2FAN_IM_DHV2305601-00_EN.book Page 2 Monday, October 28, 2019 3:25 PM
Installation Manual
Thank you for purchasing this Toshiba air conditioner.
This Installation Manual describes the installation method of the outdoor unit. For installation of indoor units, follow the
Installation Manual supplied with the indoor unit.
Moreover, as this installation manual includes the important articles concerning the “Machinery” Directive (Directive
2006/42/EC), please read through the manual and make sure you understand it. After installation, give this Installation
Manual, the Owner’s Manual and the Installation Manual supplied with the indoor unit to the customer and tell the
customer to keep them safe.
Prepare an exclusive power source for indoor units, independent to that for outdoor units.
Y-shaped branching joints or a branching header (separately purchased) are required for connecting pipes between
indoor and outdoor units. Choose either of them considering the system capacity concerning piping. For installing
branching pipes, refer to the installation manual of the Y-shaped branching unit or branching header (separately
purchased).
Generic Denomination: Air Conditioner
Definition of Qualified Installer or Qualified Service Person
The air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified service
person. When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you.
A qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the
table below.
AgentQualifications and knowledge which the agent must have
Qualified
installer
• The qualified installer is a person who installs, maintains, relocates and removes the air
conditioners made by Toshiba Carrier Corporation. He or she has been trained to install,
maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or,
alternatively, he or she has been instructed in such operations by an individual or individuals
who have been trained and is thus thoroughly acquainted with the knowledge related to these
operations.
• The qualified installer who is allowed to do the electrical work involved in installation,
relocation and removal has the qualifications pertaining to this electrical work as stipulated by
the local laws and regulations, and he or she is a person who has been trained in matters
relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or,
alternatively, he or she has been instructed in such matters by an individual or individuals who
have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to do the refrigerant handling and piping work involved
in installation, relocation and removal has the qualifications pertaining to this refrigerant
handling and piping work as stipulated by the local laws and regulations, and he or she is a
person who has been trained in matters relating to refrigerant handling and piping work on the
air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been
instructed in such matters by an individual or individuals who have been trained and is thus
thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to work at heights has been trained in matters relating to
working at heights with the air conditioners made by Toshiba Carrier Corporation or,
alternatively, he or she has been instructed in such matters by an individual or individuals who
have been trained and is thus thoroughly acquainted with the knowledge related to this work.
Qualified
service
person
• The qualified service person is a person who installs, repairs, maintains, relocates and
removes the air conditioners made by Toshiba Carrier Corporation. He or she has been
trained to install, repair, maintain, relocate and remove the air conditioners made by Toshiba
Carrier Corporation or, alternatively, he or she has been instructed in such operations by an
individual or individuals who have been trained and is thus thoroughly acquainted with the
knowledge related to these operations.
• The qualified service person who is allowed to do the electrical work involved in installation,
repair, relocation and removal has the qualifications pertaining to this electrical work as
stipulated by the local laws and regulations, and he or she is a person who has been trained
in matters relating to electrical work on the air conditioners made by Toshiba Carrier
Corporation or, alternatively, he or she has been instructed in such matters by an individual or
individuals who have been trained and is thus thoroughly acquainted with the knowledge
related to this work.
• The qualified service person who is allowed to do the refrigerant handling and piping work
involved in installation, repair, relocation and removal has the qualifications pertaining to this
refrigerant handling and piping work as stipulated by the local laws and regulations, and he or
she is a person who has been trained in matters relating to refrigerant handling and piping
work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she
has been instructed in such matters by an individual or individuals who have been trained and
is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to work at heights has been trained in matters
relating to working at heights with the air conditioners made by Toshiba Carrier Corporation
or, alternatively, he or she has been instructed in such matters by an individual or individuals
who have been trained and is thus thoroughly acquainted with the knowledge related to this
work.
Definition of Protective Gear
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and
‘safety’ work clothing.
In addition to such normal protective gear, wear the protective gear described below when undertaking the special
work detailed in the table below.
Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns, electric
shocks and other injuries.
Work undertakenProtective gear worn
All types of workProtective gloves
Electrical-related
work
Work done at heights
(50 cm or more)
Transportation of
heavy objects
Repair of outdoor
unit
‘Safety’ working clothing
Gloves to provide protection for electricians
Insulating shoes
Clothing to provide protection from electric shock
Helmets for use in industry
Shoes with additional protective toe cap
Gloves to provide protection for electricians
EN
EN-3EN-4
– 2 –
Page 4
CAUTION
Do not touch the aluminum
fins of the unit.
Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before
the operation, otherwise there
might be the burst.
Never recover the refrigerant
into the outdoor outdoor unit.
01_IM_DHV2305601-00_EN.fm Page 3 Thursday, December 5, 2019 5:00 PM
Warning Indications on the Air Conditioner Unit
Warning indicationDescription
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote
electric power supplies
before servicing.
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric
power supplies before servicing.
WARNING
WARNING
Moving parts.
Do not operate unit with grille
removed.
Stop the unit before the servicing.
Moving parts.
Do not operate unit with grille
removed.
Stop the unit before the servicing.
CAUTION
High temperature parts.
You might get burned
when removing this panel.
CAUTION
High temperature parts.
You might get burned when
removing this panel.
– 3 –
CAUTION
Do not climb onto the
top side.
Doing so may result in injury.
Installation Manual
CAUTION
BURST HAZARD
Open the service valves before
the operation, otherwise there
might be the burst.
Never recover the refrigerant into
the outdoor outdoor unit.
CAUTION
Do not climb onto the fan
guard.
Doing so may result in injury.
EN-5EN-6
CAUTION
Do not touch the aluminum fins of
the unit.
Doing so may result in injury.
Page 5
WARNING
01_IM_DHV2305601-00_EN.fm Page 4 Wednesday, November 27, 2019 11:26 AM
Installation Manual
1Precautions for Safety
The manufacturer shall not assume any liability for the damage
caused by not observing the description of this manual.
General
• Before starting to install the air conditioner, read through the
Installation Manual carefully, and follow its instructions to install the
air conditioner. Otherwise, falling down of the unit may occur, or the
unit may cause noise, vibration or water leakage.
• Only a qualified installer or qualified service person is allowed to do
installation work. If installation is carried out by an unqualified
individual, a fire, electric shocks, injury, water leakage, noise and /
or vibration may result.
• Do not use any refrigerant different from the one specified for
complement or replacement. Otherwise, abnormally high pressure
may be generated in the refrigeration cycle, which may result in a
failure or explosion of the product or an injury to your body.
• If using separately sold products, make sure to use Toshiba
specified products only. Using unspecified products may cause fire,
electric shock, water leak or other failure.
• Before opening the service panel of the outdoor unit, set the circuit
breaker to the OFF position. Failure to set the circuit breaker to the OFF
position may result in electric shocks through contact with the interior
parts. Only a qualified installer or qualified service person is allowed to
remove the service panel of the outdoor unit and do the work required.
• Before carrying out the installation, maintenance, repair or removal
work, be sure to set the circuit breakers for both the indoor and
outdoor units to the OFF position. Otherwise, electric shock may
result.
• Place a “Work in progress” sign near the circuit breaker while the
installation, maintenance, repair or removal work is being carried
out. There is a danger of electric shocks if the circuit breaker is set
to ON by mistake.
• Only a qualified installer or qualified service person is allowed to
undertake work at heights using a stand of 50 cm or more.
• When working at heights, use a ladder which complies with the ISO
14122 standard, and follow the procedure in the ladders
instructions. Also wear a helmet for use in industry as protective
gear to undertake the work.
• Wear protective gloves and safety work clothing during installation,
servicing and removal.
• Do not touch the aluminium fin of the outdoor unit. You may injure
yourself if you do so. If the fin must be touched for some reason, first
put on protective gloves and safety work clothing, and then proceed.
• Do not climb onto or place objects on top of the outdoor unit. You may
fall or the objects may fall off of the outdoor unit and result in injury.
• When working at height, put a sign in place so that no-one will
approach the work location before proceeding with the work. Parts
or other objects may fall from above, possibly injuring a person
below. Also, be sure that workers put on helmets.
• When cleaning the filter or other parts of the outdoor unit, set the
circuit breaker to OFF without fail, and place a “Work in progress”
sign near the circuit breaker before proceeding with the work.
• The refrigerant used by this air conditioner is the R410A.
• You shall ensure that the air conditioner is transported in stable
condition. If you find any part of the product broken, contact your dealer.
• Do not modify the products. Do not also disassemble or modify the
parts. It may cause a fire, electric shock or injury.
• Before starting to repair the air conditioner, read carefully through
the Service Manual, and repair the air conditioner by following its
instructions.
• Only qualified service person is allowed to repair the air conditioner.
Repair of the air conditioner by unqualified person may give rise to a
fire, electric shocks, injury, water leaks and/or other problem.
• Once the repair work has been completed, check for refrigerant
leaks, and check the insulation resistance and water drainage. Then
perform a trial run to check that the air conditioner is running properly.
EN
EN-7EN-8
– 4 –
Page 6
01_IM_DHV2305601-00_EN.fm Page 5 Wednesday, November 27, 2019 11:26 AM
• This appliance is intended to be used by expert or trained users in
shops, in light industry, or for commercial use by lay persons.
• This appliance is not intended for use by persons (including children)
with reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given supervision
or instruction concerning use of the appliance by a person
responsible for their safety.
• Children should be supervised to ensure that they do not play with
the appliance.
Selection of installation location
• If you install the unit in a small room, take appropriate measures to
prevent the refrigerant from exceeding the limit concentration even if it
leaks. Consult the dealer from whom you purchased the air conditioner
when you implement the measures. Accumulation of highly
concentrated refrigerant may cause an oxygen deficiency accident.
• Do not install the air conditioner in a location that may be subject to
a risk of exposure to a combustible gas. If a combustible gas leaks
and becomes concentrated around the unit, a fire may occur.
• When transporting the air conditioner, wear shoes with additional
protective toe caps.
• When transporting the air conditioner, do not take hold of the bands around
the packing carton. You may injure yourself if the bands should break.
• Do not place any combustion appliance in a place where it is
directly exposed to the wind of air conditioner, otherwise it may
cause imperfect combustion.
• Places where the operation sound of the outdoor unit may cause a
disturbance. (Especially at the boundary line with a neighbour,
install the air conditioner while considering the noise.)
• When transporting the air conditioner, use a forklift and when
moving the air conditioner by hand, move the unit with 6 people.
Installation
• Follow the instructions in the installation manual to install the air
conditioner. Failure to follow these instructions may cause the
– 5 –
Installation Manual
product to fall down or topple over or give rise to noise, vibration,
water leakage, etc.
• The designated bolts (M12) and nuts (M12) for securing the
outdoor unit must be used when installing the unit.
• Install the outdoor unit property in a location that is durable enough
to support the weight of the outdoor unit. Insufficient durability may
cause the outdoor unit to fall, which may result in injury.
• Install the unit in the prescribed manner for protection against
strong wind and earthquake. Incorrect installation may result in the
unit falling down, or other accidents.
• Be sure to fix the screws back which have been removed for
installation or other purposes.
Refrigerant piping
• Install the refrigerant pipe securely during the installation work
before operating the air conditioner. If the compressor is operated
with the valve open and without refrigerant pipe, the compressor
sucks air and the refrigeration cycles is over pressurized, which
may cause a injury.
• Tighten the flare nut with a torque wrench in the specified manner.
Excessive tighten of the flare nut may cause a crack in the flare nut
after a long period, which may result in refrigerant leakage.
• Ventilate the air if the refrigerant gas leaks during installation. If the
leaked refrigerant gas comes into contact with fire, toxic gas may
be produced.
• After installation work, check the refrigerant gas does not leak. If
the refrigerant gas leaks in the room, poisonous gas generates
when gas touches to fire such as fan heater, stove or cocking stove
though the refrigerant gas itself is innocuous.
• When the air conditioner has been installed or relocated, follow the
instructions in the Installation Manual and purge the air completely
so that no gases other than the refrigerant gas will be mixed in the
refrigerating cycle. Failure to purge the air completely may cause
the air conditioner to malfunction.
EN-9EN-10
Page 7
01_IM_DHV2305601-00_EN.fm Page 6 Wednesday, November 27, 2019 11:26 AM
Installation Manual
• Nitrogen gas must be used for the airtight test.
• The charge hose must be connected in such a way that it is not slack.
• If refrigerant gas has leaked during the installation work, ventilate
the room immediately. If the leaked refrigerant gas comes in
contact with fire, noxious gas may be generated.
Electrical wiring
• Only a qualified installer or qualified service person is allowed to
carry out the electrical work of the air conditioner. Under no
circumstances must this work be done by an unqualified individual
since failure to carry out the work properly may result in electric
shocks and / or electrical leaks.
• When connecting the electrical wires, repairing the electrical parts
or undertaking other electrical jobs, wear gloves to provide
protection for electricians, insulating shoes and clothing to provide
protection from electric shocks. Failure to wear this protective gear
may result in electric shocks.
• When executing address setting, test run, or troubleshooting
through the checking window on the electric parts box, put on
insulated gloves to provide protection from electric shock.
Otherwise you may receive an electric shock.
• Use wiring that meets the specifications in the Installation Manual
and the stipulations in the local regulations and laws. Use of wiring
which does not meet the specifications may give rise to electric
shocks, electrical leakage, smoking and / or a fire.
• Check that the product is properly earthed. (grounding work)
Incomplete earthing may cause electric shock.
• Do not connect the earth line to a gas pipe, water pipe, lightning
conductor, or a telephone earth line.
• After completing the repair or relocation work, check that the
ground wires are connected properly.
• Install a circuit breaker that meets the specifications in the installation
manual and the stipulations in the local regulations and laws.
• Install the circuit breaker where it can be easily accessed by the
qualified service person.
• When installing the circuit breaker outdoors, install one which is
designed to be used outdoors.
• Under no circumstances must the power cable be extended.
Connection trouble in the places where the cable is extended may
give rise to smoking and / or a fire.
• Electrical wiring work shall be conducted according to law and
regulation in the community and installation manual. Failure to do
so may result in electrocution or short circuit.
• Do not supply power from the power terminal block equipped on
the outdoor unit to another outdoor unit. Capacity overflow may
occur on the terminal block and may result in fire.
• When carrying out electric connection, use the wire specified in the
Installation Manual and connect and fix the wires securely to
prevent them applying external force to the terminals. Improper
connection or fixing may result in fire.
• If the supply cord is damaged, it must be replaced by the
manufacturer, its service agent or similarly qualified persons in
order to avoid a hazard.
Installation of earth leakage circuit breaker
• Install the earth leakage circuit breaker that meets the stipulations
in the local regulations and laws.
• The earth leakage circuit breaker needs to have over-current
protection and leakage prevention function that can be manually reset.
Test run
• Before operating the air conditioner after having completed the
work, check that the electrical parts box cover of the indoor unit and
service panel of the outdoor unit are closed, and set the circuit
breaker to the ON position. You may receive an electric shock if the
power is turned on without first conducting these checks.
• When you have noticed that some kind of trouble (such as when an
error display has appeared, there is a smell of burning, abnormal
sounds are heard, the air conditioner fails to cool or heat or water is
EN
EN-11EN-12
– 6 –
Page 8
CAUTION
01_IM_DHV2305601-00_EN.fm Page 7 Wednesday, November 27, 2019 11:26 AM
leaking) has occurred in the air conditioner, do not touch the air
conditioner yourself but set the circuit breaker to the OFF position,
and contact a qualified service person. Take steps to ensure that
the power will not be turned on (by marking “out of service” near
the circuit breaker, for instance) until qualified service person
arrives. Continuing to use the air conditioner in the trouble status
may cause mechanical problems to escalate or result in electric
shocks or other failure.
• After the work has finished, be sure to use an insulation tester set
(500 V Megger) to check the resistance is 1 MΩ or more between
the charge section and the non-charge metal section (Earth
section). If the resistance value is low, a disaster such as a leak or
electric shock is caused at user’s side.
• Upon completion of the installation work, check for refrigerant leaks
and check the insulation resistance and water drainage. Then
conduct a test run to check that the air conditioner is operating
properly.
Explanations given to user
• Upon completion of the installation work, tell the user where the
circuit breaker is located. If the user does not know where the
circuit breaker is, he or she will not be able to turn it off in the event
that trouble has occurred in the air conditioner.
• If you have discovered that the fangard is damaged, do not
approach the outdoor unit but set the circuit breaker to the OFF
position, and contact a qualified service person to have the repairs
done. Do not set the circuit breaker to the ON position until the
repairs are completed.
• After the installation work, follow the Owner’s Manual to explain to
the customer how to use and maintain the unit.
Relocation
• Only a qualified installer or qualified service person is allowed to
relocate the air conditioner. It is dangerous for the air conditioner to
be relocated by an unqualified individual since a fire, electric
– 7 –
Installation Manual
shocks, injury, water leakage, noise and / or vibration may result.
• When carrying out the pump-down work shut down the compressor
before disconnecting the refrigerant pipe. Disconnecting the
refrigerant pipe with the service valve left open and the compressor
still operating will cause air or other gas to be sucked in, raising the
pressure inside the refrigeration cycle to an abnormally high level,
and possibly resulting in rupture, injury or other trouble.
• Never recover the refrigerant into the outdoor unit. Be sure to use a
refrigerant recovery machine to recover the refrigerant when moving
or repairing. It is impossible to recover the refrigerant into the outdoor
unit. Refrigerant recovery into the outdoor unit may result in serious
accidents such as explosion of the unit, injury or other accidents.
New Refrigerant Air Conditioner Installation
• This air conditioner adopts the new HFC refrigerant (R410A) which
does not destroy ozone layer.
• The characteristics of R410A refrigerant are; easy to absorb water,
oxidizing membrane or oil, and its pressure is approx. 1.6 times
higher than that of refrigerant R22. Accompanied with the new
refrigerant, refrigerating oil has also been changed. Therefore,
during installation work, be sure that water, dust, former refrigerant,
or refrigerating oil does not enter the refrigerating cycle.
• To prevent charging an incorrect refrigerant and refrigerating oil,
the sizes of connecting sections of charging port of the main unit
and installation tools are changed from those for the conventional
refrigerant.
• Accordingly the exclusive tools are required for the new refrigerant
(R410A).
• For connecting pipes, use new and clean piping designed for
R410A, and please care so that water or dust does not enter.
EN-13EN-14
Page 9
NOTE
01_IM_DHV2305601-00_EN.fm Page 8 Wednesday, November 27, 2019 11:26 AM
Installation Manual
2Accessory Parts
Part nameQ’tyShapeUsage
Owner’s Manual1Hand this directly to the customer.
Installation Manual1Hand this directly to the customer.
CD-ROM
(Owner’s manual,
Installation manual)
F-GAS label1Fill the items on the label after adding refrigerant.
Attached pipe1
• Before installing the unit, check that the unit has the correct model name to prevent the wrong unit from being
installed in the wrong place.
• Before proceeding to braze the refrigerant pipe, be sure to pass nitrogen through the pipe.
• Before installing the indoor units, read the instructions in the installation manual provided with the indoor units.
• Before installing a branch pipe, read the instructions in the installation manual provided with the branch pipe kit.
1-
For other languages that do not appear in this Installation
Manual, Please refer to the enclosed CD-ROM.
Gas pipe connection pipe
Ø19.05 to Ø22.22 (MCY-MHP1006HS8* only)
3Installation of New Refrigerant Air
Conditioner
This air conditioner adopts the new HFC refrigerant (R410A) which does not deplete the ozone layer.
• R410A refrigerant is vulnerable to impurities such as water, oxidizing membranes, or oils because the pressure of
R410A refrigerant is higher than that of the former refrigerant by approximately 1.6 times.
As well as the adoption of the new refrigerant, the refrigerating oil has been also changed. Therefore, pay attention
so that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle of the new refrigerant
air conditioner during installation.
• To prevent mixing of refrigerant or refrigerating oil, the size of the charge port of the main unit or connecting section
of the installation tool differs to that of an air conditioner for the former refrigerant.
Accordingly, exclusive tools are required for the new refrigerant (R410A) as shown below.
• For connecting pipes, use new and clean piping materials so that water or dust does not enter.
Required tools and cautions on handling
It is necessary to prepare the tools and parts for installation as described below. The tools and parts which will be
newly prepared in the following items should be restricted to exclusive use.
Explanation of symbols
: Newly prepared (It is necessary to use it exclusively with R410A, separately from those for R22 or R407C.)
: Former tool is available.
Used toolsUsageProper use of tools / parts
Gauge manifold
Charging hoseExclusive to R410A
Charging cylinderCharging refrigerant
Gas leak detectorChecking gas leakExclusive to R410A
Vacuum pumpVacuum drying
Vacuum pump with counterflow Vacuum dryingR22 (Existing article)
Flare toolFlare processing of pipesUsable by adjusting size
BenderBending processing of pipesR22 (Existing article)
Refrigerant recovery deviceRecovering refrigerantExclusive to R410A
Torque wrenchTightening flare nutExclusive to Ø12.70 mm and Ø15.88 mm
Vacuuming, charging refrigerant
and operation check
Welding of pipesR22 (Existing article)
Exclusive to R410A
Unusable (Use the Refrigerant charging
balance.)
Usable if a counter-flow preventive adapter is
attached
Exclusive to R410A
Enter the refrigerate name for identification
EN
EN-15EN-16
– 8 –
Page 10
WARNING
CAUTION
WARNING
CAUTION
01_IM_DHV2305601-00_EN.fm Page 9 Wednesday, November 27, 2019 11:26 AM
4Installation Conditions
Before installation
Be sure to prepare to the following items before installation.
Airtight test
1 Before starting an airtight test, further tighten the spindle valves on the gas and liquid sides.
2 Pressurize the pipe with nitrogen gas charged from the service port to the design pressure to conduct an
airtight test.
3 After the airtight test is completed, evacuate the nitrogen gas.
Air purge
• To purge air, use a vacuum pump.
• Do not use refrigerant charged in the outdoor unit to purge air. (The air purge refrigerant is not contained in the
outdoor unit.)
Electrical wiring
Be sure to fix the power wires, indoor / outdoor connecting wires and remote controller wires with clamps so that they
do not come into contact with the cabinet, etc.
Earthing
Make sure that proper earthing is provided.
Improper earthing may cause an electric shock. For details on how
to check earthing, contact the dealer who installed the air conditioner
or a professional installation company.
– 9 –
Installation Manual
Installation location
Install the outdoor unit properly in a location that is durable
enough to support the weight of the outdoor unit.
Insufficient durability may cause the outdoor unit to fall, which may
result in injury.
This outdoor unit has a weight of about 147 kg. Pay special attention
when installing the unit onto a wall surface.
Do not install the outdoor unit in a location that is subject to
combustible gas leaks.
Accumulation of combustible gas around the outdoor unit may cause
a fire.
Install the outdoor unit in a location that meets the following conditions after the customer’s consent is
obtained.
• A well-ventilated location free from obstacles near the air intake and air discharge
• A location that is not exposed to rain or direct sunlight
• A location that does not increase the operating noise or vibration of the outdoor unit
• A location that does not produce any drainage problems from discharged water
• Proper earthing can prevent charging of electricity on the outdoor unit surface due to the presence of a high
frequency in the frequency converter (inverter) of the outdoor unit, as well as prevent electric shock. If the outdoor
unit is not properly earthed, you may be exposed to an electric shock.
• Be sure to connect the earth wire (grounding work).
Incomplete earthing can cause an electric shock.
Do not connect earth wires to gas pipes, water pipes, lightning rods or earth wires for telephone wires.
Test run
Turn on the leakage breaker at least 12 hours before starting a test run to protect the compressor.
Incorrect installation work may result in a malfunction or complaints
from customers.
Do not install the outdoor unit in the following locations.
• A location with a saline atmosphere (coastal area) or one that is full of sulfide gas (hot-spring area) (Special
maintenance is required.)
• A location subject to oil, vapor, oily smoke, or corrosive gases
• A location in which organic solvent is used
• Places where iron or other metal dust is present. If iron or other metal dust adheres to or collects on the interior of
the air conditioner, it may spontaneously combust and start a fire.
• A location where high-frequency equipment (including inverter equipment, private power generator, medical
equipment, and communication equipment) is used
(Installation in such a location may cause malfunction of the air conditioner, abnormal control or problems due to
noise from such equipment.)
• A location in which the discharged air of the outdoor unit blows against the window of a neighboring house
• A location where the operating noise of the outdoor unit is transmitted
• When the outdoor unit is installed in an elevated position, be sure to secure its fixing leg.
• A location in which drain water poses any problems.
When collectively draining discharged water completely, use a drain pan.
EN-17EN-18
Page 11
CAUTION
800 mm
Strong wind
Strong wind
<Example>
Snow shield
Snow shield
01_IM_DHV2305601-00_EN.fm Page 10 Wednesday, November 27, 2019 11:26 AM
1. Install the outdoor unit in a location where the discharge air is not
blocked.
2. When an outdoor unit is installed in a location that is always
exposed to strong winds like a coast or on the high stories of a
building, secure normal fan operation by using a duct or wind
shield.
3. When installing the outdoor unit in a location that is constantly
exposed to strong winds such as on the upper stairs or rooftop of
a building, apply the wind-proofing measures referred to in the
following examples.
1) Install the unit so that its discharge port faces the wall of the building.
Keep a distance 800 mm or more between the unit and wall surface.
Installation Manual
4. When installing the unit in an area where snowfalls may be heavy,
take steps to prevent the unit from being adversely affected by the
fallen or accumulated snow.
• Either make the foundation higher or install a stand (which is high enough to ensure that the unit will be above
the fallen or accumulated snow) and place the unit on it.
• Attach a snow shield (locally procured).
EN
2) Consider the wind direction during the operational season of the air conditioner, and install the unit so that the
discharge port is set at a right angle relative to the wind direction.
EN-19EN-20
– 10 –
Page 12
150 or more
150 or more300 or more
200 or more
The height of the
obstacle should be
lower than the height
of the outdoor unit.
150 or
more
200 or more
300 or
more
300 or
more
300 or
more
150 or
more
500 or more
800 or more
1,000 or
more
300 or more 300 or more
1,000 or more
800 or more
150 or more
800 or more
300 or more
150 or
more
1,000
or more
1,000
or more
200 or
more
250 or more
250 or
more
1,000 or
more
300 or
more
1,500 or
more
2,000 or
more
200 or
more
Drain hole
Knockout hole
Back side
Front side (Air discharge side)
01_IM_DHV2305601-00_EN.fm Page 11 Wednesday, November 27, 2019 11:26 AM
Necessary space for installation
(Unit: mm)
Be sure to observe the necessary space for instllation.
Install the outdoor unit in a well-ventilated location.
Failure to do so may cause short circuit (intake of discharge air) or performance deterioration due to locations around
the outdoor unit.
Obstacle at rear side
Upper side is free
1. Single unit installation
2. Obstacles on both right and left sides
3. Serial installation of two or more units
The height of the obstacle should be lower than the
height of the outdoor unit.
Obstacle in front
Above unit is free
1. Single unit installation
2. Serial installation of two or more units
Obstacle also above unit
Obstacles in front and both right and left side
– 11 –
Installation Manual
Obstacles in both front and rear of unit
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit, should be lower than the height of the outdoor unit.
Standard installation
1. Single unit installation
2. Serial installation of two or more units
Serial installation in front and rear
Open above and to the right and left of the unit.
The height of an obstacle in both the front and rear of the
unit should be lower than the height of the outdoor unit.
Standard installation
Installation of outdoor unit
• Before installation, check the strength and horizontalness of the base so that abnormal sounds do not emanate.
• According to the following base diagram, fix the base firmly with the anchor bolts.
(Anchor bolt, nut: M12 x 4 pairs)
164660164
Obstacle also above unit
EN-21EN-22
490
445
Page 13
CAUTION
Fixing leg
CorrectCorrect
Foundation
Absorb vibration with
vibration-proof rubber
pads
Foundation
Bottom plate of
outdoor unit
Support the bottom surface of the
fixing leg that is in contact with and
underneath the bottom plate of the
outdoor unit.
Incorrect
If only the end of the
fixing leg is supported,
it may deform.
Do not support the outdoor
unit only with the fixing leg.
Foundation
20 or less
Tip-over prevention part
Tip-over prevention part
01_IM_DHV2305601-00_EN.fm Page 12 Thursday, December 5, 2019 4:55 PM
Installation Manual
• As shown in the figure below, install vibration-proof rubber pads to directly support the bottom surface of the fixing leg.
* When installing the foundation for an outdoor unit with downward piping, consider the piping work.
Set the out margin of the anchor bolt to 20 mm or less.
• When the unit is to be installed in a location where it is likely to be exposed to strong winds or where the foundation
is unstable, additional measures must be taken to prevent tip-over as shown in the figure below.
For reference
If a heating operation is to be continuously performed for a long time under the condition that the outdoor temperature
is 0 °C or lower, draining defrosted water may be difficult due to the bottom plate freezing, resulting in trouble with the
cabinet or fan.
It is recommended to procure an anti-freeze heater locally in order to safely install the air conditioner.
For details, contact the dealer.
EN
• Carry out the installation work by following the prescribed
procedure to make provision against the shaking of the unit caused
by strong winds, earthquakes, etc.
• Failure to carry out the installation work as prescribed may lead to
the unit tipping over, in turn causing an accident.
EN-23EN-24
– 12 –
Page 14
REQUIREMENT
Side
Bottom
Front
CAUTION
90°
Correct
IncorrectIncorrectIncorrect
ObliquityRoughness
Warp
A
B
01_IM_DHV2305601-00_EN.fm Page 13 Thursday, December 5, 2019 4:55 PM
5Refrigerant Piping
Leading out the pipes
• The indoor/outdoor unit connecting pipes can be connected in any of 3 directions. Use a screwdriver to punch out
the knockout part of the front panel or base. Wear heavy work gloves to protect yourself from injury while doing this
work. After punching out the knockout hole in a manner which ensures that the pipes and wires will not be damaged
in any way, remove the burrs from around the hole.
Follow the instructions in the installation manual provided with the branch pipe kit and the instructions in the
installation manual of the indoor unit to connect the refrigerant pipe between the branch pipe and indoor unit.
– 13 –
Installation Manual
Refrigerant piping connection
TAKE NOTE OF THESE 4 IMPORTANT POINTS BELOW FOR
PIPING WORK
1. Keep dust and moisture away from inside the connecting pipes.
2. Tightly connect the connection between pipes and the unit.
3. Evacuate the air in the connecting pipes using a VACUUM PUMP.
4. Check for gas leaks at connection points.
Pipe connection method
Flaring
1. Cut the pipe with a pipe cutter.
2. Remove the burr inside of the pipe. When removing the burr, be careful so that chips do not fall into the pipe.
3. Remove the flare nuts attached to the outdoor / indoor unit, then insert them into each of the pipes.
4. Flare the pipes. See the following table for the projection margin (A) and flaring size (B).
PipeABFlare Nut
Outside
diameter
mmmmmmmmmmmmN•mkgf•m
6.350.80 to 0.51.0 to 1.59.91714 to 181.4 to 1.8
9.520.80 to 0.51.0 to 1.513.22233 to 423.3 to 4.2
12.700.80 to 0.51.0 to 1.516.62650 to 625.0 to 6.2
15.881.00 to 0.51.0 to 1.519.72968 to 826.8 to 8.2
19.051.20 to 0.51.0 to 1.524.036100 to 12010.0 to 12.0
* In case of flaring for R410A with the conventional flare tool, pull the tool out approx. 0.5 mm more than that for R22
to adjust it to the specified flare size. The copper pipe gauge is useful for adjusting the projection margin size.
Thickness
Rigid
(clutch type)
R410A tool
Imperial
(wing nut type)
R410A tool
Width across
flat
Tighten torque
EN-25EN-26
Page 15
REQUIREMENT
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.03
-0.03
01_IM_DHV2305601-00_EN.fm Page 14 Thursday, December 5, 2019 4:55 PM
• For a brazing work of the refrigerant pipes, be sure to use nitrogen gas in order to prevent oxidation of the inside of
the pipes; otherwise clogging of the refrigerating cycle due to oxidized scale may occur.
• Use clean and new pipes for the refrigerant pipes and perform piping work so that water or dust does not
contaminate the refrigerant.
* Remove all flux after brazing.
• Be sure to use a double spanner to loosen or tighten the flare nut. If a single spanner is used, the required level of
tightening cannot be obtained. Tighten the flare nut with the specified torque.
• Do not apply refrigerant oil to the surface of the flare.
Coupling size of brazed pipe
Connected section
External sizeInternal size
K
ØC
Standard outer dia. of
connected copper
pipe
External sizeInternal size
Standard outer dia.
(Allowable difference)
CFKG
6.356.35 (±0.03)6.45 ()760.06 or less
9.529.52 (±0.03)9.62 ()870.08 or less
12.7012.70 (±0.03)12.81 ()980.10 or less
15.8815.88 (±0.03)16.00 ()980.13 or less
19.0519.05 (±0.03)19.19 ()11100.15 or less
22.2222.22(±0.03)22.36 ()11100.16 or less
G
ØF
Connected section
Min. depth of
insertion
Oval value
Min. thickness of
(Unit: mm)
coupling
0.50
0.60
0.70
0.80
0.80
0.90
Installation Manual
Selection of pipe materials and size
Selection of pipe material
Material: Phosphorus deoxidation seam-less pipe
Capacity code of indoor and outdoor units
• For the indoor unit, the capacity code is decided at each capacity rank.
• The capacity codes of the outdoor units are decided at each capacity rank.
The maximum No. of connectable indoor unit and the total value of capacity codes of the indoor units are also decided.
Minimum wall thickness for R410A application
SoftHalf Hard or HardOD (Inch)OD (mm)Minimum wall thickness (mm)
CorrectCorrect1/4”6.350.80
CorrectCorrect3/8”9.520.80
CorrectCorrect1/2”12.700.80
CorrectCorrect5/8”15.881.00
1
Incorrect *
1
Incorrect *
*1 If the pipe size is Ø19.05, use a suitable material.
Tab le 1
Indoor unit
capacity type
005 type0.61.7018 type2.05.6
007 type0.82.2020 type2.256.3
008 type0.92.5024 type2.57.1
009 type1.02.8027 type3.08.0
010 type1.13.2030 type3.29.0
012 type1.253.6036 type4.011.2
014 type1.54.0048 type5.014.0
015 type1.74.5056 type6.016.0
017 type1.855.0
Tab le 2
Outdoor unit
capacity type
0806 type82 to 126.410.4
1006 type102 to 168.0
Correct3/4”19.051.00
Correct7/8”22.221.00
Capacity code
Equivalent to HP
Capacity codeNo. of
Equivalent to HPMin. (HP)Max. (HP)
Equivalent to
capacity
connectable
indoor units
Indoor unit
capacity type
Equivalent to HP
Total capacity code of connectable indoor units
(When the number of indoor units is 2 to 12)
(When the number of indoor units is 13 to 16)
Capacity code
13.0
11. 0
Equivalent to
capacity
EN
EN-27EN-28
– 14 –
Page 16
Ball valve
Ø19.05 Main pipe
(Locally procured)
Ball valve
Ø19.05 Main pipe
(Locally procured)
Ball valve
Ø
19.05-Ø22.22
socket (Attached)
Ø
22.22 Main pipe
(Locally procured)
Ball valve
Ø
19.05 pipe
(Locally procured)
Ø
22.22 Main pipe
(Locally procured)
Ø
19.05-Ø22.22 socket
(Locally procured)
CAUTION
Wet cloth
Brazing
01_IM_DHV2305601-00_EN.fm Page 15 Wednesday, November 27, 2019 11:26 AM
Pipe connection method of valve at the gas side (Example)
Diameter of pipeFront and right leading outDownward direction leading out
Attach the Ø19.05 pipe to the ball valve by flare
conection.
O.D.
19.05 mm
Attach the Ø19.05 pipe to the ball valve by flare
conection.
– 15 –
Installation Manual
• The brazed part of the pipe connection should be sufficiently away from the ball valve.
• When carrying out brazing nearthe ball valve, wrap the ball valve in a wet cloth to keep it cool and prevent the heat
from the torch from damaging it, and, prepare a shield plate on-site to prevent the soundproofing cloth or other part
from catching fire.
Attach Ø19.05-Ø22.22 socket to the ball valve by
flare conection and braze the locally procured
Ø22.22 main pipe.
Attach Ø19.05 pipe to the ball valve by flare
conection and braze the locally procured Ø19.05Ø22.22 socket and Ø22.22 main pipe.
O.D.
22.22 mm
EN-29EN-30
Page 17
Outdoor unit
Liquid pipe
Gas pipe
Main pipe
L1
1st branching
section
Branching
pipe
Branching
header
Indoor
unit
Indoor
unit
Branching
pipe
Y-shaped
branching joint
Height
difference
between
indoor and
outdoor
units H1
Gas side Liquid side
19.059.52
Conditions for size of main pipe
selection *
Size of main pipe
Height between indoor
and outdoor units
H1(m)
Equivalent length
of main pipe
L1(m)
Gas pipe
Liquid
pipe
30
≧ H1 > 20
40 > L1
19.05
9.52
L1
≧ 4012.70
20
≧ H1 > 10
60 > L19.52
L1
≧ 6012.70
10
≧ H1 > 0No condition9.52
Conditions for size of main pipe
selection *
Size of main pipe
Height between indoor
and outdoor units
H1(m)
Equivalent length
of main pipe
L1(m)
Gas pipe
Liquid
pipe
30
≧ H1 > 20
30 > L1
22.22
9.52
L1
≧ 3012.70
20
≧ H1 > 10
40 > L19.52
L1
≧ 4012.70
10
≧ H1 > 0
50 > L19.52
L1
≧ 5012.70
Total capacity codes of indoor units
at down stream side
Gas pipe Liquid pipe
Equivalent to HP
Equivalent to
capacity
Below 2.4Below 6.612.709.52
2.4 to below 6.46.6 to below 18.015.889.52
6.4 or more18.0 or more22.2212.70
Capacity rankGas pipe Liquid pipe
005 to 012 type 9.526.35
014 to 018 type12.706.35
020 to 056 type15.889.52
Total capacity codes of indoor units at
down stream side
Model name
Equivalent to HP Equivalent to capacity
Y-sharp branch joint
Below 6.4Below 18.0RBM-BY55E
6.4 or more18.0 or moreRBM-BY105E
Model name
Branching header
For 4 branches RBM-HY1043E
For 8 branches RBM-HY1083E
01_IM_DHV2305601-00_EN.fm Page 16 Wednesday, November 27, 2019 11:26 AM
Installation Manual
Selection of refrigerant piping
(1)
(4)
(2)
(2)
No. Piping partsNameSelection of pipe sizeRemarks
Size of valve
-Outdoor unit
Connection
Val ve
0806 type
Outdoor unit
(1)
1st
branching
section
Main pipe
(5)
(3)
(3)
(3)
(4)
(3)
(3)
(3)
-
*The main liquid
pipe size differs
based on outdoor
unit capacity type,
equivalent length of
main pipe, and hight
difference between
outdoor and indoor
units.
(2)
(3)
(4)
(5)
Branching
section
Branching
section
Branching
section
Indoor unit
Branching
section
Branching
section
Branching
pipe
Indoor unit
connecting
pipe
Y-shaped
branching
joint
Branching
header
1006 type
Pipe size between branching sections
* When exceed the main pipe size, use the same size as the main
pipe.
Connecting pipe size of indoor unit
Selection of branching section (Y-shaped branching joint)
Selection of branching section (Branching header)
Pipe size differs
based on the total
capacity code value
of indoor units at the
downstream side. If
the total value
exceeds the
capacity code of the
outdoor unit, apply
the capacity code of
the outdoor unit.
(See Table 1 and 2.)
EN
EN-31EN-32
– 16 –
Page 18
(5)
(2)
(4)
(1)
(3)
(6)
(3)
(3)
(2)
(4)
(3)
(6)
(6)
(6)
(3)
(6)
(3)
(6)
Outdoor unit
Liquid pipe
Gas pipe
Main
pipe
L1
1st branching
section
Branching
pipe
Branching
header
Indoor
unit
Indoor
unit
Branching
pipe
Y-shaped
branching joint
PMV Kit
Height
difference
between
indoor and
outdoor
units H1
Gas side Liquid side
19.059.52
Conditions for size of main pipe
selection *
Size of main pipe
Height between indoor
and outdoor units
H1(m)
Equivalent length
of main pipe
L1(m)
Gas pipe
Liquid
pipe
30
≧ H1 > 20
40 > L1
19.05
9.52
L1
≧ 4012.70
20
≧ H1 > 10
60 > L19.52
L1
≧ 6012.70
10
≧ H1 > 0No condition9.52
Conditions for size of main pipe
selection *
Size of main pipe
Height between indoor
and outdoor units
H1(m)
Equivalent length
of main pipe
L1(m)
Gas pipe
Liquid
pipe
30
≧ H1 > 20
30 > L1
22.22
9.52
L1
≧ 3012.70
20
≧ H1 > 10
40 > L19.52
L1
≧ 4012.70
10
≧ H1 > 0
50 > L19.52
L1
≧ 5012.70
Total capacity codes of indoor units
at down stream side
Gas pipe Liquid pipe
Equivalent to HP
Equivalent to
capacity
Below 2.4Below 6.612.709.52
2.4 to below 6.46.6 to below 18.015.889.52
6.4 or more18.0 or more22.2212.70
Capacity rankGas pipe Liquid pipe
005 to 012 type 9.526.35
014 to 018 type12.706.35
020 to 056 type15.889.52
Total capacity codes of indoor units at
down stream side
Model name
Equivalent to HP Equivalent to capacity
Y-sharp branch joint
Below 6.4Below 18.0RBM-BY55E
6.4 or more18.0 or moreRBM-BY105E
Model name
Branching header
For 4 branches RBM-HY1043E
For 8 branches RBM-HY1083E
Capacity rankModel name
005 to 014 typeRBM-PMV0363E
015 to 027 typeRBM-PMV0903E
01_IM_DHV2305601-00_EN.fm Page 17 Wednesday, November 27, 2019 11:26 AM
Selection of refrigerant piping for quiet place (with PMV Kit)
No. Piping partsNameSelection of pipe sizeRemarks
Size of valve
-Outdoor unit
Connection
Val ve
– 17 –
Installation Manual
1006 type
(2)
Branching
section
Branching
section
Branching
pipe
Pipe size between branching sections
* When exceed the main pipe size, use the same size as the main
pipe.
Pipe size differs
based on the total
capacity code value
of indoor units at the
downstream side. If
the total value
exceeds the
capacity code of the
outdoor unit, apply
the capacity code of
the outdoor unit.
(See Table 1 and 2.)
Connecting pipe size of indoor unit
Branching
section
(3)
Indoor unit
-
Indoor unit
connecting
pipe
Selection of branching section (Y-shaped branching joint
Outdoor unit
1st
(1)
branching
EN-33EN-34
section
Main pipe
0806 type
Y-shaped
branching
joint
Branching
header
Selection of branching section (Branching header)
*The main liquid
pipe size differs
based on outdoor
unit capacity type,
equivalent length of
main pipe, and hight
difference between
outdoor and indoor
units.
(4)
(5)
Branching
section
Branching
section
Selection of PMV Kit
(6) PMV KitPMV Kit
* PMV kit can be connected less than 027 type FCU.
Page 19
f
abcd
A
*1
L3
L1
L2
e
Outdoor unit
Height difference
between indoor and
outdoor units H1
Main
pipe
1st branching
section
Branching pipe
Branching
header
Indoor unit
Y-shaped
branching joint
Branching pipe
Equivalent length corresponded to farthest piping L
Equivalent length corresponded to farthest piping after 1st branching Li
Height
difference
between indoor
units H2
Outdoor unit
Height
difference
between
indoor and
outdoor
units H1
Main
pipe
1st branching
section
Branching pipe
Branching
header
Indoor unit
Y-shaped
branching joint
Branching pipe
Equivalent length corresponded to farthest piping L
Equivalent length corresponded to farthest piping after 1st branching Li
Height difference
between indoor unit
and PMV Kit H2 *
* Between highest
unit and lower
units.
PMV Kit
Example)
01_IM_DHV2305601-00_EN.fm Page 18 Thursday, November 28, 2019 1:21 PM
Installation Manual
Allowable length / height difference of refrigerant piping
Allowable
value
Total extension of pipe (liquid pipe, real length)300 mL1 + L2 + L3 + a + b + c + d + e + f
Real length120 m
Equivalent length150 m
40 mL3 + f
Piping Length
Furthest piping length L
(*1)
Max. equivalent length of main pipe80 m *2L1
Max. real length of furthest piping from 1st
branching Li (*1)
Max. real length of indoor unit connecting pipe15 ma, b, c, d, e, f
Height
Difference
*1 Furthest indoor unit from 1st branch to be named “A”.
*2
The main liquid pipe size varies depending on L1 and H1. See the page of “Selection of refrigerant piping” for details.
Height between indoor
and outdoor units H1
Height between indoor units H215 m
EN-35EN-36
Upper outdoor unit30 m *2
Lower outdoor unit30 m *2
Pipes
L1 + L3 + f
– 18 –
Allowable length / height difference of refrigerant piping for quiet places (with PMV Kit)
L1
L3
Total extension of pipe (Liquid pipe, real length)250 m
Furthest piping length L
(*1)
Piping Length
Max. equivalent length of main pipe70 m *2L1
Max. real length of furthest piping from 1st
branching Li (*1)
Max. real length of indoor unit connecting pipe15 ma + g, b + h, c + i, d + j, e + k, f + l
Real length between PMV Kit and indoor unit
Height
Difference
Height between indoor
and outdoor units H1
Height between indoor units (PMV Kit) H215 m
*1 Furthest indoor unit from 1st branch to be named “A”.
*2
The main liquid pipe size varies depending on L1 and H1. See the page of “Selection of refrigerant piping” for details.
L2
ab
cd
ghi j
e
k
Allowable
value
f
l
L1 + L2 + L3 + a + b + c + d + e + f + g + h
Real length100 m
Equivalent length130 m
30 mL3 + f + l
2 m or more
Below 10 m
Upper outdoor unit30 m *2
Lower outdoor unit30 m *2
*1
A
Pipes
+ i + j + k + l
L1 + L3 + f + l
g, h, i, j, k, l
H2
H2
H2
EN
Page 20
NOTE
IncorrectCorrect
PMV Kit
PMV Kit
Indoor unitIndoor unit
REQUIREMENT
Main pipe
Connected to indoor unit
Low pressure
guage
High pressure
guage
Ball valve fully closed
(Gas side)
Flare connection
Flare connection
Packed valve fully closed
(Liquid side)
Service port
Ø6.4 Copper pipe
Ø6.4 Copper pipe
Nitrogen gas
Reducing
valve
Gauge
manifold
Outdoor unit
Service
port
01_IM_DHV2305601-00_EN.fm Page 19 Thursday, December 5, 2019 4:54 PM
Do not connect two or more indoor units to one PMV Kit. Arrange one indoor unit and one PMV Kit set to 1 by 1.
– 19 –
Installation Manual
Airtight test
Before starting an airtight test, further tighten the spindle valves on the gas side and liquid side.
Pressurize the pipe with nitrogen gas charged from the service port to the design pressure to conduct the airtight test.
After the airtight test is completed, evacuate the nitrogen gas.
• Apply pressure from the service ports of the packed valves (or ball valves) at liquid side and gas side.
• An air tight test can be only performed to the service ports at liquid side and gas side of the outdoor unit.
• Close fully valves at liquid side and gas side. As there is possibility that nitrogen gas enters in the refrigerant cycle,
re-tighten the valve rods before applying pressure.
(Re-tightening of the valve rods are unnecessary for valves at gas side because they are ball valves.)
• For each refrigerant line, apply pressure gradually with steps at liquid side and gas side.
Apply pressure to gas side and liquid side.
Do not use “Oxygen”, “Flammable gas” and “Noxious gas” in an airtight test.
To detect a gross leakage
1. Apply pressure 0.3 MPa (3.0 kg / cm
2. Apply pressure 1.5 MPa (15 kg / cm
To detect a slow leakage
EN-37EN-38
3. Apply pressure 4.15 MPa (42.3kg / cm
• Check pressure down.
No pressure down: Accepted
Pressure down: Check the leaked position.
2
G) for 3 minutes or more.
2
G) for 3 minutes or more.
2
G) for approx. 24 hours.
Page 21
NOTE
REQUIREMENT
NOTE
Main pipe
Connected to indoor unit
Low pressure
guage
High pressure
guage
Ball valve fully closed
(Gas side)
Flare connection
Flare connection
Packed valve fully closed
(Liquid side)
Service port
Vac uu m pu mp
Gauge
manifold
Outdoor unit
Service port
01_IM_DHV2305601-00_EN.fm Page 20 Wednesday, November 27, 2019 11:26 AM
Installation Manual
Air purge
However, if the environmental temperature changes from the moment of applying pressure to 24 hours after that, the
pressure will change by about 0.01 MPa (0.1 kg / cm
2
G) per 1 °C. Consider the pressure change when checking the
test result.
When pressure decrease is detected in steps 1-3, check the leakage at the connecting points.
Check the leakage using a foaming agent or other measures and seal the leak with re-brazing, flare retightening or
other methods. After sealing, execute an airtight test again.
For the air purge at installation time (Discharge of air in connecting pipes), use “Vacuum pump method” from
EN
viewpoint of the protection of the earths environment.
• For protection of the earths environment, do not discharge the refrigerant gas in the air.
• Eliminate the remaining air (nitrogen gas, etc.) in the unit by using a vacuum pump.
If gas remains, performance and reliability of the unit may be reduced.
After the airtight test, discharge nitrogen gas. Then connect the gauge manifold to the service ports at gas side and
liquid side, and connect the vacuum pump as shown in the following figure.
Perform vacuuming for gas side and liquid side.
• Perform vacuuming from both liquid and gas sides.
• Use a vacuum pump with counter-flow preventive function so that oil in the pump does not back up in the pipe of the
air conditioner when the pump has been stopped. (If oil in the vacuum pump enters in to the air conditioner with
R410A refrigerant, an error may occur in the refrigeration cycle.)
• Use a vacuum pump that has a high vacuum (below -755 mmHg) and a large exhaust gas amount (over 40 L /
minute).
• Perform vacuuming for 2 or 3 hours though time differs due to pipe length.
In this time, check all valves at liquid and gas sides are fully closed.
• If vacuuming valve amount is not decreased to below -755 mmHg even after vacuuming for 2 hours or more,
continue vacuuming for 1 hour or more.
EN-39EN-40
– 20 –
If -755 mmHg or less cannot be obtained by 3 hours or more vacuuming, detect and repair the leak.
• When the vacuuming valve has reached -755 mmHg or less after vacuuming for 2 hours or more, close valves VL
and VH on the gauge manifold fully. Stop the vacuum pump, leave it as it is for 1 hour and then check the vacuum
does not change. If it does change then there may be a leak within the system.
• After the above procedure for vacuuming has finished, exchange the vacuum pump with a refrigerant cylinder and
advance to the additional charging of refrigerant.
Page 22
NOTE
L1
L2
L3
L4
L5
L6
L7
DCBA
01_IM_DHV2305601-00_EN.fm Page 21 Monday, December 2, 2019 5:02 PM
Adding refrigerant
After finishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging of refrigerant.
Calculation of additional refrigerant charge amount
Default refrigerant amount does not include the refrigerant for pipes at the local site.
For refrigerant to be charged in pipes at the local site, calculate the amount and charge it additionally.
Do not degas the refrigerant from the air conditioner when the result of additional refrigerant charge amount
calculation is negative value.
Outdoor unit type0806HS81006HS8
Charging amount (kg)4.44.4
Additional
refrigerant charge
amount at local site
Real length of liquid
=
pipe
Additional refrigerant
charge amount per
×
1 m liquid pipe
(Table 1)
Tab l e 1
Liquid pipe dia. (mm)6.359.5212.70
Additional refrigerant amount /
1 m liquid pipe (kg / m)
0.0250.0550.105
Tab l e 2
Capacity rank
Capacity code
(Equivalent to HP)
4-way cassette
2-way cassette MMU-AP****WH*-
1-way cassette MMU-AP****YH / SH*-
Duct
Indoor
unit
model
Under-ceilingMMC-AP****HP*----
name
High wall
Floor standing
MMU-AP****HP*--
MMU-AP****MH*0.3
MMD-AP****BHP*-
MMD-AP****SPH*0.3
MMD-AP****HP*-----
MMK-AP****H*-
MMK-AP****HP*0.3
MMF-AP****H*----
MML-AP****H*-
MML-AP****BH*-
MML-AP****NH*-
005007009012015018024027030036048056
0.60.81.0
0.40.40.40.60.6
0.40.40.40.50.70.70.70.71.11.11.1
0.40.40.40.50.50.6
0.50.50.50.50.50.70.70.71.11.11.1
0.30.30.30.50.50.80.8
0.50.50.50.70.70.7
0.30.30.30.70.70.7-----
0.50.50.50.50.80.8
0.30.30.30.50.50.7
0.50.50.50.50.5
1.25
0.40.40.80.80.80.80.81.21.21.2
Corrective amount of
refrigerant depending
+
on the indoor units
(Table 2)
1.72.02.53.03.24.05.06.0
------
-----
0.70.70.7
0.60.60.80.8-1.21.21.2
-----
0.70.71.01.0-1.31.31.3
-----
-----
------
Compensation by
+
----
-
1.11.11.1
outdoor HP
(Table 3)
(Unit: kg)
– 21 –
Installation Manual
Mid temperature Hot water module
Capacity rank027056
Capacity code
MMW-AP****LQ*0.20.4
Tab le 3
Outdoor unit type0806HS81006HS8
Compensation by outdoor HP (kg)–1.0–1.0
Example: (1006 type)
L1Ø9.52: 10 mL2Ø9.52: 10 mL3Ø9.52: 5 mL4Ø9.52: 3 m
= ( Lx × 0.025 kg/m) + ( Ly × 0.055 kg/m) + ( a + b + c + d ) + ( –1.0 kg )
= ( 12 × 0.025 kg) + ( 28 × 0.055 kg) + ( 2.7 kg ) + ( –1.0 kg )
= 3.54 kg
Lx: Real total length of liquid pipe diameter 6.35 mm (m)
Ly: Real total length of liquid pipe diameter 9.52 mm (m)
a: Corrective amount of refrigerant depending on the unit A [kg]
b: Corrective amount of refrigerant depending on the unit B [kg]
c: Corrective amount of refrigerant depending on the unit C [kg]
d: Corrective amount of refrigerant depending on the unit D [kg]
Charging of refrigerant
• Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the
liquid side.
• If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and gas
sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas side. In
this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
• The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
Equivalent to Capcity7.114.0
Equivalent to HP2.55.0
EN-41EN-42
Page 23
CAUTION
Charge port
Body cap
Closed
completely
Opened
fully
Using a minus
screwdriver, turn it
counterclockwise
by 90° until it hits
the stopper. (Full
open)
Body cap
Flare nut
Charge
port
Grooves
for
driver
When using the piping cover
Drawing-out
sideward
Close the opening
with the pipe cover.
Drawing-out downward
Drawing-out
frontward
Drawing-out sideward
Fill silicon or putty into the
periphery of the pipes.
Drawing-out downward
Drawing-out
frontward
When not using the piping cover
2FAN_IM_DHV2305601-00_EN.book Page 22 Monday, October 28, 2019 3:25 PM
Installation Manual
EN-43EN-44
Full opening of the valve
Open the valves of the outdoor unit fully.
Liquid sideGas side
Packed valve
Using a 4 mm-hexagonal wrench, fully open the
valve rods.
Refer to the table below when you tight the valve cap
Val ve
Liquid side14 ~ 1814 ~ 18
Gas side20 ~ 2514 ~ 18
Body capCharge port
Ball valve
Using a minus screwdriver, turn it counterclockwise by 90° until it hits the stopper.
(Full open)
Tightening force[N•m]
F-GAS label
Contains fluorinated greenhouse gases
• Chemical Name of GasR410A
• Global Warming Potential (GWP) of Gas2088 (ex.R410A ref.AR4)
(1) Stick the enclosed refrigerant label adjacent to the service ports
for charging or recovering location and where possible adjacent
to existing nameplates or product information label.
(2) Clearly write the charged refrigerant quantity on the refrigerant label
using indelible ink. Then, place the included transparent protective
sheet over the label to prevent the writing from rubbing off.
(3) Prevent emission of the contained fluorinated greenhouse gas.
Ensure that the fluorinated greenhouse gas is never vented to the
atmosphere during installation, service or disposal. When any
leakage of the contained fluorinated greenhouse gas is detected,
the leak shall be stopped and repaired as soon as possible.
(4) Only qualified service personnel are allowed to access and
service this product.
– 22 –
(5) Any handling of the fluorinated greenhouse gas in this product,
such as when moving the product or recharging the gas, shall
comply under (EU) Regulation No.517/2014 on certain
fluorinated greenhouse gases and any relevant local legislation.
(6) Periodical inspections for refrigerant leaks may be required
depending on European or local legislation.
(7) Contact dealers, installers, etc., for any questions.
Heat insulation for pipe
• Apply heat insulation of pipe separately at the liquid, gas, and balance sides.
• Be sure to use thermal insulator resistant up to 120 °C or higher for pipes at the gas side.
Finishing after connecting pipes
• After piping connection work has been finished, cover the opening of the piping / wiring panel with the piping cover,
or fill silicon or putty into the space between the pipes.
• In case of drawing-out the pipes downward or sideward, also close the openings of the base plate and the side
plate.
• Under the opened condition, a problem may be caused due to the entering of water or dust.
Pipe holding bracket
Attach pipe holding brackets following the table below.
Diameter of pipe (mm)Interval
Ø19.05 or less2 m
Ø22.22 or more3 m
EN
Page 24
WARNING
CAUTION
Circuit breaker
(Earth leakage breaker)
Main switch
(Fuse)
01_IM_DHV2305601-00_EN.fm Page 23 Thursday, December 5, 2019 4:53 PM
6Electric Wiring
The appliance shall be installed in accordance with national
wiring regulations.
Capacity shortages of the power circuit or an incomplete installation
may cause an electric shock or fire.
• Perform wiring of power supply complying with the rules and
regulations of the local electric company.
• Do not connect 380-415 V power to the terminal blocks for control
cables (U1, U2, U3, U4); otherwise, the unit may break down.
• Be sure that electric wiring does not come into contact with hightemperature parts of piping; otherwise, the coating of cables may
melt and cause an accident.
• After connecting wires to the terminal block, take off the traps and
fix the wires with cord clamps.
• Do not conduct power to indoor units until vacuuming of the
refrigerant pipes has finished.
• For the wiring of power to indoor units and that between indoor and
outdoor units, follow the instructions in the installation manual of
each indoor unit.
– 23 –
Power wiring selection
Standard model
MOCP: Maximum Overcurrent Protection (Amps)
Model
MCY-MHP0806HS8-E
MCY-MHP1006HS8-E20.0
Nominal Voltage, Phase and frequency
Power Supply
380-415V 3N~, 50Hz
MCA: Maximum Circuit Amps
Installation Manual
MCA
(A)
17.0
MOCP
(A)
20.0
25.0
EN-45EN-46
Page 25
U1 U2 U3 U4
U1 U2
U3 U4
U1 U2 A
B2UB
AU1
U2U1
A
2
UBU1A B
BABABA
Outdoor unit
Central controller
Communication wiring between indoor and outdoor units
(Shield wire)
Communication wiring between indoor units (Shield wire)
2FAN_IM_DHV2305601-00_EN.book Page 24 Monday, October 28, 2019 3:25 PM
Installation Manual
Specifications for communication wiring
Design of communication wiring
Summary of communication wiring
Communication wiring and central control wiring use 2-core non-polarity wires.
Use 2-core shield wires to prevent noise trouble.
In this case, for the system grounding, close (connect) the end of shield wires, and isolate the end of terminal.
Use 2-core non-polarity wire for remote controller. (A, B terminals)
Use 2-core non-polarity wire for wiring of group control. (A, B terminals)
Keep the rule of below tables about size and length of communication wiring.
U1U3U2
U4
L4
U3 U4
U1 U2
L1
U1 U2
A B
U1 U2
U1 U2
U3 U4
A B
U1 U2
A B
U3 U4
U1 U2U5U6
U2
U1
L7
U1 U2
B
A
A
U2
U1
B
A
L6
U1 U2
B
A B
L7
U3 U4
U5
U1 U2
L5
3L2L
U2
U1
A B
L6
Table-1Control wiring between indoor and outdoor units (L1, L2, L3), Central control wiring (L4)
Wiring2-core, non-polarity
TypeShield wire
Size / Length *1
1.25 mm
2.0 mm
2
: Up to 1000 m
2
: Up to 2000 m
*1 Total of control wiring length for all refrigerant circuits ( L1 + L2 + L3 + L4 )
Table-2Control wiring between outdoor units (L5) (Other system)
Wiring2-core, non-polarity
TypeShield wire
Size / Length
2
to 2.0 mm
1.25 mm
Up to 100 m (L5)
2
Table-3Remote controller wiring (L6, L7)
Wiring2-core
Size0.5 mm
Length
2
to 2.0 mm
• Up to 500 m (L6 + L7)
• Up to 400 m with of wireless remote controller in group control.
• Up to 200 m total length of control wiring between indoor units ( L6 )
2
EN
U6
U2
U1
A B
EN-47EN-48
– 24 –
Page 26
NOTE
Indoor unit No.1No.2No.3No.4No.7No.8
Remote controller
Knockout for the communication wires
and refrigerant piping
Jugged bushings
(locally purchased)
The cover of the electrical control box
Terminal block
(Power supply)
Earth screw
(Power supply)
Cord clamp
(Power supply)
Power supply wires
Communication wires
Terminal block
(Communication)
Earth screw
(Communication)
Cord clamp
(Communication)
01_IM_DHV2305601-00_EN.fm Page 25 Thursday, December 5, 2019 4:50 PM
Group control through a remote controller
Group control of multiple indoor units (8 units) through a single remote controller
BABABABABABA
(A.B)
Connection of power wires and communication wires
Remove knockouts on the piping / wiring panel on the front of the unit or the panel on the bottom to get the power and
communication wires through the holes.
Use protective parts (such as jugged bushings) to prevent the power wires and communication wires from directly
touching the edge of the sheet metal.
The local installer must purchase the non-removable jugged bushings to wrap around the hole, and use insulated
bushings (locally purchased) to protect the wires from directly touching the sheet metal.
– 25 –
Installation Manual
Remove the front panel and then remove the cover of the electrical control box.
Separate the power wire and communication wires.
EN-49EN-50
Page 27
L1 L2 L3 N
L
1L2L3
N
10 mm or more
Earth line
Power supply wire
60 mm or less
U1 U2 U3 U4
U1 U2 U3 U4
CN02
CN10
[U1, U2] and [U3, U4] not connected
Communication
terminal board
TO INDOOR
UNIT
TO CENTRAL
CONTROLLER
Communication
terminal board
TO INDOOR
UNIT
TO CENTR AL
CONTROLLER
[U1, U2] and [U3, U4] connected
U3, U4: Central control device
U1, U2: Communication wiring between Indoor / Outdoor unit
2FAN_IM_DHV2305601-00_EN.book Page 26 Monday, October 28, 2019 3:25 PM
Installation Manual
Power supply wire connection
1. Insert the power supply wire through the cutout on the side of the electrical control box and connect the power
supply wire to the power supply terminal block and the earth line to the earth screw. After that, fix the power supply
wire with the cord clamp.
2. Use round-type crimping terminals for power connection.
Also, apply insulating sleeves to the crimping parts. Use a driver of appropriate size to fix the terminal screws.
Wire size*
2
2.5 mm
* Design 60245 IEC66
Screw size and tightening torque
Power supply terminalM62.5 to 3.0
Earth screwM85.5 to 6.6
Screw size
Tightening torque
(N•m)
Communication wire connection
Connect the communication wires to the communication wire terminals from under the electrical control box, and fix
them with the communication cable clamps.
CN02
CN10
U1 U2 U3 U4
U1 U2 U3 U4
Screw size and tightening torque
Screw size
Communication wire terminalM41.2 to 1.4
Tightening torque
(N•m)
EN
EN-51EN-52
– 26 –
Page 28
ModelSsc(kVA)
MCY-MHP0806HS8-E
MCY-MHP1006HS8-E
1596
CAUTION
REQUIREMENT
2FAN_IM_DHV2305601-00_EN.book Page 27 Monday, October 28, 2019 3:25 PM
Regulation of harmonic currents
This equipment complies with IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equal
to Ssc (*1) at the interface point between the user’s supply and the public system. It is the responsibility of the
installer or user of the equipment to ensure, by consultation with the distribution network operator if necessary,
that the equipment is connected only to a supply with a short-circuit power Ssc greater than or equal to Ssc
(*1).
Furthermore, when similar equipment or other equipment which may cause harmonic current emissions are to
be connected to the same interface point with this equipment, to reduce the risk of possible problems which
may be caused from addition of those harmonic current emissions, it is recommended to make sure that the
short-circuit power Ssc at the interface point is greater than the sum of the minimum Ssc required by all the
equipment which will be connected to the interface point.
Ssc (*1)
This unit complies with EN 61000-3-11.
However, the impedance of the power supply system to be connected to the unit at the incoming power point
must be less than the Zmax given below.
In order to meet this condition, consult with the supply authority as required.
Zmax = 0.39 (Ω)
In addition, it is recommended that voltage drops occurring during the unit’s operation in the area at the power
input shall be around 3.3% of the nominal power-supply voltage or less.
– 27 –
7Address Setting
On this unit, it is required to set the addresses of the indoor units before starting air conditioning.
Set the addresses following the steps below.
• Be sure to complete the electric wiring before setting the
addresses.
• If you turn on the outdoor unit before turning on the indoor units,
the CODE No. [E19] is indicated on the 7-segment display on the
interface P.C. board of the outdoor unit until the indoor units are
turned on. This is not a malfunction.
• It may take up to ten minutes (normally about five minutes) to
address one refrigerant line automatically.
• Settings on the outdoor unit are required for automatic addressing.
(Address setting is not started simply by turning on the power.)
• Running the unit is not required for address setting.
• The addresses can be set manually.
Automatic addressing: setting addresses using SW15 on the
Manual addressing:setting addresses on the wired remote
* When setting an address manually, the wired remote controller
must temporarily be paired with an indoor unit one-to-one. (when
the system is organized for group operation and no Remote
controller)
Installation Manual
interface P.C. board on the outdoor unit
controller.
High voltage parts exist in the electrical control box.
If you set addresses on an outdoor unit, operate the unit through the cover of electrical control box, to avoid electric
shock.
Do not remove the cover of electrical control box.
EN-53EN-54
Page 29
OutdoorOutdoor
Central
controller
Central
controller
IndoorIndoorIndoor Indoor
Remote
controller
Remote
controller
Remote
controller
Outdoor
Indoor
Remote
controller
Outdoor
Central
controller
IndoorIndoor Indoor
Remote
controller
Remote
controller
U. 1. L08 (U. 1. flash)
Auto 1 Auto 2 Auto 3
U. 1. - - - (U. 1. flash)
U. 1. - - - (U. 1. light)
3
2, 4
D600 D601 D602 D603 D604
SW04SW05SW15
SW01SW02SW03
REQUIREMENT
NOTE
Outdoor
Indoor
Remote
controller
IndoorIndoor Indoor
Outdoor
(Group control)
SW06SW07SW09SW10
SW11SW12SW13SW14
12341234 1234 1234
12341234 1234 1234
2FAN_IM_DHV2305601-00_EN.book Page 28 Monday, October 28, 2019 3:25 PM
Automatic address setting
No central control (single refrigerant line):go to Address setting procedure 1
Central control of 2 or more refrigerant lines:go to Address setting procedure 2
1 Turn on indoor units first, and then turn on outdoor units.
2 About one minute after turning the power on, confirm that the 7-segment display on the interface P.C.
board of the outdoor unit indicates .
3 Press SW 15 to start the automatic address setting.
(It may take up to 10 minutes (normally about 5 minutes) to complete one line’s setting.)
4 The 7-segment display indicates .
After the indication, starts flashing on the display.
When the flashing stops and remains lit on the display, the setting is complete.
Interface P.C. board on the outdoor unit
Installation Manual
• When 2 or more refrigerant lines are controlled as a group, be sure to turn on all the indoor units in the group before
setting addresses.
• If you set the unit addresses of each line separately, each line’s header indoor unit is set separately. In that case,
the CODE No. “L03” (Indoor header unit overlap) is indicated as running starts. Change the group address to make
one unit the header unit using wired remote controller.
(Example)Controlling 2 or more refrigerant lines as a group
System wiring diagram
Address setting procedure 2
1 Set a system address for each system using SW 13 and 14 on the interface P.C. board on the outdoor unit
of each system.
(Factory default: Address 1)
Be sure to set a unique address on each system. Do not use a same address as another system (refrigerant line) or a
custom side.
EN
EN-55EN-56
Interface P.C. board on the outdoor unit
– 28 –
Page 30
NOTE
U1 U2 U3 U4
CN02
CN10
U1 U2 U3 U4
TO INDOOR
UNIT
TO CENTRAL
CONTROLLER
[U1, U2] and [U3, U4] not connected
Communication
terminal board
U. 1. L08 (U. 1. flash)
Auto 1 Auto 2 Auto 3
U. 1. - - - (U. 1. flash)
U. 1. - - - (U. 1. light)
2FAN_IM_DHV2305601-00_EN.book Page 29 Monday, October 28, 2019 3:25 PM
Switch settings for a line (system) address on the interface P.C. board on the outdoor unit
( : switch ON, : switch OFF)
Line (system) address
1–––
2–––
3–––
4–––
5–––
6–––
7–––
8–––
9–––
10–––
11–––
12–––
13–––
14–––
15–––
16–––
17–––
18–––
19–––
20–––
21–––
22–––
23–––
24–––
25–––
26–––
27–––
28–––
“–”: not used for system address setting (Do not change their positions.)
12341234
SW13SW14
– 29 –
Installation Manual
2 In all the outdoor units connected to the central control, please make sure that the relay connector of the
interface P.C. board “CN10” has not been connected to the “CN02”.
If you connect a relay connector “CN10” to “CN02”, the communication line [U1, U2] will be connected to [U3, U4].
If [U1, U2] is connected to the [U3, U4], refrigerant line address cannot be set correctly.
)
3 Turn on indoor units first, and then turn on outdoor units.
4 About 1 minute after turning the power on, confirm that the 7-segment display on the interface P.C. board
of the outdoor unit indicates .
5 Press SW 15 to start the automatic address setting.
(It may take up to 10 minutes (normally about 5 minutes) to complete one line’s setting.)
6 The 7-segment display indicates .
After the indication, starts flashing on the display.
When the flashing stops and remains lit on the display, the setting is
complete.
7 Repeat steps 4 to 6 for other refrigerant lines.
8
After completing address setting of all systems, turn off dip switch 2 of SW30 on the interface P.C. boards of
all the outdoor units connected to the same central control, except the unit that has the lowest address.
(For unifying the termination of the wiring for the central control of indoor and outdoor units)
EN-57EN-58
Page 31
NOTE
Header unit inter face P.C. board
U1 U2 U3 U4
CN02
CN10
U1 U2 U3 U4
TO INDOOR
UNIT
TO CENTRAL
CONTROLLER
[U1, U2] and [U3, U4] connected
Communication
terminal board
CAUTION
2U1U
B
A
2U1U2U1U
B
A
BA
A
2U1U
2U1U
B
AB
U4
U3
U2
U1
CN02
CN10
U4
U3
U2
U1
CN02
CN10
U4
U3
U2
U1
CN02
CN10
Central
controller
Remote
controller
Remote
controller
Remote
controller
Remote
controller
GroupIndividual
Indoor units
(automatic setting)
Outdoor unit
[U1, U2] and
[U3, U4] connected
Outdoor unit
[U1, U2] and
[U3, U4] connected
Outdoor unit
[U1, U2] and
[U3, U4] connected
2FAN_IM_DHV2305601-00_EN.book Page 30 Monday, October 28, 2019 3:25 PM
SW04 SW05 SW15
D600 D601 D602 D603 D604
SW01 SW02 SW03
SW30
SW06SW10
SW11
SW12 SW13
SW16
SW17
SW30
SW09SW07
SW14
9 Connect the relay connectors “CN10” to “CN02”, which are mounted on the interface P.C. boards of all
the outdoor units connected to the central control.
Installation Manual
Switch setting (setting example when controlling 2 or more refrigerant lines centrally)
Outdoor units (setting manually)
Outdoor unit’s
interface P.C. board
SW13, 14
(Line (system) address)
Dip switch 2 of SW30
(Terminator of indoor /
outdoor communication
line and central control
line)
Please make sure that before you perform this task, address setting of the refrigerant line all have been completed.
Line (system) address11223
Indoor unit address12121
Group address00120
Relay connector connection
Never connect relay connectors between the [U1, U2] and [U3, U4]
terminals before completing address setting of all the refrigerant
lines. Otherwise, the addresses cannot be set correctly.
10
Set the central control address.
(For the setting of the central control address, refer to the installation manuals of the central control devices.)
EN-59EN-60
– 30 –
Page 32
Refrigerant line 1Refrigerant line 2
Outdoor
unit
Outdoor
unit
Indoor unit 1 Indoor unit 2 Indoor unit 3Indoor unit 1 Indoor unit 2
Remote
controller
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
11
4, 7, 10
2, 5, 8
3, 6, 9
1
CODE No.
SET DATA
NOTE
2FAN_IM_DHV2305601-00_EN.book Page 31 Monday, October 28, 2019 3:25 PM
Manual address setting with the remote controller
Procedure when setting indoor units’ addresses first under the condition that indoor wiring has been completed and
outdoor wiring has not been started (manual setting using the remote controller)
Wiring example of 2 refrigerant lines
Line (system) address11122
Indoor unit address12312
Group address
In the example above, disconnect the remote controller connections between the indoor units and connect a
wired remote controller to the target unit directly before address setting.
1
Header unit2Follower unit2Follower unit2Follower unit2Follower unit
– 31 –
Installation Manual
<Line (system) address>
2 Push the TEMP. / buttons repeatedly to set the CODE No. to .
3 Push the TIME / buttons repeatedly to set a system address.
(Match the address with the address on the interface P.C. board of the outdoor unit in the same refrigerant line.)
4 Push the button.
(It is OK if the display turns on.)
<Indoor unit address>
5 Push the TEMP. / buttons repeatedly to set the CODE No. to .
6 Push the TIME / buttons repeatedly to set an indoor unit address.
7 Push the button.
(It is OK if the display turns on.)
<Group address>
8 Push the TEMP. / buttons repeatedly to set the CODE No. to .
9 Push the TIME / buttons repeatedly to set a group address. If the indoor unit is individual, set the
address to ; header unit, ; follower unit, .
Individual: 0000
Header unit: 0001
Follower unit: 0002
10
Push the button.
(It is OK if the display turns on.)
11
Push the button.
The address setting is complete.
( flashes. You can control the unit after has disappeared.)
In case of group
control
1. Do not use address numbers 29 or 30 when setting system addresses using the remote controller.
These 2 address numbers cannot be used on outdoor units and the CODE No. [E04] (Indoor / outdoor
communication error) will appear if they are mistakenly used.
Pair the indoor unit to set and the remote controller one-to-one.
Turn on the power.
1 Push and hold the , , and buttons at the same time for more than 4 seconds.
LCD starts flashing.
EN-61EN-62
2. If you set addresses to indoor units in 2 or more refrigerate lines manually using the remote controller and will
control them centrally, set the outdoor unit of each line as below.
• Set a system address for the outdoor unit of each line with SW13 and 14 of their interface P.C. boards.
• Turn off dip switch 2 of SW30 on the interface P.C. boards of all the outdoor units connected to the same central
control, except the unit that has the lowest address. (For unifying the termination of the wiring for the central
control of indoor and outdoor units)
• Connect the relay connectors (CN10) between the [U1, U2] and [U3, U4] terminals on the interface P.C. board to
CN02 in all the outdoor units to which the central control is connected.
• After finishing all the settings above, set the address of the central control devices. (For the setting of the central
control address, refer to the installation manuals of the central control devices.)
Page 33
Star ts
running
UNIT LOUVER
UNIT LOUVER
3
1
2
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Stop
5
6
1
3
4
2
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
SWING/FIX
2FAN_IM_DHV2305601-00_EN.book Page 32 Monday, October 28, 2019 3:25 PM
Installation Manual
Confirming the indoor unit addresses and the position of an indoor unit
using the remote controller
Confirming the numbers and positions of indoor units
To see the indoor unit address of an indoor unit which you know the position of
When the unit is individual (the indoor unit is paired with a wired remote controller one-to-one), or it is a
group-controlled one.
CODE No.
UNIT No.
FILTER
RESET
TEMP.
TEST
TIMER SET
TIME
SET CL
ON / OFF
1
2
(Execute it while the units are running.)
1 Push the button if the units stop.
2 Push the button (left side of the button).
A unit numbers is indicated on the LCD (it will disappear after a few seconds). The indicated number shows
the system address and indoor unit address of the unit.
When 2 or more indoor units are connected to the remote controller (group-controlled units), a number of other
connected units appears each time you push the button (left side of the button).
To find an indoor unit’s position from its address
When checking unit numbers controlled as a group
(Execute it while the units are stopped.)
The indoor unit numbers in a group are indicated one after another. The fan and louvers of the indicated units are
activated.
1 Push and hold the and buttons at the same time for more than 4 seconds.
• appears on UNIT No. on the LCD display.
• The fans and louvers of all the indoor units in the group are activated.
2 Push the button (left side of the button). Each time you push the button, the indoor unit numbers
are indicated one after another.
• The first-indicated unit number is the address of the header unit.
• Only the fan and louvers of the indicated indoor unit are activated.
UNIT LOUVER
3 Push the button to finish the procedure.
All the indoor units in the group stop.
To check all the indoor unit addresses using an arbitrary wired remote controller.
(When communication wirings of 2 or more refrigerant lines are interconnected for central control)
(Execute it while the units are stopped.)
You can check indoor unit addresses and positions of the indoor units in a single refrigerant line.
When an outdoor unit is selected, the indoor unit numbers of the refrigerant line of the selected unit are indicated one
after another and the fan and louvers of the indicated indoor units are activated.
EN
1 Push and hold the TIME and buttons at the same time for more than 4 seconds.
At first, the line 1 and CODE No. (Address Change) are indicated on the LCD display. (Select an
outdoor unit.)
2 Push the (left side of the button) and buttons repeatedly to select a system address.
UNIT LOUVER
3 Push the button to confirm the system address selection.
• The address of an indoor unit connected to the selected refrigerant line is indicated on the LCD display and its
fan and louvers are activated.
4 Push the button (left side of the button). Each time you push the button, the indoor unit numbers
EN-63EN-64
– 32 –
of the selected refrigerant line are indicated one after another.
• Only the fan and louvers of the indicated indoor unit are activated.
UNIT LOUVER
Page 34
3
5
8
1
4
2, 6, 7
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Finish
UNIT LOUVER
NOTE
Cancels the line selection
SWING/FIX
4
8
5, 7
6
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Finish
Press to finish
setting.
2FAN_IM_DHV2305601-00_EN.book Page 33 Monday, October 28, 2019 3:25 PM
To select another system address
5 Push the button to return to step 2.
• After returning to step 2, select another system address and check the indoor unit addresses of the line.
6 Push the button to finish the procedure.
Changing the indoor unit address using a remote controller
To change an indoor unit address using a wired remote controller.
The method to change the address of an individual indoor unit (the indoor unit is paired with a wired remote
controller one-to-one), or an indoor unit in a group.
(The method is available when the addresses have already been set automatically.)
(Execute it while the units are stopped.)
1 Push and hold the , , and buttons at the same time for more than 4 seconds.
(If 2 or more indoor units are controlled in a group, the first indicated UNIT No. is that of the head unit.)
2 Push the button (left side of the button) repeatedly to select an indoor unit number to change if 2
or more units are controlled in a group. (The fan and louvers of the selected indoor unit are activated.)
(The fan of the selected indoor unit is turned on.)
UNIT LOUVER
3 Push the TEMP. / buttons repeatedly to select for CODE No.
4 Push the TIME / buttons repeatedly to change the value indicated in the SET DATA section to that
you want.
5 Push the button.
6 Push the button (left side of the button) repeatedly to select another indoor UNIT No. to change.
Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.
UNIT LOUVER
7 Push the button (left side of the button) to check the changed addresses.
8 If the addresses have been changed correctly, push the button to finish the procedure.
– 33 –
Installation Manual
To change all the indoor unit addresses using an arbitrary wired remote controller.
(The method is available when the addresses have already been set automatically.)
(When communication wirings of 2 or more refrigerant lines are interconnected for central control)
You can change the addresses of indoor units in each refrigerant line using an arbitrary wired remote controller.
* Enter the address check / change mode and change the addresses.
UNIT No.
R.C. No.
CODE No.
ON / OFF
2
DATA
SET
SETTING
TEMP.
TIMER SET
TIME
1
FILTER
RESET
CL
SET
TEST
3
If no number appears on UNIT No., no outdoor unit exists on the line. Push button and select another line following
step 2.
(Execute it while the units are stopped.)
1 Push and hold the TIME and buttons at the same time for more than 4 seconds.
At first, the line 1 and CODE No. (Address Change) are indicated on the LCD display.
2 Push (left side of the button) and buttons repeatedly to select a system address.
UNIT LOUVER
3 Push the button.
• The address of one of the indoor units connected to the selected refrigerant line is indicated on the LCD display
and the fan and louvers of the unit are activated.
At first, the current indoor unit address is displayed in SET DATA.
(No system address is indicated.)
EN-65EN-66
Page 35
U1 U2
A B
U1 U2
A B
U1 U2
A B
U1
U2
A B
U1
U3
U2
U4
U1
U2
A B
U4
U3
U2
U1
CN02
CN10
U4
U3
U2
U1
CN02
CN10
U4
U3
U2
U1
CN02
CN10
Remote
controller
Central controller
Remote
controller
Remote
controller
Remote
controller
Indoor units to have their addresses initialized
Outdoor unit
[U1, U2] and
[U3, U4] connected
[U1, U2] and
[U3, U4] connected
[U1, U2] and [U3, U4]
not connected
Outdoor unitOutdoor unit
NOTE
U. 1. - - -
A.d.buS
A.d.nEt
A.d. c.L.
U.1.L08
A.d. n.G.
2FAN_IM_DHV2305601-00_EN.book Page 34 Monday, October 28, 2019 3:25 PM
Installation Manual
4 Push the TIME / buttons repeatedly to change the value of the indoor unit address in SET DATA.
Change the value in SET DATA to that of a new address.
5 Push the button to confirm the new address on SET DATA.
6 Push the button (left side of the button) repeatedly to select another address to change.
Each time you push the button, the indoor unit numbers in a refrigerant line are indicated one after
another. Only the fan and louvers of the selected indoor unit are activated.
Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.
UNIT LOUVER
7 Push the button.
(All the segments on the LCD display light up.)
8 Push the button to finish the procedure.
Resetting the address
(Resetting to the factory default (address undecided))
Method 1
Clearing each address separately using a wired remote controller.
Set the system address, indoor unit address and group address to “0099” using a wired remote controller.
(For the setting procedure, refer to the address setting procedures using the wired remote controller on the previous
pages.)
Method 2
Clearing all the indoor unit addresses on a refrigerate line at once from the outdoor unit.
1 Turn off the refrigerant line to reset to the factory default and set the outdoor unit of the line as below.
1) Disconnect the relay connectors between the [U1, U2] and [U3, U4] terminals.
(Leave them as they are if they have already been disconnected.)
2) Turn on dip switch 2 of SW30 on the interface P.C. board of the outdoor unit if the switch is OFF.
(Leave it as it is if it has already been set to ON.)
2 Turn on the indoor and outdoor units of the refrigerant line for which you want to initialize the addresses.
About one minute after turning on the power, confirm that the 7-segment display on the outdoor unit
indicates and operate the interface P.C. board on the outdoor unit of the refrigerant line as
follows.
SW01SW02SW03SW04Clearable addresses
212
222
Confirm that the 7-segment display indicates
five seconds.
Confirm that the 7-segment display indicates
five seconds.
and turn SW04 ON for more than
and turn SW04 ON for more than
System / indoor unit / group address
Central control address
3 Confirm that the 7-segment display indicates and set SW01, SW02 and SW03 to 1, 1, 1
respectively.
4 After a time appears on the 7-segment display if the address clearing has been completed
successfully.
If appears on the 7-segment display, the outdoor unit may still be connected to another
refrigerant line. Check again the connection of the relay connectors (CN10) between the [U1, U2] and [U3,
U4] terminals.
Take care to carry out the procedure above correctly; otherwise, addresses in other refrigerate lines may also be
cleared.
5 Set the addresses again after finishing the clearance.
EN
– 34 –
EN-67EN-68
Page 36
CAUTION
L23-02
SW06SW07SW09SW10
SW11SW12
1234 1234 1234 1234
1234 1234
CAUTION
NOTE
1, 5
3
2, 4
ON / OFF
TEMP.
TIME
SET CL
FILTER
RESET
TEST
TIMER SET
2FAN_IM_DHV2305601-00_EN.book Page 35 Monday, October 28, 2019 3:25 PM
8Test Run
Settings for hot water modules
After automatic addressing is completed, if there is hot water module in the system, 7-segment display will indicate
.
Please adjust the DIP switch as below, and slide SW09-bit4 to "ON" position.
Before test run
Confirm that the valve of the refrigerate pipe of the outdoor unit is OPEN.
• Before turning on the power, confirm that the resistance between the terminal block of power supply and the earth is
more than 1 MΩ using a 500 V megohmmeter.
Do not run the unit if it is less than 1 MΩ.
• Turn on the power and turn on the case heater of the compressor.
To save the compressor when it is activated, leave the power on for
more than 12 hours.
Methods of test run
When executing a test run using a remote controller
Operate the system normally to check the running condition using the wired remote controller. Follow the instructions
in the supplied owner’s manual when operating the unit.
If you use a wireless remote controller for operations, follow the instructions in the installation manual supplied with
the indoor unit.
To execute a test run forcibly under the condition that the thermostat automatically turns the unit off due to the indoor
temperature, follow the procedure below.
The forcible test run will automatically stop after 60 minutes to prevent continuous forcible running and return to
normal running.
– 35 –
Installation Manual
Do not use forcible running except for a test run as it overloads the
unit.
1 Push and hold the button for more than 4 seconds. TEST appears on the LCD display and the unit
enters the test mode.
(TEST is indicated on the LCD display during the test run.)
TEST
2 Push the button.
3 Push the button to switch the running mode to COOL or HEAT.
• Do not run the unit in any mode other than COOL or HEAT.
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
TEST
EN-69EN-70
4 Push the button to stop running after finishing the test run.
The indication on the LCD display returns to the status of procedure 1.
Page 37
NOTE
2FAN_IM_DHV2305601-00_EN.book Page 36 Monday, October 28, 2019 3:25 PM
Installation Manual
5 Push the button to exit the test mode.
(TEST disappears on the LCD display and the status changes to normal stopped mode.)
When executing a test run using the interface P.C. board on the outdoor unit
You can execute a test run by operating switches on the interface P.C. board of the outdoor unit.
“Individual test run”, which tests each indoor unit separately, and “collective test run”, which tests all the indoor units
connected, are available.
<Individual test run>
Starting operation
1 Set the running mode to “COOL” or “HEAT” on the remote controller of the indoor unit to be tested.
(The unit will run in the current mode unless you set the mode otherwise.)
7-segment display
[A]
[U1]
[B]
[ ]
2 Set the rotary switches on the interface P.C. board of the outdoor unit: SW01 to [16], SW02 and SW03 to
the address of the indoor unit to be tested.
SW02SW03Indoor unit address
1 to 1611 to 16Set number of SW02
1 to 16217 to 32Set number of SW02 + 16
1 to 16333 to 48Set number of SW02 + 32
1 to 16449 to 64Set number of SW02 + 48
7-segment display
[A]
[ ]
Address display of
the corresponding
indoor unit
[B]
[ ]
3 Push and hold SW04 for more than 10 seconds.
7-segment display
[A]
[ ]
Address display of
the corresponding
indoor unit
• The running mode follows the mode setting on the remote controller of the target indoor unit.
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after turning the power on or stopping running.
Finishing operation
[B]
[ ]
[FF] is displayed for 5
seconds.
1 Set the rotary switches on the interface P.C. board of the outdoor unit back: SW01 to [1], SW02 to [1] and
SW03 to [1].
7-segment display
[A]
[U1]
[B]
[ ]
<Collective test run>
Start operation
1 Set the rotary switches on the interface P.C. board of the outdoor unit as below.
When in “COOL” mode: SW01=[2], SW02=[5], SW03=[1].
When in “HEAT” mode: SW01=[2], SW02=[6], SW03=[1].
7-segment display
[A]
[C ]
[H ]
[B]
[ ]
[ ]
2 Push and hold SW04 for more than 2 seconds.
7-segment display
[A]
[C ]
[H ]
[B]
[ - C ]
[ - H ]
EN
EN-71EN-72
– 36 –
Page 38
NOTE
SW09SW07
SW11
SW06SW10
SW12 SW13
SW16
SW14
SW17
D600 D601 D602 D603 D604
SW04 SW05 SW15
SW01 SW02 SW03
SW30
D600 D601 D602 D603 D604
SW04 SW05 SW15
SW01 SW02 SW03
Interface P.C. board
Push switch
7-segment
display [A]
Push switch
7-segment
display [B]
Rotary switches
2FAN_IM_DHV2305601-00_EN.book Page 37 Monday, October 28, 2019 3:25 PM
– 37 –
Installation Manual
9Troubleshooting
• You cannot change the temperature setting during the test run.
• Errors are detected as usual.
• The unit does not perform test run for 3 minutes after turning the power on or stopping running.
Stop operation
1 Set the rotary switches on the interface P.C. board of the outdoor unit back:
SW01 to [1], SW02 to [1] and SW03 to [1].
7-segment display
[A]
[U1]
EN-73EN-74
[B]
[ ]
In addition to the CODE No. on the remote controller of an indoor unit, you can diagnose failure type of an outdoor unit
by checking the 7-segment display on the interface P.C. board.
Use the function for various checks.
Set every dip switch to OFF after checking.
7-Segment display and check code
Rotary switch setting
value
IndicationLED
SW01SW02SW03
111Outdoor unit check code
A
BCheck code display*
* If a check code has an auxiliary code, the display indicates the check code for three seconds and the auxiliary code
for one second alternately.
Check code (indicated on the 7-segment display on the outdoor unit)
Indicated when SW01 = [1], SW02 = [1], and SW03 = [1].
Check code
Auxiliary code
E06Number of indoor units which received normallyDecrease of number of indoor units, or HWM unit only
E07—Indoor / Outdoor communication circuit trouble
E08Duplicated indoor addressesDuplication of indoor addresses
E15—No indoor unit during automatic addressing
E1600: Capacity over 01 or more: No. of connected units Number of connected capacity over / indoor units
01: Other line outdoor connected
E20
02: Other line indoor connected
Other line connected during automatic addressing
E31IPDU quantity information*1IPDU communication trouble
F04—TD sensor trouble
F06—TE sensor trouble
01: TL1 sensor
F07
03: TL3 sensor
TL1 or TL3 sensor trouble
F08—TO sensor trouble
01: TS1 sensor
F12
03, 04: TS3 sensor
TS1 or TS3 sensor trouble
F13—TH sensor (Board installed) trouble
F15—Outdoor temp. sensor miswiring (TE, TL1)
F16—Outdoor pressure sensor miswiring (Pd, Ps)
F23—Ps sensor trouble
F24—Pd sensor trouble
D600
D601 D602 D603 D604
AB
Outdoor unit number
Check code nameIndication on 7-segment display on the outdoor unit
(U1)
Page 39
e.g., charged amount (10 kg)
Outdoor unit
e.g., charged amount (15 kg)
Indoor unit
Room ARoom BRoom CRoom DRoom ERoom F
01_IM_DHV2305601-00_EN.fm Page 38 Wednesday, November 27, 2019 11:36 AM
Installation Manual
*1 IPDU number information
01: Compressor 02: Fan 1 03: Compressor and Fan 1
04: Fan 2 05: Compressor and Fan 2 06: Fan 1 and Fan 2
07: Compressor, Fan 1 and Fan 2 08: Fan 3 09: Compressor and Fan 3
0A: Fan 1 and Fan 3 0B: Compressor, Fan 1 and Fan 3 0C: Fan 2 and Fan 3
0D: Compressor, Fan 2 and Fan 3 0E: Fan 1, Fan 2 and Fan 3
0F: Compressor, Fan 1, Fan 2 and Fan 3
EN-75EN-76
Check code
Check code nameIndication on 7-segment display on the outdoor unit
Auxiliary code
F31—Outdoor program trouble
H01—Compressor breakdown
H02—Compressor trouble (Lock)
H03—Current detective circuit system trouble
H05—TD sensor miswiring
H06—Low-pressure protective operation
H07—Oil level down detection
H0801TK sensor trouble for oil level
H1601Oil level detector circuit trouble
L04—Outdoor system address duplicated
L06Number of indoor units with priorityDuplication of indoor units with priority
L08—Indoor group / Address unset
L10—Outdoor capacity unset
L2302SW setting trouble when connecting to HWM unit
L29IPDU quantity information *1IPDU quantity trouble
L30Detected indoor unit addressExternal interlock of indoor unit
P03—Discharge temp TD trouble
P04—High-pressure switch trouble
00Phase missing detection
P05
*E (* : FAN motor number)Fan motor Vdc trouble
—Compressor Vdc trouble
P07—Heat sink overheat trouble
P10Detected indoor unit addressIndoor overflow trouble
*0: Elemental device short
*1: Position detective circuit trouble
*2: Input current sensor trouble
*3: Fan motor lock trouble *4: Motor current trouble
P22
*5: Synchronize, step out trouble
*C: Sensor temperature trouble
*D: Sensor short, free trouble
(*: Fan motor number)
P26—Compressor IPM short protection trouble
P29—Compressor position detective circuit system trouble
Outdoor fan IPDU trouble
– 38 –
WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit
The room in which the air conditioner is to be installed requires a design that in the event of
refrigerant gas leaking out, its concentration will not exceed a set limit.
The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia,
and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it
poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost
non-existent. With the recent increase in the number of high concentration buildings, however, the installation of multi
air conditioner systems is on the increase because of the need for effective use of floor space, individual control,
energy conservation by curtailing heat and carrying power etc.
Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with
conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small
room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its
concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can
occur).
In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical
ventilation combined with a gas leak detection device.
The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m
≤ Concentration limit (kg/m
3
)
The concentration limit of R410A which is used in multi air conditioners is 0.3 kg/m
NOTE 1
If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as
charged in each independent device.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A, B and C is 10 kg.
The possible amount of leaked refrigerant gas in rooms D, E and F is 15 kg.
3
)
3
.
EN
Page 40
Outdoor unit
Refrigerant piping
Indoor unit
Refrigerant piping
Outdoor unit
Indoor unit
Mechanical ventilation device - Gas leak detector
Very small room
Small
room
Medium
room
Large room
0
5
10
102030
15
20
25
30
35
40
m
2
Min. indoor floor area
Total amount of refrigerantkg
Range below the
density limit of
0.3 kg/m
3
(countermeasures
not needed)
Range above the density
limit of 0.3 kg/m
3
(countermeasures
needed)
2FAN_IM_DHV2305601-00_EN.book Page 39 Monday, October 28, 2019 3:25 PM
Important
NOTE 2
The standards for minimum room volume are as follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the
adjacent room for ventilation of leaking refrigerant gas
(opening without a door, or an opening 0.15% or
larger than the respective floor spaces at the top or
bottom of the door).
(3) If an indoor unit is installed in each
partitioned room and the refrigerant
piping is interconnected, the smallest
room of course becomes the object. But
when a mechanical ventilation is
installed interlocked with a gas leakage
detector in the smallest room where the
density limit is exceeded, the volume of
the next smallest room becomes the
object.
– 39 –
Installation Manual
NOTE 3
The minimum indoor floor area compared with the amount
of refrigerant is roughly as follows:
(When the ceiling is 2.7m high)
EN-77
Page 41
2FAN_IM_DHV2305601-00_EN.book Page 40 Monday, October 28, 2019 3:25 PM
MEMO
Installation Manual
EN
– 40 –
Page 42
2FAN_IM_DHV2305601-00_EN.book Page 41 Monday, October 28, 2019 3:25 PM
MEMO
– 41 –
Installation Manual
Page 43
2FAN_IM_DHV2305601-00_EN.book Page 42 Monday, October 28, 2019 3:25 PM
MEMO
Installation Manual
EN
– 42 –
Page 44
2FAN_IM_DHV2305601-00_EN.book Page 43 Monday, October 28, 2019 3:25 PM
DHV2305601-00
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.