Toshiba MMU-AP0071MH, MMU-AP0151MH, MMU-AP0091MH, MMU-AP0181MH, MMU-AP0121MH SERVICE MANUAL

Engineering Data
Compact 4-way
Cassette (600 x 600) Type
Mar. 06
,
Indoor Unit
MMU-AP0071MH MMU-AP0091MH MMU-AP0121MH MMU-AP0151MH MMU-AP0181MH
Contents
1. Specifications
2. Dimension
4. Sensible capacity table
5. Wiring diagram
6. Air throw distance chart
7. Sound characteristics (NC-Curve)
8. Fresh air intake (Design guide)
9. Accessories
1. Specifications
Compact 4-way Cassette (600 x 600) Type
Model name MMU-
Cooling/Heating capacity (Note 1) (kW)
Power supply
Electrical characteristics
Appearance
Outer dimension
Running current (A)
Power consumption (kW)
Starting current (A)
Main unit
Ceiling Panel
Main unit
Ceiling panel
Model
Panel color
Height (mm)
Width (mm)
Depth (mm)
Height (mm)
Width (mm)
AP0071MH
2.2/2.5
1 phase 50Hz 230V (220-240V) (Separate power supply for indoor units is required.)
0.28
0.034
0.49
Zinc hot dipping steel plate *Heat-insulating material attached to only upper plate
AP0091MH
2.8/3.2
0.30
0.036
0.52
Moon white (Munsell/2.5GY 9.0/0.5)
AP0121MH
3.6/4.0
0.31
0.038
0.54
RBC-UM11PG(W)E
268
575
575
27
700
AP0151MH
4.5/5.0
0.34
0.041
0.59
50Hz
AP0181MH
5.6/6.3
0.42
0.052
0.73
Total weight
Heat exchanger
Soundproof/Heat-insulating material
Fan unit
Air filter
Controller
Connecting pipe
Sound pressure level(Note 2) (High/Mid/Low)
Main unit (kg)
Ceiling panel (kg)
Fan
Standard air flow (High/Mid/Low)
Motor (W)
Gas side (mm)
Liquid side (mm)
Drain port
(Nominal dia. mm)
Depth (mm)
3
(m
(dB(A))
700
17
3
Finned tube
Non-flammble insulation
Turbo fan
/h)
552/462/378 570/468/378 594/504/402 660/552/468 762/642/522
60
Long life filter
Remote controller
O
36/32/28
9.5
/
O
6.4
/
25 (Polyvinyl choride tube)
37/33/28 37/33/29 40/35/30 44/39/34
O
12.7
/
PMV Kit
Available
A-55
1. Specifications
Compact 4-way Cassette (600 x 600) Type
Model name MMU-
Cooling/Heating capacity (Note 1) (kW)
Power supply
Electrical characteristics
Appearance
Outer dimension
Running current (A)
Power consumption (kW)
Starting current (A)
Main unit
Ceiling Panel
Main unit
Ceiling panel
Model
Panel color
Height (mm)
Width (mm)
Depth (mm)
Height (mm)
Width (mm)
AP0071MH
2.2/2.5
0.27
0.034
0.49
Zinc hot dipping steel plate *Heat-insulating material attached to only upper plate
AP0091MH
2.8/3.2
1 phase 60Hz 220V (Separate power supply for indoor units is required.)
0.29
0.036
0.52
Moon white (Munsell/2.5GY 9.0/0.5)
AP0121MH
3.6/4.0
0.30
0.038
0.54
RBC-UM11PG(W)E
268
575
575
27
700
AP0151MH
4.5/5.0
0.33
0.041
0.59
60Hz
AP0181MH
5.6/6.3
0.41
0.052
0.73
Total weight
Heat exchanger
Soundproof/Heat-insulating material
Fan unit
Air filter
Controller
Connecting pipe
Sound pressure level(Note 2) (High/Mid/Low)
Main unit (kg)
Ceiling panel (kg)
Fan
Standard air flow (High/Mid/Low)
Motor (W)
Gas side (mm)
Liquid side (mm)
Drain port
(Nominal dia. mm)
Depth (mm)
3
(m
(dB(A))
700
17
3
Finned tube
Non-flammble insulation
Turbo fan
/h)
552/462/378 570/468/378 594/504/402 660/552/468 762/642/522
60
Long life filter
Remote controller
O
36/32/28
9.5
/
O
6.4
/
23 (Polyvinyl choride tube)
37/33/28 37/33/29 40/35/30 44/39/34
O
12.7
/
A-56
PMV Kit
Available
2. Dimension
Compact 4-way Cassette (600 x 600) Type (MMU-AP***MH)
Bottom face of ceiling
For bracch duct knockout square hole O
Bottom face of ceiling O
575 unit external dimension
Refrigerant pipe (Gas) 0151, 0181MH 0071, 0091, 0121MH
.................
Refrigerant pipe (Liquid) O
For branch duct knockout square hole O
(NOTE) As ABS is used for the drain discharge port of the main unit, the vinyl chloride paste cannot be used. Use the flexible hose (Band fix) included in the package.
O
12.7
/
.......
9.5
O
/
190.5
193.5
Wiring connection port
162
/
Electric parts box
6.4
/
70.5
105
93
150
/
320.5
97.5
55
150
/
105
235 235
575 unit external dimension
331.5
Model name
MMU-AP0071MH
4-way air Discharge Cassete Type
MMU-AP0091MH
MMU-AP0121MH
MMU-AP0151MH
Arialb1i0c0p34;TOSHIBA CARRIER CORPORATION
MMU-AP0181MH
21
158
148
105
142
177
256
O
/
162
525 hanging bolt pitch
595 to 660 ceiling open dimension
700 Panel external dimension
214
42
120
93
145.5
105
70.5
Knockout for flesh air intake O
525 hanging bolt pitch
700 Panel external dimension
595 to 660 ceiling open dimension
Hanging bolt M10 or W3/8 local arrange
Drain discharge port
268
134
145.5
Indoor unit
220.5
27
63
Ceiling panel
100
/
29
142
64368.5
Bottom face of ceiling
300
Stand-up
827.5 or less
Stand-up
207
175
149
64
850 or less
Wired remote controller RBC-AMT31E
Simple wired remote controller RBC-AS21E2
Drain-up standing-up size
595 to 660 ceiling open dimension
595 to 660 ceiling open dimension
1000 or more
Wireless remote controller kit TCB-AX21E2
Weekly timer application RBC-AMT31E and RBC-EXW21E2
Bottom face of ceiling
1000 or more 1000 or more
15 or more
Obustacle
Space required for installation and servicing
Check port ( 450)
15 or more
Note: All dimensions are in mm.
200
A-57
Loading...