Multi Controller ................................................................................................................................... 17
Multi Controller ................................................................................................................................... 20
Diagnostic procedure for check code ................................................................................................. 37
Control features ..................................................................................................................................... 63
Valve and sensor function and operation
Multi Controller valve function and operation ...................................................................................... 65
Outdoor unit valve functions ............................................................................................................... 66
Manual operation of valves ................................................................................................................. 67
Sensor and switch operation .............................................................................................................. 68
Refrigeration pipe installation
Leak test ............................................................................................................................................. 69
Multi Controller exploded view ............................................................................................................ 78
Multi Controller electrical parts ........................................................................................................... 79
3
Page 3
Introduction
Precautions
Please read these instructions carefully before starting the installation.
This equipment should only be installed by suitably trained operatives.
In all cases ensure safe working practice: Observe precautions for persons in the vicinity of the works.
Ensure that all local, national and international regulations are satisfied.
Check that the electrical specifications of the unit meet the requirements of the site.
Carefully unpack the equipment, check for damage or shortages. Please report any damage immediately.
Model MAR-F105HTM8-PE complies with the following EU Directives:
73/23/EEC (Low Voltage Directive), 89/336/EEC (Electromagnetic Compatibility) and 97/23/EC (Pressure
Equipment Directive). Accordingly, they are designated for use in commercial and industrial environments.
Compressor, category II, Module A1Liquid receiver, category II
Accumulator, category IHigh pressure switch, category II, Module A1
Notified body for inspection and quality assurance systems: BSI, Maylands Avenue, Hemel Hempstead,
WP2 4SQ, UK.
Avoid installation in the following locations:
Where there is danger of flammable gas leakages.
Where there are high concentrations of oil.
Where the atmosphere contains an excess of salt (as in coastal areas). The air conditioner is prone to
failure when used under this condition unless special maintenance is provided.
Where the airflow from the outdoor unit may cause annoyance.
Where the operating noise of the outdoor unit may cause annoyance.
Where the foundation is not strong enough to fully withstand the weight of the outdoor unit.
Where the water drainage may cause a nuisance or a hazard when frozen.
Where strong winds may blow against the air outlet of the outdoor unit.
Precautions for R407C outdoor units
R407C outdoor units use synthetic oils which are extremely hygroscopic. Therefore ensure that the
refrigerant system is NEVER exposed to air or any form of moisture.
Mineral oils are unsuitable for use in these units and may lead to premature system failure.
Use only equipment which is suitable for use with R407C. Never use equipment which has been used
with R22.
R407C should only be charged from the service cylinder in the liquid phase. It is advisable to use a
gauge manifold set equipped with a liquid sight glass fitted in the centre (entry) port.
4
Page 4
Introduction
Precautions
Precautions for R-407C outdoor units
Liquid receiver fusible plug
In the event of the system being subjected to abnormal conditions it is protected by a fusible plug,
positioned on the liquid receiver, within the outdoor unit. It is rated to fail at 70°C.
Position of
fusible plug
System pressure measurement
To measure the system’s high and low pressures, connect a gauge manifold to the corresponding access
port as indicated below.
Low pressure
access port
High pressure
access port
Explanation of Toshiba serial number
A serial label is attached to all Toshiba air conditioning units. Located on the label is an 8-digit number,
which represents the month, year and batch number of the manufactured unit. A breakdown of the 8-digit
number is defined below.
ODU= Outdoor UnitIDU= Indoor Unit
R/C= Remote ControllerD.O.L.= Direct On-Line compressor
INV= Inverter ODUWB= Wet Bulb
DB= Dry BulbIOL= Inner Overload Relay
Mg-Sw = Magnetic ContactorIGBT= Inverter Gate Bi-Polar Transistor
OCR= Over Current RelayIPDU= Intelligent Power Drive Unit
M/C= Multi Controller
Note 9: MPaG ⇒ kgf/cm2G conversion multiplier
1.0 MPaG = 10.2 kgf/cm2G
7
Page 7
Introduction
Super multi system basic components
3-pipe heat pump with simultaneous heating and cooling
This system allows separate operation of each indoor unit in either heating or cooling simultaneously.
3 pipes
3-pipe
outdoor unit
T-pieces
Multi Controller
Indoor unit remote controller requesting cooling
Cooling operation
Indoor unit remote controller requesting heating
Heating operation
Indoor units
Remote controller
2 pipes
8
Page 8
Introduction
Outline of control system
The refrigerant and electrical systems of the Super Multi air conditioner are controlled by the Multi
Controller and the outdoor unit microprocessors.
All RAV heat pump, R-407C, 4/5 series indoor units are compatible with the Super Multi system, i.e. 1~5 HP.
For system operation, initially the microprocessor in each indoor unit calculates the difference between the
current room temperature (TA) and the requested temperature which has been set on the remote
controller. A demand signal is determined and transmitted to the Multi Controller microprocessor in the
form of operation commands (i.e. ON/OFF, cooling or heating operation mode, operation demand frequency).
The Multi Controller microprocessor receives operation commands from all indoor units connected,
calculates the accumulative operation command and transmits this information to the outdoor unit interface
microprocessor.
The interface microprocessor calculates the capacity required for heating or cooling and determines the
operation mode of the outdoor unit and the actual frequency of the compressor.
•The setting of the indoor unit capacities is important. Set the correct indoor unit code numbers
according to the indoor unit capacity. The capacities are set by the rotary switches on the printed
circuit board switch A (unit A), switch B (unit B), switch C (unit C) and switch D (unit D).
•During manufacture, the indoor capacity selection switches are set at ‘0’.
•Record the indoor capacity codes, indoor unit model names and locations in the installation manual,
and on the wiring diagram on the electrical panel cover.
Example:Room ARoom BRoom C
Capacity 16Capacity 16Capacity 26
Indoor unit CapacityNo connection10131620263646
Code number023456810
(Example: Model RAV-364UH-PE, capacity = 36)
Multi Controller PCB
MCC-1210
Capacity select switches
•Multiple indoor units may be connected to each outdoor unit, providing the total indoor code does not
exceed the limits shown below.
Combination of Multi Controllers and indoor units
Number ofMaximum No. ofIndoor unit diversityMaximum system codeMaximum code per
Multi Controllersindoor unitsMulti Controller
Sound powerdB(A)70
Dimensions (H x W x D)mm1700 x 990 x 790
Net weightkg285
ColourSilky Shade (Munsell 1-Y8.5/0.5)/RAL 1013 (DE ~9)
CompressorTypeHermetically sealed (twin scroll)
Suction gasmm28.6 (brazing connection)
Max. equivalent piping lengthm120
Max. actual piping lengthm100
Max. piping headm50: when the outdoor unit is installed above
Suction accumulator case heaterW29 (240 V AC)
m20: when the outdoor unit is installed below
Notes:
1. Specifications are subject to change without notice.
2. The specification shown in ( ) denotes operation with an indoor unit load diversity of 135%.
3. Operating conditions:
Outdoor temperature °CCooling-5 to 43
Heating-15 to 21
Room temperature °CCooling18 to 32
Heating15 to 29
4. Sound level: 1 m horizontal from centre.
1.5 m vertical from base.
12
Page 12
Parts specification
Outdoor unit
Specification of outdoor unit refrigeration cycle parts
Maximum pressureMPa3.53
Expansion valveEXV-V-E80HTF-9WS
Compressor heater(Internal within the compressor)
Accumulator heaterW29 (240 V AC)
Pressure sensorModel name: NTP-Q250TF-2
Input voltage: DC12 V
Output voltage: DC 0.5 - 4.5 V
Discharge temperature sensor25°C = 50 kΩ
50°C = 18.1 kΩ
100°C = 3.35 kΩ
Suction temperature sensor/0°C = 34.6 kΩ
outdoor air temperature sensor25°C = 10 kΩ
50°C = 3.4 kΩ
Pulse modulating valve (Cooling bypass PMV1)EV18RC1, coil DC 12 V
Pulse modulating valve (PMV2)EV23RC2, coil DC 12 V
2-way valve (SV1, SV2, SV4, SV5, SV16, SV17)NEV202DXF, coil AC 240 V
2-way valve (SV13, SV14, SV15)RP100-03, coil AC 240 V
Note:
Specifications are subject to change without notice.
13
Page 13
Parts specification
Outdoor unit
Specification of outdoor unit inverter assembly parts
Model nameMAR-F105HTM8-PE
Power supply380-415 V, 3 phase, 50 Hz
PC board assemblyPCB (IPDU)MCC-1342
PC board assemblyPCB (noise filter)MCC-1366
PC board assemblyPCB (interface)MCC-1223
PC board assemblyPCB (communication)MCC-1387
Fan motor capacitor8 µF/450 V AC
Electrolytic capacitor2200 µF/400 V
Power supply terminal plateL1, L2, L3600 V AC, 60 A, 3 pole
TransformerInterfaceTT01
Magnetic contactorInverter sideFMCa - 1S
Magnetic contactorFixed sideFC - 3
ReactorCH - 25 - 2FK
Fuse6 A500 V AC
Fuse20 A600 V AC
Fuse3.15 A250 V AC
Fuse6.3 A250 V AC
Fuse20 A250 V AC
Fuse10 A250 V AC
Thermistor (PTC)
Relay15 A, 240 V AC
Note:
Specifications are subject to change without notice.
14
Page 14
Parts specification
Multi Controller unit
Specification of 3-pipe Multi Controller parts
Model nameRBM-Y1034F-PERBM-Y1044F-PE
Pulse modulating valveEV23RC7, coil DC 12 V
Temperature sensorAt 0°C = 32.8 kΩ, 25°C = 10 kΩ, 50°C = 3.6 kΩ
Float switchFS-085-0031
PC board assemblyPCB MCC-1222
Power supply transformerModel nameFT69
SpecificationPrimary side: AC 240 V, secondary side: AC 12 V
Relay (PC board)G2R-117P, coil DC 12 V
Heater10.4 W/m
50 W65 W
Thermal fuse for heaterCut out at 119°C
Heater fuseT1A
Discharge gas side 2-way valveRP100-03, coil AC 240 V
Suction gas side 2-way valveREV-1506DXFQ6, coil AC 240 V
2-way valveNEV202DXF-AC 240 V
2-way valveNEV603DXF-AC 240 V
Note:
Specifications are subject to change without notice.
ModelABCDEF
RBM-Y1034F-PE 460300-90-90
RBM-Y1044F-PE 53037090909090
All dimensions are in mm
2 notches for
hanging bolts
(12 x 21)
Electric parts box
Refrigerant pipe
connection (brazing)
55
Liquid side ø 12.7
55
50
80
300
300
A
D
C
EF
90
90
2 slots for
hanging bolts
(12 x 52)
3-pipe:
RBM-Y1034F/Y1044F-PE
Connection (brazing)
Liquid side ø 15.9
Wiring knockouts
6 x ø 20
110
Refrigerant pipe
connection (brazing)
Gas side ø 19
Refrigerant pipe
connection (brazing)
Delivery gas side ø 19
Refrigerant pipe
connection (brazing)
Suction gas side ø 28.6
17
Page 17
MAR-F105HTM8-PE
Wiring diagrams
Outdoor unit
18
Page 18
Wiring diagrams
Outdoor unit
19
Page 19
Wiring diagram
Multi Controllers
3-pipe Multi Controller (RBM-Y1034F-PE, RBM-Y1044F-PE)
Spark
killer
Capacity rank
setting
ABCD
7-segment LED
Display
selector switch
Indoor
unit A
Indoor
unit B
Indoor
unit C
SymbolPart Name
PMVA, B, C, DPulse modulating valve
Th A, B, C, D, XTemperature sensor
TrPower transformer
CSFloat switch
HHeater
MSReset switch
FFuse (T1A)
SVD (A), (B), (C), (D)Electrically operated valve for discharge gas side
SVD (A), (B), (C), (D)Electrically operated valve for suction gas side
SVDDElectrically operated valve for increasing pressure
SVSSElectrically operated valve for decreasing pressure
SVHElectrically operated valve for superheat control
LD 101, 102, 103, 104Fault indicator LED
Parts layout
Control PC board
Terminal plate
Trans
•The dashed lines indicate wiring on site.
•and indicate terminal blocks, and numbers within them are
terminal numbers.
•indicates a printed circuit board.
•The frameindicates the product body.
•RBM-Y1034F-PE does not have PMVD, SVD(D), SVS(D), ThD or the
Reset
switch
connection block for indoor unit D.
The capacity rank code setting for unit D is to be set to “0”.
Indoor
unit D
Outdoor
unit
20
Page 20
Refrigeration piping schematic diagram
Outdoor unit
21
Page 21
Refrigeration piping schematic diagram
Normal operation - heat mode
High pressure gas
Low pressure gas
Key:
High pressure liquid
Low pressure liquid
22
Page 22
Refrigeration piping schematic diagram
Normal operation - cool mode
High pressure gas
Low pressure gas
Key:
High pressure liquid
Low pressure liquid
23
Page 23
Refrigeration piping schematic diagram
Simultaneous operation - mainly heat
High pressure gas
Low pressure gas
Key:
High pressure liquid
Low pressure liquid
24
Page 24
Refrigeration piping schematic diagram
Simultaneous operation - mainly cool
High pressure gas
Low pressure gas
Key:
High pressure liquid
Low pressure liquid
25
Page 25
Diagnostic procedure
Outdoor unit
MAR-F104HTM8-PE, 3-pipe outdoor unit
Malfunction judgement is performed using the self-diagnostic function of the outdoor unit. The combination
of the display switches (SW1, SW2) and the LEDs (LD 71~LD 74) indicates the diagnostic details.
Located on the electrical inverter cover is a transparent window, which allows the 7-segment LED to be
viewed while the unit is in operation.
The transparent window has access holes to allow the adjuster pen, which is attached to the window,
access to alter the setting of the display switch SW1 and SW2 while the unit is running.
A slit is positioned at one end of the pen to locate onto the rotary switch.
The adjuster pen can also be used to push switches SW3 and SW4 during the diagnostic procedure
check.
A crimp connector is located on the other end of the adjuster pen. This connector can be used to ‘short’
TP1 or TP2 connectors when performing manual operation of the outdoor valves.
No other component other than that supplied must be used to adjust the rotary switches. Failure to do
so may result in damage to the unit, malfunction or risk of electric shock.
26
Page 26
Diagnostic procedure
Outdoor unit
1.Communication serial signals and the system operating status are displayed by changing display
switch SW2.
Display Display Indication7-segment LED display
switchswitchLD 71LD 72LD73LD74
SW1SW2
position position
00Sending/receiving status ofBetweenBetweenBetweenNon-inverter
interface control board serialM/C (1)M/C (2)invertercompressor
signalSendingNot sendingAbnormal [E]
only [S]or receiving
[ ]
ReceivingSending andNormal [0]
only [J]receiving [0]
6.The indoor unit capacity rank setting is displayed.
DisplayDisplayIndication7-segment LED display
switchswitchLD 71 LD 72LD 73LD 74
SW1SW2
position position
30Outdoor unit HP[9]8 HP [8], 10 HP [A][H][P]
1Capacity rank of Unit A [A]Displays the code number of the
2indoor unitUnit B [b]indoor unit registered to each M/C.
3connected toUnit C [C]
4M/C (1)Unit D [d]Refer to the table below (7) for
5Capacity rank of Unit A [A]indoor unit model capacity rank.
6indoor unitUnit B [b]
7connected toUnit C [C]
8M/C (2)Unit D [d]
7.Indoor unit code No. conversion table
Code No.023456810
Capacity rank No correction10131620263646
(Indoor unit model example: Model RAV-364UH-PE, capacity rank = 36)
8.Sensor temperature display
DisplayDisplayIndication7-segment LED display
switchswitchLD 71LD 72LD 73LD 74
SW1SW2
position position
40Pressure sensor data[P][d]Refer to table 9 conversion chart
These are sample displays. Intermediate displays to those above are possible.
Display [00] signifies sensor open circuit.
30
Page 30
Diagnostic procedure
Outdoor unit circuit test procedure
12. Outdoor unit circuit test procedure
•These systems have a feature which enables them to check that the wiring and piping connections
are aligned with each other. This is carried out by allowing refrigerant to flow to one indoor unit at a
time and monitoring that indoor unit’s coil sensor for a corresponding drop in temperature. Each
indoor unit is tested in turn and where two Multi Controllers are installed each Multi Controller is tested
in turn.
•This test would normally be used at the commissioning stage.
•Procedure for initialising the circuit test.
1.Turn the power off.
2.Ensure the capacity codes are set correctly, capacity switches set to ‘0’ are not tested.
3.Put the outdoor display switches SW1 and SW2 to 9 and Multi Controller(s) display switch to 6.
4.Turn the power back on.
5.Set all the remote controllers to cool mode and 29°C.
6.Press the on/off button to start all the indoor units (the outdoor LEDs show ‘1020’).
7.Press the outdoor unit switch SW3, and hold for 3 seconds.
8.The system is now in self-testing (all 8 LEDs will be flashing rapidly).
9.The system will stop at the end of the test.
•In the event of cross wiring/piping the system will indicate which units are faulty, see table below:
Outdoor display switch SW1 and SW2 set to position 9.
One and two Multi Controllers
DisplayMulti ControllerFault
1020AllNone
1A201Unit A
1B20Unit BUnits that are indicated
1C20Unit Cfailed the test
1D20Unit D
102A2Unit A
102BUnit B
102CUnit C
102DUnit D
Three or more Multi Controllers
DisplayMulti ControllerFault
1020AllNone
1A201Unit A or B
1B20Unit C or DUnits that are indicated
1C202Unit A or Bfailed the test
1D20Unit C or D
102A3Unit A or B
102BUnit C or D
102C4Unit A or B
102DUnit C or D
31
Page 31
Diagnostic procedure
Multi Controller
The combination of the display switch and the four 7-segment LEDs (LD 101-LD 104) indicates the
diagnostic details.
MCC - 1223
7-segment LED
LD 101
LD 102
LD 103
LD 104
Unit B
Unit A
Capacity rank switches
Unit D
Unit C
Display switch
Multi Controller control board
7 segment LED display
Switch Indication LD 101LD 102 LD 103LD 104
position
timer
6Circuit test [c][k]Displays unit being tested [A b C d]Indicates faulty unit connection [A b C d]
7PMV A[P][A]Displays the degree of PMV opening (0-240) as a hexadecimal code:
8PMV B[P][b][00]: Closed, [FO]: Fully open
9PMV C[P][c]
10PMV D[P][d]
11ThA[h][A]Displays sensor temperature
12ThB[h][b]Refer to the Multi Controller sensor temperature conversion table (1).
13ThC[h][c]
14ThD[h][d]
15ThX[h][H]
Heating [H-],
Cooling [C-]*
unit Bunit Bunit Aunit Aoudoorunit Dunit Dunit Cunit Coutdoor
unitunit
* and Simultaneous Cooling/Heating [HC], Defrost [J-]
32
Page 32
Diagnostic procedure
Multi Controller
1.Display switch set to position “11”, “12”, “13” and “14”
Multi Controller - ThA, B, C, D and X sensor conversion table
DisplayTemp. °CDisplayTemp. °CDisplayTemp. °CDisplayTemp. °C
Remote controller fault code display time lapse for system malfunctions
Serial signal abnormalities:Between the I/F and the INVMore than 3 minutes
Between the M/C and the I/FMore than 2 minutes
Between the indoor unit and the M/CMore than 1 minute
Between the remote controller and indoor unitA few seconds
INV abnormality:More than 3 minutes
I/F abnormality:More than 2 minutes
M/C and indoor unit abnormality:More than 1 minute
Inverter
control board
INV
33
Page 33
Fault code display
Self-diagnostic function
The remote controller, Multi Controller and outdoor unit have the facility to display fault codes which are
used to determine any malfunction of the system.
•The remote controller is provided with a “check” button and a check display.
•The Multi Controllers and outdoor units are provided with display switches and LED displays.
Initially malfunctions can be identified from the remote controller check display.
Details of the Multi Controller and outdoor unit malfunctions can be determined from their control boards.
(Multi Controller malfunctions are also displayed on the outdoor unit interface control board).
Fault code identification
When a malfunction has been identified, do not reset the system. Press the “CHECK” button on the remote
controller and observe the display.
The location and cause of the malfunction can be determined from the fault code.
“CHECK”
Flashes when
phases are rotated.
FAN
MODE
FAN ONLY
AUTO
OPERATION
HIGH
COOL
MED
HEAT
LOW
AUTO
CHECK
TEMP
UNITMANUAL
C
˚
88
OFF ON
TIMER
CONT.
88 : 88
H
“STANDBY” displayed
•The total capacity rank settings of indoor units connected exceeds
the allowable level, or an indoor capacity rank is set at “0” (Multi
Controller).
NETWORK
CENTRAL
STANDBY
PREHEAT
DEFROST
LOUVER
ADDRESS
FILTER
M
REMOTE CONTROLLER
MODE
-
TIMER ADJUST
CHECK
FILTER
ON/OFF
+
Reset button
•Pressing the reset button with a pin will clear the memory.
Check button
•Pressing for 1 second will display fault codes.
•Pressing for 5 seconds will reset the indoor unit microprocessor.
•Pressing for 10 seconds will clear only the fault codes.
34
Page 34
Fault code display
Self-diagnostic function
Details of the malfunction check display
The following fault code display occurs when the check button is pressed for 1 second.
(Note: Up to 16 indoor units can be connected to one remote controller using group control.)
2 fault codes for each of the 16 indoor units can be displayed at 2 second intervals.
No communication signal between Interface PCB and IPDU
04 No communication signal between M/C and O/D
No communication signal between I/D and M/C
0b Drain pump fault - I/D unit
0C TA sensor fault
0d TC sensor fault
08 Reverse TC temperature change
09 No TC temperature change
11 Motor short circuit
12 Indoor PC board short circuit
b5 External input display fault
(High level refrigerant leak if RBC-RD1-PE fitted)
97 Central management communication short circuit
98 Central management address set-up fault
99 No communication I/D to R/C
15 Refer to M/C
1C Refer to O/D 1C Refer to O/D 08 Four-way valve alarm.
14 Refer to O/D 14 Refer to O/D 14 G-Tr short-circuit protective operation
17 Refer to O/D 17 Refer to O/D 17 Current detection circuit
21 Refer to O/D 21 Refer to O/D 21 High pressure SW circuit
1d Refer to O/D 1d Refer to O/D 1d Compressor error
1F Refer to O/D 1F Refer to O/D 1F Inverter malfunction
d3 Refer to O/D d3 Refer to O/D d3 TH sensor circuit - Inverter microprocessor (IPDU)
dA Refer to O/D dA Refer to O/D dA Heat sink overheat protective operation (IPDU)
NOTE:
•To retrieve fault codes from the outdoor unit ensure rotary switch SW1 is set to position ‘2’ and SW2 is set to position ‘0’.
•To retrieve fault codes from the Multi Controller ensure the display switch is set to position ‘1’.
04 No communication signal between Interface PCB and IPDU
tt
t
tt
No communication signal between M/C and O/D.
8A Multi Controller PCB error
88 Communication error between outdoor unit and Multi
82 ThC sensor fault 82 ThC sensor fault
83 ThD sensor fault 83 ThD sensor fault
84 ThX sensor fault 84 ThX sensor fault
0b Drain pump fault - M/C unit 0b Drain pump fault - M/C unit
89 Indoor units capacity codes too high or set to 0 89 Over capacity
tt
t
tt
tt
t
tt
tt
t
tt
tt
t
tt
tt
t
tt
tt
t
tt
tt
t
tt
tt
t
tt
04 No communication signal between Interface PCB and
tt
t
tt
IPDU
tt
t
tt
tt
t
tt
tt
t
tt
tt
t
tt
tt
t
tt
tt
t
tt
tt
t
tt
Er[E][r] fault code refers to Outdoor unit
tt
t
tt
A0 Discharge temp. sensor (TD1) short circuit
A1 Discharge temp. sensor (TD2) short circuit
A2 Suction temp. sensor (TS) short circuit
A4 External air sensor (THo) short circuit
A5 Outdoor heat exchanger sensor (TE) short circuit
A6 Discharge temp. (TD1 and TD2) protective operation
A7 Suction temp. (TS) protective operation
AA High pressure sensor (Pd) short circuit
Ad DOL compressor fault
AE Low pressure fault (Ps)
AF Outdoor Unit power source phase order miswiring
1C Extension IC, EEPROM short circuit
tt
t
tt
tt
t
tt
tt
t
tt
tt
t
tt
tt
t
tt
tt
t
tt
tt
t
tt
36
Page 36
Troubleshooting
Diagnostic procedure for check code
Check codeStatus of air conditionerOperation cause
[04]Outdoor unit stops1. Wiring fault between indoor and Multi
Inverter serial signalIndoor unit fan continuesController or Multi Controller and outdoor
short circuitinterface PC board.
Inter-unit communication2. Defective communication PC board.
3. Defective IPDU PC board.
4. Noise from outside.
5. High level refrigeration leak (RBC-RD2-PE).
Is there continuity of the
communication cable between
the indoor unit and Multi
Controller?
Ye s
j
Is there continuity of the
communication cable between
the Multi Controller the outdoor
Is there continuity of the
communication cable between
the outdoor interface PC board
and outdoor IPDU PC board?
Is there voltage present
between pins 4 and 5 of CN1
on communication PC board?
(DC 0 to 5 V, pin 5-GND)
between pins 3 and 5 of CN1
(DC 0 to 5 V, pin 5-GND)
Check noise interference from
unit
Ye s
j
Ye s
j
Ye s
j
Is there voltage present
on interface PC board?
Ye s
j
outside, etc.
Ye s
j
Is refrigerant detector
RBC-RD2-PE fitted?
Ye s
No
No
No
No
No
No
h
h
h
h
h
h
Replace communication cable
Replace communication cable
Replace communication cable
Communication PC board is defective - replace
IPDU PC board is defective - replace
Complete checks detailed above
Are the high level alarm and
j
the shutdown LEDs on the
RBC-RD2-PE (RED) on?
Ye s
j
Refrigerant leak.
Leak-check unit.
No
Complete checks detailed above
h
37
Page 37
Troubleshooting
Diagnostic procedure for check code
Check codeOperation cause
[08]1. 4-way valve operation error.
Modify connection of connectors.
TS sensor: PJ3
TE sensor: PJ4
Pd sensor: PJ7
Sensor error
Sensor error
Correct wiring
j
Does 4-way valve operate?
No
j
Is fixed-speed compressor
activated?
Ye s
j
4-way valve error
Ye s
No
Does refrigerant bypass
h
from discharge to suction
on 4-way valve?
h
Does OL of Mg-SW
Does IOL of fixed-speed
compressor operate?
Ye s
operate?
No
j
No
No
Ye s
Ye s
Restart the operation if a trouble has not
h
h
h
h
h
occurred in trial operation.
Check 4-way valve
Restart the operation after manual reset
Restart the operation after compressor
IOL reset (automatic reset)
Mg-SW error
38
Page 38
Troubleshooting
Diagnostic procedure for check code
Check codeOperation cause
[09]1. Compressor running but not pumping.
No temperature change in TC temperature2. Bi-Metal thermostat protection device.
3. Compressor wiring.
4. Faulty TC temperature sensor.
Is the power supply
voltage to the outdoor
unit normal?
Ye s
j
Is the compressor
running but not
pumping?
Ye s
j
Are the gas suction,
gas discharge and
liquid packed valves
fully open?
Ye s
j
Is the wiring of the
compressor normal?
Ye s
j
See judgement flow [1d]
compressor fault
No
No
No
No
h
h
h
Modify power supply
Open packed valves
Modify connection of
wiring
h
Is the indoor unit in
Is the indoor TC sensor
normal and connected
Confirm:
Lack of gas charge
Pipe blockage
frost conditions?
Ye s
j
correctly?
Ye s
j
No
No
See judgement flow
h
[1d] compressor fault
Replace TC sensor
h
39
Page 39
Troubleshooting
Diagnostic procedure for check code
Check codeStatus of air conditionerOperation cause
[0b]Operation stops for Multi1. Float switch disconnection.
Drain pump faultController fault.2. Drain pump operation error.
Indoor unit or MultiIndoor unit fan continues for 3. Drain hose blockage.
Controllerunit fault.
Check connection of connector CN10
(Drain pump: Indoor main, PC board
h
h
(MCC-1292), CN10)
(Drain pump: Multi Controller, PC board
(MCC-1210) PJ10)
Check and modify wiring circuit.
(MCC-1292), (MCC-1210)
Is drain pump connected?
Ye s
j
Does float switch operate?
Ye s
No
No
h
Is circuit wiring
normal?(*1)
No
Indoor PC board error
(MCC-1292), (MCC-1210)
Float switch error
Check and modify wiring
circuit.
1 and 2/1 to 3 of the indoor main PC board,
is 230V or not (MCC-1292), (MCC-1210).
j
Does drainage water collect?
Ye s
j
Does drain pump operate?
Ye s
j
Check for blockage of
drainage hose.
(*1) For confirmation, check voltage under condition that
connector is connected to CN10, pins 5 and 7,
PJ10, pins 1 and 2
No
No
h
Is power to drain
pump turned on?(*2)
Ye s
j
Drain pump error
No
h
h
h
(*2) Check whether voltage of CN10/PJ10, pins
Check codeOperation cause
[0C]
Indoor sensor (TA) short or open circuit alarmTA sensor open/short
TA sensor open/short has been detected. Check disconnection of connector connection (TA sensor: CN04)
circuit and resistance value characteristics of sensor.
When the sensors are normal, replace indoor PC board (MCC-1292).
Check codeStatus of air conditionerOperation cause
[0D]Indoor unit fan stops.TC sensor open/short
Indoor sensor (TC) short ‘Preheat defrost’ is
or open circuit alarmdisplayed on R/C.
TC sensor open/short has been detected. Check disconnection of connection (TC sensor: CN05) circuit
and resistance value characteristics of sensor.
When the sensors are normal, replace indoor PC board (MCC-1292).
40
Page 40
Troubleshooting
Diagnostic procedure for check code
Check codeOperation cause
[11]1. Fan motor circuit connection error.
Indoor fan motor short circuit alarm2. Capacitor error.
3. Fan motor error.
4. Defective indoor PC board.
Does indoor fan operate for a
short period after resetting and
resuming?
Ye s
j
Is there a connection error of
CN07 connector?
No
j
Is approx. DC12V to 13V output
to CN07 connector 1-3 pins?
Ye s
j
No
Ye s
No
j
Is there a connection error
of CN07 connector?
No
j
Is capacitor normal?
Ye s
j
Confirm there is no
mechanical lock on the fan
motor?
No
Ye s
No
Ye s
j
Modify connection and wiring.
h
h
Replace capacitor.
Is revolution pulse input from
hole IC to CN18 connector 2-3
pins during fan operation?
(Measurement by tester:
Approx. DC2 to 2.5V)
Ye s
No
j
h
j
j
h
Check codeOperation cause
[12]1. Irregularity of power source.
Indoor PC board short circuit alarm2. Noise of peripheral equipment.
3. Defective indoor PC board.
Is there an irregularity of
power source?
No
j
Indoor PC board check
Defective t Replacement
Ye s
Check power source voltage, modify
h
Replace fan motor.
Replace MCC-1292
PC board
lines, remove noise, etc.
41
Page 41
Troubleshooting
Diagnostic procedure for check code
Check codeStatus of air conditionerOperation cause
[14]Operation stops1. Outdoor unit power supply error.
IPDU short circuit2. Wiring error on IPDU PC board.
protective operation3. AC fuse disconnection.
alarm (Power Transistor)4. Inverter compressor error.
5. Defective IPDU PC board.
Is the power supply voltage
of the outdoor unit normal?
Ye s
j
Is the connection of the wiring
connector on the IPDU PC board
normal?
Ye s
j
Is AC 20A fuse working?
Ye s
j
Is inverter compressor normal?
Ye s
j
Is smoothing capacitor normal?
(2200µ F,400V x 2)
Ye s
No
No
No
No
No
h
h
h
h
h
Confirm the power supply line.
Modify connector of wiring.
Replace IPDU PC board and fuse.
Replace IPDU PC board and inverter
compressor.
Confirm capacitance and appearance -
Replace if faulty.
Replace IPDU PC board.
42
j
Check IPDU PC board.
Page 42
Troubleshooting
Diagnostic procedure for check code
Check codeOperation cause
[17]1. Defective wiring of IPDU PC board.
Current detection circuit alarm2. Defective IPDU PC board.
Refer to outdoor unit
Is wiring connector on IPDU PC
board normal?
Ye s
j
Is compressor operation normal?
Ye s
j
Check IPDU PC board.
No
No
h
h
Modify connection of wiring
Compressor error
Check codeOperation cause
[1C]1. Outdoor unit power source error.
Extension IC, EEPROM short circuit alarm2. Interface PC board error.
(Outdoor unit error)
Is there an irregularity of outdoor
unit power source?
No
Ye s
h
Check power source voltage.
Modify power source line.
Check noise interference from outside, etc.
j
Check interface PC board fault code.
43
Page 43
Troubleshooting
Diagnostic procedure for check code
Check codeStatus of air conditionerOperation cause
[1d]Operation stops1. Outdoor unit power source error.
Compressor error alarm2. Inverter compressor circuit system error.
Refer to outdoor unit3. Inverter compressor error.
4. Inverter compressor refrigerant stagnation.
5. Defective IPDU PC board.
Is the power source voltage of the
outdoor unit normal?
Ye s
j
Does voltage reduction occur
when the fixed-speed compressor
has been activated?
No
j
Is the connection of wiring on
the IPDU PC board normal?
Ye s
j
Is there an abnormal overload?
No
j
Is the inverter compressor normal?
Ye s
No
Ye s
No
Ye s
No
Confirm the power source supply.
i
h
h
h
h
Modify connector wiring.
Modify cause of overload.
Compressor error
Is there refrigerant stagnation
in the compressor case?
Check IPDU PC board.
44
j
Ye s
h
No
j
Is the inverter winding
output normal?
No
j
Check IPDU PC board.
Ye s
Modify refrigerant stagnation in
the compressor case, and start
h
the operation.
Page 44
Troubleshooting
Diagnostic procedure for check code
Check codeStatus of air conditionerOperation cause
[1F]Operation stops1. Outdoor unit power source error.
Compressor break down2. Inverter compressor circuit system error.
Refer to outdoor unit3. IPDU PC board error.
Is the power source voltage of the
outdoor unit normal?
Ye s
j
Does the voltage reduction occur
when the fixed-speed compressor
has been activated?
No
j
Is the wiring connection on the
IPDU PC board correct?
Ye s
j
Is there an abnormal overload?
No
j
Check IPDU PC board.
No
Ye s
No
Ye s
Confirm the power source supply.
i
h
h
h
Modify wiring connector.
Remove cause of overload.
45
Page 45
Troubleshooting
Diagnostic procedure for check code
Check codeOperation cause
[21]1. Inverter high pressure SW error.
Inverter high pressure SW system alarm2. Inverter IOL operation.
3. Service valve closed.
4. Outdoor fan, capacitor error.
5. Indoor/Outdoor PMV blockage.
6. Outdoor heat exchanger blockage.
7. SV2 circuit blockage.
8. Indoor – Outdoor communication error.
9. Pd sensor error.
10.Refrigerant overcharge.
Does the inverter high pressure
switch operate?
Ye s
j
Are the inverter high pressure
switch parts normal?
Ye s
j
Is service valve fully open?
Ye s
Does the cooling outdoor fan
Is there a problem with the
outdoor unit heat exchanger?
(1) Blockage of heat exchanger
Il circuito di bypass della SV2 è normale?
Is SV2 bypass circuit normal?
j
normally operate?
Ye s
j
(2) Short circuit
No
j
Ye s
No
No
j
Check parts.
If defective, replace.
No
j
Open service valve fully.
No
Ye s
j
Remove cause.
No
j
Repair SV2 bypass circuit.
See judgment flow of IPDU IOL
Check and modify wiring
j
Are the connection, capacitor
and fan motor normal?
Ye s
Repair defective position.
j
Are the high pressure sensor
characteristics normal?
Ye s
Replace high pressure sensor.
j
Check outdoor IPDU PC board.
If defective, replace board.
(Coil error, disconnection of wiring, etc.)
No
j
operation circuit “E5”.
No
j
No
j
No
j
j
Is the inverter IOL
circuit normal?
Ye s
j
Is circuit wiring normal?
Ye s
j
46
j
A
Page 46
Troubleshooting
Diagnostic procedure for check code
A
j
Does heating indoor fan
operate normally?
Ye s
j
Are the Multi Controller PMV/
solenoid valves normal?
Ye s
j
Is there any element to block
heat exchange in the room?
(1) Filter blockage
(2) Heat exchanger blockage
(3) Short circuit
No
j
Is communication line
between indoor and outdoor
units correct?
Ye s
No
No
Ye s
j
Eliminate blocking
element
Check Multi Controller
No
j
Check and modify
wiring
j
Are the connector
connection and coil
normal?
Ye s
j
Is there a blockage on
whole valve?
No
j
PC board.
If defective, replace
h
No
j
Repair defective
position
Ye s
j
Replace PMV unit
Are the
connection and fan
motor normal?
Ye s
j
Is the sensor resistance
value characteristic TC
normal?
No
j
Repair defective
position
NoYe s
Refrigerant overcharge
j
Blockage
Pipe breakage
Abnormal overload
Check indoor PC board.
jj
If defective, replace
Replace TC sensor
47
Page 47
Troubleshooting
Diagnostic procedure for check code
Check codeOperation cause
[E5]1. Inverter IOL operation.
Inverter IOL operation2. Service valve closed.
3. Outdoor PMV 1 error.
4. Miswiring of communication between indoor and
outdoor unit.
Is IOL circuit normal?
1. Connector
2. Wiring
3. Outdoor PC board
Ye s
j
Are gas pipe, liquid pipe and
service valve of the outdoor
unit fully open?
Ye s
j
Is outdoor PMV 1
normal?
1. Connector connection
2. Wiring
3. Coil
4. Valve unit
5. Outdoor PC board
Ye s
j
Is wiring correct?
Ye s
j
Insufficient refrigerant,
blockage, pipe breakage
No
No
No
No
(Check miswiring of the outdoor unit according to miswiring check function.)
(Check there is no blockage or pipe breakage.)
h
h
h
h
Repair IOL circuit
Open service valve fully
Repair outdoor PMV
Set normal wiring
48
Page 48
Troubleshooting
Diagnostic procedure for check code
Check codeOperation cause
[80]
Gas temp. sensor (Tha) short circuitTha sensor open/short
Open/short of Tha sensor was detected. Check connector (Tha sensor: PJ1) and characteristics of sensor
resistance value.
When sensor is normal, replace interface PC board of the Multi Controller.
Check codeOperation cause
[81]
Gas temp. sensor (Thb) short circuitThb sensor open/short
Open/short of Thb sensor was detected. Check connector (Thb sensor: PJ2) and characteristics of sensor
resistance value.
When sensor is normal, replace interface PC board of the Multi Controller.
Check codeOperation cause
[82]
Gas temp. sensor (Thc) short circuitThc sensor open/short
Open/short of Thc sensor was detected. Check connector (Thc sensor: PJ3) and characteristics of sensor
resistance value.
When sensor is normal, replace interface PC board of the Multi Controller.
Check codeOperation cause
[83]
Gas temp. sensor (Thd) short circuitThd sensor open/short
Open/short of Thd sensor was detected. Check connector (Thd sensor: PJ4) and characteristics of sensor
resistance value.
When sensor is normal, replace interface PC board of the Multi Controller.
Check codeOperation cause
[84]
Gas temp. sensor (Thx) short circuitThx sensor open/short
Open/short of Thx sensor was detected. Check connector (Thx sensor: PJ5) and characteristics of sensor
resistance value.
When sensor is normal, replace interface PC board of the Multi Controller.
49
Page 49
Troubleshooting
Diagnostic procedure for check code
Check codeOperation cause
[88]1. Error connection between Multi Controller
Communication alarm between Multi Controllerand outdoor unit.
and outdoor unit2. Outdoor PC board error (MCC-1223).
3. Multi Controller PC board error (MCC-1210).
4. Multi Controller does not recognise outdoor
capacity.
Check lead connection between indoor unit and Multi Controller.
If no error is detected, replace Multi Controller board (MCC-1210) or outdoor PC board (MCC-1223).
Check codeOperation cause
[89]1. No. of connected indoor units/connected over
Indoor over capacitycapacity.
2. Incorrect set-up of indoor unit horse power or
set to 0.
Is No. of connected indoor
units acceptable? (*1)
Ye s
j
Is set-up of indoor unit
horse power correct? (*2)
Ye s
j
Is total capacity of
connected indoor units
within indoor unit diversity?
1. M/C = 135%
2. 4 M/C = 160%
Ye s
j
Check IPDU PC board
No
No
No
Indoor units from another system have been
h
h
h
incorrectly connected.
Modify miswiring/installation.
Modify set-up of horse power.
Keep capacity of connected indoor units
within unit diversity.
(*1)
Number ofMaximum No. of Indoor unit diversity Maximum system code Maximum code per
Multi Controllers indoor unitsMulti Controller
Are A, B, C internal wires normal?Check connection of wiring.
Ye s
j
Is there a connection error?
No
j
Is group operation performed?
No
No
Ye s
Ye s
j
Is SW01 set to No. 1 on
the master unit?
Ye s
j
Is SW01 duplicated?
No
No
Ye s
h
Check indoor PC board.
h
If defective, replace.
h
h
Set SW01 to 1.
Correct switch SW01.
j
Is SW01 set to No. 1?
Ye s
g
j
Does the indoor unit operate?
Ye s
No
No
j
Does serial LED (Green)
D15 on the indoor PC board
flash?
No
j
Does serial LED (Orange)
D14 on the indoor PC
board flash?
No
j
Ye s
Ye s
h
Check indoor PC board.
h
i
If defective, replace.
Check remote controller.
h
If defective, replace.
Make unit set-up No.1.
53
Page 53
Troubleshooting
Diagnostic procedure for check code
Check codeOperation cause
[A0]
Discharge temp. sensor (TD1) short circuitTD1 sensor open/short
Open/short of TD1 sensor was detected. Check connector (TD1 sensor: PJ1) and characteristics of
sensor resistance value.
When sensor is normal, replace interface PC board of the outdoor unit.
Check codeOperation cause
[A1]
Discharge temp. sensor (TD2) short circuitTD2 sensor open/short
Open/short of TD2 sensor was detected. Check connector (TD2 sensor: PJ2) and characteristics of
sensor resistance value.
When sensor is normal, replace interface PC board of the outdoor unit.
Check codeOperation cause
[A2]
Suction temp. sensor (TS) short circuitTS1 sensor open/short
Open/short of TS1 sensor was detected. Check connector (TS1 sensor: PJ3) and characteristics of sensor
resistance value.
When sensor is normal, replace interface PC board of the outdoor unit.
Check codeOperation cause
[A4]
External air sensor (Tho) short circuitTho sensor open/short
Open/short of Tho sensor was detected. Check connector (Tho sensor: PJ5) and characteristics of sensor
resistance value.
When sensor is normal, replace interface PC board of the outdoor unit.
Check codeOperation cause
[A5]
Outdoor heat exchange sensor (TE) short circuit TE sensor open/short
Open/short of TE sensor was detected. Check connector (TE sensor: PJ4) and characteristics of sensor
resistance value.
When sensor is normal, replace interface PC board of the outdoor unit.
54
Page 54
Troubleshooting
Diagnostic procedure for check code
Check codeOperation cause
[A6]1. Outdoor unit service valve closed.
Discharge temperature TD1 and TD2 alarm2. Cooling bypass PMV error.
(>130°C)3. TD sensor error.
4. Insufficient refrigerant, blockage in pipe.
5. Blockage of PMV assembly on the liquid line.
Are the gas pipe and liquid pipe
service valves of the outdoor unit
fully open ?
Ye s
j
Are PMV 2 and SV13
operating normally?
Ye s
j
Is the cooling bypass
PMV 1 normal ?
Ye s
j
Are the resistance characteristics
of TD sensor normal ?
Ye s
j
Is wiring correct ?
Ye s
No
No
No
No
No
(Check miswiring of the outdoor unit according to miswiring check function.)
h
h
h
h
h
Open valves fully.
Replace defective part.
Cooling bypass PMV 1 error.
Replace TD sensor.
Correct wiring.
Insufficient refrigerant, blockage,
Multi Controller blockage.
j
pipe breakage.
55
Page 55
Troubleshooting
Diagnostic procedure for check code
Check codeOperation cause
[A7]1. Outdoor unit service valve closed.
Suction temperature (TS) alarm (>40°C)2. Blockage PMV assembly on the liquid line.
3. TS pressure switch error.
4. Insufficient refrigerant, blockage in pipe.
Are the gas pipe and liquid pipe
service valves of the outdoor unit
fully open ?
Ye s
j
Is there a blockage in the
expansion valve on the liquid line?
No
j
Are the characteristics of TS
pressure switch normal?
(N/C type)
Ye s
j
Insufficient refrigerant, blockage,
pipe breakage.
No
Ye s
No
h
h
h
Open valves fully.
Replace expansion valve.
Replace TS pressure switch.
Check codeOperation cause
[AA]
High pressure sensor (Pd) short circuitPd sensor output voltage alarm
If there is an abnormal output voltage of Pd sensor: Check connector circuit (Pd sensor: PJ7) and output
voltage of the sensor.
If the sensor is normal, replace the outdoor interface PC board.
Sensor characteristics:
Input12 V DC (± 10%) across red and black leads of the pressure sensor.
Output0.5 to 4.5 V at 0 to 2.45 MPa across white and black leads of the pressure sensor.
56
Page 56
Troubleshooting
Diagnostic procedure for check code
Check codeOperation cause
[Ad]1. Fixed-speed compressor high pressure SW error.
Check codeOperation cause
[AF]Abnormal power phase order or missing phase of
Outdoor unit power source phasepower supply to the outdoor unit.
order miswiring
There is an abnormal power phase order or missing phase of power supply to the outdoor unit. Check
power supply wiring.
60
Page 60
Troubleshooting
Diagnostic procedure for check code
Check codeOperation cause
[b5]1. External device error.
External input display fault2. Indoor PC board error.[b6]
External interlock display fault
Fault on CN17 - fault on external device
(accessory)
Is the external device connected
to connector CN17 ?
Ye s
j
Is the external device
operating normally ?
Ye s
j
Check cause of the operation.
No
No
Check indoor PC board.
h
If defective, replace.
Check external device.
h
If defective, replace.
Check codeOperation cause
[d3]Error of temp. sensor incorporated in IGBT
TH sensor alarm(Inverter Gate Bi-Polar Transistor)
Refer to outdoor unit
There is an error with the temp. sensor incorporated in IGBT. Check connectors CN07 on IPDU PC board
and CN600 on interface PC board. If there is no problem, replace IPDU PC board.
61
Page 61
Troubleshooting
Diagnostic procedure for check code
Check codeOperation cause
[dA]1. Power supply failure.
Abnormal overheat of heat sink2. Outdoor fan error.
Refer to outdoor unit3. Heat sink installation failure.
4. Blockage of heat sink cooling duct.
5. Defective inverter PC board.
Is power supply voltage normal ?
Ye s
j
Is the wiring connector
connection normal on the
inverter PC board ?
Ye s
j
Is outdoor fan normal ?
Ye s
j
Is there a screw loose on the
IGBT module or heat sink on
inverter PC board ?
No
j
Is there a blockage in the heat
sink cooling duct ?
No
No
No
Ye s
Ye s
No
h
Check the circuit wiring, for example wiring to the
h
inverter compressor or connector connection.
h
h
h
Check power supply.
Check fan and fan motor.
Tighten screws.
Remove blockage.
Check inverter PC board.
j
62
Page 62
Control features
Outdoor unit
No. ControlDescriptionDiagram
1Defrost• During heating operation, defrost is
(Heating mode)controlled by the outdoor unit heat
exchanger temperature sensor (TE).
• When the cumulative operating time with
TE in zone [A] has amounted to 25 minutes,
defrost operation starts. Subsequent
defrosts occur after a cumulative time of 55
minutes. When heating operation resumes
after defrost, the timer is reset.
• The maximum defrost period after TE
returns to zone [B] is 1 minute.
• Heating operation resumes immediately
after TE returns to zone [C].
2Oil retrieval• During cooling operation, oil retrieval is
(Cooling mode)performed if one or more Indoor units are
OFF.
• If this condition is satisfied, when cooling
operation commences, oil retrieval takes
place for 1 minute.
If cooling operation continues, oil retrieval is
repeated for 1 minute every 60 minutes.
• During oil retrieval the following occurs:
a. All Multi Controller PMVs are opened.
The degree of opening is dependant
on the capacity of the Indoor unit .
b. If the D.O.L. compressor is OFF the
inverter compressor speed increases
to SD.
• When cooling operation ends the timer is
reset.
3Superheat control • Superheat is controlled by the Multi
(Cooling mode)Controller for cooling operation.
The level of superheat is determined by the
difference between the evaporator outlet
temperature for each indoor unit (ThA, B,
C, D) and the saturation temperature (ThX).
• If the superheat of an indoor unit enters
zone [Y], the relevant M/C PMV opens
further to compensate for this increase. The
degree of additional opening is dependant
on the capacity of the indoor unit.
• When zone [Z] is reached the PMV opening
is held at the level set in zone [Y].
• When the level of superheat returns to zone
[X] the control is cancelled.
Temp.
(°C)
12
8
-3
60 min.
1 min.
Oil
retrieval
Superheat
(°C)
13
9
A
Cooling mode
1 min.
Oil
retrieval
Y
X
C
B
< 60 min.
Z
Compr.
off
Timer
reset
63
Page 63
Control features
Outdoor unit/Multi Controller
No. ControlDescription
4Simultaneousa. Changeover between cooling and heating operations for each indoor unit.
cooling/heating
operationThe solenoid valves inside the Multi Controller are energised when operation
commands are sent from the indoor units.
• SVS valve (suction side) opens for a cooling command.
• SVD valve (discharge side) opens for a heating command.
b. Determination of the outdoor unit operation mode and frequency of the
compressor.
These are determined by the difference between the total requested cooling
command frequencies and the total requested heating command frequencies
of all Indoor units.
c. Outdoor unit refrigerant control during cooling dominant mode.
• Refrigerant flow is controlled by PMV2. The degree of opening is
controlled by the difference of all requested cooling and heating command
frequencies and the compressor operation frequency.
This flow control is required to divide cooling exhaust heat appropriately
between indoor units in heating mode and the outdoor unit heat exchanger.
• High pressure control is performed to ensure that the capacity of the
indoor units in heating is maintained. This is controlled by the outdoor
unit fan control and the changeover from the main heat exchanger to the
sub heat exchanger.
d. Outdoor unit refrigerant control during heating dominant mode.
• Superheat control is performed by the outdoor unit expansion valve.
• Evaporating temperature control is performed by the outdoor unit fan
control to ensure that the capacity of the Indoor units in cooling mode is
maintained.
• Changeover from expansion valve to capillary control is performed
when there is a minimal difference between the cooling and heating
demands and the heat absorption of the outdoor unit heat exchanger is low.
64
Page 64
Valve and sensor function and operation
Multi Controller
Multi Controller - valve functions
SymbolName of valveDescription of function
PMV (A, B, C, D)Flow rate control valveThis opens to the extent corresponding to the capacity
and performance required of each indoor unit.
SVS (A, B, C, D)Suction gas valveOpens when commands from the indoor units require
cooling operation.
SVD (A, B, C, D)Discharge gas valveOpens when commands from the indoor units require
heating operation.
SVSSPressure reducingOpens when the number of units in heating operation
solenoid valveis reduced (heating to shutdown or cooling).
Opens when defrost operation starts.
Opens during oil retrieval control in cooling operation.
SVDDPressure increasingOpens when the number of units in heating operation
solenoid valveis increased (shutdown or cooling to heating).
Opens while control is performed to prevent liquid
in discharge pipe from being blocked.
SVHSuperheat solenoid valveOpens when unit in cooling operation is present.
control
SimultaneousExpansion valveONOFFOFFONOFFONheating-dominantCapillaryONOFFOFFOFFONON-
operation
Manual operation of valves
Note:1. Ensure that the system is OFF before valves are manually operated.
2. Valves will reassume their required position unless electrically isolated.
a.Multi Controller
Display switchValveShort point
position
0PMV ATP 1TP 2
1PMV BSelected valve is fully opened for 2Selected valve is fully closed for 2
2PMV Cminutes.minutes
3PMV D
b.Outdoor unit
SW1 SW2Short pointOperationFunction
0N/ATP1Valves will automatically assumePMV 1 fully open for 2 minutes.
1their required position after 2PMV 2 fully open for 2 minutes.
0TP2minutes.PMV 1 fully closed for 2 minutes.
1PMV 2 fully closed for 2 minutes.
20TP3Push SW04Solenoid valves manually energised
in sequence when pressed.
Press SW03Solenoid valves automatically
energised in sequence
(1 second intervals)
Note:
During Manual/Automatic operation of outdoor valves, SV17 will not be energised. To confirm operation of SV17 operation is as follows: Energised valve
when compressor ON.
67
Page 67
Valve and sensor function and operation
Sensor and switch operation
Multi Controller sensor operation
TemperatureAccording to a difference between the evaporator outlet temperature and
sensor(ThA, B, C, D) saturation temperature (ThX):
a. Performs superheat control.
(cooling operation)
b. Determines the degree of opening of PMV 2.
(cooling-dominant operation)
Outdoor unit sensor and switch operation
Discharge pressureDetermines the frequency of the inverter compressor and the ON/OFF status of
sensorD.O.L. compressor.
Controls the outdoor unit fan operation.
Controls the hot gas bypass SV2.
Controls the changeover from outdoor unit main heat exchanger to sub heat
exchanger.
Suction temperatureControls the degree of opening of PMV 1.
sensor (ThS)Stops operation when ThS > 40°C for 10 minutes (Fault code [A7]).
Discharge temperature Controls the degree of opening of PMV 1.
sensor (ThD1, ThD2)Stops operation when the discharge temperature > 130°C (Fault code [A6]).
Outdoor unit heatControls the defrost operation.
exchanger sensor (TE) Controls the outdoor unit fan operation.
Heating operationControls the high pressure release valve SV1.
Outdoor temperatureControls the hot gas bypass SV2.
sensor (ThO)Controls the outdoor unit fan operation.
Prevents heating operation when ThO > 25°C.
High pressure switchStops operation when Pd > 30 kgf/cm2G.
Low pressure switchStops operation when suction pressure < 0.25 kgf/cm2G:
• After 30 seconds for cooling operation.
• After 10 minutes for heating operaton.
The low pressure switch is ignored during defrost operation.
68
Page 68
Refrigerant pipe installation
Leak test
Airtight test
Carry out an airtight test after the refrigerant piping is complete. For an airtight test, connect a nitrogen
gas bottle as shown, and apply pressure (use oxygen-free nitrogen, OFN).
The pressure test must be completed before supplying power to ensure that the Multi Controller PMVs
(pulse modulating valves) are open.
The test must be completed with the indoor units, Multi Controllers and outdoor unit connected.
•Be sure to carry out the test from the service ports of the packed valves at the discharge gas,
liquid and suction gas side.
•Keep all of the valves at discharge gas, liquid and suction gas sides fully closed. Nitrogen may
enter the cycle of the outdoor unit. Therefore, retighten the valve rod before applying pressure.
(For all valves.)
•For each refrigerant line, apply pressure gradually at the discharge gas, liquid and suction gas
sides.
Never use oxygen, or a flammable noxious gas.
Detailed drawing of packed valve
Service port at gas
discharge side
To
manifold
Service port at
gas suction side
Service port at
liquid side
Packed valve fully closed
(gas suction side)
Brazed
Flare
connection
Flare
connection
Inverter outdoor unit
Service port
Service port
Packed valve fully
closed (liquid side)
Packed valve fully closed
(gas discharge side)
Copper
pipe
ø 6.4
Low
pressure
gauge
High
pressure
gauge
Gauge
manifold
Regulator
Copper
pipe
ø 6.4
Nitrogen
gas
To detect a large leakage
Step 1: 0.3 MPa (3 kg/cm2 G) Apply pressure for 3 minutes or more
Step 2: 1.5 MPa (15 kg/cm2 G) Apply pressure for 3 minutes or more
To detect a fine leakage
Step 3: 3.0 MPa (30 kg/cm2 G) Apply pressure for 24 hours
•Check for a reduction in pressure.
If there is no reduction in pressure this is acceptable.
If there is a reduction in pressure check for a leakage.
(Note: If there is a difference of ambient temp. between when the pressure was applied and 24 hours later,
then pressure could change by approx. 0.01 MPa (0.1 kg/cm2 G) - so correct the pressure change.
69
Page 69
Refrigerant pipe installation
Vacuuming
Leak position check
If a pressure drop is detected, check for leakage at connecting points. Locate the leakage by listening,
feeling, using foaming agent, etc. - then rebraze or retighten.
Air purge
The air purge must be completed before supplying power to ensure the Multi Controller’s PMVs are
open.
Using a vacuum pump, complete an air purge. Never use refrigerant gas.
•After the airtight test, discharge the nitrogen gas.
•Connect a gauge manifold to the service port at discharge gas, liquid and suction gas sides, and
connect a vacuum pump as shown.
•Be sure to vacuum at discharge gas, liquid and suction gas sides.
Detailed drawing of packed valve
Packed valve fully closed
(gas suction side)
Inverter outdoor unit
Low
pressure
gauge
High
pressure
gauge
Gauge
manifold
Service port at gas
discharge side
To
manifold
Service port at
gas suction side
Service port at
liquid side
Brazed
Flare
connection
Flare
connection
Service port
Service port
Packed valve fully
closed (liquid side)
Packed valve fully closed
(gas discharge side)
Vacuum pump
•Use a vacuum pump with high vacuum carry-over degree (-0.013 x 105 Pa; 0.750 mm Hg or less) and
large displacement (40 l/min. or more).
•Ensure to create a vacuum at -0.013 x 105 Pa (0.75 mm Hg) at the discharge gas, liquid and suction
gas.
•After the procedure has been completed, replace the vacuum pump with a refrigerant bottle and add
the refrigerant if required.
70
Page 70
Refrigerant pipe installation
Charging the system with additional refrigerant
Adding the refrigerant
After the airtight test, replace the vacuum pump with a refrigerant bottle to charge the system.
Calculating the additional refrigerant required
The Super Multi contains sufficient refrigerant to operate an installation having 5 metres of pipework (when
delivered). The refrigerant amount at shipment does not include the refrigerant needed for the piping - so
first calculate this amount, and then add it.
The total refrigerant charge must be calculated by the weight and within a tolerance of ± 50 g.
Refrigerant charge amount shipped from the factory:
Outdoor unit model nameMAR-F105HTM8-PE
Charging amount (kg)19.0
Maximum gas charge (kg)36.3
The amount of additional refrigerant is calculated from the actual length of the liquid pipe.
To calculate the additional refrigerant volume, refer to the diagram and follow the steps below:
(i)The main pipe length is taken as the addition of pipes X, Y and Z.
(ii) The sub pipe length is taken as the addition of the two longest of the four (if 4 Multi Controllers).
(iii) The branch pipe lengths must be individually calculated using the 8 longest pipes.
(iv) Do not attempt to add gas above the maximum shown in the table above.
(v) For systems with one Multi Controller ignore the sub-pipe section within the additional gas charge
calculation.
(vi) When using three Multi Controllers, it is important that a reducer is used on the pipework for the third
Multi Controller. Pipework before the reducer is classed as main piping and after as sub piping.
Charging the system
•Keeping the outdoor unit valve closed, charge the refrigerant from the service port on the liquid side.
•If the specified amount of refrigerant cannot be charged - fully open all the outdoor unit’s valves, then
perform the cooling operation with the valve at the gas side slightly closed.
•If leaks cause a shortage of refrigerant - recover the refrigerant from the system, and recharge with
new refrigerant to the total refrigerant charge.
•Prolonged operation with either an overcharge or deficiency in refrigerant will lead to a loss of
performance, increased running costs and will cause damage to the machine. Warranty will be void.
71
Page 71
Additional refrigerant
One Multi Controller
Additional refrigerant
Piping
Outdoor
L1
Two Multi Controllers
Outdoor
L1
L2
Three Multi Controllers
Outdoor
X
Y
Z
Indoor
M/C
L3
Indoor
M/C
L3
Table 1 - Branch pipes
RAV-10* : 0.030 kg/m
RAV-13* : 0.030 kg/m
Indoor
RAV-16* : 0.030 kg/m
RAV-26* : 0.045 kg/m
M/C
RAV-36* : 0.045 kg/m
RAV-46* : 0.045 kg/m
L2
L3
Example:
RAV-464CH-PE i RAV-46*
Four Multi Controllers
Indoor
Outdoor
X
Y
Z
PipeAdditional gas/metreAdditional gas
MAR-F105 - main pipe L1 (X+Y+Z) (minus 2 m) x0.19 kg/m=
1st longest sub pipe L2 (minus 1 m)x0.125 kg/m=
2nd longest sub pipe L2 (minus 1 m)x0.125 kg/m=
1st longest branch pipe L3 (minus 2 m)xRefer to Table 1=
2nd longest branch pipe L3 (minus 2 m)xRefer to Table 1=
3rd longest branch pipe L3 (minus 2 m)xRefer to Table 1=
4th longest branch pipe L3 (minus 2 m)xRefer to Table 1=
5th longest branch pipe L3 (minus 2 m)xRefer to Table 1=
6th longest branch pipe L3 (minus 2 m)xRefer to Table 1=
7th longest branch pipe L3 (minus 2 m)xRefer to Table 1=
8th longest branch pipe L3 (minus 2 m)xRefer to Table 1=
M/C
L1 = Main pipe (X + Y + Z)
L2 = Sub pipe
L2
L3
Total additional gas charge=kg
L3 = Branch pipe
72
Page 72
Refrigerant pipe installation
Additional refrigerant charging method
(1) Loosely connect the refrigerant cylinder hose to the gauge manifold, then open the source valve VH on
the cylinder, purge the air in the hose, and then tighten the hose.
(2) As shown in the diagram below, turn the refrigerant cylinder upside down, open the valve VH on the
gauge manifold, and then charge the liquid side pipe with refrigerant in the liquid state. (Note that with
some types of refrigerant cylinders, the liquid refrigerant will be output through siphoning action with
the cylinder in the normal upright position.) If the proper charging amount cannot be reached, close
the valve VH, turn the refrigerant cylinder upright, open the liquid-side and balance packed valves
completely, and open the gas-side packed valve only half way. Begin the cooling operation, open
valve VL, and then charge the gas-side pipe with refrigerant in the liquid state.
(3) While watching the scales display, quickly close the valve VL completely when the system has been
charged with the proper amount of additional refrigerant. Then close the source valve Va on the
cylinder, and open the gas-side packed valve completely.
(4) Record the amount of additional refrigerant that was added to the system on the nameplate inside the
front panel (lower) of the outdoor unit.
Indoor unit
Liquid pipe
Gauge manifold
Gas pipe
Refrigerant
bottle
V
Scales
Packed valve
(liquid side)
Low
High
pressure
pressure
V
H
V
L
Gas
Liquid
a
Refrigerant
gas
Packed valve (discharge gas side)
Outdoor unit
73
Page 73
Exploded view and service parts
Outdoor unit
74
Page 74
Exploded view and service parts
Outdoor unit
12
j
14
75
Page 75
Exploded view and service parts
Outdoor unit
Ref. ServiceDescription
part No.
0143A00020Plate side (Right)
0243A00021Plate side (Left)
0343A00022Air-in cabinet (Front)
0443A00023Air-in cabinet (Back)
0543A00024Cabinet-down (Front)
0643A00025Cabinet-down (Back)
0743A00026Service panel
0843A00027Air-out cabinet
0943A20004Propeller fan - PY631
1043A41504Compressor - 10 HP (INV)
1143A49011Switch, high pressure
1243A49006Switch, high pressure
1343151230Switch, low pressure
1443A49012Pressure sensor service kit
1543A46038Solenoid coil assembly
1643A46039Solenoid coil assembly
1743A6040Solenoid coil assembly
1843146252Check valve
1943A46032Check valve - Dia. 15 mm
2043146351Service valve (1-1/8”)
2143146503Packed valve (5/8”)
2243146504Packed valve (3/4”)
2343146398Valve body
24430461512-way valve
2543A46041Pulse modulating valve (PMV 1)
2643A46042Pulse modulating valve (PMV 2)
2743A46010Expansion valve
2843A460074-way valve
Note:
Part 35 - Replace both dryers at the same time.
Ref. ServiceDescription
part No.
2943A48005Accumulator
3043A48006Liquid tank
3143A60013Fusible plug
3243A43018Condenser assembly - right
3343A43019Condenser assembly - left
3443A44089Sub condenser
3543A45003Dryer-XH-10C
3643A46036Check joint
3743147529Strainer
3843147537Strainer
3943A57002Accumulator heater
4043A51005Isolator
4143A21022Fan motor
4243107200Spring
4343195198Spacer
4443195186Rubber cushion - under
4543195185Rubber cushion - upper
4643A95001Rubber support cushion
4743A19011Fan guard
4843A16007Wiring diagram
4943A55008Capi-form-SV15
5043A55009Capi-form-4WV
5143A55010Capi-form-SV1
5243A55011Capi-SV2 (straight)
5343A55012Capi-form-SV16
5443A47034Capi-form-compressor
5543A86001EP window
5643A89002Push fastener
5743A89003Adjuster pen
76
Page 76
Exploded view and service parts
Outdoor unit - inverter assembly
Ref. ServiceDescription
part No.
10143A52005 Magnetic contactor - FC - 3
10243A58009 Transformer - TT01
10343A55004 MF - capacitor - 8µF/450 V AC
10443A55005 Capacitor - electrolytic -
2200µF/400 V
10543A50030 Temperature sensor TS - blue
10643A50031 Temperature sensor THO - green
10743A50032 Temperature sensor TE - black
10843A50015 Temperature sensor TD1 - white
10943A50016 Temperature sensor TD2 - red
11043A50033 Thermistor (PTC)
11143A69016 Heatsink
11243A69035 PC board (IPDU) MCC-1342
11343A69018 PC board (noise filter) MCC-1366
14443A69036 PC board (interface) MCC-1223
11543A69037 PC board (communication)