(1) Outdoor unit connecting pipe
(2) Balance pipe
(3) Connecting pipe between outdoor units
(4) Outdoor unit connection piping kit
(5) Main pipe
(6) Branching pipe
(7) FS unit and indoor unit connection pipe
(8) Branching and indoor unit connection pipe
(9) Y-shaped branching joint
(10) Branching header
■ FS unit
*1: The capacity code of outdoor unit and indoor unit, please refer to 2-2.
*2: If the size of the pipe to be selected is larger than the size of the main pipe, please use the same pipe size as the main pipe.
*3: Two pipes in downstream of FS unit and cooling only indoor unit use liquid pipe and suction gas pipe.
*4: The first branching joint, select at capacity code of outdoor unit.
*5: If the total capacity code of indoor units exceed the capacity code of outdoor unit, select the size from the capacity code of the outdoor unit.
*6: For one line pipe line of header branching, total 57 capacity code of indoor units is connectable.
If connecting the branching header to the first branch section with the capacity code of outdoor unit is more than 114 (kBtu/h) and less than 247 (kBtu/h), use the
RBM-2043FUL (4 branch), and RBM-HT2083FUL (8 branch). Also, the branching header can not be used for the first branch section when the capacity code of outdoor
unit is more than 247 (kBtu/h).
*7: The main pipe is the starting point. The follower unit side is the downstream side.
*8: Selection piping is the starting point. The indoor unit side is the downstream side.
*9: Use indoor units with group control if connecting indoor units of two or more to one FS unit.
Outdoor unit capacity type
Suction
gas side
Discharge
gas side
Liquid side
072 type Ø7/8" Ø3/4" Ø1/2"
096 type Ø7/8" Ø3/4" Ø1/2"
120 type Ø1-1/8" Ø3/4" Ø1/2"
Capacity code of outdoor unit (*1) Balance pipe
144 to 336 type Ø3/8"
Total capacity of outdoor
units at downstream side (*1 *7)
Suction gas
side
Discharge
gas side
Liquid side
228 or more Ø1-3/8" Ø1-1/8" Ø3/4"
Total capacity of outdoor units
at downstream side (*1 *7)
Model name
Below 247 RBM-BT14FUL
247 or more RBM-BT24FUL
Capacity code of outdoor unit
Suction
gas side
Discharge
gas side
Liquid side
072, 096 Ø7/8" Ø3/4" Ø1/2"
120 Ø1-1/8" Ø3/4" Ø1/2"
144 Ø1-1/8" Ø7/8" Ø5/8"
168, 192 Ø1-1/8" Ø7/8" Ø3/4"
216, 240 Ø1-3/8" Ø1-1/8" Ø3/4"
288, 312, 336 Ø1-3/8" Ø1-1/8" Ø7/8"
Total cpacity code of indoor units
at downstream side (*1 *2 *3 *8)
Suction
gas side
Discharge
gas side
Liquid side
Below 61 Ø5/8" Ø1/2" Ø3/8"
61 to below 115.5 Ø7/8" Ø3/4" Ø1/2 "
115.5 to below 153.5 Ø1-1/8" Ø7/8" Ø5/8"
153.5 to below 191.5 Ø1-1/8" Ø7/8" Ø3/4"
191.5 to below 239 Ø1-3/8" Ø1-1/8" Ø3/4"
239 to below 334 Ø1-3/8" Ø1-1/8" Ø7/8"
334 or more Ø1-5/8" Ø1-3/8" Ø7/8"
Indoor unit capacity type Gas side Liquid side
007 to 012 type Ø3/8" Ø1/4"
015 to 018 type Ø1/2" Ø1/4"
021 to 054 type Ø5/8" Ø3/8"
072 to 096 type Ø7/8" Ø1/2"
Indoor unit capacity type Gas side Liquid side
007 to 012 type
Pipe length
(Actual length)
49 ft or less Ø3/8" Ø1/4"
Over 49 ft Ø1/2" Ø3/8"
015 to 018 type
Pipe length
(Actual length)
49 ft or less Ø1/2" Ø1/4"
Over 49 ft Ø5/8" Ø3/8"
021 to 054 type Ø5/8" Ø3/8"
072 to 096 type Ø7/8" Ø1/2"
Total capacity code of indoor units
on downstream side from
Y-shaped branching joint (*4 *5)
Model name
For 3 pipe For 2 pipe
Below 61 RBM-BY55FUL RBM-BY55UL
61 to below 134.5 RBM-BY105FUL RBM-BY105UL
134.5 to below 239 RBM-BY20 5FUL RBM-BY205UL
239 or more RBM-BY305FUL RBM-BY305UL
Total capacity code of indoor units
on downstream side from
branching header(*4 *5 *6)
Model name
For 3 pipe For 2 pipe
For 4 branching
Below 134.5 RBM -HY1043FUL RBM-HY1043UL
134.5 or more RBM-HY2043FUL RBM-HY204 3UL
For 8 branching
Below 134.5 RBM -HY1083FUL RBM-HY1083UL
134.5 or more RBM-HY2083FUL RBM-HY208 3UL
Total capacity code of outoor units
on downstream side from FS unit
Max. number of
connectable indoor units
Model name
Below 38 6 RBM-Y0383FUL
38 to below 61 8 RBM-Y0613FUL
61 to 96 or less 8 RBM-Y0963FUL