Thank you for purchasing this Toshiba air conditioner.
Please read carefully through these instructions that contain important information which complies with the
“Machinery” Directive (Directive 2006/42/EC), and ensure that you understand them.
After completing the installation work, hand over this Installation Manual as well as the Owner’s Manual provided
to the user, and ask the user to keep them in a safe place for future reference.
Generic Denomination: Air Conditioner
Definition of Qualified Installer or Qualified Service Person
The air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified service
person. When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you.
A qualified installer or qualified service person is an agent who has the qualifications and knowledge described in
the following table.
AgentQualifications and knowledge which the agent must have
• The qualified installer is a person who installs, maintains, relocates and removes the air conditioners
made by Toshiba Carrier Corporation. He or she has been trained to install, maintain, relocate and
remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been
instructed in such operations by an individual or individuals who have been trained and is thus
thoroughly acquainted with the knowledge related to these operations.
• The qualified installer who is allowed to do the electrical work involved in installation, relocation and
removal has the qualifications pertaining to this electrical work as stipulated by the local laws and
regulations, and he or she is a person who has been trained in matters relating to electrical work on
the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been
instructed in such matters by an individual or individuals who have been trained and is thus thoroughly
Qualified installer
Qualified service
person
acquainted with the knowledge related to this work.
• The qualified installer who is allowed to do the refrigerant handling and piping work involved in
installation, relocation and removal has the qualifications pertaining to this refrigerant handling and
piping work as stipulated by the local laws and regulations, and he or she is a person who has been
trained in matters relating to refrigerant handling and piping work on the air conditioners made by
Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an
individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge
related to this work.
• The qualified installer who is allowed to work at heights has been trained in matters relating to working
at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she
has been instructed in such matters by an individual or individuals who have been trained and is thus
thoroughly acquainted with the knowledge related to this work.
• The qualified service person is a person who installs, repairs, maintains, relocates and removes the
air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, repair,
maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or,
alternatively, he or she has been instructed in such operations by an individual or individuals who have
been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified service person who is allowed to do the electrical work involved in installation, repair,
relocation and removal has the qualifications pertaining to this electrical work as stipulated b y the local
laws and regulations, and he or she is a person who has been trained in matters relating to electrical
work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been
instructed in such matters by an individual or individuals who have been trained and is thus thoroughly
acquainted with the knowledge related to this work.
• The qualified service person who is allowed to do the refrigerant handling and piping work involved in
installation, repair, relocation and removal has the qualifications pertaining to this refrigerant handling
and piping work as stipulated by the local laws and regulations, and he or she is a person who has
been trained in matters relating to refrigerant handling and piping work on the air conditioners made
by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an
individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge
related to this work.
• The qualified service person who is allowed to work at heights has been trained in matters relating to
working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he
or she has been instructed in such matters by an individual or individuals who have been trained and
is thus thoroughly acquainted with the knowledge related to this work.
1-EN2-EN
Page 3
Definition of Protective Gear
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote
electric power supplies
before servicing.
WARNING
Moving parts.
Do not operate unit with grille
removed.
Stop the unit before the servicing.
CAUTION
High temperature parts.
You might get burned
when removing this panel.
CAUTION
Do not touch the aluminum
fins of the unit.
Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before
the operation, otherwise there
might be the burst.
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves
and ‘safety’ work clothing.
In addition to such normal protective gear, wear the protective gear described below when undertaking the special
work detailed in the following table.
Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns,
electric shocks and other injuries.
Work undertakenProtective gear worn
All types of work
Electrical-related
work
Work done at heights
(50 cm or more)
Transportation of
heavy objects
Repair of outdoor unit Gloves to provide protection for electricians and from heat
Protective gloves
‘Safety’ working clothing
Gloves to provide protection for electricians and from heat
Insulating shoes
Clothing to provide protection from electric shock
Helmets for use in industry
Shoes with additional protective toe cap
Warning indications on the air conditioner unit
Warning indicationDescription
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts.
Do not operate unit with grille removed.
Stop the unit before the servicing.
CAUTION
High temperature parts.
You might get burned when removing this panel.
CAUTION
Do not touch the aluminium fins of the unit.
Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be
the burst.
3-EN4-EN
–2–
Page 4
–3–
WARNING
1Precautions for safety
The manufacturer shall not assume any liability for the damage caused by not observing the description of this
manual.
General
• Before starting to install the air conditioner, read through the Installation Manual carefully, and follow its instructions
to install the air conditioner.
• Only a qualified installer or service person is allowed to do installation work. Inappropriate installation may result in
water leakage, electric shock or fire.
• Do not use any refrigerant different from the one specified for complement or replacement. Otherwise, abnormally
high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or
an injury to your body.
• Before opening the electrical control box cover of the indoor unit or service panel of the outdoor unit, set the circuit
breaker to the OFF position. Failure to set the circuit breaker to the OFF position may result in electric shocks through
contact with the interior parts. Only a qualified installer(*1) or qualified service person(*1) is allowed to remove the
electrical control box cover of the indoor unit or service panel of the outdoor unit and do the work required.
• Before carrying out the installation, maintenance, repair or removal work, set the circuit breaker to the OFF position.
Otherwise, electric shocks may result.
• Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work
is being carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
• Only a qualified installer(*1) or qualified service person(*1) is allowed to undertake work at heights using a stand of
50 cm or more or to remove the intake grille of the indoor unit to undertake work.
• Wear protective gloves and safety work clothing during installation, servicing and removal.
• Do not touch the aluminium fin of the unit. You may injure yourself if you do so. If the fin must be touched for some
reason, first put on protective gloves and safety work clothing, and then proceed.
• Before opening the inspection opening, set the circuit breaker to the OFF position. Failure to set the circuit breaker
to the OFF position may result in injury through contact with the rotation parts. Only a qualified installer (*1) or
qualified service person (*1) is allowed to remove the inspection opening and do the work required.
• When work is performed at heights, use a ladder which complies with the ISO 14122 standard, and follow the
procedure in the ladder’s instructions. Also wear a helmet for use in industry as protective gear to undertake the work.
• Before cleaning the filter or other parts of the outdoor unit, set the circuit breaker to OFF without fail, and place a
“Work in progress” sign near the circuit breaker before proceeding with the work.
• Before working at heights, put a sign in place so that no-one will approach the work location, before proceeding with
the work. Parts and other objects may fall from above, possibly injuring a person below. While carrying out the work,
wear a helmet for protection from falling objects.
• The refrigerant used by this air conditioner is the R410A.
• The air conditioner must be transported in stable condition. If any part of the product is broken, contact the dealer.
• When the air conditioner must be transported by hand, carry it by two or more people.
• Do not move or repair any unit by yourself. There is high voltage inside the unit. You may get electric shock when
removing the cover and main unit.
Selection of installation location
• When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration
of refrigerant leakage occur in the room does not exceed the critical level.
• Do not install in a location where flammable gas leaks are possible. If the gas leak and accumulate around the unit,
it may ignite and cause a fire.
• To transport the air conditioner, wear shoes with additional protective toe caps.
• To transport the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if
the bands should break.
• Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure themselves or receive
electric shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running.
• Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise
it may cause imperfect combustion.
Installation
• Suction duct length must be longer than 850 mm.
• When the indoor unit is to be suspended, the designated hanging bolts (M10 or W3/8) and nuts (M10 or W3/8) must
be used.
• Install the air conditioner securely in a location where the base can sustain the weight adequately. If the strength is
not enough, the unit may fall down resulting in injury.
• Follow the instructions in the Installation Manual to install the air conditioner. Failure to follow these instructions may
cause the product to fall down or topple over or give rise to noise, vibration, water leakage or other trouble.
• Carry out the specified installation work to guard against the possibility of high winds and earthquake. If the air
conditioner is not installed appropriately, a unit may topple over or fall down, causing an accident.
• If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas
comes in contact with fire, noxious gas may generate.
• Use forklift to carry in the air conditioner units and use winch or hoist at installation of them.
• Helmet must be worn to protect your head from falling objects.
Especially, when you work under an inspection opening, helmet must be worn to protect your head from falling
objects from the opening.
Refrigerant piping
• Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor
is operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is
over pressurized, which may cause a injury.
• Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a
crack in the flare nut after a long period, which may result in refrigerant leakage.
• After the installation work, confirm that refrigerant gas does not leak. If refrigerant gas leaks into the room and flows
near a fire source, such as a cooking range, noxious gas may be generated.
• When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge
the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge
the air completely may cause the air conditioner to malfunction.
• Nitrogen gas must be used for the airtight test.
• The charge hose must be connected in such a way that it is not slack.
Electrical wiring
• Only a qualified installer(*1) or qualified service person(*1) is allowed to carry out the electrical work of the air
conditioner. Under no circumstances must this work be done by an unqualified individual since failure to carry out the
work properly may result in electric shocks and/or electrical leaks.
• To connect the electrical wires, repair the electrical parts or undertake other electrical jobs, wear gloves to provide
protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks.
Failure to wear this protective gear may result in electric shocks.
• Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and
laws. Use of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage,
smoking and/or a fire.
• Connect earth wire. (Grounding work)
Incomplete grounding causes an electric shock.
• Do not connect earth wires to gas pipes, water pipes, and lightning conductor or telephone earth wires.
• After completing the repair or relocation work, check that the earth wires are connected properly.
• Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local
regulations and laws.
• Install the circuit breaker where it can be easily accessed by the agent.
• When installing the circuit breaker outdoors, install one which is designed to be used outdoors.
• Under no circumstances the power wire must not be extended. Connection trouble in the places where the wire is
extended may give rise to smoking and/or a fire.
• Electrical wiring work shall be conducted according to law and regulation in the community and installation manual.
Failure to do so may result in electrocution or short circuit.
5-EN6-EN
Page 5
Test run
CAUTION
• Before operating the air conditioner after having completed the work, check that the electrical control box cover of the
indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may
receive an electric shock if the power is turned on without first conducting these checks.
• If there is any kind of trouble (such as an error display has appeared, smell of burning, abnormal sounds, the air
conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner, do not touch the air conditioner
yourself but set the circuit breaker to the OFF position, and contact a qualified service person. Take steps to ensure
that the power will not be turned on (by marking “out of service” near the circuit breaker, for instance) until qualified
service person arrives. Continuing to use the air conditioner in the trouble status may cause mechanical problems to
escalate or result in electric shocks or other trouble.
• After the work has finished, use an insulation tester set (500 V Megger) to check the resistance is 1 MΩ or more
between the charge section and the non-charge metal section (Earth section). If the resistance value is low, a disaster
such as a leak or electric shock is caused at user’s side.
• Upon completion of the installation work, check for refrigerant leaks and check the insulation resistance and water
drainage. Then conduct a test run to check that the air conditioner is operating properly.
Explanations given to user
• Upon completion of the installation work, tell the user where the circuit breaker is located. If the user does not know
where the circuit breaker is, he or she will not be able to turn it off in the event that trouble has occurred in the air
conditioner.
• After the installation work, follow the Owner’s Manual to explain to the customer how to use and maintain the unit.
Relocation
• Only a qualified installer(*1) or qualified service person(*1) is allowed to relocate the air conditioner. It is dangerous
for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage,
noise and/or vibration may result.
• When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe.
Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air or
other gas to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly
resulting in rupture, injury or other trouble.
2Accessory parts
Accessory parts
Part nameQ’tyShapeUsage
Installation Manual1This manual
CD-ROM1—Installation Manual
Heat insulating pipe2For heat insulation of pipe connecting section
Washer8For hanging-down unit
Hose band1For connecting drain pipe
Flexible hose1For adjusting center of drain pipe
Heat insulator1For heat insulation of drain connecting section
Filter stopper1For fixing the filter
(Hand over to customers)
(For other languages that do not appear in this Installation Manual,
please refer to the enclosed CD-R.)
New refrigerant air conditioner installation
• This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer.
• The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is
approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also
been changed. Therefore, do not let water, dust, former refrigerant, or refrigerating oil enter the refrigerating cycle
during installation work.
• To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of
the main unit and installation tools are changed from those for the conventional refrigerant.
• Accordingly the exclusive tools are required for the new refrigerant (R410A).
• For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not
enter.
To disconnect the appliance from main power supply.
• This appliance must be connected to the main power supply by means of a switch with a contact separation of at
least 3 mm.
Part nameShape
Filter fixing rail 1 (700 L)12
Filter fixing rail 2 (700 L)12
Filter fixing rail 3 (490 L)2
Filter fixing rail 4 (490 L)2
AP0076~
AP0186
Q’ty
AP0246~
AP0306
AP0366~
AP0566
The installation fuse (all types can be used) must be used for the power supply line of this conditioner.
(*1) Refer to the “Definition of Qualified Installer or Qualified Service Person.”
7-EN8-EN
–4–
Page 6
–5–
3Selection of installation place
Avoid installing in the following places
Select a location for the indoor unit where the cool or warm air will circulate evenly.
Avoid installation in the following kinds of locations.
• Saline area (coastal area)
• Locations with acidic or alkaline atmospheres (such as areas with hot springs, factories where chemicals or
pharmaceuticals are made and places where the exhaust air from combustion appliances will be sucked into the
unit).
Doing so may cause the heat exchanger (its aluminum fins and copper pipes) and other parts to become
corroded.
• Locations with atmospheres with mist of cutting oil or other types of machine oil.
Doing so may cause the heat exchanger to become corroded, mists caused by the blockage of the heat
exchanger to be generated, the plastic parts to be damaged, the heat insulators to peel off, and other such
problems to result.
• Places where iron or other metal dust is present. If iron or other metal dust adheres to or collects on the interior
of the air conditioner, it may spontaneously combust and start a fire.
• Locations where vapors from food oils are formed (such as kitchens where food oils are used).
Blocked filters may cause the air conditioner’s performance to deteriorate, condensation to form, the plastic parts
to be damaged, and other such problems to result.
• Locations near obstructions such as ventilation openings or lighting fixtures where the flow of the blown air will
be disrupted (a disruption of the air flow may cause the air conditioner’s performance to deteriorate or the unit to
shut down).
• Locations where an in-house power generator is used for the power supply.
The power line frequency and voltage may fluctuate, and the air conditioner may not work properly as a result.
• On truck cranes, ships or other moving conveyances.
• The air conditioner must not be used for special applications (such as for storing food, plants, precision
instruments or art works).
(The quality of the items stored may be degraded.)
• Locations where high frequencies are generated (by inverter equipment, in-house power generators, medical
equipment or communication equipment).
(Malfunctioning or control trouble in the air conditioner or noise may adversely affect the equipment’s operation.)
• Locations where there is anything under the unit installed that would be compromised by wetness.
(If the drain has become blocked or when the humidity is over 80 %, condensation from the indoor unit will drip,
possibly causing damage to anything underneath.)
• In the case of the wireless type of system, rooms with the inverter type of fluorescent lighting or locations
exposed to direct sunlight.
(The signals from the wireless remote controller may not be sensed.)
• Locations where organic solvents are being used.
• The air conditioner cannot be used for liquefied carbonic acid cooling or in chemical plants.
• Location near doors or windows where the air conditioner may come into contact with high-temperature, highhumidity outdoor air.
(Condensation may occur as a result.)
• Locations where special sprays are used frequently.
Installation under high-humidity atmosphere
In some cases including the rainy season, especially inside of the ceiling may become high-humidity atmosphere
(dew-point temperature: 23 °C or higher).
1. Installation to inside of the ceiling with tiles on the roof
2. Installation to inside of the ceiling with slated roof
3. Installation to a place where inside of the ceiling is used for pathway to intake the fresh air
4. Installation to a kitchen
• In the above cases, additionally attach the heat insulator to all positions of the air conditioner, which come to
contact with the high-humidity atmosphere. In this case, arrange the side plate (Check port) so that it is easily
removed.
• Apply also a sufficient heat insulation to the duct and connecting part of the duct.
[Reference]Condensation test conditions
Indoor side:
Air volume: Low air volume, operation time 4 hours
27 °C dry bulb temperature
24 °C wet bulb temperature
9-EN10-EN
Page 7
Installation space(Unit: mm)
100 or
more
Air discharge
Ceiling
25
A
25
2500 or
more
B
or more
70 or
more
5 or
more
275
Inspection opening (Ceiling opening)
Floor surface
Air discharge
100 or more
450
Check port
120
Service space
(B for maintenance of air filter)
B
Ceiling
25
50 or more
Inspection opening (Ceiling opening)
570
Air intake
Air intake
570
25
Ceiling
Inspection opening (Ceiling ope ning)
Air intake
570
25
Ceiling
Inspection opening (Ceiling ope ning)
300 or more
AB
AP0076~AP0186750700
AP0246~AP03061050500
AP0366~AP05661450700
CAUTION
180
275
750
355
345
236
22
25
C
L
570
43
187.5
131
415
113.5
Main unit dimension A
Hanging bolt pitch B
External dimensions of flange C
Access panel
Electrical
control box
D
345 or more
70 or more
Drain pan / Drain
pump check cover
Reserve sufficient space required for installation or service work.
4Installation
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit or let a person get on it. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, use buffering
cloth or other material to not damage the unit.
• To move the indoor unit, hold the hooking brackets (4 positions) only.
Do not apply force to the other parts (such as refrigerant pipe, drain pan, foamed parts, or resin parts).
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other than specified.
• To install vibration isolation material to hanging bolts, confirm that it does not increase the unit vibration.
External dimensions(Unit: mm)
Filter cleaning sign term setting
The lighting term setup of the filter sign (Notification of filter cleaning) of the remote controller can be changed
according to the condition of installation.
For setup method, refer to “Filter sign setting” in the Applicable controls of this Manual.
11-EN12-EN
▼ Dimension
ABCD
AP0076~AP0186700765640750
–6–
AP0246~AP0306100010659401050
AP0366~AP05661400146513401450
Page 8
–7–
REQUIREMENT
Rubber
Anchor bolt
(Blade type
bracket)
(Slide type
bracket)
(Pipe hanging
anchor bolt)
Hanging bolt
Hanging bolt
Support angle
Nut
(W3/8 or M10)
M10 flat washer
M10 flat washer
Hanging bolt
(W3/8 or M10)
Nut
(W3/8 or M10)
0 to 5 mm
±5 mm
Set the air intake and air
discharge sides are within 5 mm
with each other.
Set the drain pipe connecting
port side within 5 mm lower
than opposite side.
Front view
Side view
CAUTION
Filter stopper (accessory)
Lower filter rail
Square hole
Fit this hook into
the square hole.
Upper filter rail
Suction board cover
Suction board cover
Hook part
Hook part
Screw
Suction board cover
Suction board cover
Screw
Installation of hanging bolt
• Consider the piping / wiring after the unit is hung to
determine the location of the indoor unit installation
and orientation.
• After the location of the indoor unit installation has
been determined, install hanging bolts.
• For the dimensions of the hanging bolt pitches, refer
to the external view.
• When a ceiling already exists, lay the drain pipe,
refrigerant pipe, control wires, and remote controller
wires to their connection locations before hanging
the indoor unit.
Procure hanging bolts washer and nuts for installing
the indoor unit (these are not supplied).
Hanging boltM10 or W3/84 pieces
NutM10 or W3/812 pieces
WasherM108 pieces
Installation of hanging bolt
Use M10 hanging bolts (4 pcs, locally procured).
Matching to the existing structure, set pitch according
to size in the unit external view as shown below.
New concrete slab
Install the bolts with insert brackets or anchor bolts.
Steel flame structure
Use existing angles or install new support angles.
Installation of indoor unit
Treatment of ceiling
The ceiling differs according to structure of building.
For details, consult your constructor or interior finish
contractor.
In the process after the ceiling board has been
removed, it is important to reinforce ceiling foundation
(frame) and to keep horizontal level of installed ceiling
correctly in order to prevent vibration of ceiling board.
• Attach the nuts and the M10 flat washers to the
hanging bolt.
• Put washers at up and down of the hanging bracket
of the indoor unit to hang down the indoor unit.
• Check that four sides are horizontal with a level
gauge. (Horizontal degree: Within 5 mm)
• Hang the unit in a horizontal position.
When unit is hanged to slant, it may cause overflow of
drainage.
• Install the unit within the dimension according to the
figure below.
• Use level gauge to confirm whether the unit is hang
horizontally.
Mounting filter rails and filters
1 Mount the filter rail so that the hooks fit into the corresponding holes.
(Note that the upper and lower filter rails are not identical.)
2 Mount the filter stopper.
When mounting the rails, push them until the 3
latches click.
3 Slide and push the filters until it stop.
* Insert the filters into the direction which the
arrows, carved on the filters, show. (2 filters
are identical)
Changing from back air intake to under air intake
1 Remove the filters on back of unit.
2 Remove the suction board cover attached to the bottom, and screw it to the back of unit.
3 Mount the supplied rail to the bottom, then set the filter.
Existing concrete slab
Use a hole-in anchors, hole-in plugs, or a hole-in bolts.
13-EN14-EN
* The sizes of the left and right covers of SM80 class unit are not identical. As shown in the figure, re-mount the
covers left-right reversed by facing the hook part upwards.
Page 9
5Drain piping
CAUTION
REQUIREMENT
1.5 m to 2 m
Support
bracket
Downward slope
1/100 or more
Arched shape
Trap
Downward slope
1/100 or more
(Collective
piping)
As long as possible
(Approx. 10 cm)
Heat
insulator
Incorrect
VP30
Flexible
drain hose
Hose band
Flexible
drain hose
Hose band
Indoor unit
10 to 12 mm
15 mm or less
10 mm
Move the drain cap from
the lower pipe to the
upper pipe.
Lower pipe
Upper pipe
Red
CN504
Black
850 or less
Drain up setup dimensions
Flexible drain hose
(supplied)
618 or less
For drain pipes that will be
connected after setup, make a
downward slope of 1/100 or more.
300 or less
Following the Installation Manual, perform the drain piping work so that water is properly drained. Apply a heat
insulation so as not to cause a dew condensation.
Inappropriate piping work may result in water leakage in the room and wet furniture.
• Provide the indoor drain piping with proper heat insulation.
• Provide the area where the pipe connects to the indoor unit with proper heat insulation. Improper heat insulation
will cause condensation to form.
• The drain pipe must be sloping downward (at an angle of 1/100 or more), and do not run the pipe up and down
(arched shape) or allow it to form traps. Doing so may cause abnormal sounds.
• Restrict the length of the traversing drain pipe to 20 meters or less. For a long pipe, provide support brackets at
intervals of 1.5 to 2 meters to prevent flapping.
• Install the collective piping as shown in the following figure.
• Do not provide any air vents. Otherwise, the drain water will spout, causing water to leak.
• Do not allow any force to be applied to the connection area with the drain pipe.
Pipe material, size and insulator
The following materials for piping work and insulating process are locally procured.
InsulatorFoamed polyethylene foam, thickness: 10 mm or more
Gravitational drainage
1 Reattach the drain cap.
* For gravitational drainage, remove the white connector
(CN504) on the upper left of the circuit board in the
electrical control box.
2 Insert flexible drain hose into lower drain pipe and
fix it with hose band.
3 Remove drain pump connector CN504.
Drain up
When a down-gradient cannot be secured for the drain pipe, drain-up
piping is possible.
• The height of the drain pipe must be 850 mm or less from the underside
of the indoor unit.
• Take the drain pipe out of the drain pipe joint with the indoor unit in 300
mm or less, and bend up the pipe vertically.
• Immediately after the pipe is bent up vertically, lay the pipe making a
down-gradient.
Connecting drain pipe
Insert flexible drain hose into upper drain pipe of main unit as far as it will go. Fix it with hose band.
Mount the flexible drain hose using the hose band without using adhesive.
15-EN16-EN
–8–
Page 10
–9–
Supply water hose
Pull out connector CN34
(Red) from P.C. board.
White
Red
Black
Black
220 V: 60 Hz
220 V to 240 V: 50 Hz
Access panel
CAUTION
Wrap the attached heat insulator tightly from
the surface of the indoor unit.
Heat insulator of the drain
connecting section
(accessory)
Indoor unit
Heat insulator
(locally procured)
Flange (locally procured)
Aluminum tape (locally procured)
Aluminum tape (locally proc ured)
Under surface
Air discharge side
Indoor unit
Air intake side
Connect a duct to the
outside of the flange
Duct: Insulation material
(locally procured)
Flange
Check the draining
In the test run, check that water drain is properly performed and water does not leak from the connecting part of
the pipes. When doing this, also check that no abnormal sounds are heard from the drain pump motor. Check
draining also when installed in heating period.
When the electrical and wiring work has been completed
Pour some water by following the method shown in the following figure. Then, while performing a cooling operation,
check that the water drains from the drain pipe connecting port (transparent) and that no water is leaking from the
drain pipe.
When the electrical and wiring work has not been completed
• Disconnect the float switch connector (3P: red) from the connector (CN34: red) on the printed circuit board inside
the electrical control box. (Before doing this, the power must be turned off.)
• Connect a 220 V to 240 V supply voltage to (L) and (N) on the power supply terminal block. (Do not apply a 220
V to 240 V voltage to (A), (B), (U
damaged.)
• Pour the water by following the method shown in the following figure. (Amount of water poured: 1500 cc to 2000
cc)
• When the power is turned on, the drain pump automatically starts running. Check whether the water is draining
from the drain pipe connecting port, and check that no water is leaking from the drain pipe.
• After checking that the water drains and there are no water leaks, turn off the power, connect the float switch
connector to its original location (CN34) on the printed circuit board, and return the electrical control box to its
original position.
1), (U2) of the terminal block. Otherwise, the printed circuit board may be
Heat insulating process
• As shown in the figure, cover the flexible hose and hose band with the attached heat insulator up to the bottom
of the indoor unit tightly.
• Cover the drain pipe tightly with a heat insulator procured locally so that it overlaps with the attached heat
insulator of the drain connecting section.
Connecting method of the duct
17-EN18-EN
Incomplete heat insulation of the supply air flange and sealing may occur dewing resulted in falling of water drop.
Page 11
Fan characteristics
0
20
40
60
80
100
120
140
200300400500600700800
External staticpressure(Pa)
Air volume(m3/h)
Standard air volume :540m3/h
Upperlimitofexternalstaticpessure(120Pa)
Lower limit of externalstaticpessure(120Pa)
High tap(120Pa)
Standard filterpressureloss
Low tap(120Pa)
High tap(100Pa)
High tap(80Pa)
High tap(65Pa)
High tap(50Pa)
High tap(40Pa)
High tap(30Pa)
Standard air volume: 540 m3/h
Upper limit of
external static
pressure (120 Pa)
High tap (120 Pa)
Lower limit of external static
pressure (120 Pa)
Low (120 Pa)
Standard filter pressure
loss
External static pressure (Pa)
Air Volume (m3/h)
High tap (100 Pa)
High tap (80 Pa)
High tap (65 Pa)
High tap (50 Pa)
High tap (40 Pa)
High tap (30 Pa)
0
20
40
60
80
100
120
140
200300400500600700800
External staticpressure(Pa)
Air volume(m3/h)
Standard air volume :570m3/h
Upper limit of externalstaticpessure(120Pa)
Lower limit of externalstaticpessure(120Pa)
High tap(120Pa)
Standard filter
pressureloss
Lowtap(120Pa)
High tap(100Pa)
High tap(80Pa)
High tap(65Pa)
High tap(50Pa)
High tap(40Pa)
High tap(30Pa)
Standard air volume: 570 m3/h
Upper limit of
external static
pressure (120 Pa)
High tap (120 Pa)
Lower limit of external static
pressure (120 Pa)
Low (120 Pa)
Standard filter
pressure loss
External static pressure (Pa)
Air Volume (m3/h)
High tap (100 Pa)
High tap (80 Pa)
High tap (65 Pa)
High tap (50 Pa)
High tap (40 Pa)
High tap (30 Pa)
0
20
40
60
80
100
120
140
380480580680780880980
External staticpressure(Pa)
Air volume(m3/h)
Standard air volume :800m3/h
Upper limit of
externalstaticpessure(120Pa)
Lower limit of externalstaticpessure(120Pa)
High tap(120Pa)
Standard filter
pressureloss
Lowtap(120Pa)
High tap(100Pa)
High tap(80Pa)
High tap(65Pa)
Hightap(50Pa)
High tap(40Pa)
High tap(30Pa)
Standard air volume: 800 m3/h
Upper limit of external
static pressure (120 Pa)
High tap (120 Pa)
Lower limit of external
static pressure (120 Pa)
Low (120 Pa)
Standard filter
pressure loss
External static pressure (Pa)
Air Volume (m3/h)
High tap (100 Pa)
High tap (80 Pa)
High tap
(65 Pa)
High tap (50 Pa)
High tap
(30 Pa)
High tap
(40 Pa)
0
20
40
60
80
100
120
140
57077097011701370
External staticpressure(Pa)
Air volume(m3/h)
Standard air volume: 1200m3/h
Upper limitofexternalstaticpessure(120Pa)
Lowerlimit ofexternalstaticpessure(120Pa)
High tap(80Pa)
Lowtap(120Pa)
Hightap(100Pa)
High tap(65Pa)
Hightap(50Pa)
High tap(120Pa)
Hightap(40Pa)
High tap(30Pa)
Standard filter
pressureloss
Standard air volume: 1200 m3/h
Upper limit of external
static pressure
(120 Pa)
High tap (120 Pa)
Lower limit of external
static pressure
(120 Pa)
Low (120 Pa)
Standard filter
pressure loss
External static pressure (Pa)
Air Volume (m3/h)
High tap
(100 Pa)
High tap
(80 Pa)
High tap
(65 Pa)
High tap
(50 Pa)
High tap
(40 Pa)
High tap
(30 Pa)
0
20
40
60
80
100
120
140
630830103012301430
External staticpressure(Pa)
Air volume(m3/h)
Standard air volume : 1260m3/h
Upperlimit ofexternalstaticpessure(120Pa)
Lowerlimitofexternalstaticpessure(120Pa)
High tap(80Pa)
Lowtap(120Pa)
Hightap(100Pa)
Hightap(65Pa)
High tap(50Pa)
High tap(120Pa)
Hightap(40Pa)
High tap(30Pa)
Standard filter
pressureloss
Standard air volume: 1260 m3/h
Upper limit of
external static
pressure (120 Pa)
High tap (120 Pa)
Lower limit of
external static
pressure (120 Pa)
Low (120 Pa)
Standard filter
pressure loss
External static pressure (Pa)
Air Volume (m3/h)
High tap
(100 Pa)
High tap
(80 Pa)
High tap
(65 Pa)
High tap (50 Pa)
High tap
(40 Pa)
High tap
(30 Pa)
0
20
40
60
80
100
120
140
9001100 1300 1500 1700 1900 2100 2300 2500
External staticpressure(Pa)
Air volume(m3/h)
Standard air volume :1920m3/h
Upperlimitofexternalstaticpessure(120Pa)
Lower limit of externalstaticpessure(120Pa)
High tap(80Pa)
High tap(100Pa)
High tap(65Pa)
High tap(50Pa)
High tap(120Pa)
High tap(40Pa)
High tap(30Pa)
Lowtap(120Pa)
Standard filter
pressureloss
Standard air volume: 1920 m3/h
Upper limit of
external static
pressure (120 Pa)
High tap (120 Pa)
Lower limit of external static
pressure (120 Pa)
Low (120 Pa)
Standard filter
pressure loss
External static pressure (Pa)
Air Volume (m3/h)
High tap (100 Pa)
High tap (80 Pa)
High tap (65 Pa)
High tap (50 Pa)
High tap (40 Pa)
High tap (30 Pa)
0
20
40
60
80
100
120
140
1000 1200 1400 1600 1800 2000 2200 2400 2600
External static pressure(Pa)
Air volume(m3/h)
Standard air volume :2100m3/h
Upperlimitofexternalstaticpessure(120Pa)
Lowerlimitofexternalstaticpessure(120Pa)
High tap(80Pa)
High tap(100Pa)
High tap(65Pa)
High tap(50Pa)
High tap(120Pa)
High tap(40Pa)
High tap(30Pa)
Standard filter
pressureloss
Lowtap(120Pa)
Standard air volume: 2100 m3/h
Upper limit of
external static
pressure (120 Pa)
High tap (120 Pa)
Lower limit of
external static
pressure (120 Pa)
Low (120 Pa)
Standard filter
pressure loss
External static pressure (Pa)
Air Volume (m3/h)
High tap (100 Pa)
High tap (80 Pa)
High tap (65 Pa)
High tap
(50 Pa)
High tap
(40 Pa)
High tap
(30 Pa)
AP0076 typeAP0096, AP0126 typeAP0156, AP0186 typeAP0246, AP0276 type
AP0306 typeAP0336 typeAP0486, AP0566 type
19-EN20-EN
–10–
Page 12
–11–
<Under air intake>
<Back air intake>
<Under air intake>
<Back air intake>
<Under air intake>
<Back air intake>
AP0076, AP0096, AP0126,
AP0156, AP0186
AP0246, AP0276, AP0306AP0366, AP0486, AP0566
6Duct design
Arrangement(Unit: mm)
Referring to the following dimensions, manufacture duct at the local site.
235.4
37.5
235.2
87.5
100
659.4
100100100100
660
100100
675
100
27
235.4
254
100 100
27
37.5
100
27
100100
254
27
87.5
100100
37.5
235.2
37.5
100100
959.4
27
254
100 100
27
37.5
100100
960
100100
100100100100
975
100100100100100
2727
100100
254
100100100
37.5
235.4
37.5
235.2
37.5
100
100
100
100100100
100
100
100
100100100
1359.4
100
1360
100
1375
254
100 100
2727
37.5
100100
100
100
100100
2727
100100
254
100
100100100100100
37.5
21-EN22-EN
Page 13
7Refrigerant piping
CAUTION
CAUTION
REQUIREMENT
REQUIREMENT
REQUIREMENT
Work using double spanner
When the refrigerant pipe is long, provide support
brackets at intervals of 2.5 m to 3 m to clamp the
refrigerant pipe. Otherwise, abnormal sound may be
generated.
Use the flare nut attached with the indoor unit or R410A
flare nut.
Permissible piping length and
height difference
They vary depending on the outdoor unit. For details,
refer to the Installation Manual attached to the outdoor
unit.
Pipe size
Model MMD-
AP007 to AP012Ø9.5Ø6.4
AP015 to AP018Ø12.7Ø6.4
AP024 to AP056Ø15.9Ø9.5
Pipe size (mm)
Gas sideLiquid side
Connecting refrigerant piping
Flaring
1. Cut the pipe with a pipe cutter.
Remove burrs completely. (Remaining burrs may
cause gas leakage.)
2. Insert a flare nut into the pipe, and flare the pipe.
Use the flare nut provided with the unit or the one
used for the R410A refrigerant. The flaring
dimensions for R410A are different from the ones
used for the conventional R22 refrigerant. A new
flare tool manufactured for use with the R410A
refrigerant is recommended, but the conventional
tool can still be used if the projection margin of the
copper pipe is adjusted to be as shown in the
following table.
Projection margin in flaring: B (Unit: mm)
Outer dia. of
copper pipe
6.4, 9.5
12.7, 15.9
R410A tool used
0 to 0.51.0 to 1.5
Flaring diameter size: A (Unit: mm)
Outer dia. of copper pipeA
6.49.1
9.513.2
12.716.6
15.919.7
Conventional
tool used
+0
–0.4
• The sealed gas was sealed at the atmospheric
pressure so when the flare nut is removed, there will
no “whooshing” sound: This is normal and is not
indicative of trouble.
• Use two wrenches to connect the indoor unit pipe.
• Use the tightening torque levels as listed in the
following table.
Outer dia. of connecting
pipe (mm)
6.414 to 18
9.534 to 42
12.749 to 61
15.963 to 77
• Tightening torque of flare pipe connections.
Pressure of R410A is higher than that of R22.
(Approx. 1.6 times) Therefore, using a torque
wrench, tighten the flare pipe connecting sections
which connect the indoor and outdoor units of the
specified tightening torque.
Incorrect connections may cause not only a gas leak,
but also a trouble of the refrigeration cycle.
Tightening with an excessive torque may crack the nut
depending on installation conditions.
Tightening torque (N•m)
Evacuation
Perform vacuuming from the charge port of valve of the
outdoor unit by using a vacuum pump.
For details, follow to the Installation Manual attached to
the outdoor unit.
• Do not use the refrigerant sealed in the outdoor unit
for evacuation.
For the tools such as charge hose, use those
manufactured exclusively for R410A.
Refrigerant amount to be added
For addition of the refrigerant, add refrigerant “R410A”
referring to the attached Installation Manual of outdoor
unit.
Use a scale to charge the refrigerant of specified
amount.
• Charging an excessive or too little amount of
refrigerant causes a trouble of the compressor.
Charge the refrigerant of specified amount.
• A personnel who charged the refrigerant should write
down the pipe length and the added refrigerant
amount in the F-GAS label of the outdoor unit. It is
necessary to fix the compressor and refrigeration
cycle malfunction.
Open the valve fully
Open the valve of the outdoor unit fully. A 4 mmhexagonal wrench is required for opening the valve.
For details, refer to the Installation Manual attached to
the outdoor unit.
Gas leak check
Check with a leak detector or soap water whether gas
leaks or not, from the pipe connecting section or cap of
the valve.
Use a leak detector manufactured exclusively for HFC
refrigerant (R410A, R134a).
* In case of flaring for R410A with the conventional
flare tool, pull it out approx. 0.5 mm more than that
for R22 to adjust to the specified flare size. The
copper pipe gauge is useful for adjusting projection
margin size.
23-EN24-EN
–12–
Page 14
–13–
REQUIREMENT
Indoor unit
Union
Heat insulation
pipe
(Accessory)
Flare nut
Heat insulator
of the pipe
Wrap the pipe with the attached heat insulator
without any gap between the indoor unit.
The seam must be faced upward
(ceiling side).
Banding band
(locally
procured)
WARNING
CAUTION
REQUIREMENT
U
1
A
B
Heat insulation process
Apply heat insulation for the pipes separately at liquid side and gas side.
• For the heat insulation to the pipes at gas side, be sure to use the material with heat-resisting temperature 120
°C or higher.
• To use the attached heat insulation pipe, apply the heat insulation to the pipe connecting section of the indoor
unit securely without gap.
• Apply the heat insulation to the pipe connecting section of the indoor unit securely up to the root without exposure of
the pipe. (The pipe exposed to the outside causes water leak.)
• Wrap heat insulator with its slits facing up (ceiling side).
8Electrical connection
• Use the specified wires for wiring connect the
terminals. Securely fix them to prevent external
forces applied to the terminals from affecting the
terminals.
Incomplete connection or fixation may cause a fire or
other trouble.
• Connect earth wire. (grounding work)
Incomplete grounding cause an electric shock.
Do not connect earth wires to gas pipes, water pipes,
lightning conductor or telephone earth wires.
• Appliance shall be installed in accordance with
national wiring regulations.
Capacity shortage of power circuit or incomplete
installation may cause an electric shock or a fire.
• If incorrect/incomplete wiring is carried out, it will
cause an electrical fire or smoke.
• Use the cord clamps attached to the product.
• Do not damage or scratch the conductive core and
inner insulator of power and system interconnection
wires when peeling them.
• Use the power cord and system interconnection wire
of specified thickness, type, and protective devices
required.
• Do not connect 220 V – 240 V power to the terminal
blocks ( , , , ) for control wiring. (Otherwise,
the system will fail.)
• Perform the electric wiring so that it does not come to
contact with the high-temperature part of the pipe.
The coating may melt resulting in an accident.
U
2
Power supply wire and
communication wires
specifications
Power supply wire and communication wires are
procured locally.
For the power supply specifications, follow to the
following table. If capacity is little, it is dangerous
because overheat or burnout may be caused.
For specifications of the power capacity of the outdoor
unit and the power supply wires, refer to the Installation
Manual attached to the outdoor unit.
Indoor unit power supply
• For the power supply of the indoor unit, prepare the
exclusive power supply separated from that of the
outdoor unit.
• Arrange the power supply, circuit breaker, and main
switch of the indoor unit connected to the same
outdoor unit so that they are commonly used.
• Power supply wire specification: Cable 3-core 2.5
mm², in conformity with Design 60245 IEC 57.
• For power supply wiring, strictly conform to the Local
Regulation in each country.
• For wiring of power supply of the outdoor units, follow
the Installation Manual of each outdoor unit.
• Perform the electric wiring so that it does not come to
contact with the high-temperature part of the pipe.The
coating may melt resulting in an accident.
• After connecting wires to the terminal blocks, provide
25-EN26-EN
a trap and fix wires with the cord clamp.
• Run the refrigerant piping line and contr ol wiring line in
the same line.
• Do not turn on the power of the indoor unit until
vacuuming of the refrigerant pipes completes.
Page 15
▼ Power supply
CAUTION
L1
L
L2Ln
Indoor unit
Remote controller inter-unit wiring
Indoor unitIndoor unitIndoor unit
Remote
controller
(Max. 8 units)
Remote
controller
wiring
NOTE
Outdoor Power supply
380 V - 415 V ~, 50 Hz
380 V ~, 60 Hz
Circuit breaker,
Power switch
Remote controller
Indoor unit
Outdoor Power supply
380 V - 415 V ~, 50 Hz
380 V ~, 60 Hz
Remote controllerRemote controller
Indoor unitIndoor unitIndoor unit
Circuit breakerCircuit breaker
Header outdoor
unit
Follower outdoor
unit
Control wiring between outdoor units
Control wiring between indoor and outdoor units
Control wiring between indoor units
Indoor power supply
220 V - 240 V ~, 50 Hz
220 V ~, 60 Hz
EarthEarthEarthEarth
Group control
Pull boxPull boxPull box
Earth
terminal
Earth
terminal
Power supply
Power supply switch/circuit breaker or power supply wiring/fuse rating for indoor units should be selected by the accumulated
total current values of the indoor units.
Power supply wiringBelow 50 m2.5 mm
220 V – 240 V ~, 50 Hz
220 V ~, 60 Hz
2
Wiring between indoor unit and outdoor unit
An outdoor unit connected with control wiring between indoor and outdoor units wire becomes automatically the
header unit.
Control wiring, Central controller wiring
• 2-core with polarity wires are used for the Control wiring between indoor unit and outdoor unit and Central
controller wiring.
• To prevent noise trouble, use 2-core shield wire.
• The length of the communication line means the total length of the inter-unit wire length between indoor and
outdoor units added with the central control system wire length.
▼ Communication line
Control wiring between indoor units, and
outdoor unit (2-core shield wire)
Central control line wiring (2-core shield
wire)
Wire size
Wire size
(Up to 1000 m) 1.25 mm²
(Up to 2000 m) 2.0 mm²
(Up to 1000 m) 1.25 mm²
(Up to 2000 m) 2.0 mm²
Remote controller wiring
• 2-core with non-polarity wire is used for wiring of the remote controller wiring and group remote controllers wiring.
Total wire length of remote controller wiring and remote
controller inter-unit wiring = L + L1 + L2 + … Ln
Total wire length of remote controller inter-unit wiring = L1 + L2 + … LnUp to 200 m
The remote controller wire (Communication line) and AC 220 – 240 V wires cannot be parallel to contact
each other and cannot be stored in the same conduits. If doing so, a trouble may be caused on the control
system due to noise or other factor.
Wire size: 0.5 mm² to 2.0 mm²
In case of wired type onlyUp to 500 m
In case of wireless type
included
Up to 400 m
▼ Wiring example
U1 U2 U3 U4L1 L2 L3 NU5U6
U1 U2
LNAB
AB
U1 U2LNAB
AB
U1 U2 U3 U4L1 L2 L3 NU5U6
U1 U2LNAB
AB
U1 U2LNAB
27-EN28-EN
–14–
Page 16
–15–
REQUIREMENT
Remove screw A.
Loosen screw B.
Electrical control
box cover
NL
BA
System interconnection
wire
Cord clamp
Remote controller
wiring
Earth screw
Select side C or D for the power cable clamping position referring t o
the following table according to the cable type and diameter.
* Cable clamp can be attached on either right or left side.
When twin system are connected, clamp two cab les with one cable
clamp.
Wire typeSpecificationCable clamping position
Cabtyre cable 3-core stranded wire 2.5 mm²Side D
Cabtyre cable 4-core stranded wire 1.5 mm²Side C
Side D (Space: 8.5 mm)
Side C (Space: 4 mm)
System interconnection wire
Earth wire
2 mm or
less
System interconnection wire
See the figure on the lef t for
system interconnection wires to
the terminal block.
A
B
A
B
Terminal block
Remote
controller
unit
Terminal block for remote
controller wiring of indoor unit
Remote controller wire
(Locally procured)
REQUIREMENT
CAUTION
1
6
1
3
2
5
4
(* Display content varies with the indoor unit
model.)
Wire connection
• Connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
• Pass the wires through the bushing of wire connection holes of the indoor unit.
• Keep a margin (Approx. 100 mm) on a wire to hang down the electrical control box at servicing or other purpose.
• The low-voltage circuit is provided for the remote controller. (Do not connect the high-voltage circuit)
•
• Before performing wiring work in the electrical control box, remove the
cover of the box (fixed with 2 screws).
• Remove screw A, and loosen screw B.
• Pull up the electrical control box cover and then open it forward.
• Tighten the screws of the terminal block firmly, and fix the wires with
the cord clamps attached to the electrical control box. (Do not apply
tension to the connecting section of the terminal block.)
1
2
• Slide the electrical control box cover to install it. Do not pinch the wire
too strong, and reduce the load on the wire. Make the gap as small as
possible when installing the cover.
R
(L)S(N)
10
70
10
30
Remote controller wiring
Strip off approx. 9 mm the wire to be connected.
Wiring diagram
9Applicable controls
When the air conditioner is used for the first time, it will
take some moments after the power has been turned on
before the remote controller becomes available for
operations: This is normal and is not indicative of trouble.
• Concerning the automatic addresses (The automatic
addresses are set up by performing operations on the
outdoor interface circuit board.)
While the automatic addresses are being set up, no
remote controller operations can be performed. Setup
takes up to 10 minutes (usually about 5 minutes).
• When the power is turned on after automatic address
setup
It takes up to 10 minutes (usually about 3 minutes) for
the outdoor unit to start operating after the power has
been turned on.
Before the air conditioner was shipped from the factory,
all units are set to [STANDARD] (factory default). If
necessary, change the indoor unit settings.
The settings are changed by operating the wired remote
controller.
* The settings cannot be changed using only a
wireless remote controller, simple remote controller
or group control remote controller by itself so install
a wired remote controller separately as well.
Basic procedure for changing
settings
Change the settings while the air conditioner is not
working. (Stop the air conditioner before making
settings.)
Set only the CODE No. shown in the following table: Do
NOT set any other CODE No.
If a CODE No. not listed is set, it may not be possible to
operate the air conditioner or other trouble with the
product may result.
* The displays appearing during the setting process
differ from the ones for previous remote controllers
(AMT31E). (There are more CODE No.)
1 Push and hold button and “TEMP.”
button simultaneously for 4 seconds or
more. After a while, the display flashes as
shown in the figure. Confirm that the CODE
No. is [01].
• If the CODE No. is not [01], push button to
clear the display content, and repeat the
procedure from the beginning. (No operation of
the remote controller is accepted for a while
after button is pushed.)
(While air conditioners are operated under the
group control, “ALL” is displayed first. When
is pushed, the indoor unit number
displayed following “ALL” is the header unit.)
29-EN30-EN
Page 17
2 Each time button is pushed, indoor
SW501
SW501-1OFFONOFFON
SW501-2OFFOFFONON
SET DATA
Factory
default
000100030006
To reset to the factory default
Switch off SW501-1 and SW501-2, connect a separately-sold
wired remote controller, and then perform the procedure for
installing a separately-sold filter on this page to set the [5d] data
to "0000".
unit numbers in the control group change
cyclically. Select the indoor unit to change
settings for.
The fan of the selected unit runs and the louvers
start swinging. The indoor unit for change settings
can be confirmed.
3 Specify CODE No. [] with “TEMP.” /
buttons.
4 Select SET DATA [] with “TIME” /
buttons.
5 Push button. When the display changes
from flashing to lit, the setup is completed.
• To change settings of another indoor unit,
repeat from Procedure
• To change other settings of the selected indoor
unit, repeat from Procedure
• Use button to clear the settings. To make
settings after button was pushed, repeat
from Procedure
2.
3.
2.
6 When settings have been completed, push
button to determine the settings.
When button is pushed, flashes
and then the display content disappears and
the air conditioner enters the normal stop
mode.
(While is flashing, no operation of the
remote controller is accepted.)
External static pressure
settings
<Change on wired remote controller>
Set up a tap change based upon the external static
pressure of the duct to be connected.
To set up a tap change, follow to the basic operation
procedure (
• Specify [5d] to the CODE No. in procedure
• For the SET DATA of procedure
SET DATAExternal static pressure
The list above is when SW501-1 and SW501-2 is OFF.
If the setting is wrong, "P12" may appear indicating a
fan motor error.
1 → 2 → 3 → 4 → 5 → 6).
3.
4, select a SET
DATA of the external static pressure to be set up
from the following table.
000040 Pa
000130 Pa
000265 Pa—
000350 Pa
000480 Pa—
0005100 Pa—
0006120 Pa—
AP024 to 030
(Factory default)
AP007 to 018
(Factory default)
AP036 to 058
(Factory default)
<Setting up on the circuit board of the indoor unit>
To set up the external static pressure, use the DIP switch on the circuit board of the wireless reception part.
For details, refer to the instruction manual of the wireless remote controller kit. Alternatively, use the switch on the
indoor micro computer circuit board as shown in the following figure and table.
31-EN32-EN
–16–
Page 18
–17–
CAUTION
2, 4
3
1,5
Filter sign setting
According to the installation condition, the filter sign
term (Notification of filter cleaning) can be changed.
Follow to the basic operation procedure
(
1 → 2 → 3 → 4 → 5 → 6).
• For the CODE No. in Procedure
• For the [SET DATA] in Procedure
DATA of filter sign term from the following table.
SET DATAFilter sign term
0000None
0001150 H
0002
00035000 H
000410000 H
3, specify [01].
4, select the SET
2500 H
(Factory default)
To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator or other device to circulate
heat air near the ceiling.
Follow to the basic operation procedure
(
1 → 2 → 3 → 4 → 5 → 6).
• For the CODE No. in Procedure
• For the SET DATA in Procedure
DATA of shift value of detection temperature to be
set up from the following table.
SET DATADetection temperature shift value
0000No shift
0001+1 °C
0002
0003+3 °C
0004+4 °C
0005+5 °C
0006+6 °C
3, specify [06].
4, select the SET
+2 °C
(Factory default)
Remote controller sensor
The temperature sensor of the indoor unit senses room
temperature usually. Set the remote controller sensor
to sense the temperature around the remote controller.
Select items following the basic operation procedure
(
1 → 2 → 3 → 4 → 5 → 6 ).
• Specify [32] for the CODE No. in Procedure
• Select the following data for the SET DATA in
Procedure
SET DATA00000001
Remote controller
sensor
When flashes, the remote controller sensor is
defective.
Select the SET DATA [0000] (not used) or replace the
remote controller.
4.
(Factory default)
Not used
3.
Used
Group control
In a group control, a remote controller can control up to
maximum 8 units.
• The wired remote controller only can control a group
control. The wireless remote controller is unavailable
for this control.
• For wiring procedure and wires of the individual line
(Identical refrigerant line) system, refer to “Electrical
Connection” in this Manual.
• Wiring between indoor units in a group is performed
in the following procedure.
• Connect the indoor units by connecting the remote
controller wires from the remote controller terminal
blocks (A, B) of the indoor unit connected with a
remote controller to the remote controller terminal
blocks (A, B) of the other indoor unit. (Non-polarity)
• For address setup, refer to the Installation Manual
attached to the outdoor unit.
10Test run
Before test run
• Before turning on the power supply, carry out the
following procedure.
1) By using 500 V-megger, check that resistance
of 1 MΩ or more exists between the terminal
block L to N and the earth (grounding).
If resistance of less than 1 MΩ is detected, do
not run the unit.
2) Check the valve of the outdoor unit being
opened fully.
• To protect the compressor at activation time, leave
power-ON for 12 hours or more before operating.
• Do not press the electromagnetic contactor to
forcibly perform a test run. (This is very dangerous
because the protective device does not work.)
• Before starting a test run, set addresses by following
the Installation Manual supplied with the outdoor
unit.
Execute a test run
• When a fan operation is to be performed for an
individual indoor unit, turn off the power, short CN72
on the circuit board, and then turn the power back
on. (First set the operating mode to “fan,” and then
operate.) When the test run has been performed
using this method, do NOT forget to release the
shorting of CN72 after the test run is completed.
Operate the unit with the wired remote controller as
usual.
For the procedure of the operation, refer to the
attached Owner’s Manual to the outdoor unit.
A forced test run can be executed in the following
procedure even if the operation stops by thermostatOFF.
In order to prevent a serial operation, the forced test
run is released after 60 minutes have passed and
returns to the usual operation.
Do not use the forced test run for cases other than the
test run because it applies an excessive load to the
devices.
Wired remote controller
1 Push button for 4 seconds or more.
[TEST] is displayed on the display part and
the selection of mode in the test mode is
permitted.
2 Push button.
3 Select the operation mode with
button, [ Cool] or [ Heat].
• Do not run the air conditioner in a mode other
than [ Cool] or [ Heat].
• The temperature controlling function does not
work during test run.
• The detection of error is performed as usual.
4 After the test run, push button to
stop a test run.
(Display part is same as procedure 1.)
5 Push button to cancel (release from) the
test run mode.
([TEST] disappears on the display and the status
returns to a normal.)
33-EN34-EN
Page 19
Wireless remote controller
TEMPORARY button
WARNING
CAUTION
3
1,2
1 When TEMPORARY button is pushed for 10
seconds or more, “Pi!” sound is heard and
the operation changes to test run. After
approx. 3 minutes, a cooling operation starts
forcedly.
Check cool air starts blowing. If the operation does
not start, check wiring again.
2 To stop a test operation, push TEMPORARY
button once again (Approx. 1 second).
Check wiring / piping of the indoor and outdoor
units in test run.
When a test run is not
performed properly
• When a test run is not performed properly, refer to
the error code and the part to be checked on
“Troubleshooting”.
• When a test run is executed before installing the
external duct, a protection control may be activated
and lets the unit stop and the code P12 may be
displayed. (This is not due to a malfunction but to the
current control function of the DC motor in this unit.)
When a test run executed before installing the
external duct, select “Low” for the fan speed level or
cover the air discharge.
• In addition, stop the operation before replacing the
High-efficiency filter or opening the service panel.
After the test run, reset the circuit breaker of the
indoor unit.
11Maintenance
<Daily maintenance> (Once every 3 months)
▼ Cleaning of air filter
If is displayed on the remote controller, maintain the air filter.
1 Push the button to stop the operation, then
turn off the circuit breaker.
1. Take out the air filter.
• Slide and remove the filter as shown in the following figure:
When the first filter comes out without connected to the other one, insert it once more to connect the two filters together
and pull out them as connected. Do not insert hands to take out the second filter. You may injure yourself.
2. Cleaning with water or vacuum cleaner
• If dirt is heavy, clean the air filter by tepid water with neutral detergent or water.
• After cleaning with water, dry the air filter sufficiently in a shade place.
3. Mount the air filter.
* Insert the filters into the direction which the arrows, carved on the filters, show. (2 filters are identical)
2 Turn on the circuit breaker, then push the button on the remote controller to start the
operation.
3 After cleaning, push .
display disappears.
• Do not start the air conditioner while leaving air filter removed.
• Push the filter reset button. ( indication will be turn off.)
35-EN36-EN
–18–
Page 20
–19–
REQUIREMENT
Error codeIndoor UNIT No. in
which an error occurred
▼ Periodic Maintenance
For environmental conservation, it is strongly recommended that the indoor and outdoor units of the air conditioner
in use be cleaned and maintained regularly to ensure efficient operation of the air conditioner.
When the air conditioner is operated for a long time, periodic maintenance (once a year) is recommended.
Furthermore, regularly check the outdoor unit for rust and scratches, and remove them or apply rustproof
treatment, if necessary.
As a general rule, when an indoor unit is operated for 8 hours or more daily, clean the indoor unit and outdoor unit
at least once every 3 months. Ask a professional for this cleaning / maintenance work.
Such maintenance can extend the life of the product though it involves the owner’s expense.
Failure to clean the indoor and outdoor units regularly will result in poor performance, freezing, water leakage, and
even compressor failure.
▼ Inspection before maintenance (Once a year)
Following inspection must be carried out by a qualified installer or qualified service person.
PartsInspection method
Heat exchanger
Fan motorAccess from inspection opening and check if any abnormal noise can be heard.
Fan
FilterAccess from check port and check if there are any stains or breaks on the filter.
Drain pan
Access from inspection opening and remove the access panel. Examine the heat exchanger if there
is any clogging or damages.
Access from inspection opening and remove the access panel. Examine the fan if there are any
waggles, damages or adhesive dust.
Access from inspection opening and remove the access panel. Check if there is any clogging or drain
water is polluted.
Take appropriate measures when
abnormal sound is generated.
• Wash the filter with water when it is
contaminated.
• Replace it when it is damaged.
• Replace the fan when vibration or
balance is terrible.
• Brush or wash the fan when it is
contaminated.
Fix or replace them when they are
deformed or damaged.
Clean the drain pan and check the
downward slope for smooth drainage.
Wash them when they are contaminated
or apply repair coating.
Apply repair coating.
12Troubleshooting
Confirmation and check
When an error occurred in the air conditioner, an error
code and indoor UNIT No. appear on the display part
of the remote controller.
The error code is only displayed during the operation.
If the display disappears, operate the air conditioner
according to the following “Confirmation of error log” for
confirmation.
Confirmation of error log
When an error occurred on the air conditioner, the error
log can be confirmed with the following procedure.
(The error log is stored in memory up to 4 errors.)
The log can be confirmed from both operating status
and stop status.
2
3
1
1 When and buttons are pushed
simultaneously for 4 seconds or more, the
following display appears.
If is displayed, the mode enters in the error log
mode.
•[01: Order of error log] is displayed in CODE
No..
• [Error code] is displayed in CHECK.
• [Indoor unit address in which an error occurred]
is displayed in Unit No..
2 Every pushing of button used to set
temperature, the error log stored in memory
is displayed in order.
The numbers in CODE No. indicate CODE No.
[01] (latest) → [04] (oldest).
Do not push button because all the error log of the
indoor unit will be deleted.
3 After confirmation, push button to return
to the usual display.
37-EN38-EN
Page 21
Check method
On the wired remote controller, central control remote controller and the interface P.C. board of the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C. board) to display the operation
is provided. Therefore the operation status can be known. Using this self-diagnosis function, a trouble or position with error of the air conditioner can be found as shown in the following table.
Check code list
The following list shows each check code. Find the check contents from the list according to part to be checked.
• In case of check from indoor remote controller: See “Wired remote controller display” in the list.
• In case of check from outdoor unit: See “Outdoor unit 7-segment display” in the list.
• In case of check from AI-NET central control remote controller: See “AI-NET central control display” in the list.
• In case of check from indoor unit with a wireless remote controller: See “Sensor block display of receiving unit” in the list.
01:TK1 oil circuit system error
02:TK2 oil circuit system error
03:TK3 oil circuit system error
04:TK4 oil circuit system error
05:TK5 oil circuit system error
AI-NET central
control display
18ALT
43ALTTH sensor errorIPDU
IFCompressor break downIPDU
1dCompressor trouble (lock)IPDU
17Current detect circuit system errorIPDU
d4Oil level detective temp sensor errorI/F
d7Oil level detective circuit errorI/F
Sensor block display of receiving unit
TE1 sensor error
TE2 sensor error
Check code nameJudging device
I/F
Page 23
Check codeWireless remote controller
Wired remote
controller display
L05——96SIMDuplicated indoor units with priority (Displayed in indoor unit with priority)I/F
L06L06 No. of indoor units with priority96SIM
L07——99SIMGroup line in individual indoor unitIndoor unit
L08L08—99SIMIndoor unit group/Address unsetIndoor unit, I/F
L09——46SIMIndoor unit capacity unsetIndoor unit
L10L10—88SIMOutdoor unit capacity unsetI/F
L17——46SIMOutdoor unit type mismatch errorI/F
L20——98SIMDuplicated central control addressesAI-NET, Indoor unit
L26L26 Number of heat storage units connected46SIMToo many heat storage units connectedI/F
L27L27 Number of heat storage units connected46SIMError in number of heat storage units connectedI/F
L28L28—46SIMToo many outdoor units connectedI/F
L29L29 Number of IPDU (*1)CFSIMNo. of IPDU errorI/F
L30L30 Detected indoor unit addressb6SIMIndoor unit outside interlockIndoor unit
—L31———Extended I/C errorI/F
P01——11ALTIndoor fan motor errorIndoor unit
P03P03—1EALTDischarge temp. TD1 errorI/F
P04P04
P05P05
P07P07
P09P09 Detected heat storage address47ALTNo heat storage unit water errorHeat storage unit
P10P10 Detected indoor unit addressObALTIndoor unit overflow errorIndoor unit
P12——11ALTIndoor unit fan motor errorIndoor unit
P13P13—47ALTOutdoor liquid back detection errorI/F
P15P15
P17P17—bbALTDischarge temp. TD2 errorI/F
P18P18—E2ALTDischarge temp. TD3 errorI/F
P19P19 Detected outdoor unit numberO8ALT4-way valve inverse errorI/F
P20P20—22ALTHigh-pressure protective operationI/F
P22P22
P26P26
Outdoor unit 7-segment display
Auxiliary codeOperationTimerReadyFlash
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
00:
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
01:TS condition
02:TD condition
0*:IGBT circuit
1*:Position detective circuit error
3*:Motor lock error
4*:Motor current detection
C*:TH sensor error
D*:TH sensor error
E*:Inverter DC voltage error (outdoor unit
fan)
01:Comp. 1 side
02:Comp. 2 side
03:Comp. 3 side
AI-NET central
control display
21ALTHigh-pressure SW system operationIPDU
AFALT
ICALTHeat sink overheat errorIPDU, I/F
AEALTGas leak detectionI/F
1AALT
14ALTG-TR short protection errorIPDU
Sensor block display of receiving unit
Duplicated indoor units with priority (Displayed in unit other than indoor unit
with priority)
Phase missing detection/Power failure detection
Inverter DC voltage error (comp.)
Inverter DC voltage error (comp.)
Inverter DC voltage error (comp.)
Outdoor unit fan IPDU error
Note: Ignore 0 to F displayed in “*” position.
Check code nameJudging device
I/F
I/F
IPDU
43-EN44-EN
–22–
Page 24
Check codeWireless remote controller
Wired remote
controller display
P29P29
P31——47ALT
———b7By alarm deviceALTError in indoor unit groupAI-NET
Commercial name:Super Modular Multi System Air Conditioner
Complies with the provisions of the “Machinery” Directive (Directive 2006/42/EC) and the regulations transposing
into national law
“Declaration of incorporation of partly completed machinery”
Must not be put into service until the final machinery into which it is to be incorporated has been declared in
conformity with the provisions of this Directive, where appropriate.
336 Tadehara, Fuji-shi, Shizuoka-ken 416-8521 JAPAN
Nick Ball
Toshiba EMEA Engineering Director
Toshiba Carrier UK Ltd.
Porsham Close, Belliver Industrial Estate,
PLYMOUTH, Devon, PL6 7DB.
United Kingdom
Super Heat Recovery Multi System Air Conditioner
Mini-Super Modular Multi System Air Conditioner (MiNi-SMMS series)
Complies with the provisions of the following harmonized standard:
EN 378-2: 2008+A1: 2009
This declaration becomes invalid if technical or operational modifications are introduced without the manufacturer’s
consent.
47-EN48-EN
–24–
Page 26
Warnings on Refrigerant Leakage
e.g., charged amount (10 kg)
e.g., charged amount (15 kg)
Outdoor unit
Indoor unit
Room A Room B Room C Room D Room E Room F
Important
Refrigerant piping
Indoor unit
Outdoor unit
Outdoor unit
Very small room
Refrigerant piping
Indoor unit
Mechanical ventilation device - Gas leak detector
Small
room
Medium
room
Large room
0
5
10
102030
15
20
25
30
35
40
m
2
kg
Min. indoor floor area
Range above the
density limit of 0.3 kg/m
3
(countermeasures
needed)
Range below the
density limit of
0.3 kg/m
3
(countermeasures
not needed)
Total amount of refrigerant
Check of concentration limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant
gas leaking out, its concentration will not exceed a set limit.
The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia,
and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than
air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A
is almost non-existent. With the recent increase in the number of high concentration buildings, however, the
installation of multi air conditioner systems is on the increase because of the need for effective use of floor space,
individual control, energy conservation by curtailing heat and carrying power etc.
Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with
conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small
room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its
concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can
occur).
In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install
mechanical ventilation combined with a gas leak detection device.The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m
≤ Concentration limit (kg/m
3
3
)
)
–25–
2) When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening
without a door, or an opening 0.15 % or larger than the respective floor spaces at the top or bottom of the
door).
3) If an indoor unit is installed in each partitioned room and the refrigerant piping is interconnected, the
smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with
a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next
smallest room becomes the object.
The concentration limit of R410A which is used in multi air conditioners is 0.3 kg/m
3
.
▼ NOTE 1
If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as
charged in each independent device.
▼ NOTE 3
The minimum indoor floor area compared with the amount of refrigerant is roughly as follows:
(When the ceiling is 2.7 m high)
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A, B and C is 10 kg.
49-EN50-EN
The possible amount of leaked refrigerant gas in rooms D, E and F is 15 kg.
▼ NOTE 2
The standards for minimum room volume are as follows.
1) No partition (shaded portion)
Page 27
REQUIREMENT
Confirmation of indoor unit setup
(For check method, refer to APPLICABLE CONTROLS in this manual.)
Others ( )
Incorporation of parts sold
Panel
Standard panel
Others ( )
Others ( )
Panel
Standard panel
Others ( )
Others ( )
Panel
separately
separately
separately
Incorporation of parts sold
Incorporation of parts sold
+5°C[0005]
+6°C[0006]
+5°C[0005]
+6°C[0006]
+3°C[0003]
+4°C[0004]
+3°C[0003]
+4
°C[0004]
+2°C[0002]
+2°C[0002]
NO SHIFT[0000]
+1°C[0001]
+1
NO SHIFT[0000]
°C[0001]
Detected temp. shift value setup
2500H[0002]
5000H[0003]
2500H[0002]
5000H[0003]
NONE[0000]
150H[0001]
NONE[0000]
150H[0001]
CHANGE
NO CHANGE
NO CHANGE
(CODE NO. [06])
Detected temp. shift value setup
Detected temp. shift value setup
10000H[0004]
10000H[0004]
NO CHANGE
(CODE NO. [06])
NO CHANGE
(CODE NO. [06])
NO
NONE[0000]
150H[0001]
2500H[0002]
5000H[0003]
10000H[0004]
Have you changed detected temp. shift value? If not, fill check mark [×] in [NO CHANGE], and fill check mark [×] in [ITEM] if changed, respectively.
(For check method, refer to APPLICABLE CONTROLS in this manual.)
NO CHANGE
NO SHIFT[0000]
+1°C[0001]
+2°C[0002]
+3°C[0003]
+4°C[0004]
+5°C[0005]
+6°C[0006]
Have you incorporated the following parts sold separately? If incorporated, fill check mark [×] in each [ITEM].
(When incorporating, the setup change is necessary in some cases. For setup change method, refer to Installation Manual attached to each part sold
separately.)
Standard panel
Others ( )
(CODE NO. [01])
(CODE NO. [01])
(CODE NO. [01])
Filter sign lighting time
Filter
sign lighting time
Filter sign lighting time
Have you changed lighting time of filter sign? If not, fill check mark [×] in [NO CHANGE], and fill check mark [×] in [ITEM] if changed, respectively.
STATIC 4[0004]
STATIC 5[0005]
STATIC 6[0006]
STATIC 4[0004]
STATIC 5[0005]
STATIC 6[0006]
STATIC 6[0006]
STATIC 5[0005]
STATIC 4[0004]
STATIC 2[0002]
STATIC 3[0003]
STATIC 2[0002]
STATIC 3[0003]
STATIC 3[0003]
STATIC 2[0002]
STATIC 1[0001]
STATIC 1[0001]
STATIC 1[0001]
NO CHANGE
STANDARD[0000]
NO CHANGE
STANDARD[0000]
NO CHANGE
STANDARD[0000]
(CODE NO. [5d])
(CODE NO. [5d])
(CODE NO. [5d])
External static pressure
External static pressure
External static pressure
setup is automatically changed.
(For check method, refer to APPLICABLE CONTROLS in this manual.) * In case of replacement of jumper blocks on indoor microcomputer P.C. board,
Have you changed high ceiling setup? If not, fill check mark [×] in [NO CHANGE], and fill check mark [×] in [ITEM] if changed, respectively.
Various setupVarious setupVarious setupVarious setup
Central control addressCentral control addressCentral control addressCentral control address
*In case of a single system, it is unnecessary to enter the indoor address. (CODE NO.: Line [12], Indoor [13], Group [14], Central control [03])
Check indoor unit address. (For check method, refer to APPLICABLE CONTROLS in this manual.)
Room nameRoom nameRoom nameRoom name
Indoor unit setup check sheet
Indoor unitIndoor unitIndoor unitIndoor unit
This check sheet is required for maintenance after installation. Fill this sheet and then pass this Installation Manual to the customers.
Data of four units can be entered in this check sheet. Copy this sheet according to the No. of the indoor units. If the installed system is a group control system, use
this sheet by entering each line system into each installation manual attached to the other indoor units.
Prior to delivery to the customer, check the address and setup of the indoor unit, which has been installed in this time and fill the check sheet (Following table).
Detected temp. shift value setup
10000H[0004]
(CODE NO. [01])
–26–
Others ( )
Others ( )
Standard panel
Panel
51-EN52-EN
+6°C[0006]
Incorporation of parts sold
(CODE NO. [06])
separately
NO CHANGE
NO SHIFT[0000]
+1°C[0001]
+2°C[0002]
+3°C[0003]
+4°C[0004]
+5°C[0005]
NO CHANGE
NONE[0000]
150H[0001]
2500H[0002]
5000H[0003]
STATIC 6[0006]
Filter sign lighting time
External static pressure
(CODE NO. [5d])
NO CHANGE
STANDARD[0000]
STATIC 1[0001]
STATIC 2[0002]
STATIC 3[0003]
STATIC 4[0004]
STATIC 5[0005]
Page 28
EH99892399
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.