AIR TO WATER HEAT PUMP SYSTEM
INSTALLATION AND SERVICE MANUAL3
SYSTÈME DE POMPE À CHALEUR AIR-EAU
MANUEL D'INSTALLATION ET DE RÉPARATION14
LUFT-WASSER-WARMERPUMPENSYSTEM
INSTALLATIONS - UND WARTUNGSANLEITUNG26
SYSTÉM TEPELNÉHO ČERPADLA(VZDUCH - VODA)
SERVISNÍ A MONTÁŽNÍ MANUÁL38
SUSTAV S TOPLINSKOM CRPKOM ZRAK-VODA
PRIRUČNIK ZA UGRADNJU I SERVISIRANJE49
LEVEGŐ-VÍZ HŐSZIVATTYÚ RENDSZER
FELSZERELÉSI ÉS SZERVIZELÉSI KÉZIKÖN60
ΣΥΣΤΗΜΑΑΝΤΛΙΑΣ ΘΕΡΜΑΝΣΗΣ ΑΕΡΑ- ΝΕΡΟΥ
ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ ΚΑΙ ΣΥΝΤΗΡΗΣΗΣ72
LUFT/VATTEN-VÄRMEPUMPSSYSTEM
INSTALLATIONS- OCH SERVICEMANUAL84
LUFT-TIL-VANN VARMEPUMPESYSTEM
INSTALLASJONS- OG VEDLIKEHOLDSHÅNDBOK95
EN
FR
DE
CZ
CR
HU
GR
SV
NO
SYSTÉM TEPELNÉHO ČERPADLA VZDUCH-VODA
NÁVOD NA INŠTALÁCIU A OBSLUHU106
SISTEM TOPLOTNE ČRPALKE ZRAK–VODA
PRIROČNIK ZA MONTAŽO IN VZDRŽEVANJE118
SK
SL
AIR TO WATER HEAT PUMP SYSTEMINSTALLATION AND SERVICE MANUAL
AIR TO WATER HEAT PUMP SYSTEM
HOT WATER CYLINDER
INDIRECT HEATING METHOD
CLOSED OUTLET (UNVENTED)
INSTALLATION AND SERVICE MANUAL
IMPORTANT
PLEASE READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE
INSTALLING THE WATER CYLINDER. INCORRECT INSTALLATION MAY
INVALIDATE GUARANTEE. THE WATER CYLINDER MUST BE INSTALLED
BY A QUALIFIED INSTALLER IN ACCORDANCE WITH LOCAL PLUMBING,
BUILDING AND ELECTRICAL REGULATIONS. PLEASE LEAVE THIS MANUAL
WITH THE UNIT FOR FUTURE REFERENCE.
•Water cylinder incorporating electric cylinder heater and thermal controls.
•Safety Group incorporating a Pressure Relief Valve, Check (Non-return) Valve
and Isolating Valve.
•Compression nuts and olives.
•Cylinder heater key spanner.
EN
3
AIR TO WATER HEAT PUMP SYSTEMINSTALLATION AND SERVICE MANUAL
1.0IMPORTANT INSTALLATION POINTS
1.1The unit, for use with the ESTIA air to water heat pump system, is a purpose
designed unvented water cylinder.
1.2The water cylinder MUST be fitted with a Pressure Relief Valve that complies
with your local Plumbing and Building Regulations. FAILURE TO PROVIDE
ADEQUATE PRESSURE RELIEF WILL INVALIDATE ANY GUARANTEE
AND LEAD TO A DANGEROUS INSTALLATION.
1.3Where the inlet pressure exceeds 0.6 MPa (6 bar) a Pressure Reducing Valve
(set at max. 0.5 MPa (5 bar)) should be fitted to the inlet supply to the water
cylinder
cylinder.
1.4A Check (non-return) Valve should be fitted to the inlet supply to the water cylinder.
This MUST NOT be fitted between the Pressure Relief Valve and the water cylinder.
1.5This appliance is not intended for use by persons (including children) with
reduced physical, sensory or mental capabilities, or lack of experience or
knowledge, unless they have been given supervision or instruction concerning
use of the appliance by a person responsible for their safety. Children should be
supervised to ensure that they do not play with the appliance.
. This MUST NOT be fitted between the Pressure Relief Valve and the water
EN
2.0INSTALLATION – GENERAL REQUIREMENTS
2.1National Wiring Regulations may contain restrictions concerning the installation
of these units in certain areas, eg. Bathrooms.
2.2The unit MUST be installed vertically.
2.3The unit must be positioned on a level surface.
2.4Enough space should be left around the unit for pipe connections and for access
to controls and any safety valves fitted. Refer to Diagram 1 and the Dimensions
Table to determine a suitable position for the water cylinder.
2.5NOTE: Ensure the floor can support the full weight of the unit (see TECHNICALSPECIFICATIONS).
2.6DO NOT install where the unit may freeze.
2.7The mains water supply to the property will be supplying both the hot and cold
water requirements simultaneously. It is recommended that the maximum water
demand is assessed and the water supply checked to ensure this demand can
be satisfactorily met.
NOTE: a high mains water pressure will not always guarantee high flow rates.
We suggest the minimum supply requirements should be 0.1 MPa (1.0 bar)
pressure and 20 litres per minute flowrate. However, at these values outlet flow
rates may be poor if several outlets are used simultaneously. The higher the
available pressure and flow rate the better the system performance.
2.8LIMITATIONS:
The water cylinder should not be used in association with any of the following:
•Situations where maintenance is likely to be neglected or safety devices
tampered with.
4
AIR TO WATER HEAT PUMP SYSTEMINSTALLATION AND SERVICE MANUAL
•Water supplies that have either inadequate pressure or where the supply
may be intermittent.
•Situations where it is not possible to safely pipe away any discharge from the
safety valves.
•Areas where the water supply consistently contains a high proportion of
solids or suspended matter unless adequate filtration can be ensured on the
inlet water supply.
Diagram 1
NOMINAL CAPACITY (litres)
A (mm)
B (mm)
C (mm)
D (mm)
SURFACE AREA (sq.m)
HOT WATER OUTPUT AT 60ºC (litres)
MIXED HOT WATER OUTPUT AT 40ºC (litres)
HEAT LOSS (kWh/24h)
HEATING TIME 15ºC TO 60ºC - USING ELECTRIC
CYLINDER HEATER ONLY (mins)
CAPACITY HEATED USING ELECTRIC
CYLINDER HEATER ONLY (litres)
150210300
315315315
354354354
8001184 1474
1090 1474 2040
0.650.790.79
102163254
243 329.5 476
1.451.912.52
123188262
102163254
EN
3.0INSTALLATION – PLUMBING
3.1Refer to section IMPORTANT INSTALLATION POINTS. Plumb in valves in the
sequence shown in Diagram 2. Ensure the valves are installed in the correct
orientation by reference to the direction of flow arrows marked on them.
The water cylinder MUST be fitted with a Pressure Relief Valve that complies
with your local Plumbing and Building Regulations. (Safety Group supplied).
FAILURE TO PROVIDE ADEQUATE PRESSURE RELIEF WILL INVALIDATE
ANY GUARANTEE AND LEAD TO A DANGEROUS INSTALLATION. Any
discharge pipe connected to the Pressure Relief device must be installed in a
continuously downward direction in a frost free environment.
3.2The water connections on the unit accept direct connection of 22mm outside
diameter pipe; nuts and olives are supplied for this purpose. The thread on the
connections is G3/4 to enable the use of G3/4 female connections to be used if
required. DO NOT use zinc plated water pipes. When steel pipes are used the
pipe should be insulated from the stainless steel vessel by using di-electric
couplings.
3.3The sanitary water INLET is marked BLUE,theOUTLET is marked RED.
Several hot outlets can be served, however, individual site demands should be
considered when choosing capacity and the number of outlets to be served.
3.4It is recommended that an isolating valve is fitted on the cold water supply to
the water cylinder.
5
AIR TO WATER HEAT PUMP SYSTEMINSTALLATION AND SERVICE MANUAL
3.5A drain cock must be fitted below the water cylinder in the inlet pipework. It must
be sited between the water cylinder and the Check Valve.
3.6A sanitary circuit expansion vessel may be fitted to the cold water supply as
shown in Diagram 2 to prevent wastage of expanded water. The following sizes
are recommended:
150 litre12 litre vessel
210 litre18 litre vessel
300 litre24 litre vessel
3.7A re-circulation circuit can be installed on the sanitary water circuit. A connection
is provided for the re-circulation circuit return pipe (threaded G3/4 female).
3.8The primary heating circuit MUST be connected via the Hydro Unit. Refer to the
Installation Instructions supplied with the Hydro Unit for full details.
EN
Diagram 2
8
9
1
6
7
4
3
5
1
2
4.0ELECTRICAL REQUIREMENTS
4.1The unit is supplied with a factory fitted cylinder heater complete with thermal
sensor and over-temperature cut-out. The cylinder heater is rated 2.75kW at
230V~.
4.2The cylinder heater is located behind the white terminal cover on the front of the
unit. The cover is secured by 2 screws on each side of the cover and a threaded
domed nut on the front of the cover. ISOLATE THE ELECTRICAL SUPPLYBEFORE REMOVING THE COVER.
1 COLD WATER INLET
2 ISOLATING VALVE
3 SAFETY GROUP NF7 BAR
4 SANITARY WATER
EXPANSION VESSEL
5 DISCHARGE PIPE
6 PRIMARY CIRCUIT RETURN
7 PRIMARY CIRCUIT FLOW
8 HOT WATER OUTLET
9 SANITARY WATER
RE-CIRCULATION
CONNECTION
4.3The cylinder heater MUST be earthed.
4.4All electrical wiring should be carried out by a competent electrician and be in
accordance with the latest national Wiring Regulations. The circuit must be
protected by a suitable fuse and double pole isolating switch with a contact
separation of at least 3mm in both poles.
4.5The cylinder heater should be wired in accordance with Diagram 3 and the Air to
Water Heat Pump Installation Manual. The supply cable must be via the Heat
Pump Controls Housing, direct connection to the mains electrical supply will
invalidate the guarantee and may result in a dangerous installation. The supply
cable must be routed through the right hand cable gland provided and the outer
sheath of the cable firmly secured by tightening the screw on the cable gland.
The recommended cable type is 2.5mm
2
3 core heat resistant sheathed.
4.6The thermal sensor should be connected to the Heat Pump Controls Housing in
accordance with Diagram 3 and the Air to Water Heat Pump Installation Manual.
6
AIR TO WATER HEAT PUMP SYSTEMINSTALLATION AND SERVICE MANUAL
1 TO HYDRO UNIT
2 SENSOR
3 GREEN/YELLOW
4BLUE
5 DOUBLE POLE THERMAL
CUT-OUT
6BROWN
7 230V~ MAINS SUPPLY
FROM HYDRO UNIT.
1.5mm
2
MIN. CABLE SIZE
The cable to the thermal sensor must be routed through the left hand cable gland
provided and the outer sheath of the cable firmly secured by tightening the screw on
2
the cable gland. The sensor cable should be 0.75mm
2 core + shield (ground) with
a maximum current rating of 100mA. The cable should not be longer than 5 metres.
4.7Replace the terminal cover before operating.
4.8DO NOT heat the unit until the water cylinder has been completely filled with
water.
4.9Thermal control of the water cylinder is done by the Hydro Unit controls. Refer to
the Air to Water Heat Pump Installation Manual for instructions for setting the hot
water storage temperature.
4.10 The electrical supply from the Air to Water Heat Pump to the cylinder heater
incorporates an over-temperature thermal cut-out that will switch off the cylinder
heater in the event of a thermal control failure. DO NOT bypass the thermal
cut-out in any circumstances.
Diagram 3
5
4
4
3
2
B
A
TBO6 (TTW)
1
5.0COMMISSIONING
WARNING: Water that is left standing in a stainless steel water cylinder for long
periods without draw off will become de-oxygenated and potentially corrode
the vessel material. If the installation is to be left unused following installation
and commissioning the water cylinder should be drained or regularly (once per
week) flushed through with fresh mains water.
When placing the unit into service the procedure for filling the unit and the
system checks detailed below should be repeated.
5.1DO NOT switch on the Air to Water Heat Pump until the unit has been filled with
water and checked for leaks.
5.2Check that all installation, electrical and discharge pipe requirements have been
met.
6
6
2
1
TBO3 (230V)
3
EN
7
5.3Check that all water and electrical connections are correctly made and are tight.
5.4Open a hot tap supplied by the unit, turn on the cold water supply to the unit.
5.5Allow the unit to fill and leave the hot tap running for a short while to purge any
air and flush out the pipework. Close the hot tap.
5.6Open successive hot taps to purge any air from the system.
5.7With all hot taps closed, check the system for water leaks and rectify as necessary.
7
AIR TO WATER HEAT PUMP SYSTEMINSTALLATION AND SERVICE MANUAL
5.8Manually test the operation of the Pressure Relief Valve. Ensure water flows
freely from the valve and through the discharge pipe.
5.9Fill the primary circuit following the “Water Pipe” section in the Hydro Unit
Installation Manual. Vent any trapped air by opening the air bleed point or
automatic air vent.
5.10 Switch on the electrical supply to the Air to Water Heat Pump and ensure the
programmer is set to HOT WATER mode. Check that any motorised valves or
primary pumps are working and allow the unit to heat. The hot water temperature
may be varied using the Hydro Unit remote controller, for details refer to the Air to
Water Heat Pump Owners Manual.
6.0MAINTENANCE –
DESCALING CYLINDER HEATER
6.1Little maintenance is required, however in hard water areas the unit will require
periodic descaling to ensure efficient operation. To descale the unit:
EN
6.2Switch off and disconnect the electrical supply and shut down the heat pump.
Turn off the water supply to the unit.
6.3Open a hot tap served by the unit to relieve any system pressure. Empty the unit
by opening the drain valve in the inlet pipework.
6.4Open the terminal cover. Carefully remove the thermal sensor from its pocket on
the cylinder heater by pulling outwards.
6.5Disconnect the link wires connecting the thermal cut-out to the cylinder heater.
Carefully remove the thermal cut-out sensing bulb from its pocket on the cylinder
heater by pulling outwards. Be careful not to kink the capillary tube.
6.6Remove the element tail insulating shroud by pulling it outwards from the element.
6.7Unscrew cylinder heater backnut. A key spanner is provided with the unit for
easy removal/tightening of the cylinder heater backnut. Remove the cylinder
heater from the unit. NOTE over time the cylinder heater gasket may become
stuck to the mating surface, to break the seal insert a round bladed screwdriver
into one of the pockets on the cylinder heater and gently lever up and down.
6.8Carefully remove any scale from the surface of the element. DO NOT use a
sharp implement as damage to the element surface could be caused.
6.9Ensure sealing surfaces are clean and seals are undamaged. If in doubt fit a
new gasket.
6.10 Replace cylinder heater ensuring the element tails are in the VERTICAL plane (see
Diagram 3). Secure in place by re-fitting cylinder heater backnut and tightening.
It may be helpful to support the cylinder heater using a round bladed screwdriver
inserted into one of the element pockets whilst the backnut is being tightened.
6.11 Replace the element tail insulating shroud by carefully pushing over the element
tails until it sits flush with the face of the element mounting plate.
6.12 Replace the thermal cut-out capillary in the LEFT HAND pocket of the cylinder
heater. Ensure it is fully inserted and that the capillary tube is not kinked.
Ensure the capillary tube is routed such that it does not come into contact with
the element tails.
8
AIR TO WATER HEAT PUMP SYSTEMINSTALLATION AND SERVICE MANUAL
1 TERMINAL BRACKET
2 THERMAL CUT-OUT
3 SENSOR TERMINAL
BLOCK
4 MAINS TERMINAL
BLOCK
5 RESET BUTTON
LOCATED ON THIS FACE
NOTE:
THE COVER AND ELEMENT
ASSEMBLY HAVE BEEN
REMOVED FROM THIS VIEW
FOR CLARITY
6.13 Replace the thermal sensor into the LEFT HAND pocket of the cylinder heater
behind the thermal cut-out. Ensure it is fully inserted, and the securing grommet
is pushed into the open end of the pocket.
6.14 Refit the cylinder heater wiring links by inserting the male terminations into the
female terminals on the element tails in accordance with Diagram 3. Check all
wiring terminations are tight and secure. Replace and secure the terminal cover.
6.15 DO NOT SWITCH ON EITHER THE AIR TO WATER HEAT PUMP OR CYLINDERHEATER UNTIL THE UNIT HAS BEEN RE-FILLED WITH WATER. Re-commission
the unit following the Installation and COMMISSIONING instructions.
Diagram 4
1
3
4
5
2
7.0MAINTENANCE – SAFETY VALVES
7.1The Pressure Relief Valve and any other safety valves fitted should be regularly
checked for correct operation.
7.2Manually operate the valve(s) and ensure that water flows freely from the valve
and through the discharge pipe. NOTE: the water discharged may be very hot.
Ensure the valve re-seats correctly when released.
EN
8.0USER INSTRUCTIONS
8.1The water storage temperature at the Air to Water Heat Pump System Water
Cylinder is set at the control panel of the Hydro Unit. This can be set to give
temperatures in the range of 40ºC to 75ºC, 60ºC is recommended. Refer to the
Hydro Unit Installation Manual for details of how to adjust the storage
temperature should this be necessary.
8.2To avoid any risk of freezing when the cylinder is not in use for long periods
during the winter months, it is recommended that the Air to Water Heat Pump
primary supply and the cylinder heater are switched off and the water cylinder is
drained. NOTE: this will not protect other parts of the system pipework. If this is
done the water cylinder must be fully re-commissioned prior to switching on the
Air to Water Heat Pump and cylinder heater or damage may be caused.
8.3To ensure the water cylinder continues to operate at its optimum performance it
should periodically be maintained in accordance with the instructions given under
the sections headed MAINTENANCE.
9
Loading...
+ 18 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.