Toshiba MBSB80-225-43 User Manual

A B C D E F G H I J
11.8"
30.1" 225 Amp M.L.O.
27.0"
w/ (1) #6-250kcmil
Lug per Phase (typ)
225 Amp Box-
Mounted Neutral w/
(2) #6-250kcmil Lugs
N
42.4"
0.5" Dia.
Utility Feed
ABC
52C
52M
Maintenance
Bypass Breaker
52L
To Critical Load
UPS Bypass Input Breaker
UPS Output Breaker
39.3"
Mounting Hole (4)
Front View
Left Side View
Front View
(Door Removed)
Feed From Utility
Part No.
UPS KVA
UPS Output Amp Rating
150MBSB80-225-43 FD 480/600 25/14180
Enclosure
Box/Trim
- NEMA 1, Surface-Mount (UL Listed).
- 12-Gauge painted steel, trim held with adjustable clamps; Door equiped with one 3x5 directory cardholder and Corbin type 15767 Snaplock.
- Beige polyester powdercoat on all surfaces, treated with sealer.
Finish
Breakers
- Cutler-Hammer thermal-magnetic type, 225A frame, 3-pole, trip settings as shown, supplied with (1) #4-4/0 terminal lug per phase.
- Approximately 190 lbs total.
Weight
Breaker
Type
Voltage
10
NOTES
1) This drawing is for illustration purposes only and is subject to change without notice. TIC is not responsible for any errors or omissions.
kAIC rating at
480/600V
Drawn by
EO
Date 07/07/04
Approved by
JIS
Date 07/07/04
TOSHIBA INTERNATIONAL CORPORATION AND SHALL NOT
A
N
A B C
Feed To Critical Load
TOSHIBA
INTERNATIONAL CORPORATION
Houston Texas, USA
THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF
BE REPRODUCED, USED, OR DISCLOSED TO OTHERS
UNLESS PRIOR WRITTEN AUTHORIZATION IS OBTAINED.
B
C
52C
225AT
A
Feed to
B
UPS
Input
C
52L
225AT
ST
Feed
A
from
B
UPS
C
Output
TITLE
52M
225AT
150kVA G8000 Series UPS
3-Breaker Maintenance Bypass Panel
DRAWING NO. REV.
MBSB80-225-43
10
1.0