1.OUTLINE OF TOSHIBA SUPER HRM
(Super Heat Recovery Multi System)
Shortest route design by free branching
Combination of line and header branching is highly flexible.
This follows for the shortest design route possible, thereby saving
on installation time and cost. Line/header branching after
header branching is only available with TOSHIBA Super HRM.
Line branching
Outdoor unit
Branching joint
FS unit
Indoor unit
Header branching
Outdoor unit
Branching
header
FS unit
Indoor unit
Line + Header branching
Outdoor unit
Branching joint
Indoor
unit
Header
Line branching after header branching
Outdoor unit
8F
7F
2F
FS
unit
1F
Branching joint
Super HRM
MMS Only
Only
Indoor unit
Header
Header branching after header branching
Outdoor unit
Header
Super HRM
Only
Header
FS unit
Indoor unit
3
FS unit
Page 4
• Non-polarized control wiring
between outdoor and indoor units
8F
7F
Outdoor unit
Indoor unit
FS unit
Indoor
unit
Heating Cooling Cooling Cooling
• Simultaneous operation
U1 U2
U1 U2U1 U2U1 U2
main heat exchanger
Sub heat exchanger
Outdoor unit
Compressor
2F
1F
Allowable pipe length :
Outdoor
unit
Height difference between indoor
unit and indoor unit : 35m
Height difference between indoor
unit and outdoor unit : 50m
From 1st branching to the
farthest indoor unit : 50m
150m equivalent length
1st branching
section
4
Page 5
Energy saving
No. 1 COP in heat recovery VRF industry. Compared with the conventional chiller fan coil system,
a large energy saving can be realized.
Advanced bus communication system
Wiring between indoor and outdoor unit is a simple 2 wire system.
Communication address is also automatically configured.
A default test mode operation is available.
Self diagnostics system
Comprehensive troubleshooting code allows for timely identification of problems arising.
High lift and flexible piping design
Equivalent pipe length of 150m and vertical lift of 50m is made possible with TOSHIBA Super HRM.
Vertical lift between indoor units of 35m is the highest in the industry.
Also, maximum piping length from 1st branching is 50m.
These allow for greater flexibility in the location of the system.
Simultaneous operation
By controling the FS unit, Super HRM enables freely simultaneous operation of cooling and heating.
This operation meets the various needs of modern buildings that has highly airtight or an increasing
heat load due to use of computers. Also, Super HRM improves energy efficiency by recycling
exhaust heat.
Extended outdoor temperature operating range
By employing sophisticated system control with all inverter driven compressor, the operating range
in cooling has been extended from -5ºC to -10ºC.
Compact FS unit design
The compact and light weight design of the FS unit (Flow selector unit) allows it to be easily
installed in limited spaces.
Group control by one FS unit
Up to 8 indoor units of group control by one FS unit gives the design flexibility for various type and
size of rooms.
Intelligent control
TOSHIBA Super HRM intelligent controls and modulating valves deliver the required capacity,
according to the load variation from 50% to 100%.
The intelligent controls and modulating valves limit or increase the cooling capacity dynamically so
humidity and temperature are kept in the comfort zone.
Conforms to building control law
IAQ (Indoor Air Quality) is also achieved by combining various accessories required by the Building
Control Law.
Wide control applications
Artificial Intelligence Network system
• Central control and monitoring system available
• Weekly schedule operation through weekly timer
Integration with Building Management System (BMS) is available.
5
Page 6
2.SUMMARY OF SYSTEM EQUIPMENTS
Equipments
1. Outdoor units
Inverter unit
8HP10HP12HP
Model nameMMY-MAP0802FT8MAP1002FT8MAP1202FT8
Cooling capacity (kW)22.428.033.5
Heating capacity (kW)25.031.535.5
2. Outdoor units (Combination of outdoor units)
Corresponding HP
Combined model
Cooling capacity (kW)
Heating capacity (kW)
Combined outdoor units
No. of connectable indoor units
Corresponding HP
Combined model
Cooling capacity (kW)
Heating capacity (kW)
Combined outdoor units
No. of connectable indoor units
MMY-MAP0802FT8
MMY-AP2002FT8
8HP
22.4
25
8HP
13
20HP
56
63
10HP
10HP
33
10HP
MAP1002FT8
28
31.5
10HP
16
24HP
AP2402FT8
68
76.5
8HP
8HP
8HP
40
12HP
MAP1202FT8
33.5
35.5
12HP
16
26HP
AP2602FT8
73
81.5
10HP
8HP
8HP
43
AP1602FT8
AP2802FT8
3. FS units (Flow selector units)
Model nameUsage
RBM-Y1122FE
RBM-Y1802FE
RBM-Y2802FETotal capacity for indoor unit : 18.0 to 28.0 kw or less
Total capacity for indoor unit : Below 11.2 kw
Total capacity for indoor unit : 11.2 to below 18.0 kw
16HP
45
50
8HP
8HP
27
28HP
78.5
88
10HP
10HP
8HP
47
AppearanceCorresponding HP
AP1802FT8
AP3002FT8
Appearance
18HP
50.4
56.5
10HP
8HP
30
30HP
84
95
10HP
10HP
10HP
48
Accessory part (Sold separately): Connection cable kit (RBC-CBK15FE), up to 15m.
*
4. Branching joints and headers
Model nameAppearance
RBM-BY53FE
Y-shape
branching
joint (*3)
4-branching
header (*4) (*5)
8-branching
header (*4) (*5)
T-shape
branching
joint (For
connection
of outdoor
units)
1 “Capacity code” can be obtained from page 8. (Capacity code is not actual capacity)
*
2 If total capacity code value of indoor unit exceeds that of outdoor unit, apply capacity code of outdoor unit.
*
3 When using Y-shape branching joint for 1st branching, select according to capacity code of outdoor unit.
*
4 Max. 6.0 capacity code in total can be connected.
*
5 If capacity code of outdoor unit is 26 or more, it is not used for 1st branching.
*
6 This is used for branching to “cooling only” indoor unit.
*
7 Model names for outdoor and indoor units described in this guide are shortened because of the space constraint.
*
RBM-BY203FE
RBM-BY303FE
RBM-BY53E
RBM-BY103E
RBM-BY203E
RBM-BY303E
RBM-HY1043FE
RBM-HY2043FE
RBM-HY1043E
RBM-HY2043E
RBM-HY1083FE
RBM-HY2083FE
RBM-HY1083E
RBM-HY2083E
RBM-BT13FE
Indoor unit capacity code (*1) : Total below 6.4
Indoor unit capacity code (*1) : Total 6.4 or more and below 14.2RBM-BY103FE
Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2
Indoor unit capacity code (*1) : Total 25.2 or more
Indoor unit capacity code (*1) : Total below 6.4
Indoor unit capacity code (*1) : Total 6.4 or more and below 14.2
Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2
Indoor unit capacity code (*1) : Total 25.2 or more
Indoor unit capacity code (*1) : Total below 14.2
Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2
Indoor unit capacity code (*1) : Total below 14.2
Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2
Indoor unit capacity code (*1) : Total below 14.2
Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2
Indoor unit capacity code (*1) : Total below 14.2
Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2
1 set 4 types T-shape joint pipes as described below:
The required quantity is arranged and they are combined on site.
Connection pipingCorresponded dia. (mm) Q'ty
Balance pipe
Piping at liquid side
Piping at discharge gas side
Piping at suction gas side
Usage
Ø 9.51
Ø12.7 to Ø22.2
Ø19.1 to Ø28.6
Ø22.2 to Ø38.1
6
For 3
piping
For 2
piping (*6)
For 3
piping
For 2
piping (*6)
For 3
piping
For 2
piping (*6)
1
1
1
Page 7
Super Heat Recovery Multi System Outdoor Unit
50Hz
HP (Capacity
code)
8HP ( 8) MAP0802HT8 1 MAP0802FT8 1
10HP (10) MAP1002HT8 1 MAP1002FT8 1
12HP (12) MAP1202HT8 1 MAP1202FT8* 1
16HP (16) 2 MAP0802FT8 2
18HP (18) 2 MAP0802FT8 1 MAP1002FT8 1
20HP (20) 2 MAP1002FT8 2
24HP (24) MAP0802FT8 3
26HP (26) MAP0802FT8 2 MAP1002FT8 1
28HP (28) MAP0802FT8 1 MAP1002FT8 2
30HP (30) MAP1002FT8 3
*
Model name
MMY-
12HP unit is for stand-alone usage only.
Outdoor unit combination with 12HP unit is not available.
No. of
combined
units
Inverter
8 HP
MMY-
Used
Q'ty
Inverter
10 HP
MMY-
Used
Q'ty
Inverter
12 HP
MMY-
Used
Q'ty
1. Allocation standard of model name
MMY– MAPT8
F
Power supply specifications, 3Ø 380–415 V, 50Hz ....... 8
T : Capacity variable unit
F : Heat recovery
Development series No.
Capacity rank HP x 10
New refrigerant R410A
M : Single module unit, No mark : Combined Model name
Modular Multi
2. Rated conditions (Rated mode : Condition)
Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
3. Compatibility with 1 Series
Oudoor unit MMY-
1 Series
FS unit
RBM-Y***1E
2 Series
RBM-Y***2E
2 series outdoor units cannot be used with 1 series outdoor units.
*
1 Series 2 Series*
-MAP**1FT8 -MAP**2FT8
OK NG
OK OK
7
Page 8
4. Indoor unit
*1) China only *2) European market only
Type Appearance Model name Capacity rank Capacity code
MMU-AP0091H 009 type 1 2.8 3.2
MMU-AP0121H 012 type 1.25 3.6 4.0
MMU-AP0151H 015 type 1.7 4.5 5.0
MMU-AP0181H 018 type 2 5.6 6.3
MMU-AP0241H 024 type 2.5 7.1 8.0
MMU-AP0271H 027 type 3 8.0 9.0
MMU-AP0301H 030 type 3.2 9.0 10.0
MMU-AP0361H 036 type 4 11.2 12.5
MMU-AP0481H 048 type 5 14.0 16.0
MMU-AP0561H 056 type 6 16.0
MMU-AP0071WH 007 type 0.8 2.2 2.5
MMU-AP0091WH 009 type 1 2.8 3.2
MMU-AP0121WH 012 type 1.25 3.6 4.0
MMU-AP0151WH 015 type 1.7 4.5 5.0
MMU-AP0181WH 018 type 2 5.6 6.3
MMU-AP0241WH 024 type 2.5 7.1 8.0
MMU-AP0271WH 027 type 3 8.0 9.0
MMU-AP0301WH 030 type 3.2 9.0 10.0
MMU-AP0481WH*
MMU-AP0071YH 007 type 0.8 2.2 2.5
MMU-AP0091YH 009 type 1 2.8 3.2
MMU-AP0121YH 012 type 1.25 3.6 4.0
MMU-AP0151SH 015 type 1.7 4.5 5.0
MMU-AP0181SH 018 type 2 5.6 6.3
MMU-AP0241SH 024 type 2.5 7.1
MMD-AP0071BH 007 type 0.8 2.2 2.5
MMD-AP0091BH 009 type 1 2.8 3.2
MMD-AP0121BH 012 type 1.25 3.6 4.0
MMD-AP0151BH 015 type 1.7 4.5 5.0
MMD-AP0181BH 018 type 2 5.6 6.3
MMD-AP0241BH 024 type 2.5 7.1 8.0
MMD-AP0271BH 027 type 3 8.0 9.0
MMD-AP0301BH 030 type 3.2 9.0 10.0
MMD-AP0361BH 036 type 4 11.2 12.5
MMD-AP0481BH 048 type 5 14.0 16.0
MMD-AP0561BH 056 type 6 16.0
MMD-AP0181H 018 type 2 5.6 6.3
MMD-AP0241H 024 type 2.5 7.1 8.0
MMD-AP0271H 027 type 3 8.0 9.0
MMD-AP0361H 036 type 4 11.2 12.5
MMD-AP0481H 048 type 5 14.0 16.0
MMD-AP0721H 072 type 8 22.4 25.0
MMD-AP0961H 096 type 10 28.0
MMC-AP0151H 015 type 1.7 4.5 5.0
MMC-AP0181H 018 type 2 5.6 6.3
MMC-AP0241H 024 type 2.5 7.1 8.0
MMC-AP0271H 027 type 3 8.0 9.0
MMC-AP0361H 036 type 4 11.2 12.5
MMC-AP0481H 048 type 5 14.0
MMK-AP0071H 007 type 0.8 2.2 2.5
MMK-AP0091H 009 type 1 2.8 3.2
MMK-AP0121H 012 type 1.25 3.6 4.0
MMK-AP0151H 015 type 1.7 4.5 5.0
MMK-AP0181H 018 type 2 5.6 6.3
MMK-AP0241H 024 type 2.5 7.1
MMK-AP0072H 007 type 0.8 2.2 2.5
MMK-AP0092H 009 type 1.0 2.8 3.2
MMK-AP0122H 012 type 1.25 3.6
MML-AP0071H 007 type 0.8 2.2 2.5
MML-AP0091H 009 type 1 2.8 3.2
MML-AP0121H 012 type 1.25 3.6 4.0
MML-AP0151H 015 type 1.7 4.5 5.0
MML-AP0181H 018 type 2 5.6 6.3
MML-AP0241H 024 type 2.5 7.1
MML-AP0071BH 007 type 0.8 2.2 2.5
MML-AP0091BH 009 type 1 2.8 3.2
MML-AP0121BH 012 type 1.25 3.6 4.0
MML-AP0151BH 015 type 1.7 4.5 5.0
MML-AP0181BH 018 type 2 5.6 6.3
MML-AP0241BH 024 type 2.5 7.1
MMF-AP0151H 015 type 1.7 4.5 5.0
MMF-AP0181H 018 type 2 5.6 6.3
MMF-AP0241H 024 type 2.5 7.1 8.0
MMF-AP0271H 027 type 3 8.0 9.0
MMF-AP0361H 036 type 4 11.2 12.5
MMF-AP0481H 048 type 5 14.0 16.0
MMF-AP0561H 056 type 6 16.0
1)
048 type 5 14.0 16.0
4-way Air Discharge
Cassette Type
2-way Air Discharge
Cassette Type
1-way Air Discharge
Cassette Type
Concealed Duct
Standard Type
Concealed Duct
High Static
Pressure Type
Under Ceiling Type
High Wall Type
(1 Series)
High Wall Type
(2 Series)
Floor Standing
Cabinet Type
Floor Standing
Concealed Type
Floor Standing Type
*2)
Cooling
capacity (kW)
8
Heating
capacity (kW)
18.0
8.0
18.0
31.5
16.0
8.0
4.0
8.0
8.0
18.0
Page 9
5. Remote controller
Name
Wired remote controller
Model
name
RBC-AMT21E
AppearanceApplication
Connected to indoor unit
UNIT No.
R.C. No.
UNIT
CODE No.
Wired remote
controller
Wired remote controller
(In case of control by
2 remote controllers)
SET DATA
SETTING
TEST
CL
SET
Connected to indoor unit
TEST
SETTING
˚C
˚F
Function
• Start / Stop
• Changing mode
• Temperature setting
• Air flow changing
• Timer function
Either “ON” time or “OFF” time or “CY-
CLIC” can be set how many 30 min. later
ON or OFF is operated.
Combined with the weekly timer, weekly
schedule operation can be operated.
• Filter sign
Displays automatically maintenance time of
indoor filter.
Filter sign flashes.
• Self-diagnosis function
Pressing “CHECK” button displays cause of
trouble on the check code.
• Control by 2 remote controllers is available.
Two remote controllers can be connected to
one indoor unit. The indoor unit can be
separately operated from the isolated places.
• Start / Stop
• Temperature setting
• Air flow changing
• Check code display
Simple remote controller
Wireless remote controller kit
RBC-AS21E
Simple remote controller
Connected to indoor unit
• Start / Stop
• Changing mode
• Temperature setting
• Air flow changing
• Timer function
Either “ON” time or “OFF” time or “CYCLIC”
can be set how many 30 min. later ON or OFF
is operated.
• Control by 2 remote controllers is available.
Two wireless remote controllers can operate
one indoor unit. The indoor unit can be
separately operated from the isolated places.
• Check code display
TCB-AX21U (W)-E
(For 4-way air discharge cassette)
RBC-AX22CE
(For under ceiling)
TCB-AX21E
(For others except concealed duct high static
pressure)
TCB-AX21ERBC-AX22CETCB-AX21U (W)-E
9
Page 10
Name
Model
name
AppearanceApplication
Performance
Weekly timer
RBC-EXW21E
PROGRAM1
PROGRAM2
PROGRAM3
WEEKLY TIMER
SuMoTuWeTh Fr Sa
ERROR
Connected to central
remote controller,
wired remote controller
Wired
remote controller
Outdoor unit
Central
remote controller
Weekly
timer
Weekly
timer
• Weekly schedule operation
Setting different start / stop time for
each day of the week
ON / OFF can be easily set 3 times
a day.
ON
8:0012:00 13:00 18:00 19:00 21:00
“CHECK” “PROGRAM” “DAY”
OFF ONOFF ONOFF
button make setting copy easy.
Two patterns of schedule for a
week can be specified.
(Summer schedule and winter
schedule, etc.)
“CANCEL” “DAY” button make
holiday setting easy.
If power supply fails, the setting
contents are stored in memory, for
100 hours.
TCB-SC642TLE
Central remote controller
ZONE
ALL
ZONE
GROUP
1234
UNIT No.
SET DATA
SETTING
R.C.
No.
SELECTZONE
CL
SET
Connected to outdoor unit,
indoor unit
Outdoor
unit
• Individual control for max. 64 indoor
units divided 1 to 4 zone.
Up to 16 indoor units for each
zone
• Up to 16 outdoor header units are
connectable.
• 4 type central control setting to inhibit
individual operation by remote
controller can be selected.
• Individual control up to 64 indoor units.
CODE
TEST
No.
• Setting for one of 1 to 4 zone is
available.
• Usable with other central control
devices (Up to 10 central control
GROUP
Central
remote controller
devices in one control circuit)
• Two control mode selectivity
Central controller mode
Remote controller mode
• Setting of simultaneous ON/OFF 3
times for each day of the week
combined with weekly timer.
Central
remote
controller
Indoor
remote controller
10
Page 11
3.BASIC SYSTEM CONFIGURATION
8HP system
• Max. indoor unit : 13 units
• Capacity code of indoor unit :Min. : 5.6
Outdoor unit
8HP
10.4
4.8
007
(0.8)
Max. : 10.8
4.03.22.41.6
007
(0.8)
Capacity code
over the branch
(0.8 + 0.8 = 1.6)
007
(0.8)
007
(0.8)
007
(0.8)
Capacity code
Total 10.4
No. of total units
13
Indoor unit
designation
Capacity
code
007
(0.8)
FS unit
Indoor unit
Remote
controller
5.64.84.03.22.41.60.8
007
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
11
Page 12
10 HP system
• Max. indoor unit : 16 units
• Capacity code of indoor unit :Min. : 7
Outdoor unit
10HP
Max. : 13.5
Capacity code
Total 12.8
No. of total units
16
12.8
FS unit
Indoor unit
Remote
controller
6.4
007
5.64.84.03.22.41.6
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
007
6.45.64.84.03.22.41.6
007
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
(0.8)
007
(0.8)
007
(0.8)
12
Page 13
12 HP system
• Max. indoor unit : 16 units
• Capacity code of indoor unit :Min. : 8.4
Outdoor unit
12HP
Max. : 14.4
Capacity code
Total 14.0
No. of total units
16
14.0
FS unit
Indoor unit
Remote
controller
6.4
007
5.64.84.03.22.41.6
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
007
7.66.86.05.04.03.02.0
007
(0.8)
007
(0.8)
009
(1.0)
009
(1.0)
009
(1.0)
009
(1.0)
009
(0.8)
(1.0)
007
(0.8)
009
(1.0)
13
Page 14
20 HP system
• Max. indoor unit : 33 units
10
10HP10HP
Max. : 27
• Capacity code of indoor unit :Min. : 14
Outdoor unit
Capacity code
Total 26.75
No. of total units
19
26.75
16.5
FS unit
Indoor unit
Remote
controller
10.258.25
018
(2.0)
6.255.03.752.5
018
(2.0)
012
(1.25)
012
(1.25)
8.256.255.03.752.5
018
(2.0)
012
(1.25)
012
(1.25)
012
(1.25)
8.256.255.03.752.5
018
(2.0)
012
(1.25)
012
(1.25)
012
(1.25)
012
(1.25)
012
(1.25)
012
(1.25)
012
(1.25)
012
(1.25)
012
(1.25)
012
(1.25)
14
Page 15
30 HP system
• Max. indoor unit : 48 units
10HP 10HP10HP
Max. : 40.5
1020
• Capacity code of indoor unit :Min. : 21
Outdoor unit
Capacity code
Total 40
No. of total units
28
40
30
20
FS unit
109.28.47.66.86
007
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
018
109.28.47.66.86
007
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
018
109.28.47.66.86
007
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
007
(0.8)
018
109.28.47.66.86
(2)
(2)
(2)
036
(4)
036
(4)
036
(4)
Indoor unit
Remote
controller
007
(0.8)
007
(0.8)
007
(0.8)
15
007
(0.8)
007
(0.8)
018
(2)
036
(4)
Page 16
4.EQUIPMENT SELECTION PROCEDURE
1. Selection flow chart
1. Determination of indoor air conditioning load
2. Preliminary selection of indoor units
3. Preliminary selection of outdoor unit with indoor units
4. Capacity correction for piping length/height between indoor and outdoor units
5. Capacity correction based on indoor and outdoor temperature
6. Validate preliminary selection of indoor units
7. Confirmation of selection for indoor unit and outdoor units
NO
End
2. Combination conditions for indoor unit and outdoor unit
1. For indoor unit, the capacity code is decided for each capacity rank.
Capacity rank type
Capacity code
NOTE :
Capacity rank : Correspondence to Btu/h. Capacity code : Correspondence to Horsepower.
2. For outdoor unit, maximum No. of connectable indoor units and total capacity code of indoor units are decided.
Outdoor unit
(Heat recovery)
MMY-MAP0802FT8 8 13 5.6 to 10.8
MMY-MAP1002FT8 10 16 7.0 to 13.5
MMY-MAP1202FT8 12 16 8.4 to 14.4
MMY-AP1602FT8 16 27 11.2 to 21.6
MMY-AP1802FT8 18 30 12.6 to 24.3
MMY-AP2002FT8 20 33 14.0 to 27.0
MMY-AP2402FT8 24 40 16.8 to 32.4
MMY-AP2602FT8 26 43 18.2 to 35.1
MMY-AP2802FT8 28 47 19.6 to 37.8
MMY-AP3002FT8 30 48 21.0 to 40.5
007
0091012
0.8
70 to 135% of outdoor unit capacity for all systems except 12HP
70 to 120% of outdoor unit capacity for 12HP
Indoor air dry bulb temperature vs. capacity correction value
1.2
1.1
1.0
0.9
0.8
152024
Capacity correction value
Indoor air dry bulb temp. (˚C)
Outdoor air wet bulb temperature vs. capacity correction value
,
,
,
,
*1,
*2) kW
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
–15–10–5051015
Capacity correction value
Outdoor air wet bulb temp. (˚C)
Air flow variation ratio of indoor unit vs. capacity correction (For concealed duct type only)
1.1
1.0
0.9
8090100110120
Capacity correction value
1 : Coefficient to use for correction of outdoor unit capacity when total capacity of the indoor
*
units are not equal to the outdoor unit capacity.
2 : Refer to item 3 in page 20.
*
Air flow variation ratio (%)
19
Page 20
Connecting pipe length and lift difference between indoor and outdoor units vs. capacity correction value
Outdoor unit (8 to 30HP)
50
40
30
20
10
100%
0
–10
–20
–30
Height of outdoor unit H (m)
1002030405060708090
Pipe length (Equivalent length) L (m)
Correction of outdoor unit diversity
99
98
97
96
120
100
93
94
95
100 110 120 130 140 150
80
92
91
hol’o
hb
hc
Outdoor unit
L’ is the longest one of
(l’o + l’a, l’o + l’b, l’o + l’c)
H = ho +
(Largest one of ha, hb, and hc)
ha
l’a
A
l’b
B
Indoor unit
l’c
C
60
40
Correction (%)
20
0
20406080100120 135
Standard capacity ratio
Indoor units total capacity ratio (%)
1 : Coefficient to use for correction of outdoor unit capacity when total capacity of the indoor
*
units are not equal to the outdoor unit capacity.
3. Capacity correction in case of frost on the outdoor heat exchanger in heating
Correct the heating capacity when frost was found on the outdoor heat exchanger.
Heating capacity = Capacity after correction of outdoor unit × Correction value of capacity resulted from frost
(Capacity after correction of outdoor unit : Heating capacity calculated in the above item 2.)
6 Capacity correction in case of frost on the outdoor heat exchanger
1.0
0.9
0.8
Capacity correction value
–15–10–50510
Outdoor air wet bulb temp. (˚C)
20
Page 21
4. Capacity calculation for each indoor unit
Capacity for each indoor unit
= Capacity after correction of outdoor unit ×
5. Operating temperature range
Required standard capacity of indoor unit
Total value of standard indoor unit capacity
45
40
35
30
25
20
15
10
Outdoor air dry bulb temp. (˚C)
–5
–10
In cooling time
Continuously
operable
range
5
0
Indoor air wet bulb temp. (˚C)
Usable range
(in pull down)
Outdoor air wet bulb temp. (˚C)
302528201510
In heating time
20
15
10
5
Usable range
(in warming-up)
Continuously
operable
range
0
–5
–10
–15
–20
5 1015202530
Indoor air dry bulb temp. (˚C)
* The unit can be operated even if outdoor temperature gets down to -20°C, however note that the war-
ranty covers only up to -15°C because operation beyond that temperature is out of specification.
* When outdoor air temperature falls to under -15°C, it may cause shortening the product lifetime.
* When outdoor temperature goes out of specified range “ or ” mark is indicated on the remote control-
ler display and required operation will stop.
“ & ”: When heating operation
“ ”: When cooling operation
[Notice]
• This indication is not failure.
• When outdoor temperature goes back to specified range, “ or ” disappear and start normal operation.
• Operation stops because concurrent operation can not be kept in the condition of out of specification
for Super HRM.
(Outdoor temp.(DB)<-10°C: Cooling,
>21°C: Heating)
* Do not use “Super HRM” for other than personal usage where the ambient temperature may go down
below -10°C. (For example, OA equipment/Electric device/Food/Animals and plants/Art object)
6. Rated conditions
Cooling :
Indoor air temperature 27°C DB/19.0°C WB, Outdoor air temperature 35°C DB
Heating :
Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
21
Page 22
2 – 12 – 22 – 3
1
–
1
1
–
3
1
–
2
1
–
4
2
–
42 – 5
Office rooms
(2–1, 2–2 : Computer room)
Stores
(1-4 : Kitchen)
1F
2F
Non-air conditioning zone
4. Example of equipment selection
The following shows an example of equipment selection based upon a building model
Fig. 1 Overview of building model
<Outside view><Stories configuration>
8m
2F
1F
7.2m
14.4m
• Steel frame, reinforced concrete building, four stories
above ground. Total floor area : 207m²
2F : Outdoor capacity exactly matches the total indoor capacity.
Total indoor HP = Outdoor unit HP Indoor : 2.5 HP x 2 units + 1.25 HP + 2 HP x 2 = 10.25 HP
Outdoor : 10 HP Same capacity
Heat load of room 2-1 and 2-2 is higher than other rooms.
1F : Consider the increasing heat load in the specific room.
• Total indoor units HP > Outdoor unit HP
• Select each indoor unit based on individual peak room load.
Indoor : 2.5HP + 2.5HP + 3.2HP + 2.0HP =
10.2HP <> Outdoor : 10HP (Same capacity)
• The room “1-4” is designed for “cooling only” because of its high heat load.
• The outdoor module should have sufficient capacity to cover the peak demand of the indoor unit
connected.
22
Page 23
Procedure and result of equipment selection
1. Procedure of equipment selection
a. Calculate cooling for every rooms.
b. Select an indoor unit to match the cooling load for every room from the table in pages 8.
c. Choose a tentative outdoor module that will match with the indoor units. Perform capacity correction
based on the pipe length, system lift, indoor set temperature, outdoor temperature.
Then, make sure the corrected system cooling capacity satisfies the cooling load.
2. Equipment selection and capacity check
Air conditioning load Equipment selection
Indoor unit Outdoor unit
Capacity (kW) Capacity (kW)
Cooling Heating
Model
MMY-
Cooling Heating
Floor Room No.
2-1 6.0 3.4 MMU-AP0241H 7.1 8.0
2-2 5.0 2.2 MMU-AP0181H 5.6 6.3
Indoor air conditioning load
(kW)
Cooling Heating
Model
2F
1F
Floor Room No.
2F
1F
2-3 5.0 4.2 MMU-AP0181H 5.6 6.3
2-4 3.2 2.7 MMU-AP0121H 3.6 4.0
2-5 6.4 5.4 MMU-AP0241H 7.1 8.0
1-1 6.1 6.0 MMU-AP0241H 7.1 8.0
1-2 6.3 6.3 MMU-AP0241H 7.1 8.0
1-3 7.2 7.0 MMU-AP0301H 9.0 10.0
1-4 5.1 — MMD-AP0181H 5.6 6.3
Piping distance Capacity correction Capacity check after correction
2-1 6.6
2-2 5.2 5.5
2-3 5.2
2-4 3.3 3.5
2-5 6.6
1-1 6.6
1-2 6.6
1-3 8.4 8.8
Equivalent
length (m)
34 5
Height
difference
(m)
MAP2002FT8 56.0 63.0
Pipe correction x temp.
correction
Cooling Heating Cooling Heating
1.0
1.0
×
1.0
×
0.936
=
0.936
×
0.95
×
0.98
×
0.95
=
0.884
Capacity
Capacity (kW)
7.0
5.5
7.0
7.0
7.0
Judgment
good
1-4
5.2 5.5
23
Page 24
Schematic diagram
MMY-MAP2002FT8
1010
Outdoor unit
1st branching joint
2nd branching
joint
3rd branching
joint
4th branching
joint
5th branching
joint
FS unit
RBM-Y1122FE
Indoor unit
MMU-AP0241H
MMU-AP0181H
RRRRR
1
FS unit
RBM-Y1122FE
Computer
Room
Computer
Room
2
–
Indoor unit
MMU-AP0241H
R
StoreStore
1 – 11
FS unit
RBM-Y1122FE
Indoor unit
2 – 22
Indoor unit
MMU-AP0241H
FS unit
RBM-Y1122FE
Indoor unit
MMU-AP0181H
OfficeOfficeOffice
–
32
FS unit
RBM-Y1122FE
R
–
21
FS unit
RBM-Y1122FE
Indoor unit
MMU-AP0121H
–
Branching header
FS unit
RBM-Y1122FE
Indoor unit
MMU-AP0301H
R
Restaurant
FS unit
RBM-Y1122FE
Indoor unit
MMU-AP0241H
42
–
5
Indoor unit
MMD-AP0181H
R
<Cooling only>
Kitchen
–
31
–
4
24
Page 25
5.REFRIGERANT PIPING DESIGN
1. Warnings on refrigerant leakageImportant
Check of Concentration Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed
a set limit.
The refrigerant R410A which is used in the air conditioner
is safe, without the toxicity or combustibility of ammonia,
and is not restricted by laws to be imposed which protect
the ozone layer. However, since it contains more than air,
it poses the risk of suffocation if its concentration should
rise excessively. Suffocation from leakage of R410A is
almost non-existent. With the recent increase in the
number of high concentration buildings, however, the
installation of multi air conditioner systems is on the
increase because of the need for effective use of floor
space, individual control, energy conservation by curtailing heat and carrying power etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared with
conventional individual air conditioners. If a single unit of
the multi conditioner system is to be installed in a small
room, select a suitable model and installation procedure
so that if the refrigerant accidentally leaks out, its
concentration does not reach the limit (and in the event of
an emergency, measures can be made before injury can
occur).
In a room where the concentration may exceed the limit,
create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection
device.
The concentration is as given below.
NOTE 2 :
The standards for minimum room volume are as follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the adjacent
room for ventilation of leaking refrigerant gas
(opening without a door, or an opening 0.15% or
larger than the respective floor spaces at the top or
bottom of the door).
Outdoor unit
Refrigerant piping
Indoor unit
(3) If an indoor unit is installed in each partitioned room
and the refrigerant tubing is interconnected, the
smallest room of course becomes the object. But
when a mechanical ventilation is installed interlocked
with a gas leakage detector in the smallest room
where the density limit is exceeded, the volume of the
next smallest room becomes the object.
Refrigerant piping
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m³)
≤
Concentration limit (kg/m³)
The concentration limit of R410A which is used in multi
air conditioners is 0.3kg/m³.
(For details, refer and comply with local regulations.)
NOTE 1 :
If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should be
as charged in each independent device.
e.g., charged
amount (10kg)
Room A Room B Room C Room D Room E Room F
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms
A, B and C is 10kg.
The possible amount of leaked refrigerant gas in rooms
D, E and F is 15kg.
Outdoor unit
e.g.,
charged amount (15kg)
Indoor unit
Outdoor unit
Ver y
small
room
Small
room
Mechanical ventilation device - Gas leak detector
Medium
room
Large room
Indoor unit
NOTE 3 :
The minimum indoor floor area compared with the
amount of refrigerant is roughly as follows:
(When the ceiling is 2.7m high)
40
Range below the
35
m²
density limit
of 0.3 kg/m³
30
(countermeasures
not needed)
25
20
15
10
5
Min. indoor floor area
0
102030
Total amount of refrigerant
Range above
the density limit
of 0.3 kg/m³
(countermeasures
needed)
kg
25
Page 26
2. Free branching system
Line branching system
Header branching system
Header branching system after line branching
Line branching system after header branching
Header branching system after header branching
The above five branching systems are available to dramatically increase the flexibility of refrigerant piping design.
Outdoor unit
Branching joint
Line
branching
system
FS unit
Indoor unit
Remote
controller
Outdoor unit
Header
branching
system
Header
branching
system
after line
branching
Line
branching
system after
header
branching
Indoor unit
Outdoor unit
FS unit
Indoor unit
Outdoor unit
FS unit
Branching joint
Remote
controller
Branching header
Remote controller
Branching header
Branching header
Header
branching
system after
header
branching
FS unit
Indoor
unit
Remote
controller
Branching
joint
26
Page 27
g
3. Allowable length/height difference of refrigerant piping
Height
difference
between
outdoor
units
H3 5m
Height
difference
between
outdoor
and indoor
units
H1 50m
Outdoor Unit
T-shape
branching
Main piping
L1
1st branching
section
Follower Unit
C
Header Unit
Branching piping
Connecting piping of
indoor unit
L3
Equivalent length corresponded to farthest piping after 1st branching Li 50m
FS unit
Follower Unit
A
a
ghi j
Indoor unit
Equivalent length corresponded to farthest piping L 150m
L4L5L6 L7LhL8
def
lmn
Indoor unit
B
LaLbLc
LA
Main connecting piping between outdoor units
Length corresponded to farthest piping
between outdoor units LO 25m
Branching
header
L2
L9
bc
FS unit
< Cooling only >
FS unit
k
o
(Header)
< Cooling only >
Lj
pq
Note:
In case of connecting method <Ex.2>, a large
amount of refrigerant and refrigerant oil may
return to the head unit. Therefore, set the T-shape
joint so that oil does not enter directly.
<Ex.1>
Header UnitAFollower UnitBFollower Unit
<Ex.2>
Header UnitAFollower UnitBFollower Unit
Height difference
between
indoor
units
H2 35m
(Upper outdoor unit)
(q)
C
C
Height difference
between indoor units
in group control by
one FS unit
H4 0.5 m
* Allowable length and height difference of refrigerant piping
Allowable value Piping section
Total extension of pipe (Liquid pipe, real length) 300 m
Ø 6.4 007 to 012 Type
Ø 6.4 015 to 018 Type
Ø 9.5 024 to 056 Type
Ø 12.7
Ø 6.4 15m or less
Ø 9.5 15m above
Ø 6.4 15m or less
Ø 9.5 15m above
Ø 9.5
Ø 12.7
* Selection for branching section
No.
Y-Shape branching joint
*4 *5
Branching
Header
*4, *5, *6
T-Shape branching joint
(For connecting outdoor
unit)
For
4 Branchin
For
8 Branchin
40.0 to below 70.5 14.2 to below 25.2 RBM-HY2043FE RBM-HY2043E
40.0 to below 70.5 14.2 to below 25.2 RBM-HY2083FE RBM-HY2083E
1 set of 4 types of T-shape joint pipes as described below : The rewired
quantity is arranged and combined at the site.
- Balance pipe (Ø 9.52) X 1
- Piping at liquid side (Ø 12.7 to Ø 22.2) X 1
- Piping at discharge gas side (Ø 19.1 to Ø 28.6) X 1
- Piping at suction gas side (Ø 22.2 to Ø 38.1) X 1
Total capacity code of indoor unit Model Name
Equivalent to capacity Equivalent to HP For 3 piping For 2 piping
Below 18.0 Below 6.4 RBM-BY53FE RBM -BY53E
18.0 to below 40.0 6.4 to below 14.2 RBM-BY103FE RBM-BY103E
40.0 to below 70.5 14.2 to below 25.2 RBM-BY203FE RBM-BY203E
70.5 or more 25.2 or more RBM-BY303FE RBM-BY303E
Below 40.0 Below 14.2 RBM-HY1043FE RBM-HY1043E
Below 40.0 Below 14.2 RBM-HY1083FE RBM-HY1083E
1st branching section
Liquid pipe
4
Discharge gas pipe
Suction gas pipe
8
4
Liquid pipe
Discharge gas pipe
Suction gas pipe
—
Balance
pipe
Total capacity code of all outdoor units
MM
Total capacity code of indoor units at
Equivalent to
capacity
Equivalent to
capacity
-MAP1202FT8
downstream side
—
73.0 or more 26 or more
Total capacity code of all indoor units
Equivalent to
capacity
—
70.5 or more 25.2 or more
—
18.0 or more 6.4 or more
—
072 to 096 T
—
— 072 to 096 T
024 to 056 T
555
10
FS unit
6
8
8
4
5
10
FS unit
6
Indoor unit
Equival ent to HP
Equival ent to HP
Equival ent to HP
e
007 to 012 Type
015 to 018 Type
e
e
Y-Shape branching joint
8
4
Y-Shape branching joint
8
66
8
4
5 5
6 6 6 6 6
77
< Cooling only >
4
4 4
Group control
< Cooling only >
Selection of FS unit
Total capacity code of
Model Name
RBM-Y1122FE Below 11.2 Below 4.0 5
RBM-Y1802FE
RBM-Y2802FE
* Minimum wall
thickness for R410A
application
Half
Outer
Hard
Soft
OK OK 1/4” 6.35 0.80
OK OK 3/8” 9.52 0.80
OK OK 1/2” 12.70 0.80
OK OK 5/8” 15.88 1.00
NG OK 3/4” 19.05 1.00
NG OK 7/8” 22.20 1.00
NG OK 1.1/8” 28.58 1.00
NG OK 1.3/8” 34.92 1.10
*1 In case the pipe exceeds main pipe size, it
*2 2 pipes for cooling only indoor unit shall be
*3 2 pipes from FS unit to branching section shall
*4 Branching pipe on the 1st branch should be
*5 In case total capacity code for indoor units shall
*6 For 1 line after header branching, indoor units
RBM-BT13FE
dia.
or
(Inch)
Hard
should be the same as main pipe size.
used with liquid pipe and suction gas pipe.
be used with liquid pipe and suction gas pipe.
selected according to the capacity code for
outdoor unit.
be exceeded to capacity code for outdoor unit,
the pipe size should be selected with capacity
code for outdoor unit.
with a maximum of 6.0 capacity code in total
can be connected.
indoor unit
Equivalent to
capacity (kW)
11.2 to below
18.0
18.0 to 28.0
or less
Outer
dia.
(mm)
Minimum
Thickness
Equivalent
to HP
4.0 to below
6.4
6.4 to 10.0
or less
Wall
(mm)
Max.No. of
connected
indoor
units
8
8
28
Page 29
5. Charging requirement with additional refrigerant
After the system has been vacuumed, replace the vacuum pump with a refrigerant cylinder and charge the
system with additional refrigerant.
Calculating the amount of additional refrigerant required
Refrigerant in the system when shipped from the factory
R410A
8HP10HP12HP
Refrigerant amount charged in factory
11.5kg11.5kg11.5kgHeat recovery model
When the system is charged with refrigerant at the factory, the amount of refrigerant needed for the pipes at the
site is not included. Calculate the additional amount needed, and add that amount to the system.
(Calculation)
Additional refrigerant charge amount is calculated from size of liquid pipe at site and its real length.
[Additional refrigerant charge amount at site] =
[Real length of liquid pipe] ×
Additional refrigerant charge amount
per liquid pipe 1m (Table 1)system HP (Table 2)
× 1.3
+Compensation by
Example : Additional charge amount R (kg) = {(L1 x 0.025kg/m) + (L2 x 0.055kg/m) + (L3 x 0.105kg/m)
+ (L4 x 0.160kg/m) + (L5 x 0.250kg/m)} x 1.3
L1 : Real total length of liquid pipe Ø6.4 (m)
L2 : Real total length of liquid pipe Ø9.5 (m)
L3 : Real total length of liquid pipe Ø12.7 (m)
L4 : Real total length of liquid pipe Ø15.9 (m)
L5 : Real total length of liquid pipe Ø19.1 (m)
System : 24HP
Table 1
Pipe dia. at liquid side
Additional refrigerant amount/1m
Table 2
Combined
horse power
(HP)
882.0
10102.5
12123.0
1688-1.5
181080.0
2010102.0
24888-4.5
261088-3.0
2810108-1.5
301010100.0
Outdoor
combination (HP)
Ø6.4Ø9.5Ø12.7Ø15.9Ø19.1Ø22.2
0.025kg0.055kg0.105kg0.160kg0.250kg0.350kg
Compensation
by system HP
(kg)
29
Page 30
6.WIRING DESIGN
1. General
(1) Perform wiring of the power supply in conformance with the regulations of the local electric company.
(2) For the control wires connecting indoor units, and between indoor and outdoor units, use of double-core shield
wires is recommended to prevent noise trouble.
(3) Be sure to set the earth leakage breaker and the switches to the power supply section of the indoor unit.
(4) Supply power to each outdoor unit and provide an earth leakage breaker or hand switch for each outdoor unit.
(5) Never connect the 220–240V power to the terminal block (U1, U2, U3, U4, U5, U6) for control cables.
(Trouble is caused.)
(6) Store wiring system for control and refrigerant piping system in the same line.
(7) Arrange the cables so that the electric wires do not come to contact with high-temperature part of the pipe ;
otherwise coating melts and an accident may be caused.
(8) Do not turn on power of the indoor unit until vacuuming of the refrigerant pipe will finish.
2. For outdoor unit power supply
• Select the power supply cabling and fuse of each outdoor unit from the following specifications:
Cable 5-core, in conformance with Design 60245 IEC 66
• Do not connect them via the incorporated terminal block (L1, L2, L3, N).
L1
L2
L3
N
Outdoor power supply
3-phase 380-415V, 50Hz
3. Electrical wiring design
3-phase
50Hz 380-415V
Earth leakage breaker
hand switch
Outdoor
power source
Indoor
power source
Earth
Single phase
50Hz 220-240V
Earth leakage breaker
power switch
FS unit
Indoor unit
FS unit
L1
L2
L3
N
L1
L2
FS unit
Indoor unit
FS unit
L3
N
Pull box
FS unit
Indoor unit
FS unit
FS unit
Indoor unit
FS unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
• Unit capacities and power supply wire sizes (Reference)
Model
MMY-
MAP0802FT8
MAP1002FT8
MAP1202FT8
Wire size
3.5 mm² (AWG #10) Max. 20 m
5.5 mm² (AWG #10) Max. 28 m
5.5 mm² (AWG #10) Max. 27 m
Power supply wiring
Field fuse
30 A
30 A
30 A
• Determine the wire size for indoor unit according to the number of connected indoor units downstream.
• Observe local regulation regarding wire size selection and installation.
30
Page 31
4.
For Indoor unit power supply (Must be independent from outdoor unit power.)
Item
Model
Power supply wiring
Wire size
Field fuse
All models of indoor units 2.0mm² (AWG#14) Max. 20m 3.5mm² (AWG#12) Max. 50m 15A
FS unit
NOTE :
Be sure to use the attached cable. If the length between indoor and FS unit exceeds 5 m,
connect by using the connection cable kit (RBC-CBK15FE). (Sold separately)
The connecting length indicated in the table represents the length from the pull box to the outdoor unit when the indoor
units are connected in parallel for power, as shown in the above illustration. A voltage drop of no more than 2% is also
assumed. If the connecting length will exceed the length indicated in the table, select the wire thickness in accordance
with local wiring standards.
CAUTIONS
(1) Keep the refrigerant piping system and the indoor-indoor/indoor-outdoor control wiring systems together.
(2) When running power wires and control wires parallel to each other, either run them through separate conduits, or
maintain a suitable distance between them.
(Current capacity of power wires: 10A or less for 300m, 50A or less for 500m)
5. Design of control wiring
Power supply
Single phase
220-240V 50Hz
(Open)
Earth
[Central remote controller] (Option)
TCB-SC642TLE (For line 64)
Remote
controller
FS unit
Transmission wire for control
between outdoor units
Transmission wire for control
Transmission wire for control
between outdoor unit and
between outdoor unit and
indoor unit
indoor unit
FS unitFS unit
(Header)(Follower)
FS unitFS unit
Connection of shield wire must be connected
(Connected to all connecting sections in each outdoor unit)
Connection of shield wire must be connected
Connection of shield wire must be connected
(Connected to all connecting sections in each indoor unit)
(Connected to all connecting sections in each indoor unit)
Transmission wire for
control between indoor
and FS unit.
FS unit
Transmission wire for
control between indoor
and FS unit.
FS unit
• Wire specification, quantity, size of crossover wiring and remote controller wiring
Name
Crossover wiring
(indoor-indoor / indoor-outdoor / control wiring,
central control wiring)
Remote controller wiring
Control wiring between indoor and FS unit
Q’ty
2 cores
2 cores
Be sure to use the attached connection cable. If the length between indoor and FS unit
exceeds 5 m, connect by using the connection cable kit (RBC-CBK15FE). (Sold separately)
Up to 500mUp to 1000m1000 to 2000m
1.25mm
0.5 to 2.0mm
2
Size
2
——
2.0mm
2
Specification
Shield wire
—
(1) The crossover wiring and central control wiring use 2-core non-polarity transmission wires. Use 2-core shield wires to
prevent noise trouble. In this case, close (connect) the end of shield wires, and perform the functional grounding for
the end of the shield wires which are connected to both indoor and outdoor units. For the shield wires which are
connected between the central remote controller and the outdoor unit, perform the functional grounding at only one
end of central control wiring.
(2) Use 2-core and non-polarity wire for remote controller. (A, B terminals)
Use 2-core and non-polarity wire for wiring of group control. (A, B terminals)
31
Page 32
6.
System Wiring Design
Outdoor unit
Outdoor side
Indoor side
Power supply
3 phase 380-415V 50Hz
Earth leakage breaker
Power swith
Earth
terminal
U1
U2U3 U4 U5 U6
Earth
terminal
Power supply
3 phase 380-415V 50Hz
Earth
terminal
U1 U2U3 U4 U5 U6
Earth leakage breaker
Power swith
Earth
terminal
Earth
terminal
U1/U3
U2/U4
Central remote
Earth
terminal
controller
Power supply
3 phase 380-415V 50Hz
Earth leakage breaker
Power swith
Earth
terminal
U1 U2U3 U4 U5 U6
Single phase
220-240V 50Hz
Earth
terminal
Earth
terminal
Power supply
Single phase
220-240V
50Hz
Earth leakage
breaker
Power switch
U1/U2
Earth terminal
LN
Earth
terminal
Pull
Box
Indoor unit
A
B
Control
wiring
Powe r
line
Remote
controller
A
B
FS unit
CN02
CN01
Earth
terminal
U1/U2
Earth terminal
LN
terminal
Pull
Box
Indoor unit
CN81
Earth
Remote
controller
line
A
B
FS unit
CN02
CN01
Earth
terminal
U1/U2
Earth terminal
LN
A
B
Control
wiring
Powe r
Indoor unit
Earth
terminal
A
B
Control
wiring
Powe r
line
Remote
controller
FS unit
NOTE :
Control wire and power line wire between FS unit and indoor unit are the accessary parts of FS unit. (Wire length : 6m)
If the length between indoor and FS unit exceeds 5m, connect by using the connection cable kit sold separately (RBCCBK15FE).
A
B
CN02
CN01
Earth
terminal
32
Page 33
7.
Design
■ Indoor unit
Type Model
4-Way Air
Discharge
Cassette Type
2-Way Air
Discharge
Cassette Type
1-Way Air
Discharge
Cassette Type
Concealed Duct Type
Concealed Duct
High Static
Pressure Type
Under Ceiling Type
High Wall Type (1 series)
High Wall Type (2 series)
Floor Standing
Cabinet Type
Floor Standing
Concealed Type
Floor Standing Type
LegendMCA: Minimum Circuit AmpsFLA : Full Load Amps
50Hz
Nominal Volta ge Voltage Range Fan Motor Power Supply
Enabling a range of controls to meet various system needs
As the size of the building increases so does the number of air-conditioning units
required. The multiple air-conditioning system Super HRM ensures energy-saving and
comfort by allowing a control of multiple units requiring different loads.
The Super HRM provides a range of functions to enable an integrated, centralized
control of multiple units. Design an optimal system that best suits the application and
scale of your project.
1. Control via indoor remote controller
1-1. Remote controller
Individual air-conditioning units can be controlled
remotely.
1-2. Group control
One remote controller can control a maximum of 8
indoor units in group.
1-3. Two remote controller
The units can be controlled from two locations
using two remote controllers.
1-4. Weekly timer
The units can be run on a weekly schedule using a
“remote controller with weekly timer”.
2. Control via the central remote
controller
2-1. Central control + individual control
Up to 64 units can be controlled using the central
remote controller and/or indoor remote controllers.
Central control with Super MMS system is also
available.
2-2. Weekly timer controller
The central remote controller can be connected to
a weekly timer to set a weekly running schedule.
2-3. Control without indoor remote controller
The units can be operated from the central remote
controller only, without the use of indoor remote
controllers.
2-4. Control control with 1 by 1 model
Additionally, 1 by 1 model as Digital Inverter or
Super Digital Inverter can be joined into the Super
MMS and Super HRM central control scheme.
3. Network control
The Super HRM control system can realize
flexible centralized network control facility
according to customer’s various requirements, for both open network building
control in combination with other building
apparatus like elevator, fire alarm, lighting,
etc., and also for stand-alone air conditioning central control.
These central control scheme is mainly
established by advanced local server
platform.
3-1. Open network control
Super HRM open network facility is
applicable for major building management
global standards.
3-1-1. LONWORKS
The LONWORKS interface manages the
Super HRM air conditioning system as a
LON device to command a building
computer message and to monitor the
operation status.
3-1-2. BACnet
The local server serves air conditioning
sub-system in a building control BACnet
system.
3-2. Stand-alone central control
Simple stand-alone type exclusive air
conditioning central control with less
system integration work.
3-2-1. Touch screen controller
Combination of touch screen and local
server enables easy operation and comfortable display.
®
®
35
Page 36
1. Applications for indoor remote controller
1-1
1-2
Basic function
Individual control
Air conditioner is
individually operated
at a distance.
GROUP control
One remote controller
can control group of
Max. 8 indoor units.
Operating on the
same setting
Main remote controller
Indoor
unit
Remote
controller
Indoor
unit
Remote
controller
System diagram
Wireless remote controller
Indoor
unit
Possible up to Max.
total length 500m
Receiver unit
Wireless
remote
controller
Max.8 indoor units
Indoor
unit
Indoor
unit
Indoor
Possible up to Max.total length 500m
unit
Model
• Wired remote controller
RBC-AMT21E
• Simple remote controller
RBC-AS21E
• Wireless remote controller
kit
TCB-AX21U(W)-E
RBC-AX22CE
TCB-AX21E
• Wired remote controller
RBC-AMT21E
• Simple remote controller
RBC-AS21E
Two remote control
Air conditioner is
1-3
controlled by two
remote controllers at
two places.
Control by
weekly timer
1-4
Weekly schedule
operation
Wired systemWireless system
Indoor
Indoor
unit
Wireless
remote
controller 1
Master
Remote
controller
Master
Remote
controller
Side
Possible up to Max.
total length 500m
Indoor
Wired & Wireless
combination control
(Either controller
should be set as
side controller)
Remote
controller
Weekly timer function
• Setting of ON-OFF
3 times par day
Indoor
unit
• Timer time is displayed.
• Designation of holiday
unit
unit
Wireless
remote
controller 2
Side
Wireless
remote
controller
• Wired remote controller
RBC-AMT21E
• Simple remote controller
RBC-AS21E
• Wireless remote controller
kit
TCB-AX21U(W)-E
RBC-AX22CE
TCB-AX21E
• Wired remote controller
RBC-AMT21E
+
• Weekly timer
RBC-EXW21E
Remote
controller
Weekly
timer
36
Page 37
2. Application controls for central remote controller
Basic functionModelSystem diagram
Header
Central management
2-1
controller for 64 units
Zone
Zone
Zone
Zone
Powe r
supply
4
U3, U4
3
2
U3, U4
1
unit
U3, U4
U1, U2
Header
unit
U1, U2
Header
unit
U1, U2
FS unit
Central
Single phase
220/230/240V
remote controller
Super MMS
Outdoor unit
Line-3
U5, U6
Indoor remote controller
U5, U6
Indoor remote controller
Outdoor unit
Line-1
Indoor remote controller
Indoor unit
Outdoor unit
Line-2
Super HRM
Indoor unit
Super MMS
Indoor unit
• Central remote controller
TCB-SC642TLE
<Indoor remote controller>
• Wired remote controller
RBC-AMT21E
• Simple remote controller
RBC-AS21E
Central remote
controller
Weekly timer
2-2
+
Weekly operation
schedule
can be set by
connecting a weekly
timer to the central
remote controller
Function of central remote controller
• Individual control up to 64 indoor units.
• Individual control for max. 64 indoor units divided 1 to
4 zone. (Up to 16 indoor units for each zone.)
• Up to 16 outdoor header units are connectable.
• 4 type central control setting to inhibit individual
operation by remote controller can be selected.
• Setting for one of 1 to 4 zone is available.
• Usable with other central control devices
(Up to 10 central control devices in one control circuit)
• Two control mode selectivity
Central controller mode/Remote controller mode
• Setting of simultaneous ON/OFF 3 times for each day
of the week combined with weekly timer.
Outdoor unitU3, U4
Single phase
220/230/240V
Power
supply
remote controller
FS
unit
Indoor remote controller
Central
Indoor unit
Weekly timer
U1, U2
• Central remote controller
TCB-SC642TLE
+
• Weekly timer
RBC-EXW21E
<Indoor remote controller>
• Wired remote controller
RBC-AMT21E
or
• Simple remote controller
RBC-AS21E
37
Page 38
Basic function
System diagramModel
Remote central
control without
2-3
indoor remote
controller
U3, U4
Powe r
supply
Single phase
220/230/240V
Example of grouping operation
Powe r
supply
Single phase
220/230/240V
Powe r
supply
Single phase
220/230/240V
FS unit
Central remote controller
U3, U4
Central remote controller
U3, U4
Central remote controller
Outdoor unit
Even when grouping operation is performed
by connecting multiple indoor units to 1 line,
the indoor remote controller is required.
Outdoor unit
U1, U2
(Group)
U1, U2
Indoor unit
FS unit
Available
Outdoor unit
U1, U2
(Group)
FS unit
Available
• Central remote controller
TCB-SC642TLE
<Indoor remote controller>
• Wired remote controller
RBC-AMT21E
Central manage-
2-4
ment control with
“1 : 1 model”
Powe r
supply
U3, U4
Header
unit
U1, U2
FS
unit
Central remote controller
Super HRM
Indoor unit
Indoor remote controller
*
"1:1 model"
connection interface
1
* TOSHIBA Digital Inverter System and Super Digital
Inverter System
38
• Central remote controller
TCB-SC642TLE
• “1 : 1 model” connection
interface
TCB-PCNT30TLE
RAV-SM560KRT-E,
SM800KRT-E are not
available
<Indoor remote controller>
• Wired remote controller
RBC-AMT21E
• Simple remote controller
RBC-AS21E
Page 39
3. Application control for network
3-1-1
Basic function
LONWORKS
®
(*1)
System diagram
LON Center
LON Talk
LN Interface
FS
unit
TCB-
Super HRM
Remote controller
*
"1:1 model"
connection interface
1
*1 TOSHIBA Digital Inverter System and Super Digital
Inverter System
The LONWORKS interface shall be connected between a building management computer and the Super
HRM and Super MMS system.
Max. 64 indoor units are connectable per interface.
Model
• LN interface
TCB-IFLN640TLE
• “1 : 1 model” connection
interface
TCB-PCNT30TLE
RAV-SM560KRT-E,
SM800KRT-E are not
available
<Indoor remote controller>
• Wired remote controller
RBC-AMT21E
or
• Simple remote controller
RBC-AS21E
3-1-2BACnet
(*2)
BAC net center
BAC net
server
TCN-NET
relay interface
FS
unit
TCB-
Super HRM
Remote controller
*
"1:1 model"
connection interface
1
*1 TOSHIBA Digital Inverter System and Super Digital
Inverter System
The local server shall be connected under the BACnet
network, and shall be connected the Super HRM and
Super MMS system through the interface.
Appliance name Model name Contents of application control
Remote location
ON/OFF control box
Network adapter TCB-PCNT20E Central control with AI-Network system Indoor unit
"1:1 model" connection
interface
• Application controls of outdoor unit
Appliance name Model name Contents of application control
Power peak-cut control
board
External master
ON/OFF control board
Error output control
board
TCB-IFCB-4E
TCB-PCNT30TLE
TCB-PCDM2E
TCB-PCMO2E
TCB-PCIN2E
· Monitoring from outside
· ON/OFF command from external signals
Central control with " 1:1 model"
(link Toshiba Digital Inverter system and
Super Digital Inverter system)
Power peak-cut (Standard function)
Power peak-cut (Expansion function)
Snowfall fan control
External master ON/OFF control
Night operation (sound reduction) control
Operation mode selection control
Operation and error monitoring from
external position
Connecting device or
setting method
Indoor unit
Indoor unit
Connecting device or
setting method
Inverter assembly of the
header outdoor unit
Accessories parts for indoor unit
• Remote controller
Indoor unit type Accessory parts name Model Applicable model
4-way Air Discharge Cassette Type
2-way Air Discharge Cassette Type
1-way Air Discharge Cassette Type
Concealed Duct Type
Concealed Duct, High Static Pressure Type
Under Ceiling Type
High Wall Type (1 series)
High Wall Type (2 series)
Floor Standing Cabinet Type
Floor Standing Concealed Type
Floor Standing Type
Wired remote controller
Central remote controller
Weekly timer
Simple remote controller
Remote sensor
Wire-less remote controller kit
1
*
RBC-AMT21E
TCB-SC642TLE
RBC-EXW21E
RBC-AS21E
TCB-TC21LE
TCB-AX21U(W)-E
RBC-AX22CE Under Ceiling Type
TCB-AX21E
WH-H2UE
Common parts for
all type model
4-way Air
Discharge
Cassette Type
Universal Type
Except concealed
(
duct high static
pressure type)
High Wall Type
(2 series)
Packed with indoor
unit
*1: For handling the Wireless Remote Controller kit, consult your dealer about availability.
41
Page 42
• Panels and accessories
Indoor unit type Accessory parts name Model Application model Remarks
Required accessory Ceiling panel RBC-U21PG(W )-E
4-way Air Discharge
Cassette Type
2-way Air Discharge
Cassette Type
1-way Air Discharge
Cassette Type
Concealed Duct
Type
Concealed Duct
High Static Pressure
Type
Under Ceiling Type Optional
Optional
Required accessory Ceiling panel
Required accessory Ceiling panel
Optional
Optional
Super Long Life Filter TCB-LF1601UE
High Efficiency Filter 65 TCB-UFM1601UE
High Efficiency Filter 90 TCB-UFH1601UE
Fresh air and Filter
Chamber
Fresh air inlet Box TCB-GB1601UE Be used with TCB-GFC1601UE
Auxiliary fresh air Flange TCB-FF101URE
Spacer for height
adjustment
Air discharge direction kit TCB-BC1601UE Three-piece set
High Efficiency Filter 65
High Efficiency Filter 90
Ceiling panel
Suction Canvas
Filter Chamber
Filter kit for underside
High Efficiency Filter 65
High Efficiency Filter 90
Long Life Pre-Filter
Filter Chamber
Drain pump kit
Drain pump kit TCB-DP22CE AP0151-0481
Elbow piping kit
TCB-GFC1601UE
TCB-SP1601UE
RBC-UW136PG AP0071-0121
RBC-UW266PG AP0151-0301
RBC-UW466PG AP0361-0561
RBC-US165PG AP0151-0181
RBC-US265PG AP0241
RBC-UY135PG AP0071-0121
TCB-UFM11BFCE AP0071-0121/AP0241-0301 AP0241-AP0301 use two pcs.
TCB-UFM21BFCE AP0151-0181/AP0361-0561 AP0361-AP0581 use two pcs.
TCB-UFM11BE AP0071-0121
TCB-UFM21BE AP0151-0181
TCB-UFM31BE AP0241-0301
TCB-UFM41BE AP0361-0561
TCB-UFH51BFCE AP0071-0121/AP0241-0301 AP0241-AP0301 use two pcs.
TCB-UFH61BFCE AP0151-0181/AP0361-0561 AP0361-AP0561 use two pcs.
TCB-UFH51BE AP0071-0121
TCB-UFH61BE AP0151-0181
TCB-UFH71BE AP0241-0301
TCB-UFH81BE AP0361-0561
RBC-UD281PE(W) AP0071-0121
RBC-UD501PE(W) AP0151-0181
RBC-UD801PE(W) AP0241-0301
RBC-UD1401PE(W) AP0361-0561
TCB-CA281BE AP0071-0121
TCB-CA501BE AP0151-0181
TCB-CA801BE AP0241-0301
TCB-CA1401BE AP0361-0561
TCB-FC281BE AP0071-0121
TCB-FC501BE AP0151-0181
TCB-FC801BE AP0241-0301
TCB-FC1401BE AP0361-0561
TCB-FK281BE AP0071-0121
TCB-FK501BE AP0151-0181
TCB-FK801BE AP0241-0301
TCB-FK1401BE AP0361-0561
TCB-UFM1D-1E AP0181/0481 AP0481 use two pcs.
TCB-UFM2D-1E AP0241-0361 Use two pcs.
TCB-UFM3DE AP0721-0961
TCB-UFH5D-1E AP0181/0481 AP0481 use two pcs.
TCB-UFH6D-1E AP0241-0361 Use two pcs.
TCB-UFH7DE AP0721-0961
TCB-PF1D-1E AP0181/0481 AP0481 use two pcs.
TCB-PF2D-1E AP0241-0361 Use two pcs.
TCB-PF3DE AP0721-0961
TCB-FCY21DE AP0181
TCB-FCY31DE AP0241-0361
TCB-FCY51DE AP0481
TCB-FCY100DE AP0721-0961
TCB-DP31DE AP0181-0481
TCB-DP32DE AP0721-0961
TCB-KP12CE AP0151-0181
TCB-KP22CE AP0241-0481
Be used with TCB-GFC1601UE
For underside suction
For underside suction
(Half panel for underside
suction)
For underside suction
For rear suction
* Required accessories when
using Drain Pump Kit
42
Page 43
1. Accessory Parts for 4-Way Air Discharge Cassatte type (Detail)
Operation time : 1800 hours
Reuse is not available with
TCB-GFC1601UE
Fresh Air and
Filter Chamber
Fresh Air Inlet
Box
Auxiliary Fresh
Air Flange
Spacer for
Height
Adjustment
Air Discharge
Direction kit
TCB-GFC1601UE
TCB-GB1601UE
TCB-FF101URE
TCB-SP1601UE
TCB-BC1601UE
For fresh air intake and
installing high efficiency filter
or super long life filter
Use with TCB-GFC1601UE
Easy fresh air intake by
using the knockout hole of
indoor unit.
(dia.=100mm)
Height = 50mm
Air direction change by
cutting off of air discharge
port (3 pcs.)
TCB-BC1601UE
TCB-FF101URE
TCB-GFC1601UE
TCB-SP1601UE
RBC-U21PG(W)-E
TCB-GB1601UE
TCB-UFM1601UE
TCB-UFH1601UE
TCB-LF1601UE
2. Accessory for 4-way Air Discharge Cassette Type:Combination Pattern
Ceiling Panel
RBC-U21PG (W)-E
Wireless remote controller kit
TCB-AX21U (W)-E
Auxiliary fresh air flange
TCB-FF101URE
Fresh air and filter chamber (as fiter chamber)
TCB-GFC1601UE
Panel
Optional
Parts
Ceiling Panel
Wireless remote controller kit
Auxiliary fresh air flange
Fresh air and filter chamber
(Used for filter frame)
Fresh air inlet box +
Fresh air and filter chamber
Super long life filter
High efficiency filter (65%)
High efficiency filter (90%)
Spacer for height adjustment
Air discharge direction kit
(*1)Setup of air volume by connecting main wired remote controller and item code setting is necessary.
(*2) Procedure same as (*1) is necessary when indoor unit is used under the different air volume from setting at shipment.
RBC-U21PG (W)-E
TCB-AX21U (W)-E
TCB-FF101URE
TCB-GFC1601UE
TCB-GB1601UE +
TCB-GFC1601UE
TCB-LF1601UE
TCB-UFM1601UE
TCB-UFH1601UE
TCB-SP1601UE
TCB-BC1601UE
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
(*1)
OK
(*1)
-
(*1)
-
OK
(*2)
OK
OK
OK
OK
OK
OK
OK
OK
OK
OK
43
Fresh air inlet box + Fresh air and filter chamber
TCB-GB1601UE + TCB-GFC1601UE
Super long life fitler
TCB-LF1601UE
High efficiency filter (65%)
TCB-UFM1601UE
High efficiency filter (90%)
TCB-UFH1601UE
Spacer for height adjustment
TCB-SP1601UE
Air discharge direction kit
TCB-BC1601UE
OK
OK
OK
(*1)
(*1)
OK
OK
OK
OK
OK
OK
OK
OK
-
-
-
OK
OK
-
(*1)
OK
OK
OK
OK
-
-
-
-
OK
-
-
OK
OK
OK
OK
OK
OK
OK
OK
OK
(*2)
OK
OK
OK
-
OK
-
-
-
OK
Page 44
9.TECHNICAL SPECIFICATIONS
50Hz
Indoor unit (50Hz specifications)
• 4-way Air Discharge Cassette Type
Model na me MMU- AP0091H AP0121H AP0151H AP0181H AP0241H AP0271H AP0301H AP0361H AP0481H AP0561H
(Shield wire) 1.25mm² x 2 cores up to 1000m, and (Shield wire) 2.0mm² x 2 cores up to 2000m
When connecting to outdoor unit :
3.46
3.82
57
Page 58
50Hz
Equivalent HP Equivalent to 26HP Equivalent to 28HP Equivalent to 30HP
Set Model name Heat Recovery MMY- AP2602FT8 AP2802FT8 AP3002FT8
Outdoor unit type Inverter
Outdoor unit model Heat Recovery MMY- M AP1002FT8 MAP0802FT8 MAP0802FT8 MAP 1002FT8 MAP1002FT8 MAP0802FT8 MAP1002FT8 MAP1002FT8 MAP1002FT8
• Energy mountoring relay interface/Digital I/O relay interface
BMS-IFWH3E
BMS-IFDD01E
198
39
Grommet for
power input
181853.5103.5
234
220
246
1818
92.5
64.5
(193)
63.6
Grommet for
power meter
Grommet for
RS-485
84
Page 85
Outdoor unit
MMY-MAP0802FT8, MAP1002FT8, MAP1202FT8
755
790
750
anchor bolt pitch
(including steady leg)
4-15 × 20
(Long hole)
700
anchor bolt pitch
990
(NOTES)
1. If there is an obstacle at the upper side of the outdoor unit,
set the top end of the outdoor unit 2000mm apart from the obstacle.
2. Limit the height of the obstacle surrounding the outdoor unit to
800mm or less from the bottom end of the outdoor unit.
3. Draw out the pipe procured locally to the front of the outdoor unit
horizontally, and keep 500mm or more between the outdoor unit
and traversing pipe if placing pipe transversely.
2-60 × 150 square hole
(Hole for handling goods)
Knockout for
control piping (Ø27)
Earth-attaching section of bottom plate
610100100
Knockout hole for
power piping (Ø48)
135
Refrigerant pipe
connecting port
(Suction gas side)
Refrigerant pipe
connecting port
(Discharge gas side)
Refrigerant pipe
connecting port
(Liquid side)
Foundation
8080630
700
anchor bolt pitch
Refrigerant pipe
connecting port (Liquid side)
Refrigerant pipe
connecting port
(Discharge gas side)
A
755
anchor bolt pitch
Foundation
57
59
Model name
MMY-MAP0802FT8
MMY-MAP1002FT8
MMY-MAP1202FT8
1 Cutting position of L-shape pipe when pipe
at gas side is connected
(Recommended pipe connecting position)
1010 or more
500
or more
1750
or more
500
or more
10 or more
Front side
(For work and service)
10 or more
ØA
22.2
22.2
28.6
Space required for service
800
or less
500
or more
(Note 3)
600 or more
(1000 or more)
500
or more
Front side
Front side
500
or more
Front side
(Note 3)
Refrigerant pipe
connecting port
(Suction gas side)
Front side
600 or more
(1000 or more)
600
or more
Front side
500
or more
225
231
215
154
88
88115
144
Square hole
139
8
173
52
130
58
112
Details of front pipe/cabling holesDetails of hole for piping at lower side (Plane view)
Note: All dimensions are in mm.
85
Page 86
<Two units connected>
MMY-AP1602FT8, AP1802FT8, AP2002FT8
(NOTES)
1. If there is an obstacle at the upper side of the outdoor unit,
set the top end of the outdoor unit 2000mm apart from the
obstacle.
2. Limit the height of the obstacle surrounding the outdoor unit
to 800mm or less from the bottom end of the outdoor unit.
3. Draw out the pipe procured locally to the front of the outdoor
unit horizontally, and keep 500mm or more between the
outdoor unit and traversing pipe if placing pipe transversely.
4. Arrange each outdoor unit in order of its capacity.
(Head unit > Follower)
12
165
1800
1640
700
20 or more
990990
700
anchor bolt pitch
(310)
700
anchor bolt pitch
755
750
anchor bolt pitch
8-15 × 20
(Long hole)
790
(including steady leg)
Combination unit
MMY-AP1602FT8
MMY-AP1802FT8
MMY-AP2002FT8
500
or more
(Note 4)
Front side
(Note 3)
(1000 or more)
500
(Note 4)
Front side
600 or more
or more
Front side
Front side
500
or more
(Note 4)
(Note 3)
600 or more
(1000 or more)
600
or more
500
or more
88
Header
MAP0802FT8
MAP1002FT8
MAP1002FT8
Front side
Front side
Front side Front side
Front side
Front side
2000
Combination outdoor unit
MAP0802FT8
MAP0802FT8
MAP1002FT8
(Note 4)
500mm or more
10mm or more
Front side (For work and service)
500mm
or more
2020mm or more
Follower
20mm or more
1750mm or more
10mm
or more
800
or less
800
or less
Space required for service
Note: All dimensions are in mm.
86
Page 87
<Three units connected>
MMY-AP2402FT8, AP2602FT8, AP2802FT8, AP3002FT8
(NOTES)
1. If there is an obstacle at the upper side of the
outdoor unit, set the top end of the outdoor unit
2000mm apart from the obstacle.
2. Limit the height of the obstacle surrounding the
outdoor unit to 800mm or less from the bottom end
of the outdoor unit.
3. Draw out the pipe procured locally to the front of the
outdoor unit horizontally, and keep 500mm or more
between the outdoor unit and traversing pipe if
placing pipe transversely.
4. Arrange each outdoor unit in order of its capacity.
2
(Head unit > Follower
> Follower 3 )
1800
1640
anchor bolt pitch
1
20 or more
990990
700
(310)
990
700
anchor bolt pitch
20 or more
(310)
32
700
anchor bolt pitch
755
790
750
anchor bolt pitch
12-15 × 20
(Long hole)
(including steady leg)
Combination unit
MMY-AP2402FT8
MMY-AP2602FT8
MMY-AP2802FT8
MMY-AP3002FT8
(Note 4)
500 or more
Front side
Front side
Front side
(Note 3)
600 or more
(1000 or more)
(Note 4)
500 or more
Front side
Front side
Front side
700
88165
Header
MMY-MAP0802FT8
MMY-MAP1002FT8
MMY-MAP1002FT8
MMY-MAP1002FT8
(Note 4)
500 or more
Front side
Front side
Front side
(Note 3)
600 or more
(1000 or more)
600
or more
500
or more
Front side
Front side Front side Front side
3010
Combination outdoor unit
Follower
MMY-MAP0802FT8
MMY-MAP0802FT8
MMY-MAP1002FT8
MMY-MAP1002FT8
(Rear side)
Front side
Front side
(Note 4)
500mm or more
10mm or more 20mm or more 20mm or more
500mm
Front side (For work and service)
or more
Space required for service
(Front side)
MMY-MAP0802FT8
MMY-MAP0802FT8
MMY-MAP0802FT8
MMY-MAP1002FT8
3030mm or more
Follower
32
10mm
1750mm or more
or more
800
or less
800
or less
Note: All dimensions are in mm.
87
Page 88
FS unit (Flow Selector Unit)
RBM-Y1122FE, Y1802FE
Outdoor unit side
Refrigerant pipe connecting
port (Discharge gas)
Refrigerant pipe connecting
port (Liquid)
Refrigerant pipe connecting
port (Suction gas)
160
5739
154
21
44
87
(Specifications)
Model name
Indoor unit
side
Outdoor
unit side
Connecting indoor unit capacity
Power supply
Total weight
Dimension (mm)
Liquid side
Gas side
Liquid side
Discharge gas side
Suction gas side
(hanging bolt pitch)
320
250
(94)
(55)
190
(99)(55)
Y1802FE only
Earth
screw
RBM-Y1122FE
Connecting
pipe
Ø9.5
Ø15.9
Ø9.5
Ø12.7
Ø15.9
Connecting
method
1
*
Flare
1
*
Flare
Flare
Flare
007 to 030 type
Single phase 50Hz 230V(220-240V)
5kg
Height 190 X Width 250 X Depth 160
RBM-Y1802FE
Connecting
pipe
Connecting
method
Flare
Ø9.5
Flare
Ø15.9
Flare
Ø9.5Flare
Flare
Ø12.7
Flare
Ø15.9
036 to 056 type
5kg
Indoor unit side
Refrigerant pipe connecting
port (Liquid)
Refrigerant pipe connecting
port (Gas)
(99)
54
75
Accessory pipe and socket
Ø9.5, Brazing
3
Ø12.7, Brazing
2
Ø6.4, Brazing
1
For gas pipe
For gas pipe
31
79
007 to 012 type
015, 018 type
007 to 018 typeFor liquid pipe
(Installation space)
<RBM-Y1122FE (when attached pipes are used)>
(159)
or
50
more
2
3
(118)
or
200 or
more
<RBM-Y1122FE, RBM-Y1802FE>
200 or
more
1) When the capacity of connected indoor unit is less than 5.6 kW, adjust the pipe
*
50
more
or
50
more
or
50
more
1
300 or more
200 or
more
Outdoor unit
side
or more
500
size by using this accessory pipe.
88
50
Electrical parts
box cover
Note: All dimensions are in mm.
or
more
Indoor unit
side
Check port
450X450
Page 89
RBM-Y2802FE
Tentative
Outdoor unit side
Refrigerant pipe connecting
port (Discharge gas)
Refrigerant pipe connecting
port (Liquid)
Refrigerant pipe connecting
port (Suction gas)
199
684942
200
105
28 38
(Specifications)
Model name
Indoor unit
side
Outdoor unit
side
Total capacity of indoor unit (kW)
Power Supply
Total Weight
Dimension (mm)
Liquid side
Gas side
Liquid side
Discharge gas side
Suction gas side
470 (hanging bolt pitch)
(108)(398)(109)
(66)
(109)
(65)
Earth
screw
RBM-Y2802FE
8 kg
Connecting
method
Flare
Flare
Flare
Flare
Flare
Ø19.1 (Flare) Ø22.2 (Brazing)
2
Ø15.9 (Flare) Ø19.1 (Brazing)
1
Ø19.1 (Flare) Ø22.2 (Brazing)
2
Connecting
port
Ø12.7
1
*
Ø22.2
Ø12.7
1
*
Ø15.9
1
*
Ø22.2
18.0 to 28.0 or less
Single phase 50Hz 230V (220-240V)
Height 200 X Width 398 X Depth 199
Indoor unit side
Refrigerant pipe connecting
port (Gas)
Refrigerant pipe connecting
port (Liquid)
773212.5
67
105
Accessory pipe
31
(Installation space)
<RBM-Y2802FE (when attached pipes are used)>
(198)
1
2
(210)
400 or more
1) Adjust the pipe size by using this accessory pipe.