
TD2
2
Compressor
TO
TS1
Accumulator
PMV1 PMV2
TL
Liquid
tank
Follower unit
(MMY-MAP1001H)
FM
TE1
SV5
TK3
TK4
SV2
OS
SV3C
TK2
Oil tank
Pd sensor
SV3D
SV41SV42
HPHP
TD1
1
Compressor
TK1
SV3E
TO
4-Way valve
TS1
Ps sensor
Accumulator
TD2
2
Compressor
PMV
TC2
Strainer
TCJ
SV3A
SV3B
Balance pipe
Liquid pipe
Gas pipe
Gas pipe
Liquid pipe
StrainerStrainer
PMV
TC1
TC2
TCJ
StrainerStrainer
PMV
TC1
TC2
TCJ
Indoor unit
High-pressure gas or condensate liquid refrigerant
Evaporative gas refrigerant (Low-pressure gas)
SV3A
StrainerStrainer
PMV
TC1
TC2
TCJ
SV3B
Strainer
TC1
NOTE
An outdoor unit which is connected with indoor/outdoor communication
lines is the “Header unit”, and the other unit is called “Follower unit”.
60
(Example: 20HP system)
Page 61
5-3. Emergent Operation
(Cooling Operation when Center Outdoor Backup)
Failure
1
*
PMV1 PMV2
TL
Liquid
tank
Header unit
(MMY-MAP1001H)
FM
TE1
SV5
TK3
TK4
SV2
OS
SV3C
TK2
Oil tank
Pd sensor
SV3D
SV41SV42
HPHP
TD1
1
Compressor
TK1
SV3E
4-Way valve
Ps sensor
TD2
2
Compressor
TO
TS1
Accumulator
Header unit set
temporarily in
emergent time
PMV1 PMV2
TL
Liquid
tank
Follower unit
(MMY-MAP1001H)
FM
TE1
SV5
TK3
TK4
SV2
OS
SV3C
TK2
Oil tank
Pd sensor
SV3D
SV41SV42
HPHP
TD1
1
Compressor
TK1
SV3E
TO
4-Way valve
TS1
Ps sensor
Accumulator
TD2
2
Compressor
*
PMV
SV3A
SV3B
3
TC2
Strainer
TCJ
2
*
StrainerStrainer
TC1
Balance pipe
Liquid pipe
Gas pipe
PMV
TC2
TCJ
Gas pipe
Liquid pipe
StrainerStrainer
PMV
TC1
TC2
TCJ
1
When liquid leaks from PMV, packed valve
*
at liquid side = Close fully
2 Gas pipe service valve = Close fully
*
Balance pipe packed valve = Open fully
3
*
StrainerStrainer
TC1
SV3A
PMV
TC2
SV3B
Strainer
TC1
TCJ
Indoor unit
High-pressure gas or condensate liquid refrigerant
Evaporative gas refrigerant (Low-pressure gas)
NOTE
An outdoor unit which is connected with indoor/outdoor communication
lines is the “Header unit”, and the other unit is called “Follower unit”.
61
(Example: 20HP system)
Page 62
5-4. Emergent Operation
(Heating Operation when Center Outdoor Backup)
Failure
1
*
PMV1 PMV2
TL
Liquid
tank
Header unit
(MMY-MAP1001H)
FM
TE1
SV5
TK3
TK4
SV2
OS
SV3C
TK2
Oil tank
Pd sensor
SV3D
SV41SV42
HPHP
TD1
1
Compressor
TK1
SV3E
4-Way valve
Ps sensor
TD2
2
Compressor
TO
TS1
Accumulator
Header unit set
temporarily in
emergent time
PMV1 PMV2
TL
Liquid
tank
Follower unit
(MMY-MAP1001H)
FM
TE1
SV5
TK3
TK4
SV2
OS
SV3C
TK2
Oil tank
Pd sensor
SV3D
SV41SV42
HPHP
TD1
1
Compressor
TK1
SV3E
TO
4-Way valve
TS1
Ps sensor
Accumulator
TD2
2
Compressor
*
PMV
SV3A
SV3B
3
TC2
Strainer
TCJ
2
*
StrainerStrainer
TC1
Balance pipe
Liquid pipe
Gas pipe
PMV
TC2
TCJ
Gas pipe
Liquid pipe
StrainerStrainer
PMV
TC1
TC2
TCJ
1
When liquid leaks from PMV, packed valve
*
at liquid side = Close fully
2 Gas pipe service valve = Close fully
*
Balance pipe packed valve = Open fully
3
*
StrainerStrainer
SV3A
TC1
PMV
TC2
SV3B
Strainer
TC1
TCJ
Indoor unit
High-pressure gas or condensate liquid refrigerant
Evaporative gas refrigerant (Low-pressure gas)
NOTE
An outdoor unit which is connected with indoor/outdoor communication
lines is the “Header unit”, and the other unit is called “Follower unit”.
62
(Example: 20HP system)
Page 63
5-5. Recovery of Refrigerant in Failed Outdoor Unit
(In Case of Failure of Follower Unit)
PMV1 PMV2
TL
Liquid
tank
Header unit
(MMY-MAP1001H)
FM
TE1
SV5
TK3
TK4
SV2
OS
SV3C
TK2
Oil tank
Pd sensor
SV3D
SV41SV42
HPHP
TD1
1
Compressor
TK1
SV3E
4-Way valve
Ps sensor
TD2
2
Compressor
TO
TS1
Accumulator
Failure
PMV1 PMV2
TL
Liquid
tank
Follower unit
(MMY-MAP1001H)
FM
TE1
SV5
TK3
TK4
SV2
OS
SV3C
TK2
Oil tank
Pd sensor
SV3D
SV41SV42
HPHP
TD1
1
Compressor
TK1
SV3E
TO
4-Way valve
TS1
Ps sensor
Accumulator
TD2
2
Compressor
PMV
TC2
Strainer
TCJ
SV3A
SV3B
Balance pipe
Liquid pipe
Gas pipe
1
*
3
*
2
*
*
*
*
Gas pipe
Liquid pipe
StrainerStrainer
PMV
TC1
TC2
TCJ
High-pressure gas or condensate liquid refrigerant
Evaporative gas refrigerant (Low-pressure gas)
StrainerStrainer
PMV
TC1
TC2
TCJ
Indoor unit
SV3A
SV3B
1 Packed valve of balance pipe = Open fully
2 Packed valve at liquid side = Close fully
3
Service valve open fully at gas side
Close fully 10 minutes after operation start
StrainerStrainer
PMV
TC1
TC2
TCJ
Strainer
TC1
NOTE
An outdoor unit which is connected with indoor/outdoor communication
lines is the “Header unit”, and the other unit is called “Follower unit”.
63
(Example: 20HP system)
Page 64
6.CONTROL OUTLINE
6-1. Indoor Unit
6-1-1. Control Specifications
No.
1
2Operation
3Room temp.
Item
Power supply
is reset.
select
control
Outline of specifications
(1) Distinction of outdoor unit
When the power supply is reset, the outdoor units are
distinguished, and control is exchanged according to the
distinctive results.
(2) Check code clear
When the power supply is reset, the check code is also reset
once. If an abnormal status which the check code appears
after Start/Stop button of the remote controller has been
pushed continues, the check code is displayed again on the
remote controller.
(1) Based upon the operation select command from the remote
controller or central controller, the operation mode is selected.
Remote controller command
STOP
FAN
COOL
DRY
HEAT
(1) Adjustment range Set temperature on remote controller (°C)
In cooling/drying
Wired type
Wireless type
18 to 29°C
18 to 30°C
Control outline
Stops air conditioner.
Fan operation
Cooling operation
Dry operation ∗
Heating operation
In heating
18 to 29°C
16 to 30°C
Remarks
∗ Concealed duct type air
conditioner cannot operate
for drying.
(2) From the item code 06, the setup temperature in heating
operation can be corrected.
Setup data
Setup temp. correction
Setup at shipment
Setup data2
4Automatic
capacity
control
Air volume
5HH > H+ > H >
control
(1) Based upon difference between Ta and Ts, the operation
frequency is indicated to the outdoor unit.
(1) By the command from the remote controller, “HIGH (HH)”,
“MED (H)”, or “LOW (L)”“AUTO” operation is executed.
(2) While air speed is in AUTO mode, the air speed is changed
according to the difference between Ta and Ts.
0246
+0°C+2°C+4°C+6°C
Heating suction temperature
shift
L+ > L > LL
64
Page 65
No.
Item
Outline of specifications
Remarks
6
Prevention of
cold air
discharge
7Freeze preven-
tion control
(Low temp.
release)
(1) In heating operation, the upper limit of the fan tap is set by
one with higher temperature of TC2 sensor and TCJ sensor.
• When B zone has continued for 6 minutes, the operation
shifts to C zone.
• In defrost time, the control point is set to +6°C.
(˚C)
32
30
28
26
D
C
A zone: OFF
B zone:
Over 26˚C, below 28˚C, LOW
C zone:
E
Over 28˚C, below 30˚C, MED
D zone:
Over 30˚C, below 32˚C, HIGH
E zone: Ultra HIGH
20
16
B
A
(1) In cooling operation, the air conditioner operates as de-
scribed below based upon temp. detected by TC1, TC2 and
TCJ sensors.
To prevent the heat exchanger from freezing, the operation
stops.
• When “J” zone is detected for 5 minutes, the command
frequency becomes “S0” to the outdoor unit.
• In “K” zone, the timer count is interrupted, and held.
• When “1 ” zone is detected, the timer is cleared and the
operation returns to the normal operation.
• When the command frequency became S0 with continuation of “J” zone, operation of the the indoor fan in LOW
mode until it reaches the “1 ” zone.
It is reset when the following conditions are satisfied.
• In D and E zones, pr iority
is given to remote controller air speed setup.
• In A and B zones, “
” is
displayed.
Reset conditions
>
1) TC1
12°C and TC2 > 12°C and TCJ > 12°C
2) 20 minutes passed after stop.
TC1TC2, TCJ
10°C (5°C)10°C
0°C–14°C
(˚C)
P1
Q1
K
J
a
P1
Q1
(2) In cooling operation, the air conditioner operates as
described below based upon temp. detected by TC2 and
TCJ sensors.
• When “M” zone is detected for 45 minutes, the command
frequency becomes “S0” to the outdoor unit.
• In “N” zone, the timer count is interrupted and held.
• When shifting to “M” zone again, the timer count restarts
and continues.
• If “L” zone is detected, the timer is cleared and the
operation returns to normal operation.
Reset conditions
>
1) TC1
12°C and TC2 > 12°C and TCJ > 12°C
2) 20 minutes passed after stop.
(˚C)
P2
Q2
L
N
M
P2
Q2
TC2, TCJ
–2.0°C
5°C
∗ In a Model without TC2,
TC2 is not judged.
65
Page 66
No.
Item
Outline of specifications
Remarks
8
Recovery control
for cooling
refrigerant and oil
9
Recovery control
for heating
refrigerant and oil
10
Short inter mittent
operation
compensation
control
1) The indoor unit which stops operation, thermostat is OFF,
or operates in FAN mode opens PMV of the indoor unit by
the specified opening degree when cooling refrigerant or oil
recovery signal receive from the outdoor unit.
2) Drain pump of 4-way air discharge cassette type and
concealed duct type operate during recovery control mode.
The indoor unit which stops operation, thermostat is OFF, or
operates in FAN mode performs the following controls when
the heating refrigerant/Oil recovery signal is received from the
outdoor unit.
1) Opens PMV of the indoor unit by the specified opening
degree.
2) Stops the fan.
3) Only 4-way Air Discharge Cassette type air conditioner
rotates the indoor fan with intermittent operation for approx.
1 minute after recovery control.
4) Only 4-way Air Discharge Cassette type air conditioner
rotates the indoor fan with intermittent operation for approx.
1 minute after recovery control as the outdoor unit.
5) After recovery control, drain pump of 4-way air discharge
cassette type and concealed duct type will operate.
(1) For 5 minutes after the operation has started, the operation
is continued even if entering thermostat-OFF condition.
(2) However, if the ther mostat has been turned off by changing
the set up temp., the thermostat is OFF with even the
above condition. The protective control has priority.
• Recovery operation is
usually executed every 2
hours.
• In the indoor unit which
thermostat is OFF, or
operates in FAN mode,
” lamp goes on.
“
• Recovery operation is
usually executed every
1 hour.
11
Drain pump
control
12Elimination of
remaining heat
13Auto flap control(1) When the louver signal has been received from the remote
14Filter sign display
(None in wireless
type)
∗ Provided in the
separately laid
type
TCB-AX21E.
(1) During “COOL” operation (including DRY operation), the
drain pump operates.
(2) While the drain pump operates, if the float switch works,
the drain pump continues operation and a check code is
displayed.
(3) While the drain pump stops, if the float switch works, turn
off the capacity demand command, stop the operation, and
operate the drain pump. If the float switch continues
operating for approx. 5 minutes, the operation stops and
the check code is displayed.
(4) In heating operation, if humidifier “provided” is judged,
compressor “ON”, fan “ON”, and MAX (TC2, TCJ)
the drain pump operates.
(1) When the air conditioner stops in the “HEAT” mode, drive
the indoor fan with “LOW” mode for approx. 30 seconds.
controller, the louver operates if the indoor fan is operating.
(2) In 4-way Air Discharge Cassette type, the discharge louver
automatically directs downward if the operation stops.
(3) In 4-way Air Discharge Cassette type, the discharge louver
directs upward if the heating operation is being prepared.
(1) The operation time of the indoor fan is integrated and
stored in memory, and the filter exchange signal is sent to
the remote controller to display on the remote controller
LCD after the specified time. (2500H)
(2) When the filter reset signal is received form the remote
controller, time of the integrated timer is cleared. In this
time, if the specified time has passed, the measured time is
reset and LCD display disappears.
>
33°C,
Check code [P10]
When CN70 is connected
or the item code 40 setup
data is 1, the setup
becomes humidifier
“provided”, and the drain
pump operates with the left
conditions.
66
Page 67
No.
Item
Outline of specifications
Remarks
15
“” and “ ”
display
(Operation and
heating stand-by)
<Operation standby> .......... Display on remote controller
(1) •“P05” is one of displays of power wire missingand when
it’s detected.
•“COOL/DRY” operation cannot be performed because the
other indoor unit is under “HEAT” operation.
•“HEAT” operation cannot be perfor med because COOL
priority is set (Outdoor I/F P.C. board SW11 1-bit is ON)
and the other indoor unit is under “COOL/DRY” operation.
•“FAN” operation cannot be performed because the system
performs “Heat oil/Refrigerant recovery” operation.
• There is a unit in which indoor overflow “P10” is detected.
• There is a unit in which inter lock alarm “P23” is detected.
(2) The above indoor units unavailable to operate waits under
condition of thermostat OFF.
<HEAT standby> .................. Display on remote controller
(1) • HEAT thermostat is OFF.
• During HEAT operation, the fan rotates with lower air speed
than one specified in order to prevent discharge of cold
draft or stops. (including case that defrost operation is
being performed)
•“HEAT” operation cannot be perfor med because COOL
priority is set (Outdoor I/F P.C. board SW11 bit 1 is ON) and
the other indoor unit is under “COOL/DRY” operation.
(2) “HEAT standby” is displayed until the above conditions are
released.
•“ ” goes on.
” goes on.
•“
16Selection of
central control
mode
(1) The contents which can be changed on the remote controller
at indoor unit side can be selected by setup at the central
controller side.
(2) In case of operation from TCC-LINK central controller
(TCB-SC642TLE, etc.)
[Central control mode 1] : Cannot operate
[Central control mode 2] :
Cannot operate, stop, select mode, set up temp.
[Central control mode 3] :
Cannot select mode, set up temp.
[Central control mode 4] : Cannot select mode
(3) RBC-AMT21E (Wired remote controller)
While mode is the central control mode, “
lights on the display part of the remote controller.
[After command priority]
Both remote controller at indoor unit side and central
controller are available to set up the operation mode, and the
unit operate by the newest command.
[Center]
The remote controller at indoor unit side can operate only
ON or OFF.
[Access inhibit]
The remote controller at indoor unit can’t operate.
CENTRAL”
If operation is performed
from the remote control
“CENTRAL CONTROL”
mode, the status is
notified with receiving
sound.
67
Page 68
6-2. Outdoor Unit
6-2-1. Operation Start/Operation End
The compressor, solenoid valve, pulse motor valve (PMV), outdoor fan, etc. are controlled by a command from
the indoor controller. The follower outdoor unit starts/stops by a command from the header outdoor unit.
No.
1
Pulse Motor Valve
(PMV) control
Item
Operation explanation and applied data, etc.
(1) PMV control (using two PMV, 1 and 2)
1) PMV (Pulse Motor Valve) is controlled between 90 to
1000 pulses during operation.
2) In cooling operation, PMV opening is controlled
based upon detected TL sensor temp. and detected
Pd pressure value. (Under-Cool control)
3) In heating operation, PMV opening is controlled
based upon detected TS and TD sensor temp. and
detected PS pressure value. (Super-Heat control)
4) Close fully PMV opening when thermostat is OFF,
operation stops and A.C. stops in trouble.
1000
PMV 2
550
500
90
PMV opening
45
PMV 1
Min.Med.Max.
Remarks
• In heating operation,
PMV2 is 0 pulses and
PMV may be controlled by
PMV1 only with the
minimum 45 pulses.
2Outdoor fan control(1) Cooling fan control
1) Outdoor fan speed (mode) is controlled based upon
detected Pd pressure value.
2) In a specified time when cooling operation started,
the center outdoor unit controls the outdoor fan
speed based upon detected Pd pressure value.
The follower outdoor unit controls the outdoor fan
speed (mode) based upon detected TE sensor temp.
(2) Heating fan control
1) Outdoor fan speed (mode) is controlled based upon
detected TE sensor temp.
2) If TE > 25°C has been continuously detected for 5
minutes, the operation may stop. In this case, the
status is same as one in usual thermostat-OFF, so
the operation restarts.
3) After A.C started, this control is not performed during
the specified time after defrost operation and defrost
control.
4) When refrigerant is excessively shortened, START/
STOP operation may be repeated by this control.
(3) Control for follower unit stop
The fan is driven with lower limit mode to prevent
refrigerant accumulation into the outdoor heat exchanger.
When TE temp. (ambient
temperature) exceeds 25°C,
Heating operation stops.
(Over the operation temp.
condition of ambient temp.)
68
Page 69
No.
Compressor 1
Compressor 2
Item
Operation explanation and applied data, etc.
Remarks
3
Capacity control
4Oil level detection
control
1) According to the capacity demand command from the
indoor controller, the inverter frequency control of the
header and follower units is determined. The header
unit sets the start order of the follower unit connected
to the system and then starts the operation.
2) Two compressors in the outdoor unit rotate every stop
of compressor and exchanges the start order when
the compressor will be ON in the next time.
3) When two or more follower units are connected, if the
system thermostat is OFF, the rotation is judged
every compressor-OFF of the follower unit and the
start priority order of the follower units in the next
start time is exchanged.
1) Based upon the detected temperature of TK1 to TK4
sensors, whether the right amount of oil is included in
the compressor case or not is judged. The header
unit and follower unit perform this control individually.
2) From relation between the detected temperature of
the operating compressor TK1 or TK2 and detected
temperature of TK3, TK4, whether oil level in the
compressor case is right or not is judged. If it is
insufficient, the control shifts to the oil equation
control.
3) This control is usually performed during operation of
the compressor.
• Min. frequency: 26Hz
• The detection is per-
formed in both cases of
operation of a compressor
and operation of two
compressors.
(SV3D)
Balance
pipe
Packed
valve
(SV41)
ON
(SV3E)
OFF
(TD1)
Oil
separator
(TK3)
Compressor 1
Compressor 1
(TK1)
(TK4)
OFF
(SV3C)
(TK2)
Oil tank
(SV3A)
OFF
(SV2)
(TD2)
Compressor 2
Compressor 2
(SV42)
(SV3B)
69
Page 70
No.
Item
Operation explanation and applied data, etc.
Remarks
5
Oil equation
control
6Refrigerant/Oil
recovery control
This control is provided to prevent the oil short in the compressor
of each outdoor unit. This control is basically performed by ON/OFF
operation of the solenoid valves SV3A, SV3B, SV3C, SV3D.
(For the schematic diagram of oil equation control.)
(1) Normal oil equalizing operation
This control is used when the oil level down has been detected
for a long time.
(2) Oil equation control
This control supplies oil accumulated in the oil cylinder of each
outdoor unit to the outdoor unit in which oil level moved down.
This control is performed during compressor-ON of the header
unit when oil level judgment result of the header unit shows
“Short” or the oil equation demand is issued from the system of
even a header unit. In a case of system with a header unit (No
follower unit is connected.), this control is not executed.
(3) Oil-short protective control
If an oil equation control is executed, the protection stops when
the status of oil short continues for 30 minutes, and it restarts
after 2 minutes and 30 seconds after. After then, if the protection stop is repeated 3 times, an error is determined.
(Restart is not performed.) The error code is “H07”.
(1) In cooling operation, this control is executed to regularly
recover the refrigerating oil stagnated in gas inter-unit pipe or
indoor unit to the outdoor unit when the compressor driving
command is weak, and to prevent refrigerant accumulation in
the outdoor heat exchanger while low ambient cooling operation is performed.
This control is managed by the header outdoor unit.
1) Control conditions
• Cooling oil recovery control is executed every 2 hours
approximately.
2) Contents of control
• Recovery time continues for approx. 2 or 3 minutes though
it differs according to the system capacity.
(2) Refrigerant recovery control in heating room
During heating operation, this is executed to recover liquid
refrigerant stagnated in the stopped indoor unit. It is also used to
recover oil in the outdoor heat exchanger in heating overload
operation except with defrost condition.
This control is managed by the header outdoor unit.
1) Heating refrigerant recovery control is executed every an
hour approximately.
2) Recovery time continues for approx. 2 to 10 minutes though
it differs according to the load condition.
7Defrost control
(Reverse
defrost method)
(1) Defrost start condition
In heating operation, the operating time is integrated when the
detected TE sensor temp was lower than -2°C, and when 25
minutes have passed in the initial time after the compressor
started and 55 minutes in the second time and after.
(2) Contents of control
• If the outdoor units are combined, the defrost operation
forcedly continues for 2 minutes if the defrost operation has
been once started.
(3) Stop conditions of defrost operation
• If the outdoor units are combined, the fan drive and compres-
sor inverter frequency may be controlled by Pd pressure
during defrost operation.
70
• Dur ing defrosting
operation, all the
solenoid valves of
4-way are OFF and all
compressors are
driven.
Page 71
No.
Item
Operation explanation and applied data, etc.
Remarks
8
Release valve
control
9Compressor
stop by high
pressure
release control
(1) SV2 gas balance control
This control is executed to balance the gas when opening
SV2 while the compressor is off, in order to decrease the
activation load in the next compressor-ON time. This control is
individually executed by the header outdoor unit and each
follower outdoor unit.
(2) SV2 high pressure release control
This control is to control pressure rising in low-frequency
operation of the inverter.
(3) SV2 low pressure release control
This control is to prevent quick pressure dropping in transient
operation. This control is individually executed by the header
outdoor unit.
This control is executed as necessary except during stop time
and thermostat-OFF time.
(4) SV41, 42 low pressure release control
This control is to prevent low pressure dropping and is
individually executed by the header unit and each follower unit.
This control is executed during defrost operation, heating
start pattern control operation, and cooling operation.
(5) SV5 high pressure release control
This control is to prevent high pressure rising and is executed
for the header unit only.
This control is to forcedly stop the compressor in each outdoor
unit according to Pd pressure. It is individually executed by the
header unit and each follower unit.
(1) Contents of control
• The compressor stops when Pd pressure is over 3.5MPa.
10Case heater
control
11IPDU controlIPDU controls the inverter compressor by command frequency,
The case heater output includes compressor case heater and
accumulator case heater. This control is to prevent accumulation
of refrigerant in the compressor case by turning of the power of
heater while the compressor stops, and it is executed in all the
outdoor units.
If electricity is not turned on for a specified time before the test
run after installation, a trouble of the compressor may be caused.
When the power has been interrupted for a long time and the
operation starts from the status as it was, it is desirable to turn on
the power before start of operation as per the test run time.
This control is used often together with the compressor winding
heating control. In this case, the power sound may be heard but it
is not a trouble.
(1) Contents of control
• Turns on during compressor-OFF
• Turns off when the detected TO sensor temp is 28°C orhigher, and turns on when it is 25°C or lower
• The operation continues for 10 minutes after compressor-
OFF changed to compressor-ON.
frequency up/down speed, and current release control value from
the interface P.C. board.
The main controls of IPDU control P.C. board are described
below.
(1) Current release control
The output frequency is controlled by AC input current value
which is detected by inputting current sensor (CT) on the
control P.C. board to prevent the inverter input current from
rising higher than the specified value.
71
Page 72
No.
Item
Operation explanation and applied data, etc.
Remarks
11
IPDU
control
(Continued)
12High
pressure
prevention
control
(2) Heat sink temp detection control
1) This control protects IGBT overheat preventive protection by the
thermistor (TH temp) on the compressor driving module in
IPDU.
∗ For TH temperature, the higher one of IPDU1 temperature and
IPDU2 temperature is applied.
(3) Over-current protective control
1) The compressor stops when IPDU control P.C. board detects
over-current.
(4) Compressor case thermo control
1) When the compressor case thermostat works, the compressor
stops.
2) When the compressor stops, 1 is counted to the error count,
and the compressor reactivates after 2 minutes and 30 seconds.
After reactivated, the error count is cleared if the operation
continues for 10 minutes or more.
3) The error is determined with error count 4. The error “H04” is
displayed in compressor 1 and “H14” in compressor 2, respectively.
(1) High pressure SW control
• The high-pressure SW is usually closed and connected to IPDU.
1) The compressor driver stops when high pressure SW at inverter
compressor operates.
2) When the compressor driver stops, 1 is counted to the error
count, and the compressor driver reactivates after 2 minutes 30
seconds. After reactivated, the error count is cleared if the
operation continues for 10 minutes or more.
3) The error is determined with error count 4. The error “P04” is
displayed.
• TH sensor is provided
to IPDU1 and 2 each.
• The case thermostat is
usually closed and
connected to the
interface P.C. board.
72
Page 73
<Other cautions>
1. Cooling operation in low ambient temperature
1) When low pressure is lowered, the freeze pre vention control by the indoor unit TC sensor may decrease
the frequency.
2) When low pressure is lowered, the cooling capacity control may decrease the frequency.
3) When discharge temp. sensor value lowers below 60°C, the frequency may be increased over the
receive command from the indoor unit.
2. PMV (Pulse Motor Valve) for outdoor unit
1) When the power is turned on, a tap sound to initialize PMV is heard. If this sound is not heard, PMV
operation error is considered. However, this sound may not be heard at a place where outside sound
takes precidence.
2) Do not remove the driving part (Head part) of PMV during operation. It may cause error in opening.
3) When transporting (replacing) the set, never keep the driving part removed. The valve is closed, and the
valve is damaged by sealed liquid compression.
4) When removing the driving part and attaching it again, push in it securely until a “click” sound can be
heard. Then, turn off the power once, and turn on the power again.
<Oil equation control schematic diagram>
Unit to
send oil
PMV1 PMV2
TL
Liquid
tank
Header outdoor unit
(MMY-MAP1201HT)
FM
TE1
SV5
TK3
TK4
SV2
SV3C
ON
TK2
Oil tank
Pd sensor
Oil
separator
SV3D
SV41SV42
HPHP
TD1
1
Compressor
TK1
SV3E
4-Way valve
Ps sensor
TD2
2
Compressor
TO
TS1
Accumulator
PMV1 PMV2
TL
Liquid
tank
Follower outdoor unit
(MMY-MAP1201HT)
FM
TE1
SV5
TK3
TK4
SV2
OS
SV3C
TK2
Oil tank
Pd sensor
SV3D
SV41SV42
HPHP
TD1
1
Compressor
TK1
SV3E
Unit to
received oil
TO
4-Way valve
TS1
Ps sensor
Accumulator
TD2
2
Compressor
SV3A
ON
Balance pipe
Liquid pipe
Gas pipe
SV3B
SV3A
SV3B
ON
73
Page 74
7.APPLIED CONTROL
7-1. Indoor Unit
7-1-1. Setup of Selecting Function in Indoor Unit
(Be sure to Execute Setup by a Wired Remote Controller)
<Procedure> Execute the setup operation while the unit stops.
5
6
UNIT
CL
SET
4
3
1
1
Push
The firstly displayed unit No. indicates the header indoor unit address in the group control.
In this time, the fan of the selected indoor unit is turned on.
2
Every pushing
displayed. In this time , the fan of the selected indoor unit only is turned on.
3
Specify the item code (DN) using the setup temperature and buttons.
4
Select the setup data using the timer time and buttons.
(When selecting the DN code to “33”, change the temperature indication of the unit from “°C”
to “°F” on the remote controller.)
SET
CL
,
, and buttons simultaneously for 4 seconds or more.
UNIT
button, the indoor unit numbers in the group control are successively
2
5
Push
• To change the selected indoor unit, return to procedure 2 .
• To change the item to be set up, return to procedure 3 .
6
Pushing button returns the status to normal stop status.
button. (OK if display goes on.)
SET
74
Page 75
Table: Function selecting item numbers (DN)
(Items necessary to perform the applied control at the local site are described.)
1-way Air Discharge Cassette
4-way Air Discharge Cassette
2-way Air Discharge Cassette
1-way Air Discharge Cassette (Compact type)
Concealed Duct Standard
Concealed Duct High Static Pressure
Under Ceiling
High Wal l
Floor Standing Cabinet
Floor Standing Concealed
Floor Standing
~
Indoor unit capacity
Type
—
Abbreviated Model name
MMU-AP XXX SH
MMU-AP XXX H
MMU-AP XXX WH
MMU-AP XXX YH
MMD-AP XXX BH
MMD-AP XXX H
MMC-AP XXX H
MMK-AP XXX H
MML-AP XXX H
MML-AP XXX BH
MMF-AP XXX H
n Remote location ON/OFF control box (TCB-IFCB-4E)
[Wiring and setup]
• Use the exclusive connector for connection with the indoor control P.C. board.
• In a group control, the system can operate when connecting with any indoor unit (Control P.C. board) in the
group. However when taking out the operation/error signal from the other unit, it is necessary to take out from
each unit individually.
(1) Control items
1) Start/Stop input signal : Operation start/stop in unit
2) Operation signal: Output during normal operation
3) Error signal: Output during alarm
(Serial communication error or indoor/outdoor protective device) oper ation
(2) Wiring diagram using remote control interface (TCB-IFCB-4E)
InputIFCB-4E : No voltage ON/OFF serial signal
OutputNo voltage contact for operation, error display
Contact capacity: Below Max. AC240V 0.5A
Indoor control P.C. board
Start/Stop input
COM (GND)
Remote controller prohibition/clear input
Operation signal output
COM (+12V)
Error signal output
1
2
3
4
5
6
CN61
T10
(YEL)
1
2
3
4
CN06
1
2
3
4
5
6
CN13
TCB-IFCB-4E
Power supply 220–240V, 50Hz
220V, 60Hz
ON side
Start signal input
OFF side
Stop signal input
COM
Operation signal output
Error signal output
77
Page 78
n Ventilating fan control from remote controller
[Function]
• The start/stop operation can be operated from the wired remote controller when air to air heat exchanger or
ventilating fan is installed in the system.
• The fan can be operated even if the indoor unit is not operating.
• Use a fan which can receive the no-voltage A contact as an outside input signal.
• In a group control, the units are collectively operated and they can not be individually operated.
(1) Operation
Handle a wired remote controller in the following procedure.
∗ Use the wired remote controller during stop of the system.
∗ Be sure to set up the wired remote controller to the header unit. (Same in group control)
∗ In a group control, if the wired remote controller is set up to the header unit, both header and follower units
are simultaneously operable.
1
Push concurrently
The unit No. displayed firstly indicates the header indoor unit address in the group control.
In this time, the fan of the selected indoor unit turns on.
2
Every pushing
SET
UNIT
CL
+
+ buttons for 4 seconds or more.
button, the indoor unit numbers in group control are displayed succes-
sively.
In this time, the fan of the selected indoor unit only turns on.
3
Using the setup temp or button, specify the item code !.
4
Using the timer time or button, select the setup data. (At shipment: )
The setup data are as follows:
Setup data
5
Push
• To change the selected indoor unit, go to the procedure 2 ).
• To change the item to be set up, go to the procedure 3 ).
SET
button. (OK if display goes on.)
Handling of operation of air to air heat exchanger or ventilating fan
Unavailable (At shipment)
Available
6
Pushing returns the status to the usual stop status.
(2) Wiring
Relay (DC12V, procured locally)
CN32
FAN DRIVE
(2P WHI)
Indoor control
P.C. board
Note) Determine the cable length between the
121
2
indoor control P.C. board and the relay within 2m.
Outside control
input of fan
To terminal
78
4-way Air Discharge Cassette type
Concealed Duct Standard type
Under Ceiling type
High Wall type
Corresponds up to a relay in which rated current of the
operation coil is approx. 75mA
Other type models:
Correspond up to a relay in which rated current of the
operation coil is approx. 16mA (Does not correspond
to a terminal block type relay on the market.)
model :
Page 79
n Leaving-ON prevention control
[Function]
• This function controls the indoor units individually. It is connected with cable to the control P.C. board of the
indoor unit.
• In a group control, it is connected with cable to the indoor unit (Control P.C. board), and the item code - is
set to the connected indoor unit.
• It is used when the start operation from outside if unnecessary but the stop operation is necessary.
• Using a card switch box, card lock, etc, the forgotten-OFF of the indoor unit can be protected.
• When inserting a card, start/stop operation from the remote controller is allowed.
• When taking out a card, the system stops if the indoor unit is operating and start/stop operation from the
remote controller is forbidden.
(1) Control items
1) Outside contact ON: The start/stop operation from the remote controller is allowed.
(Status that card is inserted in the card switch box)
2) Outside contact OFF : If the indoor unit is operating, it is stopped forcedly.
(Start/Stop prohibited to remote controller)
(Status that card is taken out from the card switch box)
∗ When the card switch box does not perform the above contact operation, convert it using a relay with b
contact.
(2) Operation
Handle the wired remote controller switch in the following procedure.
∗ Use the wired remote controller switch during stop of the system.
1
Push concurrently
2
Using the setup temp or button, specify the item code - .
3
Using the timer time or button, set to the setup data.
4
Push
5
Push button. (The status returns to the usual stop status.)
SET
button.
SET
(3) Wiring
CN61
T10
(YEL)
Indoor control P.C. board
Note) Determine the cable length between the indoor control P.C. board and the relay within 2m.
CL
+
121
2
343
4
565
6
+ buttons for 4 seconds or more.
Relay (procured locally)
* In the figure, the contact indicates
a status that the card is taken out.
When the relay is turned on, a forced thermostat-OFF operation starts.
• Wiring example
CN73
(2P plug: RED)
Indoor control P.C. board
EXCT
121
2
Relay (procured locally)
Relay coil signal
79
Note) Determine the cable length between the indoor or
outdoor control P.C. board and the relay within 2m.
Page 80
7-2. Outdoor Unit
7-2-1. Applied Control in Outdoor Unit
The following functions become available by setting the switches on the outdoor interface P.C. board.
No.
1
Outdoor fan high static pressure shift
2
Cooling priority, Heating prior ity control
Function
<Interface P.C. board of outdoor unit>
Switch No.
SW10
SW11
Bit
2
1, 2
<Switch position magnified drawing>
SW11
Bit 1 Bit 2
For setup of cooling priority,
heating priority control
80
SW10
For setup of outdoor fan high static pressure shift
Bit 2
Page 81
7-2-1-1. Outdoor fan High Static Pressure Shift
n Usage/Features
This function is set when connecting a duct to discharge port of the outdoor unit.
n Setup
Turn “Bit 2” of the Dip switch [SW10] on the interface P.C. board of the outdoor unit to ON side. For the outdoor
units which are connected with the ducts, set this function regardless of the header unit or follower unit.
n Specifications
Increase No. of rotations of the propeller fan of the outdoor fan so that a duct with the maximum outside static
pressure 35Pa (3.5mmAq) can be installed. If installing a discharge duct (Below 35Pa (3.5mmAq)) exceeding
the duct resistance 15Pa (1.5mmAq), execute this setup.
Discharge air volume in each outdoor unit is described in the following table.
Capacity rank (MMY-MAP)
Standard air volume of outdoor unit (m³/min.)
0501, 0601 type0801 type1001, 1201 type
150165175
7-2-1-2. Cooling Priority, Heating Priority Control
n Usage/Features
Cooling priority or heating priority can be selected.
There are the following four patterns in selecting setup of the priority mode. Select a priority mode based upon
the demand of the destination to be installed.
n Setup
(Note) In “Specific indoor unit priority” mode only, it is necessary to set up an indoor unit only which you desire
to give priority.
1. Outdoor unit (Header unit only) setup
SW11
Bit 1Bit 2
OFFOFF
Heating priority (Setup at shipment)
Operation
ONOFF
OFFON
ONON
Cooling priority
No. of operating units (Priority is given to operation mode with which much more units operate.)
Specific indoor unit priority (Priority is given to operation mode of the indoor unit to which the
operation mode priority has been set up.)
81
Page 82
2. Indoor unit setup in “Specific indoor unit priority” mode
The setup can be changed during stop of operation. (Be sure to stop the system.)
Procedure
1
2
CODE No.
2
4
SET DATA
UNIT No.
R.C. No.
6
UNIT
1
SET
CL
3
5
Operation contents
When pushing
the display section flashes after a while confirm the displayed item code is [
• When the item code is one other than [ ], push button to
eliminate the display and then repeat the procedure from the first step.
(The remote controller operation is not accepted approx. 1 minute
after pushing
(In a group control, the indoor unit with number displayed firstly is set to
the header unit.)
Every pushing
Select the indoor unit of which setup is to be changed.
In this time, as the fan and louver of the selected indoor unit operate,
the position of the indoor unit of which setup is to be changed can be confirmed.
SET
+ CL + buttons at the same time for 4 seconds or more, as shown in the figure,
].
button.)
, the indoor unit numbers in the group control are successively displayed.
UNIT
SET DATA
CODE No.
UNIT No.
R.C. No.
Using the setup temperature and buttons, specify the item code [" ].
3
4
5
6
Using the timer time and buttons, select the setup data [
Priority:
SET
Push
lighting.
After setup operation has finished, push button. (Setup is determined.)
When pushing button, the display disappears and the status returns
to the usual stop status.
(The remote controller operation is not accepted for approx. 1 minute.)
, No priority:
button. In this time, the setup operation finishes when the display changes from flashing to
].
SET DATA
UNIT No.
R.C. No.
CODE No.
(NOTE)
Only one indoor unit can be set to “Priority”. If the multiple indoor units are accidentally set to “Priority”, an error
code (L05 or L06: Duplicated indoor unit priority) is displa yed.
To the unit displaying “L05”, [0001 (Priority)] is setup. Separate a unit which you will give priority from the other
indoor units, and return the setup data of the other indoor units to [0000 (No priority)].
Error code
L05
Indoor unit priority duplication ([
Error contents
] is set up.)
L06
Indoor unit priority duplication ([
82
] is set up.)
Page 83
7-2-2. Applied Control in Outdoor Unit
The following functions become a vailable by using a control P.C. board sold separately.
Set up the switches or the header outdoor unit (U1).
The outdoor unit fan operates by the Snowfall signal from outside.
Terminal
COOL
(SMC)
The control contents are accepted during leading and trailing of
the input signal.
(The status of leading and trailing should be held for 100mm. sec.
or more.)
External master ON/OFF control board : TCB-PCM02E
Outdoor unit destination to be connected becomes the header
outdoor unit (U1).
SMC: Cooling Mode Select (switch)
Input signal
ON
OFF
ON
OFF
Operation
Snowfall fan control
(Operates outdoor unit fan.)
Usual operation
(Releases control.)
7-2-2-4. External master ON/OFF control
Header outdoor unit interface P.C. board
CN512 (4P BLU)
Connection cable
External master
ON/OFF
control board
HEAT
COOL
SMH
PJ17
SMC
(4P WHI)
COM
Operation
The outdoor unit starts or stops the system.
The control contents are accepted during trailing of the input signal.
(The status of trailing should be held for 100m. sec. or more.)
NOTES
1) Do not turn on COOL and HEAT ter minals concurrently.
2) Be sure to prepare a contact for each terminal.
External master ON/OFF control board : TCB-PCM02E
Outdoor unit destination to be connected becomes the header
outdoor unit (U1).
Terminal
COOL
(SMC)
Heat
(SMH)
Input signal
ON
Starts collectively indoor units.
OFF
ON
Stops collectively indoor units.
OFF
Outside signal: No voltage pulse contact
Operation
Procured locally
SMH: Heating Mode Select (switch)
86
Page 87
7-2-2-5. Night Operation Control
Header outdoor unit interface P.C. board
CN508 (4P RED)
Connection cable
External master
ON/OFF
control board
HEAT
COOL
PJ17
(4P WHI)
COM
SMC
Procured locally
Operation
The noise decreases in the night.
Terminal
COOL
(SMC)
Input signal
ON
OFF
ON
OFF
Night (sound reduction)
operation control
Usual operation
The control contents are accepted during leading and trailing of
the input signal.
(The status of leading and trailing should be held for 100mm. sec.
or more.)
Capacity criterion during night operation control
Capacity during control indicates values as described in the
External master ON/OFF control board : TCB-PCM02E
Outdoor unit destination to be connected becomes the header outdoor unit (U1).
7-2-2-6. Operation Mode Selection Control
Header outdoor unit interface P.C. board
CN510 (4P WHI)
Connection cable
External master
ON/OFF
control board
HEAT
COOL
SMH
PJ17
SMC
(4P WHI)
COM
Operation
SMC: COOL mode specification input switch
SMH: HEAT mode specification input switch
This control can be operated with the operation mode which is
permitted by SMC or SMH.
The indoor unit operating by operation mode without permission
is as follows:
1) Display on remote controller
“Mode select controlled” goes on.
2) Indoor fan
In FAN mode: Fan normally operates.
In COOL mode: Fan normally operates.
In HEAT mode: Fan operates with ultra low speed.
* Be sure to prepare a contact for each contact terminal.
External master ON/OFF control board : TCB-PCM02E
Outdoor unit destination to be connected becomes the header
outdoor unit (U1).
Outside signal: No voltage serial contact
Procured locally
87
Page 88
8.TEST OPERATION
8-1. Procedure and Summary of Test Operation
A test operation is executed in the following procedure. When a trouble or an error occurs in each step, remo ve
causes of a trouble or an error referring to the section “9. T roubleshooting”.
Check before test operation
Check the main power supply
is turned on.
Set up the addresses.
Test operation
Check the basic items, mainly the installation work.
Be sure to enter the check results in the check list 1 and 2.
It is the check after the power has been turned on.
Check the refrigerant circuit system is normally turned on.
Start the address setup in the outdoor/indoor units.
(NOTE) The operation does not start by only power-ON.
Carry out a test operation.
Check air blowing and cooling/heating operation in the indoor unit.
END
8-2. Check Items bef ore Test Operation
Prior to the test operation, check the follo wing items
so that there is no trouble in the installation work.
<Main check items for electric wiring>
The communication system differs from
that of R22 or R407 refrigerant
“Modular Multi system”
air conditioner .
Check again cautious points on wiring.
Header unit (A)
Outdoor
unit
1
U1U3U2
Earth
U4
24
U5 U6
Follower unit (B)
U4
U1U3U2U5 U6
3
Follower unit (C)
U4
U1U3U2U5 U6
1. In case that a center control
system is not connected:
No.
Are indoor and outdoor communication lines of the header unit connected to U1/U2
terminals?
Is the relay connector between U1/U2 terminal and U3/U4 terminal removed?
(Set up at shipment from the factory)
Is the communication line between each outdoor units connected to U5/U6 terminal?
Is the terminal resistance (SW30-2) on the interface P.C. board of the header unit
turned on? (Set up at shipment from the factory)
Is the end terminal of the shield cable grounded?
Main check items
3-phase
380-415V
Leak interception
Main switch
Indoor
unit
1-phase 230V
Leak interception
Main switch
55
U1AU2
B
Remote controller
NOTE) The above figure does not show all the electric cables.
For details, refer to the installation manuals for outdoor unit, indoor unit, remote controller, or optional devices.
U1AU2
U1AU2
B
U1AU2
B
B
Check
88
Page 89
2. In case that a central control system is connected (Before address setup)
Central control units
U1U3U2
U4
4
25
3
Other refrigerant line
Other refrigerant line
U1U3U2U5 U6
U4
To indoor unit
Outdoor unit
1
3-phase
380-415V
Leak interception
Main switch
Indoor unit
1-phase 230V
Leak interception
Main switch
Header unit (A)
U1U3U2
Earth
U1AU2
Remote
controller
Follower unit (B)
U4
U5 U6
U4
U1U3U2U5 U6
6
U1AU2
B
Remote
controller
U1AU2
B
B
Remote
controller
Follower unit (C)
U4
U1U3U2U5 U6
6
U1AU2
B
No.
Are indoor and outdoor communication lines of the header unit connected to U1/U2
terminals?
Is the relay connector between U1/U2 terminal and U3/U4 terminal removed?
(Set up at shipment from the factory) (Before address setup, remo ve the relay connector.)
Is the communication line between outdoor and indoor units connected to U5/U6 terminal?
Main check items
Is the communication line of the central control system connected to the header unit U3/U4
terminals of each refrigerant line?
(The communication line of the central control system may be connected to the communication lines of the indoor/outdoor communication lines.)
Is the terminal resistance (SW30-2) on the interface P.C. board of the header unit turned on?
(Set up at shipment from the factory)
(After address setup, turn off SW30-2 of the header unit except the smallest unit after
check of trial operation.)
Is the end terminal of the shield cable grounded?
When the refrigerant line and the central control system of the custom air conditioner are
connected:
→ Are TCC-LINK adaptors correctly connected?
→ When the digital inverter air conditioner operates with group operation, twin, or triple
operation, are the adopters connected to the header unit of the indoor unit?
NOTE) The above figure does not show all the electric cables.
For details, refer to the installation manuals for outdoor unit, indoor unit, remote controller, or optional
devices.
Check
89
Page 90
<Check list 1>
• Using the “Check list 1”, check there is no trouble in the installation w ork.
Is capacity of the leakOutdoor total capacity XXXX AHeader unit (A)XXXX AIndoor unit XXXX A
breaker appropriate?
Is diameter of the power cable correct?Header unit (A)XXXX mm²Indoor unit XXXX mm²
Is control communication line correct?Indoor –outdoor connection terminals (U1, U2)XXXX
Is power of indoor units supplied collectively?
Is earth grounded
Is insulation good?
Is the main power voltage good?XXXX V
Is diameter of connecting pipe correct?
Follower unit (B) XXXX A
Follower unit (C) XXXX A
Follower unit (D) XXXX A
Follower unit (B)
Follower unit (C) XXXX mm²
Follower unit (D) XXXX mm²
Outdoor–outdoor connection terminals (U5, U6)XXXX
Central control system connection terminals (U3, U4)XXXX
XXXX mm²
Is the branch kit correct?
Is drain water of the indoor unit arranged so that it flows without accumulation?
Is thermal insulation of pipes good? (Connecting pipes, Branch kit)
Is not short-circuit of discharge air in indoor/outdoor units?
After airtight test for pipes, are vacuuming and adding of refrigerant executed?
Are valves of all the outdoor units fully opened?Gas sideLiquid sideBalance side
Header unit (A)XXXXXXXXXXXX
Follower unit (B)XXXXXXXXXXXX
Follower unit (C)XXXXXXXXXXXX
Follower unit (D)XXXXXXXXXXXX
90
Page 91
• Check the additional amount of refrigerant.
<Check list 2>
Calculate the additional amount of refrigerant from the additional amount of refrigerant (A) by the pipe diameter at liquid side and the pipe length to be connected and the corrective amount of refrigerant (C) by the
system capacity.
Additional amount=Actual liquid×Additional amount of
of refrigerantpipe lengthrefrigerant per liquid pipe 1mrefrigerant by system capacity
(A) (C)
Firstly enter the total length for each liquid pipe in the following table, and then calculate the additional amount
of refrigerant by pipe length.
<Additional amount of refrigerant by pipe length>
Corrective amount of
+
Pipe dia at
liquid side
Ø6.4
Ø9.5
Ø12.7
Ø15.9
Ø19.0
Ø22.2
Standard amount of refrigerant
kg/m
0.025 ×
0.055 ×
0.105 ×
0.160 ×
0.250 ×
0.3505 ×
Total pipe length at each liquid side
=
=
=
=
=
=
Additional amount of refrigerant by pipe
length (A)
Additional amount of refrigerant pipe
dia at each liquid side kg
Next, refer to the following table for the corrective amount of refrigerant (C) by system capacity.
<Corrective amount of refrigerant by system capacity>
Lastly add the additional amount of refrigerant by pipe length (A) to the corrective amount of refrigerant by
system capacity (C). It is the final additional amount of refrigerant.
As the result, If minus sign is indicated, do not add the refrigerant (=0kg).
<Additional amount of refrigerant>
Additional amount of refrigerant by pipe length (A)
Corrective amount of refrigerant by system HP (C)
Additional amount of refrigerant
kg
kg
kg
91
Page 92
8-3. Check at Main Power-ON
After turning on the main power of the indoor units and outdoor unit in the refrigerant line to be ex ecuted with a
test operation, check the following items in each outdoor and indoor unit.
(After turning on the main power, be sure to check in order of indoor unit
<Check on outdoor unit>
1. Check that all the rotary switches, SW01, SW02, and SW03 on the interface P.C. board of the header unit are
set up to “1”.
2. If other error code is displayed on 7-segment [B], remove the cause of troub le referring to
“9. T roubleshooting”.
3. Check that [L08] is displayed on 7-segment display [B] on the interf ace P.C. board of the header unit.
(L08: Indoor address unset up)
(If the address setup operation has already finished in service time, etc, the above check code is not displayed, and only [U1] is displayed on 7-segment display [A].)
→→
→ outdoor unit.)
→→
7-segment display [A]
Interface P.C. board
SW01SW02SW03
7-segment display [B]
<Check on indoor unit>
1. Display check on remote controller (In case of wired remote controller)
Check that a frame as shown in the following left figure is displayed on LC display section of the remote
controller.
SET
UNIT
CL
UNIT
CL
SET
Normal status
(Power and operation stop)
(Power is not normally turned on.)
Abnormal status
If a frame is not displayed as shown in the above right figure, the power of the remote controller is not normally
turned on. Therefore check the following items.
• Check power supply of indoor unit.
• Check cabling between indoor unit and remote controller.
• Check whether there is cutoff of cable around the indoor control P.C. board or not, and check connection
failure of connectors.
• Check failure of transformer for the indoor microcomputer.
• Check indoor control P.C. board failure.
92
Page 93
8-4. Address Setup
After power-ON, set up the indoor address from the interface P.C. board of the header unit.
(The address setup operation cannot be performed by power-ON only.)
8-4-1. Cautions
1. It requires approx. 5 minutes usually for 1 line to automatically set up address.
Howe ver in some cases, it may require maximum 10 minutes.
2. It is unnecessary to operate the air conditioner for address setup.
3. Manual address setup is also available besides automatic setup.
Automatic address: Setup from SW15 on the interface P.C. board of the header unit
Manual address: Setup from the wired remote controller.
(For details, refer to section “8-4-3. Ad dress setup procedure”)
8-4-2. Address Setup and Check Procedure
Procedure
1
2
3
4
5
6
Item
Indoor unit power-ON
Outdoor unit power-ON
7-segment display
check
Address setup start
Display check after
setup
System information
check after setup
Operation and check contents
Turn on power of indoor unit in refrigerant line to which address is set up.
Turn on power of all the outdoor units in refrigerant line to which address is set up.
Check that [L08] is displayed on 7-segment display [B] on the interface P.C. board of the header
unit in the system to which address is set up.
Confirm the corresponding items in “8-4-3 Address setup procedure”, and then set up address
according to the operation procedure.
(Be sure that the setup operation may differ in group control or central control.)
Note) Address cannot be set up if switches are not operated.
• After address setup, [U1] is displayed in 7-segment display section.
• For follower outdoor units, [U2] to [U4] are displayed in 7-segment display [A].
• If an error code is displayed in 7-segment display [B], remove the cause of trouble referring to
“9. Troubleshooting”.
Using 7-segment display function, check the system infor mation of the scheduled system.
(This check is executed on the interface P.C. board of the header unit.)
Rotary switch setup
SW01 SW02 SW03
System capacity
No. of connected outdoor units
No. of connected indoor units
After the above checks, return rotary switches SW01, SW02, SW03 to 1/1/1.
123
133
143
[Connected No. of units]
7-segment display
[A][B]
[No. of HP][HP]
[No. of units][ P]
Interface P.C. board
7-segment
display [A]
Push-switch
SW04
SW01SW02
<Rotary switches>
93
Push-switch
SW05
SW03
Push-switch
SW15
7-segment
display [B]
Page 94
8-4-3. Address Setup Procedure
In this air conditioner, it is required to set up address to the indoor unit before starting operation. Set up the address according to the following setup procedure.
CAUTIONS
1. Set up address after wiring work.
2. Be sure to turn on the power in order of indoor unit → outdoor unit. If turning on the power in the reverse
order, a check code [E19] (Error of No. of header units) is output. When a check code is output, turn on
the power again.
3. It requires maximum 10 minutes (Usually, approx. 5 minutes) to set up automatically an address to 1 line .
4. To set up an address automatically, the setup at outdoor side is necessary.
(Address setup cannot be performed by power-ON only.)
5. To set up an address, it is unnecessary to operate the air conditioner.
6. Manual address setup is also available besides automatic setup.
Automatic address : Setup from SW15 on the interface P.C. board of the header unit
Manual address: Setup from the weird remote controller
∗ It is temporarily necessary to set the indoor unit and wired to 1 : 1.
(In group operation and in time without remote controller)
Automatic Address Setup
Without central control : To the address setup procedure 1
With central control: To the address setup procedure 2
(However, go to the procedure 1 when the central control is performed in a single refrigerant line.)
(Example)
Address setup procedure
Cable systematic diagram
In case of central control in a single refrigerant line
To procedure 1
Outdoor
IndoorIndoor
Remote
controller
Central control
remote controller
Remote
controller
Outdoor
IndoorIndoor
Remote
controller
Central control
remote controller
Address setup procedure 1
1. Turn on power of indoor/outdoor units.
(In order of indoor
2. After approx. 1 minute, check that U. 1. L08 (U. 1. flash)
is displayed in 7-segment display section on the interface
P.C. board of the header unit.
3. Push SW15 and start setup the automatic address.
(Max. 10 minutes for 1 line (Usually, approx. 5 minutes))
4. When the count Auto 1 → Auto 2 → Auto 3 is displayed in 7-segment display section, and it changes from
U. 1. - - - (U. 1. flash) to U. 1. - - - (U. 1. light) , the
setup finished.
5. When perform a central control, connect a relay
connector between [U1, U2] and [U3, U4] terminals in
the header unit.
→→
→ Outdoor)
→→
In case of central control over refrigerant lines
To procedure 2
Outdoor
IndoorIndoor
Remote
controller
Remote
controller
Outdoor
IndoorIndoor
Remote
controller
Central control
remote controller
Header unit interface P.C. board
SW04
SW05 SW15
3
2, 4
D600 D601 D602 D603 D604
SW01
SW02 SW03
111
5
U1 U2
For internal
wiring between
indoor and
outdoor
U3 U4
For wiring of
central control
system
U5 U6
For internal
wiring between
outdoor units
94
Page 95
REQUIREMENT
U1 U2
For internal
wiring between
indoor and
outdoor
U3 U4
For wiring of
central control
system
U5 U6
For internal
wiring between
outdoor units
2
• When a group control is performed over the
multiple refrigerant lines, be sure to turn on the
power supplies of all the indoor units connected
in a group in the time of address setup.
• If turning on the power for each refrigerant line
to set up address, a header indoor unit is set for
each line. Theref ore , an alarm code “L03”
(Duplicated indoor header units) is output in
operation after address setup. In this case,
change the group address from the wired
remote controller for only one header unit is set
up.
(Example)
Cabling
systematic
diagram
Group control over
multiple refrigerant lines
Outdoor
IndoorIndoor
Remote
controller
Outdoor
IndoorIndoor
Address setup procedure 2
1. Using SW13 and 14 on the interface P.C. board of
Header unit interface P.C. board
ON
1
2 3 4
1ON2 3 4
1ON2 3 4
1ON2 3 4
the header unit in each system, set up the refrigerant line address for each system.
(At shipment from factory: Set to Address 1)
Note) Be careful not to duplicate with other refriger-
ant line.
SW11
1ON2 3 4
SW06
SW12
ONONONON
1
2 3 4
SW07
SW13
112 3 4
SW09SW08
SW14
1 2 3 4
SW10
System address switch on outdoor interface P.C. board(¡: Switch ON, × : Switch OFF)
2. Check that the relay connectors between [U1U2] and
[U3U4] terminals are come out in all the header units to
which the central control is connected.
(At shipment from factory: No connection of connector)
3. T urn on power of indoor/outdoor.
(In order of indoor
→→
→ outdoor)
→→
4. After approx. 1 minute, check that 7-segment display is
U.1.L08 (U.1. flash) on the interface P.C. board of the
header unit.
5. Push SW15 and start setup the automatic address.
(Max. 10 minutes for 1 line (Usually, approx. 5 minutes))
6. When the count Auto 1
→→
→ Auto 2
→→
→→
→ Auto 3 is displa yed
→→
in 7-segment display section, and it changes from
U. 1. - - - (U. 1. flash) to U. 1. - - - (U. 1. light) , the
setup finished.
7. Procedure 4. to 6. are repeated in other refrigerant lines.
95
Page 96
8. How to set up resistance of the end terminal
Header unit interface P.C. board
When all the address setups have finished in the same refrigerant circuit system, put the resistance of the end terminals in the
same central control line into one.
• Remain only SW30-2 of the header outdoor unit with the least
refrigerant line address number as it is ON.
(With end terminal resistance)
• Set up SW30-2 of the other header outdoor units to OFF.
(Without end terminal resistance)
1ON2 3 4
SW11
1ON2 3 4
1ON2 3 4
1ON2 3 4
SW12
ONONONON
1
2 3 4
9. Connect the relay connector between [U1U2] and [U3U4] of the
header unit for each refrigerant line.
SW06
SW07
10. Then set up the central control address.
(For the central control address setup, refer to the Installation manual of the central control devices.)
123
Header
unit
U3 U4
Follower unit
U3 U4
U3 U4
Header unit
Follower unit
U3 U4
Header unit
U3 U4
1ON2
SW30
SW13
112 3 4
SW09SW08
SW30
1ON2 3 4
SW14
1 2 3 4
SW10
Before address setup
During setup of address
After address setup
Outdoor interface
P.C. board
SW13, 14
(Refrigerant line address)
SW30-2
Terminal-end resistance
of indoor/outdoor communi
cation line/central control
communication line
Relay
connector
Relay connector
U1 U2 U5 U6
U1 U2
A B
Remote
controller
Header
unit
U3 U4
SW30
U1 U2 U5 U6
U1 U2
A B
Remote
controller
U1 U2 U5 U6
U1 U2
A B
Remote
controller
IndividualGroup
Follower unit
U1 U2 U5 U6
U1 U2
A B
Remote
controller
U3 U4
SW30
21
ON
OFF
IndividualGroup
Relay
connector
21
ON
OFF
Relay
connector
U1 U2 U5 U6
U1 U2
A B
Remote
controller
U3 U4
SW30
U1 U2 U5 U6
U1 U2
A B
Remote
controller
U1 U2 U5 U6
U1 U2
A B
Header unitHeader unit
21
ON
OFF
Follower unit
U3 U4
SW30SW30
U1 U2 U5 U6
U1 U2
A B
21
ON
OFF
U1 U2 U5 U6
U1 U2
A B
Remote
controller
U3 U4
U1 U2 U5 U6
U1 U2
A B
Remote
controller
Header unitFollower unitFollower unitHeader unitHeader unit
12
ON
Connect short
after
address setup
(Setup is
unnecessary.)
(Setup is
unnecessary.)
Open
OFF after
address setup
Connect short
after
address setup
(Setup is
unnecessary.)
(Setup is
unnecessary.)
OpenOpen
31
OFF after
address setup
Connect short
after
address setup
Relay
connector
21
ON
OFF
Relay
connector
Setup at shipment
from factory
ON
Indoor side (Automatic setup)
Refrigerant line address
Indoor unit address
Group address
1
1
0
1
2
0
2
1
1
2
2
2
Point
Relay connector — NOTE —
Nev er connect a relay connector until address setup for all the refrigerant lines finishes;
otherwise address cannot be correctly set up.
96
3
1
0
Page 97
Manual address setup from remote controller
In case to decide an address of the indoor unit prior to finish of indoor cabling work and unpracticed outdoor
cabling work (Manual setup from remote controller)
Arrange one indoor unit and one remote controller set to 1 by 1.
Turn on the power.
(Wiring example in 2 lines)
#1
Outdoor
Indoor Indoor Indoor
Line address 1
Indoor address
Group address
In the above example, under condition of
no jump wire of the remote controller, set
the address after individual connecting of
the wired remote controller.
Group address
Individual: 0000
Center unit: 0001
Terminal unit : 0002
1
1
Remote
controller
Header
1
2
2
} In case of group control
Outdoor
1
3
2
Terminal
#2
Indoor Indoor
2
1
2
1
(Refrigerant line address)
2
3
2
2
2
(Indoor address)
4
5
6
7
(Group address)
8
Push simultaneously
buttons for 4 seconds or more.
LCD changes to flashing.
Using the setup temp. /
buttons, set to the item code .
Using the timer time / buttons, set
up the line address.
(Match it with the line address on the interface
P.C. board of the header unit in the identical
refrigerant line.)
Push
(OK when display goes on.)
Using the setup temp. /
buttons, set ! to the item code .
Using the timer time / buttons, set
up the indoor address.
Push
(OK when display goes on.)
Using the setup temp. /
buttons, set " to the item code .
SET
SET
button.
button.
SET
+
CL
+
9
Using the timer time / buttons, set
Individual = , Header unit = ,
Follower unit =
Operation procedure
1 2 3 4 5 6
8 9 10 11
7
SET DATA
DataItem code
UNIT No.
R.C. No.
End
CODE No.
11
UNIT
1
SET
CL
10
Push
(OK when display goes on.)
11
Push button.
Setup operation finished.
(Status returns to normal stop status.)
3, 6, 9
2, 5, 8
4, 7, 10
97
SET
.
button.
Page 98
Note 1)
When setting the line address from the remote controller, do not use address 29 and 30.
The address 29 and 30 cannot be set up in the outdoor unit. Therefore if they are incorrectly set up, a check
code [E04] (Indoor/outdoor communication circuit error) is output.
Confirmation of indoor unit address and position by using the remote controller
[Confirmation of indoor unit address and the position]
1. When you want to know the indoor address though position of the indoor unit itself can be
recognized;
<Procedure> (Operation while the air conditioner operates)
1
If it stops, push button.
2
Push
The unit NO 1-1 is displayed on the LCD.
(Disappears after several seconds) The displayed
unit No indicates the line address and indoor
address. (If there is other indoor unit connected
to the same remote controller (Group control
unit), other unit No is displayed every pushing
UNIT
button.
UNIT
button.)
1
Operate
SET
UNIT No.
CL
CODE No.
UNIT
2
Operation procedure
1 2
2. When you want to know position of the indoor unit using the address
• To confirm the unit numbers in a group control;
<Procedure> (Operation while the air conditioner stops)
The indoor unit numbers in a group control are successively displayed, and the corresponding indoor fan is
turned on. (Operation while the air conditioner stops)
1
Push + buttons simultaneously
for 4 seconds or more.
• Unit No ALL is displayed.
• The fans of all the indoor units in a group
control are turned on.
2
Every pushing
unit numbers in the group control are
successively displayed.
• The firstly displayed unit No indicates the
address of the header unit.
• Only fan of the selected indoor unit is turned
on.
3
Push button to finish the procedure.
All the indoor units in group control stop.
button, the indoor
UNIT
3
End
1
2
SET DATA
Operation procedure
1 2 3
SET
UNIT No.
R.C. No.
UNIT
CL
CODE No.
End
98
Page 99
• To confirm all the unit numbers from an arbitrary wired remote controller;
<Procedure> (Operation while the air conditioner stops)
The indoor unit No and position in the same refrigerant piping can be confirmed. An outdoor unit is selected, the
indoor unit numbers in the same refrigerant piping are successively displayed, and then its indoor unit fan is
turned on.
1
Push the timer time + buttons simultaneously for 4 seconds or more.
Firstly, the line 1, item code )+ (Address Change) is displayed. (Select outdoor unit.)
2
Using
address.
3
Using
address.
• The indoor unit address, which is connected to the
SET
refrigerant pipe of the selected outdoor unit is displayed and the fan is turned on.
+ buttons, select the line
UNIT
button, determine the selected line
SET DATA
CODE No.
UNIT No.
R.C. No.
4
2
4
Every pushing
numbers in the identical pipe are successively
displayed.
• Only fan of the selected indoor unit operates.
button, the indoor unit
UNIT
6
1
SET
UNIT
CL
[To select another line address]
5
Push
• The indoor address of another line can be successively confirmed.
6
Push button to finish the procedure.
Change of indoor address from remote controller
Change of indoor address from wired remote controller
• To change the indoor address in individual operation (Wired remote controller : Indoor unit = 1 : 1) or
group control (When the setup operation with automatic address has finished, this change is available.)
<Procedure> (Operation while air conditioner stops)
1
Push simultaneously
(The firstly displayed unit No indicates the header unit in group control.)
2
In group control, select an indoor unit No to be changed by
(The fan of the selected indoor unit is turned on.)
3
Using the setup temp. / buttons,
! to the item code.
set
4
Using the timer time / buttons, change
the displayed setup data to a data which you
want to change.
button to return to procedure 2 ).
CL
SET
+
+ buttons for 4 seconds or more.
CL
3
Operation procedure
1 2 3
5 6
4
button.
UNIT
SET DATA
4
End
CODE No.
UNIT No.
R.C. No.
5
2,
6,
5
Push
6
Using the
be changed at the next time. Repeat the procedure
that it is not duplicated.
7
After the above change, push
confirm the changed contents.
8
If it is acceptable, push button to finish
confirmation.
button.
SET
button, select the unit No. to
UNIT
4
to 6 and change the indoor address so
button to
UNIT
99
8
1
SET
CL
5
Operation procedure
1 2 3 4
6 7 8
5
UNIT
7
3
End
Page 100
• To change all the indoor addresses fr om an arbitrary wired remote controller;
6
(When the setup operation with automatic address has finished, this change is available.)
Contents: Using an arbitrary wired remote controller, the indoor unit address can be changed for each same
refrigerant piping line
∗∗
∗ Change the address in the address check/change mode.
∗∗
<Procedure> (Operation while air conditioner stops)
1
Push the timer time + buttons simultaneously for 4 seconds or more.
Firstly, the line 1, item code AC (Address Change) is displayed.
2
Using
3
Push
• The indoor unit address, which is connected to the refrigerant pipe of the selected outdoor unit is dis-
4
The indoor address of the setup data moves up/down by the timer time / buttons.
Change the setup data to a new address.
5
Push
6
Every pushing
displayed. Only fan of the selected indoor unit operates.
Repeat the procedure 4 to 6 and change all the indoor addresses so that they are not duplicated.
SET
played and the fan is turned on.
First the current indoor address is displayed on the setup data. (Line address is not displayed.)
SET
+ buttons, select the line address.
UNIT
button.
button to determine the setup data.
button, the indoor unit numbers in the identical pipe are successively
UNIT
7
Push
(All the displays on LCD go on.)
8
Push button to finish the procedure.
SET
button.
SET DATA
CODE No.
UNIT No.
R.C. No.
1
UNIT
CL
SET
3
Cancel of line selection
2
4
8
5, 7
To finish the setup
SET DATA
SET
CODE No.
UNIT No.
R.C. No.
UNIT
CL
Here, if the unit No is not called up, the outdoor unit in
this line does not exist.
Push
procedure 2 .
button, and then select a line according to
CL
100
Operation procedure
1 2 3 4
6 7 8
5
End
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.