In addition to description for the normal-type model,
descriptions about the models with anti-corrosion
(based on JRA Standard light protection and heavy
protection) models are added in this Manual.
PRINTED IN JAPAN, Sep.,2006 ToMo
WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit
The room in which the air conditioner is to be
installed requires a design that in the event of
refrigerant gas leaking out, its concentration will not
exceed a set limit.
The refrigerant R410A which is used in the air
conditioner is safe, without the toxicity or combustibility
of ammonia, and is not restricted by laws to be imposed
which protect the ozone layer. However, since it
contains more than air, it poses the risk of suffocation if
its concentration should rise excessively. Suffocation
from leakage of R410A is almost non-existent. With the
recent increase in the number of high concentration
buildings, however, the installation of multi air
conditioner systems is on the increase because of the
need for effective use of floor space, individual control,
energy conservation by curtailing heat and carrying
power etc.
Most importantly, the multi air conditioner system is able
to replenish a large amount of refrigerant compared with
conventional individual air conditioners. If a single unit of
the multi conditioner system is to be installed in a small
room, select a suitable model and installation procedure
so that if the refrigerant accidentally leaks out, its
concentration does not reach the limit (and in the event
of an emergency, measures can be made before injury
can occur).
In a room where the concentration may exceed the limit,
create an opening with adjacent rooms, or install
mechanical ventilation combined with a gas leak
detection device.
The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m³)
≤ Concentration limit (kg/m³)
The concentration limit of R410A which is used in multi
air conditioners is 0.3kg/m³.
NOTE 1 :
If there are 2 or more refrigerating systems in a single
refrigerating device, the amounts of refrigerant should
be as charged in each independent device.
e.g., charged
amount (10kg)
Room A Room B Room C Room D Room E Room F
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in
rooms A, B and C is 10kg.
The possible amount of leaked refrigerant gas in
rooms D, E and F is 15kg.
Outdoor unit
e.g.,
charged amount (15kg)
Indoor unit
Important
NOTE 2 :
The standards for minimum room volume are as follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the adjacent
room for ventilation of leaking refrigerant gas
(opening without a door, or an opening 0.15% or
larger than the respective floor spaces at the top or
bottom of the door).
Outdoor unit
Refrigerant piping
Indoor unit
(3) If an indoor unit is installed in each partitioned room
and the refrigerant piping is interconnected, the
smallest room of course becomes the object. But
when a mechanical ventilation is installed
interlocked with a gas leakage detector in the
smallest room where the density limit is exceeded,
the volume of the next smallest room becomes the
object.
Refrigerant piping
Outdoor unit
Very
small
room
Small
room
Mechanical ventilation device - Gas leak detector
Medium
room
Large room
NOTE 3 :
The minimum indoor floor area compared with the
amount of refrigerant is roughly as follows:
(When the ceiling is 2.7m high)
40
Range below the
35
m²
density limit
of 0.3 kg/m³
30
(countermeasures
not needed)
25
20
15
10
5
Min. indoor floor area
0
102030
Total amount of refrigerant
Range above
the density limit
of 0.3 kg/m³
(countermeasures
needed)
15.EXPLODED VIEWS AND PARTS LIST ................................................ 189
In addition to description for the normal-type model, descriptions about the models with anti-corrosion
(based on JRA Standard light protection and heavy protection) models are added in this Manual.
3
SAFETY CAUTION
The important contents concerned to the safety are described on the product itself and on this Service Manual.
Please read this Service Manual after understanding the described items thoroughly in the following contents
(Indications/Illustrated marks), and keep them.
[Explanation of indications]
Indication
DANGER
WARNING
CAUTION
∗ Property damage : Enlarged damage concerned to property, furniture, and domestic animal/pet
Indicates contents assumed that an imminent danger causing a death or serious injury of
the repair engineers and the third parties when an incorrect work has been executed.
Indicates possibilities assumed that a danger causing a death or serious injury of the
repair engineers, the third parties, and the users due to troubles of the product after work
when an incorrect work has been executed.
Indicates contents assumed that an injury or property damage ( ∗) may be caused on the
repair engineers, the third parties, and the users due to troubles of the product after work
when an incorrect work has been executed.
Explanation
[Explanation of illustrated marks]
MarkExplanation
Indicates prohibited items (Forbidden items to do)
The sentences near an illustrated mark describe the concrete prohibited contents.
Indicates mandatory items (Compulsory items to do)
The sentences near an illustrated mark describe the concrete mandatory contents.
Indicates cautions (including danger/warning)
The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.
[Confirmation of warning label on the main unit]
Confirm that labels are indicated on the specified positions
(Refer to the Parts disassembly diagram (Outdoor unit).)
If removing the label during parts replace, stick it as the original.
DANGER
Turn “OFF” the breaker before removing the front panel and cabinet, otherwise an electric
shock is caused by high voltage resulted in a death or injury.
During operation, a high voltage with 400V or higher of circuit (∗) at secondary circuit of the highvoltage transformer is applied.
Turn off breaker.
Execute discharge
between terminals.
Prohibition
If touching a high voltage with the naked hands or body, an electric shock is caused even if using an
electric insulator.
∗ : For details, refer to the electric wiring diagram.
When removing the front panel or cabinet, execute short-circuit and discharge between highvoltage capacitor terminals.
If discharge is not executed, an electric shock is caused by high voltage resulted in a death or injury.
After turning off the breaker, high voltage also keeps to apply to the high-voltage capacitor.
Do not turn on the breaker under condition that the front panel and cabinet are removed.
An electric shock is caused by high voltage resulted in a death or injury.
4
Check earth wires.
Prohibition of modification.
Use specified parts.
Do not bring a child
close to the equipment.
Insulating measures
No fire
Refrigerant
Assembly/Wiring
WARNING
Before troubleshooting or repair work, check the earth wire is connected to the earth
terminals of the main unit, otherwise an electric shock is caused when a leak occurs.
If the earth wire is not correctly connected, contact an electric engineer for rework.
Do not modify the products.
Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury.
For spare parts, use those specified (*).
If unspecified parts are used, a fire or electric shock may be caused.
∗: For details, refer to the parts list.
Before troubleshooting or repair work, do not bring a third party (a child, etc.) except
the repair engineers close to the equipment.
It causes an injury with tools or disassembled parts.
Please inform the users so that the third party (a child, etc.) does not approach the equipment.
Connect the cut-off lead wires with crimp contact, etc, put the closed end side upward
and then apply a water-cut method, otherwise a leak or production of fire is caused at
the users’ side.
When repairing the refrigerating cycle, take the following measures.
1) Be attentive to fire around the cycle. When using a gas stove, etc, be sure to put out fire
before work; otherwise the oil mixed with refrigerant gas may catch fire.
2) Do not use a welder in the closed room. When using it without ventilation, carbon
monoxide poisoning may be caused.
3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may
catch the inflammables.
(For more details, please refer Page 7 to Page 9)
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the
ozone layer.
Check the used refrigerant name and use tools and materials of the parts which
match with it.
For the products which use R410A refrigerant, the refrigerant name is indicated at a
position on the outdoor unit where is easy to see. To prevent miss-charging, the route of the
service port is changed from one of the former R22.
For an air conditioner which uses R410A, never use other refrigerant than R410A.
For an air conditioner which uses other refrigerant (R22, etc.), never use R410A.
If different types of refrigerant are mixed, abnormal high pressure generates in the refrigerating cycle and an injury due to breakage may be caused.
Do not charge refrigerant additionally.
If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in
the refrigerating cycle changes resulted in change of air conditioner characteristics or
refrigerant over the specified standard amount is charged and an abnormal high pressure is
applied to the inside of the refrigerating cycle resulted in cause of breakage or injury.
Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute
vacuuming, and then newly recharge the specified amount of liquid refrigerant. In this time,
never charge the refrigerant over the specified amount.
When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant
or air other than R410A into the specified refrigerant.
If air or others is mixed with the refrigerant, abnormal high pressure generates in the
refrigerating cycle resulted in cause of injury due to breakage.
After installation work, check the refrigerant gas does not leak.
If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire
such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
Never recover the refrigerant into the outdoor unit.
When the equipment is moved or repaired, be sure to recover the refrigerant with recovering device. The refrigerant cannot be recovered in the outdoor unit; otherwise a serious
accident such as breakage or injury is caused.
After repair work, surely assemble the disassembled parts, and connect and lead the
removed cables as before. Perform the work so that the cabinet or panel does not
catch the inner cables.
If incorrect assembly or incorrect cable connection was done, a disaster such as a leak or
fire is caused at user’s side.
5
WARNING
Insulator check
Ventilation
Be attentive to
electric shock
Compulsion
After the work has finished, be sure to use an insulation tester set (500V mugger) to
check the resistance is 2M
metal section (Earth position).
If the resistance value is low, a disaster such as a leak or electr ic shock is caused at user’s
side.
When the refrigerant gas leaks during work, execute ventilation.
If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the
refrigerant and the closed room full with gas is dangerous because a shortage of oxygen
occurs. Be sure to execute ventilation.
When checking the circuit inevitably under condition of the power-ON, use rubber
gloves and others not to touch to the charging section.
If touching to the charging section, an electric shock may be caused.
When the refrigerant gas leaks, find up the leaked position and repair it surely.
If the leaked position cannot be found up and the repair work is interrupted, pump-down
and tighten the service valve, otherwise the refrigerant gas may leak into the room.
The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking
stove though the refrigerant gas itself is innocuous.
When installing equipment which includes a large amount of charged refrigerant such
as a multi air conditioner in a sub-room, it is necessary that the density does not the
limit even if the refrigerant leaks.
If the refrigerant leaks and exceeds the limit density, an accident of shor tage of oxygen is
caused.
For the installation/moving/reinstallation work, follow to the Installation Manual.
If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric
shock or fire is caused.
ΩΩ
Ω or more between the charge section and the non-charge
ΩΩ
Check after rerair
Check after reinstallation
Put on gloves
Cooling check
After repair work has finished, check there is no trouble.
If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off
the power breaker.
After repair work (installation of front panel and cabinet) has finished, execute a test
run to check there is no generation of smoke or abnormal sound.
If check is not executed, a fire or an electric shock is caused. Before test run, install the
front panel and cabinet.
Check the following items after reinstallation.
1) The earth wire is correctly connected.
2) The power cord is not caught in the product.
3) There is no inclination or unsteadiness and the installation is stable.
If check is not executed, a fire, an electric shock or an injury is caused.
CAUTION
Be sure to put on gloves (
If not putting on gloves, an injury may be caused with the parts, etc.
(∗) Heavy gloves such as work gloves
When the power was turned on, start to work after the equipment has been
sufficiently cooled.
As temperature of the compressor pipes and others became high due to cooling/heating
operation, a burn may be caused.
∗∗
∗) during repair work.
∗∗
6
• New Refrigerant (R410A)
1. Safety Caution Concerned to New Refrigerant
The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of
refrigerant, the refrigerating oil has been also changed. Therefore, be sure that water , dust, the former
refrigerant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner with
new refrigerant during installation work or service work. If an incorrect work or incorrect service is performed, there is a possibility to cause a serious accident. Use the tools and materials exclusive to R410A to
purpose a safe work.
2. Cautions on Installation/Service
1) Do not mix the other refrigerant or refrigerating oil.
For the tools e xclusive to R410A, shapes of all the joints including the service port differ from those of the
former refrigerant in order to prev ent mixture of them.
2) As the use pressure of the new refrigerant is high, use material thickness of the pipe and tools which are
specified for R410A.
3) In the installation time , use clean pipe materials and work with great attention so that water and others do
not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc.
Use the clean pipes.
Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.)
4) For the earth protection, use a vacuum pump for air purge.
5) R410A refrigerant is azeotropic mixture type refriger ant. Therefore use liquid type to charge the refrigerant. (If using gas for charging, composition of the refrigerant changes and then characteristics of the air
conditioner change.)
3. Pipe Materials
For the refrigerant pipes, copper pipe and joints are mainly used. It is necessary to select the most appropriate pipes to conform to the standard. Use clean material in which impurities adhere inside of pipe or joint to a
minimum.
1) Copper pipe
<Piping>
The pipe thickness, flare finishing size , flare nut and others differ according to a refrigerant type.
When using a long copper pipe for R410A, it is recommended to select “Copper or copper-base pipe without
seam” and one with bonded oil amount 40mg/10m or less . Also do not use crushed, deformed, discolored
(especially inside) pipes. (Impurities cause clogging of expansion valves and capillary tubes.)
<Flare nut>
Use the flare nuts which are attached to the air conditioner unit.
2) Joint
The flare joint and socket joint are used for joints of the copper pipe. The joints are rarely used for installa-
tion of the air conditioner. However clear impurities when using them.
7
4. Tools
(1)Required T ools for R410A
Mixing of different types of oil ma y cause generation of sludge, clogging of capillary, etc.
Accordingly, the tools to be used are classified into the following three types.
1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2) Tools exclusive for R410A, but can be also used for conv entional refrigerant (R22)
3) Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Tools whose specifications are changed for R410A and their interchangeability
No.
Used tool
Flare tool
Copper pipe gauge for
adjusting projection
margin
Torque wrench
Gauge manifold
Charge hose
V acuum pump adapter
Electronic balance for
Refrigerant charge
Gas leakage check
Refrigerant charge
air conditioner installation
Existence of
new equipment
for R410A
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
(Note 2)
R410A
Whether conventional
equipment can be
used
*(Note 1)
*(Note 1)
No
No
No
Yes
No
No
No
Conventional air
conditioner installation
Whether new equipment
can be used with
conventional refrigerant
Yes
*(Note 1)
No
No
Yes
Yes
No
Yes
No
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the f ollowing equipments which serve also for R22 are necessary
as the general tools.
1) Vacuum pump
Use vacuum pump by
attaching vacuum pump adapter.
2) Torque wrench
3) Pipe cutter
4) Reamer
5) Pipe bender
6) Level vial
7) Screwdriver (+, –)
8) Spanner or Monkey wrench
9) Hole core drill
10) Hexagon wrench (Opposite side 4mm)
11) Tape measure
12) Metal saw
Also prepare the following equipments for other installation method and run check.
1) Clamp meter
2) Thermometer
3) Insulation resistance tester (Megger)
4) Electroscope (Volt meter)
8
5. Recharge of Refrigerant
When recharge of the refrigerant is required, charge the new refrigerant with the specified amount in the
procedure as described below .
Recover the refrigerant and check there is no refrigerant in the
equipment.
Connect the charge hose to the packed valve service ports at gas
side, liquid side of the outdoor unit.
Connect the charge hose to vacuum pump adaptor.
Open the packed valves fully at liquid and gas sides, and then return
the valve at gas side a little to the closed side.
Open fully PMV of the outdoor unit.
• Turn on power of the outdoor unit.
• Short CN30 on I/F P.C. board of the outdoor unit.
•
Turn off power of the outdoor unit within 2 minutes after
Open fully the handle on the Low side of the gauge manifold, and
then turn on the power of vacuum pump for vacuuming.
When the pressure has lowered until indication of the compound
gauge pointed –0.1MPa (–76cmHg), open fully the handle Low and
turn off the power of vacuum pump.
Never charge the refrigerant over the specified amount.
Do not charge the additional refrigerant.
shorting CN30
If charging refrigerant additionally when refrigerant gas
leaks, the refrigerant composition in the refrigerating cycle
changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is
charged and an abnormal high pressure is applied to the
inside of the refrigerating cycle resulted in cause of
breakage or injury.
.
Leave it as it is for 1 to 2 minutes and check the indicator
of the compound gauge does not return.
Set the refrigerant cylinder on the electronic balance,
connect the charge hose to connecting ports of the
cylinder and the gauge manifold, and then charge the
liquid refrigerant from the service port at liquid side.
(Shield with the gauge manifold so that refrigerant does
not flow to gas side.)
Low-
pressure gauge
Connected to
indoor unit
Connected to other
terminal units
Main
pipe
Brazed
Fully
tightened
Valve fully closed
(gas side)
Center unit
Service
port
Copper pipe
Service port
Valve fully closed
(liquid side)
VL VH
Ø6.4
4mm-hexagonal wrench is required.
High-
pressure gauge
Gauge
manifold
Reducing
valve
Nitrogen
Ø6.4
Copper pipe
gas
Set the equipment so that liquid refrigerant can be charged.
When using a cylinder with siphon pipe, liquid can be charged without inverting the cylinder.
[ Cylinder with siphon ][ Cylinder without siphon ]
Refrigerant
cylinder
Electronic
balance
Gauge manifold
OUTDOOR unit
Electronic
balance
Gauge manifold
cylinder
Refrigerant
OUTDOOR unit
Siphon
R410A refrigerant is consisted with HFC mixed refrigerant.
Therefore if the refrigerant gas is charged, the composition
of the charged refrigerant changes and characteristics of
the equipment changes.
6. Environmental concern
Use “Vacuum pump method” for an air purge (Discharge of air in the connecting pipe) in installation time.
• Do not discharge flon gas into the air to protect the earth environment.
• Using the vacuum pump method, clear the remaining air (Nitrogen, etc.) in the unit. If the air remains , the
pressure in the refrigerating cycle becomes abnormally high and an injury could occur through failure of
the product.
009 type
012 type
015 type
018 type
024 type
027 type
030 type
036 type
048 type
007 type
009 type
012 type
015 type
018 type
007 type
009 type
012 type
015 type
018 type
024 type
027 type
030 type
007 type
009 type
012 type
015 type
018 type
024 type
007 type
009 type
012 type
015 type
018 type
024 type
027 type
030 type
036 type
048 type
007 type
009 type
012 type
015 type
018 type
018 type
024 type
027 type
036 type
048 type
015 type
018 type
024 type
027 type
036 type
048 type
Capacity
code
1.00
1.25
1.70
2.00
2.50
3.00
3.20
4.00
5.00
0.80
1.00
1.25
1.70
2.00
0.80
1.00
1.25
1.70
2.00
2.50
3.00
3.20
0.80
1.00
1.25
1.70
2.00
2.50
0.80
1.00
1.25
1.70
2.00
2.50
3.00
3.20
4.00
5.00
0.80
1.00
1.25
1.70
2.00
2.00
2.50
3.00
4.00
5.00
1.70
2.00
2.50
3.00
4.00
5.00
Cooling
capacity (kW)
2.8
3.6
4.5
5.6
7.1
8.0
9.0
11.2
14.0
2.2
2.8
3.6
4.5
5.6
2.2
2.8
3.6
4.5
5.6
7.1
8.0
9.0
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
4.5
5.6
7.1
8.0
9.0
11.2
14.0
2.2
2.8
3.6
4.5
5.6
5.6
7.1
8.0
11.2
14.0
4.5
5.6
7.1
8.0
11.2
14.0
Heating
capacity (kW)
3.2
4.0
5.0
6.3
8.0
9.0
10.0
12.5
16.0
2.5
3.2
4.0
5.0
6.3
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
5.0
6.3
8.0
9.0
10.0
12.5
16.0
2.5
3.2
4.0
5.0
6.3
6.3
8.0
9.0
10.0
16.0
5.0
6.3
8.0
9.0
12.5
16.0
PMV Kit
——
——
——
——
——
——
——
——
——
Available
Available
Available
Available
Available
——
——
——
——
——
——
——
——
Available
Available
Available
Available
Available
Available
007 type
009 type
012 type
015 type
018 type
024 type
007 type
009 type
012 type
007 type
009 type
012 type
015 type
018 type
024 type
007 type
009 type
012 type
015 type
018 type
024 type
015 type
018 type
024 type
027 type
036 type
048 type
Capacity
code
0.80
1.00
1.25
1.70
2.00
2.50
0.80
1.00
1.25
0.80
1.00
1.25
1.70
2.00
2.50
0.80
1.00
1.25
1.70
2.00
2.50
1.70
2.00
2.50
3.00
4.00
5.00
Cooling
capacity (kW)
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
2.2
2.8
3.6
4.5
5.6
7.1
2.2
2.8
3.6
4.5
5.6
7.1
4.5
5.6
7.1
8.0
11.2
14.0
Heating
capacity (kW)
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
2.5
3.2
4.0
5.0
6.3
8.0
2.5
3.2
4.0
5.0
6.3
8.0
5.0
6.3
8.0
9.0
10.0
16.0
PMV Kit
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
Available
——
——
——
——
——
——
——
——
——
——
——
——
Allocation standard of model name
MMAPH--
Destination C : China
H : Heat pump type
M : Compact 4-way Cassete Type
W: 2-way Cassette Type
S : 1-way Cassette Type
Y : Small sized 1-way Cassette Type
B : Built-in Type (Built-in Duct Type) (Floor concealed type)
SP(S) : Slim Duct Type
Development series No.
Based on the cooling capacity (Btu/h) /1,000
R410A
U : Cassette Type
C : Under Ceiling Type
D : Duct Type
K : High Wall Type
L : Floor Type (Cabinet type) (Concealed type)
F : Floor Standing Type
MM : Modular Multi type
12
1-1-3. Branching Joints and Headers *1
1st revised : Jun. 2006
Model name
Y-shape branching joint
4-branching header *1
8-branching header *1
*1: For each line after branching header, total indoor capacity code must be 6.0 maximum.
RBM-BY53E
RBM-HY1043E
RBM-HY1083E
Appearance
1-1-4. PMV Kit
Model name
RBM-PMV0361E
RBM-PMV0901E
Indoor unit capacity type
007, 009, 012 type
015, 018, 024 type
Appearance
13
1-1-5. Remote Controller
Name
Wired remote controller
Model
name
RBC- AMT31ERBC- AS21E2
AppearanceApplication
Connected to indoor unit
Wired remote
controller
Wired remote
controller
In case of control by
( )
2 remote controllers
Connected to indoor unit
TEST
SETTING
ûC
ûF
Function
• Star t / Stop
• Mode Change
• Temperature setting
• Fan speed
• Timer function
1) On or off elapsed timer with
30 minutes increments.
Automatic off function.
2) Weekly when combined with
RBC-EXW21E2 weekly schedule
operation can be operated.
• Filter dirty indicator
Displays automatically maintenance time
of indoor filter by flashes.
• Self-diagnosis function. Pressing
“CHECK” button displays status code.
• Control by 2 remote controllers is available.
Two remote controllers can be connected
to one indoor unit.
The indoor unit can be separately
operated from a different location.
• Star t / Stop
• Temperature setting
• Change of air flow
• Check code display
Simple wired remote controller
Wireless remote controller kit
Simple remote controller
• Star t / Stop
• Mode change
• Temperature setting
• Change of air flow
• Timer function
On or off timer operation, setting in 30
minutes increments.
Automatic Off function.
• Control by 2 remote controllers is available.
Two wireless remote controllers can
operate one indoor unit.
The indoor unit can be separately
operated from a different location.
• Check code display
TCB-AX21U(W)-E2
(for 4-way air discharge cassette)
RBC-AX22CE2 (for under ceiling)
TCB-AX21-E2 (for other units except for
the concealed duct high static pressure)
TCB- AX21U(W)-E2RBC-AX22CE2TCB-AX21E2
14
Name
Model
name
AppearanceApplication
Performance
Central remote controllerON- OFF controller
ZONE
ALL
ZONE
GROUP
1234
TEST
UNIT No.
SET DATA
SETTING
R.C.
No.
SELECT ZONE
TCB- SC642TLE2TCB- CC163TLE2
CL
SET
GROUP
CODE
Connected to outdoor unit
or indoor unit
Individual control up to 64 indoor units.
Individual control for max. 64 indoor
units divided into 4 zones.
Outdoor unit
(Up to 16 indoor units for each zone)
Up to 16 outdoor units are connect-
able.
Four selectable central control settings
to restrict individual remote controller
operations.
Setting for one of 1 to 4 zones is
available.
Can be used with other central control
No.
devices (Up to 10 central control
devices with in one control circuit)
Two selectable control modes
(Central controller mode.
Central
remote controller
Remote controller mode)
Setting of simultaneous ON/OFF 3
times for each day of the week
combined with a weekly timer.
Central
remote
controller
Indoor
remote controller
Connected to outdoor unit
or indoor unit
Outdoor unit
ON-OFF
controller
Indoor unit
• Individual control up to 16 indoor
units.
• Setting of simultaneous ON-OFF 3
times for each day of the week when
combined with a weekly timer.
• Connected to 2 remote controllers is
possible.
ON-OFF
controller
Indoor
remote controller
15
Name
Model
name
AppearanceApplication
Performance
Weekly timer
PROGRAM1
PROGRAM2
PROGRAM3
WEEKLY TIMER
RBC- EXW21E2
SuMoTuWeTh FrSa
ERROR
Connected to central
remote controller or
wired remote controller
Wired
remote controller
Outdoor unit
Weekly
timer
Weekly schedule operation
1) Setting different start / stop time for
each day of the week
2) ON / OFF can be set 3 times a day.
ON
8:0012:00 13:00 18:00 19:00 21:00
OFF ONOFF ONOFF
3) “CHECK“ “PROGRAM” “DAY” button
copying of settings easy.
4) Two different schedules for a week
can be specified.
(Summer schedule and winter
schedule, etc.)
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
Indoor unit
Earth screw
Flow selector
unit earth
S(N)R(L)
Power supply
Single phase
220-240V 50Hz
220V 60Hz
FM
screw
Closed end
connector
CN039
(YEL)
WHI
121
2
RED
343
4
565
6
77
9
(BLK)
CN304
(GRY)
1
2
3
1
2
3
CN066
(WHI)
CN044
(BRW)
TR
Line Filter
1
Outdoor unit
1
2
3
1
2
3
1
2
3
1
2
1
2
U2U
P301
CN067
(BLK)
CN040
(BLU)
1 2
1 2
BLU
U
1
BLU
U
RY004
Fuse
T5.0A
250V~
CN041
(BLU)
1 2 3
1 2 3
BLK
BLK
BA
2
CN1
(WHI)
1 2
1 2
Remote controller
FAN
CN083
YX
(WHI)
RED
RY007
3 3
1 1
CN02
(BLU)
RC
BLK
9 8 7 6
9 8 7 6
ORN
5 4 3 2 1
5 4 3 2 1
HML UL
RY006
RY005
CN050
(WHI)
1 2 3 4 5
Network
1 2
1 2
adaptor
(Option)
CN01
(WHI)
2
MCC-1401
LM
DP
(BLU)
CN068
RY001
1 2
1 2
1 2 3
1 2 3
LM
(GRN)
CN033
FS
1 2 3
1 2 3
DM
YEL
BLU
1 2 3
1 2 3
RY002
Indoor control P.C. board
Power supply
circuit
CN074
(WHI)
CN075
(WHI)
1 2 3
1 2 3
1 2 3
4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
Sub P.C. board
MCC-1520
1 2 3 4 5 6
1 2 3 4 5 6
1 1
TR
2 2
CN03
(RED)
1. indicates the terminal block, letter at inside
indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
CN02
(YEL)
CN01
(WHI)
CN061
(YEL)
1 2 3 4 5 61 2 3 4 5 6
FS
(RED)
CN030
6 4 3
6 4 3
1 2 3
1 2 3
CN032
(WHI)
1 2
Fan drive
Symbol
FM
RC
TR
LM
TA
TC1,TC2,TCJ
RY001
RY002
RY004
RY005~007
FS
DM
PMV
PMV
1 2 5
1 2 5
PMV
4 5 6
(BLU)
4 5 6
CN082
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRW)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
CN060
(WHI)
1 2 3 4 5 6
Option
Parts name
Fan motor
Running capacitor
Transformer
Louver motor
Indoor temp sensor
Temp sensor
Louver control relay
Drain control relay
Heater control relay
Fan motor control relay
Float switch
Drain pump motor
Pulse Motor Valve
2-1-3. 1-way Air Discharge Cassette Type (Compact type)
Model: MMU-AP0071YH, AP0091YH, AP0121YH
20
Color
indication
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
Indoor unit
Earth screw
Flow selector
WHI
RED
RED
S(N)R(L)
Power supply
Single phase
220-240V 50Hz
220V 60Hz
FM
unit earth
screw
Closed end
connector
WHI
RC
2
4
6
CN304
(GRY)
CN309
(YEL)
AC IN
CN066
(WHI)
BLU
121
343
565
CN301
(BLK)
Heater
1
2
3
1
2
3
TR
Line Filter
1
Outdoor
unit
1
2
3
1
2
3
1
2
3
1
2
U2U
CN067
(BLK)
CN044
(BRW)
1 2
1 2
BLU
U
1
BLU
RY004
Fuse
T5.0A
CN040
(BLU)
1 2
1 2
BLU
BLK
BLU
U
2
1 2
1 2
Remote controller
BLK
BA
CN1
(WHI)
CN041
1 2 3
13
FAN
CN083
(BLU)
YX
AI-NET
central control
terminal
(WHI)
BLK
RED
9 8 7 6
9 8 7 6
HML UL
RY007
CN050
(WHI)
1 2 3 4 5
MCC-1401
CN01
(WHI)
1 1
Network
2 2
adaptor
CN03
P.C. board
(RED)
ORN
5 4 3 2 1
5 4 3 2 1
RY006
RY005
Network
1 2
adaptor
(Option)
1 2
2 1
2331
DM
1 2 3
1 2 3
YEL
BLU
RY002
1 2 3
1 2 3
CN068
DP
(BLU)
RY001
LM
2 1
2 1
1 2 3
1 2 3
LM
(GRN)
CN033
Indoor control P.C. board
Power supply
circuit
4 5 6
CN075
(WHI)
CN02
(YEL)
CN01
(WHI)
TR
CN074
(WHI)
1 2 3
1 2 3
1 2 3
1 2 3 4 5 6
1 2 3 4 5 6
Sub P.C. board
MCC-1520
1 2 3 4 5 6
1 2 3 4 5 6
CN02
(BLU)
1. indicates the terminal block, letter at inside
indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
2 1
2 1
1 2 3
1 2 3
1 2 3 4 5 61 2 3 4 5 6
FS
CN061
(YEL)
FS
(RED)
CN030
6 4 3
6 4 3
1 2 3
1 2 3
CN032
(WHI)
1 2
Fan drive
Symbol
FM
RC
TR
LM
TA
TC1,TCJ
RY001
RY002
RY004
RY005~007
FS
DM
PMV
PMV
1 2 5
1 2 5
4 5 6
4 5 6
CN082
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRW)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
CN060
(WHI)
1 2 3 4 5 6
Option
Fan motor
Running capacitor
Power transformer
Louver motor
Indoor temp sensor
Temp sensor
Louver motor control relay
Drain pump control relay
Heater control relay
Fan motor control relay
Float switch
Drain pump motor
Pulse Motor Valve
PMV
(BLU)
121
2
121
2
TCJ
1
2
121
2
33
1
PNL
2
3
1
EXCT
2
1
1
Filter
2
2
1
2
3
4
5
Parts name
TA
TC1
2-1-4. 1-way Air Discharge Cassette Type
Model: MMU-AP0152SH, AP0182SH, AP0242SH
21
Indoor unit
earth screw
S(N)R(L)
Power supply
single phase
220-240V 50Hz
220V 60Hz
FM
TA
TC1
TCJ
TC2
LM
DM
FS
RY302
PMV
TR
Flow selector unit
earth screw
RED
WHI
Closed-end
connector
U
U
1
Outdoor
unit
Symbol
1
2
U2U
Fan motor
Indoor temp sensor
Temp sensor
Temp sensor
Temp sensor
Louver motor
Drain pump motor
Float switsh
Drain control relay
Pulse motor valve
Transformer
BA
A B
Wired
remote
controller
Parts name
WHI
WHI
2
112
CN001(WHI)
Adapter for
wireless remote
controller
BLK
BLK
Color
indication
RED: RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY: GRAY
PNK: PINK
ORN: ORANGE
BRN: BRWN
GRN: GREEN
TR
131
2
3
MCC-1401
AI-NET
Network adapter
CN02
(BLU)
(Option)
RED
WHI
112
CN01
(WHI)
CN03
(RED)
112
X Y
PMV
FM
5
5
CN82
(BLU)
6
CN112
Power
supply
circuit
Control P.C. board
CN32
(WHI)
Fan
drive
High ceiling setup
1 2
1 21 21 2
CN111
(WHI)
(WHI)
DC20V
DC15V
DC12V
DC7V
for indoor unit
MCC-1402
CN60
(WHI)
1 2 3 4 5 6
Option
CN110
(WHI)
1 2 3 4 5
1
2
3
4
6
1
2
3
4
6
CN334
5 41
(WHI)
313
1
3
1
T6.3A 250V~
3
1
2
2
2
131
2
3
RY302
RY303
P301
CN66
(WHI)
CN40
(BLU)
CN41
(BLU)
Fuse
5
1
3
1
3
CN68
(BLU)
1
DM
CN304
(GRY)
1
CN67
(BLK)
3
BLK
BLU
1
1
2
2
BLU
BLK
BLK
CN309
(YEL)
1
1
Motor drive
CN50
(WHI)
1 2 3 4 5
CN333
1 2 3 4 5 6
5
3
(WHI)
1
2
3
4
54 3
32 1
5
circuit
Fuse
T3.15A
250V~
CN061
(YEL)
1 21 23 4 5 61 2 3 4 5
T10GRL
1. indicates the terminal bolock letter.
Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the
wiring at side
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
RED
WHI
Closed
end
connector
Indoor unit
Earth screw
S(N)R(L)
Power supply
Single phase
220-240V 50Hz
220V 60Hz
(BLK)
CN304
(GRY)
1
2
3
1
2
3
TR
Flow selector
unit earth
screw
T10A,250V~
Closed end
connector
Surge
absorber
87
43F1
FAN
CN083
(WHI)
P301
1
RY004
2
3
1
CN309
2
(YEL)
3
CN067
(BLK)
1
2
3
1
2
YEL
CN066
(WHI)
CN044
(BRW)
EMG
U2U
1
Outdoor unit
REDREDF
RED
6
43F1
4
Fuse
T5.0A
CN040
(BLU)
1 21 2
1 2
OC
U
1
WHI
1 2 3 4
RC
U
2
Remote controller
5
43F1
3
RED
GRY
1 2 3 4
WHI
RED
REDWHI
CN041
(BLU)
1 2 3
13
1 2
1 2
GRY
9 8 7 6
9 8 7 6
RY007
BA
5 4 3 2 1
HML UL
RY006
CN01
(WHI)
3 3
2
1 1
CN1
CN02
(WHI)
(BLU)
WHI
RC
FM
42
RY002
RY005
CN050
(WHI)
1 2 3 4 5
Network adaptor
(Option)
MCC-1401
1 2
1 2
CN03
1 2
(RED)
1 2
X Y
A
F1F2F3F
BLU
ORN
BLK
(Option)
DM
1 2 3
1 2 3
DP
(BLU)
CN068
RY001
1 2 3
1 2 3
LM
(GRN)
CN033
1 2 3
1 2 3
FS
CN030
(RED)
TA
1 2
1 2
CN104
(YEL)
Indoor control P.C. board
Power
supply
circuit
CN074
(WHI)
1 2 3
1 2 3
1 2 3
4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
Sub P.C. board
MCC-1520
1 2 3 4 5 6
1 2 3 4 5 6
1. indicates the terminal block, letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
4. When attaching a drain pump, exchange CN030 connector with the connector
of the float switch.
5. A part is connected to the terminal block.
When exchanging to the outside static pressure necessary at the local site,
check the terminal No. and lead color of the fan motor in the below diagram,
and then exchange the lead wire indicated by the arrow mark ( ).
4
BRN
Wired for MMD-AP0481 only
(BRN Wire)
Motor over heating protection switch
CN075
BLK
WHI
GRY
RED
(WHI)
1 2 3 4 5 61 2 3 4 5 6
T10
CN02
(YEL)
CN01
(WHI)
TR
CN061
(YEL)
49F
TCJ
1 2
1 2
CN102
(RED)
CN032
(WHI)
1 2
Fan drive
BLU
ORN
BRN
CN060
(WHI)
TC1
1 2 3
1 2 3
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
CN082
(BLU)
TC2
1 2
1 2
CN101
(BLK)
1 2 3 4 5 6
Option
Sold
separately
CN100
(BRN)
1
2
PNL
3
1
EXCT
2
1
Filter
2
1
2
3
4
5
6
6
5
5
4
4
3
3
2
2
1
1
Symbol
FM
RC
TR
TA
TC1,TC2,TCJ
RY005~007
RY001
RY002
PMV
F
43F1
DM
FS
5
5
2
2
1
1
PMV
3
3
4
4
6
6
Parts name
Fan motor
Running capacitor
Transformer
Indoor temp sensor
Temp sensor
Fan motor control relay
Louver motor control relay
Drain control relay
Pulse Motor Valve
Fuse
Fan motor control relay
Drain pump motor
Float switch
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
Symbol
FM
RC
TR
TA
TC1,TC2,TCJ
RY001
RY002
RY004
RY005~007
PMV
Parts name
Fan motor
Running capacitor
Transformer
Indoor temp sensor
Temp sensor
Louver control relay
Drain control relay
Heater control relay
Fan motor control relay
Pulse motor valve
28
Indoor unit
earth screw
RED
WHI
RED
R(L) S(N)
Power supply
single phase
220-240V 50Hz
220V 60Hz
Flow selector
unit earth
screw
Closed-end
connector
WHI
WHI
1
GRN
1
3
3
2
2
4
4
FM
5
5
6
6
RED
RED BLK ORN BLU YEL
FAN
CN083
(WHI)
95 3 1
RC
GRN
FM
RED
5 3 1779
WHI
For AP0071BH,AP0091BH,AP0121BH
R301
(BLK)
1
3
1
313
AC IN
1
T5.0A 250V~
313
1
CN066
(WHI)
2
1
CN044
(BRW)
2
EMG
2
112
Network
adaptor
3
2
112
CN01(WHI)
CN02
(BLU)
CN03(RED)
MCC-1401
2
(Option)
1 1
2 2
CN03
(RED)
TR
U1 U2
U1 U2
Outdoor unit
A BX Y
2
112
CN1
Remote controller
3
1 1
1. indicates the terminal block.
Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at side.
3. indicates the control P.C. board.
(GRY)
CN304
(YEL)
CN309
FUSE
(BLK)
CN067
RC
RY004
CN040
(BLU)
112
2
2
424
5
5
6
6
3
3
RED BLK ORN BLU YEL
FAN
CN083
(WHI)
CN041
(BLU)
1 2331 2 3 4 5
1
5 3 1779
95 3 1
M LUL
H
RY007
RY006
CN050
Color
indication
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
RY005
(WHI)
CN068
(BLU)
RY002
CN074
(WHI)
133
1
113
3
3
CN033
(GRN)
113
RY001
Control P.C. board
for undoor unit
Power supply
circuit
CN075
MCC-1520
(WHI)
CN02
(YEL)
CN01
(WHI)
TR
1 2 3 4 5 6 1 21 23 4 5 61 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
Sub P.C. boar d
1 2 3 4 5 6
1 2 3 4 5 6
MCC-1403
CN061
(YEL)
112 3
CN030
(RED)
Symbol
FM
RC
TR
TA
TC1,TC2,TCJ
RY001
RY002
RY004
RY005~007
PMV
PMV
1 23456
1 23456
3
CN032
(WHI)
Fan
drive
1 2 3 4 5 6
1 2 3 4 5 6
CN082
(BLU)
CN060
(WHI)
Option
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRW)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
PMV
1
212
1
212
1
1
2
2
131
2
3
1
2
3
1
2
1
2
1
2
3
4
5
Parts name
Fan motor
Running capacitor
Transformer
Indoor temp sensor
Temp sensor
Louver control relay
Drain control relay
Heater control reley
Fan motor control relay
Pulse motor valve
1. indicates the terminal block, letter.
Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate
the wiring at side.
3. indicates the control P.C. board.
3
CN030
112 3
MCC-1403
CN061
(YEL)
(RED)
CN032
(WHI)
Fan
drive
PMV
1 23456
1 23456
1 2 3 4 5 6
1 2 3 4 5 6
CN060
(WHI)
Option
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
CN100
(BRW)
CN080
(GRN)
CN073
(RED)
CN070
(WHI)
CN081
(BLK)
CN082
Symbol
FM
RC
TR
LM
TA
TC1,TC2,TCJ
RY001
RY002
RY005~007
PMV
PMV
(BLU)
TA
1
212
TCJ
1
212
TC2
1
1
2
2
131
1
2
3
1
2
1
2
1
2
3
4
5
TC1
3
PNL
EXCT
Filter
Fan motor
Running capacitor
Transformer
Louver motor
Indoor temp sensor
Temp sensor
Louver control relay
Drain control relay
Fan motor control relay
Pulse motor valve
Color
indication
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
Compressor
Pulse motor valve
2-way valve coil
4-way valve coil
Compressor case thermo.
Pipe temp. sensor (Suction)
Pipe temp. sensor (Discharge)
Heat exchange temp. sensor
Air temp. sensor
Liquid temp. sensor
Compressor case heater
Accumlator case heater
Fan motor (DC)
Low pressure sensor
High pressure sensor
High pressure switch
PMV
CN300
(WHI)
RY502
RY504
RY506
RY516
RY517
RY518
(L)
Pressure
sensor
PS
CN500
(WHI)
Pressure
sensor
PD
CN501
(RED)
Option
board
CN508
(RED)
Option
board
CN509
(BLK)
Option
board
CN510
(WHI)
Option
board
CN513
(BLU)
Interface Control P.C. Board
MCC-1429
ON
34
2
1
SW11
ON
2
34
1
SW07
SW32
CR521
1 33 1211357
CN305
(RED)
4WV1
(Service)
1
2
3
4
5
6
CN800
SWRT
1
1
1
1
2
2
2
2
2
CN802
FLASH
ON
1
SW30
CN317
(BLU)
ON
1
2
SW06
SW31
RY521
(Notes)
1. The two-dot chain line indicates wiring at the local site,
and the dashed line indicates accessories sold separately
and service cables, respectively.
2. , , and indicate the terminal blocks and the numerals
indicate the terminal numbers.
3. indicates P.C. board.
4. This relay connector is not connected at shipment from the factory.
ON
2
34
2
1
SW12
34
SW04
SW13
ON
ONOFF
1
SW08
SW15
SW05
D602
D601D600D603 D604
SW02
SW01SW03
Comp.
thermo.
34
2
SW09
13
34
ON
1
T6.3A
Fuse
CN400
(WHI)
2
SW14
ON
1
Option
board
CN512
(BLU)
ON
12
SW30
34
2
SW10
34
314
2-2. Outdoor Unit
Model: MCY-MAP0401HT, HTZ, HTZG,
+
Capacitor
CN22
(BLU)
(BLU)
WHI
RED
BLK
–
MCY-MAP0501HT, HTZ, HTZG,
MCY-MAP0601HT, HTZ, HTZG,
MCY-MAP0401HT2D, HT2DZ, HT2DZG,
MCY-MAP0501HT2D, HT2DZ, HT2DZG,
MCY-MAP0601HT2D, HT2DZ, HT2DZG
CN21CN20
5 5
4 4
CN300
3
(WHI)
2
1 1
3 3
CN301
2 2
(WHI)
FM 1
1 1
Reactor
NBNB
NANA
LBLB
LALA
2nd revised : Sep. 2006
1 2 3 4 5
CN502 (WHI)
CN600
313
(WHI)
41 3
CN325
(YEL)
CN504
(WHI)
CN505
(GRN)
CN507
(YEL)
CN521
(WHI)
CN511
(GRN)
CN100
(BLK)
indication
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BRWN
GRN : GREEN
1
(RED)
212
1
(GRY)
212
1
(BLU)
212
1
(BLK)
212
1
(WHI)
434
3
2 2
1 1
BLU
3 3
BLU
1 1
Transformer
CN402
WHI
CN401
Color
TD1
TS1
TE1
TO
TL
Option
board
RED
HP SW
CM
FM 2
Power supply
* HT2K series 220V
RED
WHI
BLK
RED
WHI
NL
NL
3 3
1 1
5 5
1 1
5 5
1 1
3 3
1 1
5 5
4 4
1 1
3 3
2 2
1 1
7 7
5 5
3 3
1 1
T02 CT
CN500
(GRN)
CN13
(RED)
CN09
CN10
CN11
CN01
(RED)
CN02
(BLK)
CN302
3
(WHI)
2
CN303
(WHI)
CN08
(WHI)
CN01
CN02
Earth screw
~
60Hz
1 2 3 4 5
CN06
(WHI)
CN02
CN01
Comp. IPDU P.C. Board
MCC-1535
CN04
(WHI)
1 31 21 2 3 4 5
1 311 2 3 4 5
1 31
1 31 2
CN03
CN04
(WHI)
(WHI)
Fan IPDU P.C. Board
MCC-1531
Noise Filter
P.C. Board
MCC-1551
CN05
(WHI)
YELBLU
1 2 3 4 5
1 2 3 4 5
CN804
CN04
CN03
P01
2-3. Connection of PMV Kit
Model: RBM-PMV0361E, RBM-PMV0901E
1st revised : Jun. 2006
Indoor unit
PMV lead wires
PMV Kit
Connection cable
CN82 connector
Indoor control P.C. board
Connector conversion cable *1
*1: MMK-AP✻✻✻2H (High Wall Type) does not use a this conversion cable.
Pulse motor valve (PMV)
(Indoor unit side)
PMV
32
3.PARTS RATING
3-1. Indoor Unit
4-way Air Discharge Cassette Type
ModelMMU-AP0091H0121H0151H0181H0241H0271H0301H
Fan motorSWF-230-60-1
Drain pump motorADP-1409
Float switchFS-0218-102
TA sensorLead wire length : 155mm
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B25YGTFEDM-B40YGTF
Louver motor (panel)MP24GA
ModelMMU-AP0361H0481H
Fan motorSWF-200-90-1
Drain pump motorADP-1409
Float switchFS-0218-102
TA sensorLead wire length : 155mm
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM - B6 0YGTF- 1
Louver motor (panel)MP24GA
Compact 4-way Air Discharge Cassette Type
ModelMMU-AP0071MH0091MH0121MH0151MH0181MH
Fan motorSWF-230-60-1
Drain pump motorADP-1409
Float switchFS-0218-102
TA sensorLead wire length : 155mm
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B25YGTFEDM-B40YG TF
Louver motor (panel)MP24GA
33
2-way Air Discharge Cassette Type
ModelMMU-AP0071WH0091WH0121WH0151WH0181WH
Fan motorAF-230-53-4GAF-230-39-4B
Running capacitor for fan motorAC 400V, 1.0µFAC 450V, 2.0µF
Drain pump motorPJD-05230TF-1
Float switchFS-0208-608
Control P.C. board transformerTT-13
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B25YGTFEDM-B40YGTF
TA sensorLead wire length : 268mm
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
ModelMMU-AP0241WH0271WH0301WH
Fan motorAF-200-53-4F
Running capacitor for fan motorAC 450V, 2.5µFAC 450V, 3.5µF
Drain pump motorPJD-05230TF-1
Float switchFS-0208-608
Control P.C. board transformerTT-13
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B40YGTF
TA sensorLead wire length : 268mm
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
1-way Air Discharge Cassette (Compact type) Type
ModelMMU-AP0071YH0091YH0121YH
Fan motorAF-200-22-4N-1
Running capacitor for fan motorAC 400V, 1µF
Drain pump motorPJD-05230TF-1
Float switchFS-0208-602
Control P.C. board transformerTT-13
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B25YGTF
TA sensorLead wire length : 818mm
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
ModelMMU-AP0152SH0182SH0242SH
Fan motorSWF-280-60-1
Running capacitor for fan motor—
Drain pump motorADP-1409
Float switchFS-0218-103
Control P.C. board transformer—
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B40YGTF-3
TA sensorLead wire length : 155mm Vinyl tube
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
34
Concealed Duct Standard Type
ModelMMD-AP0071BH0091BH0121BH0151BH0181BH
Fan motorICF-280-120-2
Drain pump motorADP-1409
Float switchFS-0218-102
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B25YGTFEDM-B40YGTF
TA sensorLead wire length : 618mm
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 s i ze l ead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
ModelMMD-AP0241BH0271BH0301BH0361BH0481BH
Fan motorICF-280-120-1ICF-280-120-2
Drain pump motorADP-1409
Float switchFS-0218-102
Pulse motorEDM-MD12TF-3
Pulse motor valveED M - B4 0YGTFEDM - B60 YGTF-1
TA sensorLead wire length : 618mm
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 s i ze l ead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 size lead wire length : 1200mm Vinyl tube (Red)
Concealed Duct High Static Pressure Type
ModelMMD-AP0181H0241H0271H0361H0481H
Fan motorSTF-200-160-4BSTF-200-160-4ASTF-200-260-4CSTF-200-260-4B
Running capacitor for fan motorAC 500V, 4µFAC 400V, 8µFAC 450V, 6µFAC 400V, 8µF
Drain pump motorADP-1409
Float switchFS-0218-102-6
Pulse motorEDM-MD12TF-3
Pulse motor valveEDM-B40YGTFEDM-B60YGTF-1
TA sensorLead wire length : 1200mm
TC1 sensorØ4 size lead wire length : 1200mm Vinyl tube (Blue)
TC2 sensorØ6 size lead wire length : 1200mm Vinyl tube (Black)
TCJ sensorØ6 si ze lead wire length : 1200mm Vinyl tube (Red)
Hot air is discharged when cooling operation is performed.
Cold air is discharged when heating operation is performed.
Power source hole
Refrigerant pipe
connecting hole
2-way discharge/3-way discharge
2-way discharge or 3-way discharge can be
selected according to the shape or
arrangement of the room.
For details, consult with the dealer which you
have purchased the air conditioner.
Air filter
Removes dust and trash.
(Air filter is provided in the air grille.)
Air inlet grille
Air in the room is sucked from here.
Air outlet/Air outlet louver
Select air blow direction in cooling or
heating operation each.
Connecting valve is
included inside here.
Sold Separately Parts
TEST
TIMER SET
UNIT No.
R.C. No.
CODE No.
ON / OFF
FAN
MODE
SWING/FIXTIME
VENT
UNITSET CL
˚C
RBC-AMT31E
FILTER
RESET
Wired remote controller
RBC-AS21E2
Simple wired remote controller
DATA
SET
SETTING
H
TEMP.
TEST
TEST
SETTING
PROGRAM1
PROGRAM2
PROGRAM3
WEEKLY TIMER
Weekly timer
RBC-EXW21E2
ZONE
ALL
ZONE
GROUP
1234
SET DATA
SETTING
R.C.
SELECT ZONE
TCB-SC642TLE2
Central remote controller
SuMoTuWeThFr Sa
ERROR
CODE
No.
TEST
UNIT No.
No.
GROUP
SET
CL
Clip
The clip is to open/close the
air inlet grille.
[2-way Air Discharge Cassette Type]
Earth screw
It is included in the electric parts box.
Center panel
Air inlet
Air in the room is
sucked from here.
Air filter
Removes dust and trash.
(Air filter is provided in the air grille.)
Air inlet grille
Air in the room is sucked from here.
Air outlet/Air outlet louver
Select air blow direction in cooling or
heating operation each.
Air filter
Removes dust and trash.
(Air filter is provided in the center panel.)
Wireless remote controller kit
TCB-AX21E2RBC-AX22CE2 RBC-AX21U(W)-E2
[Under Ceiling Type]
2
15
5
78 9
3
1
4
6
10
11
13
16
12
14
17
CODE No.
UNIT No.
TEST
SETTING
DATA
SET
R.C. No.
H
MODE
Button
Button to open/close the suction port
Air filter
Removes dust or trash.
(Provided on the suction port.)
[High Wall T ype]
MMK-AP0071H to AP0241H
Air inlet grille
Air in the room is sucked from here.
Air filter
Removes dust and trash.
(Air filter is provided in the air inlet grille.)
MMK-AP0072H to AP0122H
Air inlet grille
Air in the room is sucked from here.
Air filter
Removes dust and trash.
(Air filter is provided in the air inlet grille.)
Air inlet port
The air in the room is sucked in from this
port.
Earth screw
Earth screws are provided in the electric
Air outlet/Air outlet louver
Change the direction of the air to be discharged according to cool/heat mode.
parts box.
Earth screw
Earth screws are provided in the electric
parts box.
Air outlet/Air outlet louver
Change the direction of the air to be
discharged according to cool/heat mode.
Air outlet/Air outlet louver
Change the direction of the air to be
discharged according to cool/heat mode.
Earth screw
Earth screws are provided in the electric
parts box.
3-7. Parts Name of Remote Controller
Display section
In the display example, all indicators are displayed for the explanation.
In reality only, the selected contents are displayed.
• When turning on the leak breaker for the first time, [SET DATA] flashes on
the display part of the remote controller. While this display is flashing, the
model is being automatically confirmed. After the [SET DATA] display has
disappeared, you may use the remote controller.
TEST
TIMER SET
UNIT No.
R.C. No.
CODE No.
Display
section
ON / OFF
FAN
MODE
SWING/FIXTIME
UNITSET CL
Operation
VENT
section
DATA
SET
SETTING
H
TEMP.
FILTER
TEST
RESET
40
[Floor Standing Cabinet Type]
Air filter
Removes dirt or dust.
(It is included in the suction port.)
[Floor Standing Concealed Type]
Earth screw
It is prepared in the electric parts box.
Air inlet port
Sucks air inside of the room from here.
Front panel (Lower side)
[Floor Standing Type]
Horizontal louver/Air outlet port
Exchanges the air direction according
to cooling or heating time.
Air inlet port
Sucks air inside of the room from here.
Air filter
Removes dirt or dust.
Earth screw
It is prepared in the electric parts box.
Air outlet/Air outlet louver
Exchanges the air direction according to
cooling or heating time.
Earth screw
It is prepared in the electric parts box.
Air inlet port
Sucks air inside of the room from here.
Air outlet port
Drain pan (With drain filter)
This accessory is installed at the local site.
Air filter
Removes dirt or dust.
(It is included in the suction port.)
Fixing metal holder
Vertical louver
The air can be automatically discharged
rightward/leftward at stated periods.
Drain pan
Water accumulated in the drain pan is
drained from here through the drain pipe.
Fixing metal holder (Right and left)
1 SET DA TA display
Displayed during the setup of the timer.
2 Operation mode select display
The selected operation mode is displayed.
3 CHECK display
Displayed while the protective device works or
a fault/error occurs.
4 Timer time display
Time on the timer is displayed.
(When a fault/error occurs, the check code is
displayed.)
5 Timer setting setup display
When pushing the Timer setting button, the
display on the timer is selected in order of
[OFF] → [OFF] repeat OFF timer →
[ON]
→ No display.
6 Filter display
If “FIL TER ” is displayed, clean the air filter.
7 TEST run display
Displayed during a test run.
8 Flap position display
(for 4-Wa y Air Discharge Cassette Type
and Under Ceiling Type model only)
Displays louver position.
9 SWING display
Displayed during the up/down movement of the
flap.
10Set up temperature display
The selected set up temp. is displayed.
11Remote controller sensor display
Displayed while the sensor on the remote
controller is used.
12PRE-HEAT display
(for Heat-pump model only)
Displayed when the heating operation starts or a
defrost operation is carried out.
While this indication is displayed, the indoor f an
will stop or will go into LOW mode.
13Operation ready display
Displayed when cooling or heating operation is
impossible because the outdoor temperature goes
out of the operable range.
14No function display
Displayed if there is no function even when the
button is pushed.
15Air volume select display
The selected air volume mode is displayed.
(AUTO)
(MED.)(LOW)
In the Concealed Duct High Static Pressure type
models, [HIGH] only is displayed for the air speed.
(HIGH)
16Mode select control display
Displayed when pushing the “Operation mode
select
in heating or cooling mode by the system manager
of the air conditioner.
” button while the operation mode is fixed
17Central control display
Displayed when using the remote controller together
with a central control remote controller.
If the Remote controller is prohibited at the central
control side,
ON / OFF
The change will not be accepted.
(The contents available to be set up on the remote
controller differ according to the central control
mode. For details, refer to Owner’s Manual of the
central control remote controller.)
flashes when operating the
,
, / buttons.
Operation section
1
3
2
4
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
HEATDRYCOOLFAN
Heat-pump model
DRYCOOLFAN
Cooling only model
(Dehumidity)
LOW MED. HIGH
AUTO
Push each button to select a desired operation.
This remote controller can operate a maximum of 8 indoor units.
• Before the unit can begin operation, it is firstly necessary to set the units operating parameters.
After this has been completed the air conditioner can be used by pushing the
1 Air volume select button
2 Timer set button
41
3 Check button
4 Fan
5 Filter reset button
6 Air flow direction and Swing function
1
TEMP.
10
TIMER SET
2
FILTER
TEST
RESET
5
3
Selects the desired air volume mode.
F or the Concealed Duct High Static Pressure
type models this function is unavailable.
The TIMER SET button is used when the timer is
set up.
The CHECK button is used to check the units
operation.
During normal operation, do not use this button.
VENT
button
VENT
The
sold on the market is connected.
• If
Resets (Erases) the “F ILTER ” display.
If there are multiple indoor units that are controlled by a single remote controller, simply select
each unit in turn for which you wish to adjust the
air flow direction.
SWING/FIX
Set up the auto swing and the angle of the
louver.
• This function is not provided on the Concealed
button is used when a fan which is
is displayed on the remote controller
when pushing the
connected.
UNIT
:
:
Duct Standard Type, High Static Pressure Type,
F loor standing Cabinet Type, F loor Standing
Concealed Type, or Slim Duct Type.
VENT
button, a fan is not
ON / OFF
button only.
7
ON / OFF
8
FAN
SWING/FIXTIME
UNITSET CL
MODE
VENT
9
4
6
7 Operation lamp
The light will be ON when the unit is in operation and OF F when the unit is not being used.
Note) The light will flash if a protective device
has been operated or if the timer function has
an error.
ON / OFF
8
9 Operation select button
10Set up temperature button
OPTION :
Remote controller sensor
In normal installations the temperature of the room
is sensed by a temperature sensor on the indoor
unit. However it is possible to have the sensor
within your remote controller. F or further details
please contact your local dealer.
• In cases where one remote controller controls the
multiple indoor units, the setup operation is
unavailable in group control.
button
When the button is pushed, the operation
starts. If the button is pressed again, the unit
operation will stop.
When the unit operation has stopped, the
operation lamp and all of the displays will
disappear.
Selects the desired operation mode.
Adjusts the room temperature.
Set the desired set temperature by pushing
or buttons.
the
3-8. Correct Usage
When you use the air conditioner for the first time or when you change the SET DATA value, follow the procedure shown below . F or consequent uses the display on the remote controller can be turned on by pushing the
ON / OFF
button only.
Preparation
Turn on the main power supply and/or the leakage breaker.
• When the power supply is turned on, a partition line is shown on the display part of the remote controller.
Note) When the power supply is turned on, the remote controller will not accept any operational inputs until
approximately 1 minute has passed. This is not a failure of the unit.
REQUIREMENT
• While using the air conditioner, only operate it with the
power switch or the leakage breaker.
• Do not turn off the leakage breaker while the air conditioner is in use.
• Turn on the leakage breaker 12 hours or more before the air conditioner is to begin operation or if the
system has not been in use for long periods of time.
1 Push the
The operation lamp goes on, and the operation will start.
2 Select an operation mode with the
One push of the button, and the display
changes in the order shown on the right.
•“DRY
Concealed Duct High Static Pressure Type.
3 Select the air volume with the
One push of the button, and the display
changes in the order shown on the right.
• When the air volume is set to “AUTO
ture.
• In DRY
• In heating operation, if the room temperature is not heated sufficiently with the air volume set at “LOW
• The temperature sensor for the indoor unit is located near to the air inlet opening and therefore will
differ slightly from the actual room temperature. This difference may be increased/decreased depending
on the type of room and its design. (A utomatic air speed cannot be selected in F AN mode.)
• The Air V olume function is not provided on the “Concealed Duct High Static Pressure Type” instead the
air speed “HIGH
ON / OFF
button.
MODE
button.
mode” function is not provided on the
FAN
button.
”, the air volume will differ according to the room tempera-
mode, the “AUTO ” symbol will be displayed and the air volume will be LOW.
” operation, select the “MED. ” or “HIGH ” operation.
” symbol is displayed.
ON / OFF
button. Do not turn it off with the main
4 Determine the set up temperature by pushing the “TEMP. ” or “TEMP. ” button.
Stop
Push the
The operation lamp goes off and the unit will stop.
ON / OFF
button.
[In Cooling operation]
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
In FAN operation
1, 2, 34
In all modes
Display when stopping the swing
Initial setup
Series of
operation
Fan/Heat
operation
Cool/Dry
operation
Unit No. 1-1No displayUnit No. 1-2
Unit No. 1-4Unit No. 1-3
UNIT
• The operation will start after approximately 1 minute.
[In Heating operation (For Heat-pump model only)]
• In heating operation, the fan operation may continue for approximately 30 seconds after the air conditioner has stopped.
• The indoor fan will continue the preheat operation for 3 to 5 minutes under stop conditions. The indoor
unit will then begin to blow out hot air.
(
symbol on the remote controller display will come on.)
• When the temperature of the room has reached the setup temperature and the outdoor unit stops, the
air speed reduces and so the air volume will decrease.
• In HEAT
the air flow / volume will decrease.
• In the defrost mode, the fan will stop so that cool air is not discharged and the PRE-DEF
mode, if the room temperature reaches the set temperature, the outdoor unit will stop and
3-9. Adjustment of Wind Direction
To increase the cooling or heating effect, be sure to use the discharge louver in different directions when in cooling or heating operation.
The characteristics of air are such that cold air will accumulate in the lower half of the room, while hot air will
accumulate in the upper half.
42
Set the louver horizontally in cooling operation.
If a cooling operation is performed with a downwards discharge, the surface of the discharge port or
louver will become wet with dew, and water may drip down.
• If a heating operation is performed with a horizontal discharge, unevenness the room temperature may
not be equal i.e. there may be a large variance between one side of the room with the other.
4-way Air Discharge Cassette Type
• When the air conditioner is not in operation, the discharge louver will automatically directs downwards.
• When the air conditioner is in ready status for heating,
the discharge louver will be directed upwards.
The swinging operation will begin after heating ready
status has been cleared. Please note the “SWING
symbol will still be displayed on the remote controller
even when the unit status is ready to begin the heating operation.
[In Cooling operation]
Use the discharge louver with a horizontal set point.
[In Heating operation (For Heat-pump model only)]
Use the discharge louver with a downwards set point.
REQUIREMENT
CAUTION
REQUIREMENT
”
is displayed.
How to set up the air direction
SWING/FIX
Push
button.
1 Every pushing the button, the air direction changes.
In Heating operation
Set the air outlet louver downward.
If directing it upward, the hot air may not come to the foot.
In Cooling / Dry operation
Set the air outlet louver Upwards.
If directing it downwards, the dew may form on the near side of the air discharge
port and could drip.
How to adjust the the air flow direction,
using the swinging function
2 Push the
Set the direction of the air outlet louver to
the lowest position and then push the
SWING/FIX
• [SWING ] is displayed and the air flow
How to stop the louver from swinging
3 Push the
horizontal louver is moving.
• The horizontal louver can be stopped at any
4
• To set up the air flow direction individually,
• If there is no display, all the indoor units can be
• F or every push of the
SWING/FIX
button.
button again.
direction will automatically change either
upwards/downwards.
In the case where one remote controller
controls multiple indoor units, each indoor unit
can be selected and its air flow direction can
be adjusted.
SWING/FIX
button again while the
position desired. If you wish to return the
louver to it original upwards position, press the
SWING/FIX
button again.
* During the cooling/drying operation the
horizontal louver will not stop at its most
downwards facing position 9 (reduce the risk
of water dripping), but will instead move to
the 3rd position from the top (as shown in the
figure).
UNIT
push the
unit No. in a group control. You can then set the
air flow direction for the display ed indoor unit.
operated collectively.
will alter between units as shown in the figure.
UNIT
button to display each indoor
button, the display
Initial setup
Initial setup
Based on the shape or arrangement of the room, the cold air and hot air can be discharged in two directions
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
In FAN operation
1, 2, 34
In all modes
Display when stopping the swing
Initial setup
Series of
operation
Fan/Heat
operation
Cool/Dry
operation
UNIT
or three directions. F or details, please contact your local dealer.
• If cooling operation is performed with a downwards discharge, dew may form on the surface of the
cabinet or the horizontal louver resulting in dripping.
• If heating operation is performed with a hori zontal discharge, the room temperature may not be equal
i.e. there may be a large variance between one side of the room with the other.
• Do not move the horizontal louver directly with your hands; otherwise a fault maybe caused.
Select the direction of the horizontal louver using the louver operation switch on the remote controller.
The horizontal louver will not stop immediately, even if the switch is pushed.
Note) Pushing the switch again when the required louver direction has been reached will stop the louver.
2-way Air Discharge Cassette Type
[In Cooling operation]
Use the air outlet louver with a horizontal set point.
[In Heating operation (For Heat-pump model only)]
Use the air outlet louver with a downwards set point.
Setup of air flow direction and swinging function
1 Push the
• [SWING ] is displayed and the air flo w direction will automatically change either upwards/do wnwards .
In the case of one remote controller that controls multiple indoor units, each indoor unit can be selected
and its air flow direction can be adjusted.
43
2 Push the
the air outlet louver.
• The air outlet louver will be stopped at the desired position.
UNIT
3
• To set up the air flow direction individually, push the
button to display each indoor unit No. in a group control.
You can then set the air flow direction for the displayed
indoor unit.
• If there is no display, all the indoor units can be operated
collectively.
• F or every push of the
between units, as shown in the figure.
1-way Air Discharge Cassette Type
Adjustment of air flow direction upwards/downwar ds
[In Cooling operation]
In cooling operation, use the air outlet louver with a horizontal set
point so that the cold air diffuses the whole room.
[In Heating operation (For Heat-pump model only)]
In heating operation, use the air outlet louver with a downwards set
point so that the hot air is directed towards the floor.
Adjustment of air flow direction rightwards/
leftwards
To change the discharge direction to right or left side, set the
vertical grille inside of the air outlet louver to the desired direction.
Setup the air flow direction and swinging function
Refer to the description of the “2-way Air Discharge Cassette Type”.
INFORMATION
SWING/FIX
button during operation.
SWING/FIX
button again during the swinging of
UNIT
button, the display alters
UNIT
TEMP.
FAN
SWING/FIXTIME
UNITSET CL
FILTER
RESET
TIMER SET
TEST
1, 23
Unit No. 1-1No displayUnit No. 1-2
Unit No. 1-4Unit No. 1-3
ON / OFF
MODE
VENT
Under Ceiling Type
• While the air conditioner is not in operation, the horizontal louver (Up/Down air direction
adjustment plate) will automatically point upwards.
• When the air conditioner is in ready status for heating, the horizontal louver (Up/Down air
direction adjustment plate) will points upwards. The swinging operation will begin after the
heating ready status has been cleared. Please note the “SWING
” symbol will still be dis-
played on the remote controller even when the status is ready to heat.
How to adjust the air flow direction
SWING/FIX
Push the
button during operation.
1 Every time you push the button the air
flow direction will change.
In Heating operation
Set the horizontal louver (Up/Down
air direction adjustment plate)
downwards. If the air flow is directed
upwards, the hot air may not reach
the floor, creating an une ven temperature within the room.
Initial setup
In Cooling / Dry operation
Set the horizontal louver
(Up/Down air direction adjustment plate)
upwards. If directing the air flow
downwards, condensation may
form on the surface of the louver
and may cause water to drip.
Initial setup
How to adjust the air flow direction, using the
swinging function
2 Push the
Set the direction of the horizontal louver
(Up/Down air direction adjustment plate) to its
lowest position and then push the
again.
• [SWING ] is displayed and the air direction will
How to stop the louver from swinging
3 Push the
louver is moving
• The horizontal louver can be stopped at any position
4
• To set up the air flow direction individually, push the
• If there is no display, all the indoor units can be
• F or every push of the
SWING/FIX
button.
SWING/FIX
button
automatically upwards or downwards.
In cases where one remote controller controls
multiple indoor units, it is possible to set each
indoor unit individually, so that the air flow direction
can be altered.
SWING/FIX
button again while the horizontal
desired. If you wish to return the louvre to it original
upwards position, press the
SWING/FIX
button again.
* During the cooling/drying operation the horizontal
louver will not stop at its most downwards facing
position 9 (reduce the risk of water dripping), but
will instead move to the 3rd position from the top
(as shown in the figure).
UNIT
UNIT
button to display each indoor unit No. in a
group control. You can then set the air flow direction
for the displayed indoor unit.
operated collectively.
button, the display will
alter between units as shown in the figure.
Unit No. 1-1No displayUnit No. 1-2
Unit No. 1-4Unit No. 1-3
Right/Left air direction adjustment
To change the air outlet direction to the right or left side, set the vertical louver located behind the horizontal
louverp to the desired direction.
INFORMATION
• If cooling operation is performed with a downwards discharge, dew may form on surface of the cabinet or the
horizontal louver resulting in possible dripping.
• If heating operation is performed with a horizontal discharge,
the room temperature may not be equal i.e. there may be a
large variance between one side of the room with the other .
High Wall T ype
Adjustment of air flow direction upwards/downwards
Floor Standing Cabinet Type
[In Cooling operation]
In cooling operation, set the air outlet louver with a horizontal
set point so that the cold air diffuses the whole room.
[In Heating operation (For Heat-pump model only)]
In heating operation, set the air outlet louver with a downwards set point so that the hot air blows towards the floor.
44
[In Cooling operation]
In cooling operation, use the horizontal louver with a horizontal set
point so that the cold air diffuses the whole room.
[In Heating operation (For Heat-pump model only)]
In heating operation, use the horizontal louver with a downwards set
point so that the hot air blows towards the floor.
REQUIREMENT
• If cooling operation is performed with the louver set at a downwards position, dew may form on the surface of the cabinet or the
horizontal louver resulting in possible dripping.
• If heating operation is performed with the louver set in a horizontal position, the room temperature may not be equal i.e. there
may be a large variance between one side of the room with the
other.
• Do not move the horizontal louver directly with your hands;
otherwise a fault/error may be caused. Select the direction of the
horizontal louver using the
The horizontal louver will not stop immediately even if the switch
is pushed.
Note) Pushing the switch again when the required louver direction has been reached will stop the louver.
SWING/FIX
button on the remote controller.
Adjustment of air flow direction rightwards/leftwards
To change the air outlet direction to the right or left side, set the
vertical louver located behind the horizontal louver to the desired
direction.
How to change the air outlet port
Change the air outlet port using the following procedure.
1 Remove the two fixing screws on the air outlet
port. (The fixing screws are reused.)
2 Remove the discharge port, by pushing up on the
rear side, to a point where you can remove it from
the rear clip.
3 Lift the air outlet port upwards and remove it.
4 Reverse the air outlet port and attach it to the
main unit.
Pay attention so that four claw hooks (two at rear and
two at the lower sides) are hooked on the mounting
position.
5 Be sure to tighten the air outlet port with the
removed fixing screws so that the air outlet port
does not come off.
Setup of air direction and swinging
1H series: Refer to the description of “2-way Air Discharge Cassette
2H series: Refer to the description of “Under Ceiling Type, 1-way Air
Type”.
Discharge Cassette Type (2SH Series)”.
Floor Standing Type
4
3
2
1
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
OFF
(OFF timer)(Repeat OFF timer)
No display
(ON timer)
OFFON
Adjustment of air flow direction upwards/downwards
[In Cooling operation]
In cooling operation, move the louver with your hands so that the horizontal
air outlet points in a direction so that the cold air diffuses the entire room.
[In Heating operation (For Heat-pump model only)]
In heating operation, move the louver with your hands so that the horizontal
air outlet points in a downward direction, towards the floor.
Adjustment of air flow direction rightwards/leftwards
[In case of using unsymmetrical air directions]
Lift up the vertical louver lightly and direct it towards the
desired direction.
Once completed lower the louver back down.
In this case, do not use the Swing function.
2
3-10. Timer Operation
A type of timer operation can be selected from the following three types.
OF F timer: The operation stops when the time on the timer has reached the set time.
Repeat OF F timer : The unit will stop, every time the set time period has elapsed.
ON timer: The unit will start when the time on the timer has reached the set time.
Timer operation
1
45
[In case of automatic swing]
1 Push the
• [SWING ] is displayed and the air direc-
2 Push the
SWING/FIX
button during operation.
tion will automatically change rightwards/
leftwards.
In cases where one remote controller controls
multiple indoor units, it is possible to set each
indoor unit individually, so that the air flow
direction can be altered.
SWING/FIX
button again while the
vertical louver is moving will allow you to
In this case, do not use the
swing function.
TEMP.
TIMER SET
FILTER
TEST
RESET
FAN
SWING/FIXTIME
UNITSET CL
stop the louver in the desired position.
3 Swing button
• To set up the air flow direction individually,
push the
unit No. in a group control. Then set up the air
flow direction to the desired indoor unit.
• If there is no display, all the indoor units can
be operated collectively.
• Every push of the
the display as shown in the figure.
• If cooling operation is performed with downward air outlet, dew may form on the surface of the cabinet
or the horizontal louver, resulting in possible dripping of water.
• If heating operation is performed with the horizontal air outlet actively moving, unevenness of the
temperature may increase in the room.
• Do not move the louver directly with your hands during swing operation; otherwise a fault may be caused.
The vertical louver does not stop immediately even if the
position, push the
UNIT
UNIT
button to display each indoor
UNIT
button, will change
SWING/FIX
button.
INFORMATION
SWING/FIX
1, 23
Unit No. 1-1No displayUnit No. 1-2
Unit No. 1-4Unit No. 1-3
button is pushed. To adjust the stop
ON / OFF
MODE
VENT
1 Push the TIMER SET button.
• The timer display (type) changes for every
push of the button.
• SET DATA and timer time displays flash.
2 Push the
F or every push of the button, the set time increases in the unit of 0.5 hr (30 minutes).
The maximum set time is 72.0 hr.
F or every push of the
The minimum set time is 0.5 hr.
TIME
buttons to select the “SET TIME”.
button, the set time decreases in the unit of 0.5 hr (30 minutes).
3 Push the SET button.
SETTING
•
display disappears and timer time display goes on.
When the ON timer is activated, the chosen time period will be displayed. Once the time has been
reached, all displays except the ON light will disappear.
Cancel of timer operation
4 Push the CL button.
• TIMER display will disappear.
NOTICE
• When the unit stops after the timer reached the preset time, the Repeat OF F timer will resume the
operation. How ever by pushing the
timer has again reached its set time.
ON / OFF
button the repeat function will stop once the time on the
46
4-way Air Discharge
Cassette Type
Under Ceiling TypeSlim Duct Type
2-way Air Discharge
Cassette Type
Concealed Duct
Standard Type
1-way Air Discharge
Cassette Type
Concealed Duct
High Static Pressure Type
NO GOOD
NO GOOD
NO GOOD
NO GOOD
NO GOOD
NO GOODNO GOOD
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
TEST
SETTING
DATA
SET
R.C. No.
H
FILTER display
Notifies the time to clean the air filter.
FILTER reset
Push the FILTER switch after cleaning.
“FILTER” display disappears.
3-11. Installation
Installation location
WARNING
• Select a location for installation that will be able to safely support the weight of the unit.
If the installation location is not strong enough to support the unit and the unit falls, injury could result.
CAUTION
• Do not install the unit in a location where combustible gases could conceivably leak.
Leaking gases that accumulate in the vicinity of the unit could be ignited by the unit.
REQUIREMENT
• A location that permits the level installation of the unit
• A location that provides enough space to service the unit safely
• A location where water draining from the unit will not pose a problem
Avoid the following types of locations :
• Locations where salt is present in large amounts (seaside areas), or where sulfuric gases are present in
large amounts (hot springs areas)
(If the unit is to be used in such areas, special maintenance is necessary.)
• Locations that generate oils (including machine oils), steam, oily smoke, or corrosive gases
• Locations where organic solvents are used
• Locations in the vicinity of equipment that generates high frequency signals
• Locations where the outdoor unit will blow in the direction of a neighbor's window
• Locations where the noise of the outdoor unit will pose a problem
• Locations with poor air circulation
Electric wiring
WARNING
Ensure that the unit is correctly earthed.
Grounding is necessary. If earthing is incomplete, an electric shock may be caused.
3-12. Maintenance
Cleaning of air filter
• When [F IL TER] is displayed on the remote controller, it is time to chec k and if necessary clean the filter.
• Clogging of air filter decreases the cooling/heating effect.
WARNING
Be sure to turn off the main power supply prior to any maintenance.
• Please do not intend to do the daily maintenance and/or Air Filter cleaning by yourself.
Cleaning the air filter and other parts of the unit involves dangerous work in high places, so be sure to
have a qualified service person do it. Do not attempt it b y yourself.
Daily maintenance
• F or daily maintenance including Air F ilter cleaning, please use qualified service personnel, particularly for
the following models -
4-way Air Discharge Cassette TypeConcealed Duct Standard TypeUnder Ceiling Type
2-way Air Discharge Cassette TypeSlim Duct Type
1-way Air Discharge Cassette TypeConcealed Duct High Static Pressure Type
CAUTION
Check that the circuit breaker is fitted.
Attaching a earth leakage breaker is necessary. Otherwise, an electric shock may be caused.
Make sure that the correct capacity fuses are used.
Using wire or copper wire may cause a fire or unit fault.
Ensure that the power supply to the unit is exclusive and is the correct rated voltage.
To disconnect the appliance from the main power supply.
This appliance must be connected to the main power supply by means a circuit breaker or a switch with a
contact separation of at least 3mm.
47
Filter holder
High Wall T ype
(Model : 1H series)
• Push the projection at the center of the air filter.
• Undo the clip on the air filter, pull the air filter downwards while
pushing it towards the main unit side.
(Model : 2H series)
• Open the air inlet grille.
Lift the air inlet grille up to the horizontal position.
• Take hold of the left and right handles of the air filter and lift it up
slightly, then pull downwards to take it out from the filter holder .
Filter holder
Floor Standing Cabinet Type
• Gently push down on the upper part of the suction port, and then
pull towards you to remov e it.
• Take out the air filter inside of the suction port.
Floor Standing Concealed Type
• Push down hook of the air filter on the front panel (Lower side).
• Pull the air filter towards you to remove it.
Push the air filter,
and pull it downward.
Re-installing the air filter
• Insert the the air filter back into the unit, ensuring that both sides of the filter are positioned correctly inside
of the plastic frame.
• Close the air inlet grille.
If the F IL TER lamp on the indoor unit is displayed, press the F ILTER button on the remote controller or the
TEMPORARY button on the indoor unit. This will turn the light off.
Cleaning the air inlet grille
1. Remove the air inlet grille.
Hold the two sides of the air inlet grille and open upwards.
Move the center arm to the left and remove the grille.
2. Wash the grille with water using a soft sponge or towel.
(Do not use metallic scrubbing brush or other hard brushes.)
• Use of such hard objects will cause scratches on the
surface of the grille, and the metal coating to peel off.
• If very dirty, clean the air inlet g rille with a neutral detergent
for kitchen use, and rinse off with water .
3. Dry the inlet grille, ensuring no water is left.
4. F it the left and right arms of the air inlet grille to the shafts on
the two sides of the air conditioner and push in completely.
Then push in the center arm.
5. Check that the center arm has been completely inserted and
then close the air inlet grille.
• Push the arrow locations (four) at the bottom of the air inlet
grille to check whether the grill is completely closed.
Floor Standing Type
Removal / Attachment of air filter
• Pull the air filter towards you.
• To attach the air filter, insert it into the main body and push it in.
NOTE
• When cleaning the air filter, use a small brush or cleaning device. If the air
filter is heavily stained, use a neutral detergent mixed with warm water.
• After washing the filter, rinse it out thoroughly and place in the shade to
dry. Do not expose to direct sun light.
• Once the air filter has dried, place the air filter back into the unit.
Front panel
(Lower)
Air filter knob
Cleaning of the main unit / remote controller
CAUTION
• Wipe them with a soft and dry cloth.
• A cloth dampened with cold water may be used on the indoor
unit if it is very dirty.
• Never use a damp cloth on the main unit and the remote
controller.
• Do not use or leave a chemically treated duster on the unit for
long periods of time, as it may damage or alter the colour of
the unit surface.
• Do not use benzine, thinner, polishing powder, or similar
solvents for cleaning. These may cause the plastic surface to
crack or deform.
Polishing
powder
Benzene
Thinner
Chemical
floor-cloth
Do not use.
48
If you do not plan to use the unit for more than 1 month
1. Operate the fan for 3 to 4 hours to dry the inside of the unit
• Operate “FAN” mode.
2. Stop the air conditioner and turn off the main power supply
or the circuit breaker.
I will wipe soft
and dry cloth!
Checks before operation
1. Check that the air filters are installed.
2. Check that the air outlet or inlet is not blocked.
3. Turn on the main power switch or the circuit breaker for the
main power supply to the air conditioner.
Use after drying
when it has not been
used for a long time!
NOTE
F or Air conditioning system which is operated regularly, cleaning and maintenance of the indoor/outdoor
units are strongly recommended.
As a general rule, if an indoor unit is operated for about 8 hours daily, the indoor/outdoor units will need to
be cleaned at least once every 3 months. This cleaning and maintenance shall be carried out by a qualified person.
F ailure to clean the indoor/outdoor units regularly will result in poor performance, icing, water leakage and
even compressor failure.
HINTS FOR ECONOMICAL OPERATION
Maintain room temperature at comfortable level
Clean air filters
The clogged air filter impairs the performance of the air conditioner.
Never open doors and windows more than what is necessary
To keep the cool or warm air in the room, nev er open doors and
windows more than what is necessary.
Window curtains
In cooling, close the curtains to avoid direct sunlight.
In heating, close the curtains to keep the heat in.
Ensure uniform circulation of room air
Adjust the air flow direction so that the air
is evenly circulated throughout the room.
Please close
Blows upward
Cool and
dry air
Clean, please.
Gee, chilly
Control
Air flow adjustment
Warm
air
Blows downward
3-13. Air Conditioner Operations and Performance
Check before operation
• Check whether earth wire is disconnected or out of place.
• Check that air filter is installed to the indoor unit.
Heating capacity (for Heat-pump model only)
• During heating operation the heat pump system operates by
absorbing the heat from the outside air and discharging it into the room.
Therefore if the outside temperature drops, the units heating capacity will decrease.
• When temperature of the outside air is low, it is recommended that you use other forms of heating in conjunction
with the air conditioner.
Turn on the power supply 12
hours or more before starting
the air conditioner.
Defrost operation during heating operation (for Heat-pump model only)
• If the outdoor unit has a build up of frost during the heating operation, the operation mode changes automatically to defrost mode to increase the heating effect (for approximately 2 to 10 minutes).
• During defrost operation, fans of the indoor and the outdoor units will stop.
Protection for 3 minutes
• The outdoor unit will not operate for approximately 3 minutes after the air conditioner has been immediately
restarted after being stop, or the power supply has been turned on. This is to protect the system.
Main power failure
• If a power failure occurs during operation, all operations stop.
• When restarting the unit, push the ON/OF F button again.
Fan rotation of stopped unit
• When other indoor units within the same system are in operation, the fan on the indoor units that are on “standby” will rotate to protect the machine once approximately 1 hour for several minutes.
Protective device (High pressure switch)
The high pressure switch operates the unit automatically when excessive load is applied to the air conditioner.
If the protective device operates, the operation lamp will stay but the operation will stop.
When the protective device operates, check characters “
The protective device may operate in the following cases.
” on the remote controller display.
In Cooling operation
• When suction or discharge port of the outdoor unit is closed.
• When strong winds blow continuously against the discharge port of the outdoor unit.
In Heating operation (For Heat-pump model only)
• When excessive dirt or dust is adhered to the air filter of the indoor unit.
• When the discharge port of the indoor unit is blocked.
Cooling/heating operation of MiNi-SMMS air conditioner
In MiNi-SMMS air conditioner, each indoor unit can be individually controlled. However, cooling operation and
heating operation cannot be performed concurrently for the indoor units, which are connected to the same outdoor
unit.
When cooling operation and heating operation are performed concurrently, the indoor unit which is performing
cooling operation stops, and the “
continue operation.
If the manager has fixed the setting to COOL or HEAT, no other operation can be performed.
When another operation other than the set up one is performed, the “
the indoor unit.
” on the unit display will be lit. The indoor unit that is in heating mode will
” light is displayed on the display part of
Characteristics of heating operation (For Heat-pump model only)
• Hot air will not be blown out immediately from the indoor unit. It will take between 3 to 5 minutes (depending on
temperature conditions of the room and the outside) before the indoor heat exchanger warms up sufficiently, to
allow hot air to be blown.
• During operation, the outdoor unit may stop if the outside temperature becomes to high.
• When other indoor units are in heating operation, the fan operation of the indoor unit on fan only operation may
be stopped temporarily to prevent hot air from being blown out.
WARNING
49
It’s strange.
Silent
The slot provided at side surface of the outdoor
unit is an air intake for cooling the electrical parts.
If the air intake would be clogged, a trouble is
caused on the electrical parts.
Therefore nev er close the air intake or do not
place any obstacle near the air intake.
Slot for air intake
Air conditioner operating conditions
F or the specified performance, operate the air conditioner under the follo wing temper ature conditions:
Cooling operation
Heating operation
Outdoor temperature : –5°C to 43°C (Dry-bulb temp.)
Room temperature : 21°C to 32°C (Dry-bulb temp.), 15°C to 24°C (Wet-bulb temp.)
CAUTION
Outdoor temperature : –15°C to 15.5°C (Wet-bulb temp.)
Room temperature : 15°C to 28°C (Dry-bulb temp.)
Room relative humidity – less than 80 %. If the air conditioner operates
in excess of this figure, the surface of the air conditioner may cause dewing.
If air conditioner is used outside of the above conditions the units, safety protection devices may operate.
3-14. Re-Installation
DANGER
If the unit position is to be changed and re-located to a new position ask your local dealer or
installation specialist. Do not attempt to move the air conditioner yourself, as incorrect installation
may cause electric shock or fire.
Do not install the air conditioner in the following places
• Do not install the air conditioner in any place within 1 m from a TV , stereo, or radio set. If the unit is installed in
such places, noise transmitted from the air conditioner may effect the operation of these appliances.
• Do not install the air conditioner near a high frequency appliance (sewing machine or massager for business
use, etc.), as the air conditioner may malfunction.
• Do not install the air conditioner in a humid or oily place, or in a place where steam, soot, or corrosive gas may
be generated.
• Do not install the air conditioner in a salty place such as a seaside area.
• Do not install the air conditioner in a place where a great deal of machine oil is used.
• Do not install the air conditioner in a place where it is usually exposed to strong winds such as in a seaside area
or on the roof / upper floor of a building.
• Do not install the air conditioner in a place where sulfureous gas may be generated such as in a spa.
• Do not install the air conditioner in a vessel or mobile crane.
Be careful with noise or vibrations
• Do not install the air conditioner in a place where the noise or the hot air created by the outdoor unit will come
into contact with your neighbours.
• Install the air conditioner on a solid and stable foundation as this will reduce the transmission of noise and
vibration that is produced from the outdoor unit.
• If one indoor unit is operating, some sound may be audible from other indoor units that are connected within the
same system (even when not in operation).
3-15. When The Following Symptoms Air Found
Check the points described below before contacting your local service repair center.
Symptom
Outdoor unit• White misty cold air or
Indoor unit•“Swish” sound is
It is not a failure.Check again.
Operates or stops automatically.
Does not operate.
Air is not cooled or warmed sufficiently.
When the following symptoms are found, stop the operation immediately, turn off the power supply, and contact the
dealer from where you have purchased the air conditioner.
• Activation of the power supply causing the unit to operate in an unstable fashion
(power on, power off , power on, power off etc).
water is blown out.
• Sometimes, the noise
“Pushu !” is heard.
sometimes heard.
• A stopping indoor unit
in the same operating
air conditioner system
emitted sound, white
vapor or cool air.
• Slight “Pishi!” sound is
heard.
• Discharge air smells.
•“
” indication is lit.
• When power of the air
conditioner is turned
on, “Ticktock” sound is
heard.
• F an of the outdoor unit stops automatically and performs defrost
operation.
• Solenoid valve works when defrost operation starts or finishes.
• When the unit is in operation,a sound such as the movement of
water from one area to another may be heard. This sound may
become larger after a period of 2 to 3 minutes once the unit has
begun operation. This is not a cause for concern, but is the movement of the refrigerant or the draining sound of the dehumidifier.
• When the air conditioner system is operating, the stopping indoor
unit in the same system needs temporary flow of refrigerant to
prevent the stay of oil or refrigerant.
Therefore, refrigerant flow sound “shaa/cyu” may be heard, or white
vapor may come out when other indoor unit heating, or cool air may
come out when other indoor unit cooling.
• This sound is generated when the heat exchanger, etc. expands
and contracts slightly due to the change of temperature.
• V arious odurs such as those from a carpet, clothes, cigarette, or
cosmetics will adhere to the air conditioner.
• When cooling operation cannot be performed because another
indoor unit performs heating operation.
• When the manager of the air conditioner has fixed the operation to
either COOL or HEAT, but a request or demand contrary to the
setup operation is requested.
• When the fan operation is stopped to prevent the discharge of hot
air.
• Sound is generated when the expansion valve operates when the
power supply has been turned on.
• Is the timer “ON” or “OF F”?
• Is there a power failure to the unit?
• Has the power supply been turned off?
• Has the power fuse or breaker blown?
• Has the protective device operated? (The operation lamp goes on.)
• Is the timer “ON”? (The operation lamp goes on.)
• Are COOL and HEAT selected simultaneously?
(“
” indication is lit on the display column of the remote controller.)
• Is the suction port or discharge port of the outdoor unit obstructed?
• Are there any doors or windows open?
• Is the air filter clogged with dust?
• Is the discharge louver of the indoor unit set at appropriate position?
• Is the air selection set to “LOW” or “MED” and is the operation
mode set to “FAN”?
• Is the setup temp. the appropriate temperature?
• Are COOL and HEAT selected simultaneously?
” indication is lit on the display column of the remote controller.)
(“
• The main power fuse often blows out, or circuit breaker is often activated.
• F oreign matters or water have entered the unit by mistake.
• When the unit fails to operate after the protective device (circuit breaker) has been removed.
Not recommended.
• Other unexplained symptoms or unit abnormalities, that cannot be explained.
Cause
Confirmation and check
When a error has occurred in the air conditioner,
the check code and the indoor unit No. will appear
on the display part of the remote controller.
The check code is only displayed during while the
unit is operating.
If the display disappears, operate the air conditioner according to the following “Confirmation of
error history” for confirmation.
Confirmation of error history
When a error has occurred on the air conditioner,
the error history can be confirmed with the following
procedure. (up to 4 errors can be stored in the
memory of the remote controller)
The history can be confirmed from both operating
status and stop status.
2
Check code
FILTER
RESET
TEMP.
TEST
UNIT No.
R.C. No.
Indoor unit No. in which
an error occurred
FAN
TIMER SET
SWING/FIXTIME
UNITSET CL
CODE No.
ON / OFF
MODE
VENT
50
3
Procedure
SET
When pushing the
for 4 seconds or more, the following display will appear.
If [Service check] is displayed, the mode enters into the
error history mode.
• [01 : Order of error history] is displayed in CODE No.
1
2
3
window.
• [Check code] is displayed in CHECK window.
• [Indoor unit address in which the error has occurred] is
displayed in UNIT No.
F or every push of the [ , ] button, the error history stored in memory is displayed in order.
The numbers in CODE No. indicate CODE No. [01] (latest) → [04] (oldest).
CAUTION
Do not push the
After confirmation, push the
TEST
and
buttons at the same time
CL
button because all the error history of the indoor unit will be deleted.
TEST
button to return to the normal display.
1. Check the error codes according to the above procedure.
2. Ask an authorized dealer or qualified service (maintenance) professional to repair or maintain the air
conditioner.
3. More details of the service codes are explained in the Service Manual.
1) Detects indoor suction temperature
(Connector CN100 (3P): Brown)
1) Controls PMV super heat in cooling operation
(Connector CN101 (2P): Black)
1) Controls PMV under cool in heating operation
(Connector CN102 (2P): Red)
1) Controls PMV super heat in cooling operation
2) [MMU-AP0071 to AP0121YH only]
Controls PMV under cool in heating operation
53
5.SWITCH (SW08) SET UP OF THE OUTDOOR UNIT
When using the outdoor unit under the following conditions, it is necessary to set up DIP switch on the outdoor
unit interface P.C. board.
CAUTION
When anyone of the following condition is applied, set up DIP switch.
1. When using PMV Kit in the Mini-SMMS system
2. When using the indoor unit under high humidity condition
[Reference]
Indoor side: 27°C dry bulb temperature
24°C wet bulb temperature
Operation time 4 hours or more.
5-1. Setup Method
• Turn on DIP switch [SW08] on the interface P.C. board of the outdoor unit.
Outdoor unit interface P.C. board
SW11
1ON2 3 4
SW06
1ON2 3 4
SW12
1ON2 3 4
SW07
ONONONON
1
2 3 4
Switch [SW08]
SW13
1ON2 3 4
SW09SW08
112 3 4
SW14
1ON2 3 4
SW10
1 2 3 4
54
6.CONTROL OUTLINE
6-1. Indoor Unit
6-1-1. Control Specifications
No.
1
2
3
Item
Power supply
is reset.
Operation
select
Room temp.
control
Outline of specifications
(1) Identification of outdoor unit
When the power supply is reset, the outdoor units are
individually identified and communication is established.
(2) Check code clear
When the power supply is reset, the check code is also reset.
If an abnormal status is still present upon restart the check
code will be displayed again on the remote controller.
(1) Based upon the operation command received from the
remote controller or central controller, the operation mode is
selected.
Remote controller
command
STOP
FAN
COOL
DRY
HEAT
(1) Set point temperature adjustment range on remote controller
(°C)
Control outline
Stops air conditioner.
Fan only operation
Cooling operation
Dry operation ∗
Heating operation
Remarks
∗ Concealed Duct High
Static Pressure type air
conditioner cannot operate
in drying mode.
4
5
Automatic
capacity
control
Air volume
control
All cooling
Wired type
Wireless type
(2) The set point temperature in heating operation can be offset
using item code (DN) 06.
Setup data
Setup temp. correction
Setup at shipment
Setup data2
(1) The difference between the temperature reading taken from
the Ta (room) sensor and the Ts (set point) selected on the
remote controller is used to determine the demand frequency
to the outdoor unit.
(1) The remote controller is used to select the modes “HIGH
(HH)”, “MED (M)”, “LOW (L)” or “AUTO”.
(2) The difference between the temperature reading taken from
the Ta (room) sensor and the Ts (set point) selected is used
to control the air volume setting when in “AUTO” mode.
18 to 29°C
18 to 30°C
0246
+0°C+2°C+4°C+6°C
All heating
18 to 29°C
16 to 30°C
Heating suction temperature
shift
HH > H+ > H >
L+ > L > LL
55
No.
6
Prevention of
cold air
discharge
7
Freeze
prevention
control (Low
temp. release)
Item
Outline of specifications
(1) In all heating operation, the upper limit of the fan tap is set by
one with higher temperature of TC2 sensor and TCJ sensor.
• When B zone has continued for 6 minutes, the operation
shifts to C zone.
• In defrost time, the control point is set to +6°C.
(˚C)
32
30
28
26
D
C
A zone: OFF
B zone:
Over 26˚C, below 28˚C, LOW
C zone:
E
Over 28˚C, below 30˚C, MED
D zone:
Over 30˚C, below 32˚C, HIGH
E zone: Ultra HIGH
20
16
B
A
(1) In all cooling operation, the air conditioner operates as de-
scribed below based upon temp. detected by TC1, TC2 and
TCJ sensors.
To prevent the heat exchanger from freezing, the operation
stops.
• When “J” zone is detected for 5 minutes, the command
frequency becomes “S0” to the outdoor unit.
• In “K” zone, the timer count is interrupted, and held.
• When “1 ” zone is detected, the timer is cleared and the
operation returns to the normal operation.
• When the command frequency became S0 with continuation of “J” zone, operation of the the indoor fan in LOW
mode until it reaches the “1 ” zone.
It is reset when the following conditions are satisfied.
Remarks
• In D and E zones, priority
is given to remote controller air speed setup.
• In A and B zones, “
” is
displayed.
Reset conditions
>
1) TC1
12°C and TC2 > 12°C and TCJ > 12°C
2) 30 minutes passed after stop.
TC1
10°C (5°C)
0°C
(˚C)
P1
Q1
I
K
J
a
P1
Q1
(2) In all cooling operation, the air conditioner operates as
described below based upon temp. detected by TC2 and TCJ
sensors.
• When “M” zone is detected for 45 minutes, the command
frequency becomes “S0” to the outdoor unit.
• In “N” zone, the timer count is interrupted and held.
• When shifting to “M” zone again, the timer count restarts
and continues.
• If “L” zone is detected, the timer is cleared and the opera-
tion returns to normal operation.
Reset conditions
>
1) TC1
12°C and TC2 > 12°C and TCJ > 12°C
2) 30 minutes passed after stop.
(˚C)
P2
Q2
L
N
M
P2
Q2
TC2, TCJ
5°C
–2.0°C
∗ In a Model without TC2,
TC2 is not judged.
56
1st revised : Jun. 2006
No.
8
Recovery control
for cooling
refrigerant and oil
9
Recovery control
for heating
refrigerant and oil
10
Short intermittent
operation
compensation
control
Item
Outline of specifications
(1) The indoor unit which stops operation, thermostat is OFF,
or operates in FAN mode opens PMV of the indoor unit by
the specified opening degree when cooling refrigerant or oil
recovery signal is received from the outdoor unit.
(2) Drain pump of 4-way air discharge cassette type and
concealed duct type operate during recovery control mode.
The indoor unit which stops operation, thermostat is OFF, or
operates in FAN mode performs the following controls when
the heating refrigerant/Oil recovery signal is received from the
outdoor unit.
1) Opens PMV of the indoor unit by the specified opening
degree.
2) Stops the fan.
3) Only 4-way Air Discharge Cassette type air conditioner
rotates the indoor fan with intermittent operation for
approximately 1 minute after recovery control.
4) Only 4-way Air Discharge Cassette type air conditioner
rotates the indoor fan with intermittent operation for
approximately 1 minute after recovery control as the
outdoor unit.
5) After recovery control, drain pump of 4-way air discharge
cassette type and concealed duct type will operate.
(1) For 5 minutes after the operation has started, the operation
is continued even if entering thermostat-OFF condition.
(2) However, if the thermostat has been turned off by changing
the set up temp., the thermostat is OFF with even the
above condition. The protective control has priority.
Remarks
• Recovery operation is
usually executed every 3
hours.
• In the indoor unit which
thermostat is OFF, or
operates in FAN mode,
“
” lamp goes on.
• Recovery operation is
usually executed every
1 hour.
11
Drain pump
control
12
Elimination of
remaining heat
13
Auto louver
control
14
Filter sign display
(None in wireless
type)
∗ Provided in the
separately laid
type
TCB-AX21E.
(1) During “COOL” operation (including DRY operation), the
drain pump operates.
(2) While the drain pump operates, if the float switch works,
the drain pump continues operation and a check code is
displayed.
(3) While the drain pump stops, if the float switch works, turn
off the capacity demand command, stop the operation, and
operate the drain pump. If the float switch continues
operating for approx. 5 minutes, the operation stops and
the check code is displayed.
(4) In heating operation, if humidifier “provided” is judged,
compressor “ON”, compressor “ON”, fan “ON”, and MAX
(TC2, TCJ) > 33°C, the drain pump operates.
(1) When the air conditioner stops in the “HEAT” mode, drive
the indoor fan with “LOW” mode for approx. 30 seconds.
(1) When the louver signal has been received from the remote
controller, the louver operates if the indoor fan is operating.
(2) In 4-way Air Discharge Cassette type, the discharge louver
automatically directs downward if the operation stops.
(3) In 4-way Air Discharge Cassette type, the discharge louver
directs upward if the heating operation is being prepared.
(1) The operation time of the indoor fan is integrated and
stored in memory, and the filter exchange signal is sent to
the remote controller to display on the remote controller
LCD after the specified time.
(2) When the filter reset signal is received form the remote
controller, time of the integrated timer is cleared. In this
time, if the specified time has passed, the measured time is
reset and LCD display disappears.
Check code [P10]
57
No.
15
“” and “ ”
display
(Operation and
heating stand-by)
Item
Outline of specifications
<Operation standby> .......... Display on remote controller
(1) •“P05” is one of displays of power wire missing.
•“P05” of power cable is detected.
•“COOL/DRY” operation cannot be performed because theother indoor unit is under “HEAT” operation.
•“HEAT” operation cannot be performed because COOL
priority is set (Outdoor I/F P.C. board SW11 1-bit is ON)
and the other indoor unit is under “COOL/DRY” operation.
•“FAN” operation cannot be performed because the system
performs “Heat oil/Refrigerant recovery” operation.
• There is a unit in which indoor overflow “P10” is detected.
• There is a unit in which interlock alarm “P23” is detected.
(2) The above indoor units unavailable to operate waits under
condition of thermostat OFF.
<HEAT standby> .................. Display on remote controller
(1) • HEAT thermostat is OFF.
• During HEAT operation, the fan rotates with lower air speed
than one specified in order to prevent discharge of cold
draft or stops. (including case that defrost operation is
being performed)
•“HEAT” operation cannot be performed because COOL
priority is set (Outdoor I/F P.C. board SW11 bit 1 is ON) and
the other indoor unit is under “COOL/DRY” operation.
(2) “HEAT standby” is displayed until the above conditions are
released.
Remarks
•“ ” goes on.
•“ ” goes on.
16
Selection of
central control
mode
(1) The contents which can be changed on the remote controller
at indoor unit side can be selected by setup at the central
controller side.
(2) In case of operation from TCC-LINK central controller
(TCB-SC642TLE, etc.)
[Central control mode 1] : Cannot operate
[Central control mode 2] :
Cannot operate, stop, select mode, set up temp.
[Central control mode 3] :
Cannot select mode, set up temp.
[Central control mode 4] : Cannot select mode
(3) RBC-AMT21E (Wired remote controller)
While mode is the central control mode, “
lights on the display part of the remote controller.
CENTRAL”
If operation is performed
from the remote
controller “CENTRAL
CONTROL” mode, the
status is notified with
receiving sound.
58
1st revised : Jun. 2006
6-2. Outdoor Unit
6-2-1. Operation Start/Operation End
The compressor, solenoid valve, pulse motor valve (PMV), outdoor fan, etc. are controlled by a command from
the indoor controller. The follower outdoor unit starts/stops by a command from the header outdoor unit.
No.
1
Pulse Motor Valve
(PMV) control
2
Outdoor fan
control
Item
Operation explanation and applied data, etc.
(1) PMV control
• PMV is controlled between 45 to 500 pulses during
operation.
• In cooling operation, PMV opening is dependent upon
detected readings from the TL sensor and Pd pressure
sensor (sub-cool control).
• In heating operation, PMV opening is dependent upon
detected readings from the TS and TD sensors and the Ps
pressure sensor (super-heat control).
• PMV will be fully closed when the system is in ‘Standby’ or
‘No demand’ modes and when a malfunction in the system
has occurred.
(1) Fan control in all cooling operation
1) The outdoor fan speed/mode is determined by the
detected Pd pressure value.
2) When cooling operation has star ted, the outdoor fan
speed of the master unit is controlled using the detected
Pd pressure value.
(2) Fan control in all heating operation
1) The outdoor fan speed/mode is determined by the
detected TE sensor value.
2) If a TE value > 25°C has been continuously detected for 5
minutes, the operation may stop.
3) After star t up, this control is not available during the
specified time after a defrost operation.
4) This operation may start and stop repeatedly when the
system is undercharged.
(3) Fan control for mainly cooling, part heating operation
The outdoor fan speed (mode) is controlled according to the
target of the Pd (Discharge pressure).
Remarks
When TE temp. (ambient
temperature) exceeds
25°C, Heating operation
stops.
• The maximum fan
speed differs depending on the outdoor HP.
3Capacity control• Min. frequency: 26Hz(1) The capacity request command received from the indoor
4Refr igerant/Oil
recovery control
controller determines the inverter frequency control of the
outdoor unit.
(1) During cooling operation, this function is executed to
regularly to recover the refrigerant/oil from the indoor units
and connecting pipe-work back to the outdoor unit.
This function is also performed to prevent stagnated refrigerant accumulating in the outdoor heat exchanger during low
ambient cooling.
1) Control conditions
• Cooling oil recovery operation is executed approximately
every 3 hours.
2) Contents of control
• The recovery period lasts for approximately 2 or 3 minutes
though this is dependant on the system capacity.
(2) Refrigerant recovery control in heating room
This function is executed regularly to recover the liquid
refrigerant from the indoor unit.
It is also used to recover oil present in the outdoor heat
exchanger during the heating overload operation
(except during defrost operation).
1) Heating operation oil, recovery control is executed
approximately every hour.
2) The period of recovery lasts for approximately 2 to 10
minutes though this is dependent upon the load condition.
• Control for refrigerant/
oil recovery is performed approximately
every 3 hours.
• Recovery lasts for
approximately 2 or 3
minutes though this is
dependent upon the
system capacity.
59
1st revised : Jun. 2006
No.
5
6Solenoid valve
Item
Defrost control
(Reverse cycle
defrost method)
control
Operation explanation and applied data, etc.
(1) Defrost start condition
The defrost function is initiated when the measurement
temperature taken from the TE sensor is lower than –1°C for
a period of 25 minutes after compressor initial start up and 55
minutes after subsequent start ups.
(2) Contents of control
• If the outdoor units are combined, the minimum duration for
the defrost operation is 2 minutes.
(3) Defrost stop condition
• The outdoor fan speed and compressor inverter frequency
are determined by the measurement of Pd pressure during
defrost operation.
(1) SV2 gas balance control
This control is executed to balance the gas when opening
SV2 while the compressor is off, in order to decrease the
activation load in the next compressor-ON time.
This control is individually executed by the outdoor unit.
(2) SV2 high-pressure release control
This control is to control pressure rising in low-frequency
operation of the inverter.
(3) SV2 low-pressure release control
This control is to prevent quick pressure dropping transient
operation. This control is individually executed by the outdoor
unit.
This control is executed as necessary except during stop time
and thermostat-OFF time.
(4) SV4 low-pressure release control
This control is to prevent low-pressure dropping and is
individually executed by unit.
This control executed during defrost operation, heating start
pattern control operation and cooling operation.
(5) SV5 high-pressure release control
This control is to prevent high-pressure rising and executed
unit only.
Remarks
• During the defrost
operation, all solenoid
4-way valves are OFF
and all compressors
are operating.
7Frequency
release control
Compressor
8Each compressor is stopped should the Pd pressure sensor
stop due to high
pressure release
(1) High pressure release control
This function is to correct the operation command of the
compressor and suppress the rise of high pressure.
1) Control contents
The operation frequency is decreased by 1 step when Pd
pressure ≥ 3.4MPa. It is decreased by 1 step every 10
seconds until Pd pressure dropsbelow 3.4MPa.
2) Release condition
• When Pd pressure ≤ 3.2MPa
• When refrigerant recovery control starts in all heating
mode
• During defrost operation, stop, thermo OFF.
reach a value of 3.5 MPa.
This control is performed by the outdoor units.
60
No.
9
10
Item
Case heater
control
IPDU control
Operation explanation and applied data, etc.
Heating is provided for both the compressor case and accumulator.
When the compressor in any outdoor unit is stopped, the heater is
switched on to prevent accumulation of refrigerant.
After installation of a system, it should be powered for the specified
period of time prior to operating a test run to prevent damage to the
system.
If the system has not been powered for a prolonged period of time, it
is important to apply power for the specified period of time before
resuming operation.
This function is often performed in conjunction with the compressor
winding heating control. When this occurs, a noise may be heard
which is not an indication of a malfunction.
(1) Contents of control
• The function is performed during when the compressor is off.
• When the TO sensor temp measures 28°C or higher the heaterturns off and turns on when it change:measures 25°C or lower
• The heater remains ‘ON’ for 10 minutes after the compressor
has changed mode from Off to On.
The IPDU controls the inverter compressor by communicating a
command frequency that controls the compressor speed, depending
on any active releases.
The main controls of the IPDU P.C. board are:
(1) Current release control
Feedback from the AC input current sensor (CT) is used to
prevent the inverter input current exceeding its specified limit
(2) Heat sink temperature detection control
• Feedback from the thermistor (TH) on the compressor driving
module is used to prevent the IGBT from overheating.
The highest value is taken from IPDU TH sensors.
(3) Over-current protective control
• When an over-current condition is detected by the IPDU, the
compressor is stopped.
(4) Compressor case thermo control
• The compressor stops when the compressor case thermostat is
activated.
• Whenever this condition occurs, a 1 count is added to the
system error count.
• After a period of 2 minutes and 30 seconds, the compressor is
reactivated and the error count cleared if the operation continues without further error for a period of 10 minutes or more.
• If the error count reaches 4, the check code [H04] is displayed.
Remarks
• The case thermostat
is normally closed
and connected to
interface P.C. board.
11
High pressure
prevention
control
(1) High pressure SW control
• The high pressure switch is connected to the IPDU board and is
in the normally closed condition.
• When the high pressure switch is activated, the compressor is
stopped.
• Whenever this condition occurs, a 1 count is added to the
system error count.
• After a period of 2 minutes and 30 seconds, the drive to the
compressor is reactivated and the error count is cleared if the
operation continues with further error for a period of 10 minutes
or more.
• If the error count reaches 4, the check code [P04] is displayed.
61
Other cautions
1. Cooling operation in low ambient temperatures
1) The indoor unit freeze prevention control system (TC sensor) may decrease the command frequency to
the outdoor unit when low coil temperatures are detected.
2) The cooling capacity control may decrease the command frequency to the outdoor unit when low ambient
temperature is detected.
3) When the discharge temperature sensor value reaches 60°C or below, the frequency may be increased
above the required demand from the indoor unit.
2. PMV (Pulse Motor Valve) for outdoor unit
1) When the system power is turned on an audible “clicking” sound is omitted due to the PMV initializing,
this is a normal condition. When the outdoor unit is situated near other sources of noise, this sound may
not be noticeable.
2) Do not remove the driving part (head) of the PMV during operation as it may cause the PMV to malfunction.
3) When transporting or replacing the outdoor unit, never keep the driving part (head) removed from the
PMV body as the valve will be closed and ma y result in damage or failure due to sealed liquid compression.
4) When refitting the driving part (head) to the body of the PMV, apply pressure until a “click” sound can be
heard, complete the process by resetting the power to the system.
62
7.APPLIED CONTROL
7-1. Indoor Unit
7-1-1. Setup of Selecting Function in Indoor Unit
(Be sure to Execute Setup by a Wired Remote Controller)
<Procedure> Execute the setup operation while the unit stops.
TEMP.
ON / OFF
3
TIMER SET
FAN
MODE
5
6
FIL TER
RESET
TEST
SWING/FIXTIME
UNITSET CL
VENT
1
1
SET, CL
Push
The firstly displayed unit No. indicates the master indoor unit address in the group control.
In this time, the fan of the selected indoor unit is turned on.
, and
TEST
buttons simultaneously for 4 seconds or more.
4
2
2
Every pushing
displayed. In this time, the fan of the selected indoor unit only is turned on.
3
Specify the item code (DN) using the setup temperature and buttons.
4
Select the setup data using the timer time and buttons.
(When selecting the DN code to “33”, change the temperature indication of the unit from “°C”
to “°F” on the remote controller.)
5
6
SET
Push
• To change the selected indoor unit, return to procedure 2 .
• To change the item to be set up, return to procedure 3 .
Pushing
button. (OK if display goes on.)
TEST
UNIT
button, the indoor unit numbers in the group control are successively
button returns the status to normal stop status.
63
Table: Function selecting item code (DN)
(Items necessary to perform the applied control at the local site are described.)
1-way Air Discharge Cassette
4-way Air Discharge Cassette
2-way Air Discharge Cassette
1-way Air Discharge Cassette (Compact type)
Concealed Duct Standard
Slim Duct
Concealed Duct High Static Pressure
Under Ceiling
High Wall
Floor Standing Cabinet
Floor Standing Concealed
Floor Standing
Compact 4-way Air Discharge Cassette
—
Abbreviated Model name
MMU-AP ✻✻✻ SH
MMU-AP ✻✻✻ H
MMU-AP ✻✻✻ WH
MMU-AP ✻✻✻ YH
MMD-AP ✻✻✻ BH
MMD-AP ✻✻✻ SPH, SH
MMD-AP ✻✻✻ H
MMC-AP ✻✻✻ H
MMK-AP ✻✻✻ H
MML-AP ✻✻✻ H
MML-AP ✻✻✻ BH
MMF-AP ✻✻✻ H
MMU-AP ✻✻✻ MH
n Remote location ON/OFF control box (TCB-IFCB-4E)
[Wiring and setup]
• Use the exclusive connector for connection with the indoor control P.C. board.
• In a group control, the system can operate when connecting with any indoor unit (Control P.C. board) in the
group. However when taking out the operation/error signal from the other unit, it is necessary to take out from
each unit individually.
(1) Control items
1) Start/Stop input signal : Operation start/stop in unit
2) Operation signal: Output during normal operation
3) Error signal: Output during alarm
(Serial communication error or indoor/outdoor protective device) operation
(2) Wiring diagram using remote control interface (TCB-IFCB-4E)
InputIFCB-4E : No voltage ON/OFF serial signal
OutputNo voltage contact for operation, error display
Contact capacity: Belo w Max. AC240V 0.5A
Indoor control P.C. board
Start/Stop input
COM (GND)
Remote controller prohibition/clear input
Operation signal output
COM (+12V)
Error signal output
1
2
3
4
5
6
CN61
T10
(YEL)
Remote location ON/OFF control box
(TCB-IFCB-4E)
1
2
3
4
CN06
1
2
3
4
5
6
CN13
Power supply 220–240V,
220V, ~60Hz
~
50Hz
ON/OFF serial
signal input
COM
Operation signal output
Error signal output
66
n Ventilating fan control from remote controller
[Function]
• The start/stop operation can be operated from the wired remote controller when air to air heat exchanger or
ventilating f an is installed in the system.
• The fan can be operated even if the indoor unit is not operating.
• Use a fan which can receive the no-voltage A contact as an outside input signal.
• In a group control, the units are collectively operated and they can not be individually operated.
(1) Operation
Handle a wired remote controller in the following procedure.
∗ Use the wired remote controller during stop of the system.
∗ Be sure to set up the wired remote controller to the header unit. (Same in group control)
∗ In a group control, if the wired remote controller is set up to the header unit, both header and follower units
are simultaneously operable .
1
Push concurrently
The unit No. displayed firstly indicates the header indoor unit address in the group control.
In this time, the fan of the selected indoor unit turns on.
2
Every pushing
SET
+ CL +
UNIT
button, the indoor unit numbers in group control are displayed succes-
sively.
In this time, the fan of the selected indoor unit only turns on.
TEST
buttons for 4 seconds or more.
3
Using the setup temp or button, specify the item code !.
4
Using the timer time or button, select the setup data. (At shipment: )
The setup data are as follows:
Setup data
5
6
SET
Push
• To change the selected indoor unit, go to the procedure 2 ).
• To change the item to be set up, go to the procedure 3 ).
Pushing
button. (OK if display goes on.)
TEST
returns the status to the usual stop status.
Handling of operation of air to air heat exchanger or ventilating fan
Unavailable (At shipment)
Available
(2) Wiring
Relay (DC12V, procured locally)
CN32
FAN DRIVE
(2P WHI)
Indoor control
P.C. board
Note) Determine the cable length between the
121
2
indoor control P.C. board and the relay within 2m.
Outside control
input of fan
To terminal
4-way Air Discharge Cassette type
1-way Air Discharge Cassette type (2 series)
Concealed Duct Standard type
Slim Duct type
Under Ceiling type
High Wall type
Corresponds up to a relay in which rated current of the
operation coil is approx. 75mA
Other type models:
Correspond up to a relay in which rated current of the
operation coil is approx. 16mA (Does not correspond
to a terminal block type relay on the market.)
model :
67
n Leaving-ON prevention control
[Function]
• This function controls the indoor units individually. It is connected with cable to the control P.C. board of the
indoor unit.
• In a group control, it is connected with cable to the indoor unit (Control P.C. board), and the item code
set to the connected indoor unit.
• It is used when the start operation from outside if unnecessary but the stop operation is necessary.
• Using a card switch box, card lock, etc, the forgotten-OFF of the indoor unit can be protected.
• When inserting a card, start/stop operation from the remote controller is allowed.
• When taking out a card, the system stops if the indoor unit is operating and start/stop operation from the
remote controller is forbidden.
(1) Control items
1) Outside contact ON : The start/stop operation from the remote controller is allowed.
(Status that card is inserted in the card switch box)
2) Outside contact OFF : If the indoor unit is operating, it is stopped forcedly.
(Start/Stop prohibited to remote controller)
(Status that card is taken out from the card switch box)
∗ When the card switch box does not perform the abov e contact operation, convert it using a relay with b
contact.
(2) Operation
Handle the wired remote controller switch in the f ollowing procedure.
∗ Use the wired remote controller switch during stop of the system.
1
Push concurrently
SET
+ CL +
TEST
buttons for 4 seconds or more.
- is
2
Using the setup temp or button, specify the item code - .
3
Using the timer time or button, set to the setup data.
4
5
(3) Wiring
SET
Push
Push
button.
TEST
button. (The status returns to the usual stop status.)
Indoor control P.C. board
Note) Determine the cable length between the indoor control P.C. board and the relay within 2m.
7-2-1-1. Cooling Priority, Heating Priority Control
n Usage/Features
Cooling priority or heating priority can be selected.
There are the following four patterns in selecting setup of the priority mode. Select a priority mode based
upon the demand of the destination to be installed.
n Setup
(Note)In “Specific indoor unit priority” mode only, it is necessary to set up an indoor unit only which you
desire to give priority.
1. Outdoor unit (Header unit only) setup
SW11
Bit 1Bit 2
OFFOFF
ONOFF
OFFON
ONON
Operation
Heating priority (Setup at shipment)
Cooling priority
No. of operating units (Pr iority is given to operation mode with which much more units operate.)
Specific indoor unit priority (Priority is given to operation mode of the indoor unit to which the
operation mode priority has been set up.)
70
2. Indoor unit setup in “Specific indoor unit priority” mode
The setup can be changed during stop of operation. (Be sure to stop the system.)
1st revised : Jun. 2006
Procedure
1
2
CODE No.
2
4
SET DATA
UNIT No.
R.C. No.
6
UNIT
1
SET
CL
3
5
Operation contents
When pushing
the display section flashes after a while confirm the displayed item code is [ ].
• When the item code is one other than [ ], push button to
eliminate the display and then repeat the procedure from the first step.
(The remote controller operation is not accepted approx. 1 minute
after pushing
(In a group control, the indoor unit with number displayed firstly is set to
the header unit.)
Every pushing
Select the indoor unit of which setup is to be changed.
In this time, as the fan and louver of the selected indoor unit operate,
the position of the indoor unit of which setup is to be changed can be confirmed.
SET
+ CL + buttons at the same time for 4 seconds or more, as shown in the figure,
button.)
, the indoor unit numbers in the group control are successively displayed.
UNIT
SET DATA
CODE No.
UNIT No.
R.C. No.
3
Using the setup temperature and buttons, specify the item code [" ].
CODE No.
4
5
6
Using the timer time and buttons, select the setup data [
Priority:
SET
Push
lighting.
After setup operation has finished, push button. (Setup is determined.)
When pushing button, the display disappears and the status returns
to the usual stop status.
(The remote controller operation is not accepted for approx. 1 minute.)
, No priority:
button. In this time, the setup operation finishes when the display changes from flashing to
].
SET DATA
UNIT No.
R.C. No.
(NOTE)
Only one indoor unit can be set to “Priority”. If the multiple indoor units are accidentally set to “Priority”, an error
code (L05 or L06: Duplicated indoor unit priority) is displayed.
To the unit displaying “L05”, [0001 (Priority)] is setup. Separate a unit which you will give priority from the other
indoor units, and return the setup data of the other indoor units to [0000 (No priority)].
Error code
L05
Indoor unit priority duplication ([
Error contents
] is set up.)
L06
Indoor unit priority duplication ([
71
] is set up.)
1st revised : Jun. 2006
7-2-2. Placing position
Install this optional P.C. board to the back side of the Interface P.C. board on outdoor unit.
Be sure to turn off the power switch bef ore installing.
1) If the screw of the position shown in Fig. 1 is removed and an upper right hook is slipped, an interface board
will open.
2) Place this P.C. board by using the support of the electric component box.
There are four installation holes to place the support of the electric component box.
Only cooling mode permitted
Only heating mode permitted
Normal operation
Note
∗1
∗1
∗1: “ (mode select control)” mark is indicated on the remote controller display.
CAUTION
• Be sure to prepare non voltage continuous point of contact for each terminal.
77
7-2-8. Error Output Control
n Feature
Operation and error monitoring is possible by using error output control board “TCB-PCIN2E”.
n Wiring
Output wiring
Size
4-core, 0.75 mm² ∗
4-core, 1.5 mm² ∗
Length
Up to 200 m
Up to 400 m
Type
Shield wire
* In conformity with design 60245 IEC 57.
n Function / Electric wiring diagram
Operation monitoring : Display relay is ON with more than one indoor unit operation.
EMG monitoring: Display relay is ON when the system in error status.
Outdoor unitLocal supply
I/F P.C. boardTCB-PCIN2E
Display
relay
Connection
cable
CN513PJ17
Display
relay
OPERATION
EMG
Power supply
L1
Power supply
L2
L1 : Operation monitoring lamp
L2 : Error monitoring lamp
Shield wire
CAUTION
• Be sure to prepare non voltage point for each terminal.
• Display relay capacity of “OPERATION” and “EMG”.
Below AC240V 0.5A (COSf = 100%)
When connecting load such as relay coil to “L1, L2” load, insert the noise surge absorber.
Below DC24V 1A (Non-inductive load)
When connecting load such as relay coil to “L1, L2” load, insert the bypass circuit.
78
8.PMV KIT OUT LINE
8-1. Purpose of Using
In the case of very quiet room, and also very nervous for indoor unit noise lev el, PMV Kit should be installed
before indoor unit which should become lower noise level.
Multi-indoor units have Pulse Motor Valve (PMV) for control refrigerant flow.
Multi-air conditioner, on unstable condition, for example starting time, flowing noise of refrigerant can be heard
conspicuously.
This refrigerant noise mainly comes from PMV. Especially ve ry quiet room, for example bed room, somebody
feels uncomf ortable for this refrigerant noise from PMV.
Main purpose of PMV Kit restrains refrigerant noise which comes from PMV installed in indoor unit.
PMV Kit should be installed at out of residence area, for e xample back of ceiling board.
After installed PMV Kit, control function of refrigerant shifts to PMV of PMV Kit and PMV in indoor unit does not
be used.
After that, refrigerant noise of PMV will be coming from back ceiling board, and refrigerant noise of indoor unit
may be restrained.
[Image of installation]
Without PMV KitWith PMV Kit
To
outdoor unit
Refrigerant pipe
[Living space]
gobo... gobo....
Shuru shuru...
[Underpart of the roof]
CeillingCeilling
Indoor unit
8-2. How to Use
Connect PMV Kit between refrigerant pipe of indoor unit.
Connect control cable of PMV Kit to control
P.C. board of indoor unit, then PMV Kit is
controlled by indoor unit side.
But, before connecting PMV Kit to
P.C. board of indoor unit, PMV of
indoor unit should be fully opened.
Heat insulating pipe
Binding band M
Binding band L
Refrigerant pipe
(Liquid side)
To
outdoor unit
Binding band M
PMV Kit
Refrigerant pipe (Liquid side)
gobo... gobo....
Shuru shuru...
[Living space]
Refrigerant noise is small.
Binding band M
Connection cable
[Underpart of the roof]
Indoor unit
Binding band L
Binding band M
Refrigerant pipe
(Gas side)
79
Heat insulating pipe
Refrigerant pipe
(Liquid side)
1st revised : Jun. 2006
8-3. Effect of Connecting PMV Kit without Fully Opening of
Indoor Unit PMV
Effect of miss-installation which PMV of indoor unit was not fully opened (1500 pulse) are as follows.
Following symptom occurred, PMV of indoor unit should be fully opened.
1. Cooling operation
1) Even though command of PMV is fully open (1500 pulse), actual SH is larger than aim SH.
2) Even though command of PMV is fully open (1500 pulse), cool air does not discharge.
3) Ps is abnormally low, or outdoor unit stops by Ps protection.
2. Heating operation
1) Even though command of PMV is fully open (1500 pulse), actual UC is larger than aim UC.
2) Even though command of PMV is fully open (1500 pulse), hot air does not discharge.
3) Pd is abnormally high, or outdoor unit stops by Pd protection.
8-4. How to Fully Open PMV of Indoor Unit
1. Stop indoor and outdoor units operation and turn off power supply to each units.
2. Remove connection cable of PMV Kit from P.C. board of indoor unit and connect PMV of indoor unit to P.C.
board.
Pulse motor valve (PMV)
(Indoor unit side)
PMV
PMV Kit
Connection cable
Remove
Indoor unit
PMV lead wires
Connect
CN82 connector
Indoor control P.C. board
Connector conversion cable
Note : MMK-APXXX2H (High Wall Type) does not use a this conversion cable
3. Turn on power supply of only indoor unit and fully open PMV of indoor unit.
Note : While turn on power supply of indoor unit, outdoor unit also turns on power supply, PMV of indoor unit
can not be fully opened.
4. After 2 minutes from turn on power supply of indoor unit, turn off power supply of indoor unit.
* After this work, PMV of indoor unit is fully opened. While this work, do not order of operation from remote
controller.
ON
(Over 2 minutes)
5. Remove PMV of indoor unit from P.C. board and connect connection cable of PMV Kit to P.C. board.
6. Treat wires and close electrical parts box of indoor unit.
Surely OFF
80
9. TEST OPERATION
Outdoor unit
U1 U2
U3 U4
ENL
3
4
3
4
U1 U2
U3 U4
AB
U1 U2
ENL
2
5115
AB
U1 U2
ENL
Indoor unit
Earth leakage breaker
Power supply
Power supply
Over current breaker (fuse)
Earth leakage breaker
Central control units
Remote
controller
AB
U1 U2
ENL
Other refrigerant system
Other refrigerant
system
U1 U2
U3 U4
ENL
2
9-1. Procedure and Summary of Test Operation
A test operation is executed in the following procedure. When a trouble or an error occurs in each step, remove
causes of a trouble or an error referring to the section “9. T roubleshooting”.
Check before test operation
Check the basic items, mainly the installation work.
Be sure to enter the check results in the check list 1 and 2.
2. In case that a central control system is connected (Before address setup)
9-2. Check Items before Test Operation
Prior to the test operation, check the following items so that there is no trouble in the installation work.
Main check items for electric wiring
81
The communication system differs from
that of R22 or R407 refrigerant
“Modular Multi system”
air conditioner.
Check again cautious points on wiring.
1. In case that a center control
No.
Note) The above figure does not show all the electric cables.
Check the main power supply
is turned on.
Set up the addresses.
Test operation
END
system is not connected:
Are indoor and outdoor communication lines of the outdoor unit connected to U1/U2
terminals?
Is the relay connector between U1/U2 terminal and U3/U4 terminal removed?
(Set up at shipment from the factory)
Is the terminator resistor (SW30-2) on the interface P.C. board of the outdoor unit
turned on? (Set up at shipment from the factory)
Is the end terminal of the shield cable grounded?
For details, refer to the installation manuals for outdoor unit, indoor unit, remote controller, or optional de vices.
It is the check after the power has been turned on.
Check the refrigerant circuit system is normally turned on.
Start the address setup in the outdoor/indoor units.
(NOTE) The operation does not start by only power-ON.
Carry out a test operation.
Check air blowing and cooling/heating operation in the indoor unit.
ENL
ENL
Remote
controller
U1 U2
U1 U2
AB
3
U3 U4
ENL
Over current breaker (fuse)
Earth leakage breaker
Power supply
Earth leakage breaker
Power supply
Main check items
Outdoor unit
Indoor unit
2
41
U1 U2
AB
Check
No.
Are indoor and outdoor communication lines of the outdoor unit connected to U1/U2
terminals?
Is the relay connector between U1/U2 terminal and U3/U4 terminal removed?
U1 U2
AB
ENL
(Set up at shipment from the factory) (Before address setup, remove the relay connector.)
Is the communication line of the central control system connected to the outdoor unit
U3/U4 terminals of each refrigerant line?
(The communication line of the central control system may be connected to the communication lines of the indoor/outdoor communication lines.)
Is the terminal resistance (SW30-2) on the interface P.C. board of the outdoor unit turned on?
(Set up at shipment from the factory)
(After address setup, turn off SW30-2 of the outdoor unit except the smallest unit after
check of trial operation.)
Is the end terminal of the shield cable grounded?
When the refrigerant line and the central control system of the 1 : 1 air conditioner
(DI, SDI) are connected:
→ Are “1 : 1 model” connection interface (TCB-PCINTLE2) adaptors correctly connected?
→ When the digital inverter air conditioner operates with group operation, twin, operation,
are the adopters connected to the header unit of the indoor unit?
Main check items
Check
Note) The above figure does not show all the electric cables.
For details, refer to the installation manuals for outdoor unit, indoor unit, remote controller, or optional
devices.
Check list 1
Additional
refrigerant charge
amount at site
R
(kg)
Real length
of liquid pipe
=×+
Additional refrigerant charge
amount per liquid pipe 1m
(Table 1)
Compensation
by outdoor HP
(Table 2)
• Using the “Check list 1”, check there is no trouble in the installation work.
Is capacity of the leak breaker appropriate? Outdoor total capacity XXXX AIndoor unit XXXX A
Is the diameter of the power cable correctly wired?Outdoor unit (A) XXXX mm²Indoor unit XXXX mm²
Is the control communication line correctly wired?Indoor –outdoor connection ter minals (U1, U2)XXXX
Is the power of the indoor units supplied collectively?
Is the earth grounded
Is the insulation good? (10MΩ or more)XXXX MΩ or more
Is the main power voltage correct? ( ± 10%)XXXX V
Is the diameter of the connecting pipe correct?
Is the branch kit correct?
Does the indoor unit condensate drain adequately?
Is the thermal insulation of pipes good? (Connecting pipes, Branch kit)
For both indoor and outdoor units, ensure air is not short-circuited from discharge to inlet ports.
After pressure test, check that the pipework and indoor units have been v acuumed and the correct amount of additional gas has been charged.
Are valves of all the outdoor units fully opened?Gas sideLiquid side
outdoor unit (A)
• Check the additional amount of refrigerant.
82
Central control system connection terminals (U3, U4)
XXXXXXXX
XXXX
Check list 2
Calculate the additional amount of refrigerant from the following:
Firstly enter the total length for each liquid pipe in the following tab le and then calculate the additional amount of
refrigerant by pipe length.
(Table 1) Additional amount of refrigerant by pipe length
Pipe dia at
liquid side
Next, refer to the following table for the corrective amount of refrigerant (B) by system capacity.
(Table 2) Compensation by outdoor HP
Standard amount of refrigerant
Ø6.4
Ø9.5
0.025 ×
0.055 ×
Outdoor unit capacity type
0401 type
0501 type
0601 type
kg/m
Total pipe length at each liquid side
=
=
Additional amount of refrigerant by pipe
length (A)
Compensation by outdoor HP kg
Additional amount of refrigerant pipe
dia at each liquid side kg
–0.8
–0.4
0
kg
kg
kg
Finally add the additional amount of refrigerant by pipe length (A) to the corrective amount of refrigerant by
system capacity (B). This is the final additional amount of refrigerant.
If the result is indicated as a negative, do not add any refrigerant. Do not add the refrigerant (= 0kg).
Additional refrigerant charge amount at site (R)
Additional amount of refrigerant by pipe length (Table 1)
Compensation by outdoor HP(Table 2)
Additional amount of refrigerant(R)
kg
kg
kg
9-3. Check at Main Po wer-ON
Interface P.C. board
SW01SW02
Rotary switches
SW03
7-segment
display [A]
Push-switch
SW04
Push-switch
SW05
Push-switch
SW15
7-segment
display [B]
After turning on the main power of the indoor units and outdoor unit in the refrigerant line to be executed with a
test operation, check the following items in outdoor and each indoor unit.
(After turning on the main power, be sure to check in order of indoor unit
→→
→ outdoor unit.)
→→
If the power supply of the outdoor unit has been firstly turned on, [E19] appears on the 7-segment display on
the interface P.C. board until the power supply of the indoor unit is turned on. However it is not an error.
Check on outdoor unit
1. Check that all the rotary switches, SW01, SW02, and SW03 on the interface P.C. board of the outdoor unit
are set up to “1”.
2. If other error code is displayed on 7-segment [B], remove the cause of trouble referring to
“9. T roubleshooting”.
3. Check that [L08] is displayed on 7-segment display [B] on the interface P.C. board of the outdoor unit.
(L08: Indoor address unset up)
(If the address setup operation has already finished in service time, etc, the above check code is not displayed, and only [U1] is displa yed on 7-segment display [A].)
Interface P.C. board
7-segment display [A]
7-segment display [B]
83
SW01 SW02SW03
Check on indoor unit
1. Display check on remote controller (In case of wired remote controller)
Check that a frame as shown in the following left figure is displayed on LC display section of the remote
controller.
GOOD
TEMP.
TIMER SET
FILTER
TEST
RESET
ON / OFF
FAN
MODE
SWING/FIXTIME
VENT
UNITSET CL
NO
GOOD
TEMP.
TIMER SET
FILTER
TEST
RESET
ON / OFF
FAN
SWING/FIXTIME
UNITSET CL
9-4. Address Setup
After power-ON, set up the indoor address from the interface P.C. board of the outdoor unit.
(The address setup operation cannot be performed by power-ON only.)
9-4-1. Cautions
1. It requires approx. 5 minutes usually for 1 line to automatically set up address.
However in some cases, it may require maximum 10 minutes.
2. It is unnecessary to operate the air conditioner for address setup.
3. Manual address setup is also available besides automatic setup.
Automatic address: Setup from SW15 on the interface P.C. board of the outdoor unit
Manual address: Setup from the wired remote controller.
(For details, ref er to section “9-4-3. Address setup procedure”)
9-4-2. Address Setup and Check Procedure
Procedure
1
2
3
4
5
6
MODE
VENT
Item
Indoor unit power-ON
Outdoor unit power-ON
7-segment display
check
Address setup start
Display check after
setup
System information
check after setup
Operation and check contents
Turn on power of indoor unit in refrigerant line to which address is set up.
Turn on power of all the outdoor units in refrigerant line to which address is set up.
Check that [L08] is displayed on 7-segment display [B] on the interface P.C. board of the
outdoor unit in the system to which address is set up.
Confirm the corresponding items in “8-4-3 Address setup procedure”, and then set up address
according to the operation procedure.
(Be sure that the setup operation may differ in group control or central control.)
Note) Address cannot be set up if switches are not operated.
• After address setup, [U1] [ ] are displayed in 7-segment display section.
• If an error code is displayed in 7-segment display [B], remove the cause of trouble referring to
“9. Troubleshooting”.
Using 7-segment display function, check the system information of the scheduled system.
(This check is executed on the interface P.C. board of the outdoor unit.)
Rotary switch setup
System capacity
No. of connected outdoor unit
No. of connected indoor units
After the above checks, return rotary switches SW01, SW02, SW03 to 1/1/1.
SW01 SW02 SW03
123
133
143
7-segment display
[A][B]
[No. of HP][HP]
[Connected No. of units][
[Connected No. of units]
P]
If a frame is not displayed as shown in the above right figure, the power of the remote controller is not normally
turned on. Therefore check the following items.
• Check power supply of indoor unit.
• Check wiring between indoor unit and remote controller.
• Check whether there is cutoff of cable around the indoor control P.C. board or not, and check connection
• Check failure of transformer for the indoor microcomputer.
• Check indoor control P.C. board failure.
failure of connectors.
Normal status
(Power and operation stop)
Abnormal status
(Power is not normally turned on.)
9-4-3. Address Setup Procedure
SW11
1
ON
Outdoor unit interface P.C. board
2 3 4
SW12
1ON2 3 4
SW06
1ON2 3 4
SW07
1
ONONONON
2 3 4
SW09SW08
112 3 4
SW10
1 2 3 4
SW13
1ON2 3 4
SW14
1ON2 3 4
In this air conditioner, it is required to set up address to the indoor unit before starting operation. Set up the address according to the following setup procedure.
1. Set up address after wiring work.
2. It requires maximum 10 minutes (Usually, approx. 5 minutes) to set up automatically an address to 1 line.
3. To set up an address automatically, the setup at outdoor side is necessary.
(Address setup cannot be performed by power-ON only.)
4. To set up an address, it is unnecessary to operate the air conditioner.
5. Manual address setup is also available besides automatic setup.
Automatic address : Setup from SW15 on the interface P.C. board of the outdoor unit
Manual address: Setup from the wired remote controller
∗ It is temporarily necessary to set the indoor unit and wired to 1 : 1.
(In group operation and in time without remote controller)
Automatic Address Setup
Without central control : To the address setup procedure 1
With central control: To the address setup procedure 2
(Example)
84
Address setup procedure
Cable systematic diagram
Address setup procedure 1
1. Turn on power of indoor/outdoor units .
(In order of indoor
After approx. 1 minute, check that U. 1. L08 (U. 1. flash)
2.
is displayed in 7-segment display section on the interface
P.C. board of the outdoor unit.
3. Push SW15 to start the setup of the automatic addressing.
(Max. 10 minutes for 1 line (Usually, approx. 5 minutes))
When the count Auto 1 → Auto 2 → Auto 3 is displayed
4.
in 7-segment display section, and it changes from
U. 1. - - - (U. 1. flash) to U. 1. - - - (U. 1. light) , the setup
finished.
5. When performing an automatic address setup on a
single refrigerant line with central control, connect
relay connected between [U1, U2] and [U3, U4]
terminals.
CAUTION
(However, go to the procedure 1 when the central control is performed in a single refrigerant line.)
In case of central control in a single refrigerant line
To procedure 1
Outdoor
remote controller
IndoorIndoor
Remote
Remote
controller
controller
Central
Outdoor
remote controller
IndoorIndoor
Remote
controller
Central
In case of central control over refrigerant lines
To procedure 2
Outdoor
IndoorIndoor
Remote
Remote
controller
controller
Outdoor
IndoorIndoor
Remote
controller
Outdoor unit interface P.C. board
SW04
→→
→ Outdoor)
→→
SW05 SW15
D600 D601 D602 D603 D604
SW01
SW02 SW03
111
5
U1 U2
For internal
wiring between
indoor and
outdoor
For wiring of
central control
system
Central
remote controller
3
2, 4
U3 U4
REQUIREMENT
• When a group control is performed over the
multiple refrigerant lines, be sure to turn on the
power supplies of all the indoor units connected
in a group at the time of address setup.
(Example)
Cabling
systematic
diagram
Group control over
multiple refrigerant lines
Outdoor
Outdoor
• If turning on the power for each refrigerant line
to set up address, a header indoor unit is set for
each line. Therefore, an alarm code “L03”
IndoorIndoor
IndoorIndoor
(Duplicated header indoor units) is output in
operation after address setup. In this case,
change the group address from the wired
remote controller for only one outdoor unit is set
up.
Remote
controller
Address setup procedure 2
1. Using SW13 and 14 on the interface P.C. board of the
outdoor unit in each system, set up the address for each
system. (At shipment from factory: Set to Address 1)
Note) Be careful not to duplicate addresses with the other
refrigerant line.
Line address switch on outdoor interface P.C. board(¡: Switch ON, × : Switch OFF)
Line
address
1
2
3
4
5
6
7
8
9
10
11
12
13
14
SW13SW14
12341234
ЧЧЧЧЧ
Ч
ЧЧ¡ЧЧ
Ч
ЧЧЧ¡Ч
Ч
ЧЧ
Ч
ЧЧЧЧ
Ч
ЧЧ¡Ч
Ч
ЧЧЧ
Ч
×××
¡
¡¡
¡
¡¡¡
¡
¡¡×¡
¡
××
×
¡
¡¡
××
¡¡
×
¡¡
×
×
×
¡
¡
¡
Line
address
15
16
17
18
19
20
21
22
23
24
25
26
27
28
: Is not used for setup of system address. (Do not change setup.)
2. Check that the relay connectors between [U1, U2] and [U3,
U4] terminals are not connected in all the outdoor units to
which the central control is connected.
(At shipment from factory: Connector not connected)
3. Turn on power of indoor/outdoor.
(In order of indoor
→→
→ outdoor)
→→
4. After approx. 1 minute, check that 7-segment display is
U.1.L08 (U.1. flash) on the interface P.C. board of the
outdoor unit.
5. Push SW15 to start the setup of automatic addressing.
(Max. 10 minutes for 1 line (Usually, approx. 5 minutes))
When the count Auto 1
6.
→→
→ Auto 2
→→
→→
→ Auto 3 is displayed in
→→
7-segment display section, and it changes from
U. 1. - - - (U. 1. flash) to U. 1. - - - (U. 1. light) , the setup
finished.
7. Procedure 4. to 6. are repeated in other refrigerant lines .
SW13SW14
12341234
××
×
¡
¡¡
¡
¡¡¡
¡
¡¡×¡
¡
¡¡¡¡
¡
¡¡
¡
¡¡¡×¡
U1 U2
2
For internal
wiring between
indoor and
outdoor
¡¡¡
¡¡¡¡
××××
×××
×
×ס×
×
×××
×
××
¡
××
¡¡
××
×
¡
U3 U4
For wiring of
central control
system
×
×
×
¡
¡
¡
1st revised : Jun. 2006
8. When address setup has finished in all the sysem, turn off
ON / OFF
FAN
TEMP .
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
Operation procedure
1 ® 2 ® 3 ® 4 ® 5 ® 6
®
7 ® 8 ® 9 ® 10 ® 11
End
11
4, 7, 10
2, 5, 8
3, 6, 9
1
DataItem code
Outdoor
Header
#1
Indoor Indoor Indoor
Line address 1
Indoor address
1
Group address
1
Outdoor
#2
Indoor Indoor
Follower
1
2
2
1
3
2
2
1
2
2
2
2
Remote
controller
SW30-2 on the interfase P.C. boards of the lines connected to
the identical central control except a line with least line
address number.
(Terminator resistors of the wires in the central control line of
indoor/outdoor are unified.)
9. Connect the relay connector between [U1U2] and [U3U4]
terminals of the outdoor unit for each refrigerant line.
10. Then set up the central control address.
(For the central control address setup , refer to the Installation
manual of the central control devices.)
Before address setup
During setup of address
85
After address setup
Outdoor interface
P.C. board
SW13, 14
(Refrigerant line address)
SW30-2
Terminal-end resistance
of indoor/outdoor communi
cation line/central control
communication line
Relay connector
Indoor side (Automatic setup)
Refrigerant line address
Indoor unit address
Group address
Never connect a rela y connector until address setup for all the refrigerant lines has been completed ;
otherwise address cannot be correctly set up.
Relay
connector
Outdoor unit interface P.C. board
1ON2 3 4
1ON2 3 4
SW11
SW12
ONONONON
1ON2 3 4
1
2 3 4
SW06
SW07
123
Outdoor
unit
U3 U4
U1 U2 U5 U6
Relay
connector
U1 U2
Outdoor
unit
U1 U2 U5 U6
U1 U2
U1 U2
A B
Remote
controller
U3 U4
A B
Remote
controller
Outdoor unitOutdoor unitOutdoor unit
Connect short
after address setup
1
1
0
A B
Remote
controller
IndividualGroup
21
ON
SW30
OFF
Relay
connector
U1 U2
A B
Remote
controller
IndividualGroup
12
ON
1
2
0
Outdoor unit
U3 U4
U1 U2 U5 U6
U1 U2
U1 U2 U5 U6
U1 U2
U1 U2
A B
Remote
controller
U3 U4
A B
Remote
controller
address setup
Connect short
after address setup
A B
Outdoor unitOutdoor unit
21
ON
SW30
OFF
U1 U2
A B
OFF after
2
1
1
Note
Outdoor unit
U3 U4
U1 U2 U5 U6
U1 U2
A B
Remote
controller
U3 U4
SW30
U1 U2 U5 U6
U1 U2
A B
Remote
controller
OFF after
address setup
Connect short
after address setup
2
2
2
Relay
connector
21
ON
OFF
Relay
connector
31
3
1
0
1ON2
SW30
1ON2 3 4
1ON2 3 4
SW13
SW14
112 3 4
SW09SW08
Setup at shipment
from factory
Open
SW30
1 2 3 4
SW10
ON
Manual address setup from remote controller
In case to decide an address of the indoor unit prior to finish of indoor wiring work and unpracticed outdoor
wiring work (Manual setup from remote controller)
Arrange one indoor unit and one remote
controller set to 1 by 1.
Turn on the power.
(Wiring example in 2 lines)
In the above example, under condition of
no inter-unit wire of the remote controller,
set the address after individual connecting of the wired remote controller.
Group address
Individual: 0000
Header unit : 0001
Follower unit : 0002
} In case of group control
1
Push simultaneously
SET
for 4 seconds or more.
LCD changes to flashing.
(Line address)
2
Using the setup temp. / buttons,
set
to the item code.
3
Using the timer time / buttons, set up
the line address.
(Match it with the line address on the interface
P.C. board of the outdoor unit in the identical
refrigerant line.)
Push
SET
button.
4
(OK when display goes on.)
(Indoor address)
5
Using the setup temp. / buttons,
! to the item code.
set
6
Using the timer time / buttons, set up
the indoor address.
Push
SET
button.
7
(OK when display goes on.)
(Group address)
8
Using the setup temp. / buttons,
set
" to the item code.
9
Using the timer time / buttons, set
Individual =
Follower unit =
10
Push
, Header unit = ,
.
SET
button.
(OK when display goes on.)
Push
TEST
button.
11
Setup operation finished.
(Status returns to normal stop status.)
+ CL +
TEST
buttons
Note 1)
TEST
UNIT
Operation procedure
1 ® 2 ® 3 ® 4 ®
5
®
6 ® 7 ® 8
End
Operation procedure
1 ® 2 ® 3 ®
4
®
5 ® 6
End
2,
6,
7
4
5
6
1
3
2
4
ON / OFF
FAN
TEMP .
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
3
5
8
1
ON / OFF
FAN
TEMP .
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET
CODE No.
UNIT No.
SETTING
DATA
SET
R.C. No.
When setting the line address from the remote controller, do not use address 29 and 30.
The address 29 and 30 cannot be set up in the outdoor unit. Therefore if they are incorrectly set up, a check
code [E04] (Indoor/outdoor communication circuit error) is output.
Confirmation of indoor unit address and position by using the remote controller
[Confirmation of indoor unit address and the position]
1. When you want to know the indoor address though position of the indoor unit itself can be
recognized;
<Procedure> (Operation while the air conditioner operates)
1
If it stops, push
2
Push
The unit No. 1-1 is displayed on the LCD.
(Disappears after several seconds) The displayed
unit No indicates the line address and indoor
address. (If there is other indoor unit connected
to the same remote controller (Group control
unit), other unit No. is displayed every pushing
86
2. When you want to know position of the indoor unit using the address
• To confirm the unit numbers in a group control;
<Procedure> (Operation while the air conditioner stops)
The indoor unit numbers in a group control are successively displayed, and the corresponding indoor fan is
turned on. (Operation while the air conditioner stops)
1
Push
4 seconds or more.
• Unit No. is displayed.
• The fans of all the indoor units in a group
2
Every pushing
numbers in the group control are successively displayed.
• The firstly displayed unit No. indicates the
• Only fan of the selected indoor unit is turned
3
Push
All the indoor units in group control stop.
ON / OFF
button.
UNIT
UNIT
button.)
VENT
TEST
+
buttons simultaneously for
control are turned on.
UNIT
address of the header unit.
on.
TEST
button to finish the procedure.
button, the indoor unit
button.
1
Operate
2
1
3
End
2
CODE No.
UNIT No.
FILTER
RESET
TEMP .
TIMER SET
TEST
ON / OFF
FAN
MODE
SWING/FIXTIME
VENT
UNITSET CL
Operation procedure
1 ® 2
UNIT No.
R.C. No.
CODE No.
ON / OFF
FAN
MODE
SWING/FIXTIME
VENT
UNITSET CL
End
DATA
SET
SETTING
TEMP .
TIMER SET
FILTER
TEST
RESET
Operation procedure
1 ® 2 ® 3
• To confirm all the unit numbers from an arbitrary wired remote controller;
<Procedure> (Operation while the air conditioner stops)
The indoor unit No. and position in the same refrigerant line can be confirmed.
An outdoor unit is selected, the indoor unit numbers in the same refrigerant line are successively display ed,
and then its indoor unit fan is turned on.
1
Push the timer time +
Firstly, the line 1, item code )+ (Address Change) is displayed. (Select outdoor unit.)
UNIT
2
Using
+
SWING/FIX
buttons simultaneously for 4 seconds or more.
buttons, select the line
address.
Using
SET
button, determine the selected line
3
address.
• The indoor unit address, which is connected to the
refrigerant pipe of the selected outdoor unit is displayed and the f an is turned on.
4
Every pushing
UNIT
button, the indoor unit
numbers in the identical pipe are successively
displayed.
• Only fan of the selected indoor unit operates.
[To select another line address]
5
Push CL button to return to procedure 2 ).
• The indoor address of another line can be succes-
sively confirmed.
6
TEST
Push
button to finish the procedure.
Change of indoor address from remote controller
Change of indoor address from wired remote controller
• To change the indoor address in individual operation (Wired remote controller : Indoor unit = 1 : 1) or
group control (When the setup operation with automatic address has finished, this change is a vailable.)
<Procedure> (Operation while air conditioner stops)
1
Push simultaneously
(The firstly displayed unit No. indicates the header unit in group control.)
2
In group control, select an indoor unit No. to be changed by
(The fan of the selected indoor unit is turned on.)
3
Using the setup temp. / buttons, set !
SET
to the item code.
4
Using the timer time / buttons, change the
displayed setup data to a data which you want
to change.
5
6
SET
Push
Using the
button.
UNIT
button, select the unit No. to be
changed at the next time. Repeat the procedure
4
to 6 and change the indoor address so that it
is not duplicated.
7
After the above change, push
confirm the changed contents.
8
If it is acceptable, push
confirmation.
TEST
+ CL +
TEST
buttons for 4 seconds or more.
UNIT
button to
button to finish
button.
• To change all the indoor addresses from an arbitrary wired remote controller;
U3 U4
U1 U2 U5 U6
U1 U2
A B
Outdoor unit
Remote
controller
U1 U2
A B
Remote
controller
U3 U4
U1 U2 U5 U6
U1 U2
A B
Remote
controller
U1 U2
A B
U3 U4
U1 U2
U1U3U2
U4
U5 U6
U1 U2
A B
Remote
controller
Center unitCenter unitOutdoor unitOutdoor unit
Central control
device
Unit of which address is to be returned to the initial status
(When the setup operation with automatic address has finished, this change is availab le.)
Contents: Using an arbitrary wired remote controller, the indoor unit address can be changed for each same
refrigerant line
∗∗
∗ Change the address in the address check/change mode.
∗∗
<Procedure> (Operation while air conditioner stops)
1
Push the timer time +
TEST
buttons simultaneously for 4 seconds or more.
Firstly, the line 1, item codeAC (Address Change) is displayed.
UNIT
SET
button.
SWING/FIX
+
buttons, select the line address.
2
3
Using
Push
• The indoor unit address, which is connected to the refrigerant pipe of the selected outdoor unit is displayed and the f an is turned on.
First the current indoor address is displayed on the setup data. (Line address is not displayed.)
4
The indoor address of the setup data moves up/down by the timer time / buttons.
Change the setup data to a new address.
5
6
SET
Push
button to determine the setup data.
Every pushing
UNIT
button, the indoor unit numbers in the identical pipe are successively
displayed. Only fan of the selected indoor unit operates.
Repeat the procedure 4 to 6 and change all the indoor addresses so that they are not duplicated.
7
87
8
SET
Push
button.
(All the displays on LCD go on.)
TEST
Push
button to finish the procedure.
Clearance of address (Return to status (Address undecided) at shipment from factory)
Method 1
An address is individually cleared from a wired remote controller.
“0099” is set up to line address, indoor address, and group address data from the remote controller.
(For the setup procedure, refer to the abovementioned address setup from the remote controller.)
Method 2
Clear the indoor addresses in the same refrigerant line from the outdoor unit.
1. T urn off the power of the refrigerant line to be returned to the status at shipment, and change the outdoor
unit to the following status.
1) Remove the relay connector between [U1U2] and [U3U4].
(If it has been already removed, leave it as it is.)
2) Turn on SW30-2 on the interface P.C. board of the outdoor unit if it is OFF.
(If it has been already ON, leave it as it is.)
UNIT No.
R.C. No.
CODE No.
ON / OFF
FAN
MODE
SWING/FIXTIME
VENT
UNITSET CL
2
DATA
SET
SETTING
TEMP .
TIMER SET
1
3
Here, if the unit No is not called up, the outdoor unit in
this line does not exist.
Push
FILTER
TEST
RESET
Cancel of line selection
CL
button, and then select a line according to
procedure 2 .
4
8
DATA
SET
SETTING
UNIT No.
R.C. No.
TEMP .
FAN
TIMER SET
FILTER
TEST
RESET
5, 7
SWING/FIXTIME
UNITSET CL
To finish the set
Operation procedure
1 ® 2 ® 3 ® 4 ®
®
6 ® 7 ® 8
5
CODE No.
ON / OFF
MODE
VENT
End
6
2. Turn on the indoor/outdoor power of which address is to be cleared. After approx. 1 minute, check that
“U.1. - - -” is display ed, and then execute the follo wing operation on the interface P.C. board of the outdoor
unit of which address is to be cleared in the refrigerant line.
SW01 SW02 SW03
212
222
SW04
After checking that “A.d.buS” is displayed on 7-degment
display, and then push SW04 for 5 seconds or more.
After checking that “A.d.nEt” is displayed on 7-degment
display, and then push SW04 for 5 seconds or more.
Address which can be cleared
Line + Indoor + Group address
Central address
3. After “A.d. c.L.” has been displayed on 7-degment display, return SW01/SW02/SW03 to 1/1/1.
4. When the address clearing has correctly finished, “U.1.L08” is displayed on 7-degment display after a while.
If “A.d. n.G.” is display ed on 7-degment display, there is a possibility which is connected with the other
refrigerant line. Check again the relay connector between [U1U2] and [U3U4] terminals.
NOTE) Be careful that the other refrigerant line address may be also cleared if clearing operation is not
correctly executed.
5. After clearing of the address, set up an address again.
In case of increase the address-undefined indoor units (Extension, etc.)
Outdoor unit
U1 U2
U3 U4
ENL
2
4
U1 U2
U3 U4
AB
U1 U2
ENL
1
AB
U1 U2
ENL
Indoor unit
Earth leakage breaker
Power supply
Power supply
Over current breaker (fuse)
Earth leakage breaker
Central control units
Remote
controller
AB
U1 U2
ENL
Other refrigerant system
Other refrigerant
system
Line address = 1
U1 U2
U3 U4
ENL
4
1
Line address = 2
3
If set up the indoor address of which address is undefined accompanied with extension of indoor units, replacement of P.C. board, etc, follow to the methods below.
Method 1
Set up an address individually from a wired remote controller.
(Line address, Indoor address, Group address, Central address)
For the setup method, refer to the above “Manual address setup from remote controller”.
Method 2
Set up an address from the outdoor unit.
∗ Leave the address of the unit of which address has been already set up as it is.
Set up an address only to the unit of which address is undefined.
The addresses are allocated from the low number.
Setup procedure
Arrange the outdoor units in the refrigerant line to which indoor units are added. (Figure below)
1. Remove the relay connector between [U1U2] and [U3U4].
2. T urn on SW30-2 on the interf ace P.C. board at outdoor unit side if it is OFF.
∗ Turn off the power, and then execute the oper ation.
Central control
88
Outdoor unit
U1 U2
U3 U4
Outdoor unitOutdoor unit
U1 U2
U3 U4
U1 U2
U3 U4
U5 U6
device
U1U3U2
9-4-4. Check after Ad dress Setup When Central Control System is Connected
When the central control system is connected, check the following setup has finished after address setup.
U4
3. Turn on the indoor/outdoor power of which address is to be set up. After approx. 1 minute, check that
4. Execute the following operation on the interface P.C. board of the outdoor unit.
5. When “U.1. - - -” is displayed on 7-segment display, the setup operation finished.
6. Return the following setup as before.
U1 U2
controller
A B
Remote
U1 U2
A B
Remote
controller
Added indoor unit
“U.1. - - -” is display ed on 7-segment display.
SW01 SW02 SW03
2142
“AUTO1” → “A UT O2” → “AUTO3” →
After checking that “ ” is displayed on 7-segment
display, and then push SW04 for 5 seconds or more.
…
• Return the SW01, 02, 03 setup as before.
Turn off the indoor/outdoor power.
• Relay connector
• SW30-2
U1 U2
controller
A B
Remote
SW04
U1 U2
A B
U1 U2
A B
Remote
controller
→ “AUTO9” … is counted and displayed on 7-degment display.
Main check items
Check
Relay
connector
Terminal
resistance
Line address
No.
Is relay connector of the outdoor unit connected after address setup?
Q
Is the terminal resistor (SW30-2) of the outdoor unit with the least
R
refrigerant line address number (in the central control line) turned on?
Are the terminal resistor (SW30-2) of the outdoor units except for the
line of which central control refrigerant line address is the smallest,
S
turned off?
Are not addresses in the line address (SW13, SW14) duplicated in
T
each refrigerant line?
Note) The above table does not describe all the electric cablings. For details, refer to each installation manual
for outdoor unit, indoor unit, remote controller, and optional devices.
1st revised : Jun. 2006
1st revised : Jun. 2006
9-5. Troubleshooting in T est Operation
If the phenomena appear, such as a check code is output or the remote controller is not accepted in power-ON
after cabling work or in address setup operation, the following causes are considered.
9-5-1. A check Code is Displayed on the Remote Controller
Check code
displayed on
remote controller
E04
Outdoor unit
7-segment
display
E19-00
L08
E08-XX
Cause
Outdoor power is formerly turned on.
There is none of outdoor terminator resistor.
(After address setup)
ON
2
After address was decided, all the
indoor units do not correctly response
after power-ON in outdoor unit.
Address setup error
• Only line addresses of the connected indoor units
are undefined.
• The outdoor line address and the line addresses in
all indoor units do not match.
• The indoor addresses are duplicated.
(Units except those displaying E04 are duplicated.)
• A header unit is not set up in a group.
(Except group displaying E04)
Duplication of indoor addresses.
(Address No in which sub-code of the check code
are duplicated)
1
SW30
Countermeasures
Turn on the power again.
(In order of Indoor → Outdoor)
Check SW30 bit 2 of the outdoor unit.
No connection between multiple refrigerant lines:
SW30 bit 20N
Connection between multiple refrigerant lines:
SW30 bit 2 of the connected outdoor unit is turned
on only in one line.
Check and modifies disconnection of indoor/outdoor
communication line.
(Communication line the leading indoor unit)
Check influence of communication noise.
Set up address again.
Set up address again.
E16
E25
L04
L05 (∗)
L06 (∗)
L08
E07
E06
E16-XX
E25
L04
L06
L08
There is none of outdoor terminal
resistance, or there are two or more
resistances.
(After address setup, when terminal
resistance setup is changed after
power-ON.)
Transmission circuit error at interface side
(P.C. board failure)
After address setup, communication from all the
indoor units interrupted under condition that a
normal operation can be performed.
Exceeded No of connected indoor units or
exceeded capacity.
Duplication of outdoor addresses.
(Only when outdoor address was manually set up)
Duplication of outdoor line addresses
• Line address setup error, occurred after connection between U1, U2 and U3, U4 connectors
Duplicated of indoor units with priority
There are two or more indoor units set up with
priority.
Address setup error
• Only indoor addresses of all the connected indoor
units are undefined.
ON
1
SW30
2
Check SW30 bit 2 of the outdoor unit.
No connection between multiple refrigerant lines:
SW30 bit 20N
Connection between multiple refrigerant lines:
SW30 bit 2 of the connected outdoor unit is turned
on only in one line.
Replace the interface P.C. board.
Check and correct disconnection of indoor/outdoor
communication line.(Communication line between
outdoor unit and the leading indoor unit)
Check influence of communication noise.
Adjust No of connected indoor units or capacity.
Do not use a manual setup for outdoor address.
Modify line address setup of the outdoor unit
between lines. (Set up SW 13 and 14 on the
interface P.C. board.)
The Heat Recovery Multi is not set up on priority.
Set up address again.
(∗) [L05]: Displayed on the indoor unit set up with priority
[L06]: Displayed on the indoor unit except one set up with priority
89
1st revised : Jun. 2006
9-5-2. Operation from remote controller is not accepted and a c heck code is dis-
played on 7-segment displa y of the interface P.C. board of the outdoor unit.
Remote
controller status
No response
7-segment
display of
outdoor unit
L08
E19-00
E20-01
Cause
Line addresses and indoor addresses of all the connected
indoor units are unset.
There is no outdoor unit of group control.
Indoor unit power is not turned on.
Indoor/outdoor communication line is not correctly connected
to the outdoor unit. (Fig. 1)
(Indoor/outdoor cannot communicate before address setup.)
There is none of outdoor terminator resistor,
or there are two or more resistances.
(Before address setup)
Address setup is performed with connecting indoor/outdoor
communication line. (Fig. 3)
Address setup is performed under condition of connecting
between multiple refrigerant lines. (Fig. 3)
ON
1
SW30
2
Countermeasures
Set up addresses.
Set up group address.
Turn on the power again.
(In order of indoor → outdoor)
Correct wiring.
Check SW30 bit 2 of the outdoor unit.
No connection between multiple refrigerant lines:
SW30 bit 2 0N
Connection between multiple refrigerant lines:
SW30 bit 2 of the connected outdoor unit is
turned on only in one line.
Correct wiring.
Correct wiring.
9-5-3. There is no display of a check code on 7-segment display on the interface
P.C. board of the outdoor unit though there is indoor unit which does not
accept the operation from the remote controller.
Remote
controller status
No response
No display on
remote controller
(No line is output.)
7-segment
display of
outdoor unit
None
None
Cause
Communication line is not connected between indoor and
outdoor.
Line and indoor addresses are unset.
(Unit which does not response to remote controller)
The power of the header unit of the group is not turned on in
indoor group control.
(Unit which does not response to remote controller)
Group address is set up to follower unit in the individual
control. (Unit which does not response to remote controller)
The power is not turned on.
(Unit which is not displayed on remote controller)
Remote controller is not connected with cable.
(Unit which is not displayed on remote controller)
Miscabling of remote controller
(Unit which is not displayed on remote controller)
Remote controller communication circuit error
(Unit which is not displayed on remote controller)
If 230V is incorrectly applied to the remote controller terminal,
the remote controller communication circuit fails.
Countermeasures
Modify wiring.
Set up address.
Turn on the power.
Set [0] to group address in case of individual
control.
Turn on the power.
Correct wiring.
Correct wiring.
Remove FASTON terminal connected to remote
controller terminals (A/B), and check the voltage.
If voltage is not applied, replace P.C. board.
(15 to 18V usually)
9-5-4. In check for No. of connected Indoor units after address setup,
diminished No. of connected units displayed.
(There are outdoor/indoor units which do not operate in a test operation.)
Status
Number of
connected is short.
Number of
connected indoor
units is short.
Number of outdoor
units connected to
group is short in
group operation
from remote
controller.
Miswiring of communication line unconnected cable (Fig. 4)
(Address setup operation has finished
without recognition of miswired follower unit.)
Miswiring of communication line between
indoor units or unconnected cable (Fig. 5)
(Address setup operation has finished
without recognition of miswired indoor unit.)
Remote controller is not connected with wire.
Miscabling of remote controller
Remote controller communication circuit
error
If 230V is incorrectly applied to the remote
controller terminal, the remote controller
communication circuit fails.
Cause
Countermeasures
After modification of wiring, set up address again and check No. of the
connected outdoor units.
After modification of wiring, set up address again and check No. of the
connected indoor units.
Using the main remote controller connected to a group, start a test operation,
specify the unit which does not operate (Unit unconnected to group), and then
check wiring.
Using the main remote controller connected to a group, start a test operation,
specify the unit which does not operate (Unit unconnected to group).
Remove Fasten receptacle connected to remote controller terminals (A/B),
and check the voltage. If voltage is not applied, replace P.C. board.
(15 to18V in normal time)
90
Incorrect wiring example
(Fig. 1)
1st revised : Jun. 2006
Remote
controller status
No response
Outdoor unit
7-segment display
E19-00
(Fig. 2)
Status
Number of connected outdoor units is short.
Outdoor unit
U3/U4
Indoorunit
Outdoor unit
U1/U2
Indoorunit
Incorrect
Indoorunit
Incorrect example
A/B
Indoorunit
example
Outdoor unit
Indoorunit
U1/U2
Indoorunit
91
9-6. Test Operation Check
9-6-1. Fan Operation Check
START
Push [START/STOP] button.
Select the operation mode [FAN].
Is air discharged from the
discharge port of the indoor unit?
YES
Is there any abnormal noise?
YES
Normal
Check all indoor units in turn.
NO
NO
When an error code has been displayed on the remote
controller, refer to Section 8-5-1.
Check indoor fan, fan motor and fan circuit.
(Ensure power has been isolated before removing any covers.)
Check for items in contact with fan.
(Ensure power has been isolated before removing any covers.)
9-6-2. Cooling/Heating Test Operation Check
The cooling/heating test operation check can be perf ormed on both remote controller and outdoor interf ace P.C.
board.
1. Test operation start/stop operation
Test operation from remote controller
Wired remote controller
1
When pushing
TEST
button for 4 seconds or more,
[TEST] is displayed in the display section and the
mode enters the test operation mode.
1,
TEST
5
2
Push
3
Using
• Do not use any other operation modes, only [COOL] or [HEAT].
• Temperature adjustment is unavailable during test operation.
• Errors are detected as usual.
4
When the test operation has finished, push
The same display as that in procedure 1 appears.
5
Push
[TEST] display disappears and the status returns to the normal stop status.
ON / OFF
MODE
TEST
button to clear the test operation mode.
button.
button, select an operation mode either [COOL] or [HEAT].
ON / OFF
button to stop the operation.
FILTER
RESET
TEMP.
TEST
TIMER SET
2,
ON / OFF
4
FAN
MODE
SWING/FIXTIME
VENT
UNITSET CL
3
TEST
92
Wireless remote controller
(Except 4-way Air Discharge Cassette type, Under Ceiling type and 1-way Air Dischar ge Cassette type (2 Series))
1
Remove the screw which fix es the name plate to the receiver part on the wireless remote controller.
Remove the nameplate of the receiver section by inserting a minus screwdriver, into the notch at the bottom
of the plate, and set the Dip switch to [TEST RUN ON].
2
Execute a test operation with
•, , and LED flash during test operation.
• Under status of [TEST RUN ON], the temperature adjustment from the wireless remote controller is not
available.
Ensure that this is not used for normal operation as equipment damage may occur.
3
Use either COOL or HEAT operation mode for a test operation.
Note) The outdoor unit does not operate for approx. 3 minutes.
After power-ON and after operation has stopped.
4
After the test operation finished, stop the
air conditioner using the wireless remote
controller, and return the Dip switch to its
original setting.
(A 60-minute timing function is designed into
the sensor section in order to prevent a
continuous test operation.)
ON / OFF
button on the wireless remote controller.
Receiver unit
M4 × 25 screw
(2 pieces)
Small screw
Notch
Nameplate
Spacer
Wireless remote controller (4-way Air Discharge Cassette type)
1
Turn OFF the power to the air conditioner.
Remove the adjust corner cap and the attached with sensor section from the ceiling panel. For removal
method, follow to the installation instructions attached to the ceiling panel.
(Be careful to handling the sensor section because cables are connected to the sensor.)
Remove the sensor co ver from the adjust corner cap. (1 screw)
2
Change Bit [1: TEST] of the switch [S003] on the sensor P.C. board from OFF to ON.
Mount the sensor cover and attach the adjust corner cap with sensors to the ceiling panel.
Turn on power of the air conditioner.
3
Push
or [HEAT] with
section flash during the test operation.)
• Do not use operation mode other than [COOL] or [HEAT].
• Errors are detected as usual.
4
When the test operation has finished, push
button to stop the operation.
5
Turn off the power to the air conditioner.
Change Bit [1] of the switch [S003] on the
sensor P.C. board from ON to OFF.
Attach the adjust corner cap with
sensors to the ceiling panel.
ON / OFF
button of the wireless remote controller, and select an operation mode [COOL]
MODE
button. (All the display lamps of the wireless remote controller sensor
ON
ON
ON / OFF
Sensor cover
Adjust corner cap
S003
Bit 1 : OFF
4321
Sensor P.C. board
Test operation from outdoor unit
Refer to “8-7-2. Function of Start/Stop the Indoor Unit from Outdoor Unit” in “8-7. Service Support Function”.
NOTE) The test operation returns to normal operation after 60 minutes have passed.
93
In case of wireless remote controller
(for Under Ceiling type and 1-way Air Discharge Cassette type (2 Series))
Procedure
1
2
3
4
5
6
Description
Turn on power of the air conditioner.
The operation is not accepted for 5 minutes when power has been turned on at first time after installation, and 1 minute when power has been turned on at the next time and after. After the specified time
has passed, perform a test operation.
Push [Start/Stop] button and change the operation mode to [COOL] or [HEAT] with [Mode] button.
Then change the fan speed to [High] using [Fan] button.
Test cooling operationTest heating operation
Set temperature to [18°C] using [Temperature set]Set temperature to [30°C] using [Temperature set]
button.button.
After checking the receiving sound “Pi”, immediately After checking the receiving sound “Pi”, immediately
push [Temperature set] button to set to [19°C]push [Temperature set] button to set to [29°C].
After checking the receiving sound “Pi”, immediately After checking the receiving sound “Pi”, immediately
push [Temperature set] button to set to [18°C].push [Temperature set] button to set to [30°C].
Then repeat the procedure 4 → 5 → 4 → 5 .
After approx. 10 seconds, all the display lamps on the sensor part of wireless remote controller, [Opera-
tion] (Green), [Timer] (Green), and [Ready] (Yellow) flash and the air conditioner starts operation.
2
If the lamps do not flash, repeat the procedure
and after.
7
Outline of test operation from the wireless remote controller
2. Criteria for operating pressure
General criteria is as follows:
All cooling operaton
All heating operation
High pressure : 2.0 to 3.2MPa
Low pressure : 0.5 to 0.9MPa
High pressure : 2.5 to 3.3MPa
Low pressure : 0.5 to 0.7MPa
Using the rotary switch on the outdoor unit I/F, the operating pressure, cycle temperature, and compressor rotation
count can be checked on the 7-segment display.
Refer to “Outdoor refrigerant circuit system data display” and “Indoor cycle data display” in Section 9. Tr oubleshooting.
Indoor :18 to 32°C
Outdoor :25 to 35°C
Indoor :15 to 25°C
Outdoor : 5 to 10°C
When all the units operate in cooling mode
When all the units operate in heating mode
96
1st revised : Jun. 2006
9-7. Service Support Function
9-7-1. Function to Start/Stop (ON/OFF) Indoor Unit from Outdoor Unit
The following functions enables the start and stop of the indoor units using the switches on the interface P.C.
board.
No.
1
Cooling test
operation
2
Heating test
operation
3
Batch start
Function
Changes the mode of all the connected indoor
units collectively to cooling test operation.
Note) Control operation same as test
operation for remote controller.
Changes the mode of all the connected indoor
units collectively to heating test operation.
Note) Control operation same as test
operation for remote controller.
Starts all the connected indoor units collectively.
Note) The contents follow the setup of remote
controller.
Outline
Setup/Release
[Setup]
Push SW04 for 2 seconds or more
with SW01”2”, SW02”5”, SW03”1”.
[Release]
Return SW01, SW02, SW03 to “1”.
[Setup]
Push SW04 for 2 seconds or more
with SW01”2”, SW02”6”, SW03”1”.
[Release]
Return SW01, SW02, SW03 to “1”.
[Setup]
Push SW04 for 2 seconds or more
with SW01”2”, SW02”7”, SW03”1”.
[Release]
Return SW01, SW02, SW03 to “1”.
7-segment display
Section ASection B
[C ][ –C]
Section ASection B
[H ][ –H]
Section ASection B
[CH][ 11]
[ 11] is displayed on
Section B for 5 seconds.
Batch stop
4
Individual
start
Individual
stop
Individual test
operation
Stops all the connected indoor units collectively.
Starts the specified indoor unit.
Notes)
• Control operation same as test.
• The other indoor units keepexisting status.
Stops the specified indoor unit.
Note) The other indoor units keep existing
status.
Operates the specified indoor unit.
Note) The other indoor units keep existing
status.
[Setup]
Push SW05 for 2 seconds or more
with SW01”2”, SW02”7”, SW03”1”.
[Release]
Return SW01, SW02, SW03 to “1”.
[Setup]
Push SW04 for 2 seconds or more set
SW01 “16” and set SW02 and SW03
to address No. (1 to 64) to be started.
[Release]
Return SW01, SW02, SW03 to “1”.
[Setup]
Push SW05 for 2 seconds or more set
SW01 “16” and set SW02 and SW03
to address No. (1 to 64) to be stopped.
[Release]
Return SW01, SW02, SW03 to “1”.
[Setup]
Push SW04 for 10 seconds or more
set SW01 “16” and set SW02 and
SW03 to address No. (1 to 64) to be
operated.
[Release]
Return SW01, SW02, SW03 to “1”.
Section ASection B
[CH][ 00]
[ 00] is displayed on
Section B for 5 seconds.
Section ASection B
[ ][ ]
Section A:
Displays the corresponding
indoor address.
Section B:
Displays [ 11] for 5 seconds
from operation-ON.
Section ASection B
[ ][ ]
Section A:
Displays the corresponding
indoor address.
Section B:
Displays [ 00] for 5 seconds
from operation-OFF.
Section ASection B
[ ][ ]
Section A:
Displays the corresponding
indoor address.
Section B:
Displays [ FF] for 5 seconds
from test operation-ON.
NOTE 1) This start/stop function only sends
the command signals from the
outdoor unit to the indoor unit, such
as start, stop, operation mode, etc.
Once it does not resend the signals
even if the indoor unit does not follow
the sent signals.
NOTE 2) The above controls are not available
when an error has caused the system
to stop.
Interface P.C. board
97
7-segment display [A]7-segment display [B]
SW04SW05
SW01 SW02 SW03
Rotary switch
1. Cooling test operation function
This function is provided to change collectively the mode of all the indoor units connected to the same
system for cooling test operation mode , using switches on the interface P.C. board of the outdoor unit.
Operation procedure
Power ON
Set SW01 on the interface P.C. board of the outdoor unit to [2],
Sw02 to [5], and SW03 to [1] respectively. ([C ] is displayed on the 7-segment display [A].)
Push SW04 on the interface P.C. board of the outdoor unit for 2 seconds or more.
[TEST] is displayed on the remote controller of the indoor unit to be operated.
Check that “ – C ” is displayed on the 7-segment display
[B] on the interface P.C. board of the outdoor unit.
Return SW01, SW02, SW03 on the interface P.C. board of the outdoor unit to [1], [1], [1]
respectively or push the push-switch SW05 for 2 seconds or more.
Be sure to turn on power at the indoor side before power-ON of outdoor unit.
Start
[A]
[C ]
[B]
[ –C]
Operation check
Stop/End
2. Heating test operation function
This function is provided to change collectively the mode of all the indoor units connected to the same
system for heating test operation mode, using switches on the interface P.C. board of the outdoor unit.
Operation procedure
Power ON
Be sure to turn on power at the indoor side before power-ON of outdoor unit.
Set SW01 on the interface P.C. board of the outdoor unit to [2],
Sw02 to [6], and SW03 to [1] respectively. ([H ] is displayed on the 7-segment display [A].)
Push SW04 on the interface P.C. board of the outdoor unit for 2 seconds or more.
[TEST] is displayed on the remote controller of the indoor unit to be operated.
Check that “ – H ” is displayed on the 7-segment display
[B] on the interface P.C. board of the outdoor unit.
Return SW01, SW02, SW03 on the interface P.C. board of the outdoor unit to [1], [1], [1]
respectively or push the push-switch SW05 for 2 seconds or more.
Interface P.C. board
[A]
[ H ]
7-segment display [A]7-segment display [B]
[B]
[ –H]
SW04SW05
Start
Operation check
Stop/End
SW01 SW02 SW03
Rotary switch
NOTE) The test operation returns to normal operation after 60 minutes.
98
3. Batch start/stop (ON/OFF) function
This function is provided to start/stop collectively all the indoor units connected to the same system by using
switches on the interface P.C. board of the outdoor unit.
Operation procedure
Power ON
Set up the operation mode of the remote controller.
(If it is not set up, the operation continues in the current mode.)
(FAN/COOL/HEAT)
Set on the interface P.C. board of the outdoor unit SW01 to [2],
Sw02 to [7], and SW03 to [1] respectively. ([CH ] is displayed
on 7-segment display [A].)
Push SW04 on the interface P.C. board of the outdoor unit for
2 seconds or more.
The indoor unit to be started operates.
Be sure to turn on power at the indoor side before power-ON of outdoor unit.
If an error is already displayed under condition of
SW01 [1], SW02 [1], SW03 [1], resolve the problem
using the troubleshooting guide and then execute the
test operation.
If the operation is set “heat”, indoor unit which is set to
“cool priority” will not operate or will be displayed.
If the operation is set to “cool”, indoor unit which is set to
“heat priority” will not operate or will be displayed.
Start
Push the push-switch SW05 on the interface P.C. board of the
outdoor unit for 2 seconds or more.
After test operation, return the rotary switches SW01, SW02,
and SW03 on the interface P.C. board of the outdoor unit to
[1], [1], [1] respectively.
Stop
End
99
1st revised : Jun. 2006
4. Individual star t/stop (ON/OFF) individual test operation function
This function is provided to start/stop (ON/OFF) individually each indoor unit connected to the same system
by using switches on the interface P.C. board of the outdoor unit.
Set SW01 [16] and set SW02, SW03 to indoor address No. (1 to 64) to be started (Refer to the following
) - only the setup indoor unit starts operation.
table
∗
(In the rotary switches of the indoor unit which operates in a group by the remote controller, the follow er unit
cannot be individually started or stopped. In this case, [ – – ] is displayed on 7-segment display [B] on the
interface P.C. board of the outdoor unit.)
Operation procedure
Power ON
Set up the operation mode of the remote controller.
(If it is not set up, the operation starts with the current mode.)
Match the rotary switch on the interface P.C. board of the
outdoor unit
corresponding indoor unit
Push the push-switch SW04 on the interface
P.C. board for 2 seconds or more.
(If pushing this switch continuously for 10 seconds
or more, the operation changes to the individual
test operation.)
*
with in the following table.
(7-segment display)
[A]
[ ]
Address display of
[ ]
[ 00] is displayed for
5 seconds after operation-ON.
Be sure to turn on power at the indoor side before power-ON of outdoor unit.
[B]
Address display of
corresponding indoor unit
[A]
[ ]
If an error is already displayed under condition of SW01 [1],
SW02 [1], SW03 [1], return the status to normal one according
to troubleshooting and then execute a test operation.
The unit which is not given with priority by heating priority control,
cooling priority control, and selection of cooling or heating mode
is not operated. In this case, or is displayed on the
remote controller.
(7-segment display)
[ 11] is displayed for
(For individual test operation,[ FF] is displayed.)
5 seconds after operation-ON.
[B]
[ ]
Start
The indoor unit to be started operates.
SW01SW02SW03Units to be operated
End
*
161 to 161
161 to 162
161 to 163
161 to 164
Address 1
to individually
Address 16
Address 17
to individually
Address 32
Address 33
to individually
Address 48
Address 49
to individually
Address 64
Push the push-switch SW05 on the interface
P.C. board of the outdoor unit for 2 seconds or more.
(7-segment display)
[A]
[ ]
Address display of
corresponding indoor unit
After test operation, return the display select
switches SW01, SW02, and SW03 on the interface
P.C. board of the outdoor unit to [1], [1], [1] respectiv ely.
[ 00] is displayed for
5 seconds after operation-ON.
[B]
[ ]
NOTE) The individual test operation returns to the normal operation after 60 minutes.
100
}
}
}
}
In individual
start/stop
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.