The room in which the air conditioner is to be installed should be designed or chosen
such that in the event of a refrigerant gas leak the density of gas should not exceed a
set limit.
The refrigerant R-410A, which is used in the air conditioner product, is intrinsically safe
without the toxicity or combustibility of ammonia. R-410A is environmentally friendly and
is not restricted by current or pending laws intended to protect the ozone layer.
Risk of suffocation through leakage of R-410A is minimal. However, with the recent
increase in the number of high density buildings and use of multi air conditioner
systems to ensure effective use of floor space, energy conservation and individual
control, installers should ensure it is not possible to exceed density limits in the event of
a refrigerant leak. In particular, where a single unit of the multi conditioner system is to
be installed into a small room, select a suitable model and installation procedure so that
if refrigerant leaks out, density limits are not exceeded. In a room where there is a risk
of the density limit being exceeded, create an opening with adjacent rooms, or install
mechanical ventilation combined with a gas leak detection device.
Important
The density can be calculated as shown below;
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m
The density calculation must be carried out in accordance with
local regulation or guideline like BS EN 378
The above procedure must be completed in accordance with local, national and
international standards, code of practice and statutory requirements.
£ density limit (kg/m
3
)
3
)
Page 3
Note 1: If there are 2 or more refrigerating systems in
Outdoor unit
e.g. charged amount (15 kg)
e.g. charged
amount (10 kg)
Room A
Room B
Room CRoom DRoom ERoom F
Indoor unit
Mechanical ventilation device - gas leak detector
Refrigerant piping
Outdoor unit
Indoor unit
Large room
Medium room
Small
room
Very
small
room
a single area, the amount of refrigerant should be
charged as required for each individual unit.
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in
rooms A, B and C is 10 kg.
The possible amount of leaked refrigerant gas in
rooms D, E and F is 15 kg.
Note 2: The standards for minimum room volume are
as follows:
(1)No partition (shaded portion)
(2)When there is an effective opening with the adja-
cent room for ventilation of leaking refrigerant gas
(opening without a door, or an opening 0.15% or
larger than the respective floor spaces at the top or
bottom of the door).
(3)If an indoor unit is installed in each partitioned room
and the refrigerant tubing is interconnected, attention must be paid to ensure safeguards are in place
to avoid density limits being exceeded in each
partitioned area. When leak detection is interlocked
with mechanical ventilation equipment is installed in
the smallest room where the density limit is exceeded, the volume of the next smallest room
becomes the object.
Note 3: The minimum indoor floor area compared
with the amount of refrigerant is roughly as follows
(when the ceiling is 2.7 m high):
Outdoor unit
Refrigerant piping
Indoor unit
Range below the
2
m
density limit of
3
0.3 kg/m
(countermeasures
not needed)
Min. indoor floor area
Total refrigerant amount
Range above the
density limit of
3
0.3 kg/m
(countermeasures
needed
kg
Page 4
Outline (Tentative)
World-class energy savings_COP of 4.61* achieved by Toshiba's unrivalled
S-MMS technologies and newly developed components
Quiet operation can be further enhanced with an optional PMV
(flow regulating valve) Kit.
Versatile application_13 types of indoor units for use in up to 9 rooms (6 HP)
4HP CDU system
*
Pulse Motor Valve
*
Sales launch scheduled for early 2006. Specifications differ by region.
For questions regarding availability, please contact your local distributor.
Use of quieter place
Necessity of PMV Kit (RBM-PMV0361E / RBM-PMV0901E) for
quieter place application as an optional.
PMV Kit
New compact 4-way
cassette
Page 5
Outdoor unit line-up
AppearanceModel name 50HzModel name 60Hz
Indoor unit line-up
Cooling capacity (kW)
(HP equivalent)
4-way
Air Discharge
Cassette
Compact 4-way
Cassette
(600 x 600)
2-way
Air Discharge
Cassette
1-way
Air Discharge
Cassette
MCY-MAP0401HT
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
MCY-MAP0501HT
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
MCY-MAP0601HT
2.2
0.8
2.8
1.0
1.25
3.6
4.5
1.7
5.6
2.0
MCY-MAP0401HT2D
MCY-MAP0501HT2D
MCY-MAP0601HT2D
7.1
8.0
9.0
11.2
14.0
2.5
3.0
3.2
4.0
5.0
MMU-AP***1H
MMU-AP***1MH
MMU-AP***1WH
MMU-AP***1YH / -AP***2SH
Concealed Duct
Standard
Slim Duct
Concealed Duct
High Static
Pressure
Under Ceiling
High Wall
1series
High Wall
2series
Floor Standing
Cabinet
MMD-AP***1BH
MMD-AP***1SPH
MMD-AP***1H
MMC-AP***1H
MMK-AP***1H
MMK-AP***2H
MML-AP***1H
Floor Standing
Concealed
Floor
Standing
MML-AP***1BH
MMF-AP***1H
Page 6
Mini-SMMS Design Manual
00
- Warning on refrigerant leakage
-
Outline
-
Line-up
1.Design methods
1-1. System overview
1-2. Basic system configuration
1-3. Equipment selection procedure
1-4. Piping requirements
1-5. Wiring guideline
2.Indoor units
2-1. 4-way Air Discharge Cassette type
2-2. Compact 4-way Cassette(600 x 600) type
2-3. 2-way Air Discharge Cassette type
2-4. 1-way Air Discharge Cassette type
2-5. Concealed Duct Standard type
2-6. Slim Duct type
2-7. Concealed Duct High Static Pressure type
2-8. Under Ceiling type
2-9. High Wall 1 series type
2-10. High Wall 2 series type
2-11. Floor Standing Cabinet type
2-12. Floor Standing Concealed type
2-13. Floor Standing type
2-14. Application controls of indoor unit
1-3-1. Selection flow chart
1-3-2. Combination conditions for indoor unit
and outdoor unit
1-3-3. Cooling/heating capacity characteristic
1-3-4. Example of equipment selection
1-4. Piping requirements
1-4-1. Free branching system
1-4-2. Refrigerant piping length and piping size
1-4-3. Refrigerant piping length and piping size
with PMV Kit
1-4-4. Refrigerant piping example
1-4-5. Charging requirement with additional refrigerant
1-5-1. General
1-5-2. Connection of power supply
1-5-3. Electrical wiring design
1-5-4. Design of control wiring
1-5-5. Example of system wiring design
1-5-6. Electrical characteristics
Cooling:Indoor air temperature 27
Heating:Indoor air temperature 20
Inverter unit
4HP5HP6HP
MAP0401HTMAP0501HTMAP0601HT
MAP0401HT2DMAP0501HT2DMAP0601HT2D
12.1
12.5
6
o
C DB/19oCWB,Outdoor air temperature 35oCDB
o
C DB,Outdoor air temperature 7oCDB/6oCWB
14.0
16.0
8
15.5
18.0
9
Allocation standard of model name
MCY-2DMAPH T
No mark:Power supply specification, 1O
2D :Power supply specification, 1
T : Inverter Unit
H : Heat pump
Development Number
Capacity rank HP x 10
R410A
M : Individual Unit
Multi Compact Type
1-2
220/230/240V, (50Hz)
/
O
220V, 60Hz
/
Page 10
1-1-2. Indoor units
TypeAppearanceModel name
4-way Air Discharge
Cassette Type
Compact 4-way
Air Discharge
(600x600) Type
2-way Air Discharge
Cassette Type
1-way Air Discharge
Cassette Type
Concealed Duct
Standard Type
Slim Duct Type
Concealed Duct
High Static
Pressure Type
Under Ceilling Type
MMU-AP0091H
MMU-AP0121H
MMU-AP0151H
MMU-AP0181H
MMU-AP0241H
MMU-AP0271H
MMU-AP0301H
MMU-AP0361H
MMU-AP0481H
MMU-AP0071MH
MMU-AP0091MH
MMU-AP0121MH
MMU-AP0151MH
MMU-AP0181MH
MMU-AP0071WH
MMU-AP0091WH
MMU-AP0121WH
MMU-AP0151WH
MMU-AP0181WH
MMU-AP0241WH
MMU-AP0271WH
MMU-AP0301WH
MMU-AP0071YH
MMU-AP0091YH
MMU-AP0121YH
MMU-AP0152SH
MMU-AP0182SH
MMU-AP0242SH
MMD-AP0071BH
MMD-AP0091BH
MMD-AP0121BH
MMD-AP0151BH
MMD-AP0181BH
MMD-AP0241BH
MMD-AP0271BH
MMD-AP0301BH
MMD-AP0361BH
MMD-AP0481BH
MMD-AP0071SPH
MMD-AP0091SPH
MMD-AP0121SPH
MMD-AP0151SPH
MMD-AP0181SPH
MMD-AP0181H
MMD-AP0241H
MMD-AP0271H
MMD-AP0361H
MMD-AP0481H
MMC-AP0151H
MMC-AP0181H
MMC-AP0241H
MMC-AP0271H
MMC-AP0361H
MMC-AP0481H
Capacity rank
009 type
012 type
015 type
018 type
024 type
027 type
030 type
036 type
048 type
007 type
009 type
012 type
015 type
018 type
007 type
009 type
012 type
015 type
018 type
024 type
027 type
030 type
007 type
009 type
012 type
015 type
018 type
024 type
007 type
009 type
012 type
015 type
018 type
024 type
027 type
030 type
036 type
048 type
007 type
009 type
012 type
015 type
018 type
018 type
024 type
027 type
036 type
048 type
015 type
018 type
024 type
027 type
036 type
048 type
Capacity
code
1.00
1.25
1.70
2.00
2.50
3.00
3.20
4.00
5.00
0.80
1.00
1.25
1.70
2.00
0.80
1.00
1.25
1.70
2.00
2.50
3.00
3.20
0.80
1.00
1.25
1.70
2.00
2.50
0.80
1.00
1.25
1.70
2.00
2.50
3.00
3.20
4.00
5.00
0.80
1.00
1.25
1.70
2.00
2.00
2.50
3.00
4.00
5.00
1.70
2.00
2.50
3.00
4.00
5.00
Cooling
capacity (kW)
2.8
3.6
4.5
5.6
7.1
8.0
9.0
11.2
14.0
2.2
2.8
3.6
4.5
5.6
2.2
2.8
3.6
4.5
5.6
7.1
8.0
9.0
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
4.5
5.6
7.1
8.0
9.0
11.2
14.0
2.2
2.8
3.6
4.5
5.6
5.6
7.1
8.0
11.2
14.0
4.5
5.6
7.1
8.0
11.2
14.0
Heating
capacity (kW)
3.2
4.0
5.0
6.3
8.0
9.0
10.0
12.5
16.0
2.5
3.2
4.0
5.0
6.3
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
12.5
16.0
2.5
3.2
4.0
5.0
6.3
6.3
8.0
9.0
10.0
16.0
5.0
6.3
8.0
9.0
12.5
16.0
PMV Kit
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
1-3
Page 11
TypeAppearanceModel name
High Wall Type
(1 series)
High Wall Type
(2 series)
Floor Standing
Cabinet Type
Floor Standing
Concealed Type
Floor Standing Type
MMK-AP0071H
MMK-AP0091H
MMK-AP0121H
MMK-AP0151H
MMK-AP0181H
MMK-AP0241H
MMK-AP0072H
MMK-AP0092H
MMK-AP0122H
MML-AP0071H
MML-AP0091H
MML-AP0121H
MML-AP0151H
MML-AP0181H
MML-AP0241H
MML-AP0071BH
MML-AP0091BH
MML-AP0121BH
MML-AP0151BH
MML-AP0181BH
MML-AP0241BH
MMF-AP0151H
MMF-AP0181H
MMF-AP0241H
MMF-AP0271H
MMF-AP0361H
MMF-AP0481H
Capacity
rank
007 type
009 type
012 type
015 type
018 type
024 type
007 type
009 type
012 type
007 type
009 type
012 type
015 type
018 type
024 type
007 type
009 type
012 type
015 type
018 type
024 type
015 type
018 type
024 type
027 type
036 type
048 type
Capacity
code
0.80
1.00
1.25
1.70
2.00
2.50
0.80
1.00
1.25
0.80
1.00
1.25
1.70
2.00
2.50
0.80
1.00
1.25
1.70
2.00
2.50
1.70
2.00
2.50
3.00
4.00
5.00
Cooling
capacity (kW)
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
4.5
5.6
7.1
4.5
5.6
7.1
8.0
11.2
14.0
Heating
capacity (kW)
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
5.0
6.3
8.0
5.0
6.3
8.0
9.0
10.0
16.0
PMV Kit
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Allocation standard of model name
MM- -APH
C : China model
M : Compact 4-way Cassete Type
W: 2way Cassette Type
S : 1way Cassette Type
Y : Small sized 1way Cassette Type
B : Built-in Type (Built-in Duct Type)
(Floor concealed type)
SP(S):Slim Duct Type
Development series No.
Based on the cooling capacity (Btu/h) /1,000
R410A
U : Cassette Type
C : Under Ceiling Type
D : Duct Type
K : High Wall Type
L : Floor Type (Cabinet type)
(Concealed type)
F : Floor Standing Type
MM : Modular Multi Type
1-4
Page 12
1-1-3. Branching joints and headers *1
Model name
RBM-BY53E
Y-shape branching joint
RBM-BY103E
4-branching header
8-branching header
*1 If total capacity code value of indoor unit exceeds that of outdoor unit, apply code of outdoor unit.
*2 "capacity code" can be obtained from page 1-17. (capacity code is not actual capacity)
*3 When using Y-shape branching joint for 1st branching, select according to the capacity code of outdoor unit.
RBM-HY1043E
RBM-HY1083E
Indoor unit capacity code (*2) :Total below 6.4
Indoor unit capacity code (*2) :Total 6.4 or more
and below 7.8
1 : Coefficient to use for correction of outdoor unit capacity when total capacity of the indoor
*
units are not equal to the outdoor unit capacity.
1-17
Page 25
Air flow variation ratio of indoor unit vs. capacity correction (For concealed duct type only)
30
20
10
0
-
10
-
20
010203040
Pipe length (Equivalent length) L(m)
Hight of outdoor unit H (m)
5060708090100
100%
98
96
94
92
90
88
86
84
82
1.1
1.0
0.9
8090100110120
Capacity correction value
Connecting pipe length and lift difference between indoor and outdoor units vs. capacity correction value
Air flow variation ratio (%)
30
20
10
0
-
10
Hight of outdoor unit H (m)
-
20
100%
010203040
Outdoor unit
L is the longest one of
(Ll + a, Ll + b, Ll + c)
hoLl
H = ho +
(Largest one of ha, hb, and hc)
94
96
98
92
90
5060708090100
88
86
84
82
Pipe length (Equivalent length) L(m)
(Example)
Design Pipelength: 55m
Height of outdoor unit: 15m
Capacity correction value : 89%
ha
hb
hc
a
A
b
B
Indoor unit
c
C
1-18
Page 26
Correction of outdoor unit diversity
1.1
1
(Example)
Design Outdoor unit: 5.0HP
Indoor units total capacity : 5.5HP
(Capacity ratio: 110%)
Capacity correction value : 1.03%
0.9
0.8
0.7
Capacity correction value
8080100110120130
Standard capacity ratio
Indoor units total capacity ratio (%)
Heating capacity calculation method :
2
Required heating capacity = Heating capacity x Factor (
Indoor air dry bulb temperature vs. capacity correction value
1.2
1.1
1.0
0.9
0.8
152024
Capacity correction value
Indoor air dry bulb temp. (oC)
1.1
1
0.9
0.8
0.7
Capacity correction value
8080100110120130
Indoor units total capacity ratio (%)
, , , , *1, *2) kW
Standard capacity ratio
(Example)
o
Design Indoor conditions : 21.5
C DB
Capacity correction value : 0.98
1.2
1.1
1.0
0.9
0.8
152024
Capacity correction value
Indoor air dry bulb temp. (oC)
Outdoor air wet bulb temperature vs. capacity correction value
1.2
1.1
1
0.9
0.8
0.7
0.6
0.5
Capacity correction value
-
15
-
10
-
50 51015
Outdoor air wet bulb temp. (oC)
1 : Coefficient to use for correction of outdoor unit capacity when total capacity of the indoor
*
(Example)
-
Design Outdoor conditions :
5oC WB
Capacity correction value : 0.8
1.2
1.1
1
0.9
0.8
0.7
0.6
0.5
Capacity correction value
-
15
-
10
-
50 51015
Outdoor air wet bulb temp. (oC)
units are not equal to the outdoor unit capacity.
2 : Refer to item 3.
*
1-19
Page 27
Air flow variation ratio of indoor unit vs. capacity correction (For concealed duct type only)
1.1
1.0
0.9
8090100110120
Capacity correction value
Connecting pipe length and lift difference between indoor and outdoor units vs. capacity correction value
Air flow variation ratio (%)
30
20
10
100%
0
-
10
-
20
0 102030405060 708090100
98
99
97
96
95
Height of outdoor unit H (m)
Pipe length (Equivalent length) L (m)
Outdoor unit
L is the longest one of
(Ll + a, Ll + b, Ll + c)
hoLl
H = ho +
(Largest one of ha, hb, and hc)
ha
hb
hc
a
A
b
B
Indoor unit
c
C
94
(Example)
Design Pipe length: 75m
Heigh of outdoor unit : 15m
Capacity correction value : 95.1%
30
20
10
0
-
10
-
20
Height of outdoor unit H (m)
99
100%
0 102030 405060 708090100
97
98
Pipe length (Equivalent length) L (m)
96
95
94
1-20
Page 28
Correction of outdoor unit diversity
1.1
1
(Example)
Design Outdoor unit: 5HP
Indoor units total capacity : 4.5HP
(Capacity ratio: 90%)
Capacity correction value : 0.9%
0.9
0.8
0.7
Capacity correction value
8090100110120130
Standard capacity ratio
Indoor units total capacity ratio (%)
1 : Coefficient to use for correction of outdoor unit capacity when total capacity of the indoor
*
1.1
1
0.9
0.8
0.7
Capacity correction value
8090100110120130
Indoor units total capacity ratio (%)
Standard capacity ratio
units are not equal to the outdoor unit capacity.
3
Capacity correction in case of frost on the outdoor heat exchanger in heating
Correct the heating capacity when frost was found on the outdoor heat exchanger.
Heating capacity = Capacity after correction of outdoor unit × Correction value of capacity resulted from frost
(Capacity after correction of outdoor unit : Heating capacity calculated in the above item 2.)
Capacity correction in case of frost on the outdoor heat exchanger
1.0
0.9
0.8
Capacity correction value
-
15
-
10
-
50 510
Outdoor air wet bulb temp. (oC)
Capacity calculation for each indoor unit
4
Capacity for each indoor unit
= Capacity after correction of outdoor unit x
Required standard capacity of indoor unit
Total value of standard indoor unit capacity
1-21
Page 29
5
Operating temperature range
o
C)
Outdoor air dry bulb temp. (
In cooling time
45
40
35
30
25
20
15
10
5
0
-
5
-
10
Continuously
operable
range
(in pull down)
Usable range
302528201510
Indoor air wet bulb temp. (oC)
o
C)
Outdoor air wet bulb temp. (
-
-
-
-
In heating time
20
15
10
5
Continuously
0
5
Usable range
(in warming-up)
10
15
20
5 1015202530
Indoor air dry bulb temp. (oC)
operable
range
Rated conditions
6
Cooling :
Indoor air temperature 27oC DB/19.0oC WB, Outdoor air temperature 35oC DB
Heating :
Indoor air temperature 20oC DB, Outdoor air temperature 7oC DB/6oC WB
1-22
Page 30
1-3-4. Example of equipment Selection
The following shows an example of equipment selection based upon a building model
Fig. 1 Overview of building model
<Outside view><Floor plan>
8m
2F
2F
1F
7.2m
10.4m
1F
Steel frame, reinforced concrete building, two stories
above ground. Total floor area : 150m
2
Outdoor unit is installed on the roof.
Design indoor conditions
O
Cooling : 27.0/19.0
C DB/WB, Heating : 20OC DB
Design outdoor conditions
O
Cooling : 35
C DB (Standard condition), Heating : 3OC WB (Standard condition : 6OC WB)
2 - 12 - 22 - 3
-
1
1
1
-
2
Quiet places
2
-
42 - 5
1
-
4
Stores
1
-
3
Non-air conditioning zone
Selection Criteria for Each Floor
2F : Outdoor capacity exactly matches the total indoor capacity.
Total indoor HP = Outdoor unit HP Indoor: 1.5 HP x 2 units + 1.25 HP + 1.0 HP+ 0.8HP = 6.05 HP
Outdoor: 6 HP Same capacity
1F : Consider the increasing heat load in the specific room.
Total indoor units HP > Outdoor unit HP
Select each indoor unit based on individual peak room load.
Indoor : 1.0HP + 1.5HP + 2.0HP + 2.0HP =
6.5HP Outdoor : 6HP
The outdoor unit should have sufficient capacity to cover the peak demand of the indoor unit
1-23
Page 31
Procedure and result of equipment selection
Procedure of equipment selection
1
a. Calculate cooling for every rooms.
b. Select an indoor unit to match the cooling load for every room from the table in pages.
c. Choose a tentative outdoor unit that will match with the indoor units. Perform capacity correction based
on the pipe length, system lift, indoor set temperature, outdoor temperature.
Then, make sure the corrected system cooling capacity satisfies the cooling load.
2
Equipment selection and capacity check
Floor
2F
1F
Air conditioning load
Indoor air
Room No.
2-1
2-2
2-3
2-4
2-5
1-1
1-2
1-3
1-4
conditioning load
(kW)
CoolingHeating
4.2
3.3
2.6
2.3
4.1
2.6
4.1
5.1
5.1
3.4
2.2
2.5
2.3
4.0
2.3
3.8
4.9
3.7
Indoor unit
Model
MMU-AP0151H
MMU-AP0121H
MMU-AP0091H
MMU-AP0071MH
MMU-AP0151H
MMU-AP0091H
MMU-AP0151H
MMU-AP0181H
MMU-AP0181H
Equipment selection
Capacity (kW)
CoolingHeating
4.5
3.6
2.8
2.2
4.5
2.8
4.5
5.6
5.6
5.0
4.0
3.2
2.5
5.0
3.2
5.0
6.3
6.3
Outdoor unit
Model
MCY-
MAP0601H
MAP0601H2D
MAP0601H
MAP0601H2D
Capacity (kW)
CoolingHeating
15.518.0
15.518.0
Floor
2F
1F
Piping distance
Room No.
2-1
2-2
2-3
2-4
2-5
1-1
1-2
1-3
1-4
Equivalent
length (m)
23
42
Height
difference
(m)
5
Capacity correctionCapacity check after correction
Pipe correction x temp.
correction
CoolingHeating
1.0
x
1.0
x
0.96
=0.96=
1.0
x
1.0
x
1.03
x
0.92
=0.94=
1.0
x
0.95
x
0.99
x
0.95
=0.89=
1.0
x
0.95
x
0.975
x
1.03
x
0.95
=0.90=
Capacity
Capacity (kW)
CoolingHeating
4.3
3.4
2.6
2.4
4.3
2.6
4.2
5.2
5.2
4.4
3.5
2.8
2.4
4.4
2.9
4.5
5.6
5.6
Judgment
1-24
good
Page 32
3
Schematic diagram
MCY-MAP0601HT
MCY-MAP0601HT2D
Outdoor unit
MCY-MAP0601HT
MCY-MAP0601HT2D
1st branching
joint
PMV Kit
RBM-PMV0901ERBM-PMV0361ERBM-PMV0361ERBM-PMV0361E
MMU-AP0151H
2nd branching
joint
PMV KitPMV KitPMV KitPMV Kit
MMU-AP0121HMMU-AP0091H
3rd branching
joint
4th branching
joint
MMU-AP0071MH
RRRRR
2 - 1
MMU-AP0091H
2 - 22
MMU-AP0151HMMU-AP0181HMMU-AP0181H
- 32 - 42
RRRR
RBM-PMV0901E
MMU-AP0151H
-
5
1 - 11
-
21-
1-25
31
-
4
Page 33
1-4. Piping requirement
1-4-1. Free branching system
1
Line branching system
2
Header branching system
3
Header branching system after line branching
4
Line branching system after header branching
5
Header branching system after header branching
The above five branching systems are available to dramatically increase the flexibility of refrigerant piping design.
Outdoor unit
Line
branching
system
Indoor unit
Branching joint
Remote
controller
Header
branching
system
Header
branching
system
after line
branching
Line
branching
system after
header
branching
Outdoor unit
Indoor unit
* In case of "PMV Kit"
Outdoor unit
PMV
Kit
Indoor unit
* In case of "PMV Kit"
Outdoor unit
Remote controller
Branching joint
Remote
controller
Branching header
Branching header
Branching header
Header
branching
system after
header
branching
PMV
Kit
Indoor
unit
Remote
controller
Branching
joint
1-26
Page 34
1-4-2. Refrigerant piping length and piping size
1
Allowable length and height difference of refrigerant piping
Outdoor unit
Main
pipe
L1
Branching pipe
L2
Branching header
1st branching
section
Branching
pipe
L3
Height
difference
between
Indoor and
outdoor unit
H1
ab cd
Indoor unit
Equivalent length corresponded to farthest piping
Equivalent length corresponded to farthest piping after 1st branching Li
L4
ef
Y-shape
branching joint
Height difference
between indoor units
H2
L
g
A
1-27
Page 35
1
Allowable length and height difference of refrigerant piping
Allowable valuePiping section
Piping
Length
Total extension of pipe
(Liquid pipe, real length)
Furthest piping length L
(*1)
Max.equivalent length of
main pipe
Equivalent length of furthest
piping from 1st branching
Li (*1)
Max.real length of indoor
unit connecting pipe
Real length
Equivalent
length
180m
100m
125m
65m
35m
15m
L1+L2+L3+L4+
a+b+c+d+e+f+g
L1+L3+L4+g
L1
L3+L4+g
a, b, c, d, e, f, g
Upper outdoor
unit
Height between indoor and
outdoor units H1
Height
Difference
Lower outdoor
unit
Height between indoor units H2
*1 Furthest indoor unit from 1st branch to be named "A"
30m
20m
15m
_
_
_
1-28
Page 36
1-4-2. Refrigerant piping length and piping size
2
Selection of refrigerant piping
Outdoor unit
Gas pipe
Main
pipe
Liquid pipe
1st branching
section
1
4
Branching
Branching
2
pipe
2
pipe
3
Y-shape
Branching joint
4
Branching header
4
3
Indoor unit
2
3
33
4
33
1-29
Indoor unit
Page 37
2
Selection of refrigerant piping
No. Piping partsNameSelection of pipe size
Size of main pipe
Outdoor unit
1
1st branching
section
Branching
section
2
Branching
section
Branching
section
3
Indoor unit
Main pipe
Branching
pipe
Indoor unit
connecting
pipe
Outdoor unit capacity type
0401 type
0501 type
0601 type
Pipe size between branching sections
Total capacity codes of indoor units at down stream side
Equivalent to HP
Below 2.8
2.8 to below 6.4
6.4 to below 7.2
Note) If the total capacity code value of indoor units exceeds that of the
outdoor units, apply the capacity code of outdoor units.
Connecting pipe size of indoor unit
Indoor unit capacity type
007, 009, 012 type
015, 018 type
024, 030, 036, 048 type
Gas pipe (mm)
Gas pipe
(mm)
Gas pipe (mm)
15.9
15.9
19.1
12.7
15.9
19.1
9.5
12.7
15.9
Liquid pipe (mm)
9.5
9.5
9.5
Liquid pipe
(mm)
9.5
9.5
9.5
Liquid pipe (mm)
6.4
6.4
9.5
Selection of branching section
Y-shape
Y-shape branching joint
Branching
header
Note) *1 : When using a Y-shape branching joint for the 1st branch, select
according to capacity code of the outdoor unit.
*2 : For 1 line after branching header indoor units with a maximum
capacity code of 6.0 in total can be connected.
For 4 branches
For 8 branches
4
branching joint
Branching
section
Branching
header
Minimum wall thickness for R410A application
Soft
OK
Harf Hard
or Hard
OK
OD
(inch)
1/4"
OD
(mm)
6.35
Minimum wall
thickness (mm)
Total capacity codes of indoor units at down stream side
Equivalent to HP
Below 6.4
6.4 to below 7.8
Below 7.8
Below 7.8
0.80
Model name
RBM-BY53E
RBM-BY103E
RBM-HY1043E
RBM-HY1083E
OK
OK
OK
NG*
OK
OK
OK
OK
3/8"
1/2"
5/8"
3/4"
9.52
12.70
15.88
19.05
1-30
0.80
0.80
1.00
1.00
*If the pipe size is
use a suitable material.
O
19.0 or more,
/
Page 38
1-4-3. Refrigerant piping length and piping size with PMV Kit
1
Allowable length and height difference of refrigerant piping
Outdoor unit
Main
pipe
L1
Branching pipe
L2
Branching header
1st branching
section
Branching
pipe
L3
Height
difference
between
Indoor and
outdoor unit
H1
a
bcd
hi jk
Indoor unit
Equivalent length corresponded to farthest piping
Equivalent length corresponded to farthest piping after 1st branching
L4
Y-shape
Branching joint
e
lm
f
PMV Kit
Height difference
between indoor units
(PMV Kit)
L
Li
g
n
H2
A
1-31
Page 39
1
Allowable length and height difference of refrigerant piping
Allowable valuePiping section
Piping
Length
Total extension of pipe
(Liquid pipe, real length)
Furthest piping length L
(*1)
Equivalent length of furthest
piping from 1st branching Li
(*1)
Real length
Equivalent
length
150m
65m
80m
50mMax.equivalent length of main pipe
15m
15mMax.real length of indoor unit connecting pipe
L1+L2+L3+L4+
a+b+c+d+e+f+g+
h+i+j+k+l+m+n
L1+L3+L4+g+n
L1
L3+L4+g+n
a+h, b+i, c+j, d+k,
e+l, f+m, g+n
Real length between PMV Kit and indoor unit
Upper outdoor
unit
Height between indoor and
outdoor unit H1
Height
Difference
Lower outdoor
unit
Height between indoor units (PMV Kit) H2
Height difference between highest indoor unit or PMV Kit and
lowest indoor unit or PMV Kit shall be 15m or less
*1 Furthest indoor unit from 1st branch to be named "A"
Not AvailableAvailable
PMV
Kit
Indoor unitIndoor unit
2m or more
and up to 10m
30m
20m
15m
PMV
Kit
h, i, j, k, l, m, n
_
_
_
NOTE
Don,t connect two or more indoor units to one PMV Kit. Arrange one indoor unit and one PMV Kit set to 1 by 1.
1-32
Page 40
1-4-3. Refrigeran piping length and piping size with PMV Kit
2
Selection of refrigerant piping
Outdoor unit
Gas pipe
Main
pipe
Liquid pipe
1st branching
section
1
4
Branching
pipe
2
Branching
pipe
2
Branching header
4
55
3
Y-shape
Branching joint
4
3
3
Indoor unit
2
5
55
33
4
33
PMV Kit
55
1-33
Indoor unit
Page 41
2
Selection of refrigerant piping
No. Piping partsNameSelection of pipe size
Size of main pipe
Outdoor unit
1
1st branching
section
Branching
section
2
Branching
section
Branching
section
3
Indoor unit
Main pipe
Branching
pipe
Indoor unit
connecting
pipe
Outdoor unit capacity type
0401 type
0501 type
0601 type
Pipe size between branching sections
Total capacity codes of indoor units at down stream side
Equivalent to HP
Below 2.8
2.8 to below 6.4
6.4 to below 7.2
Note) If the total capacity code value of indoor units exceeds that of the
outdoor units, apply the capacity code of outdoor units.
Connecting pipe size of indoor unit
Indoor unit capacity type
007, 009, 012 type
015, 018 type
024 type
Gas pipe (mm)
Gas pipe
(mm)
Gas pipe (mm)
15.9
15.9
19.1
12.7
15.9
19.1
9.5
12.7
15.9
Liquid pipe (mm)
9.5
9.5
9.5
Liquid pipe
(mm)
9.5
9.5
9.5
Liquid pipe (mm)
6.4
6.4
9.5
Selection of branching section
4
5
Branching
section
PMV Kit
Y-shape
branching joint
Branching
header
PMV Kit
Y-shape branching joint
Branching
header
Note) *1 : When using a Y-shape branching joint for the 1st branch, select
according to capacity code of the outdoor unit.
*2 : For 1 line after branching header indoor units with a maximum
capacity code of 6.0 in total can be connected.
Selection of PMV Kit
*1
For 4 branches
For 8 branches
*2
Indoor unit capacity type
007, 009, 012 type
015, 018, 024 type
Minimum wall thickness for R410A application
Soft
OK
Harf Hard
or Hard
OK
OD
(inch)
1/4"
OD
(mm)
6.35
Minimum wall
thickness (mm)
Total capacity codes of indoor units at down stream side
Equivalent to HP
Below 6.4
6.4 to below 7.8
Below 7.8
Below 7.8
Model name
RBM-PMV0361E
PBM-PMV0901E
0.80
Model name
RBM-BY53E
RBM-BY103E
RBM-HY1043E
RBM-HY1083E
OK
OK
OK
NG*
OK
OK
OK
OK
3/8"
1/2"
5/8"
3/4"
9.52
12.70
15.88
19.05
1-34
0.80
0.80
1.00
1.00
*If the pipe size is
use a suitable material
as detailed in the installation manual.
O
19.0 or more,
/
Page 42
1-4-4. Refrigerant piping example
1
In case of without "PMV Kit"
Outdoor unit
MCY-MAP0601HT
Main
=60m
L1
pipe
(7.6)
1st branching
L3
1
=20m
section
Branching pipe
Branching pipe
(3.4)
=7m
L2
=1m
a
MMU-AP0071MH
(4.2)
2
Branching header
Capacity
code
=6m
b
=8m
c
d
=15m
(0.8)(1.0)(0.8)(0.8)
MMU-AP0091H MMU-AP0701MH MMU-AP0701MH
Indoor unit
=10m
f
=4m
e
(1.7)
10m
12m
Y-shape
Branching joint
(2.5)
3
MMU-AP0151H
MMU-AP0241H
1-35
Page 43
Piping size
Mark
L1
L2
L3
a
b
c
Equivalent length
(m)
60
7
20
1
6
8
Seclection method
(capacity code)
0.8 + 1.0 + 0.8 + 0.8 = 3.4
1.7 + 2.5 = 4.2
0.8
1.0
0.8
Gas pipe
(mm)
O
19.1
/
O
15.9
/
O
15.9
/
O
9.5
/
O
9.5
/
O
9.5
/
Liquid pipe
(mm)
O
9.5
/
O
9.5
/
O
9.5
/
O
6.4
/
O
6.4
/
O
6.4
/
d
e
f
15
4
10
Y-shape branching joint and Header
Mark
1
2
1st branching
Branch header
0.8
1.7
2.5
Y-joint or Header select
(capacity code)
6
(capacity code of outdoor unit)
0.8 +1.0 +0.8 +0.8 = 3.4
(a+b+c+d=L2)
O
9.5
/
O
12.7
/
O
15.9
/
Model name
RBM-BY53E
RBM-HY1043E
O
6.4
/
O
6.4
/
O
9.5
/
3
Y-shape branch joint
1.7 + 2.5 = 4.2
(e+f=L3)
1-36
RBM-BY53E
Page 44
1-4-4. Refrigerant piping example
2
In cace of PMV Kit
Outdoor unit
MCY-MAP0601HT
Main
=20m
L1
pipe
(7.6)
1st branching
L3
1
=6m
section
Branching pipe
Branching pipe
(3.4)
=3m
L2
=4m
a
MMU-AP0071MH
(4.2)
2
Branching header
Capacity
code
=3m
b
=6m
c
=7m
d
(0.8)(1.0)(0.8)(0.8)
MMU-AP0091H MMU-AP0701MH MMU-AP0701MH
Indoor unit
=6m
f
=4m
e
(1.7)
10m
12m
Y-shape
Branching joint
(2.5)
3
MMU-AP0151H
PMV Kit
MMU-AP0241H
1-37
Page 45
Piping size
Mark
L1
L2
L3
a
b
c
d
e
f
Equivalent length
(m)
20
3
6
4
3
6
7
4
6
Seclection method
(capacity code)
0.8 + 1.0 + 0.8 + 0.8 = 3.4
1.7 + 2.5 = 4.2
0.8
1.0
0.8
0.8
1.7
2.5
Gas pipe
(mm)
O
19.1
/
O
15.9
/
O
15.9
/
O
9.5
/
O
9.5
/
O
9.5
/
O
9.5
/
O
12.7
/
O
15.9
/
Liquid pipe
(mm)
O
9.5
/
O
9.5
/
O
9.5
/
O
6.4
/
O
6.4
/
O
6.4
/
O
6.4
/
O
6.4
/
O
9.5
/
Y-shape branching joint and Header
Mark
1
2
3
1st branching
Branch header
Y-shape branch joint
PMV Kit
Mark
Y-joint or Header select
(capacity code)
6
(capacity code of outdoor unit)
0.8 +1.0 +0.8 +0.8 = 3.4
(a+b+c+d=L2)
1.7 + 2.5 = 4.2
(e+f=L3)
PMV Kit select
(capacity code)
0.8
1.0
Model name
RBM-BY53E
RBM-HY1043E
RBM-BY53E
Model name
RBM-PMV0361E
RBM-PMV0361E
1-38
0.8
0.8
1.7
2.5
RBM-PMV0361E
RBM-PMV0361E
RBM-PMV0901E
RBM-PMV0901E
Page 46
1-4-5. Charging requirement with additional refrigerant
After the system has been vacuumed,replace the vacuum pump
with a refrigerant cylinder and charge the system
with additional refrigerant.
R410A
Calculating the amount of additional refrigerant required
(Calculation)
Additional refrigerant charge amount is calculated from size of liquid pipe at site and its real length.
Additional refrigerant
charge amount at site
Table 1
Pipe dia. at liquid side
Additional refrigerant amount/1m (kg)
Table 2
Outdoor unit capacity type
Compensation by outdoor HP (kg)
Example :
(0501 type)
L1
b
R (kg)
L1
O
9.5 : 10m
/
O
6.4 : 3m
/
Real length of
=
liquid pipe
ab c d
L2
c
0401 type
L2
O
9.5 : 10m
/
O
6.4 : 4m
/
Additional refrigerant charge
amount per liquid pipe 1m
X
(Table 1)
O
6.4
/
0.025
-
0.8
L3
O
0.055
0501 type
L3
d
9.5
/
-
0.4
O
9.5 : 5m
/
O
6.4 : 5m
/
+
0601 type
0
a
Compensation by
outdoor HP
(Table 2)
O
9.5 : 3m
/
Additional charge amount R (kg) = (Lx X 0.025kg/m) + (Ly X 0.055kg/m) + (
= (12 X 0.025kg) + (28 X 0.055kg) + (
=1.44kg
O
Lx : Real total length of liquid pipe
Ly : Real total length of liquid pipe
Note)
If the additional refrigerant amount indicates a negative result from the calculation,
use air conditioner without the adding of any additional refrigerant.
6.4 (m)
/
O
9.5 (m)
/
1-39
-
0.4kg)
-
0.4kg)
Page 47
1-5. Wiring guideline
f
f
f
f
(
f
f
f
CAUTIONS
(1) Keep the refrigerant piping system and the indoor-indoor/indoor-outdoor control wiring systems together.
(2) When running power supplies and control wires parallel to each other, run them through separate conduits or
maintain a suitable distance between them.
(Current capacity of power supplies: 10A or less for 300m, 50A or less for 500m)
1-5-1. General
orm wiring of the power supplies in conformance with the regulation of
Per
the local electrical company.
Use a 2 core shield wire
and connecting o
This is recommended to prevent possible noise issues.
Be sure to connect an earth leakage breaker to the power supply o
the indoor units.
Never connect 220-240V power to the control wiring terminal block
U1,U2,U3,U4). Fault will be caused.
Locate wiring system
in the same line.
Arrange the cables so that the electrical wires do not come in to contact
with high-temperature parts of the pipework ; otherwise insulation will melt
and an accident may be caused.
Do not turn on the power supply o
the refrigerant pipe has finished.
indoor units to outdoor units.
or control wiring on connecting indoor units,
or the control and refrigerant piping system
1-5-2. Connection of power supply
The details are as follows.
(Terminal block)
the indoor units until vacuuming o
(Stripping length power cable)
90
50
(Power cable clamp)
Power supply specifications
Select the power supply cabling and fuse of each outdoor unit from the following
specifications:
3 core cable in conformance with Design 60245 IEC 66
Do not connect the units looping via the terminal blocks (L,N)
(Protective bush : Accessory)
1-40
Page 48
1-5-3. Electrical wiring desin
All models of indoor units
NOTE:
The above connecting lengths stated in the table indicate the length from the isolator to the outdoor unit. When the
power supply of the indoor units are connected in parallel, it is assumed that no more than a 2% voltage drop will occur.
If the connecting length is to exceed the stated lengths, select a suitable wire in accordance with the local wiring standards.
Model
Item
15A
2.0mm2 MAX.20m3.5mm2 MAX.50m
Field fuseWire size
Power supply wiring
Power supply
Outdoor
power source
Indoor
power source
MCY-MAP###1HT series1N~ 50Hz 220V-240V
MCY-MAP###1HT2D series1N~ 60Hz 220V
Earth leakage Breaker
hand switch
Single phase
50Hz 220-240V
or 60Hz 220V
Earth leakage breaker
power switch
Earth
LN
Over current breaker
breaker (fuse) switch
Earth leakage breaker
Outdoor unit power supply
Pull box
Indoor unitIndoor unitIndoor unit
Indoor unitIndoor unitIndoor unit
Determine the wire size for the indoor unit according to the number of
conncted indoor units downstream.
Outdoor Unit capacities and power supply wire sizes (Reference)
Observe local regulations in reference to the wire size selection and installtion.
Outdoor unit capacity typeInstallation fuse
0401 type6
0501 type6
0601 type6
* Design 60245 IEC66
Wire size *
2
Max. 28 m32A
mm
2
Max. 25 m32A
mm
2
Max. 22 m40A
mm
Maxim running current
25A
28A
31A
For Indoor Unit power supply
(Must be independent from the outdoor unit power supply )
1-41
Page 49
1-5-4. Design of control wiring
Power supply
Single phase
220-240V 50Hz
220V 60Hz
Central remote controller (Option)
TCB-SC642TLE2 (For line 64)
(Open)
Earth
Communication wire for control
between outdoor unit and
indoor unit
Connection of shield wire must be connected
(Connected to all connecting sections in each indoor unit)
Communication wire for
control between indoor
and PMV Kit
Remote
controller
Control device
U1U3U2
U4
Outdoor unit
Indoor unit
U1 U2
U1 U2
A B
U3 U4
Outdoor
unit
B
U1 U2
U1 U2
U3 U4
A B
(Header)
Outdoor
unit
U1 U2
A B
(Follower)
PMV Kit (option)
Communication wire for
control between indoor
and PMV Kit (option)
Mini-SMMS system
A
Outdoor
unit
U3 U4
U1 U2
B
U1 U2
A B
U1 U2
A B
U1 U2
A B
B
U1 U2
A B
U1 U2
A B
Remote
controller
Wire specification, quantity, size of crossover wiring and remote controller wiring
NameQ’ty
Crossover wiring (A + B)
(indoor-indoor / indoor-outdoor / control wiring,
central control wiring) *Total Control wiring length
Remote controller wiring
Control wiring between indoor and PMV Kit
(1)
The crossover wiring and central control wiring uses a 2-core non-polarity communication wire. Use 2-core shielded wire to prevent
Remote controller
2 cores
2 cores
Remote controller
Size
Up to 500mUp to 1000m1000 to 2000m
2
1.25mm
0.5 to 2.0mm
2
Be sure to use the attached cable. MIN 2m - MAX 10m
---
2.0mm
Specification
2
Shield wire
possible noise issues. Connect the end of the shielded wires and earth(ground) at both the outdoor and indoor unit.
Where the shielded wire is connected between a central controller and a outdoor unit, only earth(ground) at one end of the central control line.
(2) Use 2-core non-polarity wire for remote controller. (A, B terminals)
Use 2-core non-polarity wire for wiring of group control. (A, B terminals)
1-42
Page 50
1-5-5. Example of system wiring Design
1
In cace of without "PMV Kit"
Outdoor unit
Outdoor power supply
MCY-MAP###1HT ser ies : 1N~ 50Hz 220V-240V
MCY-MAP###1HT2D series : 1N~ 60Hz 220V
Central remote controller power supply
1N~ 50Hz 220-240V
1N~ 60Hz 220V
LN
Earth
U1 U2
U3 U4
(Open)
(Open)
L NU1 U2 U3 U4
Earth
Relay connector (At shipment from factory : No connection)
Outdoor unit
Indoor unit
Remote controller
Central remote controller (option)
Over current breaker (fuse) switch
Earth leakage breaker
Main switch
Pull box
PMV Kit (option)
(Option)
To other
refrigerant system
Indoor unit
Indoor unit
power supply
1N~ 50Hz 220-240V
1N~ 60Hz 220V
Eart h
Connection of shield wire must be connected
(Connected to all connecting sections in each Indoor units)
Control wiring between indoor units
U1 U2 A BU1 U2 A BU1 U2 A BU1 U2 A B
control
ad
LN
Eart h
LNLNLN
ABABAB
EarthEarth
Remote controller
[Group control]
1-43
Page 51
1-5-5. Example of system wiring Design
2
In cace of "PMV Kit"
Outdoor unit
Outdoor power supply
MCY-MAP###1HT series : 1N~ 50Hz 220V-240V
MCY-MAP###1HT2D series : 1N~ 60Hz 220V
Central remote controller power supply
1N~ 50Hz 220-240V
1N~ 60Hz 220V
(Option)
LN
Earth
U1 U2
U3 U4
(Open)
(Open)
L NU1 U2 U3 U4
Earth
Relay connector (At shipment from factory : No connection)
Outdoor unit
Indoor unit
Remote controller
Central remote controller (option)
Over current breaker (fuse) switch
Earth leakage breaker
Main switch
Pull box
PMV Kit (option)
To other
refrigerant system
Indoor unit
PMV Kit (option)
Indoor unit
power supply
1N~ 50Hz 220-240V
1N~ 60Hz 220V
Connection of shield wire must be connected
(Connected to all connecting sections in each Indoor units)
Control wiring between indoor units
U1 U2 A BU1 U2 A BU1 U2 A BU1 U2 A B
Indoor control
Indoor control
PC board
PC boad
CN82
Eart
h
LN
ABABAB
Eart h
LNLNLN
EarthEarth
Remote controller
[Group control]
1-44
Page 52
1-5-6. Electrical characteristics
Outdoor units
Model name
MCY-MAP0401HT
MCY-MAP0501HT
MCY-MAP0601HT
Legend
RLA : Rated Load Amps
FLA: Full Load Amps
kW: Fan Motor Rated Output (kW)
NOTE : RLA is based on the following conditions.
Indoor temperature : 27
Outdoor temperature : 35
Nominal
(V-Ph-Hz)
230-1-50
230-1-50
230-1-50
Voltage RangeCompressor
MinMaxRLAkWFLAMCAICF
198
198
198
o
CDB / 19oCWB
o
CDB
264
264
264
Indoor units
TypeModel
4-Way Air
Discharge
Cassette Type
Compact
4-Way Cassette
(600 x 600) Type
2-Way Air
Discharge
Cassette Type
1-Way Air
Discharge
Cassette Type
MMU-AP 0091 H
MMU-AP 0121 H
MMU-AP 0151 H
MMU-AP 0181 H
MMU-AP 0241 H
MMU-AP 0271 H
MMU-AP 0301 H
MMU-AP 0361 H
MMU-AP 0481 H
MMU-AP 0071 MH
MMU-AP 0091 MH
MMU-AP 0121 MH
MMU-AP 0151 MH
MMU-AP 0181 MH
MMU-AP 0071 WH
MMU-AP 0091 WH
MMU-AP 0121 WH
MMU-AP 0151 WH
MMU-AP 0181 WH
MMU-AP 0241 WH
MMU-AP 0271 WH
MMU-AP 0301 WH
MMU-AP 0481 WH*
MMU-AP 0071 YH
MMU-AP 0091 YH
MMU-AP 0121 YH
MMU-AP 0152 SH
MMU-AP 0182 SH
MMU-AP 0242 SH
MMD-AP 0071 BH
MMD-AP 0091 BH
MMD-AP 0121 BH
MMD-AP 0151 BH
MMD-AP 0181 BH
MMD-AP 0241 BH
MMD-AP 0271 BH
MMD-AP 0301 BH
MMD-AP 0361 BH
MMD-AP 0481 BH
MMD-AP 0071 SPH
MMD-AP 0091 SPH
MMD-AP 0121 SPH
MMD-AP 0151 SPH
MMD-AP 0181 SPH
MMD-AP 0181 H
MMD-AP 0241 H
MMD-AP 0271 H
MMD-AP 0361 H
MMD-AP 0481 H
MMC-AP 0151 H
MMC-AP 0181 H
MMC-AP 0241 H
MMC-AP 0271 H
MMC-AP 0361 H
MMC-AP 0481 H
MMK-AP 0071 H
MMK-AP 0091 H
MMK-AP 0121 H
MMK-AP 0151 H
MMK-AP 0181 H
MMK-AP 0241 H
MMK-AP 0072 H
MMK-AP 0092 H
MMK-AP 0122 H
MML-AP 0071 H
MML-AP 0091 H
MML-AP 0121 H
MML-AP 0151 H
MML-AP 0181 H
MML-AP 0241 H
MML-AP 0071 BH
MML-AP 0091 BH
MML-AP 0121 BH
MML-AP 0151 BH
MML-AP 0181 BH
MML-AP 0241 BH
MMF-AP 0151 H
MMF-AP 0181 H
MMF-AP 0241 H
MMF-AP 0271 H
MMF-AP 0361 H
MMF-AP 0481 H
MMD-AP 0071 BH
MMD-AP 0091 BH
MMD-AP 0121 BH
MMD-AP 0151 BH
MMD-AP 0181 BH
MMD-AP 0241 BH
MMD-AP 0271 BH
MMD-AP 0301 BH
MMD-AP 0361 BH
MMD-AP 0481 BH
MMD-AP 0071 SPH
MMD-AP 0091 SPH
MMD-AP 0121 SPH
MMD-AP 0151 SPH
MMD-AP 0181 SPH
MMD-AP 0181 H
MMD-AP 0241 H
MMD-AP 0271 H
MMD-AP 0361 H
MMD-AP 0481 H
MMC-AP 0151 H
MMC-AP 0181 H
MMC-AP 0241 H
MMC-AP 0271 H
MMC-AP 0361 H
MMC-AP 0481 H
MMK-AP 0071 H
MMK-AP 0091 H
MMK-AP 0121 H
MMK-AP 0151 H
MMK-AP 0181 H
MMK-AP 0241 H
MMK-AP 0072 H
MMK-AP 0092 H
MMK-AP 0122 H
MML-AP 0071 H
MML-AP 0091 H
MML-AP 0121 H
MML-AP 0151 H
MML-AP 0181 H
MML-AP 0241 H
MML-AP 0071 BH
MML-AP 0091 BH
MML-AP 0121 BH
MML-AP 0151 BH
MML-AP 0181 BH
MML-AP 0241 BH
MMF-AP 0151 H
MMF-AP 0181 H
MMF-AP 0241 H
MMF-AP 0271 H
MMF-AP 0361 H
MMF-AP 0481 H
For positioning of ceiling
position
(united with installation pattern)
For attaching pattern
Remote controller
Wired remote controller
Simple wired remote controller
Wireless remote controller kit
Weekly timer application
Central remote controller
ON-OFF controller
Heat
insulator
Washer
Hose band
Flexible hose
Heat insulator
1
8
1
1
1
For heat insulating of drain
connecting section
For hanging down unit
For connecting drain pipe
For centering the drain pipe
For sealing the wire connection
opening
Model Name
RBC-AMT31E
RBC-AS21E2
TCB-AX21U(W)-E2
RBC-AMT31E and RBC-EXW21E2
TCB-SC642TLE2
TCB-CC163TLE2
2-2
Page 58
2-1. 4-way Air Discharge Cassette Type
Optional accessories
Air discharge direction kit
TCB-BC1601UE
Auxiliary fresh air Flange
TCB-FF101URE2
Super Long Life Filter
TCB-LF1601UE2
High Efficiency Filter 65
TCB-UFM1601UE
High Efficiency Filter 90
TCB-UFH1601UE
Fresh air inlet Box
TCB-GB1601UE2
Ceiling panel
RBC-U21PG(W)-E2
Parts NameModel nameApplied ModelNotesRemarks
Ceiling panel
Super Long Life Filter
High Efficiency Filter 65
High Efficiency Filter 90
Fresh air inlet Box
Frech air and Filter Chamber
Auxiliary fresh air Flange
Spacer for height adjustment
Air discharge direction kit
RBC-U21PG(W)-E2
TCB-LF1601UE2
TCB-UFM1601UE
TCB-UFH1601UE
TCB-GB1601UE2
TCB-GFC1601UE2
TCB-FF101URE2
TCB-SP1601UE
TCB-BC1601UE
MMU-AP***1H
Fresh air and Filter Chamber
TCB-GFC1601UE2
Spacer for height adjustment
TCB-SP1601UE
Required accessory
Dust collecting effect : 50%
(Weight method)
*Not valid in combination with
TCB-FM1601UE, TCB-UFH1601UE
and TCB-BC1601UE
Dust collecting effect : 65%
(NBS Colorimentric method)
*Not valid in combination with
TCB-LF1601UE2, TCB-UFH1601UE,
TCB-FF101URE2 and TCB-BC1601UE
Dust collecting effect : 90%
(NBS Colorimentric method)
*Not valid in combination with
TCB-LF1601UE2, TCB-UFM1601UE,
TCB-FF101URE2 and TCB-BC1601UE
For fresh air intake by using the
knockout hole of Fresh air and filter
chamber. (dia=100mm)
*Not valid in combination with
TCB-FF101URE2 and
TCB-SP1601UE
For fresh air intake and installing high
efficiency filter or super long filter
*Not valid in combination with
TCB-SP1601UE
For easy fresh air intake by using
the knockout hole of indoor
unit.(dia=100mm)
*Not valid in combination with
TCB-GB1601UE2
Height = 500mm
*Not valid in combination with
TCB-GB1601UE2 and TCB-GFC1601UE2
Air direction charge by cutting off
air discharge port (3pcs)
*Not valid in combination with
TCB-LF1601UE2, TCB-UFM1601UE,
TCB-UFH1601UE
Use with TCB-GFC1601UE2
Use with TCB-GFC1601UE2
Use with TCB-GFC1601UE2
Use with TCB-GFC1601UE2
2-3
Page 59
2-1. 4-way Air Discharge Cassete Type
Specifications (50Hz)
50Hz
Model nameMMU-
Cooling/Heating capacity (Note 1)(kW)
Power supply
Electrical
characteristics
Appearance
Outer
dimension
Running current
Power consumption
Starting current (A)
Main unit
Ceiling
Panel
Main unit
Ceiling
panel
Model
Panel color
Height (mm)
Width(mm)
Depth (mm)
Height (mm)
Width(mm)
Depth (mm)
(A)
(kW)
AP0091H
2.8/3.2
AP0121H
3.6/4.0
1 phase 50Hz 230V (220-240V) (Separate power supply for indoor units is required.)
0.17
0.020
0.30
AP0151H
4.5/5.0
0.19
0.022
0.33
Heat-insulating material attached Zinc hot dipping steel plate
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the
reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
the actual operating environment become larger than the indicated values due to the effects of external sound.
Note: Rated conditionsCooling : Indoor air temperature 27oC DB/19oC WB, Outdoor air temperature 35oC DB
Heating : Indoor air temperature 20oC DB, Outdoor air temperature 7oC DB/6oC WB
2-4
Page 60
2-1. 4-way Air Discharge Cassete Type
Specifications (60Hz)
60Hz
Model nameMMU-
Cooling/Heating capacity (Note 1)
Power supply
Electrical
characteristics
Appearance
Outer
dimension
Running current
Power consumption
Starting current
Main unit
Ceiling
Panel
Main unit
Ceiling
panel
Model
Panel color
Height
Width
Depth
Height
Width
Depth
(kW)
(A)
(kW)
(A)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
AP0091H
2.8/3.2
0.18
0.020
0.30
AP0121H
3.6/4.0
AP0151H
4.5/5.0
1 phase 60Hz 220V (Separate power supply for indoor units is required.)
0.200.220.260.370.610.85
0.0220.0260.0320.0480.0700.110
0.330.360.420.590.871.23
Heat-insulating material attached Zinc hot dipping steel plate
AP0181H
5.6/6.3
Moon white (Munsell/2.5GY 9.0/0.5)
AP0241H
7.1/8.0
RBC-U21PG (W) -E2
256319
840
840
35
950
950
AP0271H
8.0/9.0
AP0301H
9.0/10.0
AP0361H
11.2/12.514.0/16.0
AP0481H
Total weight
Heat exchanger
Soundproof/Heat-insulating
material
Fan unit
Air filter
Controller
Connecting
pipe
Sound pressure level(Note 2)
(High/Mid./Low)
PMV KitNot available
Main unit
Ceiling panel
Fan
Standard air flow
(High/Mid./Low)
Motor
Gas side
Liquid side
Drain port
(Nominal dia. mm)
(kg)
(kg)
3
(m
/h)
(W)
(mm)
(mm)
(dB(A))
20
800
(730/680)
O
9.5
/
30/29/27
2223
4.5
Finned tube
Non-flammable insulation
Turbo fan
930
(830/790)
O
6.4
/
31/29/2732/29/2834/31/2837/33/3040/36/3344/38/34
1,050
(920/800)
60
Standard filter (Long life filter)
Remote controller
O
12.7
/
25 (Polyvinyl chloride tube)
1,200
(920/820)
1,320
(1,110/850)
O
15.9
/
O
9.5
/
28
1,680
(1,300/1,070)
90
2,040
(1,430/1,130)
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8615 based on the
reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 meter height.
Note 2 : The sound levels are measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in
Note : Rated conditions Cooling : Indoor air temperature 27
the actual operating environment become larger than the indicated values due to the effects of external sound.
O
C DB/19OC WB, Outdoor air temperature 35OC DB
Heating : Indoor air temperature 20OC DB, Outdoor air temperature 7OC DB/6OC WB
2-5
Page 61
2-1. 4-Way Air Discharge Cassete Type
Dimension
MMU-AP0091H to P0481H
Suction grille (Air suction port)
Electric parts box
415
950
254.5
Z
35o
723 hanging bolt pitch
950
381.6
panel external dimension
Hanging bolt
M10 or W3/8 local arrange
840
480
227
B
35
97
Bottom face of ceilingBottom face of ceiling
57.5
25
188
Bottom face
of ceiling
Knockout for flesh air intake
For
O
100
/
64
57
Indoor unitBottom face of ceiling
Z view
346.5
790 hanging bolt pitch
panel external dimension
ceiling open dimension
For branch duct knockout square hole
(2 positions at right side)
Drain discharge port
A
210
88
360
Stand-up
640 or less
(NOTE)
As ABS is used for the drain discharge
port of the main unit, the vinyl chloride
paste cannot be used.
Use the flexible hose (Band fix)
included in the package.
Stand-up
850 or less
130
Drain-up standing-up sizeSpace required for installation and servicing
Air discharge port (4-way)
860 to 910
840
250 70
270
105
105
30
1000 or more
15 or more
1000 or more
860 to 910
ceiling open dimension
Refrigerant pipe
connecting port
(Gas)
Refrigerant pipe
connecting port
(Liquid)
45
113
ModelAB
AP0091H to AP0301H
AP0361H to AP0481H
1000 or more
15 or more
O
/
174
256
319
150
mm
120
183
Wired remote controller
RBC-AMT31E
4
2.7
Simple wired remote controller
RBC-AS21E2
Wireless remote controller kit
120
TCB-AX21U(W)-E2
Weekly timer application
120
RBC-AMT31E and RBC-EXW21E2
16
2-6
200
Check port
( 450)
Check port
( 450)
200
Note: All dimensions are in mm.
Page 62
2-2. Compact 4-way cassette (600 x 600) type
Appearance
Standard accessories
Part nameQ'tyShapeUsage
Installation Manual1This manual
Heat insulating pipe2
Installation pattern
Installation gauge2
Pattern fixing screw4For attach the installation pattern
Heat insulator
1
1
_
M5 x 16
(Ensure handover to customer)
For heat insulation of the pipe connecting section
For checking of ceiling opening and the main unit position
For positioning of the ceiling position
(To be used with the installation pattern)
For heat insulation of drain connecting section
Washer
Hose band
Flexible hose
Heat insulator
8
1
1
1
Optional accessories
Air discharge direction kit
Parts NameModel nameApplied ModelNotesRemarks
Ceiling panel
Auxiliary fresh air Flange
Frech air and Filter Chamber
Fresh air inlet Box
Spacer for height adjustment
Air discharge direction kit
RBC-UM11PG(W)E
TCB-FF101URE2
TBD
TBD
TBD
TBD
For hanging unit
For connecting drain pipe
For adjusting core-out of drain pipe
For sealing of wire connecting port
Auxiliary fresh air Flange
TCB-FF101URE2
Fresh air inlet Box
*********
Fresh air Chamber
*********
Spacer for height adjustment
*********
Ceiling panel
RBC-UM11PG(W)E
Required accessory
For easy fresh air intake by using
the knockout hole of indoor
(NOTE)
As ABS is used for the drain discharge port of the main unit,
the vinyl chloride paste cannot be used.
Use the flexible hose (Band fix)
included in the package.
12.7
O
/
.......
O
9.5
/
190.5
193.5
Wiring connection port
162
/
Electric
parts box
6.4
/
70.5
105
93
150
/
320.5
97.5
55
150
/
235235
575 unit external dimension
525 hanging bolt pitch
595 to 660 ceiling open dimension
700 Panel external dimension
105
331.5
Model name
MMU-AP0071MH
4-way air Discharge Cassete Type
MMU-AP0091MH
MMU-AP0121MH
MMU-AP0151MH
Arialb1i0c0p34;TOSHIBA CARRIER CORPORATION
MMU-AP0181MH
177
105
214
42
148
21
158
142
256
O
162
/
120
93
145.5
105
70.5
Knockout for
flesh air intake O
525 hanging bolt pitch
700 Panel external dimension
595 to 660 ceiling open dimension
Hanging bolt
M10 or W3/8 local arrange
Drain discharge port
268
134
145.5
Indoor unit
220.5
27
63
Ceiling panel
100
/
29
142
64368.5
Bottom face of ceiling
300
Stand-up
827.5 or less
Stand-up
207
175
149
64
850 or less
Wired remote controller
RBC-AMT31E
Simple wired remote controller
RBC-AS21E2
Drain-up standing-up size
595 to 660 ceiling open dimension
595 to 660 ceiling open dimension
1000 or more
Wireless remote controller kit
TCB-AX21E2
Weekly timer application
RBC-AMT31E and RBC-EXW21E2
2-10
Bottom face
of ceiling
1000 or more1000 or more
15 or more
Obustacle
Space required for installation and servicing
Check port
( 450)
15 or more
Note: All dimensions are in mm.
200
Page 66
2-3. 2-way Air Discharge Cassette Type
Apperarance
Standard accessories
Part nameQ'tyShapeUse
Installation Manual
Heat insulating pipe
MMU-AP0301WH
type or lower
Installation
MMU-AP0481WH
pattern
type
This
1
manual
2
1
2
(Be sure to hand this
over to customer)
For heat insulating
pipe connecting
section
For checking the
_
position of the ceiling
openings and the unit
Installation gauge
Pattern fixing screw
Fan motor connector
Heat insulator
Ceiling panel components
NameCeiling panelCenter panelAir filter
Shape
(Q'ty)
RBC-UW466PG :
Attached to indoor unit
Attached to ceiling panel,
and removes dust.
Usage
(1 set)(1 pc)
_
_
Optional accessories
Part nameQ'tyShapeUse
For positioning of ceiling
1
6
M5 x 16
1
1
position (United with
installation pattern)
For attaching the
installation pattern
For changing fan motor
r.p.m. to apply higher
ceiling
For seal for wire
connecting port
Screw installing panelScrew installing panel
20mm
(4 pcs)(2 pcs)
For fixing ceiling panel
(4 corners)
30mm
M5 x 30M5 x 20
For tentative hanging and fixing
ceiling panel (Center part)