Toshiba MCY-MHP0806HS8-E, MCY-MHP1006HS8-E User Manual

Page 1
2FAN_IM_DHV2305601-00_EN.book Page 1 Monday, October 28, 2019 3:25 PM
AIR CONDITIONER (MULTI TYPE)
Installation Manual
DHV2305601-00
English
Outdoor Unit
Model name:
Heat Pump Model
MCY-MHP0806HS8-E MCY-MHP1006HS8-E
Page 2
2FAN_IM_DHV2305601-00_EN.book Page 1 Monday, October 28, 2019 3:25 PM
Original instruction
ADOPTION OF NEW REFRIGERANT
This Air Conditioner uses R410A an environmentally friendly refrigerant.
– 1 –
Installation Manual
Contents
1 Precautions for Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Accessory Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3 Installation of New Refrigerant Air Conditioner . . . . . . . . . . . . . . . . . 8
4 Installation Conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
5 Refrigerant Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
6 Electric Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
7 Address Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
8 Test Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
9 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
EN-1 EN-2
Page 3
2FAN_IM_DHV2305601-00_EN.book Page 2 Monday, October 28, 2019 3:25 PM
Installation Manual
Thank you for purchasing this Toshiba air conditioner. This Installation Manual describes the installation method of the outdoor unit. For installation of indoor units, follow the Installation Manual supplied with the indoor unit. Moreover, as this installation manual includes the important articles concerning the “Machinery” Directive (Directive 2006/42/EC), please read through the manual and make sure you understand it. After installation, give this Installation Manual, the Owner’s Manual and the Installation Manual supplied with the indoor unit to the customer and tell the customer to keep them safe. Prepare an exclusive power source for indoor units, independent to that for outdoor units. Y-shaped branching joints or a branching header (separately purchased) are required for connecting pipes between indoor and outdoor units. Choose either of them considering the system capacity concerning piping. For installing branching pipes, refer to the installation manual of the Y-shaped branching unit or branching header (separately purchased).
Generic Denomination: Air Conditioner
Definition of Qualified Installer or Qualified Service Person
The air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified service person. When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you. A qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the table below.
Agent Qualifications and knowledge which the agent must have
Qualified installer
• The qualified installer is a person who installs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified installer who is allowed to do the electrical work involved in installation, relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
Qualified service person
• The qualified service person is a person who installs, repairs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, repair, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified service person who is allowed to do the electrical work involved in installation, repair, relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to do the refrigerant handling and piping work involved in installation, repair, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
Definition of Protective Gear
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing. In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below. Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns, electric shocks and other injuries.
Work undertaken Protective gear worn
All types of work Protective gloves
Electrical-related work
Work done at heights (50 cm or more)
Transportation of heavy objects
Repair of outdoor unit
‘Safety’ working clothing
Gloves to provide protection for electricians Insulating shoes Clothing to provide protection from electric shock
Helmets for use in industry
Shoes with additional protective toe cap
Gloves to provide protection for electricians
EN
EN-3 EN-4
– 2 –
Page 4
CAUTION
Do not touch the aluminum fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
Never recover the refrigerant into the outdoor outdoor unit.
01_IM_DHV2305601-00_EN.fm Page 3 Thursday, December 5, 2019 5:00 PM
Warning Indications on the Air Conditioner Unit
Warning indication Description
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
CAUTION
High temperature parts. You might get burned when removing this panel.
– 3 –
CAUTION
Do not climb onto the top side.
Doing so may result in injury.
Installation Manual
CAUTION BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst. Never recover the refrigerant into the outdoor outdoor unit.
CAUTION Do not climb onto the fan guard.
Doing so may result in injury.
EN-5 EN-6
CAUTION
Do not touch the aluminum fins of the unit. Doing so may result in injury.
Page 5
WARNING
01_IM_DHV2305601-00_EN.fm Page 4 Wednesday, November 27, 2019 11:26 AM
Installation Manual
1 Precautions for Safety
The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual.
General
• Before starting to install the air conditioner, read through the Installation Manual carefully, and follow its instructions to install the air conditioner. Otherwise, falling down of the unit may occur, or the unit may cause noise, vibration or water leakage.
• Only a qualified installer or qualified service person is allowed to do installation work. If installation is carried out by an unqualified individual, a fire, electric shocks, injury, water leakage, noise and / or vibration may result.
• Do not use any refrigerant different from the one specified for complement or replacement. Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or an injury to your body.
• If using separately sold products, make sure to use Toshiba specified products only. Using unspecified products may cause fire, electric shock, water leak or other failure.
• Before opening the service panel of the outdoor unit, set the circuit breaker to the OFF position. Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with the interior parts. Only a qualified installer or qualified service person is allowed to remove the service panel of the outdoor unit and do the work required.
• Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breakers for both the indoor and outdoor units to the OFF position. Otherwise, electric shock may result.
• Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work is being carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
• Only a qualified installer or qualified service person is allowed to undertake work at heights using a stand of 50 cm or more.
• When working at heights, use a ladder which complies with the ISO 14122 standard, and follow the procedure in the ladders instructions. Also wear a helmet for use in industry as protective gear to undertake the work.
• Wear protective gloves and safety work clothing during installation, servicing and removal.
• Do not touch the aluminium fin of the outdoor unit. You may injure yourself if you do so. If the fin must be touched for some reason, first put on protective gloves and safety work clothing, and then proceed.
• Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor unit and result in injury.
• When working at height, put a sign in place so that no-one will approach the work location before proceeding with the work. Parts or other objects may fall from above, possibly injuring a person below. Also, be sure that workers put on helmets.
• When cleaning the filter or other parts of the outdoor unit, set the circuit breaker to OFF without fail, and place a “Work in progress” sign near the circuit breaker before proceeding with the work.
• The refrigerant used by this air conditioner is the R410A.
• You shall ensure that the air conditioner is transported in stable condition. If you find any part of the product broken, contact your dealer.
• Do not modify the products. Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury.
• Before starting to repair the air conditioner, read carefully through the Service Manual, and repair the air conditioner by following its instructions.
• Only qualified service person is allowed to repair the air conditioner. Repair of the air conditioner by unqualified person may give rise to a fire, electric shocks, injury, water leaks and/or other problem.
• Once the repair work has been completed, check for refrigerant leaks, and check the insulation resistance and water drainage. Then perform a trial run to check that the air conditioner is running properly.
EN
EN-7 EN-8
– 4 –
Page 6
01_IM_DHV2305601-00_EN.fm Page 5 Wednesday, November 27, 2019 11:26 AM
• This appliance is intended to be used by expert or trained users in shops, in light industry, or for commercial use by lay persons.
• This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
• Children should be supervised to ensure that they do not play with the appliance.
Selection of installation location
• If you install the unit in a small room, take appropriate measures to prevent the refrigerant from exceeding the limit concentration even if it leaks. Consult the dealer from whom you purchased the air conditioner when you implement the measures. Accumulation of highly concentrated refrigerant may cause an oxygen deficiency accident.
• Do not install the air conditioner in a location that may be subject to a risk of exposure to a combustible gas. If a combustible gas leaks and becomes concentrated around the unit, a fire may occur.
• When transporting the air conditioner, wear shoes with additional protective toe caps.
• When transporting the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if the bands should break.
• Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may cause imperfect combustion.
• Places where the operation sound of the outdoor unit may cause a disturbance. (Especially at the boundary line with a neighbour, install the air conditioner while considering the noise.)
• When transporting the air conditioner, use a forklift and when moving the air conditioner by hand, move the unit with 6 people.
Installation
• Follow the instructions in the installation manual to install the air conditioner. Failure to follow these instructions may cause the
– 5 –
Installation Manual
product to fall down or topple over or give rise to noise, vibration, water leakage, etc.
• The designated bolts (M12) and nuts (M12) for securing the outdoor unit must be used when installing the unit.
• Install the outdoor unit property in a location that is durable enough to support the weight of the outdoor unit. Insufficient durability may cause the outdoor unit to fall, which may result in injury.
• Install the unit in the prescribed manner for protection against strong wind and earthquake. Incorrect installation may result in the unit falling down, or other accidents.
• Be sure to fix the screws back which have been removed for installation or other purposes.
Refrigerant piping
• Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor is operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is over pressurized, which may cause a injury.
• Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a crack in the flare nut after a long period, which may result in refrigerant leakage.
• Ventilate the air if the refrigerant gas leaks during installation. If the leaked refrigerant gas comes into contact with fire, toxic gas may be produced.
• After installation work, check the refrigerant gas does not leak. If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
• When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge the air completely so that no gases other than the refrigerant gas will be mixed in the refrigerating cycle. Failure to purge the air completely may cause the air conditioner to malfunction.
EN-9 EN-10
Page 7
01_IM_DHV2305601-00_EN.fm Page 6 Wednesday, November 27, 2019 11:26 AM
Installation Manual
• Nitrogen gas must be used for the airtight test.
• The charge hose must be connected in such a way that it is not slack.
• If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with fire, noxious gas may be generated.
Electrical wiring
• Only a qualified installer or qualified service person is allowed to carry out the electrical work of the air conditioner. Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and / or electrical leaks.
• When connecting the electrical wires, repairing the electrical parts or undertaking other electrical jobs, wear gloves to provide protection for electricians, insulating shoes and clothing to provide protection from electric shocks. Failure to wear this protective gear may result in electric shocks.
• When executing address setting, test run, or troubleshooting through the checking window on the electric parts box, put on insulated gloves to provide protection from electric shock. Otherwise you may receive an electric shock.
• Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and laws. Use of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage, smoking and / or a fire.
• Check that the product is properly earthed. (grounding work) Incomplete earthing may cause electric shock.
• Do not connect the earth line to a gas pipe, water pipe, lightning conductor, or a telephone earth line.
• After completing the repair or relocation work, check that the ground wires are connected properly.
• Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations and laws.
• Install the circuit breaker where it can be easily accessed by the
qualified service person.
• When installing the circuit breaker outdoors, install one which is designed to be used outdoors.
• Under no circumstances must the power cable be extended. Connection trouble in the places where the cable is extended may give rise to smoking and / or a fire.
• Electrical wiring work shall be conducted according to law and regulation in the community and installation manual. Failure to do so may result in electrocution or short circuit.
• Do not supply power from the power terminal block equipped on the outdoor unit to another outdoor unit. Capacity overflow may occur on the terminal block and may result in fire.
• When carrying out electric connection, use the wire specified in the Installation Manual and connect and fix the wires securely to prevent them applying external force to the terminals. Improper connection or fixing may result in fire.
• If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
Installation of earth leakage circuit breaker
• Install the earth leakage circuit breaker that meets the stipulations in the local regulations and laws.
• The earth leakage circuit breaker needs to have over-current protection and leakage prevention function that can be manually reset.
Test run
• Before operating the air conditioner after having completed the work, check that the electrical parts box cover of the indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may receive an electric shock if the power is turned on without first conducting these checks.
• When you have noticed that some kind of trouble (such as when an error display has appeared, there is a smell of burning, abnormal sounds are heard, the air conditioner fails to cool or heat or water is
EN
EN-11 EN-12
– 6 –
Page 8
CAUTION
01_IM_DHV2305601-00_EN.fm Page 7 Wednesday, November 27, 2019 11:26 AM
leaking) has occurred in the air conditioner, do not touch the air conditioner yourself but set the circuit breaker to the OFF position, and contact a qualified service person. Take steps to ensure that the power will not be turned on (by marking “out of service” near the circuit breaker, for instance) until qualified service person arrives. Continuing to use the air conditioner in the trouble status may cause mechanical problems to escalate or result in electric shocks or other failure.
• After the work has finished, be sure to use an insulation tester set (500 V Megger) to check the resistance is 1 M or more between the charge section and the non-charge metal section (Earth section). If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.
• Upon completion of the installation work, check for refrigerant leaks and check the insulation resistance and water drainage. Then conduct a test run to check that the air conditioner is operating properly.
Explanations given to user
• Upon completion of the installation work, tell the user where the circuit breaker is located. If the user does not know where the circuit breaker is, he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner.
• If you have discovered that the fangard is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF position, and contact a qualified service person to have the repairs done. Do not set the circuit breaker to the ON position until the repairs are completed.
• After the installation work, follow the Owner’s Manual to explain to the customer how to use and maintain the unit.
Relocation
• Only a qualified installer or qualified service person is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric
– 7 –
Installation Manual
shocks, injury, water leakage, noise and / or vibration may result.
• When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air or other gas to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in rupture, injury or other trouble.
• Never recover the refrigerant into the outdoor unit. Be sure to use a refrigerant recovery machine to recover the refrigerant when moving or repairing. It is impossible to recover the refrigerant into the outdoor unit. Refrigerant recovery into the outdoor unit may result in serious accidents such as explosion of the unit, injury or other accidents.
New Refrigerant Air Conditioner Installation
• This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer.
• The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle.
• To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant.
• Accordingly the exclusive tools are required for the new refrigerant (R410A).
• For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter.
EN-13 EN-14
Page 9
NOTE
01_IM_DHV2305601-00_EN.fm Page 8 Wednesday, November 27, 2019 11:26 AM
Installation Manual
2 Accessory Parts
Part name Q’ty Shape Usage
Owner’s Manual 1 Hand this directly to the customer.
Installation Manual 1 Hand this directly to the customer.
CD-ROM (Owner’s manual, Installation manual)
F-GAS label 1 Fill the items on the label after adding refrigerant.
Attached pipe 1
• Before installing the unit, check that the unit has the correct model name to prevent the wrong unit from being installed in the wrong place.
• Before proceeding to braze the refrigerant pipe, be sure to pass nitrogen through the pipe.
• Before installing the indoor units, read the instructions in the installation manual provided with the indoor units.
• Before installing a branch pipe, read the instructions in the installation manual provided with the branch pipe kit.
1-
For other languages that do not appear in this Installation Manual, Please refer to the enclosed CD-ROM.
Gas pipe connection pipe Ø19.05 to Ø22.22 (MCY-MHP1006HS8* only)
3 Installation of New Refrigerant Air
Conditioner
This air conditioner adopts the new HFC refrigerant (R410A) which does not deplete the ozone layer.
• R410A refrigerant is vulnerable to impurities such as water, oxidizing membranes, or oils because the pressure of R410A refrigerant is higher than that of the former refrigerant by approximately 1.6 times. As well as the adoption of the new refrigerant, the refrigerating oil has been also changed. Therefore, pay attention so that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle of the new refrigerant air conditioner during installation.
• To prevent mixing of refrigerant or refrigerating oil, the size of the charge port of the main unit or connecting section of the installation tool differs to that of an air conditioner for the former refrigerant. Accordingly, exclusive tools are required for the new refrigerant (R410A) as shown below.
• For connecting pipes, use new and clean piping materials so that water or dust does not enter.
Required tools and cautions on handling
It is necessary to prepare the tools and parts for installation as described below. The tools and parts which will be newly prepared in the following items should be restricted to exclusive use.
Explanation of symbols
: Newly prepared (It is necessary to use it exclusively with R410A, separately from those for R22 or R407C.) : Former tool is available.
Used tools Usage Proper use of tools / parts
Gauge manifold
Charging hose Exclusive to R410A
Charging cylinder Charging refrigerant
Gas leak detector Checking gas leak Exclusive to R410A
Vacuum pump Vacuum drying
Vacuum pump with counterflow Vacuum drying R22 (Existing article)
Flare tool Flare processing of pipes Usable by adjusting size
Bender Bending processing of pipes R22 (Existing article)
Refrigerant recovery device Recovering refrigerant Exclusive to R410A
Torque wrench Tightening flare nut Exclusive to Ø12.70 mm and Ø15.88 mm
Pipe cutter Cutting pipes R22 (Existing article)
Refrigerant canister Charging refrigerant
Welding machine / Nitrogen gas cylinder
Refrigerant charging balance Charging refrigerant R22 (Existing article)
Vacuuming, charging refrigerant and operation check
Welding of pipes R22 (Existing article)
Exclusive to R410A
Unusable (Use the Refrigerant charging balance.)
Usable if a counter-flow preventive adapter is attached
Exclusive to R410A Enter the refrigerate name for identification
EN
EN-15 EN-16
– 8 –
Page 10
WARNING
CAUTION
WARNING
CAUTION
01_IM_DHV2305601-00_EN.fm Page 9 Wednesday, November 27, 2019 11:26 AM
4 Installation Conditions
Before installation
Be sure to prepare to the following items before installation.
Airtight test
1 Before starting an airtight test, further tighten the spindle valves on the gas and liquid sides. 2 Pressurize the pipe with nitrogen gas charged from the service port to the design pressure to conduct an
airtight test.
3 After the airtight test is completed, evacuate the nitrogen gas.
Air purge
• To purge air, use a vacuum pump.
• Do not use refrigerant charged in the outdoor unit to purge air. (The air purge refrigerant is not contained in the outdoor unit.)
Electrical wiring
Be sure to fix the power wires, indoor / outdoor connecting wires and remote controller wires with clamps so that they do not come into contact with the cabinet, etc.
Earthing
Make sure that proper earthing is provided.
Improper earthing may cause an electric shock. For details on how to check earthing, contact the dealer who installed the air conditioner or a professional installation company.
– 9 –
Installation Manual
Installation location
Install the outdoor unit properly in a location that is durable enough to support the weight of the outdoor unit.
Insufficient durability may cause the outdoor unit to fall, which may result in injury. This outdoor unit has a weight of about 147 kg. Pay special attention when installing the unit onto a wall surface.
Do not install the outdoor unit in a location that is subject to combustible gas leaks.
Accumulation of combustible gas around the outdoor unit may cause a fire.
Install the outdoor unit in a location that meets the following conditions after the customer’s consent is obtained.
• A well-ventilated location free from obstacles near the air intake and air discharge
• A location that is not exposed to rain or direct sunlight
• A location that does not increase the operating noise or vibration of the outdoor unit
• A location that does not produce any drainage problems from discharged water
• Proper earthing can prevent charging of electricity on the outdoor unit surface due to the presence of a high frequency in the frequency converter (inverter) of the outdoor unit, as well as prevent electric shock. If the outdoor unit is not properly earthed, you may be exposed to an electric shock.
• Be sure to connect the earth wire (grounding work). Incomplete earthing can cause an electric shock. Do not connect earth wires to gas pipes, water pipes, lightning rods or earth wires for telephone wires.
Test run
Turn on the leakage breaker at least 12 hours before starting a test run to protect the compressor.
Incorrect installation work may result in a malfunction or complaints from customers.
Do not install the outdoor unit in the following locations.
• A location with a saline atmosphere (coastal area) or one that is full of sulfide gas (hot-spring area) (Special maintenance is required.)
• A location subject to oil, vapor, oily smoke, or corrosive gases
• A location in which organic solvent is used
• Places where iron or other metal dust is present. If iron or other metal dust adheres to or collects on the interior of the air conditioner, it may spontaneously combust and start a fire.
• A location where high-frequency equipment (including inverter equipment, private power generator, medical equipment, and communication equipment) is used (Installation in such a location may cause malfunction of the air conditioner, abnormal control or problems due to noise from such equipment.)
• A location in which the discharged air of the outdoor unit blows against the window of a neighboring house
• A location where the operating noise of the outdoor unit is transmitted
• When the outdoor unit is installed in an elevated position, be sure to secure its fixing leg.
• A location in which drain water poses any problems.
When collectively draining discharged water completely, use a drain pan.
EN-17 EN-18
Page 11
CAUTION
800 mm
Strong wind
Strong wind
<Example>
Snow shield
Snow shield
01_IM_DHV2305601-00_EN.fm Page 10 Wednesday, November 27, 2019 11:26 AM
1. Install the outdoor unit in a location where the discharge air is not blocked.
2. When an outdoor unit is installed in a location that is always exposed to strong winds like a coast or on the high stories of a building, secure normal fan operation by using a duct or wind shield.
3. When installing the outdoor unit in a location that is constantly exposed to strong winds such as on the upper stairs or rooftop of a building, apply the wind-proofing measures referred to in the following examples.
1) Install the unit so that its discharge port faces the wall of the building. Keep a distance 800 mm or more between the unit and wall surface.
Installation Manual
4. When installing the unit in an area where snowfalls may be heavy, take steps to prevent the unit from being adversely affected by the fallen or accumulated snow.
• Either make the foundation higher or install a stand (which is high enough to ensure that the unit will be above the fallen or accumulated snow) and place the unit on it.
• Attach a snow shield (locally procured).
EN
2) Consider the wind direction during the operational season of the air conditioner, and install the unit so that the discharge port is set at a right angle relative to the wind direction.
EN-19 EN-20
– 10 –
Page 12
150 or more
150 or more 300 or more
200 or more
The height of the obstacle should be lower than the height of the outdoor unit.
150 or more
200 or more
300 or more
300 or more
300 or more
150 or more
500 or more
800 or more
1,000 or
more
300 or more 300 or more
1,000 or more
800 or more
150 or more
800 or more
300 or more
150 or
more
1,000
or more
1,000
or more
200 or
more
250 or more
250 or
more 1,000 or more
300 or more
1,500 or more
2,000 or more
200 or more
Drain hole
Knockout hole
Back side
Front side (Air discharge side)
01_IM_DHV2305601-00_EN.fm Page 11 Wednesday, November 27, 2019 11:26 AM
Necessary space for installation
(Unit: mm)
Be sure to observe the necessary space for instllation.
Install the outdoor unit in a well-ventilated location. Failure to do so may cause short circuit (intake of discharge air) or performance deterioration due to locations around the outdoor unit.
Obstacle at rear side
Upper side is free
1. Single unit installation
2. Obstacles on both right and left sides
3. Serial installation of two or more units The height of the obstacle should be lower than the height of the outdoor unit.
Obstacle in front
Above unit is free
1. Single unit installation
2. Serial installation of two or more units
Obstacle also above unit
Obstacles in front and both right and left side
– 11 –
Installation Manual
Obstacles in both front and rear of unit
Open above and to the right and left of the unit. The height of an obstacle in both the front and rear of the unit, should be lower than the height of the outdoor unit.
Standard installation
1. Single unit installation
2. Serial installation of two or more units
Serial installation in front and rear
Open above and to the right and left of the unit. The height of an obstacle in both the front and rear of the unit should be lower than the height of the outdoor unit.
Standard installation
Installation of outdoor unit
• Before installation, check the strength and horizontalness of the base so that abnormal sounds do not emanate.
• According to the following base diagram, fix the base firmly with the anchor bolts. (Anchor bolt, nut: M12 x 4 pairs)
164 660 164
Obstacle also above unit
EN-21 EN-22
490
445
Page 13
CAUTION
Fixing leg
Correct Correct
Foundation
Absorb vibration with vibration-proof rubber pads
Foundation
Bottom plate of outdoor unit
Support the bottom surface of the fixing leg that is in contact with and underneath the bottom plate of the outdoor unit.
Incorrect
If only the end of the
fixing leg is supported,
it may deform.
Do not support the outdoor unit only with the fixing leg.
Foundation
20 or less
Tip-over prevention part
Tip-over prevention part
01_IM_DHV2305601-00_EN.fm Page 12 Thursday, December 5, 2019 4:55 PM
Installation Manual
• As shown in the figure below, install vibration-proof rubber pads to directly support the bottom surface of the fixing leg. * When installing the foundation for an outdoor unit with downward piping, consider the piping work.
Set the out margin of the anchor bolt to 20 mm or less.
• When the unit is to be installed in a location where it is likely to be exposed to strong winds or where the foundation is unstable, additional measures must be taken to prevent tip-over as shown in the figure below.
For reference
If a heating operation is to be continuously performed for a long time under the condition that the outdoor temperature is 0 °C or lower, draining defrosted water may be difficult due to the bottom plate freezing, resulting in trouble with the cabinet or fan. It is recommended to procure an anti-freeze heater locally in order to safely install the air conditioner. For details, contact the dealer.
EN
• Carry out the installation work by following the prescribed procedure to make provision against the shaking of the unit caused by strong winds, earthquakes, etc.
• Failure to carry out the installation work as prescribed may lead to the unit tipping over, in turn causing an accident.
EN-23 EN-24
– 12 –
Page 14
REQUIREMENT
Side
Bottom
Front
CAUTION
90°
Correct
Incorrect Incorrect Incorrect
Obliquity Roughness
Warp
A
B
01_IM_DHV2305601-00_EN.fm Page 13 Thursday, December 5, 2019 4:55 PM
5 Refrigerant Piping
Leading out the pipes
• The indoor/outdoor unit connecting pipes can be connected in any of 3 directions. Use a screwdriver to punch out the knockout part of the front panel or base. Wear heavy work gloves to protect yourself from injury while doing this work. After punching out the knockout hole in a manner which ensures that the pipes and wires will not be damaged in any way, remove the burrs from around the hole.
Follow the instructions in the installation manual provided with the branch pipe kit and the instructions in the installation manual of the indoor unit to connect the refrigerant pipe between the branch pipe and indoor unit.
– 13 –
Installation Manual
Refrigerant piping connection
TAKE NOTE OF THESE 4 IMPORTANT POINTS BELOW FOR PIPING WORK
1. Keep dust and moisture away from inside the connecting pipes.
2. Tightly connect the connection between pipes and the unit.
3. Evacuate the air in the connecting pipes using a VACUUM PUMP.
4. Check for gas leaks at connection points.
Pipe connection method
Flaring
1. Cut the pipe with a pipe cutter.
2. Remove the burr inside of the pipe. When removing the burr, be careful so that chips do not fall into the pipe.
3. Remove the flare nuts attached to the outdoor / indoor unit, then insert them into each of the pipes.
4. Flare the pipes. See the following table for the projection margin (A) and flaring size (B).
Pipe A B Flare Nut
Outside
diameter
mm mm mm mm mm mm N•m kgf•m
6.35 0.8 0 to 0.5 1.0 to 1.5 9.9 17 14 to 18 1.4 to 1.8
9.52 0.8 0 to 0.5 1.0 to 1.5 13.2 22 33 to 42 3.3 to 4.2
12.70 0.8 0 to 0.5 1.0 to 1.5 16.6 26 50 to 62 5.0 to 6.2
15.88 1.0 0 to 0.5 1.0 to 1.5 19.7 29 68 to 82 6.8 to 8.2
19.05 1.2 0 to 0.5 1.0 to 1.5 24.0 36 100 to 120 10.0 to 12.0
* In case of flaring for R410A with the conventional flare tool, pull the tool out approx. 0.5 mm more than that for R22
to adjust it to the specified flare size. The copper pipe gauge is useful for adjusting the projection margin size.
Thickness
Rigid
(clutch type)
R410A tool
Imperial
(wing nut type)
R410A tool
Width across
flat
Tighten torque
EN-25 EN-26
Page 15
REQUIREMENT
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.03
-0.03
01_IM_DHV2305601-00_EN.fm Page 14 Thursday, December 5, 2019 4:55 PM
• For a brazing work of the refrigerant pipes, be sure to use nitrogen gas in order to prevent oxidation of the inside of the pipes; otherwise clogging of the refrigerating cycle due to oxidized scale may occur.
• Use clean and new pipes for the refrigerant pipes and perform piping work so that water or dust does not contaminate the refrigerant.
* Remove all flux after brazing.
• Be sure to use a double spanner to loosen or tighten the flare nut. If a single spanner is used, the required level of tightening cannot be obtained. Tighten the flare nut with the specified torque.
• Do not apply refrigerant oil to the surface of the flare.
Coupling size of brazed pipe
Connected section
External size Internal size
K
ØC
Standard outer dia. of
connected copper
pipe
External size Internal size
Standard outer dia.
(Allowable difference)
CFKG
6.35 6.35 (±0.03) 6.45 ( ) 7 6 0.06 or less
9.52 9.52 (±0.03) 9.62 ( ) 8 7 0.08 or less
12.70 12.70 (±0.03) 12.81 ( ) 9 8 0.10 or less
15.88 15.88 (±0.03) 16.00 ( ) 9 8 0.13 or less
19.05 19.05 (±0.03) 19.19 ( ) 11 10 0.15 or less
22.22 22.22(±0.03) 22.36 ( ) 11 10 0.16 or less
G
ØF
Connected section
Min. depth of
insertion
Oval value
Min. thickness of
(Unit: mm)
coupling
0.50
0.60
0.70
0.80
0.80
0.90
Installation Manual
Selection of pipe materials and size
Selection of pipe material
Material: Phosphorus deoxidation seam-less pipe
Capacity code of indoor and outdoor units
• For the indoor unit, the capacity code is decided at each capacity rank.
• The capacity codes of the outdoor units are decided at each capacity rank. The maximum No. of connectable indoor unit and the total value of capacity codes of the indoor units are also decided.
Minimum wall thickness for R410A application
Soft Half Hard or Hard OD (Inch) OD (mm) Minimum wall thickness (mm)
Correct Correct 1/4” 6.35 0.80
Correct Correct 3/8” 9.52 0.80
Correct Correct 1/2” 12.70 0.80
Correct Correct 5/8” 15.88 1.00
1
Incorrect *
1
Incorrect *
*1 If the pipe size is Ø19.05, use a suitable material.
Tab le 1
Indoor unit
capacity type
005 type 0.6 1.7 018 type 2.0 5.6
007 type 0.8 2.2 020 type 2.25 6.3
008 type 0.9 2.5 024 type 2.5 7.1
009 type 1.0 2.8 027 type 3.0 8.0
010 type 1.1 3.2 030 type 3.2 9.0
012 type 1.25 3.6 036 type 4.0 11.2
014 type 1.5 4.0 048 type 5.0 14.0
015 type 1.7 4.5 056 type 6.0 16.0
017 type 1.85 5.0
Tab le 2
Outdoor unit
capacity type
0806 type 8 2 to 12 6.4 10.4
1006 type 10 2 to 16 8.0
Correct 3/4” 19.05 1.00
Correct 7/8” 22.22 1.00
Capacity code
Equivalent to HP
Capacity code No. of
Equivalent to HP Min. (HP) Max. (HP)
Equivalent to
capacity
connectable indoor units
Indoor unit
capacity type
Equivalent to HP
Total capacity code of connectable indoor units
(When the number of indoor units is 2 to 12)
(When the number of indoor units is 13 to 16)
Capacity code
13.0
11. 0
Equivalent to
capacity
EN
EN-27 EN-28
– 14 –
Page 16
Ball valve
Ø19.05 Main pipe (Locally procured)
Ball valve
Ø19.05 Main pipe (Locally procured)
Ball valve
Ø
19.05-Ø22.22
socket (Attached)
Ø
22.22 Main pipe
(Locally procured)
Ball valve
Ø
19.05 pipe
(Locally procured)
Ø
22.22 Main pipe
(Locally procured)
Ø
19.05-Ø22.22 socket
(Locally procured)
CAUTION
Wet cloth
Brazing
01_IM_DHV2305601-00_EN.fm Page 15 Wednesday, November 27, 2019 11:26 AM
Pipe connection method of valve at the gas side (Example)
Diameter of pipe Front and right leading out Downward direction leading out
Attach the Ø19.05 pipe to the ball valve by flare conection.
O.D.
19.05 mm
Attach the Ø19.05 pipe to the ball valve by flare conection.
– 15 –
Installation Manual
• The brazed part of the pipe connection should be sufficiently away from the ball valve.
• When carrying out brazing nearthe ball valve, wrap the ball valve in a wet cloth to keep it cool and prevent the heat from the torch from damaging it, and, prepare a shield plate on-site to prevent the soundproofing cloth or other part from catching fire.
Attach Ø19.05-Ø22.22 socket to the ball valve by flare conection and braze the locally procured Ø22.22 main pipe.
Attach Ø19.05 pipe to the ball valve by flare conection and braze the locally procured Ø19.05­Ø22.22 socket and Ø22.22 main pipe.
O.D.
22.22 mm
EN-29 EN-30
Page 17
Outdoor unit
Liquid pipe
Gas pipe
Main pipe L1
1st branching section
Branching pipe
Branching header
Indoor unit
Indoor unit
Branching pipe
Y-shaped branching joint
Height difference between indoor and outdoor units H1
Gas side Liquid side
19.05 9.52
Conditions for size of main pipe
selection *
Size of main pipe
Height between indoor
and outdoor units
H1(m)
Equivalent length
of main pipe
L1(m)
Gas pipe
Liquid
pipe
30
H1 > 20
40 > L1
19.05
9.52
L1
40 12.70
20
H1 > 10
60 > L1 9.52
L1
60 12.70
10
H1 > 0 No condition 9.52
Conditions for size of main pipe
selection *
Size of main pipe
Height between indoor
and outdoor units
H1(m)
Equivalent length
of main pipe
L1(m)
Gas pipe
Liquid
pipe
30
H1 > 20
30 > L1
22.22
9.52
L1
30 12.70
20
H1 > 10
40 > L1 9.52
L1
40 12.70
10
H1 > 0
50 > L1 9.52 L1
50 12.70
Total capacity codes of indoor units
at down stream side
Gas pipe Liquid pipe
Equivalent to HP
Equivalent to
capacity
Below 2.4 Below 6.6 12.70 9.52
2.4 to below 6.4 6.6 to below 18.0 15.88 9.52
6.4 or more 18.0 or more 22.22 12.70
Capacity rank Gas pipe Liquid pipe
005 to 012 type 9.52 6.35
014 to 018 type 12.70 6.35
020 to 056 type 15.88 9.52
Total capacity codes of indoor units at
down stream side
Model name
Equivalent to HP Equivalent to capacity
Y-sharp branch joint
Below 6.4 Below 18.0 RBM-BY55E
6.4 or more 18.0 or more RBM-BY105E
Model name
Branching header
For 4 branches RBM-HY1043E
For 8 branches RBM-HY1083E
01_IM_DHV2305601-00_EN.fm Page 16 Wednesday, November 27, 2019 11:26 AM
Installation Manual
Selection of refrigerant piping
(1)
(4)
(2)
(2)
No. Piping parts Name Selection of pipe size Remarks
Size of valve
- Outdoor unit
Connection Val ve
0806 type
Outdoor unit
(1)
1st branching section
Main pipe
(5)
(3)
(3)
(3)
(4)
(3)
(3)
(3)
-
*The main liquid pipe size differs based on outdoor unit capacity type, equivalent length of main pipe, and hight difference between outdoor and indoor units.
(2)
(3)
(4)
(5)
Branching section
Branching section
Branching section
Indoor unit
Branching section
Branching section
Branching pipe
Indoor unit connecting pipe
Y-shaped branching joint
Branching header
1006 type
Pipe size between branching sections
* When exceed the main pipe size, use the same size as the main
pipe.
Connecting pipe size of indoor unit
Selection of branching section (Y-shaped branching joint)
Selection of branching section (Branching header)
Pipe size differs based on the total capacity code value of indoor units at the downstream side. If the total value exceeds the capacity code of the outdoor unit, apply the capacity code of the outdoor unit. (See Table 1 and 2.)
EN
EN-31 EN-32
– 16 –
Page 18
(5)
(2)
(4)
(1)
(3)
(6)
(3)
(3)
(2)
(4)
(3)
(6)
(6)
(6)
(3)
(6)
(3)
(6)
Outdoor unit
Liquid pipe
Gas pipe
Main pipe L1
1st branching section
Branching pipe
Branching header
Indoor unit
Indoor unit
Branching pipe
Y-shaped branching joint
PMV Kit
Height difference between indoor and outdoor units H1
Gas side Liquid side
19.05 9.52
Conditions for size of main pipe
selection *
Size of main pipe
Height between indoor
and outdoor units
H1(m)
Equivalent length
of main pipe
L1(m)
Gas pipe
Liquid
pipe
30
H1 > 20
40 > L1
19.05
9.52
L1
40 12.70
20
H1 > 10
60 > L1 9.52
L1
60 12.70
10
H1 > 0 No condition 9.52
Conditions for size of main pipe
selection *
Size of main pipe
Height between indoor
and outdoor units
H1(m)
Equivalent length
of main pipe
L1(m)
Gas pipe
Liquid
pipe
30
H1 > 20
30 > L1
22.22
9.52
L1
30 12.70
20
H1 > 10
40 > L1 9.52
L1
40 12.70
10
H1 > 0
50 > L1 9.52 L1
50 12.70
Total capacity codes of indoor units
at down stream side
Gas pipe Liquid pipe
Equivalent to HP
Equivalent to
capacity
Below 2.4 Below 6.6 12.70 9.52
2.4 to below 6.4 6.6 to below 18.0 15.88 9.52
6.4 or more 18.0 or more 22.22 12.70
Capacity rank Gas pipe Liquid pipe
005 to 012 type 9.52 6.35
014 to 018 type 12.70 6.35
020 to 056 type 15.88 9.52
Total capacity codes of indoor units at
down stream side
Model name
Equivalent to HP Equivalent to capacity
Y-sharp branch joint
Below 6.4 Below 18.0 RBM-BY55E
6.4 or more 18.0 or more RBM-BY105E
Model name
Branching header
For 4 branches RBM-HY1043E
For 8 branches RBM-HY1083E
Capacity rank Model name
005 to 014 type RBM-PMV0363E
015 to 027 type RBM-PMV0903E
01_IM_DHV2305601-00_EN.fm Page 17 Wednesday, November 27, 2019 11:26 AM
Selection of refrigerant piping for quiet place (with PMV Kit)
No. Piping parts Name Selection of pipe size Remarks
Size of valve
- Outdoor unit
Connection Val ve
– 17 –
Installation Manual
1006 type
(2)
Branching section
Branching section
Branching pipe
Pipe size between branching sections
* When exceed the main pipe size, use the same size as the main
pipe.
Pipe size differs based on the total capacity code value of indoor units at the downstream side. If the total value exceeds the capacity code of the outdoor unit, apply the capacity code of the outdoor unit. (See Table 1 and 2.)
Connecting pipe size of indoor unit
Branching section
(3)
Indoor unit
-
Indoor unit connecting pipe
Selection of branching section (Y-shaped branching joint
Outdoor unit
1st
(1)
branching
EN-33 EN-34
section
Main pipe
0806 type
Y-shaped branching joint
Branching header
Selection of branching section (Branching header)
*The main liquid pipe size differs based on outdoor unit capacity type, equivalent length of main pipe, and hight difference between outdoor and indoor units.
(4)
(5)
Branching section
Branching section
Selection of PMV Kit
(6) PMV Kit PMV Kit
* PMV kit can be connected less than 027 type FCU.
Page 19
f
abcd
A
*1
L3
L1
L2
e
Outdoor unit
Height difference between indoor and outdoor units H1
Main pipe
1st branching section
Branching pipe
Branching header
Indoor unit
Y-shaped
branching joint
Branching pipe
Equivalent length corresponded to farthest piping L
Equivalent length corresponded to farthest piping after 1st branching Li
Height difference between indoor units H2
Outdoor unit
Height difference between indoor and outdoor units H1
Main pipe
1st branching section
Branching pipe
Branching header
Indoor unit
Y-shaped
branching joint
Branching pipe
Equivalent length corresponded to farthest piping L
Equivalent length corresponded to farthest piping after 1st branching Li
Height difference between indoor unit and PMV Kit H2 * * Between highest
unit and lower units.
PMV Kit
Example)
01_IM_DHV2305601-00_EN.fm Page 18 Thursday, November 28, 2019 1:21 PM
Installation Manual
Allowable length / height difference of refrigerant piping
Allowable
value
Total extension of pipe (liquid pipe, real length) 300 m L1 + L2 + L3 + a + b + c + d + e + f
Real length 120 m
Equivalent length 150 m
40 m L3 + f
Piping Length
Furthest piping length L (*1)
Max. equivalent length of main pipe 80 m *2 L1
Max. real length of furthest piping from 1st branching Li (*1)
Max. real length of indoor unit connecting pipe 15 m a, b, c, d, e, f
Height Difference
*1 Furthest indoor unit from 1st branch to be named “A”. *2
The main liquid pipe size varies depending on L1 and H1. See the page of “Selection of refrigerant piping” for details.
Height between indoor and outdoor units H1
Height between indoor units H2 15 m
EN-35 EN-36
Upper outdoor unit 30 m *2
Lower outdoor unit 30 m *2
Pipes
L1 + L3 + f
– 18 –
Allowable length / height difference of refrigerant piping for quiet places (with PMV Kit)
L1
L3
Total extension of pipe (Liquid pipe, real length) 250 m
Furthest piping length L (*1)
Piping Length
Max. equivalent length of main pipe 70 m *2 L1
Max. real length of furthest piping from 1st branching Li (*1)
Max. real length of indoor unit connecting pipe 15 m a + g, b + h, c + i, d + j, e + k, f + l
Real length between PMV Kit and indoor unit
Height Difference
Height between indoor and outdoor units H1
Height between indoor units (PMV Kit) H2 15 m
*1 Furthest indoor unit from 1st branch to be named “A”. *2
The main liquid pipe size varies depending on L1 and H1. See the page of “Selection of refrigerant piping” for details.
L2
ab
cd
ghi j
e
k
Allowable
value
f
l
L1 + L2 + L3 + a + b + c + d + e + f + g + h
Real length 100 m
Equivalent length 130 m
30 m L3 + f + l
2 m or more
Below 10 m
Upper outdoor unit 30 m *2
Lower outdoor unit 30 m *2
*1
A
Pipes
+ i + j + k + l
L1 + L3 + f + l
g, h, i, j, k, l
H2
H2
H2
EN
Page 20
NOTE
Incorrect Correct
PMV Kit
PMV Kit
Indoor unit Indoor unit
REQUIREMENT
Main pipe
Connected to indoor unit
Low pressure guage
High pressure guage
Ball valve fully closed (Gas side)
Flare connection
Flare connection
Packed valve fully closed (Liquid side)
Service port
Ø6.4 Copper pipe
Ø6.4 Copper pipe
Nitrogen gas
Reducing valve
Gauge manifold
Outdoor unit
Service port
01_IM_DHV2305601-00_EN.fm Page 19 Thursday, December 5, 2019 4:54 PM
Do not connect two or more indoor units to one PMV Kit. Arrange one indoor unit and one PMV Kit set to 1 by 1.
– 19 –
Installation Manual
Airtight test
Before starting an airtight test, further tighten the spindle valves on the gas side and liquid side. Pressurize the pipe with nitrogen gas charged from the service port to the design pressure to conduct the airtight test. After the airtight test is completed, evacuate the nitrogen gas.
• Apply pressure from the service ports of the packed valves (or ball valves) at liquid side and gas side.
• An air tight test can be only performed to the service ports at liquid side and gas side of the outdoor unit.
• Close fully valves at liquid side and gas side. As there is possibility that nitrogen gas enters in the refrigerant cycle, re-tighten the valve rods before applying pressure. (Re-tightening of the valve rods are unnecessary for valves at gas side because they are ball valves.)
• For each refrigerant line, apply pressure gradually with steps at liquid side and gas side.
Apply pressure to gas side and liquid side.
Do not use “Oxygen”, “Flammable gas” and “Noxious gas” in an airtight test.
To detect a gross leakage
1. Apply pressure 0.3 MPa (3.0 kg / cm
2. Apply pressure 1.5 MPa (15 kg / cm
To detect a slow leakage
EN-37 EN-38
3. Apply pressure 4.15 MPa (42.3kg / cm
• Check pressure down. No pressure down: Accepted Pressure down: Check the leaked position.
2
G) for 3 minutes or more.
2
G) for 3 minutes or more.
2
G) for approx. 24 hours.
Page 21
NOTE
REQUIREMENT
NOTE
Main pipe
Connected to indoor unit
Low pressure guage
High pressure guage
Ball valve fully closed (Gas side)
Flare connection
Flare connection
Packed valve fully closed (Liquid side)
Service port
Vac uu m pu mp
Gauge manifold
Outdoor unit
Service port
01_IM_DHV2305601-00_EN.fm Page 20 Wednesday, November 27, 2019 11:26 AM
Installation Manual
Air purge
However, if the environmental temperature changes from the moment of applying pressure to 24 hours after that, the pressure will change by about 0.01 MPa (0.1 kg / cm
2
G) per 1 °C. Consider the pressure change when checking the
test result.
When pressure decrease is detected in steps 1-3, check the leakage at the connecting points. Check the leakage using a foaming agent or other measures and seal the leak with re-brazing, flare retightening or other methods. After sealing, execute an airtight test again.
For the air purge at installation time (Discharge of air in connecting pipes), use “Vacuum pump method” from
EN
viewpoint of the protection of the earths environment.
• For protection of the earths environment, do not discharge the refrigerant gas in the air.
• Eliminate the remaining air (nitrogen gas, etc.) in the unit by using a vacuum pump.
If gas remains, performance and reliability of the unit may be reduced.
After the airtight test, discharge nitrogen gas. Then connect the gauge manifold to the service ports at gas side and liquid side, and connect the vacuum pump as shown in the following figure. Perform vacuuming for gas side and liquid side.
• Perform vacuuming from both liquid and gas sides.
• Use a vacuum pump with counter-flow preventive function so that oil in the pump does not back up in the pipe of the air conditioner when the pump has been stopped. (If oil in the vacuum pump enters in to the air conditioner with R410A refrigerant, an error may occur in the refrigeration cycle.)
• Use a vacuum pump that has a high vacuum (below -755 mmHg) and a large exhaust gas amount (over 40 L / minute).
• Perform vacuuming for 2 or 3 hours though time differs due to pipe length. In this time, check all valves at liquid and gas sides are fully closed.
• If vacuuming valve amount is not decreased to below -755 mmHg even after vacuuming for 2 hours or more, continue vacuuming for 1 hour or more.
EN-39 EN-40
– 20 –
If -755 mmHg or less cannot be obtained by 3 hours or more vacuuming, detect and repair the leak.
• When the vacuuming valve has reached -755 mmHg or less after vacuuming for 2 hours or more, close valves VL and VH on the gauge manifold fully. Stop the vacuum pump, leave it as it is for 1 hour and then check the vacuum does not change. If it does change then there may be a leak within the system.
• After the above procedure for vacuuming has finished, exchange the vacuum pump with a refrigerant cylinder and advance to the additional charging of refrigerant.
Page 22
NOTE
L1
L2
L3
L4
L5
L6
L7
DCBA
01_IM_DHV2305601-00_EN.fm Page 21 Monday, December 2, 2019 5:02 PM
Adding refrigerant
After finishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging of refrigerant.
Calculation of additional refrigerant charge amount
Default refrigerant amount does not include the refrigerant for pipes at the local site. For refrigerant to be charged in pipes at the local site, calculate the amount and charge it additionally.
Do not degas the refrigerant from the air conditioner when the result of additional refrigerant charge amount calculation is negative value.
Outdoor unit type 0806HS8 1006HS8
Charging amount (kg) 4.4 4.4
Additional
refrigerant charge
amount at local site
Real length of liquid
=
pipe
Additional refrigerant
charge amount per
×
1 m liquid pipe
(Table 1)
Tab l e 1
Liquid pipe dia. (mm) 6.35 9.52 12.70
Additional refrigerant amount / 1 m liquid pipe (kg / m)
0.025 0.055 0.105
Tab l e 2
Capacity rank
Capacity code (Equivalent to HP)
4-way cassette
2-way cassette MMU-AP****WH* -
1-way cassette MMU-AP****YH / SH* -
Duct
Indoor unit model
Under-ceiling MMC-AP****HP* ----
name
High wall
Floor standing
MMU-AP****HP* - -
MMU-AP****MH* 0.3
MMD-AP****BHP* -
MMD-AP****SPH* 0.3
MMD-AP****HP* -----
MMK-AP****H* -
MMK-AP****HP* 0.3
MMF-AP****H* ----
MML-AP****H* -
MML-AP****BH* -
MML-AP****NH* -
005 007 009 012 015 018 024 027 030 036 048 056
0.6 0.8 1.0
0.4 0.4 0.4 0.6 0.6
0.4 0.4 0.4 0.5 0.7 0.7 0.7 0.7 1.1 1.1 1.1
0.4 0.4 0.4 0.5 0.5 0.6
0.5 0.5 0.5 0.5 0.5 0.7 0.7 0.7 1.1 1.1 1.1
0.3 0.3 0.3 0.5 0.5 0.8 0.8
0.5 0.5 0.5 0.7 0.7 0.7
0.30.30.30.70.70.7-----
0.5 0.5 0.5 0.5 0.8 0.8
0.3 0.3 0.3 0.5 0.5 0.7
0.5 0.5 0.5 0.5 0.5
1.25
0.40.40.80.80.80.80.81.21.21.2
Corrective amount of refrigerant depending
+
on the indoor units
(Table 2)
1.72.02.53.03.24.05.06.0
------
-----
0.7 0.7 0.7
0.60.60.80.8-1.2 1.2 1.2
-----
0.70.71.01.0-1.3 1.3 1.3
-----
-----
------
Compensation by
+
----
-
1.1 1.1 1.1
outdoor HP
(Table 3)
(Unit: kg)
– 21 –
Installation Manual
Mid temperature Hot water module
Capacity rank 027 056
Capacity code
MMW-AP****LQ* 0.2 0.4
Tab le 3
Outdoor unit type 0806HS8 1006HS8
Compensation by outdoor HP (kg) –1.0 –1.0
Example: (1006 type)
L1 Ø9.52: 10 m L2 Ø9.52: 10 m L3 Ø9.52: 5 m L4 Ø9.52: 3 m
L5 Ø6.35: 3 m L6 Ø6.35: 4 m L7 Ø6.35: 5 m
A MMU-AP0564H* B MMU-AP0184H* C MMU-AP0074MH* D MMD-AP0074SPH*
Additional charge amount R (kg)
= ( Lx × 0.025 kg/m) + ( Ly × 0.055 kg/m) + ( a + b + c + d ) + ( –1.0 kg ) = ( 12 × 0.025 kg) + ( 28 × 0.055 kg) + ( 2.7 kg ) + ( –1.0 kg ) = 3.54 kg
Lx: Real total length of liquid pipe diameter 6.35 mm (m) Ly: Real total length of liquid pipe diameter 9.52 mm (m) a: Corrective amount of refrigerant depending on the unit A [kg] b: Corrective amount of refrigerant depending on the unit B [kg] c: Corrective amount of refrigerant depending on the unit C [kg] d: Corrective amount of refrigerant depending on the unit D [kg]
Charging of refrigerant
• Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the liquid side.
• If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and gas sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
• The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
Equivalent to Capcity 7.1 14.0
Equivalent to HP 2.5 5.0
EN-41 EN-42
Page 23
CAUTION
Charge port
Body cap
Closed
completely
Opened
fully
Using a minus screwdriver, turn it counterclockwise by 90° until it hits the stopper. (Full open)
Body cap
Flare nut
Charge port
Grooves
for
driver
When using the piping cover
Drawing-out sideward
Close the opening with the pipe cover.
Drawing-out downward
Drawing-out frontward
Drawing-out sideward
Fill silicon or putty into the periphery of the pipes.
Drawing-out downward
Drawing-out frontward
When not using the piping cover
2FAN_IM_DHV2305601-00_EN.book Page 22 Monday, October 28, 2019 3:25 PM
Installation Manual
EN-43 EN-44
Full opening of the valve
Open the valves of the outdoor unit fully.
Liquid side Gas side
Packed valve Using a 4 mm-hexagonal wrench, fully open the valve rods.
Refer to the table below when you tight the valve cap
Val ve
Liquid side 14 ~ 18 14 ~ 18
Gas side 20 ~ 25 14 ~ 18
Body cap Charge port
Ball valve Using a minus screwdriver, turn it counterclockwise by 90° until it hits the stopper. (Full open)
Tightening force[Nm]
F-GAS label
Contains fluorinated greenhouse gases
• Chemical Name of Gas R410A
• Global Warming Potential (GWP) of Gas 2088 (ex.R410A ref.AR4)
(1) Stick the enclosed refrigerant label adjacent to the service ports
for charging or recovering location and where possible adjacent to existing nameplates or product information label.
(2) Clearly write the charged refrigerant quantity on the refrigerant label
using indelible ink. Then, place the included transparent protective sheet over the label to prevent the writing from rubbing off.
(3) Prevent emission of the contained fluorinated greenhouse gas.
Ensure that the fluorinated greenhouse gas is never vented to the atmosphere during installation, service or disposal. When any leakage of the contained fluorinated greenhouse gas is detected, the leak shall be stopped and repaired as soon as possible.
(4) Only qualified service personnel are allowed to access and
service this product.
– 22 –
(5) Any handling of the fluorinated greenhouse gas in this product,
such as when moving the product or recharging the gas, shall comply under (EU) Regulation No.517/2014 on certain fluorinated greenhouse gases and any relevant local legislation.
(6) Periodical inspections for refrigerant leaks may be required
depending on European or local legislation.
(7) Contact dealers, installers, etc., for any questions.
Heat insulation for pipe
• Apply heat insulation of pipe separately at the liquid, gas, and balance sides.
• Be sure to use thermal insulator resistant up to 120 °C or higher for pipes at the gas side.
Finishing after connecting pipes
• After piping connection work has been finished, cover the opening of the piping / wiring panel with the piping cover, or fill silicon or putty into the space between the pipes.
• In case of drawing-out the pipes downward or sideward, also close the openings of the base plate and the side plate.
• Under the opened condition, a problem may be caused due to the entering of water or dust.
Pipe holding bracket
Attach pipe holding brackets following the table below.
Diameter of pipe (mm) Interval
Ø19.05 or less 2 m
Ø22.22 or more 3 m
EN
Page 24
WARNING
CAUTION
Circuit breaker
(Earth leakage breaker)
Main switch (Fuse)
01_IM_DHV2305601-00_EN.fm Page 23 Thursday, December 5, 2019 4:53 PM
6 Electric Wiring
The appliance shall be installed in accordance with national wiring regulations.
Capacity shortages of the power circuit or an incomplete installation may cause an electric shock or fire.
• Perform wiring of power supply complying with the rules and regulations of the local electric company.
• Do not connect 380-415 V power to the terminal blocks for control cables (U1, U2, U3, U4); otherwise, the unit may break down.
• Be sure that electric wiring does not come into contact with high­temperature parts of piping; otherwise, the coating of cables may melt and cause an accident.
• After connecting wires to the terminal block, take off the traps and fix the wires with cord clamps.
• Do not conduct power to indoor units until vacuuming of the refrigerant pipes has finished.
• For the wiring of power to indoor units and that between indoor and outdoor units, follow the instructions in the installation manual of each indoor unit.
– 23 –
Power wiring selection
Standard model
MOCP: Maximum Overcurrent Protection (Amps)
Model
MCY-MHP0806HS8-E
MCY-MHP1006HS8-E 20.0
Nominal Voltage, Phase and frequency
Power Supply
380-415V 3N~, 50Hz
MCA: Maximum Circuit Amps
Installation Manual
MCA
(A)
17.0
MOCP
(A)
20.0
25.0
EN-45 EN-46
Page 25
U1 U2 U3 U4
U1 U2 U3 U4
U1 U2 A
B 2UB
AU1
U2U1
A
2
UBU1 A B
BABABA
Outdoor unit
Central controller
Communication wiring between indoor and outdoor units (Shield wire)
Communication wiring between indoor units (Shield wire)
Indoor unit Indoor unit Indoor unit Indoor unit
Remote controller Remote controller Remote controller
(Group control)
Central
controller
This system Other system
Ta bl e- 1
Header unit
Follower unit
Table-1
Tab l e- 2
Ta bl e- 3
Outdoor unit
Indoor unit
Remote controller Remote controller Remote controller
2FAN_IM_DHV2305601-00_EN.book Page 24 Monday, October 28, 2019 3:25 PM
Installation Manual
Specifications for communication wiring
Design of communication wiring
Summary of communication wiring
Communication wiring and central control wiring use 2-core non-polarity wires. Use 2-core shield wires to prevent noise trouble. In this case, for the system grounding, close (connect) the end of shield wires, and isolate the end of terminal. Use 2-core non-polarity wire for remote controller. (A, B terminals) Use 2-core non-polarity wire for wiring of group control. (A, B terminals)
Keep the rule of below tables about size and length of communication wiring.
U1U3U2
U4
L4
U3 U4
U1 U2
L1
U1 U2
A B
U1 U2
U1 U2
U3 U4
A B
U1 U2
A B
U3 U4
U1 U2U5U6
U2
U1
L7
U1 U2
B
A
A
U2
U1
B
A
L6
U1 U2
B
A B
L7
U3 U4
U5
U1 U2
L5
3L2L
U2
U1
A B
L6
Table-1 Control wiring between indoor and outdoor units (L1, L2, L3), Central control wiring (L4)
Wiring 2-core, non-polarity
Type Shield wire
Size / Length *1
1.25 mm
2.0 mm
2
: Up to 1000 m
2
: Up to 2000 m
*1 Total of control wiring length for all refrigerant circuits ( L1 + L2 + L3 + L4 )
Table-2 Control wiring between outdoor units (L5) (Other system)
Wiring 2-core, non-polarity
Type Shield wire
Size / Length
2
to 2.0 mm
1.25 mm Up to 100 m (L5)
2
Table-3 Remote controller wiring (L6, L7)
Wiring 2-core
Size 0.5 mm
Length
2
to 2.0 mm
• Up to 500 m (L6 + L7)
• Up to 400 m with of wireless remote controller in group control.
• Up to 200 m total length of control wiring between indoor units ( L6 )
2
EN
U6
U2
U1
A B
EN-47 EN-48
– 24 –
Page 26
NOTE
Indoor unit No.1 No.2 No.3 No.4 No.7 No.8
Remote controller
Knockout for the communication wires and refrigerant piping
Jugged bushings (locally purchased)
The cover of the electrical control box
Terminal block (Power supply)
Earth screw (Power supply)
Cord clamp (Power supply)
Power supply wires
Communication wires
Terminal block (Communication)
Earth screw (Communication)
Cord clamp (Communication)
01_IM_DHV2305601-00_EN.fm Page 25 Thursday, December 5, 2019 4:50 PM
Group control through a remote controller
Group control of multiple indoor units (8 units) through a single remote controller
BABABABABABA
(A.B)
Connection of power wires and communication wires
Remove knockouts on the piping / wiring panel on the front of the unit or the panel on the bottom to get the power and communication wires through the holes. Use protective parts (such as jugged bushings) to prevent the power wires and communication wires from directly touching the edge of the sheet metal. The local installer must purchase the non-removable jugged bushings to wrap around the hole, and use insulated bushings (locally purchased) to protect the wires from directly touching the sheet metal.
– 25 –
Installation Manual
Remove the front panel and then remove the cover of the electrical control box.
Separate the power wire and communication wires.
EN-49 EN-50
Page 27
L1 L2 L3 N
L
1L2L3
N
10 mm or more
Earth line
Power supply wire
60 mm or less
U1 U2 U3 U4
U1 U2 U3 U4
CN02
CN10
[U1, U2] and [U3, U4] not connected
Communication terminal board
TO INDOOR
UNIT
TO CENTRAL
CONTROLLER
Communication terminal board
TO INDOOR
UNIT
TO CENTR AL
CONTROLLER
[U1, U2] and [U3, U4] connected
U3, U4: Central control device
U1, U2: Communication wiring between Indoor / Outdoor unit
2FAN_IM_DHV2305601-00_EN.book Page 26 Monday, October 28, 2019 3:25 PM
Installation Manual
Power supply wire connection
1. Insert the power supply wire through the cutout on the side of the electrical control box and connect the power
supply wire to the power supply terminal block and the earth line to the earth screw. After that, fix the power supply wire with the cord clamp.
2. Use round-type crimping terminals for power connection.
Also, apply insulating sleeves to the crimping parts. Use a driver of appropriate size to fix the terminal screws.
Wire size*
2
2.5 mm
* Design 60245 IEC66
Screw size and tightening torque
Power supply terminal M6 2.5 to 3.0
Earth screw M8 5.5 to 6.6
Screw size
Tightening torque
(N•m)
Communication wire connection
Connect the communication wires to the communication wire terminals from under the electrical control box, and fix them with the communication cable clamps.
CN02
CN10
U1 U2 U3 U4
U1 U2 U3 U4
Screw size and tightening torque
Screw size
Communication wire terminal M4 1.2 to 1.4
Tightening torque
(N•m)
EN
EN-51 EN-52
– 26 –
Page 28
Model Ssc(kVA)
MCY-MHP0806HS8-E MCY-MHP1006HS8-E
1596
CAUTION
REQUIREMENT
2FAN_IM_DHV2305601-00_EN.book Page 27 Monday, October 28, 2019 3:25 PM
Regulation of harmonic currents
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal to Ssc (*1) at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary, that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc (*1).
Furthermore, when similar equipment or other equipment which may cause harmonic current emissions are to be connected to the same interface point with this equipment, to reduce the risk of possible problems which may be caused from addition of those harmonic current emissions, it is recommended to make sure that the short-circuit power Ssc at the interface point is greater than the sum of the minimum Ssc required by all the equipment which will be connected to the interface point.
Ssc (*1)
This unit complies with EN 61000-3-11. However, the impedance of the power supply system to be connected to the unit at the incoming power point must be less than the Zmax given below. In order to meet this condition, consult with the supply authority as required.
Zmax = 0.39 (Ω)
In addition, it is recommended that voltage drops occurring during the unit’s operation in the area at the power input shall be around 3.3% of the nominal power-supply voltage or less.
– 27 –
7 Address Setting
On this unit, it is required to set the addresses of the indoor units before starting air conditioning. Set the addresses following the steps below.
• Be sure to complete the electric wiring before setting the addresses.
• If you turn on the outdoor unit before turning on the indoor units, the CODE No. [E19] is indicated on the 7-segment display on the interface P.C. board of the outdoor unit until the indoor units are turned on. This is not a malfunction.
• It may take up to ten minutes (normally about five minutes) to address one refrigerant line automatically.
• Settings on the outdoor unit are required for automatic addressing. (Address setting is not started simply by turning on the power.)
• Running the unit is not required for address setting.
• The addresses can be set manually.
Automatic addressing: setting addresses using SW15 on the
Manual addressing: setting addresses on the wired remote
* When setting an address manually, the wired remote controller
must temporarily be paired with an indoor unit one-to-one. (when the system is organized for group operation and no Remote controller)
Installation Manual
interface P.C. board on the outdoor unit
controller.
High voltage parts exist in the electrical control box. If you set addresses on an outdoor unit, operate the unit through the cover of electrical control box, to avoid electric shock. Do not remove the cover of electrical control box.
EN-53 EN-54
Page 29
Outdoor Outdoor
Central
controller
Central
controller
Indoor Indoor Indoor Indoor
Remote
controller
Remote
controller
Remote
controller
Outdoor
Indoor
Remote
controller
Outdoor
Central
controller
Indoor Indoor Indoor
Remote
controller
Remote
controller
U. 1. L08 (U. 1. flash)
Auto 1 Auto 2 Auto 3
U. 1. - - - (U. 1. flash)
U. 1. - - - (U. 1. light)
3
2, 4
D600 D601 D602 D603 D604
SW04 SW05 SW15
SW01 SW02 SW03
REQUIREMENT
NOTE
Outdoor
Indoor
Remote
controller
Indoor Indoor Indoor
Outdoor
(Group control)
SW06 SW07 SW09 SW10
SW11 SW12 SW13 SW14
1234 1234 1234 1234
1234 1234 1234 1234
2FAN_IM_DHV2305601-00_EN.book Page 28 Monday, October 28, 2019 3:25 PM
Automatic address setting
No central control (single refrigerant line): go to Address setting procedure 1 Central control of 2 or more refrigerant lines: go to Address setting procedure 2
(Example)
Address setting procedure To procedure 1 To procedure 2
System wiring diagram
When controlling a single refrigerant line
centrally
When controlling 2 or more refrigerant
lines centrally
Address setting procedure 1
1 Turn on indoor units first, and then turn on outdoor units. 2 About one minute after turning the power on, confirm that the 7-segment display on the interface P.C.
board of the outdoor unit indicates .
3 Press SW 15 to start the automatic address setting.
(It may take up to 10 minutes (normally about 5 minutes) to complete one line’s setting.)
4 The 7-segment display indicates .
After the indication, starts flashing on the display. When the flashing stops and remains lit on the display, the setting is complete.
Interface P.C. board on the outdoor unit
Installation Manual
• When 2 or more refrigerant lines are controlled as a group, be sure to turn on all the indoor units in the group before setting addresses.
• If you set the unit addresses of each line separately, each line’s header indoor unit is set separately. In that case, the CODE No. “L03” (Indoor header unit overlap) is indicated as running starts. Change the group address to make one unit the header unit using wired remote controller.
(Example) Controlling 2 or more refrigerant lines as a group
System wiring diagram
Address setting procedure 2
1 Set a system address for each system using SW 13 and 14 on the interface P.C. board on the outdoor unit
of each system. (Factory default: Address 1)
Be sure to set a unique address on each system. Do not use a same address as another system (refrigerant line) or a custom side.
EN
EN-55 EN-56
Interface P.C. board on the outdoor unit
– 28 –
Page 30
NOTE
U1 U2 U3 U4
CN02
CN10
U1 U2 U3 U4
TO INDOOR
UNIT
TO CENTRAL
CONTROLLER
[U1, U2] and [U3, U4] not connected
Communication terminal board
U. 1. L08 (U. 1. flash)
Auto 1 Auto 2 Auto 3
U. 1. - - - (U. 1. flash)
U. 1. - - - (U. 1. light)
2FAN_IM_DHV2305601-00_EN.book Page 29 Monday, October 28, 2019 3:25 PM
Switch settings for a line (system) address on the interface P.C. board on the outdoor unit
( : switch ON, : switch OFF)
Line (system) address
1–
2–
3–
4–
5–
6–
7–
8–
9–
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
“–”: not used for system address setting (Do not change their positions.)
12341234
SW13 SW14
– 29 –
Installation Manual
2 In all the outdoor units connected to the central control, please make sure that the relay connector of the
interface P.C. board “CN10” has not been connected to the “CN02”.
If you connect a relay connector “CN10” to “CN02”, the communication line [U1, U2] will be connected to [U3, U4]. If [U1, U2] is connected to the [U3, U4], refrigerant line address cannot be set correctly.
)
3 Turn on indoor units first, and then turn on outdoor units. 4 About 1 minute after turning the power on, confirm that the 7-segment display on the interface P.C. board
of the outdoor unit indicates .
5 Press SW 15 to start the automatic address setting.
(It may take up to 10 minutes (normally about 5 minutes) to complete one line’s setting.)
6 The 7-segment display indicates .
After the indication, starts flashing on the display. When the flashing stops and remains lit on the display, the setting is complete.
7 Repeat steps 4 to 6 for other refrigerant lines. 8
After completing address setting of all systems, turn off dip switch 2 of SW30 on the interface P.C. boards of all the outdoor units connected to the same central control, except the unit that has the lowest address.
(For unifying the termination of the wiring for the central control of indoor and outdoor units)
EN-57 EN-58
Page 31
NOTE
Header unit inter face P.C. board
U1 U2 U3 U4
CN02
CN10
U1 U2 U3 U4
TO INDOOR
UNIT
TO CENTRAL
CONTROLLER
[U1, U2] and [U3, U4] connected
Communication terminal board
CAUTION
2U1U
B
A
2U1U2U1U
B
A
BA
A
2U1U
2U1U
B
AB
U4
U3
U2
U1
CN02
CN10
U4
U3
U2
U1
CN02
CN10
U4
U3
U2
U1
CN02
CN10
Central
controller
Remote
controller
Remote
controller
Remote
controller
Remote
controller
GroupIndividual
Indoor units (automatic setting)
Outdoor unit [U1, U2] and [U3, U4] connected
Outdoor unit [U1, U2] and [U3, U4] connected
Outdoor unit [U1, U2] and [U3, U4] connected
2FAN_IM_DHV2305601-00_EN.book Page 30 Monday, October 28, 2019 3:25 PM
SW04 SW05 SW15
D600 D601 D602 D603 D604
SW01 SW02 SW03
SW30
SW06 SW10
SW11
SW12 SW13
SW16
SW17
SW30
SW09SW07
SW14
9 Connect the relay connectors “CN10” to “CN02”, which are mounted on the interface P.C. boards of all
the outdoor units connected to the central control.
Installation Manual
Switch setting (setting example when controlling 2 or more refrigerant lines centrally)
Outdoor units (setting manually)
Outdoor unit’s
interface P.C. board
SW13, 14 (Line (system) address)
Dip switch 2 of SW30 (Terminator of indoor / outdoor communication line and central control line)
Relay connector
Outdoor unit Outdoor unit Outdoor unit Factory default
Connect after setting
addresses.
1 231
ON
Set to OFF after
setting addresses.
Connect after setting
addresses.
*The items in bold font must be set manually.
Set to OFF
after setting
addresses.
Connect after setting
addresses.
EN
ON
Open
Please make sure that before you perform this task, address setting of the refrigerant line all have been completed.
Line (system) address 1 1 2 2 3
Indoor unit address 1 2 1 2 1
Group address 0 0 1 2 0
Relay connector connection
Never connect relay connectors between the [U1, U2] and [U3, U4] terminals before completing address setting of all the refrigerant lines. Otherwise, the addresses cannot be set correctly.
10
Set the central control address.
(For the setting of the central control address, refer to the installation manuals of the central control devices.)
EN-59 EN-60
– 30 –
Page 32
Refrigerant line 1 Refrigerant line 2
Outdoor
unit
Outdoor
unit
Indoor unit 1 Indoor unit 2 Indoor unit 3 Indoor unit 1 Indoor unit 2
Remote
controller
ON / OFF
TEMP.
TIME
SET CL
FILTER RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
11
4, 7, 10
2, 5, 8
3, 6, 9
1
CODE No.
SET DATA
NOTE
2FAN_IM_DHV2305601-00_EN.book Page 31 Monday, October 28, 2019 3:25 PM
Manual address setting with the remote controller
Procedure when setting indoor units’ addresses first under the condition that indoor wiring has been completed and outdoor wiring has not been started (manual setting using the remote controller)
Wiring example of 2 refrigerant lines
Line (system) address 1 1 1 2 2
Indoor unit address 1 2 3 1 2
Group address
In the example above, disconnect the remote controller connections between the indoor units and connect a wired remote controller to the target unit directly before address setting.
1
Header unit2Follower unit2Follower unit2Follower unit2Follower unit
– 31 –
Installation Manual
<Line (system) address>
2 Push the TEMP. / buttons repeatedly to set the CODE No. to . 3 Push the TIME / buttons repeatedly to set a system address.
(Match the address with the address on the interface P.C. board of the outdoor unit in the same refrigerant line.)
4 Push the button.
(It is OK if the display turns on.)
<Indoor unit address>
5 Push the TEMP. / buttons repeatedly to set the CODE No. to . 6 Push the TIME / buttons repeatedly to set an indoor unit address. 7 Push the button.
(It is OK if the display turns on.)
<Group address>
8 Push the TEMP. / buttons repeatedly to set the CODE No. to . 9 Push the TIME / buttons repeatedly to set a group address. If the indoor unit is individual, set the
address to ; header unit, ; follower unit, .
Individual : 0000
Header unit : 0001
Follower unit : 0002
10
Push the button. (It is OK if the display turns on.)
11
Push the button. The address setting is complete. ( flashes. You can control the unit after has disappeared.)
In case of group control
1. Do not use address numbers 29 or 30 when setting system addresses using the remote controller.
These 2 address numbers cannot be used on outdoor units and the CODE No. [E04] (Indoor / outdoor communication error) will appear if they are mistakenly used.
Pair the indoor unit to set and the remote controller one-to-one.
Turn on the power.
1 Push and hold the , , and buttons at the same time for more than 4 seconds.
LCD starts flashing.
EN-61 EN-62
2. If you set addresses to indoor units in 2 or more refrigerate lines manually using the remote controller and will
control them centrally, set the outdoor unit of each line as below.
• Set a system address for the outdoor unit of each line with SW13 and 14 of their interface P.C. boards.
• Turn off dip switch 2 of SW30 on the interface P.C. boards of all the outdoor units connected to the same central control, except the unit that has the lowest address. (For unifying the termination of the wiring for the central control of indoor and outdoor units)
• Connect the relay connectors (CN10) between the [U1, U2] and [U3, U4] terminals on the interface P.C. board to CN02 in all the outdoor units to which the central control is connected.
• After finishing all the settings above, set the address of the central control devices. (For the setting of the central control address, refer to the installation manuals of the central control devices.)
Page 33
Star ts running
UNIT LOUVER
UNIT LOUVER
3
1
2
ON / OFF
TEMP.
TIME
SET CL
FILTER RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Stop
5
6
1
3
4 2
ON / OFF
TEMP.
TIME
SET CL
FILTER RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
SWING/FIX
2FAN_IM_DHV2305601-00_EN.book Page 32 Monday, October 28, 2019 3:25 PM
Installation Manual
Confirming the indoor unit addresses and the position of an indoor unit
using the remote controller
Confirming the numbers and positions of indoor units
To see the indoor unit address of an indoor unit which you know the position of
When the unit is individual (the indoor unit is paired with a wired remote controller one-to-one), or it is a group-controlled one.
CODE No.
UNIT No.
FILTER RESET
TEMP.
TEST
TIMER SET
TIME
SET CL
ON / OFF
1
2
(Execute it while the units are running.)
1 Push the button if the units stop. 2 Push the button (left side of the button).
A unit numbers is indicated on the LCD (it will disappear after a few seconds). The indicated number shows the system address and indoor unit address of the unit. When 2 or more indoor units are connected to the remote controller (group-controlled units), a number of other connected units appears each time you push the button (left side of the button).
To find an indoor unit’s position from its address
When checking unit numbers controlled as a group
(Execute it while the units are stopped.)
The indoor unit numbers in a group are indicated one after another. The fan and louvers of the indicated units are activated.
1 Push and hold the and buttons at the same time for more than 4 seconds.
appears on UNIT No. on the LCD display.
• The fans and louvers of all the indoor units in the group are activated.
2 Push the button (left side of the button). Each time you push the button, the indoor unit numbers
are indicated one after another.
• The first-indicated unit number is the address of the header unit.
• Only the fan and louvers of the indicated indoor unit are activated.
UNIT LOUVER
3 Push the button to finish the procedure.
All the indoor units in the group stop.
To check all the indoor unit addresses using an arbitrary wired remote controller. (When communication wirings of 2 or more refrigerant lines are interconnected for central control)
(Execute it while the units are stopped.)
You can check indoor unit addresses and positions of the indoor units in a single refrigerant line. When an outdoor unit is selected, the indoor unit numbers of the refrigerant line of the selected unit are indicated one after another and the fan and louvers of the indicated indoor units are activated.
EN
1 Push and hold the TIME and buttons at the same time for more than 4 seconds.
At first, the line 1 and CODE No. (Address Change) are indicated on the LCD display. (Select an outdoor unit.)
2 Push the (left side of the button) and buttons repeatedly to select a system address.
UNIT LOUVER
3 Push the button to confirm the system address selection.
• The address of an indoor unit connected to the selected refrigerant line is indicated on the LCD display and its fan and louvers are activated.
4 Push the button (left side of the button). Each time you push the button, the indoor unit numbers
EN-63 EN-64
– 32 –
of the selected refrigerant line are indicated one after another.
• Only the fan and louvers of the indicated indoor unit are activated.
UNIT LOUVER
Page 34
3 5
8
1
4
2, 6, 7
ON / OFF
TEMP.
TIME
SET CL
FILTER RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Finish
UNIT LOUVER
NOTE
Cancels the line selection
SWING/FIX
4 8
5, 7
6
ON / OFF
TEMP.
TIME
SET CL
FILTER RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Finish
Press to finish setting.
2FAN_IM_DHV2305601-00_EN.book Page 33 Monday, October 28, 2019 3:25 PM
To select another system address
5 Push the button to return to step 2.
• After returning to step 2, select another system address and check the indoor unit addresses of the line.
6 Push the button to finish the procedure.
Changing the indoor unit address using a remote controller
To change an indoor unit address using a wired remote controller.
The method to change the address of an individual indoor unit (the indoor unit is paired with a wired remote controller one-to-one), or an indoor unit in a group. (The method is available when the addresses have already been set automatically.)
(Execute it while the units are stopped.)
1 Push and hold the , , and buttons at the same time for more than 4 seconds.
(If 2 or more indoor units are controlled in a group, the first indicated UNIT No. is that of the head unit.)
2 Push the button (left side of the button) repeatedly to select an indoor unit number to change if 2
or more units are controlled in a group. (The fan and louvers of the selected indoor unit are activated.)
(The fan of the selected indoor unit is turned on.)
UNIT LOUVER
3 Push the TEMP. / buttons repeatedly to select for CODE No. 4 Push the TIME / buttons repeatedly to change the value indicated in the SET DATA section to that
you want.
5 Push the button. 6 Push the button (left side of the button) repeatedly to select another indoor UNIT No. to change.
Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.
UNIT LOUVER
7 Push the button (left side of the button) to check the changed addresses. 8 If the addresses have been changed correctly, push the button to finish the procedure.
– 33 –
Installation Manual
To change all the indoor unit addresses using an arbitrary wired remote controller. (The method is available when the addresses have already been set automatically.)
(When communication wirings of 2 or more refrigerant lines are interconnected for central control)
You can change the addresses of indoor units in each refrigerant line using an arbitrary wired remote controller.
* Enter the address check / change mode and change the addresses.
UNIT No.
R.C. No.
CODE No.
ON / OFF
2
DATA
SET
SETTING
TEMP.
TIMER SET
TIME
1
FILTER
RESET
CL
SET
TEST
3
If no number appears on UNIT No., no outdoor unit exists on the line. Push button and select another line following step 2.
(Execute it while the units are stopped.)
1 Push and hold the TIME and buttons at the same time for more than 4 seconds.
At first, the line 1 and CODE No. (Address Change) are indicated on the LCD display.
2 Push (left side of the button) and buttons repeatedly to select a system address.
UNIT LOUVER
3 Push the button.
• The address of one of the indoor units connected to the selected refrigerant line is indicated on the LCD display and the fan and louvers of the unit are activated. At first, the current indoor unit address is displayed in SET DATA. (No system address is indicated.)
EN-65 EN-66
Page 35
U1 U2
A B
U1 U2
A B
U1 U2
A B
U1
U2
A B
U1 U3
U2 U4
U1
U2
A B
U4
U3
U2
U1
CN02
CN10
U4
U3
U2
U1
CN02
CN10
U4
U3
U2
U1
CN02
CN10
Remote
controller
Central controller
Remote
controller
Remote
controller
Remote
controller
Indoor units to have their addresses initialized
Outdoor unit
[U1, U2] and [U3, U4] connected
[U1, U2] and [U3, U4] connected
[U1, U2] and [U3, U4] not connected
Outdoor unitOutdoor unit
NOTE
U. 1. - - -
A.d.buS
A.d.nEt
A.d. c.L.
U.1.L08
A.d. n.G.
2FAN_IM_DHV2305601-00_EN.book Page 34 Monday, October 28, 2019 3:25 PM
Installation Manual
4 Push the TIME / buttons repeatedly to change the value of the indoor unit address in SET DATA.
Change the value in SET DATA to that of a new address.
5 Push the button to confirm the new address on SET DATA. 6 Push the button (left side of the button) repeatedly to select another address to change.
Each time you push the button, the indoor unit numbers in a refrigerant line are indicated one after another. Only the fan and louvers of the selected indoor unit are activated.
Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.
UNIT LOUVER
7 Push the button.
(All the segments on the LCD display light up.)
8 Push the button to finish the procedure.
Resetting the address
(Resetting to the factory default (address undecided))
Method 1
Clearing each address separately using a wired remote controller. Set the system address, indoor unit address and group address to “0099” using a wired remote controller. (For the setting procedure, refer to the address setting procedures using the wired remote controller on the previous pages.)
Method 2
Clearing all the indoor unit addresses on a refrigerate line at once from the outdoor unit.
1 Turn off the refrigerant line to reset to the factory default and set the outdoor unit of the line as below.
1) Disconnect the relay connectors between the [U1, U2] and [U3, U4] terminals. (Leave them as they are if they have already been disconnected.)
2) Turn on dip switch 2 of SW30 on the interface P.C. board of the outdoor unit if the switch is OFF. (Leave it as it is if it has already been set to ON.)
2 Turn on the indoor and outdoor units of the refrigerant line for which you want to initialize the addresses.
About one minute after turning on the power, confirm that the 7-segment display on the outdoor unit indicates and operate the interface P.C. board on the outdoor unit of the refrigerant line as follows.
SW01 SW02 SW03 SW04 Clearable addresses
212
222
Confirm that the 7-segment display indicates
five seconds.
Confirm that the 7-segment display indicates
five seconds.
and turn SW04 ON for more than
and turn SW04 ON for more than
System / indoor unit / group address
Central control address
3 Confirm that the 7-segment display indicates and set SW01, SW02 and SW03 to 1, 1, 1
respectively.
4 After a time appears on the 7-segment display if the address clearing has been completed
successfully. If appears on the 7-segment display, the outdoor unit may still be connected to another refrigerant line. Check again the connection of the relay connectors (CN10) between the [U1, U2] and [U3, U4] terminals.
Take care to carry out the procedure above correctly; otherwise, addresses in other refrigerate lines may also be cleared.
5 Set the addresses again after finishing the clearance.
EN
– 34 –
EN-67 EN-68
Page 36
CAUTION
L23-02
SW06 SW07 SW09 SW10
SW11 SW12
1234 1234 1234 1234
1234 1234
CAUTION
NOTE
1, 5
3
2, 4
ON / OFF
TEMP.
TIME
SET CL
FILTER RESET
TEST
TIMER SET
2FAN_IM_DHV2305601-00_EN.book Page 35 Monday, October 28, 2019 3:25 PM
8 Test Run
Settings for hot water modules
After automatic addressing is completed, if there is hot water module in the system, 7-segment display will indicate
.
Please adjust the DIP switch as below, and slide SW09-bit4 to "ON" position.
Before test run
Confirm that the valve of the refrigerate pipe of the outdoor unit is OPEN.
• Before turning on the power, confirm that the resistance between the terminal block of power supply and the earth is more than 1 M using a 500 V megohmmeter. Do not run the unit if it is less than 1 MΩ.
• Turn on the power and turn on the case heater of the compressor. To save the compressor when it is activated, leave the power on for more than 12 hours.
Methods of test run
When executing a test run using a remote controller
Operate the system normally to check the running condition using the wired remote controller. Follow the instructions in the supplied owner’s manual when operating the unit. If you use a wireless remote controller for operations, follow the instructions in the installation manual supplied with the indoor unit. To execute a test run forcibly under the condition that the thermostat automatically turns the unit off due to the indoor temperature, follow the procedure below. The forcible test run will automatically stop after 60 minutes to prevent continuous forcible running and return to normal running.
– 35 –
Installation Manual
Do not use forcible running except for a test run as it overloads the unit.
1 Push and hold the button for more than 4 seconds. TEST appears on the LCD display and the unit
enters the test mode. (TEST is indicated on the LCD display during the test run.)
TEST
2 Push the button. 3 Push the button to switch the running mode to COOL or HEAT.
• Do not run the unit in any mode other than COOL or HEAT.
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
TEST
EN-69 EN-70
4 Push the button to stop running after finishing the test run.
The indication on the LCD display returns to the status of procedure 1.
Page 37
NOTE
2FAN_IM_DHV2305601-00_EN.book Page 36 Monday, October 28, 2019 3:25 PM
Installation Manual
5 Push the button to exit the test mode.
(TEST disappears on the LCD display and the status changes to normal stopped mode.)
When executing a test run using the interface P.C. board on the outdoor unit
You can execute a test run by operating switches on the interface P.C. board of the outdoor unit. “Individual test run”, which tests each indoor unit separately, and “collective test run”, which tests all the indoor units connected, are available.
<Individual test run>
Starting operation
1 Set the running mode to “COOL” or “HEAT” on the remote controller of the indoor unit to be tested.
(The unit will run in the current mode unless you set the mode otherwise.)
7-segment display
[A]
[U1]
[B]
[ ]
2 Set the rotary switches on the interface P.C. board of the outdoor unit: SW01 to [16], SW02 and SW03 to
the address of the indoor unit to be tested.
SW02 SW03 Indoor unit address
1 to 16 1 1 to 16 Set number of SW02
1 to 16 2 17 to 32 Set number of SW02 + 16
1 to 16 3 33 to 48 Set number of SW02 + 32
1 to 16 4 49 to 64 Set number of SW02 + 48
7-segment display
[A]
[ ]
Address display of the corresponding
indoor unit
[B]
[ ]
3 Push and hold SW04 for more than 10 seconds.
7-segment display
[A]
[ ]
Address display of the corresponding
indoor unit
• The running mode follows the mode setting on the remote controller of the target indoor unit.
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after turning the power on or stopping running.
Finishing operation
[B]
[ ]
[FF] is displayed for 5
seconds.
1 Set the rotary switches on the interface P.C. board of the outdoor unit back: SW01 to [1], SW02 to [1] and
SW03 to [1].
7-segment display
[A]
[U1]
[B]
[ ]
<Collective test run>
Start operation
1 Set the rotary switches on the interface P.C. board of the outdoor unit as below.
When in “COOL” mode: SW01=[2], SW02=[5], SW03=[1]. When in “HEAT” mode: SW01=[2], SW02=[6], SW03=[1].
7-segment display
[A] [C ] [H ]
[B] [ ] [ ]
2 Push and hold SW04 for more than 2 seconds.
7-segment display
[A] [C ] [H ]
[B] [ - C ] [ - H ]
EN
EN-71 EN-72
– 36 –
Page 38
NOTE
SW09SW07
SW11
SW06 SW10
SW12 SW13
SW16
SW14
SW17
D600 D601 D602 D603 D604
SW04 SW05 SW15
SW01 SW02 SW03
SW30
D600 D601 D602 D603 D604
SW04 SW05 SW15
SW01 SW02 SW03
Interface P.C. board
Push switch
7-segment display [A]
Push switch
7-segment display [B]
Rotary switches
2FAN_IM_DHV2305601-00_EN.book Page 37 Monday, October 28, 2019 3:25 PM
– 37 –
Installation Manual
9 Troubleshooting
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after turning the power on or stopping running.
Stop operation
1 Set the rotary switches on the interface P.C. board of the outdoor unit back:
SW01 to [1], SW02 to [1] and SW03 to [1].
7-segment display
[A]
[U1]
EN-73 EN-74
[B]
[ ]
In addition to the CODE No. on the remote controller of an indoor unit, you can diagnose failure type of an outdoor unit by checking the 7-segment display on the interface P.C. board. Use the function for various checks. Set every dip switch to OFF after checking.
7-Segment display and check code
Rotary switch setting
value
Indication LED
SW01 SW02 SW03
1 1 1 Outdoor unit check code
A
B Check code display*
* If a check code has an auxiliary code, the display indicates the check code for three seconds and the auxiliary code
for one second alternately.
Check code (indicated on the 7-segment display on the outdoor unit)
Indicated when SW01 = [1], SW02 = [1], and SW03 = [1].
Check code
Auxiliary code
E06 Number of indoor units which received normally Decrease of number of indoor units, or HWM unit only
E07 Indoor / Outdoor communication circuit trouble
E08 Duplicated indoor addresses Duplication of indoor addresses
E15 No indoor unit during automatic addressing
E16 00: Capacity over 01 or more: No. of connected units Number of connected capacity over / indoor units
01: Other line outdoor connected
E20
02: Other line indoor connected
Other line connected during automatic addressing
E31 IPDU quantity information*1 IPDU communication trouble
F04 TD sensor trouble
F06 TE sensor trouble
01: TL1 sensor
F07
03: TL3 sensor
TL1 or TL3 sensor trouble
F08 TO sensor trouble
01: TS1 sensor
F12
03, 04: TS3 sensor
TS1 or TS3 sensor trouble
F13 TH sensor (Board installed) trouble
F15 Outdoor temp. sensor miswiring (TE, TL1)
F16 Outdoor pressure sensor miswiring (Pd, Ps)
F23 Ps sensor trouble
F24 Pd sensor trouble
D600
D601 D602 D603 D604
AB
Outdoor unit number
Check code nameIndication on 7-segment display on the outdoor unit
(U1)
Page 39
e.g., charged amount (10 kg)
Outdoor unit
e.g., charged amount (15 kg)
Indoor unit
Room A Room B Room C Room D Room E Room F
01_IM_DHV2305601-00_EN.fm Page 38 Wednesday, November 27, 2019 11:36 AM
Installation Manual
*1 IPDU number information
01: Compressor 02: Fan 1 03: Compressor and Fan 1 04: Fan 2 05: Compressor and Fan 2 06: Fan 1 and Fan 2 07: Compressor, Fan 1 and Fan 2 08: Fan 3 09: Compressor and Fan 3 0A: Fan 1 and Fan 3 0B: Compressor, Fan 1 and Fan 3 0C: Fan 2 and Fan 3 0D: Compressor, Fan 2 and Fan 3 0E: Fan 1, Fan 2 and Fan 3 0F: Compressor, Fan 1, Fan 2 and Fan 3
EN-75 EN-76
Check code
Check code nameIndication on 7-segment display on the outdoor unit
Auxiliary code
F31 Outdoor program trouble
H01 Compressor breakdown
H02 Compressor trouble (Lock)
H03 Current detective circuit system trouble
H05 TD sensor miswiring
H06 Low-pressure protective operation
H07 Oil level down detection
H08 01 TK sensor trouble for oil level
H16 01 Oil level detector circuit trouble
L04 Outdoor system address duplicated
L06 Number of indoor units with priority Duplication of indoor units with priority
L08 Indoor group / Address unset
L10 Outdoor capacity unset
L23 02 SW setting trouble when connecting to HWM unit
L29 IPDU quantity information *1 IPDU quantity trouble
L30 Detected indoor unit address External interlock of indoor unit
P03 Discharge temp TD trouble
P04 High-pressure switch trouble
00 Phase missing detection
P05
*E (* : FAN motor number) Fan motor Vdc trouble
Compressor Vdc trouble
P07 Heat sink overheat trouble
P10 Detected indoor unit address Indoor overflow trouble
P13 Outdoor liquid back detection trouble
P15 01: TS1 condition 02: TD condition Gas leak detection
P19 4-way valve operation trouble
P20 High-pressure protective operation
*0: Elemental device short *1: Position detective circuit trouble *2: Input current sensor trouble *3: Fan motor lock trouble *4: Motor current trouble
P22
*5: Synchronize, step out trouble *C: Sensor temperature trouble *D: Sensor short, free trouble (*: Fan motor number)
P26 Compressor IPM short protection trouble
P29 Compressor position detective circuit system trouble
Outdoor fan IPDU trouble
– 38 –
WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit.
The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost non-existent. With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur). In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m
Concentration limit (kg/m
3
)
The concentration limit of R410A which is used in multi air conditioners is 0.3 kg/m
NOTE 1
If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as charged in each independent device.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A, B and C is 10 kg. The possible amount of leaked refrigerant gas in rooms D, E and F is 15 kg.
3
)
3
.
EN
Page 40
Outdoor unit
Refrigerant piping
Indoor unit
Refrigerant piping
Outdoor unit
Indoor unit
Mechanical ventilation device - Gas leak detector
Very small room
Small
room
Medium
room
Large room
0
5
10
10 20 30
15
20
25
30
35
40
m
2
Min. indoor floor area
Total amount of refrigerant kg
Range below the density limit of
0.3 kg/m
3
(countermeasures not needed)
Range above the density limit of 0.3 kg/m
3
(countermeasures needed)
2FAN_IM_DHV2305601-00_EN.book Page 39 Monday, October 28, 2019 3:25 PM
Important
NOTE 2
The standards for minimum room volume are as follows. (1) No partition (shaded portion)
(2) When there is an effective opening with the
adjacent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).
(3) If an indoor unit is installed in each
partitioned room and the refrigerant piping is interconnected, the smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object.
– 39 –
Installation Manual
NOTE 3
The minimum indoor floor area compared with the amount of refrigerant is roughly as follows: (When the ceiling is 2.7m high)
EN-77
Page 41
2FAN_IM_DHV2305601-00_EN.book Page 40 Monday, October 28, 2019 3:25 PM
MEMO
Installation Manual
EN
– 40 –
Page 42
2FAN_IM_DHV2305601-00_EN.book Page 41 Monday, October 28, 2019 3:25 PM
MEMO
– 41 –
Installation Manual
Page 43
2FAN_IM_DHV2305601-00_EN.book Page 42 Monday, October 28, 2019 3:25 PM
MEMO
Installation Manual
EN
– 42 –
Page 44
2FAN_IM_DHV2305601-00_EN.book Page 43 Monday, October 28, 2019 3:25 PM
DHV2305601-00
Loading...