Toshiba MAR-F102HTM8-PE, MAR-M102HTM8-PE SERVICE MANUAL

SERVICE MANUAL
AIR-CONDITIONER
FILE NO. A90-9819
Outdoor Unit
Multi Controller
3-PIPE SUPER MULTI, HEAT PUMP WITH
SIMULTANEOUS HEATING AND COOLING
Outdoor Unit Multi Controller
MAR-M102HTM8-PE RBM-Y1032-PE (3-way) RBM-Y1042-PE (4-way)
MAR-F102HTM8-PE RBM-Y1032F-PE (3-way) RBM-Y1042F-PE (4-way)
Printed in UK March 1998 s
CONTENTS
1. SUPER MULTI SYSTEM BASIC COMPONENTS.....................................................................................
2. OUTLINE OF CONTROL SYSTEM............................................................................................................
3. SPECIFICATIONS......................................................................................................................................
4. CONSTRUCTION VIEWS..........................................................................................................................
5. WIRING DIAGRAMS..................................................................................................................................
6. REFRIGERANT CYCLE DIAGRAMS................................................................................................... .....
7. SELF DIAGNOSTIC DISPLAY INFORMATION........................................................................................
8. FAULT CODE DISPLAY INFORMATION..................................................................................................
9. CONTROL FEATURES.............................................................................................................................
10. VALVE & SENSOR FUNCTION AND OPERATION............................ ....................................................
11. PRESSURE TEST AND DEHYDRATION.................................................................................................
12. ADDITIONAL REFRIGERANT...................................................................................................................
13. EXPLODED VIEWS AND SERVICE PARTS LIST....................................................................................
10
13
19
21
36
43
45
49
50
51
SUMMARY
The units referred to within this manual conform with the protection requirements of Directives 89/336/EEC
Electromagnetic Compatibility and 73/23/EEC Low voltage.
Operating conditions of the unit are as follows:
3
4
6
Outdoor temperature -5 ~ 43°C Cooling
-10 ~ 21°C Heating
Room Temperature 18 ~ 32°C Cooling
15 ~ 29°C Heating
Room humidity < 80% Cooling
Note 1: Cooling capacity is rated at the following temperature conditions:
Indoor air inlet temperature 27°C DB, 19°C WB. Outdoor air inlet temperature 35°C DB.
Note 2: Heating capacity is rated at the following temperature conditions:
Indoor air inlet temperature 20°C DB. Outdoor air inlet temperature 7°C DB, 6°C WB.
Note 3: For details on the Outdoor unit installation, the Indoor units or Remote Controllers refer to
the relevant literature. i.e. Installation instructions supplied with the units or Service manuals relevant to the indoor units.
Note 4: Operatives handling refrigerants must be suitably qualified in accordance with local and
national codes of practice and statutory requirements.
Note 5: Legislation may regulate the removal of waste refrigerant from the systems. We advise
awareness of any regulations and duty of care. Waste refrigerant must NEVER be discharged to atmosphere.
Note 6: Electrical work should be in accordance with all relevant codes of practice and should be
carried out by suitably qualified personnel.
Note 7: Metric / Imperial pipe conversion.
Diameter (mm) 6.4 9.5 12.7 15.9 19.0 22.0 28.6 Nominal diameter (inch) 1/4 3/8 1/2 5/8 3/4 7/8 1 1/8
Note 8: Within this manual, O/D = Outdoor unit, M/C = Multi controller, I/D = Indoor unit, R/C = Remote
controller, D.O.L. = Direct on-line compressor.
2
1. SUPER MULTI SYSTEM BASIC COMPONENTS
1.1 2-Pipe Heat Pump.
This system allows separate operation of each indoor unit in heating or cooling.
Heating operation has priority over cooling. In the event of an indoor unit requesting cooling operation when another is in heating mode, the "PREHEAT DEFROST" will flash on the remote controller.
2-Pipe Outdoor unit
T-Pieces
2 pipes
Multi controller
OFF
Indoor units
OFF
Remote controller
2 pipes
1.2 3-Pipe Heat Pump with simultaneous heating and cooling.
This system allows separate operation of each indoor unit in either heating or cooling simultaneously.
3 pipes
3-Pipe Outdoor unit
T-Pieces
Multi controller
Indoor unit remote controller requesting cooling
Cooling operation
Indoor unit remote controller requesting heating
Heating operation
Indoor units
Remote controller
2 pipes
3
2. OUTLINE OF CONTROL SYSTEM
The refrigerant and electrical systems of the Super multi air conditioner are controllled by the Multi controller and the Outdoor unit microprocessors.
All RAV Heat Pump series Indoor units are compatible with the Super multi system. i.e. 1 ~ 5 HP.
For system operation, initially the microprocessor in each Indoor unit calculates the difference between the current room temperature (TA) and the requested temperature which has been set on the Remote controller. A demand signal is determined and transmitted to the Multi controller microprocessor in the form of operation commands. (i.e. ON / OFF, cooling or heating operation mode, operation demand frequency).
The Multi controller microprocessor receives operation commands from all Indoor units connected, calculates the accumulative operation command and transmits this information to the Outdoor unit Interface microprocessor.
The Interface microprocessor calculates the capacity required for heating or cooling and determines the operation mode of the Outdoor unit and the actual frequency of the compressor.
2.1 Control system diagram.
Indoor unit 1 – A
Fan
Temp. sensor (TA)
Drain Pump
Indoor unit microprocessor
Remote
controller
1 - B
1 - C
1 - D
Multi controller 1
Capacity rank setting switch
Temp. sensor
Pulse modulating
valve
Multi controller
microprocessor
Display LED
2-way valve
(3-Pipe ONLY)
Outdoor unit
Protection unit
Comp. sensor
Temp. sensor
Pulse modulating
valve
Interface microprocessor
D.O.L.
compressor
Display LED
2-way valve
Fan
2 - A
2 - B
2 - C
2 - D
Multi controller 2
Multi controller
microprocessor
4
4-way valve
Inverter
microprocessor
Protection
unit
Inverter
compressor
Inverter
Power supply
2.2 Combination of Multi Controllers and Indoor Units.
Each Indoor unit is allocated a code number according to its capacity rank. Refer to the table below.
Capacity Rank of Indoor unit
No connection
10
13
16
20
26
36
46
Example: Indoor unit model RAV-362UH-PE, Capacity Rank = 36, Code No. = 8.
(Each Indoor unit Code No. is registered by the capacity rank setting switches on the Multi controller control board).
Multiple Indoor units may be connected to each Outdoor unit, providing the total Indoor code does not exceed the limits shown below.
Outdoor Unit
Code No.
0
2
3
4
5
6
8
10
Maximum No. of
Connected Units
Minimum Code No. Maximum Code No.
10HP 2-PIPE (MAR-M102HTM8-PE)
10HP 3-PIPE (MAR-F102HTM8-PE)
The option is available to use a 3-Way Multi controller (for 3 Indoor units), or a 4-Way Multi controller (for 4 Indoor units). If more than 4 Indoor units are required for an Outdoor unit, 2 multi controllers should be used with T-Piece connections.
Note: It is possible to connect indoor units with a total capacity exceeding the capacity of the outdoor unit
by a maximum of 35%.
2728
5
3.1 Specification of Outdoor unit.
3. SPECIFICATIONS
Model Name
Cooling capacity (kW)
Heating capacity (kW)
Power supply
Operating current (A)
Power consumption (W)
Cooling
Power factor (%)
Operating current (A)
Power consumption (W)
Heating
Power factor (%)
Starting current (A)
Starting method
Dimensions (H x W x D) (mm)
Net weight (kg)
Colour
Compressor
Type
Motor output (kW)
MAR-M102HTM8-PE
25.0 (28.0)
28.0 (31.5)
380 – 415V, 3-phase, 50Hz
15.7 (17.2)
10,600 (11,500)
17.7 (15.5)
11,800 (10,500)
1,530 x 1,290 x 834
356
To be confirmed
Hermetically sealed (Twin scroll)
MAR-F102HTM8-PE
97 (97)
96 (98)
60
Direct
370
7.5
Fan
Fan assembly
Refrigerant (charged weight) (kg)
Liquid (mm)
Discharge gas (mm)
Suction gas (mm)
Coupler style
Max. equivalent piping length (m)
Max. actual piping length (m)
Max. piping head (m)
Motor output (kW)
Air flow volume (m3/hr)
Liquid Discharge gas Suction gas
Propeller fan
0.15 x 2
10,000
R-22 (18.6)
ø15.9
- ø19.0
ø28.6
Flare connection
-
Brazing connection
120
100
50: When the outdoor unit is installed above.
20: When the outdoor unit is installed below.
R-22 (21.6)
Flare connection
Crank case heater (W)
The specification shown in ( ) denotes operation with the maximum capacity of indoor units connected
(i.e. 135% capacity of the outdoor unit).
Specifications are subject to change without notice.
6
74
3.2 Specifications of Outdoor unit Refrigerant Cycle Parts
Comp­ressor motor
Fan motor
Model Name
Model name
Motor type
Power supply
Output (kW)
Pole (P)
Coil resistance (Ω)
Compressor oil name
Amount of oil (cc)
Model name
Motor type
Power supply
Output (W)
Supply current (A)
Pole (P)
MAR-M102HTM8-PE MAR-F102HTM8-PE
HV1201CW-Y12
3-phase induction motor
380 – 415V, 3-phase, 50Hz
7.5
2/2 (Inverter side/Non-inverter side)
1.49/2.51
(Inverter side/Non-inverter side)
SUNISO 3GSD
7,000
STF-200-150C
1-phase, induction motor
220 – 240V, 1-phase, 50Hz
150
1.12 ~ 1.44
6
Inner over-load relay
High pressure switch Low pressure switch
4-way valve
Compressor case heater
Pressure sensor
Discharge temperature sensor
Suction temperature sensor
Outdoor air temperature sensor
Pulse modulating valve (For bypass)
Pulse modulating valve
2-way valve
2-way valve
Model name
Operating pressure (kgf/cm2G)
Model name
Operating pressure (kgf/cm2G)
OFF: 115 ± 5°C
20PS-B (Inverter side), 20PS-G (Non-inverter side)
Operation 30, Reset 23
20PS-1
Operation 0.25, Reset 1.5
CHV-0712, Coil AC240V
AC 240V, 74W
Model name: NTP-Q250TF-2
Input voltage: DC 12V
Output voltage: DC 0.5 – 4.5V
At 25°C = 50k, 50°C = 17.9k, 100°C =3.35k
At 0°C = 32.8k, 25°C = 10k, 50°C = 3.6k At 0°C = 32.8k, 25°C = 10k, 50°C = 3.6k
NEV202DXF, Coil AC 240V
EV18RC2, Coil DC 12V
-
-
EV23RC8, Coil DC 12V
RP100-03, Coil AC 240V
Specifications are subject to change without notice.
7
3.3 Specifications of Outdoor unit Inverter Assembly Parts.
Model Name MAR-M102HTM8-PE MAR-F102HTM8-PE
Power supply
Output voltage at operating frequency of 60Hz
IGBT
Relay
Fan motor running capacitor
Diode
AC noise filter
DC noise filter
Power supply rectifier capacitor
Fuse
Electronic starter
Reactor
Fan motor relay
Control relay
Magnetic contactor for compressor (Inverter side)
Magnetic contactor for compressor
(Non-inverter side)
380 – 415V, 3-phase, 50Hz
AC 266V
MG50Q6ES11
LY1F (AC 240V)
EAG45M605UF1, 6µF450V
SR130G-160
ZSG2208-02, 8A, 250V
LF215AV, 15A, 716V
LNT2G222KSMCTF, 2200µF/400V
20A
912X25E101YV20
CH-26-T, 6.2mH, 18A
G2R217PV
G4U-112P
13A
15A
Transformer (Inverter)
Transformer (Interface)
Power supply terminal plate
PC board (Inverter)
PC board assembly (Interface)
PC board (Gate)
Cooling fan
Specifications are subject to change without notice.
FT70
FT69
AC600V, 60A
MCC-1251 (INV-M-E) MCC-1251 (INV-F-E)
MCC-1211
MCC-1252
-
MCC-1223
3650EXV-5, 220-240V
8
3.4 Specification of 2-Pipe Multi Controller Parts.
Model Name
Pulse modulating valve
Temperature sensor
Float switch
Model name
Power supply transformer
Specification
Relay (PC board)
Heater
Thermal fuse for heater
Heater fuse
3.5 Specification of 3-Pipe Multi Controller Parts.
Model Name
Pulse modulating valve
Temperature sensor
RBM-Y1032-PE RBM-Y1042-PE
EV23RC7, Coil DC 12V
At 0ºC = 32.8k, 25°C = 10kΩ, 50°C = 3.6k
FS-085-0031
FT69
Primary side:AC240V, Secondary side:AC12V
G2R-117P, Coil DC 12V
10.4 W/m
65W50W
Cut out at 119°C
1A
RBM-Y1032F-PE RBM-Y1042F-PE
EV23RC7, Coil DC 12V
At 0ºC = 32.8k, 25°C = 10kΩ, 50°C = 3.6k
Float switch
Model name
Power supply transformer
Specification
Relay (PC board)
Heater
Thermal fuse for heater
Heater fuse
Discharge gas side 2-way valve
Suction gas side 2-way valve
2-way valve
2-way valve NEV603DXF-AC240V
Specifications are subject to change without notice.
Primary side:AC240V, Secondary side:AC12V
REV-1506DXFQ6, Coil AC240V
FS-085-0031
FT69
G2R-117P, Coil DC 12V
10.4 W/m
Cut out at 119°C
1A
RP100-03, Coil AC240V
NEV202DXF-AC240V
65W50W
9
4. CONSTRUCTION VIEWS
4.1 2-Pipe Outdoor Unit (MAR-M102HTM8-PE).
Rear air inlet.
ø 610
1290
650
1100
4 slots (15 x 20) for fixing bolts.
790
834
Air outlet.
750
120
98
Side air inlet.
Refrigerant pipe
connection.
Liquid Ø 15.9
Gas Ø 28.6
365
335
140 65
1212
100
1410
500
2 x Fork lift slots.
Piping knockout.
(150 x 60)
Wiring knockouts. 1 x Ø25, 2 x Ø20
10
4.2 3-Pipe Outdoor Unit (MAR-F102HTM8-PE).
Rear air inlet.
ø 610
1290
650
1100
4 slots (15 x 20) for fixing bolts.
834
790
Air outlet.
750
120
98
Side air inlet.
Refrigerant pipe
connection.
Suction gas Ø 28.6 Discharge gas Ø 19.0
Liquid Ø 15.9
365
335
1212
65
65140
100
1410
500
2 x Fork lift slots.
Piping knockout.
(150 x 60)
Wiring knockouts. 1 x Ø25, 2 x Ø20
11
4.3 Multi Controllers.
Wiring knockouts
Refrigerant piping joint (brazing)
Liquid side φ 15.9
6 xφ 20
Refrigerant piping joint (brazing)
Discharge gas side φ 19
Wiring knockouts
Refrigerant piping joint (brazing)
Liquid side φ 15.9
6 xφ 20
540
2 Slots for
hanging bolts
(12 x 52)
3-PIPE: RBM-Y1032F-PE, RBM-Y1042F-PE
540
2-PIPE: RBM-Y1032-PE, RBM-Y1042-PE
Refrigerant piping joint (brazing)
Suction gas side φ28.6
---
---
---
---
---
---
Refrigerant piping joint (brazing)
Suction gas side φ28.6
Indoor unit piping
100 or more
Outdoor unit
side
500
or more
500
or more
piping side
500
or more
450 x 450 inspection opening
Electric parts box
Note: Make an inspection opening at the specified location.
This is required for testing and servicing.
2 Notches for hanging bolt
(12 x 21)
Electrical parts box
Refrigerant piping joint (brazing)
Gas side φ 19
φ12.7
Refrigerant piping joint (brazing)
Liquid side
12
A BC DE F G
460 300 90 90 100
530 370 90 90 90 90 190
460 300 90 90
530 370 90 90 90 90
MODEL
RBM-Y1032-PE
RBM-Y1042-PE
RBM-Y1032F-PE
RBM-Y1042F-PE
5.1 2-Pipe Outdoor Unit (MAR-M102HTM8-PE)
9
9

5. WIRING DIAGRAMS

Symbol Part Name
CM 1, 2 Compressor FM 1, 2 Fan Motor 52C 1, 2, 3 Electromagnetic contactor
for compressor 49C 1, 2 Inner overload relay 51C 3 Overload relay PMV1 Pulse modulating valve 63H 1, 2 High pressure switch RC 1, 2 Running capacitor SV 1, 2, 4 Two-way valve 20SF Four-way valve 63L Low pressure switch CH Crank case heater Tr 1, 2 Transformer 47C Reverse phase protector Th D1, D2, S, E Temperature sensor CD 1, 2 Current detector
Ferrite Core
Noise filter
Capacitor
Fuse
Electric
Starter
3 ø
Rectifier
Noise
Filter
Reactor
Electrolytic
Capacitor
Power Transistor
Clip
Diode
Inverter Control PC Board
MCC - 1251
Thermostat
Clip Diode
(Inverter)
Notes :
1.The dashed lines indicate wiring on site.
2. and indicate terminal blocks, and numbers within them are terminal numbers.
2345678
2345678
3. indicates a printed circuit board.
DANGER
THE ELECTROLYTIC CAPACITORS IN THIS PANEL ARE CHARGED TO 600 VOLTS D. C.
BEFORE SERVICING, TURN OFF THE POWER SUPPLY AND ALLOW AT LEAST 20 MINUTES FOR THE CAPACITORS TO DISCHARGE TO A SAFE LEVEL OF 5 VOLTS D.C. OR LESS. TEST WITH A D.C. VOLT METER AS SHOWN.
Resistor
NEVER SHORT THE CAPACITOR TERMINALS WITH ANY METAL IMPLEMENT TO DISCHARGE. PERSONAL INJURY OR EQUIPMENT DAMAGE MAY RESULT.
Parts layout
Fuse
Relay
Fuse
Noise
Filter
Noise
filter
Capacitor
Interface Control Board
MCC - 1211
Pressure
Sensor
Electrolytic Capacitors
PC boards
Fuse
Power supply
PC board locations
MCC-1211
Inverter
Compressor
Power Transistor
Rectifier
3 ø
Noise filter
Connectors
1~6
7~12
Surge Absorber
Power Supply
Surge
Absorber
13
14
5.2 3-Pipe Outdoor Unit (MAR-F102HTM8-PE)
9
9
Symbol Part Name
CM 1, 2 Compressor FM 1, 2 Fan Motor 52C 1, 2, 3 Electromagnetic
contactor for compressor 49C 1, 2 Inner overload relay 51C 3 Overload relay PMV 1 Pulse modulating vavle 63H 1, 2 High pressure switch RC 1, 2 Running capacitor SV 1, 2, 4, 5, 13, 14, 15, 16 Two-way valve 20SF Four-way valve 63L Low pressure switch CH Crank case heater Tr 1, 2 Transformer 47C Reverse phase protector LD 71, 72, 73, 74 Fault indicator lamp Th D1, D2, S, E. O Temperature sensor CD 1, 2 Current detector
Ferrite Core
Noise filter
Fuse
Electric
starter
3 ø
Rectifier
Noise
filter
Reactor
Electrolytic
Capacitor
Power Transistor
Clip
Diode
Inverter Control PC Board
MCC - 1251
Thermostat
Clip Diode
(Inverter)
Notes :
1.The dashed lines indicate wiring on site.
2. and indicate terminal blocks, and numbers within them are terminal numbers.
2345678
2345678
3. indicates a printed circuit board.
DANGER
THE ELECTROLYTIC CAPACITORS IN THIS PANEL ARE CHARGED TO 600 VOLTS D. C.
BEFORE SERVICING, TURN OFF THE POWER SUPPLY AND ALLOW AT LEAST 20 MINUTES FOR THE CAPACITORS TO DISCHARGE TO A SAFE LEVEL OF 5 VOLTS D.C. OR LESS. TEST WITH A D.C. VOLT METER AS SHOWN.
Resistor
NEVER SHORT THE CAPACITOR TERMINALS WITH ANY METAL IMPLEMENT TO DISCHARGE. PERSONAL INJURY OR EQUIPMENT DAMAGE MAY RESULT.
Parts layout
FM3
Inverter
Compressor
Fuse
Surge Absorber
Relay
Surge Absorber
Power supply
Fuse
Noise
filter
Noise
filter
Pressure
sensor
Interface Control PC Board
MCC - 1223
Electrolytic Capacitors
PC boards
Fuse
Power supply
PC board locations
MCC-1223
Power Transistor
Rectifier
3 ø
Noise filter
Connectors
1~6
7~12
15 16
5.3 2-Pipe Multi Controller (RBM-Y1032-PE, RBM-Y1042-PE).
CS
K13
Spark killer
Capacity rank setting
ABCD
7 Segment LED
LD1 LD2
Display selector switch
Tr
F
H
MS
COM
NO NC
INDOOR
UNIT A
Symbol
PMVA, B, C, D
ThA, B, C, D, X
Tr
CS
H
MS
LD1, LD2
Parts layout
INDOOR
UNIT B
INDOOR
UNIT C
Part Name
Pulse modulating valve
Temperature sensor
Transformer
Float switch
Heater
Reset switch
Fault Indicator LED
Control PC Board
Terminal Plate
Trans
INDOOR
UNIT D
Reset switch
OUTDOOR
UNIT
The dashed lines indicate wiring on site.
and indicate terminal blocks, and numbers
within them are terminal numbers.
indicates a printed circuit board.
• The frame indicates the product body.
• RBM-Y1032-PE does not have PMVD, ThD or the
connection block for Indoor unit D .
The capacity rank code setting for unit D is to be set to "0".
17
5.4 3-Pipe Multi Controller (RBM-Y1032F-PE, RBM-Y1042F-PE).
7 Segment LED
Capacity rank setting
B
D C A
Display selector switch
Spark killer
Symbol
PMV A, B, C, D
Th A, B, C, D, X
Tr
CS
H
MS
F
SVD (A), (B), (C), (D)
SVS (A), (B), (C), (D)
SVDD
SVSS
SVH
LD 101, 102, 103, 104
Parts layout
Part Name
Pulse modulating valve
Temperature sensor
Power transformer
Float switch
Heater
Reset switch
Fuse (T1A)
Electrically operated valve for discharge gas side
Electrically operated valve for suction gas side
Electrically operated valve for increasing pressure
Electrically operated valve for decreasing pressure
Electrically operated valve for superheat control
Fault indicator LED
Control PC Board
Terminal Plate
Trans
Reset switch
Indoor unit A
• The dashed lines indicate wiring on site.
and indicate terminal blocks, and numbers within them are
terminal numbers.
indicates a printed circuit board.
• The frame indicates the product body.
Indoor unit B
Indoor unit C
Indoor unit D
Outdoor Unit
RBM-Y1032F-PE does not have PMVD, SVD(D), SVS(D) ThD,or the
connection block for Indoor unit D. The capacity rank code setting for unit D is to be set to "0".
18
6.1 2-Pipe system.

6. REFRIGERANT CYCLE DIAGRAMS

Check
joint
Bypass capillary 1.5 x 600L
Outdoor unit
High pressure
switch
Pressure
sensor
Heat exchanger
Expansion
valve
Packed
valve
Inverter
Dryer
D.O.L.
High pressure
switch
Ø2.0 x 800L Capillary
SV1 (For high pressure release)
receiver
Liquid
Compressor
SV4 (For No. 2 compressor start up)
SV2 (For gas balance and hot gas bypass)
Check
joint
4-Way valve
PMV1 (For cooling bypass)
Service
valve
Accumulator
Strainer
Strainer
Expansion
valve
Multi controller (1)
Strainer
Indoor unit
(Liquid
side)
(Gas side)
Strainer
Multi controller (2)
Indoor unit
19
6.2 3-Pipe system.
THX
20

7. SELF DIAGNOSTIC DISPLAY INFORMATION

7.1 MAR-M102HTM8-PE, 2-Pipe Outdoor Unit.
Malfunction judgement is performed using the self-diagnostic function of the outdoor unit. The combination of the display switch and the 8 LED's (LED 1 ~ LED 8) indicate the diagnostic details.
Fuse 20Ax3
R S T
52C3
U V W 51C3
Electrolytic
Capacitors
Interface control board
MCC-1211
L1 L2 L3 N
Power supply
Power Transistor
1 2 3
M/C (1) M/C (2)
Electrical parts location
MCC-1211
J2
MCC-1252
Inverter control board
MCC-1251
Connectors
1 2 3
LED 1~8
Display switch
Interface control board

7.1.1 Display switch information.

Switch position Malfunction information
0 System Communication 1 Status of Compressors 2 System Status 3 Fault Diagnostics (Outdoor Units) 4 M/C 1 Units A & B Indoor Capacity Codes 5 M/C 1 Units C & D Indoor Capacity Codes 6 M/C 2 Units A & B Indoor Capacity Codes 7 M/C 2 Units C & D Indoor Capacity Codes 8 Fault Diagnostics (Multi Controller) 9 Circuit Test
10 ~ 15 Not used
21
7.1.2 Display switch set to position "0".
LED 1 LED 2 LED 3 LED 4 LED 5 LED 6 LED 7 LED 8
7.1.3 Display switch set to position "1".
O: LED on
X: LED off
LED 5
LED 6
LED 7
LED 8
On: Receiving serial signal from multi controller 1 On: Sending serial signal to multi controller 1 On: Receiving serial signal from multi controller 2 On: Sending serial signal to multi controller 2 On: Receiving serial signal from inverter control board On: Sending serial signal to inverter control board
LED 1
X X X X X
X O O O O O O O O
D.O.L. compressor
Frequency control
LED 2
X
X O O O O X X X X O O O O
LED 3
X O X X O O X X O O X X O O
LED 4
X
O
X
O
X
O
X
O
X
O
X
O
X
O
LED's on: Frequency control due to protection circuit
Inverter frequency
0Hz 30Hz 36Hz 42Hz 46Hz 53Hz 61Hz 69Hz 76Hz 84Hz 92Hz
103Hz
111Hz
122Hz
LED's on : Run / LED's off : Stop
S0 S3 S4 S5 S6 S7 S8
S9 SA SB SC SD SE
SF
7.1.4 Display switch set to position "2".
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
Operating mode
Defrost operation
PMV status
Return signal
Inverter abnormality
D.O.L. Compressor abnormality
LED on: Heating LED off: Cooling
LED on: Defrost
LED on: Opening LED off: Closing
LED on: Return signal not receiving from INV
22
7.1.5 Display switch set to position "3".
LED 1 ThD1 sensor abnormality LED on: Sensor open / short circuit LED 2 ThD2 sensor abnormality LED 3 ThS sensor abnormality LED 4 High pressure abnormality LED on: High pressure abnormal
(detected by pressure sensor) LED 5 Pressure sensor abnormality LED on: Pressure sensor abnormal LED 6 Discharge temperature abnormality LED on: Discharge temperature abnormal
(detected by ThD1or ThD2 sensor) LED 7 Suction temperature abnormality LED on: Suction temperature abnormal
(detected by ThS sensor) LED 8 Low pressure, gas leakage abnormality LED on: Low pressure switch functioning
7.1.6 Display switch set to position "4", "5", "6" or "7"
Sw4
Sw5 Capacity rank of indoor unit connected to Capacity rank of indoor unit connected to
Sw6 Capacity rank of indoor unit connected to Capacity rank of indoor unit connected to
Sw7 Capacity rank of indoor unit connected to Capacity rank of indoor unit connected to
LED 1
Capacity rank of indoor unit connected to Capacity rank of indoor unit connected to M/C (1) - Unit A M/C (1) - Unit B
M/C (1) - Unit C M/C (1) - Unit D
M/C (2) - Unit A M/C (2) - Unit B
M/C (2) - Unit C M/C (2) - Unit D
O: LED on X: LED off
X X X X X
X O O
LED 2
X
X O O O O
X
X
LED 3 LED 4 LED 5 LED 6 LED 7
O O X X O O X O
Indoor unit model capacity rank Code No. X O X O X O X X
10 13 16 20 26
­36 46
LED 8
2 3 4 5 6
8
10
(Indoor unit model example: Model RAV-362UH-PE, Capacity rank = 36)
7.1.7 Display switch set to position "8".
-
LED 1 Th(A) sensor abnormality LED on: sensor open / short circuit. LED 2 Th(B) sensor abnormality LED 3 Th(C) sensor abnormality LED 4 Th(D) sensor abnormality LED 5 Th(X) sensor abnormality LED 6 Over-capacity
Light on when the total capacity of the indoor units exceeds 1.35 times the outdoor unit capacity.
LED 7 M/C (1) fault. LED on : Abnormal
LED 8 M/C (2) fault. LED on : Abnormal
7.1.8 Display switch on set to position "9".
LED 1 M/C (1) Unit A LED 2 Unit B LED 3 Unit C LED 4 Unit D LED 5 M/C (2) Unit A LED 6 Unit B LED 7 Unit C LED 8 Unit D
When a LED is ON it indicates that there is a wiring or piping fault between the multi controller and the relevant indooor unit. (Refer to circuit connection test procedure).
23
7.2 RBM-Y1032-PE / RBM-Y1042-PE, 2-Pipe Multi Controller.
The combination of the display switch and the two 7 segment LED's (LD1, LD2) indicate the diagnostic details.
MCC - 1210
7 Segment LED
Capacity rank switches.
Unit A Unit C Unit B Unit D
Multi controller control board
7.2.1 Display switch information.
Switch position Malfunction information
0 System Communication 1 Fault Codes 2 Level of Demand 3 Oil retrieval, Superheat control, Defrost 4 Operating Mode 5 Restart Timer 6 Circuit Test 7 PMV (A) Position 8 PMV (B) Position 9 PMV (C) Position 10 PMV (D) Position 11 ThA Sensor Data 12 ThB Sensor Data 13 ThC Sensor Data 14 ThD Sensor Data
15 ThX Sensor Data
LD 1
LD 2
Display switch
24
Switch Position
Indication
LD 1
7 Segment LED display.
LD 2
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Serial signal
Fault
Codes
Demand
Oil
retrieval,
superheat
control
Defrost
Operation
mode
Restart
timer
Circuit test
PMV A
PMV B
PMV C
PMV D
ThA
ThB
ThC
ThD
ThX
---
Receiving
from
unit B
Sending
to
unit B
---
Sending
to
unit A
Receiving
from
unit A
Receiving
from
Outdoor
Unit
from
unit D
Sending
to
unit D
Receiving
--- ---
Sending
to
unit C
Receiving
from
unit C
Fault code display (Normal [00]) Refer to fault code section for details.
Instructed demand frequency of Cooling or Heating [00 - 1F] Refer to table below.
---
Oil
retrieval
unit B
Superheat
control
unit B
---
Superheat
control
unit A
Oil
retrieval
unit A
---
Oil
retrieval
unit D
Superheat
control
unit D
Superheat
control
unit C
Oil
retrieval
unit C
Displays [dF] during defrost operation
Multi controller
Heating [H], Cooling [C]
Stop [0]
Outdoor unit
Heating [H], Cooling [C]
Other [0], Defrost [J]
Normal display [00], Restart timer counting [01]
Displays unit being tested [A b C d]
Indicates faulty unit connection [A b C d]
Displays the degree of PMV opening (0 - 240) as a Hexadecimal Code:
[00] : Closed, [F0] : Fully Open
Displays sensor temperature
Refer to the sensor temperature conversion table (7.2.3).
Sending
to
Outdoor
Unit
------ ---
7.2.2 Display switch set to position "2"
Displays the instructed demand frequency of heating or cooling from the multi-controller to the outdoor unit.
Display conversion table
Display code
Frequency conversion
00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F
0 0 0 3.9 6.9 10.0 13.1 16.2 19.3 22.4 25.5 28.6 31.7 34.8 37.9 41.0
value (Hz)
Display code
Frequency conversion value (Hz)
10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F
44.1 47.2 50.3 58.4 56.5 59.6 62.7 65.8 68.9 72.0 75.1 78.2 81.3 84.4 87.5 90.0
25
7.2.3 Display switch set to position "11", "12", "13" and "14".
Multi controller - ThA, B, C, D and X sensor conversion table.
Display
18 -10.0
1C -9.0
20 -8.0
24 -7.0
28 -6.0
2C -5.0
30 -4.0
34 -3.0
38 -2.0
3C -1.0
40 0.0
Display [00] signifies sensor open circuit.
7.2.4 Circuit connection test procedure.
The 2-Pipe system has a feature which enables it to check that the wiring and piping connections
Tempera-
ture (°C)
Display
44 1.0
48 2.0
4C 3.0
50 4.0
54 5.0
58 6.0
5C 7.0
60 8.0
64 9.0
68 10.0
6C 11.0
Tempera-
ture (°C)
Display
70 12.0
74 13.0
78 14.0
7C 15.0
80 16.0
84 17.0
88 18.0
8C 19.0
90 20.0
94 21.0
98 22.0
Tempera-
ture (°C)
Display
9C 23.0
A0 24.0
A4 25.0
A8 26.0
AC 27.0
B0 28.0
B4 29.0
B8 30.0
Tempera-
ture (°C)
are aligned with each other. This is carried out by allowing refrigerant to flow to one Indoor unit at
a time and monitor the Indoor units coil sensor for a corresponding drop in temperature. Each
indoor unit is tested in turn and where two Multi controllers are installed each Multi controller is
tested in turn.
This test would normally be used at the commisioning stage.
Procedure for initialising the circuit test.
1. Turn the power off.
2. Ensure capacity codes are set correctly, capacity switches set to "0" are not tested.
3. Put the Outdoor display switch to 9 and Multi controller(s) display switch to 6.
4. Turn the power back on.
5. Set all the Remote controllers to cool mode and 29ºC.
6. Press the on / off button to start the indoor units.
7. Go to the Outdoor unit and press switch J2 (above 8xLED's) for 3 seconds.
8. The system is now in self-testing mode (all 8 LED's will be flashing rapidly).
9. The system will stop at the end of the test.
In the event of cross wiring / piping the system will indicate which units are faulty. Refer to self
diagnostic information (7.1.8).
26
7.3 MAR-F102HTM8-PE, 3-Pipe Outdoor Unit.
Malfunction judgement is performed using the self-diagnostic function of the outdoor unit. The combination of the display switches (SW1, SW2) and the LED's (LD 71 ~ LD 74) indicate the diagnostic details.
Fuse 20Ax3
R S T
52C3
U V W 51C3
Electrolytic
Capacitors
Interface control board
MCC-1223
L1 L2 L3 N
Power supply
Power Transistor
1 2 3
M/C (1) M/C (2)
Electrical parts location
MCC-1223
MCC-1252
Inverter control board
MCC-1251
Connectors
1 2 3
7 Segment LED
LD71 LD72 LD73 LD74
SW1 SW2
SW4 SW3
Interface control board
Display switches
27
7.3.1 Display switch SW1 set to position "0"
Communication serial signals and the system operating status are displayed by changing display
switch SW2.
Display
Switch
SW2
Position
0
1
2
3
4
Indication
Sending / receiving status of interface control board serial signal
Operating
Operating instruction from M/C (1)
Outdoor unit operating condition
mode
Instruction frequency
Operating mode
7 Segment LED Display
Between M/C (1)
Sending only [S]
Receiving only [J]
Heating [H], Simultaneous cooling/heating [HC], Cooling [C], Stop [ ]
Heating frequency [00-1F]
(Refer to conversion table)
Heating [H], Cooling [0C], Simultaneous heating [Hc] Defrost [J0], Simultaneous cooling [hC]
M/C operation Off: [0] 1 unit: [1] 2 unit: [2]
Between M/C (2)
Not sending or receiving [ ]
Sending and receiving [0]
Frequency release No: [0] Yes: [1]
LD74LD71 LD72 LD73
Between Inverter
Cooling frequency [00-1F]
(Refer to conversion table)
Non-inverter compressor
Abnormal [E]
Normal [0]
5
6
9
10
11
Operating
Operating instruction from M/C (2)
Inverter operation status
Operating instruction to inverter from interface control board
Power supply frequency
mode
Instruction frequency
Heating [H], Simultaneous cooling/heating [HC], Cooling [C], Stop [-]
Heating frequency [00-1F]
(Refer to conversion table)
Normal [C]
Abnormal [E]
Normal [C]
Abnormal [E]
50Hz [5]
60Hz [6]
Operating frequency
[0-F], (Refer to table) Instruction frequency
,
[0-F] (Refer to table)
[0]
Cooling frequency [00-1F]
(Refer to conversion table)
28
Display code conversion table - Instruction frequency from Multi Controller.
Display code
Frequency conversion value (Hz)
Display code
Frequency conversion value (Hz)
Display code conversion table - Operating frequency of Inverter Compressor.
Display code
Frequency conversion value (Hz)
00
0
10
44.1
0
0
01
0
11
47.2
3
30.5
02
0
12
50.3
4
38.1
03
3.9
13
53.4
5
42.0
04
6.9
14
56.5
6
45.8
05
10.0
15
59.6
7
53.4
06
13.0
16
62.7
8
61.0
07
16.2
17
65.8
68.7
9
08
19.3
18
68.9
22.4
72.0
A
76.3
09
19
0A
25.5
1A
75.1
B
83.9
0B
28.6
1B
78.2
91.6
0E
37.9
1E
87.5
0F
41.0
1F
90.0
F
121.6
0C
0D
31.7
34.8
1C
1D
81.3
84.4
C
D
103.0
E
110.6
7.3.2 Display switch SW1 set to position "1"
PMV opening information is displayed.
Display
switch
SW2
2
3
7.3.3 Display switch SW1 set to position "2"
Malfunction information is displayed, refer to fault code section for details.
Display switch SW2
0
Indication
PMV1 opening
PMV2 opening
Indication
Check code display for the Outdoor unit, M/C (1), M/C (2)
LD71
[P]
[P]
[E]
7 Segment LED Display
LD72 LD73
[1]
[2]
7 segment LED display
LD72LD71
Outdoor unit: [r] M/C (1): [1] M/C (2): [2]
LD74
Displays the degree of PMV opening (0 - 240) as a Hexadecimal Code:
[00] : Closed, [F0] : Fully Open
LD73
Refer to fault code section for details.
LD74
29
7.3.4 Display switch SW1 set to position "3"
The indoor unit capacity rank setting is displayed.
Display
Switch
SW2
0
1
2
3
4
5
6
7
8
Indoor unit code No. conversion table.
Code No.
Outdoor unit HP
Capacity rank of indoor unit connected to M/C (1)
Capacity rank of indoor unit connected to M/C (2)
Indication
0
LD71
Unit A
Unit B
Unit C
Unit A
Unit B
Unit C
Unit D
2 3 4 5 6 8 10
7 Segment LED Display
LD72
[9]
[A]
[b]
[C]
Displays the code number of the indoor unit registered to each M/C.
[d]Unit D
Refer to the table below for indoor unit model capacity rank.
[A]
[b]
[C]
[d]
8 HP [8], 10 HP [A]
LD73
[H]
LD74
[P]
Capacity rank
(Indoor unit model example: Model RAV-362UH-PE, Capacity rank = 36)
7.3.5 Display switch SW1 set to position "4"
The sensor data is displayed.
Display
Switch
SW2
0
1
2
3
4
5
No Correction
Indication
Pressure sensor data
ThD1 sensor data
ThD2 sensor data
ThS sensor data
TE sensor data
TO sensor data
10 13 16 20 26 36 46
7 Segment
LED Display
LD71
[P]
[d]
[d]
[S]
[h]
[h]
LD72
[d]
[1]
[2]
[1]
[E]
[0]
LD73
Displays sensors reading.
Refer to the following
conversion tables.
LD74
30
7.3.6 Outdoor unit - Pressure sensor data.
Display
17 0.0
1E 1.0
25 2.0
2D 3.0
34 4.0
3B 5.0
43 6.0
4A 7.0
51 8.0
58 9.0
5C 9.5
60 10.0
63 10.5
These are sample displays. Intermediate displays to those above are possible.
Pressure
(kgf/cm2G)
Display
67 11.0
6B 11.5
6E 12.0
72 12.5
76 13.0
79 13.5
7D 14.0
81 14.5
84 15.0
88 15.5
8B 16.0
8F 16.5
93 17.0
Pressure
(kgf/cm2G)
Display
96 17.5
9A 18.0
9E 18.5
A1 19.0
A5 19.5
A9 20.0
AC 20.5
BD 21.0
B4 21.5
B7 22.0
BB 22.5
BE 23.0
C2 23.5
Pressure
(kgf/cm2G)
Display
C6 24.0
C9 24.5
CD 25.0
D1 25.5
D4 26.0
D8 26.5
DC 27.0
DF 27.5
E3 28.0
E7 28.5
EA 29.0
EE 29.5
F2 30.0
Pressure
(kgf/cm2G)
7.3.7 Outdoor unit - ThD1 and ThD2 sensor data.
Display
Tempera-
ture (°C)
05 -5.0
07 0.0
09 5.0
0C 10.0
0F 15.0
12 20.0
17 25.0
1C 30.0
22 35.0
These are sample displays. Intermediate displays to those above are possible.
Display [00] signifies sensor open circuit.
Display
28 40.0
30 45.0
38 50.0
41 55.0
4A 60.0
54 65.0
5E 70.0
68 75.0
72 80.0
Tempera-
ture (°C)
Display
7C 85.0
87 90.0
90 95.0
9A 100.0
A2 105.0
AB 110.0
B2 115.0
B9 120.0
C0 125.0
Tempera-
ture (°C)
Display
C6 130.0
CB 135.0
D0 140.0
Tempera-
ture (°C)
31
7.3.8 Outdoor unit - ThS, TE, TO sensor data.
Display
Tempera-
ture (°C)
2A -20.0
36 -15.0
42 -10.0
51 -5.0
60 0.0
63 1.0
66 2.0
69 3.0
6C 4.0
6F 5.0
73 6.0
76 7.0
79 8.0
These are sample displays. Intermediate displays to those above are possible.
Display [00] signifies sensor open circuit.
Display
7C 9.0
7F 10.0
82 11.0
85 12.0
88 13.0
8B 14.0
8E 15.0
91 16.0
94 17.0
97 18.0
9A 19.0
9C 20.0
9F 21.0
Tempera-
ture (°C)
Display
A2 22.0
A5 23.0
A7 24.0
AA 25.0
AC 26.0
AF 27.0
B1 28.0
B3 29.0
B6 30.0
B8 31.0
BA 32.0
BC 33.0
BE 34.0
Tempera-
ture (°C)
Display
C0 35.0
C2 36.0
C4 37.0
C6 38.0
C8 39.0
C9 40.0
D1 45.0
D8 50.0
DE 55.0
E3 60.0
E7 65.0
EA 70.0
Tempera-
ture (°C)
7.3.9 Circuit connection test procedure.
The 3-Pipe system has a feature which enables it to check that the wiring and piping connections are aligned with each other. This is carried out by allowing refrigerant to flow to one indoor unit at a time and monitor the Indoor units coil sensor for a corresponding drop in temperature. Each Indoor unit is tested in turn and where two Multi controllers are installed each Multi controller is tested in turn.
This test would normally be used at the commisioning stage.
Procedure for inialising the circuit test:
1. Turn the power off.
2. Ensure capacity codes are set correctly, capacity switches set to "0" are not tested.
3. Set the Outdoor display switches SW1 and SW2 to 9 and Multi controller(s) display switch to 6.
4. Turn the power back on.
5. Set all the Remote controllers to cool mode and 29ºC.
6. Press the on / off button to start the Indoor units. The Outdoor LED's show "1020".
7. Press the Oudoor unit switch SW3 for 3 seconds.
8. The system is now in self-testing mode (LED's will be flashing).
9. The system will stop at the end of the test.
In the event of cross wiring / piping the system will indicate which units are faulty, as shown by the LED's. Refer to the table below.
M/C 1
A
B
1
Units indicated
C
failed the test.
2
D
0
No faults
M/C 2
A
B
Units indicated
failed the test.
C
D
0
No faults
32
7.4 RBM-Y1032F-PE, RBM-Y1042F-PE, 3-Pipe Multi Controller
The combination of the display switch and the four 7 segment LED's (LD101 - LD104) indicate the diagnostic details.
MCC - 1223
7 segment LED
Unit A Unit C
Unit B Unit D
Capacity rank switches
Multi controller control board
Display switch
LD101
Indication
LD102
Switch Position
Serial signal
0
1 Fault codes
--- ---
[E]
--- ---
---
Frequency instructions to
2
the outdoor unit.
Oil retrieval, Superheat
3
control
---
---
Refer to the 2-Pipe Multi controller display conversion table for display switch position "2".
---
Defrost
M/C operating
4
Operation mode
Restart timer
5 6
Circuit test
PMV A7
8 9
10
11 12
13
14
15
PMV B PMV C
PMV D
ThA ThB
ThC ThD
ThX
and Simultaneous Cooling/Heating [HC], Defrost [J-].
*
mode: Heating [H-] Cooling: [C-]
---
---
[c]
[k]
[A]
[P]
[b]
[P] [P]
[c]
[P]
[d] [A]
[h]
[b]
[h]
[c]
[h] [h]
[d]
[h]
[H]
*
7 Segment LED Display
LD103
Receiving
from
unit B
Sending
to
unit B
Sending
---
to
unit A
from
unit A
Receiving
from
outdoor
unit
Receiving
from
unit D
Sending
to
unit D
Receiving
Fault code display (Normal [00] ) Refer to fault code section for details.
Instructed demand frequency of Cooling or Heating [00 - 1F]
Oil
retrieval
unit B
Superheat
control
unit B
---
Superheat
control
unit A
Oil
retrieval
unit A
---
unit D
unit D
Superheat
Oil
control
retrieval
---
Displays [dF] during defrost operation
Outdoor unit operating mode:Heating [H-], Cooling [-C], Simultaneous Heating [Hc],
Simultaneous Cooling [hC], Stop [--], Defrost [J-]
---
Displays unit being tested [ A b C d ]
Normal display [0], Restart timer counting [1]
Indicates faulty unit connection [A b C d]
Displays the degree of PMV opening (0 - 240) as a Hexadecimal Code:
[00] : Closed, [F0] : Fully Open
Displays sensor temperature
Refer to the 2-Pipe Multi controller sensor temperature conversion table (7.2.3).
LD104
---
---
Sending
to
unit C
Superheat
control
unit C
Receiving
from
unit C
Oil
retrieval
unit C
Sending
to
outdoor
unit
---
33
7.5 Inverter control board, 2-Pipe and 3-Pipe Outdoor Units.
The combination of the dip switch SW1 and the four LED's (D1 ~ D4) indicate the inverter compressor speed and diagnostic details.
MCC - 1251
SW1 position
1
ON
OFF
2
ON
ON
Inverter control board
Display information
Inverter compressor demand frequency
Inverter compressor actual frequency
D1D2D3
D4
SW1
2 1
ON
OFF
ON
OFF
OFF
Fault code indication
Fault indication sequence
7.5.1 Inverter compressor speed indication
LED Binary display
X X X X
X X O O
X O X X
X O X O
X O O X
X O O O
O X X X
O X X O
O X O X
O X O O
O O X X
O O X O
Inverter compressor freq.
OFF
3
4
5
6
7
8
9
A
B
C
D
0 Hz
30.5 Hz
38.1 Hz
42.0 Hz
45.8 Hz
53.4 Hz
61.0 Hz
68.7 Hz
76.3 Hz
83.9 Hz
91.6 Hz
103.0 Hz
Cooling operation maximum frequency.
O O O X
O O O O
E
F
110.6 Hz
121.6 Hz
Heating operation maximum frequency.
34
7.5.2 Inverter fault code indication.
LED Display
O O O ¤
¤ O O O
O O O O
O ¤ O O
O O ¤ O
Inverter high pressure or compressor winding temperature
Inverter compressor winding short circuit protection
TE sensor open / short circuit (2-Pipe only)
Inverter compressor overload protection
Inverter circuit / compressor failure
Fault indicated
7.5.3 Inverter fault indication sequence.
LED Display
X X X O
X X O X
X X O O
¤ O ¤ ¤
Fault indicated
First failure
Second failure
Third failure
System locked out
X LED off
O LED on
¤ LED flashing
7.6 Control board communication diagram.
Remote controller fault code
21
14
18
1d
1F
Multi controller
M/C (1)
Inverter
control board
INV
Remote
Controller
Indoor Unit
Multi controller
M/C (2)
Interface
control board
I/F
1 minute1 minuteA few seconds
1 minute
Remote controller fault code display time lapse for system malfunctions.
Serial signal abnormalities: Between the I/F and the INV More than 3 minutes.
Between the M/C and the I/F More than 2 minutes.
Between the indoor unit and the M/C More than 1 minute.
Between the remote controller and indoor unit A few seconds.
INV abnormality: More than 3 minutes.
I/F abnormality: More than 2 minutes.
M/C and Indoor unit abnormality: More than 1 minute
35

8. FAULT CODE DISPLAY INFORMATION

The remote controller, multi controller and outdoor unit have the facility to display fault codes which are used to determine any malfunction of the system.
• The remote controller is provided with a "check" button and a malfunction check display.
• The multi controllers and outdoor units are provided with display switches and LED displays.
Initially malfunctions can be identified from the remote controller check display.
Details of the multi controller and outdoor unit malfunctions can be determined from their control boards. (Multi controller malfunctions are also displayed on the outdoor unit interface control board).
8.1 Fault code identification.
When a malfunction has been identified, do not reset the system. Press the "CHECK" button on the remote controller and observe the malfunction display.
The location and cause of the malfunction can be determined from the fault code.
Flashing "PREHEAT DEFROST"
• The total capacity rank settings of indoor units connected exceeds the allowable level, or an indoor capacity rank is set at "0" (Multi controller).
• For the 2-Pipe system heating operation has priority over cooling. In the event of an indoor unit requesting cooling operation when another is in heating mode, the
"PREHEAT DEFROST" will flash.
"MALFUNCTION CHECK"
Flashes when phases are rotated.
Check button
• Pressing for 1 second will display the number of compressor actuations and fault codes.
• Pressing for 5 seconds will reset the indoor unit microprocessor.
• Pressing for 10 seconds will clear only the fault codes.
Reset button
• Pressing the reset button with a pin will clear the memory.
36
8.2 Details of the malfunction check display
The following display sequence occurs when the check button is pressed for 1 second.
(Note: Up to 16 indoor units can be connected to one remote controller using group control).
1. The number of compressor "ON" actuations for No.1 outdoor unit is displayed for 2 seconds,
followed by:
2. Fault codes. 2 fault codes for each of the 16 indoor units can be displayed at 2 second intervals.
Example:
Display for the number of compressor "ON" actuations:
MALFUNCTION CHECK
Display for fault codes:
The display is in Hexadecimal Code.
In this case [00 A4] represents 164 compressor "ON" actuations.
MALFUNCTION CHECK MALFUNCTION CHECK
Fault code
Indoor unit number
MALFUNCTION CHECK
MALFUNCTION CHECK
The 1st fault detected
The 2nd fault detected
In this case indoor unit No.1 has [0C]
fault code and indoor unit No.15 has [0d] fault code
followed by [04] fault code.
In this case indoor unit No.1 has
[0C] fault code.
i.e. TA sensor abnormality.
MALFUNCTION CHECK
37
8.3 2-Pipe system fault code summary.
Fault codes can be identified from either the Remote controller, Multi controller or Outdoor unit as shown in the diagram below.
Remote controller fault code Multi controller display switch position 1
No communication INV to I/F
No communication M/C to O/D
04
No communication I/D to M/C
Drain pump fault - I/D unit
0b
TA sensor fault
0C
TC sensor fault
0d
Reverse TC temperature change
08
No TC temperature change
09
No communication I/D to R/C
99
Refer to M/C
15
"Preheat Defrost" flashing
1C
Refer to O/D
Refer to O/D
14
1d
Refer to O/D
1F
Refer to O/D
18
Refer to O/D
Refer to O/D
Ü
Ü
Ü
Ü
ÜÜ
Ü
Ü
Ü
Ü Ü
No communication I/F to INV
04
No communication M/C to O/D
M/C control board fault
8A
No communication initially M/C to O/D
88
ThA sensor fault
80
ThB sensor fault
81
ThC sensor fault
82
ThD sensor fault
83
ThX sensor fault
84
M/C drain pump fault
0b
I/D capacity rank codes too high
89
I/D capacity code set to "0"
Refer to O/D
1C
Refer to O/D
14
Refer to O/D
1d
Refer to O/D
1F
18
Refer to O/D
21
Refer to O/D
Outdoor Unit
Ü
No communication I/F to INV
Refer to inverter control board diagnostics
Display switch set to position "8" (LED on)
Ü
LED 1
Ü
LED 2
Ü
LED 3
Ü
LED 4
Ü
LED 5
Ü
LED 6
LED 7
LED 8
Display switch set to position "3" (LED on)
LED 1
Ü
LED 2
LED 3
LED 4
LED 5
LED 6
LED 7
LED 8
Ü
Refer to the section on the inverter control
Ü
board diagnostics
Ü
ThA sensor fault
ThB sensor fault
ThC sensor fault
ThD sensor fault
ThX sensor fault
Over-capacity
M/C 1 fault
M/C 2 fault
ThD1 sensor fault
ThD2 sensor fault
ThS sensor fault
High pressure fault
Pressure sensor fault
Discharge temperature > 130ºC
Suction temperature > 40ºC
Low pressure < 0.25kgf/cm˝G
21
Phase rotation incorrect
"MALFUNCTION CHECK" flashing on R/C.
38

8.4 3-Pipe system fault code summary.

Fault codes can be identified from either the Remote controller, Multi controller or Outdoor unit as shown in the diagram below.
Remote controller fault code Multi controller display switch position 1
No communication INV to I/F
04
No communication M/C to O/D
No communication I/D to M/C
0b
Drain pump fault - I/D unit
0C
TA sensor fault
0d
TC sensor fault
08
Reverse TC temperature change
09
No TC temperature change
99
No communication I/D to R/C
15
Refer to M/C
"Preheat Defrost" flashing
Refer to O/D
1C
Refer to O/D
14
Refer to O/D
1d
Refer to O/D
1F
Refer to O/D
Ü
Ü
Ü
Ü
ÜÜ
Ü
Ü
Ü
No communication I/F to INV
04
No communication M/C to O/D
M/C control board fault
8A
No communication initially M/C to O/D
88
ThA sensor fault
80
ThB sensor fault
81
ThC sensor fault
82
ThD sensor fault
83
ThX sensor fault
84
M/C drain pump fault
0b
I/D total capacity codes too high
89
I/D capacity code set to "0"
1C
Refer to O/D
14
Refer to O/D
Refer to O/D
1d
Refer to O/D
1F
Refer to O/D
21
Outdoor Unit
No communication I/F to INV
Ü
Refer to inverter control board diagnostics
Interface control board.
SW1 set to "2", SW2 set to "0".
[E] [1] [fault code] Refers to M/C 1 [E] [2] [fault code] Refers to M/C 2
Ü
80
ThA sensor fault
Ü
Ü
Ü
Ü
Ü
Ü
Ü
Ü
Refer to the section on the inverter control
Ü
board diagnostics
Ü
ThB sensor fault
81
82
ThC sensor fault
83
ThD sensor fault
84
ThX sensor fault
0b
M/C drain pump fault
Over-capacity
89
[E] [r] [fault code] Refers to O/D
ThD1 sensor fault
AO
ThD2 sensor fault
A1
ThS sensor fault
A2
ThO sensor fault
A4
ThE sensor fault
A5
Discharge temperature > 130ºC
A6
Suction temperature > 40ºC
A7
Pressure sensor fault
AA
D.O.L. compressor fault
Ad
Low pressure < 0.25kgf/cm˝G
AE
Phase rotation incorrect
21
"MALFUNCTION CHECK" flashing on R/C.
39

8.5 Fault codes displayed at the Remote controller.

Diagnostic Funtions
Fault
Code
Sympton
Status of Air
Conditioner
Notes
SERIAL SIGNAL FAULT
Inter-unit communication.
FLOAT SWITCH OPERATION
Indoor unit or Multi controller.
RETURN AIR TEMPERATURE SENSOR (TA)
INDOOR HEAT EXCHANGER SENSOR (TC)
Outdoor unit stops.
Indoor unit fan continues.
Operation stops for Multi controller fault.
Indoor unit fan continues for Indoor unit fault.
Operation
Continues.
Indoor unit fan stops. (PREHEAT DEFROST is displayed on R/C)
1. Wiring fault between I/D and M/C, or M/C and O/D Interface control board, or O/D Interface control board and O/D Inverter control board.
2. This fault code is also displayed when the Inverter heat sink TRS thermal switch operates.
1. For an I/D fault, when other I/D units are operating, the O/D unit continues, the relevant M/C PMV closes and the faulty I/D unit fan operation continues.
2. Float switch open circuit.
3. Drain pipe blocked.
4. Drain pump fault.
1. Sensor open / short circuit.
1. O/D unit stops when the faulty Indoor unit is the only unit operating.
2. Sensor open / short circuit.
MULTI CONTROLLER FAULT
OUTDOOR UNIT FAULT
INVERTER FAULT
Operation
stops
Operation
stops
Operation
stops
1. Refer to Multi controller diagnostics and fault codes.
1. Refer to Outdoor unit diagnostics and fault codes.
1. Inverter compressor fault (short circuit).
2. Check the power supply, wiring, fuses, giant transistor, base drive board, smoothing capacitor, rectifier diode and compressor.
40
Fault
Code
Diagnostic Funtions
Sympton
Status of Air
Notes
Conditioner
INVERTER COMPRESSOR FAULT
INVERTER MALFUNCTION
OUTDOOR HEAT EXCHANGER SENSOR (TE)
2-Pipe Outdoor unit ONLY.
HIGH PRESSURE FAULT
Operation
stops
Operation
stops
Operation
stops
Operation
stops
1. Inverter compressor fault (overload).
2. Check the power supply, wiring and compressor.
1. Fault in the current detection circuit of the Inverter control board.
2. Check the power circuit, wiring, control boards and compressor.
1. Sensor open / short circuit.
1. High pressure switch or Inner over-load relay malfunction.
2. Operation of the High pressure switch or Inner over­load relay, or detected by the Pressure sensor.
REMOTE CONTROLLER COMMUNICATION
Indoor unit
stops
3. Possible causes - gas leak, refrigerant under charge or over-load operating conditions.
4. Phase rotation detected at D.O.L compressor start up.
1. Wiring fault between the Indoor unit and the Remote controller.
41

8.6 Fault codes displayed at the Multi controller. Display switch set to position "1".

Fault code
80 81 82 83 84 88
89
8A

8.7 Fault codes displayed at the Outdoor unit. 2-Pipe ; Display switch set to position "3". 3-Pipe ; Display switch SW1 set to position "2", SW2 set to position "0".

Fault code
2-Pipe
ThA sensor fault ThB sensor fault ThC sensor fault ThD sensor fault ThX sensor fault Communication between M/C and O/D
Total I/D capacity codes too high
Multi controller control board malfunction.
3-Pipe
Fault
Sensor open / short circuit.
No initial communication between M/C and O/D Check the wiring and control boards. Fault code is displayed when total I/D capacity exceeds 1.35 times the O/D unit capacity.
Fault Note
Note
LED 1 LED 2 LED 3
LED 6
LED 7
LED 5
LED 8
ErA0 ErA1 ErA2 ErA4 ErA5 ErA6
ErA7
ErAA
ErAE
ThD1 sensor fault ThD2 sensor fault ThS sensor fault ThO sensor fault ThE sensor fault Discharge temperature fault
Suction temperature fault
Pressure sensor fault
Low pressure fault
Sensor open / short circuit.
Detected by ThD1 and ThD2 >130ºC. Possible cause - gas leak, refrigerant under
charge, over-load operating condition, or valve blockage / malfunction.
Detected by ThS > 40ºC. Possible cause - gas leak, refrigerant under
charge, over-load operating condition.
Open / short circuit, or pressure sensor capillary tube block.
Possible cause - gas leak, refrigerant under charge, over-load operating condition, or valve blockage / malfunction.
LED 4
ErAd
D.O.L. compressor fault
Detected by low pressure switch. < 0.25kgf/cm˝G
High pressure switch or over-load relay malfunction.
42
9. CONTROL FEATURES
NO. CONTROL
1
2
Defrost
(Heating mode)
Oil Retrieval
(Cooling mode)
DESCRIPTION
• During heating operation, defrost is controlled by the Outdoor unit heat exchanger temperature sensor (TE).
• When the cumulative operating time with TE in zone [A] has amounted to 25 minutes, defrost operation starts. Subsequent defrosts occur after a cumulative time of 55 minutes. When heating operation resumes after defrost, the timer is reset.
• The maximum defrost period after TE returns to zone [B] is 1 minute.
• Heating operation resumes immediately after TE returns to zone [C].
• During cooling operation, oil retrieval is performed if one or more Indoor units are OFF.
• If this condition is satisfied, when cooling operation commences, oil retrieval takes place for 1 minute. If cooling operation continues, oil retrieval is repeated for 1 minute every 60 minutes.
During oil retrieval the following occurs:
a. All Multi controller PMV's are opened. The degree of opening is dependant on the capacity of the Indoor unit . b. If the D.O.L. compressor is OFF the inverter compressor speed increases to SD.
• When cooling operation ends the timer is reset.
Temp.
1 min.
Oil
retrieval
(ºC)
60 min.
DIAGRAM
A
Cooling mode
1 min.
Oil
retrieval
< 60 min.
Compressor
off
Timer
reset
Superheat control
3
(Cooling mode)
• Superheat is controlled by the Multi controller for cooling operation. The level of superheat is determined by the difference between the evaporator outlet temperature for each Indoor unit (ThA, B, C, D) and the saturation temperature (ThX).
• If the superheat of an Indoor unit enters zone [Y], the relevant M/C PMV opens further to compensate for this increase. The degree of additional opening is dependant on the capacity of the Indoor unit.
• When zone [Z] is reached the PMV opening is held at the level set in zone [Y].
• When the level of superheat returns to zone [X] the control is cancelled.
Superheat
(ºC)
13
Y
Z
9
X
43
NO.
CONTROL
DESCRIPTION
Simultaneous
4
Cooling / Heating
operation
3-Pipe ONLY
a. Changeover between cooling and heating operations for each indoor unit.
The solenoid valves inside the Multi controller are energised when operation commands are sent from the Indoor units.
• SVS valve (suction side) opens for a cooling command.
• SVD valve (discharge side) opens for a heating command.
b. Determination of the Outdoor unit operation mode and frequency of the
compressor. These are determined by the difference between the total requested cooling
command frequencies and the total requested heating command frequencies of all Indoor units.
c. Outdoor unit refrigerant control during cooling dominant mode.
Refrigerant flow is controlled by PMV2. The degree of opening is controlled by the difference of all requested cooling and heating command frequencies and the compressor operation frequency.
This flow control is required to divide cooling exhaust heat appropriately between Indoor units in heating mode and the Outdoor unit heat exchanger.
High pressure control is performed to ensure that the capacity of the Indoor units in heating is maintained. This is controlled by the Outdoor unit fan control and the changeover from the main heat exchanger to the sub heat exchanger.
d. Outdoor unit refrigerant control during heating dominant mode.
Superheat control is performed by the Outdoor unit expansion valve.
Evaporating temperature control is performed by the Outdoor unit fan control to ensure that the capacity of the Indoor units in cooling mode is maintained.
Changeover from expansion valve to capillary control is performed when there is a minimal difference between the cooling and heating demands and the heat absorbtion of the Outdoor unit heat exchanger is low.
44
10. VALVE & SENSOR FUNCTION AND OPERATION
10.1 Multi controller - Valve functions, 2-Pipe and 3-Pipe.
Symbol
PMV (A, B, C, D) Flow rate control valve
Multi controller - Valve functions, 3-Pipe ONLY.
SVS (A, B, C, D)
SVSS
SVDD
SVH Superheat solenoid valve
Name of Valve
Suction gas valve
Discharge gas valveSVD (A, B, C, D)
Pressure reducing solenoid valve
Pressure increasing solenoid valve
Description of Function
This opens to the extent corresponding to the capacity and performance required of each Indoor unit.
Opens when commands from the Indoor units requires cooling operation.
Opens when commands from the Indoor units require heating operation.
Opens when the number of units in heating operation is reduced (heating to shutdown or cooling).
Opens when defrost operation starts.
Opens during oil retrieval control in cooling operation.
Opens when the number of units in heating operation is increased (shutdown or cooling to heating).
Opens while control is performed to prevent liquid in discharge pipe from being blocked.
Opens when unit in cooling operation is present.
10.2 Multi controller - Valve operation.
Outdoor
Operation Mode
Shutdown Shutdown, fan
During operation
Indoor Operation Mode
Shutdown, fan Cooling Cooling thermo-control OFF Heating Heating thermo-control OFF
SVD
(3-Pipe ONLY)
OFF OFF OFF OFF
ON ON
SVS
(3-Pipe ONLY)
OFF
ON ON
ON OFF OFF
PMV
Fully closed Fully closed
Rated opening
Fully closed
Rated opening
Fully closed
45
10.3 Outdoor unit - Valve functions, 2-Pipe and 3-Pipe.
Symbol
20SF
SV1
SV2
SV4
Name of Valve
4-way reversing valve Cooling operation
4-way reversing valve Heating operation
High-pressure release solenoid valve
Hot gas bypass solenoid valve
Solenoid valve for D.O.L. compressor startup
Description of Function
OFF: Normal operation. ON: Low load condition when sub heat exchanger
is required. Used in combination with SV15 (3-Pipe ONLY).
ON: Normal operation. OFF: Defrost operation.
Heating operation. Energised when TE > 11ºC
Opens when Pd < 13kgf/cm˝G (cooling) (For cooling dominant mode and sub heat exchanger operation Pd < 17kgf/cm˝G - 3-Pipe ONLY).
Opens when Outdoor ThO < 0ºC (3-Pipe ONLY). Opens for gas balance when compressor stops
(2-Pipe ONLY).
Opens when the D.O.L compressor starts for unloading.
PMV1
Outdoor unit - Valve functions, 3-Pipe ONLY.
SV5
SV13 Cooling solenoid valve
SV14
SV16
SV15
PMV2
Cooling bypass flow control valve
Gas balance
Solenoid valve for expansion valve
Solenoid valve for capillary
Sub heat exchanger solenoid valve
Outdoor flow control valve
Opens when ThD1 or ThD2 > 110ºC. Opens when ThS > 20ºC
Opens when compressor stops.
Opens for cooling-only operations.
SV14 opens for heating operation.
SV16 opens for low load conditions during heating dominant operation.
Opens for sub heat exchanger requirement.
Opens during cooling dominant operation. Degree of opening depending on cooling / heating
demands.
46
10.4 Outdoor unit - Valve operation. For the 2-Pipe system only cooling operation, heating operation and valve 20SF are applicable.
Outdoor Operation Mode
Cooling operation
Heating operation
Simultaneous
Outdoor main heat exchanger
Sub heat exchanger
Outdoor main heat exchanger
20SF SV15 SV13 SV14 SV16
OFF OFF ON OFF OFF
ON ON ON OFF OFF
ON OFF OFF ON OFF
OFF OFF OFF OFF OFF
cooling-dominant operation
Simultaneous
Sub heat exchanger
Expansion valve
ON ON OFF OFF OFF
ON OFF OFF ON OFF heating-dominant operation
Capillary
ON OFF OFF OFF ON
10.5 Manual operation of valves.
Note: 1. Ensure that the system is OFF before valves are manually operated.
2. Valves will re-assume their required position unless electrically isolated.
PMV2
Opening degree control
Opening degree control
a. Multi controller
Display switch
position
0 1 2 3
Valve
PMV A PMV B PMV C PMV D
b. Outdoor unit - (3-Pipe ONLY)
SW1
SW2
Short Point
0
TP1
1
N/A
0
TP2
1
2
0
TP3
Short point
TP 1
Selected valve is fully opened for 2 minutes.
Operation Function
Valves will automatically assume
their required position after two
minutes.
Push SW04
Press SW03
TP 2
Selected valve is fully closed for 2 minutes.
PMV 1 fully open for 2 minutes.
PMV 2 fully open for 2 minutes. PMV 1 fully closed for 2 minutes. PMV 2 fully closed for 2 minutes.
Solenoid valves manually energised
in sequence when pressed
Solenoid valves
automatically energised in
sequence (1 second intervals)
47
10.6 Multi controller sensor operation.
According to a difference between the evaporator outlet temperature and (ThA, B, C, D) saturation temperature (ThX):
Temperature sensor
10.7 Outdoor unit - Sensor and switch operation.
a. Performs Superheat control.
(cooling operation)
b. Determines the degree of opening of PMV 2.
(cooling dominant operation - 3-Pipe ONLY)
Discharge pressure sensor
Suction temperature sensor (ThS)
Discharge temperature sensor (ThD1, ThD2)
Outdoor unit heat exchanger sensor (TE)
Heating operation
Outdoor temperature sensor (ThO)
3-Pipe ONLY
Determines the frequency of the inverter compressor and the ON/OFF status of D.O.L compressor.
Controls the Outdoor unit fan operation. (cooling operation)
Controls the hot gas bypass SV2.
Controls the changeover from Outdoor unit main heat exchanger to sub heat exchanger.
Controls the degree of opening of PMV 1. Stops operation when ThS > 40°C for 10 minutes.
Controls the degree of opening of PMV 1. Stops operation when the discharge temperature > 130°C.
Controls the defrost operation. Controls the Outdoor unit fan operation.
Controls the high pressure release valve SV1.
Controls the hot gas bypass SV2.
Controls the Outdoor unit fan operation. Prevents heating operation when ThO > 25°C.
High pressure switch
Low pressure switch
Stops operation when Pd > 30kgf/cm˝G.
Stops operation when suction pressure < 0.25kgf/cm˝G:-
• After 30 seconds for cooling operation.
• After 10 minutes for heating operation.
The low pressure switch is ignored during defrost operation.
48
11. PRESSURE TEST, EVACUATION AND DEHYDRATION
When Multi controllers are delivered from the factory the PMV's are in the fully open position. After power is supplied to the system the PMV's assume their required operating position, including closed. Before performing the pressure test or evacuation ensure that all Multi controller PMV's are in the fully open position as shown in the "Manual operation of valves" (10.5).
11.1 Pressure test.
• Supply oxygen free nitrogen (OFN) gas at a pressure of 30kgf/cm˝G to the charge port on the suction gas side service valve.
11.2 Evacuation and Dehydration.
• When removing air and dehydrating refrigerant pipe work use an approved type of vacuum pump, do NOT use refrigerant to purge the air.
2-Pipe evacuation positions: Liquid pipe and Gas pipe charge ports. 3-Pipe evacuation positions: Liquid pipe and Discharge gas pipe charge ports. (Refer to diagrams below).
• Ensure to create a vacuum of -76cmHg at both the Liquid and Gas sides.
2-Pipe
3-Pipe
Charge ports
Charge port
Service valve
Liquid pipe
Gas pipe
Packed valves
Liquid pipe
Discharge gas pipe
Service valve
Suction gas pipe
49
12. ADDITIONAL REFRIGERANT
• The Super multi outdoor units contain sufficient refrigerant to operate an installation having 5 metres of pipework (when delivered).
• Refer to the diagram below when calculating the amount of refrigerant required, use only HCFC - 22.
• The total refrigerant charge must be calculated by the weight, and within a tolerance of ± 50g.
• Prolonged operation with either an overcharge or deficiency in refrigerant will lead to loss of performance, increased running costs and will cause damage to the machine. Warranty will be void.
• The piping length is the actual one way length of the pipe at the liquid side of all branch circuits.
• The initial charge is:
Model
MAR-M102HTM8-PE
MAR-F102HTM8-PE
Refrigerant charge
18.6 kg
21.6 kg
Indoor unit branch pipes
RAV - 10* RAV - 13* RAV - 16* RAV - 20* RAV - 26* RAV - 36* RAV - 46*
0.030 kg/m
0.030 kg/m
0.030 kg/m
0.030 kg/m
0.045 kg/m
0.045 kg/m
0.045 kg/m
Single Multi controller
Main pipe run (minus 3m.) x 0.190 kg/m = Branch pipe A (minus 2m.) x See above table = Branch pipe B (minus 2m.) x See above table = Branch pipe C (minus 2m.) x See above table = Branch pipe D (minus 2m.) x See above table =
Total additional gas charge =
Two Multi controllers
Main pipe run (minus 2m) x 0.190 kg/m = Total sub pipe (minus 2m) x 0.125 kg/m =
M/C 1 Branch pipe A (minus 2m) x See above table =
Branch pipe B (minus 2m) x See above table = Branch pipe C (minus 2m) x See above table = Branch pipe D (minus 2m) x See above table =
M/C 2 Branch pipe A (minus 2m) x See above table =
Branch pipe B (minus 2m) x See above table = Branch pipe C (minus 2m) x See above table = Branch pipe D (minus 2m) x See above table =
Total additional gas charge =
50
Example : RAV-462CH-PE RAV-46*
kg
kg
13. EXPLODED VIEWS AND SERVICE PARTS LIST
13.1 Outdoor Units (MAR-M102HTM8-PE, MAR-F102HTM8-PE)
51
13.2 2-Pipe refrigeration assembly parts (MAR-M102HTM8-PE)
13.3 3-Pipe refrigeration assembly parts (MAR-F102HTM8-PE)
52
Location
No.
1 43A46001 Solenoid coil, 4-way valve 2 43A46002 Solenoid coil assembly
3 43A46003 Solenoid coil assembly
4 43A46005 Solenoid coil assembly
5 43A46006 Solenoid coil assembly
6 43146252 Check valve 7 43146428 Check valve 8 43146351 Service valve (1 1/8") 9 43146503 Packed valve (5/8") 10 43146504 Packed valve (3/4") 11 43146398 Valve body 12 43046151 2-way valve 13 43146526 Pulse modulating valve
14 43146525 Pulse modulating valve
15 43146497 Expansion valve 16 43A46007 4-way valve 17 43A47024 Capillary assembly 18 43A47025 Capillary assembly 19 43A47026 Capillary assembly 20 43A47027 Capillary assembly 21 43A47028 Capillary assembly 22 43A47029 Capillary assembly bypass 23 43145066 Dryer 24 43146383 Check joint 25 43147321 Check joint
Part
No.
Description
(3 coils: 4-way, SV5, SV13)
(3 coils: SV14, SV15, SV16)
(3 coils: SV1, SV2, SV4) 2-Pipe
(3 coils: SV1, SV2, SV4) 3-Pipe
(EV18RC2)
(EV23RC8)
Location
No.
26 43147529 Strainer 27 43147537 Strainer 28 43195185 Cushion, under, compressor 29 43195186 Cushion, upper, compressor 30 43195198 Spacer 31 43107200 Spring, base 32 43146367 Switch, high pressure (20PS-B) 33 43151229 Switch, high pressure (20PS-G) 34 43151230 Switch, low pressure (20PS-1) 35 43146524 Sensor, pressure 36 43141705 Compressor 37 43157254 Heater, crank case 38 43148121 Accumulator 39 43148120 Liquid tank 40 43048009 Fusible plug 41 43A43007 Condenser, right-lower 42 43A43008 Condenser, right-upper 43 43A43009 Condenser, left-lower 44 43A43010 Condenser, left-upper 45 43A43011 Condenser, sub 46 43120170 Propeller fan 47 43121545 Fan motor 48 43A00004 Fin Guard 49 43A19003 Fan Guard 50 43A00006 Side panel L 51 43A00007 Side panel R 52 43A00008 Front panel L 53 43A00009 Front panel R 54 43A00005 Air out cabi 55 43155136 Reactor 56 43A51001 Isolator
Part
No.
Description
53
13.4 Outdoor unit electrical parts assembly (MAR-M102HTM8-PE, MAR-F102HTM8-PE)
54
Location
No.
101 43131031 G-Transistor, MG50Q6ES11 102 4316V028 Diode, SR130G-160 103 43150214 TRS-Thermostat, TRC
104 43169617 Noise Filter, DC 105 43169619 Diode Clipper Assembly 106 43160438 Terminal 107 43160450 Terminal, 3P (L1,L2) 108 43160447 Terminal, 6P 109 43160448 Terminal, 6P 110 43169613 Fan Motor (3-Pipe) 111 43169624 PC Board, MCC-1252, Gate 112 4316V025 PC Board, Inverter (2-Pipe)
112 43169623 PC Board, Inverter (3-Pipe)
113 43154156 Relay, LY-1F 114 43155135 Noise Filter 115 43158140 Transformer FT70 116 43155134 Capacitor, MF 117 43060492 Terminal Block, 9P 118 43160449 Terminal, 3P (N) 119 43160503 Terminal Block, 3P (L1, L2, L3) 120 43169625 PC Board, MCC-1253, Surge 121 43160451 Holder, Fuse 122 43160452 Fuse 123 43152356 Magnetic Contactor 124 43160453 Fuse 125 43460526 Fuse
Part
No.
Description
TR-100B10SPT3A
MCC-1251 (INV-M-E) With TE sensor connection
MCC-1251 (INV-F-E)
Location
No.
126 43060859 Fuse Block 127 43169618 Noise Filter 128 43169620 Ferrite Core 129 43169616 Noise Filter, AC 130 43154148 Return Lock STR-4AB 131 43150274 Sensor - ThD1 132 43150275 Sensor - ThD2 133 43150271 Sensor - ThS 134 43150273 Sensor - TE (2-Pipe) 135 43150265 Sensor - TE (3-Pipe) 136 43150272 Sensor - ThO (3-Pipe) 137 4316V027 PC Board, MCC-1211,
138 43169628 PC Board, MCC-1223,
139 43152334 Magnetic Contactor 140 43158139 Transformer FT69 141 43169612 Starter 142 43169621 Capacitor,
143 43169614 SEM Resistor 144 43169615 Hole-CT 145 43055392 Surge Absorber 146 43160493 Clamp Filter 147 43155100 Capacitor (3-Pipe)
Part
No.
Description
Interface (2-Pipe)
Interface (3-Pipe)
LNT2G222KSMCTF
*
Note: Part 142: Replace both capacitors at the same time.
*
55
13.5 2-Pipe Multi controller (RBM-Y1032-PE, RBM-Y1042-PE)
Location
No.
1 43019604 Holder, Sensor 2 43A47019 Strainer 3 43046269 Pulse modulating valve 4 43A47018 Capillary tube 0.8 diameter 5 43146283 Check valve 6 43146540 Expansion valve 7 43151231 Float switch 8 43157253 Panel heater
8 43157252 Panel heater
Part
No.
Description
(RBM-Y1032-PE)
(RBM-Y1042-PE)
56
13.6 3-Pipe Multi controller (RBM-Y1032F-PE, RBM-Y1042F-PE)
Location
No.
1 43019604 Holder, Sensor 2 43146443 Solenoid coil 3 43046151 2 way valve 4 43046156 Check valve 5 43046269 Pulse modulating valve 6 43046270 2 way valve 7 43847010 Capillary tube 2.0 diameter 8 43146283 Check valve 9 43146398 Valve body 10 43146506 Solenoid coil 11 43146429 Expansion valve 12 43146505 2 way valve 13 43151231 Float switch 14 43157252 Panel heater
Part
No.
Description
(RBM-Y1042F-PE)
Location
No.
15 43157253 Panel heater
16 43189026 Insulator, liquid A 17 43189027 Insulator, liquid B 18 43189028 Insulator, header A
19 43189029 Insulator, header A
20 43189031 Insulator, header B
21 43189032 Insulator, header B
22 43A47011 Capillary tube 0.8 diameter 23 43A47012 Capillary tube 1.0 diameter
Part
No.
Description
(RBM-Y1032F-PE)
(RBM-Y1042F-PE)
(RBM-Y1032F-PE)
(RBM-Y1042F-PE)
(RBM-Y1032F-PE)
57
13.7 2-Pipe Multi controller electrical parts assembly (RBM-Y1032-PE, RBM-Y1042-PE)
FT69
Outdoor Unit
PJ16
PJ5
PJ4 PJ3
PJ2 PJ1
PJ9
PJ8
PJ7
PJ6
PJ12
THX
THD THC
THB THA
PJ10
PJ14
PJ13
LD2 LD1
7 Segment LED
Capacity rank
switches
Display selector
D C
B A
setting
Indoor Units
Note: Terminal D is present on RBM-Y1042-PE unit only.
Location
No.
Part
No.
Description
101 43158139 Transformer (FT69) 102 4316V026 PC board assembly (MCC-1210) 103 43150162 Sensor (ThA) 104 43150163 Sensor (ThB) 105 43150164 Sensor (ThC) 106 43150165 Sensor (ThD) (RBM-Y1042-PE)
58
Location
No.
Part
No.
Description
107 43150166 Sensor (ThX) 108 43151242 Micro-switch 109 43A60001 Terminal block 4P 111 43A60008 Fuse T1A 112 43A60007 Fuse holder
13.8 3-Pipe Multi controller electrical parts assembly (RBM-Y1032F-PE, RBM-Y1042F-PE)
FT69
PJ14
PJ13
LD4
LD3
7 Segment LED
LD2LD1
switches
Display selector
D
BC
A
setting
Capacity rank
PJ25
PJ24
PJ23
PJ5
PJ4
PJ3 PJ2 PJ1
PJ12
PJ16
THX
THD
THC THB THA
PJ9
PJ8
PJ7
PJ6
PJ10
Outdoor Unit
Indoor Units
Note: Terminal D is present on RBM-Y1042F-PE unit only.
Location
No.
Part
No.
Description
Location
101 43158139 Transformer (FT69) 102 43169627 PC board assembly (MCC-1222) 103 43150162 Sensor (ThA) 104 43150163 Sensor (ThB) 105 43150164 Sensor (ThC) 106 43150165 Sensor (ThD) (RBM-Y1042-PE)
59
No.
Part
No.
Description
107 43150166 Sensor (ThX) 108 43151242 Micro-switch 109 43A60001 Terminal block 4P 110 43060776 Terminal block 2P 111 43A60008 Fuse T1A 112 43A60007 Fuse holder
TOSHIBA (U.K.) LTD. AIR CONDITIONER DIVISION
PORSHAM CLOSE, BELLIVER INDUSTRIAL ESTATE, PLYMOUTH, PL6 7DB, U.K.
Loading...