Toshiba MMD-AP 1HF2UL, MMD-AP0481HF2UL, MMD-AP0721HF2UL, MMD-AP0961HF2UL Series Manual

MMD-AP___1HF2ULE15-3S2
MMD-AP0481HF2UL MMD-AP0721HF2UL MMD-AP0961HF2UL
Outside Air Unit Type

Contents

1. System summary
2. Specifications
3. Dimensions
4. Center of gravity
6. System combination
7. Wiring diagram
8. Electrical characteristics
9. Fan characteristics
10. Sound data
1

1. System summary

• Connectable outdoor unit
Outdoor unit of SMMS-e series.
• Corresponding system
Corresponds to a system in which there are the outside air units and the indoor air conditioners.
• Definition
The outside air unit means an air controller for taken-in outside air. Intake of the outside air often influences on the system so that the normal control of the air conditioner becomes difficult or gives a large load upon air controller and cooling performance. Therefore it is frequently adopted to handle the outside air to a certain condition before the outside air will enter in the main air conditioner. This handling device is called an outside air unit.
NOTE:
The outside air unit is an air conditioner provided to handle the outside air load and is not to control the room temperature. For correspondence to the load of the indoor air controller, set an air conditioner separately.
Outside Air Unit Type
MMD-AP___1HF2ULE15-3S2
2
MMD-AP___1HF2ULE15-3S2

2. Specifications

Model name MMD- AP0481HF2UL AP0721HF2UL AP0961HF2UL
Cooling capacity (Note1)
Heating capacity (Note1)
Power supply 230 V (208/230 V) 1phase
Electrical characteristics
Outer dimension
Main unit weight lbs 212 349
Heat exchanger Finned tube
Soundproof / Heat-insulating material Non-flammable insulation
Fan Centrifugal fan
Standard air flow cfm 636 989 1237
Motor W AC 160 AC 160 x 2
External static pressure (factory default)
External static pressure (factory default)
Air flow limit
Air filter Field supply
Controller Wired remote controller
Connecting pipe
Sound pressure level
Operation range for SMMS-e
Running current A 1.58/1.56 3.00/2.88 3.32/3.17
Power consumption kW 0.31/0.34 0.56/0.58 0.64/0.66
Starting current A 3.90/3.20 7.70/6.30 8.50/6.90
Height In 19.5"
Width In 35.4" 55"
Depth In 49.8"
208 V / 230 V In WG 0.55/0.86 0.74/1.00 0.41/0.85
208 V (H / M / L) In WG 0.75/0.55/0.16 0.84/0.74/0.24
230 V (H / M / L) In WG 1.06/0.86/0.50 1.08/1.00/0.65
Lower limit cfm 445 693 866
Upper limit cfm 700 1088 1360
Gas pipe In 5/8" 7/8"
Liquid pipe In 3/8" 1/2"
Drain pipe In VP25 (Polyvinyl chloride tube: External Dia.1-1/4 internal Dia.1)
208 V (H / M / L) dB(A) 44/43/36 47/46/40
230 V (H / M / L) dB(A) 46/45/42 48/47/46
Cooling (Note 2)
Heating (Note 3)
kBtu/h 48.0 72.0 96.0
kBtu/h 30.0 47.0 59.0
0.67/0.41
1.01/0.85
°F
°F
41 - 115
23 - 109
47/45
50/49
(H/L)
(H/L)
(H/L)
(H/L)
* The setting temperature is 60 - 80 °F * Height difference between outside air units must be within 1.97" (0.5 m).
Note 1: Rated conditions Cooling: Outdoor air temperature 91 °F DB/82 °F WB setting temperature 64 °F
Heating: Outdoor air temperature 32 °FDB/26 °F WB setting temperature 77 °F
Note 2: * When supply air temperature is “setting temperature + 5.4 °F” or less, Outside air unit operates as FAN mode.
Note 3: * When supply air temperature is “setting temperature - 5.4 °F” or over, Outside air unit operates as FAN mode.
3

3. Dimensions

Installation Notes
Unit:in(mm)
1. Provide access area to the right of the unit as shown.
2. Condensate piping should slope downwards in the direction of
condensate flow, with a minimum gradient of 1in per 100 inches.
Condensate pipe should be insulated to avoid condensation.
3. Check condensate system for proper drainage before stating the unit.
4. Avoid installation of unit in Hazardous locations.
5. Filter and filter box are field provide and field installed items which
would prevent deposition of duct and dirt in the unit.
6. Install flexible duct for easy disassembly of the unit during major
service or breakdown.
7. Insulating the suction duct is recommended to avoid any
condensation on the exterior from untreated outside air.
8. Outside air louver with screen is recommended at the outside air
operating on the exterior wall.
Access Area
23.6"
(600)
23.6"
(600)
Space required for installation and servicing
Example
Access Area
23.6" (600)
Service
space
Over
7.9"
(200)
Service
space
7.9"
(200)
Over 39.4" (1000)
Outside Air
Unit
Outside Air
Unit
Flexible duct
Filter Box
Filter
Ceiling
Air intake duct
Access Area
Outside air
Over
3.9"
(100)
Over
2.0"
(50)
Air flow
23.0" (583)Outside
15.1" (383)
Outside
Suction
Discharge temp sensor
Discharge
28.7" (728)Outside
13.7" (347)
Outside
0.7" (18)
2.3" (59)
2.5" (65)
2.6" (65)
0.4" (9)
2.6" × 5 = 12.8"
(65 × 5 = 325)
Screw hole for
duct mounting
(6-ø0.2" (5))
1.9"
(49)
8.6"
(218)
5.9"
(150)
27.5" (699)
33.3" (845)
Drain pipe connection port (V25)
Taper screw for R1,1" (25.4) pipes
0.4" (10)
0.8" (20)
49.8" (1266)
0.7" (19)
0.4" (9)
Refrigerant pipe connection port
(Liquid side ø3/8" (9.5) Flared)
Refrigerant pipe connection port
(Gas side ø5/8" (15.9) Flared)
2.6" (65)
1.1"
(28)
2.6" × 5 = 12.8"
(65 × 5 = 325)
2.6" (66)
19.5" (496)
Electrical box
50.7" (1288) Mounting Location
52.3" (1328)
Hole for hanging bolt
(4-ø1/2" (12) × 1.6" (40))
2.6" (65)
2.5" (62)
2.6" × 10 = 25.6"
(65 × 10 = 650)
2.6" (65)
2.2" (55)
2.6" × 8 = 20.5"
(65 × 8 = 520)
32.2" (818) Mounting Location
3.4" (87) 35.4" (898)
0.4" (9)
0.7" (19)
0.4" (9)
0.7" (19)
Screw hole for duct mounting(9-ø0.2" (5))
Screw hole for duct mounting(11-ø0.2" (5))
7.6" (193)
11.8" (299)
1.2" (30)
1.3" (33)
Z
Z view
ø1.2" (30) Hole for control wire
and remote control wiring
ø7/8" (22.2) Hole for power supply cable
Screw hole for duct mounting
(6-ø0.2" (5))
MMD-AP0481HF2UL
MMD-AP___1HF2ULE15-3S2
4
0.7"(18)
2.3"(59)
Discharge temp sensor
Discharge
2.1"(52)
42.6"(1083) Outside
13.7"(347)
Outside
Z
2.6"(65)
2.6"×5=12.8"
(65×5=325)
0.4"(9)
2.6"(65)
1.1"
(28)
2.6"×5=12.8"
(65×5=325)
2.6"(66)
19.5"(496)
27.5"(699)
33.3"(845)
Drain pipe connection port(V25)
Taper screw for R1,1"(25.4) pipes
Screw hole for
duct mounting
(6-Ø0.2"(5))
Screw hole for duct mounting
(6-Ø0.2"(5))
1.9"
(49)
8.6"
(218)
5.9"
(150)
0.4"(10)
0.8"(20) 49.8"(1266) 0.7"(19)
0.4"(9)
Hole for hanging bolt
Refrigerant pipe connection port
(Liquid side Ø1/2"(12.7) Flared)
(4-Ø1/2"(12)×3.6"(92))
Suction
42.6"(1083) Outside
15.1"(383)
Outside
50.7"(1288) Mounting Location
52.3"(1328)
2.6"(65)
1.8"(45) 2.6"×16=40.9"(65×16=1040)
2.6"(65)
1.8"(45)
2.6"×16=40.9"(65×16=1040)
32.2"(818)
Mounting Location
55"(1398)
3.7"(93)
0.4"(9)
0.7"(19)
0.4"(9)
0.7"(19)
Screw hole for duct mounting(17-Ø0.2"(5))
Screw hole for duct mounting(17-Ø0.2"(5))
Refrigerant pipe connection port
(Gas side Ø7/8"(22.2) Brazed)
Access Area
23.6"
(600)
23.6"
(600)
Electrical box
Air flow
Space required for installation and servicing
Example
Access Area
23.6"(600)
Service
space
Over
7.9"
(200)
Service
space
7.9"
(200)
Over 39.4"(1000)
Outside
Air Unit
Outside
Air Unit
Flexible duct
Filter Box
Filter
Flexible duct
Ceiling
Air intake duct
Access Area
Outside air
Over
3.9"
(100)
Over
2.0"
(50)
4.0"(100)
6.6"(166)
1.3"
(33)
Ø1"(26) Hole for control wire
Ø7/8"(22.2) Hole for power supply cable
and remote control wiring
Z view
Installation Notice
1. Provide access area to the right of the unit as shown.
2. Condensate piping should slope downwards in the direction of
condensate flow,with a minimum gradient of 1in per 100 inches.
Condensate pipe should be insulated to avoid condensation.
3. Check condensate system for proper drainage before starting the unit.
4. Avoid installation of unit in Hazardous locations.
5. Filter and filter box are field provided and field installed items which
would prevent deposition of duct and dirt in the unit.
6. Install flexible duct for easy disassembly of the unit during major
service or breakdown.
7. Insulating the suction duct is recommended to avoid any
condensation on the exterior from untreated outside air.
8. Outside air louver with screen is recommended at the outside air
opening on the exterior wall.
Unit: in(mm)
MMD-AP___1HF2ULE15-3S2
5

4. Center of gravity

Z
Y
X
Electrical box
Model name MMD-
AP0481HF2UL
AP0721HF2UL
AP0961HF2UL
X (In) Weight (lb)
26.4 18.9 8.7 212
26.4 30.3 8.7 349
Z (In)Y (In)
MMD-AP___1HF2ULE15-3S2
6

5. Piping diagram

M
Liquid side Gas side
Strainer
Pulse Motor Val ve (PMV)
Sensor (TC2)
Strainer
Capillary tube
Air heat exchanger
at indoor side
Sensor (TCJ)
Fan
Sensor
(TA)
Fan motor
Sensor
(TC1)
Sensor
(TF)
MMD-AP___1HF2ULE15-3S2
Functional part name Functional outline
Pulse Motor Valve PMV (Connector CN082 (6P): Blue)
1) Controls super heat in cooling operation
2) Controls sub cool in heating operation
3) Recovers refrigerant oil in cooling operation
4) Recovers refrigerant oil in heating operation
Temp. sensor 1. TA (Connector CN104 (2P): White)
1) Detects indoor suction temperature
2. TC1 (Connector CN100 (3P): Brown)
1) Controls PMV super heat in cooling operation
3. TC2 (Connector CN101 (2P): Blue)
1) Controls PMV sub cool in heating operation
4. TCJ (Connector CN102 (2P): Yellow)
1) Controls PMV super heat in cooling operation
5. TF (Connector CN103 (2P): Green)
1) Detects indoor discharge temperature
7
MMD-AP___1HF2ULE15-3S2

6. System combination 6-1. Case of MMY model

The Outside Air Unit is connectable to SMMS (Super Modular Multi system).
However this is not connectable to SHRM (Super Heat Recovery Multi system).
Keep the height difference between the Outside Air Units to 1.97" (0.5 m) or less.
Case of Outside Air connection with other indoor units
Connection which stretches over two floors is unavailable units
Correct
Height difference: 1.97" (0.5 m) or less
Case of All Outside Air connection to SMMS-e
• System that connected to Outside Air Unit only can be used with only single Outdoor unit on one line of the multi system. The combination of indoor units is only available specified in following Table 2.
Correct
Height difference: 19.7" (0.5 m) or less
Incorrect
The combination of Indoor units
1. The capacity code of Indoor unit is decided for each capacity type.
emanledomtinuroodnI
pytyticapactinuroodnI
apactinuroodnI
ocytic
2. Combination of Indoor units is decided for Outdoor unit capacity type.
It allows only the combinations of Indoor units below.
Outdoor unit capacity type Outdoor unit capacity code
epyt270
7
441epyt441
861epyt861
Combination of Indoor unit capacity type
1
2702 69069epyt690
-021epyt021
-
-
-
Please refer to “Outside Air Unit’s Installation Manual” except the above contents.
690270840e
692784ed
Number of Indoor units
270
LU2FH1690PALU2FH1270PALU2FH1840PA-DMM
32
--
840+840
270+
70+690
-
-840+270 840+840+840
-840+690
02
840+840+27
8
MMD-AP___1HF2ULE15-3S2
Allowable length/height difference of refrigerant pipinJ&DVHRI$OO2XWVLGH$LU
CAUTION
Length and height of refrigerant piping keep the limitation blow.
If installed in out of the limitation, there is a possibility that heat-exchanger in Outdoor unit will burst and leak a refrigerant gas, for freezing heat-exchanger by shortage of defrosting capacity.
Allowable length and height difference of refrigerant piping
(*1): Farthest Indoor unit from the first branching section is the Indoor unit (c).
Please refer to “Outdoor Unit’s Installation Manual” except the above contents.
System restrictions Cautions for installation
 Y-shaped branching joint must be installed
horizontally.
Max. No. of combined Outdoor units 1 unit Max. capacity of combined Outdoor units 14 ton Max. No. of combined Indoor units 3 units Max. capacity of combined Indoor units Refer to “ The combination of Indoor units”
Allowable value
Pipes
mtf
Pipe length Total extension of pipe (Liquid pipe) Actual length c + b + a + 2L + 1L003489
Farthest piping length
L (*1)
Equivalent length 051294
L1 + c
Actual length 031724
Main piping length
Equivalent length
Max. 394
0LQ
Max. 120 (Min. )
L1
Actual length
Max. 328
(Min. 164)
Max. 100 (Min. 50)
Farthest equivalent piping length from the first branching section
Li
(*1)
Equivalent length c0389
Farthest equivalent piping length between Outdoor units
LO
Equivalent length
Maximum equivalent piping length of Outdoor unit connecting pipe
Equivalent length
Maximum actual length of pipes connected to Indoor units
Actual length c ,b ,a0389
Maximum equivalent length between branching sections
Equivalent length 2L0389
Height difference
Height between Outdoor and Indoor units
H1
Upper Outdoor units 04131
Lower Outdoor units 301
Height between Indoor units
H2
5.02
Height between Outdoor units
H3
Indoor unit
Outdoor unit
Unit (A)
Unit (b)
Branching header
Branching pipe
L2
Indoor unit connecting pipe
Indoor unit
Main
piping
L1
First branching
section
The longest piping length: L  492 ft (150 m)
The longest piping length from the first branch:
Li  98 ft (30 m)
Height difference between
Outdoor and Indoor units:
H1  131 ft (40 m)
Indoor unit connecting pipe
Height difference
between Indoor units:
H2  2 ft (0.5 m)
Unit (a)
b
H2
c
a
H1
Unit (c)
Indoor unit
Max. 100 (Min. 50)
Max. 120 (Min. 50)
Max. 394
(Min. 164)
Max. 328
(Min. 164)
9
Loading...
+ 19 hidden pages