for back up heater220-230V ~ 50Hz380-400V 3N~ 50Hz380-400V 3N~ 50Hz
for hot water cylinder heater
(option)
Heating(°C)20-60
Cooling(°C)7-25
220-230V ~ 50Hz
Hot Water Cylinder (option)
Hot water cylinder (option)
Water volume(liter)150210300
Power supply220-230V ~ 50Hz
Max water temperature(°C)75
Electric heater(kW)2.7
Height(mm)1,0901,4742,040
Diameter(mm)550
MaterialStainless steel
HWS-1501CSHM3-E
HWS-1501CSHM3-UK
HWS-2101CSHM3-E
HWS-2101CSHM3-UK
HWS-3001CSHM3-E
HWS-3001CSHM3-UK
2Accessory parts
No.Parts nameQuantity
1Installation Manual (this document)1
2Owner’s Manual 1
Insulator for cooling
3-EN
3
5
Insulator
–3–
Page 5
Hydro Unit
Installation Manual
3Preparations for installation
Parts required to connect this product (Common items)
CategoryPartSpecificationQuantity
Strainer (water filter)1 1/4" 30 to 40 meshes1
Water piping
Electrical system
Options required for each function
Drain cock (for water charge)1
Isolating ball valves
Earth leakage breaker for main power supply30 mA1
Earth leakage breaker for backup heater30 mA1
(Option)
Earth leakage breaker for hot water cylinder
heater
1 1/4"
for service 1 1/4"
30 mA1
2
Purpose
Heating––
Heating &Cooling (all
rooms)
Heating & Cooling
(partly heating only)
Hot water supply
2-zone control––
Interlocking with boiler
In the Hydro UnitPurchased part
Part nameModel namePart namePrescribed specification
––Fan coil(s)
––
Hot water cylinder
150 L
210 L
300 L
Output control board
kit (1)
HWS-1501CSHM3-E
HWS-1501CSHM3-UK
HWS-2101CSHM3-E
HWS-2101CSHM3-UK
HWS-3001CSHM3-E
HWS-3001CSHM3-UK
TBC-PCIN3EBoiler
Radiator(s), Fan coil(s), Under
floor heating
Motorized 2-way valve (for
cooling)
Motorized 3-way valve
Earth leakage breaker
Motorized mixing valve
Circulator pumpOther power supply
Buffer tank
Refer to “Control parts
specifications” on page 20.
Refer to “Control parts
specifications” on page 20.
Refer to “Control parts
specifications” on page 20.
Other power supply.
Signal 12 V input function is
required for boiler.
Optional parts
No.Part nameModel nameApplicationRemarks
Boiler-linked output, Alarm output
1External output board TCB-PCIN3E
2External input boardTCB-PCMO3E
Defrost signal output, compressor operation signal
output
Cooling/heating thermostat input
Emergency stop signal input.
Use specified products for the outdoor unit, Hydro Unit, and hot water cylinder.
Do not use commercially available products.
Use parts that conform to prescribed specifications for parts to be connected to the Hydro Unit.
If unspecified products or parts are used, a malfunction, failure or fire may be caused.
–4–
Up to two boards (according to
applications)
Up to two boards (according to
applications)
4-EN
Page 6
Hydro Unit
Installation Manual
4Precautions for safety
General safety precautions
Ensure that all Local, National and International regulations are satisfied.
• Read the “Precautions for safety” carefully before installation.
• The precautions described below include the important items regarding safety – Observe them without fail.
• After the installation work has been completed, perform a test run to check for any problems. Follow the Owner’s
Manual to explain how to use and maintain the unit to the customer.
• Turn off the main power supply switch (or breaker) before unit maintenance.
• Ask the customer to keep the Installation Manual along with the Owner’s Manual.
Refrigerant precautions
• If a refrigerant leak is suspected contact the dealer who supplied the system, in the case of a recharge of
refrigerant ask service personnel for details of the leak and confirmation of the repairs completed.
The refrigerant used in the system is harmless.
• Generally the refrigerant does not leak, however, if the refrigerant should leak into a room and a heater or stove
burner in the room is lit, toxic gas may be generated.
• Do not install the system in a location subject to a risk of exposure to a combustible gas.
If a combustible gas leaks and stays around the unit a fire may occur.
• Install the refrigerant pipe securely during installation and before operation.
If the compressor is operated with no pipe work connected and valves open the compressor will suck air which
would result in over pressurization of the system which may result in bursting or injury.
Observe the same precautions for refrigerant recovery work (pump back procedure to outdoor unit) and do not
disconnect pipe work until refrigerant is recovered and valves closed.
WARNING
Installation precautions
• Ask an authorized dealer or qualified installation professional to install/maintain the Air to Water Heat Pump System.
Inappropriate installation may result in water leaks, electric shock or fire.
• Electrical work must be performed by a qualified electrician in accordance with the installation manual.
An inappropriate power supply capacity or installation may result in fire.
• When completing any electrical works to the system ensure that all Local, National and International regulations are
satisfied.
Inappropriate grounding may result in electric shock.
• Ensure all electrical cables, used for the ESTIA installation, comply with all Local and National regulations. Check all
electrical terminations are secure and tight.
• Earth wire connections.
• Install an earth leakage breaker without fail.
Incomplete grounding can cause electric shock.
Do not earth wires to gas pipes, water pipes, lightning rods or telephone cable earth wires.
• This unit must be connected to the main power supply using a circuit breaker or switch with a contact separation of
at least 3 mm.
• Be sure to turn off all main power supply switches or the circuit breaker before starting any electrical work.
Ensure all power switches are off, failure to do so can cause electric shock.
Use an exclusive power circuit for the Air to Water Heat Pump system using the rated voltage.
• Ensure correct connection of interconnecting wire between Outdoor Unit and Hydro Unit.
Incorrect connection of the interconnecting cable may result in the damage of electrical parts.
• Ensure refrigeration system remains sealed to external gases and air.
Should air or other gases contaminate the refrigeration circuit, high system pressures could result in burst pipes and
injuries.
• Do not modify or bypass any of safety guards or switches in this system.
• After unpacking the outdoor unit, examine the unit carefully for any possible damage.
• Do not install in any place that might increase the vibration of the unit.
• To avoid personal injury (with sharp edges), be careful when handling parts.
5-EN
–5–
Page 7
Hydro Unit
• Perform installation work properly in accordance with the installation manual.
Inappropriate installation may result in water leaks, electric shock or fire.
• Tighten all flare nuts with a torque wrench in the specified manner.
Excessive tightening of the flare nut may result in cracking of the pipe work or flare nut which may result in a
refrigerant leakage.
• Wear heavy duty gloves during installation work to avoid injury.
• Install the outdoor unit securely in a location where the base can sustain the weight adequately.
• In enclosed areas, if the refrigerant leaks during installation vacate and ventilate immediately.
• After installation is complete ensure and confirm that refrigerant does not leak.
If refrigerant leaks into a room and flows near a fire source noxious gas may be generated.
• Do not block any drain hoses. Hoses may come off and electric shocks may occur.
• Do not hit the manometer, because it is made of glass. It is breakable.
Installation Manual
Notes on system design
• The inlet water temperature to the Hydro Unit must be 60°C or less.
Especially, be careful when there is an external heating source such as a boiler.
When hot water over 60°C returns, it may result in a failure of the unit or water leakage.
• The flow rate of the circulating water must meet the following range.
11 kW 18 L/minute or more
8 kW 13 L/minute or more
If the flow rate becomes less than the minimum, the protective device is activated to stop the operation.
To ensure the minimum flow rate of the water system, install a bypass valve on one water circuit. Please note
this circuit must contain a minimum of 20 liters. If total water amount is not enough, the unit may not function fully
due to protective operation.
• Do not drive water by power other than the pump built in the Hydro Unit.
• The back up heaters, in the hydro unit, are designed to assist the heat pump during periods of low ambient
conditions.
• Ensure the Hydro unit and the connecting water pipes are installed in a location that is not exposed to low
ambient temperatures which could result in the water circuit freezing.
• The system operation is designed around a closed water circuit. Do not use an open circuit design.
• Circulating water must be 20 liters or more.
• Please turn on the main power supply to up to 12 hours before the start of the operation, and don’t turn off the
power all the time during the period of use.
–6–
6-EN
Page 8
Hydro Unit
Installation Manual
5Example of Hydro Unit installation
Example of installation for cooling and heating
When both cooling and heating modes are required a 2-way valve must be installed to isolate the radiator or underfloor heating circuit.
▼ Fig. 5-01
Strainer (40 mesh / 0.4 mm)
Drain Cock for water
Charge and Drain
Indirect Sanitary
Hot Water Cylinder
TTW
Isolating
Ball
Valves
M
Fan Coil Units
(Cooling or Heating)
Diverting 3-Way
Valve for
Sanitary Hot
Water Cylinder
2-Way
M
Valve
Use the 2way valve to
isolate the
heating
circuit when
in cooling
mode.
Example of 2-zone temperature control and hot water supply
system
The following shows an example of the 2-zone temperature control.
A buffer tank and a water pump are required for the 2-zone temperature control.
▼ Fig. 5-02
Hi-Pressure
By-Pass
Valve
Temperature
Regulating
Valve
(Mechanical)
TRV
Temp.
Regulating
Valve
(Mechanical)
Strainer (40 mesh / 0.4 mm)
Drain Cock for water
Charge and Drain
TTW
Isolating
Valves
(Service)
Diverting
3-Way
Valve for
Sanitary
Hot
Water
Cylinder
M
TRV
Zone 1
Fan Coil Unit (Heating
or Cooling)
Motorized 2-Way Valve
is required if fan coil
M
units are in cooling
operation.
Mixing 3-Way
M
Valve for Under
Floor Heating
External Pump for
Under Floor Heating
Indirect Sanitary Hot
Water Cylinder
–8–
TFI
Direct Buffer tank for
Under Floor Heating
Zone 2
Under-floor Heating
(2-Way Valve Control)
8-EN
Page 10
Hydro Unit
6Main components of Hydro Unit
Exploded view and description for Hydro Unit
▼ Fig. 6-01
Installation Manual
1
2
3
4
5
6
7
8
9
10
1 : Expansion vessel
2 : Temperature sensor (for Heat pump outlet -TWO)
3 : Pressure sensor
4 : Heat exchanger
5 : Flow switch (13 L/min (8 kW), 18 L/min (11 kW))
6 : Temperature sensor (for refrigerant -TC)
7 : Temperature sensor (for water inlet -TWI)
8 : Drain nipple
9 : Water inlet connection
10 : Refrigerant liquid connection
11 : Air relief valve
12 : Pressure relief valve (0.3 MPa (3 bar))
13 : Thermal protector (auto)
14 : Temperature sensor (for water outlet THO)
15 : Thermal protector (Single operation)
16 : Water pump
17 : Backup heater (3 kW, 3 kW x 2, 3 kW x 3)
18 : Manometer
19 : Water outlet connection
20 : Refrigerant gas connection
11
12
13
14
15
16
17
18
19
20
9-EN
–9–
Page 11
Hydro Unit
E-box layout
▼ Fig. 6-02
Installation Manual
Main P.C. board
MCC-1511
Trans
former
External output
P.C. board MCC1217 (Option)
External output
P.C. board MCC1217 (Option)
Relay P.C. board
MCC-1431
Fuse
(
F9 F10
Relay
(RY06)
)
MG-SW (RY05)
Relay
(RY03)
Relay
(RY01)
Fuse
MG-SW (RY04)
MG-SW (RY02)
External input
P.C. board MCC1214 (Option)
–10–
TB 07
TB07
10-EN
Page 12
Hydro Unit
Installation Manual
7Hydro Unit
installation
WARNING
• To protect yourself from injury, always use PPE
(Personal Protective Equipment), that is, wear gloves.
• Install the Hydro Unit by at least two persons.
• Install the Hydro Unit in a place strong enough to
withstand the following weights:
Hydro Unit weight with no water 60
(P1104)
Hydro Unit weight with full water 80
(P1104)
CAUTION
• Do not install the unit in a place where water freezes.
• Do not install the Hydro Unit in a place where
combustible gas may leak.
• Do not install the Hydro Unit in a place exposed to rain
or water.
• Do not install the Hydro Unit near equipment which
generates heat.
• Do not install the Hydro Unit to a movable object.
• Do not install the Hydro Unit in a place exposed to
vibration.
• The unit must be installed in accordance with national
wiring regulation.
• The Hydro Unit must not be installed in a high humidity
condition area.
kg (P804) 65kg
kg (P804) 85kg
Positioning
Service space
Secure a service space for the Hydro Unit.
• Do not install the Hydro Unit in a place where heat
stagnates.
▼ Fig. 7-01
200 mm
100 mm
500 mm
350 mm
Mounting
Install M10 bolts at the positions shown below and
secure them with nuts.
▼ Fig. 7-02
380 mm
500 mm
M10
Handling, unpacking, and
checking the Hydro Unit
• The unit should be checked when it is delivered, and
any damage reported immediately to the courier
claims the department.
960 mm
NOTE
If customer worried about vibration of ESTIA, please
insert vibration isolating material between the product
and the wall, when installing the product.
11-EN
–11–
Page 13
Hydro Unit
Installation Manual
The Hydro Unit can be installed directly without using
the fixing angles.
However, the back side of the Hydro Unit can be highly
heated, therefore, the installing surface must be heatresistant.
▼ Fig. 7-03
Remove the M5a screws to
detach the fixing angles.
▼ Fig. 7-04
380
▼ Fig. 7-05
M10
860
M10
Refrigerant piping
WARNING
• THIS SYSTEM ADOPTS HFC REFRIGERANT
(R410A) WHICH DOES NOT DESTROY THE
OZONE LAYER.
• The characteristics of R410A refrigerant are: ease to
absorb water, oxidizing membrane or oil, and its
pressure is approximately 1.6 times higher that of
R22. Accompanied with the new refrigerant the oil has
also been changed. Therefore during installation work
prevention of the invasion of water, dust, former
refrigerant or oil is of a paramount importance.
To prevent the charging of incorrect refrigerants into
the system the service valve connection ports have
also increased in size.
• The use of R410A tools is required for correct
installation of the system.
• The use of the correct pipe sizes and wall thicknesses
of copper pipe work is required for the correct
installation of the system.
CAUTION
• Ensure all refrigerant pipes are protected from the
invasion of dust and water.
• Ensure all pipe work connections are tightened to the
required torque settings detailed in this section.
• Perform an air tight using Oxygen Free Nitrogen
(OFN) only.
• Evacuate the air in the pipe work using a vacuum
pump.
• Check for refrigerant gas leaks at all connections
throughout the pipe work.
Secure the Hydro Unit with
plain washers and nuts.
Install the Hydro Unit so that its tilting angle falls within
the range below.
▼ Fig. 7-06
± 1°
▼ Fig. 7-07
± 1°
NOTE
The Air to Water Heat Pump system uses R410A
refrigerant. It is important that copper pipes used for
refrigerant piping have the following wall thickness:
• 0.8 mm for Ø6.4 mm, Ø9.5 mm and Ø12.7 mm
• 1.0 mm for Ø15.9 mm
–12–
12-EN
Page 14
Hydro Unit
Installation Manual
Refrigeration pipe
The length and height of the refrigeration pipe must be
within the following values.
As long as the Hydro Unit is installed within these
ranges, no additional refrigerant is required.
▼ Fig. 7-08
Outdoor unit
L
H
H: Max. ±30 m (above or below)
L: Max. 30 m
Min. 5 m
Refrigerant pipe sizes
Hydro Unit ModelGas Side (mm)
8 & 11 kW Hydro UnitØ 15.88Ø 9.52
Liquid Side
(mm)
Flaring
• Cut the refrigerant pipes to the correct length using a
pipe cutter. Remove any burrs that may be on the
pipes as these may cause refrigerant leaks or
component failure in the refrigeration cycle.
• Place the correct size flare nuts onto the pipes (use
the flare nuts supplied with the Hydro Unit or use
flare nuts designed specifically for R410A
refrigerant) and then flare the pipes using the correct
flaring tool.
Tightening
• Connect the refrigerant pipes, from the outdoor unit,
to the Hydro Unit as shown below.
▼ Fig. 7-09
Gas line Ø 15.88
Liquid line Ø 9.52
• Align the flare connection on each pipe with the
corresponding outlet connection on the Hydro Unit.
Tighten the flare nuts, using fingers, to secure the
pipes in place.
• Tighten the flare nuts, using a torque wrench, to the
tightening torques shown below:
Outer Ø of Copper Pipe
(mm)
9.533 to 42
15.963 to 77
Tightening Torque (N/m)
• To prevent damage, to the refrigerant pipes, use two
spanners to tighten the flare nut connections to the
required torque.
Water pipe
13-EN
WARNING
• Install water pipes according to the regulations of
respective countries.
• Install water pipes in a freeze-free place.
• Make sure that water pipes have sufficient pressure
resistance.
The setting value of the pressure relief valve is 0.3
MPa. (3 bar)
CAUTION
• Do not use zinc plated water pipes. When steel pipes
are used, insulate both ends of the pipes.
–13–
Page 15
Hydro Unit
Installation Manual
• The water to be used must meet the water quality
standard specified in EN directive 98/83 EC.
Water pipe
Design the water pipe length within the QH
characteristics of the pump (Refer to “Fig. 7-16” and “Fig.
7-17” on page 16).
The height of the pipe must be 7 m or less.
▼ Fig.7-10
H < 7 m
▼ Fig. 7-11
Attention
To avoid water leak,
exchange the seal
tapes to new one.
Attention
Water (used at test
in factory before
shipping) may be
found in the caps.
Hot water outlet
connection 1 1/4"
Water circuit
• Install a strainer with 30 to 40 meshes (locally
procured) at the water inlet of the Hydro Unit.
• Install drain cocks (locally procured) for water charge
and discharge at the lower part of the Hydro Unit.
• Make the piping route a closed circuit. (An open
water circuit may cause a failure.)
Water inlet connection
1 1/4"
▼ Fig. 7-12
Inlet
Isolating Ball Valve
Strainer (30 to 40
meshes)
Drain cock for
water charge
and discharge
–14–
Local arrangement
14-EN
Page 16
Hydro Unit
0
Installation Manual
Piping to hot water cylinder (option)
Water supplied to the hot water cylinder is branched by
a motorized 3-way valve (locally procured).
For the specifications of the motorized 3-way valve,
refer to “Control parts specifications” on page 20.
Connect the hot water cylinder to port A (open when
energized) of the valve.
▼ Fig. 7-13
to hydro unit
room heating or cooling
Open when deenergized
B
to hot water cylinder
AB
A
Open when energized
Piping to 2-zone operation
To perform 2-zone temperature control, circulate water
by another pump (locally procured) through a
motorized mixing valve (locally procured) and a buffer
tank (locally procured).
For the specifications of the motorized mixing valve,
Refer to “Control parts specifications” on page 20.
▼ Fig. 7-14
Motorized mixing valve
(locally procured)
Water pump
(locally procured)
Zone
2
AB
A
B
from hydro
unit
Expression for expansion vessel selection
V:Necessary total tank capacity ( )
:Water expansion coefficient at each hot water
temperature
Vs: Total water amount in the system
P1: System pressure at tank setting position
(MPaabs.)
= water supply pressure = 0.3 (MPaabs.)
(recommended valve)
P2: Maximum pressure used during operation at tank
setting position (MPaabs.)
= safety valve setting pressure = 0.4 (MPaabs.)
* The absolute pressure value (abs.) is obtained by
adding the atmospheric pressure (0.1 MPa (1 bar))
to the gauge pressure.
▼ Tank selection method
Water temperature and expansion coefficient
Hot water
temperature
(°C)
00.0002500.0121
40.0000550.0145
50.0000600.0171
100.0003650.0198
150.0008700.0229
200.0017750.0258
250.0029800.0292
300.0043850.0324
350.0050900.0361
400.0078
450.0100
Expansion
rate
Hot water
temperature
(°C)
Expansion
rate
15-EN
Buffer tank (locally
to hydro unit
procured)
Checking water volume and initial pressure
of expansion vessel
The expansion vessel of the Hydro Unit has a capacity
of 12 liters.
The initial pressure of the expansion vessel is
0.15 MPa (1.5 bar).
The pressure of the safety valve is 0.3 MPa (3 bar).
Verify whether the capacity of the expansion vessel is
sufficient using the following expression. If the volume
is insufficient, add the capacity locally.
–15–
▼ Fig. 7-15
18
16
14
12
10
8
6
4
2
0
050100150
Vs: Total water amount in the system( )
V: Necessary total tank capacity( )
25020030
*In case the maximum hot water temperature is 60ºC
Install an external expansion vessel when the capacity
of the expansion vessel is insufficient.
Charge water until the pressure gauge shows
recommended valve 0.2 MPa (2 bar).
Hydraulic pressure may drop when the trial run begins.
In that case, add water.
Air may enter if the charged hydraulic pressure is low.
Loosen the purge valve cap by two turns to release air.
▼ Fig. 7-18
Loosen 2
turns for
proper
venting
Loosen the air vent screw of the pump, pull out air in
the pump, and tighten again.
Loosen the cap of the pressure relief valve to release
air.
Water may come out of the pressure relief valve.
Release the air completely from the water circuit.
Failure to do so may disable correct operation.
Electrical installation
WARNING
• Ensure electrical circuits are isolated before
commencing the electrical installation.
• The electrical installation must be completed by a
qualified electrician.
• The electrical installation must comply to all Local,
National and International electrical installation
regulations.
• This product must be earthed in accordance with
Local, National and International electrical installation
regulations.
CAUTION
• The Hydro Unit must be connected to a dedicated
power supply for the back up heater circuit.
• The electrical supply must be protected by a suitably
sized over current protection device (fuse, MCB etc)
and an earth leakage protection device.
• The Hydro Unit must be connected to the mains power
supply using a isolating switch which disconnects all
poles and has a contact separation of at least 3 mm.
• The cord clamps, attached to the Hydro Unit, must be
used to secure the electrical cables.
• Wrong connection of electrical cables may result in
electrical component failure or fire.
• Ensure the electrical cables are sized in accordance
with the installation instructions.
17-EN
Water quality
The water used must satisfy EN directive 98/83 EC.
Piping insulation
It is recommended that insulation treatment be applied
to all pipes. To perform optional cooling operation,
apply insulation treatment of 20 t or more to all pipes.
–17–
Page 19
Hydro Unit
Control line
▼ Fig. 7-19
Installation Manual
Pump (local)
Max 12 m
230 V 100 mA
0.75 mm² or more
Booster heater
(local)
Max 12 m
230 V 1 A
0.75 mm² or more
2Way-Valve for
cooling stop
Max 12 m
230 V 1 A
0.75 mm² or more
3Way-Valve for hot
water cylinder
Mixing-Valve
type 2 for 2 zone
control
4
2
3
1
TB04
1
2
3
4
TB05
5
6
7
8
CN208
OPTIONOPTION
9
PJ20
2
1
3
Mixing-Valve type 1
for 2 zone control
N
CW
4
2
3
1
TB06
TB07
1
2
CN209
PJ20
2
1
4
3
Max 12 m
230 V 100 mA
0.75 mm² or more
Max 5 m shielded wire
0.75 mm² or more
CCW
A
B
C
D
Temp sensor for
2 zone control
2nd remote controller
4
Temp sensor in hot
water cylinder
A
B
Max 5 m shielded
wire 0.75 mm² or
more
Max 50 m shielded wire
0.50 mm² or more
Max 12 m non
voltage 0.75 mm² or
more
▼ Fig. 7-20
TB03
TB01
Alert output
(local)
Boiler operation
(local)
Defrost output
(local)
Compressor
operation output
(local)
3WV
1
11 12
2
TB 01
59
3
13
43
41
42
MIXV
TB 04
31 32
HOT WATER CYLINDER
Hot
water
cylinder
44
L
N
TB 03
Input power
220-230 V ~
50 Hz
L3
N
L2L1
L
N
TB 02
Input power
220-230 V ~
50 Hz
TB02
L3
L1 L2
Input power
380-400 V 3N
~ 50 Hz
N
55
53
51
52
WPM
TB 05
TTW
54
2WV
6B6A6D
6C
TF1
TB 06
565758
BH
Don't apply
220-240V
or
breakdown
will occur.
to Outdoor unit
Sensor
connection
Outdoor unit
connection
Hot water cylinder
power supply
–18–
Backup heater
power supply
18-EN
Page 20
Hydro Unit
Installation Manual
Electrical supply/cable specifications
▼ Wiring specifications
Description
Outdoor
unit
power
Hydro
inlet
heater
power
Outdoor-Hydro unitConnection1.5 mm² or more, ,
Hydro -CylinderConnection1.5 mm² or more, TB03
Power
input
Power
input for
backup
heater
Power input for cylinder
heater
Model name
HWS-
P1104HR-E
P804HR-E
P1104XWHM3-E
P1104XWHT6-E
P1104XWHT9-E
P804XWHM3-E
P804XWHT6-E
P804XWHT9-E
POWER
SUPPLY
220-230 V ~
50 Hz
220-230 V ~
50 Hz
220-230V ~
50Hz
380-400V 3N~
50Hz
380-400V 3N~
50Hz
220-230V ~
50Hz
380-400V 3N~
50Hz
380-400V 3N~
50Hz
220-230V ~
50Hz
Maximum
current
22.8 A25 A2.5 mm² or more
22.8 A25 A2.5 mm² or more
13 A16 A1.5 mm² or more,
13 A(13 A x 2P) 16 A1.5 mm² or more
13 A(13 A x 3P) 16 A1.5 mm² or more
13 A16 A1.5 mm² or more
13 A(13 A x 2P) 16 A1.5 mm² or more
13 A(13 A x 3P) 16 A1.5 mm² or more
12 A16 A1.5 mm² or more
Installation
fuse rating
Power wireConnection destination
,
, ,
,
,
, ,
,
,
TB02
TB03
▼ Wiring specifications (control line)
DescriptionLine spec
Maximum
current
Maximum length
3-way valve control2 line or 3 line 100 mA12 m0.75 mm² or more
2-way valve control2 line100 mA12 m0.75 mm² or more, (TB05)
Mixing valve control3 line 100 mA12 m0.75 mm² or more
2-zone thermo sensor 2 line 100 mA5 m0.75 mm² or more, (TB06)
Cylinder thermo sensor
2+GND(shielded
wire)
100 mA5 m0.75 mm² or more, (TB06)
Second remote controller2 line 50 mA50 m0.5 mm² or more, (TB07)
Connection
destination
, ,
(TB05)
, ,
or
, ,
(TB04)
19-EN
–19–
Page 21
Hydro Unit
▼ Control parts specifications
PowerMaximum currentType
Motorized 3-way valve
(for hot water)
Motorized 2-way valve
(for cooling)
Motorized mixing valve
(for 2-zone)
AC 230 V 100 mA
AC 230 V 100 mAspring return type (normally open)
AC 230 V 100 mA
▼ Output line specifications
Installation Manual
Default: 2-wire spring return valve or 3 wire SPST valve
Note: 3 wire SPDT valve can be used by changing DIP switch
13_1.
Default: Drive time = 60sec to 90°
Note: 3 wire SPST or SPDT valves, with drive times between
30 and 240 seconds, can be used. Valve drive time can be
changed using function code 0C
DescriptionOutput
External pump No.1AC230V1 A–12 m
External boost heaterAC230V1 A–12 m
Boiler control
ALARM Output
Compressor operation
output
Defrost Output
Non-voltage
contacts
Non-voltage
contacts
Non-voltage
contacts
Non-voltage
contacts
Maximum
current
0.5 AAC230 V12 mOutput as required when outdoor air
1 ADC24 V12 m
0.5 AAC230 V12 m
1 ADC24 V12 m
0.5 AAC230 V12 m
1 ADC24 V12 m
0.5 AAC230 V12 m
1 ADC24 V12 m
Max
voltage
Maximum
length
Output as required when outdoor air
temperature is -20°C or less
temperature is -10°C or less. The
outdoor air temperature, when the
boiler output is enabled, can be
changed using function code 23.
▼ Input line specifications
DescriptionInputMaximum length
Emergency stop controlNon-voltage12 m
Cooling thermostat inputNon-voltage12 m
Heating thermostat inputNon-voltage12 m
CAUTION
Earthing arrangements
The Hydro Unit and related equipment must be earthed in accordance with your local and national electrical regulations.
It is essential that the equipment is earthed to prevent the electric shock and damage to the equipment.
–20–
20-EN
Page 22
Hydro Unit
▼
Installation Manual
Electrical connection to hydro unit
• Remove the front cover and the electrical box cover
from the Hydro Unit.
• The Hydro Unit power cable must be sized in
accordance with refer to “Electrical supply/cable
specifications”.
• Connect the Hydro Unit power cable to Terminal 02
as shown below.
Fig. 7-21
Backup heater
220-230V ~ type
(3 kW type)
Input power
220-230V
50Hz
Leakage
breaker
30mA
L NL1 L2 L3 N
• Ensure the Hydro Unit power cable is secured using
the cable clamp fitted in the electrical box.
• Ensure the Hydro Unit power cable connection
terminals are tight.
Backup heater
380-400V 3N~
type
(6,9 kW type)
Input power
220-230V 3N~
50Hz
Leakage
breaker
30mA
TB02TB02
Outdoor unit to hydro unit electrical
connection
▼ Fig. 7-22
1
Input
power
220230V~
50Hz
Leakage
breaker
30mA
L
N
Outdoor unitHydro unit
• Ensure electrical circuits are isolated before
commencing work.
• The Outdoor Unit to Hydro Unit interconnecting
cable must be sized in accordance with refer to
“Electrical supply/cable specifications”.
• Connect the Outdoor Unit to Hydro Unit
interconnecting cable as shown in the diagram
above.
• Ensure the Outdoor Unit to Hydro Unit
interconnecting cable is secured using the cable
clamp fitted in the electrical box.
• Ensure the Outdoor Unit to Hydro Unit
interconnecting cable connection terminals are tight.
1
2
2
TB01
3
3
21-EN
–21–
Page 23
Hydro Unit
Installation Manual
Electrical connection for external booster
heater
CAUTION
• The maximum current available from the
booster heater output is 1
the booster heater directly to Terminal Block
05 on the Hydro Unit. A separate contactor,
supplied locally, must be used to supply the
booster heater.
• The booster heater can be installed only for room
heating and cannot be used for hot water supply.
• Install the booster heater downstream of the 3-way
valve on the indoor unit side.
The booster heater is an external heater, supplied
locally, used to assist the Hydro Unit during low
ambient conditions.
• The AC230
be used to energize an external contactor. (Supplied
locally)
• The output from the Hydro Unit is only enabled when
the outdoor air temperature is less than -20°C.
• Ensure the external booster heater is installed and set
up in accordance with all Local, National and
International regulations.
V 1A output from the Hydro Unit must only
• Connect the external booster heater to the Hydro
Unit in accordance with the diagram shown below.
• Connect the coil, of the field supplied contactor, to
terminals 5 & 6 on Terminal Block 05. The contactor
will energize in the event of low ambient conditions.
• A separate dedicated electrical supply must be used
for the external booster heater. This must be
connected through the contacts on the field supplied
contactor.
A. Do not connect
Electrical connection for external additional
pumps
• The Hydro Unit has the facility to connect an
additional circulating pump, if required, into the
heating or cooling system.
• There is an output available from the Hydro Unit.
AC230 V 1 A (maximum) is available from each
output. The output for each additional pump is
synchronized with the operation of the main
circulating pump inside the Hydro Unit.
• Connect the additional pumps as shown in the
diagram below.
• Connect external pump 1 to terminals 1 & 2 on
Terminal Block 05.
• Install external pumps so that their motive power
does not affect the internal pump.
▼ Fig. 7-24
Pump
01
Terminal Block 05
123456789
▼ Fig. 7-23
Booster Heater
123456789
Terminal Block 05
–22–
22-EN
Page 24
Hydro Unit
Installation Manual
3-way valve (diverter) connection
Required Valve Specification:
Electrical Specification: 230 V; 50 Hz; <100 mA
Valve Diameters: Port A, Port B: Ø 1 1/4"
Return Mechanism: 3 types of 3-way valve (diverter)
can be used.
Set the 3-way valve in use with the DIP switch SW131 on the Hydro Unit board.
SW13-1
Type 12-wire spring returnOFF
Type 23-wire SPSTOFF
Type 33-wire SPDTON
NOTE
Continuous operation of the valve motor at the fully
open position is not recommended.
• The 3-way diverter valve is used to select either
domestic hot water or space heating.
• Connect the 3-way diverter valve to terminals 7, 8
and 9 on Terminal Block 05.
• Connect the 3-way diverter valve in accordance with
the diagram below:
▼ Fig. 7-25
Type 1: SPRING RETURN
port “A” to Hot water
cylinder
Hydro Unit
▼ Fig. 7-26
Type 2: SPST
port “A” to Hot water
cylinder
port “AB” to
Hydro unit
▼ Fig. 7-27
Typ e 3: SPDT
port “AB” to
Hydro unit
port “A”
close
port “B” to Room heating
or cooling
port “A” to Hot water
cylinder
port “A”
close
open
open
Hydro Unit
TB 05
7
8
9
Hydro Unit
TB 05
7
8
9
port “AB” to
Hydro unit
port “A” open
port “B” to Room heating
or cooling
7
8
9
TB 05
port “B” to Room heating
or cooling
23-EN
–23–
Page 25
Hydro Unit
Installation Manual
3-way mixing valve connection
Required Actuator Specification
Electrical Specification:230 V; 50 Hz; <100 mA
The 3-way mixing valve is used to achieve the
temperature differential needed in a 2-zone heating
system.
• Connect the 3-way mixing valve to terminals 2, 3 and
4 on Terminal Block 04 (for Type 1 mixing valve) or
on terminals 1, 2 and 3 on Terminal Block 04 (for
Type 2 mixing valve).
• Connect the 3-way mixing valve in accordance with
the diagrams below:
▼ Fig. 7-28
Type 1: SPDT
port “A” to Zone 2 Heating
port “AB” to
Hydro unit
open
Hydro Unit
TB 04
1
2
3
port “A”
close
4
Hot water cylinder connection (optional)
• Please refer to “Electrical supply/cable
specifications” for fuse/cable size and for
connection details.
Electrical Connection (Hot Water Cylinder
Electric Heater)
• The electric heater, incorporated in the hot water
cylinder, requires a separate supply to Hydro Unit.
• Connect the hot water cylinder heater electrical
supply in accordance with shown below:
Live conductor: Terminal L on Terminal Block 03
Neutral conductor: Terminal N on Terminal Block 03
Earth Conductor: Earth terminal on Terminal Block
03
• Connect the hot water cylinder heater to the Hydro
Unit as shown below:
Live conductor to hot water cylinder: Terminal 1 on
Terminal Block 03
Neutral conductor to hot water cylinder: Terminal 2
on Terminal Block 03
Earth conductor to hot water cylinder: Earth terminal
on Terminal Block 03
▼ Fig. 7-30
Earth leakage breaker
INPUT Power
220-230 V ~
50 Hz
port “B” BLANK OFF
▼ Fig. 7-29
Type 2: SPST
port “A” to Zone 2 Heating
port “AB” to
Hydro unit
port “B” BLANK OFF
port “A”
close
open
Hydro Unit
TB 04
1
2
3
4
2
1
Hot water
cylinder
12LN
Terminal block 03
–24–
24-EN
Page 26
Hydro Unit
Installation Manual
Electrical Connection (Hot Water Cylinder
temperature Sensor)
• Connect the hot water cylinder temperature sensor
as shown below to terminals A & B on Terminal
Block 06 in the Hydro Unit.
• Please ensure that the interconnecting cable,
between the Hydro Unit and the hot water cylinder, is
connected to earth at both ends of the cable using
the shield wire.
▼ Fig. 7-31
Additional hydro unit outputs
Alarm and Boiler Outputs
Alarm Output: L1: Alarm output
• Output enabled when the system is in alarm/fault
condition.
• Volt free contact - specification shown below:
AC230 V; 0.5 A (maximum)
DC24 V; 1 A (maximum)
• Connection details: Terminals 1 and 2
(OPERATION) on MCC-1217 TB (Refer to “Fig. 732”)
Boiler Control Output: L2: Boiler drive permission
output
• Output enabled when outdoor ambient temperature
<-10°C
• Volt free contact - specification shown below:
AC230 V; 0.5 A (maximum)
DC24 V; 1 A (maximum)
• Connection details: Terminals 3 and 4 (EMG) on
MCC-1217 TB (Refer to “Fig. 7-32”)
▼ Fig. 7-32
Connection Cable
Hydro unit
Power
Supply
L2
Power
Supply
L1
Locally procured
Boiler
control
output
Alarm
output
CN208
Hydro unit
main control
board
TCB-PCIN3E
Display
Relay K1
PJ20
OPERATION
Display
Relay K2
EMG
4
3
2
1
Defrost and Compressor operation Outputs
Defrost output
• Display relay is ON when the system defrost.
• Volt free contact
AC230 V; 0.5 A (maximum)
DC24 V; 1 A (maximum)
• Connection details: Terminals 1 and 2
(OPERATION) on MCC-1217 TB (Refer to “Fig. 733”)
25-EN
–25–
Page 27
Hydro Unit
Installation Manual
Compressor operation output
• Display relay is ON with outdoor unit compressor
operation.
• Volt free contact
AC230 V; 0.5 A (maximum)
DC24 V; 1 A (maximum)
• Connection details: Terminals 3 and 4 (EMG) on
MCC-1217 TB (Refer to “Fig. 7-33”)
▼ Fig. 7-33
Connection Cable
CN209
Hydro unit
main control
board
TCB-PCIN3E
Display
Relay K1
PJ20
OPERATION
Display
Relay K2
EMG
4
3
2
1
Power
Supply
L2
Power
Supply
L1
Locally procured
Compressor
operation
output
Defrost
output
*1:Available to change the output signal by function
code 67.
Default (FC67 = 0)Setting value (FC67 = 1)
1 - 2 = Defrost output
3 - 4 = Compressor
operation output
1 - 2 = Alarm output
3 - 4 = During operation
Optional inputs to hydro unit
Room Thermostat Input:
2–3: Room thermostat input for cooling mode
1–3: Room thermostat input for heating mode
• Output enabled when either heating or cooling mode
selected on room thermostat. (locally supplied)
• Volt free contacts
• Connection details:
Cooling Connection: Terminals 3 (COM) and 2
(COOL) on MCC-1214TB (Refer to “Fig. 7-34”)
Heating Connection: Terminals 3 (COM) and 1
(HEAT) on MCC-1214TB (Refer to “Fig. 7-34”)
▼ Fig. 7-34
*1
CN211
Thermostat operation
2 - 3openclose––
1 - 3––closeopen
TCB-PCMO3E
COM
3
PJ17
COOL
HEAT
2
1
Connection
Cable
CoolingHeating
onoffonoff
Locally procured
Thermostat
Cool
Hot
CAUTION
• Be sure to prepare a non-voltage contact for each
terminal.
• Display Relay capacity of “EMG” and “OPERATION”.
Below AC230 V 0.5 A (COS
When connecting loads such as relay coil to “L1, L2”
load, insert noise surge absorber.
Below DC24 V 1 A (Non-inductive load)
When connecting load such as relay coil to “L1, L2”
load, insert the bypass circuit.
Ø = 100 %)
CAUTION
• Be sure to prepare a non-voltage continuous contact
for each terminal.
• Supplementary Insulation must be added to user
touchable part of switches.
–26–
26-EN
Page 28
Hydro Unit
Installation Manual
Emergency Shutdown input
S2: Emergency stop input, Tempo* control input
This function can be switched over with FC21 and
FC61.
• Non-voltage contacts
• Connection details:
Emergency stop, Tempo* control ON: Terminals 3
(COM) and 1 (HEAT) on MCC-1214TB (Refer to
“Fig. 7-35”)
* a price contract provided by French electric power
company EDF
Hot water tank thermostat input
S1: Local hot water tank thermostat input
This function is used with DIP switch 2_3 is “ON”, when
the customer use the local hot water tank.
* Close: Not reached setting temperature.
* Open: Reached setting temperature.
(Refer to “Fig. 7-35”)
Control of force stop and restart
S1: Hot water supply control
S2: Heating control
• This function is valid only when DIP switch 2_3 is
“OFF”, FC61 is set to “3” and FCB6 is set to “1”.
• Operation by external input can be switched over
with FC52.
▼ Fig. 7-35
TCB-PCMO3E
CN210
Connection Cable
PJ17
COM
3
2
1
Locally procured
S2S1
Earth continuity test
On completion of the electrical installation a resistance
test should be completed on the earth conductor to
ensure continuity between all pieces of equipment on
the earth conductor.
Insulation resistance test
This test must be completed using a 500 V D.C.
insulation resistance tester. Insulation resistance tests
should be completed between each live terminal and
earth.
Second remote controller
Installation place
• Install the remote controller 1 m - 1.5 m above floor
level (average room temperature area).
• Do not install the remote controller in a place
exposed to direct sunlight or outside air (such as a
window, etc.).
• Do not install the remote controller where ventilation
is poor.
• Do not install the remote controller in a freezing or
refrigerated area - the remote controller is not water
or splash-proof.
• Install the remote controller in a vertical position.
Remote controller installation dimension
Be sure to follow the installation dimension as shown in
the figure 1 when you install the remote controller on
the wall.
(mm)
120
62
18
27-EN
CAUTION
• Be sure to prepare a non-voltage continuous contact
for each terminal.
• Supplementary Insulation must be added to user
touchable part of switches.
Electrical safety checks
The electrical safety checks must be completed before
turning on the electrical supplies to the Air to Water
heat pump system. The electrical safety checks should
be completed by a qualified electrician. All results
measured should comply with your local/national
electrical installation regulations.
–27–
120
84
Page 29
Hydro Unit
Installation Manual
Remote controller installation
NOTE
• The remote controller wire should not be bundled
with other wires (mains, etc.), or installed with other
wires in the same conduit, as malfunction may
result.
• Install the remote controller away from sources of
electrical interference and electromagnetic fields.
• If electrical interference is unavoidable,
countermeasures such as appropriate filtering
should be employed.
<Remote controller
(Rear)>
Wiring slot
Wood screws
Remote controller wiring
Connection diagram
*Use 0.5 mm
* Can not use the closed end
wire joint.
Wood screws
A
B
Terminal block
(TB07) for remote
controller wiring in
Hydro unit
* Terminals A and B are non-
polar.
2
wire
Remote controller
A
B
Remote controller wiring
(Locally procured)
Second remote controller installation
requirements
Remote controller
Cover
Lower case
(Rear case)
1. For removal of the remote controller’s lower
case (rear case), insert the tip of a straight blade
screwdriver, or the like, into the two openings at
the bottom of the remote controller to open the
lower case.
2. Fix the remote controller’s rear case by wood
screws (2 pcs.). Do not over tighten, as it may
damage the rear case.
3. Connect the wires from the Hydro unit to the
remote controller terminal block.
(Refer to “How to wire the remote controller”.)
Connect the wires of the remote controller
following the terminal numbering convention of
the Hydro unit to prevent miss wiring. (Do not
apply AC 208-230V mains voltage to the remote
controller as it will be damaged.)
Remote controller
(inside, rear)
DIP switchDIP switchDIP switch
Header remote
controller/Hot
water
temperature
DIP switch
Header remote
controller/
Room
temperature
Second remote
controller/Hot
water
temperature
Second remote
controller/
Room
temperature
Installation
For a dual remote controller system, install the remote
controllers in the following way.
1. Set one of remote controllers as the header
remote controller. (Remote controller of hydro
unit is preset as Header (DIP SW1 = OFF).)
2. Set the DIP switch on all other remote controller
P.C. boards to Second. (Optional remote
controller is preset as Second (DIP SW1 = ON).)
–28–
28-EN
Page 30
Hydro Unit
• Set DIP SW2 to ON (Room temperature) on the
remote controller which you will control the room
temperature with.
DIP SW2 of optional remote controller is preset to
ON (Room temperature).
Either one of header or second remote controller
must be set as room temperature control.
• To control room temperature instead of water
temperature with this remote controller, set function
code “40” of hydro unit to “1”.
8Start up and configuration
Set the DIP switches and function codes.
Setting DIP switches on the board in the Hydro Unit
Installation Manual
• Detach the front cover and the electrical control box cover of the Hydro Unit.
• Set the DIP switches on the main board.
▼ Fig. 8-01
ON
OFF
SW No. DIP No.DescriptionDefault
Boiler install location
1
OFF = Heating side after 3 way valve
ON = Before 3 way valve
2Not Used–––––
Used to when an external cylinder thermostat is
02
10
connected
3
OFF = No external cylinder thermostat;
ON = External tank thermostat connected
Used to when an external room thermostat is
connected
4
OFF = No external room thermostat;
ON = External room thermostat connected
P1 Pump operation for hot water
1
OFF = synchronised with heat pump
ON = Normally run
P1 Pump operation for heating
2
OFF = Normally run
ON = Stopped at the outside temperature over 20°C
Synchronisation of Pump P2.
OFF = P1 synchronised with pump P1
3
ON = P2 continuous operation (pump off when
remote controller switched off)
Pump P1 power of regular, When long-term thermooff.
4
OFF = None operation
ON = regular power
SW10SW11SW12SW13
ON
1
ON
4
3
2
3
2
1
ON
4
1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
4
3
2
After
Commissioning
ON
4
3
2
1
Change 1 Change 2 Change 3
29-EN
–29–
Page 31
Hydro Unit
Installation Manual
SW No. DIP No.DescriptionDefault
Used to activate Hydro Unit back up heaters.
1
11
12
13
OFF = Back up heaters activated;
ON = back up heaters de-activated
Used to activate hot water cylinder electrical heater.
2
OFF = hot water cylinder heater activated;
ON = hot water cylinder heater de-activated
Used to activate external booster heater output.
3
OFF = external booster heater output activated;
ON = external booster heater output de-activated
4Not Used–––––
Used when a hot water cylinder is connected to
system.
1
OFF = hot water cylinder connected;
ON = hot water cylinder not connected
Used to activate Zone 1 Operation.
2
OFF = Zone 1 activated;
ON = Zone 1 de-activated
Used to activate Zone 2 Operation.
3
OFF = Zone 2 de-activated;
ON = Zone activated
4Not Used–––––
Used to determine type of 3 way diverting valve
used on system.
1
OFF = 2 wire/spring return or SPST type valve;
ON = SPDT type valve
Used to activate external boiler output.
2
OFF = external boiler output de-activated;
ON = external boiler output activated
Used to activate system auto restart after power
failure.
3
OFF = auto restart activated;
ON = auto restart de-activated
4Not UsedON––––
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
After
Commissioning
Change 1 Change 2 Change 3
Setting DIP switches on the board in second remote controller
(option)
• Detach the front cover of the Remote controller.
• Set the DIP switches on the main board
DIP No.DescriptionDefault
Used to when a second remote controller is connected
Used to determine control target when use second
remote controller
2
OFF=water temperature;
ON=room temperature
3Not Used–––––
4Not Used–––––
OFF––––
OFF––––
After
Commissioning
Change 1 Change 2 Change 3
–30–
30-EN
Page 32
Hydro Unit
Installation Manual
Setting function codes for
Hydro Unit and remote
controller
Set function codes for various operation modes with
the remote controller.
There are two types of setting.
1) Hydro Unit function code setting
2) Remote controller function code setting
Setting remote controller mode
<Setting Hydro Unit Function Code>
1Press the TEST + SET + SELECT
buttons for four seconds or more
to enter the remote controller function code
setting mode.
2Set the function code (CODE No.) with the
TEMP. buttons. (CODE No.: 01 to
13)
3Set data (DATA) with the TIME
buttons.
4Press the SET button to determine the
settings.
5The CL button is enabled only before the
SET button is pressed and the function
code is changed.
6Press the TEST button to end the
settings.
2Set the function code (CODE No.) with the
TEMP. buttons. (CODE No.: 01 to
91)
3Set data (DATA) with the TIME
buttons.
4Press the SET button to determine the
settings.
5The CL button is enabled only before the
SET button is pressed and the function
code is changed.
6Press the TEST button to end the
settings.
<Setting Remote controller Function Code>
1Press the TEST + CL + TEMP.
buttons for four seconds or more to enter
the remote controller function code setting
mode.
31-EN
–31–
Page 33
Hydro Unit
Installation Manual
Main setting items
(1) Setting Temperature Range (function code 18 to
1F)
• Set the temperature range for heating (zone 1,
zone 2), cooling, and hot water.
• The upper-limit and lower-limit temperatures of
each mode can be set.
(2) Setting Heat Pump Operation Conditions for Hot
Water Supply (function code 20 and 21)
• Set the heat pump start water temperature and
heat pump stop water temperature.
• The heat pump starts working when the water
temperature lowers below the set start water
temperature. It is recommended that the default
value be used.
(3) Compensating Hot Water Temperature
(function code 24 and 25)
• Compensate the target temperature from the
remote controller set temperature when the hot
water temperature lowers below the set outside
air temperature.
(4) Setting Hot Water Boost (function code 08 and
09)
• Set the control time and target temperature
when the HOT WATER BOOST button
on the remote controller is pressed.
(5) Setting Anti-Bacteria
• Set the control for the hot water cylinder when
ANTI BACTERIA is set with the remote
controller.
• Set the target temperature, control period, start
time (24-hour notation), and target temperature
retention period.
• Make this control setting according to
regulations and rules of respective countries.
(6) Setting Priority Mode Temperature
• Set the outside air temperature that changes the
preferred operation mode.
• Hot Water - Heating Switching Temperature
Heating operation takes precedence when the
temperature lowers the set temperature.
• Boiler HP Switching Temperature
When the temperature lowers the set
temperature the external boiler output is made.
(7) Setting Heating Auto Mode Temperature
(function code 27 to 31, A1 to A5)
• Compensate the target temperature when Auto
is set for temperature setting on the remote
controller.
• The outside air temperature (T0, T1 and T3) can
be set individually.
• The target temperature can be set to a value
from 20 to 60°C.
• However, A > B > C > D > E.
▼ Fig. 8-02
<Zone 1>
Default setting
(FC2C)
(FC2D)
(FC2E)
(FC2F)
(FC30)
(40)
(35)
(30)
(25)
(20)
A
B
C
D
E
T0T1T2
(-20)
(FCA1)(FC29)(FC2B)
Outdoor Temperature (°C)
(-10)
Auto curve shift
adjust ± 5°C (FC27)
0
T3
(10)
20-25
• The entire curve can be adjusted plus and minus
5°C by function code 27.
<Zone 2>
You can choose either a percentage or a fixed
value as the setting method of zone 2
(8) Setting Frost Protection Temperature (function
code 3A to 3B)
• Set the function when the FROST
PROTECTION button on the remote
controller is pressed.
• Set enabling/disabling of this function and the
target water temperature.
• If disabling is set, the frost protection operation
is not performed even when the FROST
PROTECTION button is pressed.
(9) Setting Frequency of Output to Internal Heater
(function code 33 to 34)
• The increase/decrease time is used to set the
response time.
–32–
32-EN
Page 34
Hydro Unit
Installation Manual
(10)Setting Night Setback (function code 26.
remote controller function code 0E to 0F)
• Set the function when the NIGHT
button on the remote controller is pressed.
• Set enabling/disabling of this function, reduction
temperature, start time, and end time.
• If disabling is set, the night setback operation is
not performed even when the NIGHT
button is pressed.
(12)Hydro 2-Way Diverting valve operation. control
• When using both cooling and heating operations
and there is an indoor unit only for heating (such
as floor heating), install the 2-way valve and set
this function code.
(13)Setting 3way Valve Operation (function code
54)
• This setting is not necessary for normal
installation. Make this setting to invert the logic
circuit in case ports A and B of the 3-way valve
are wrongly attached and it cannot be rectified
on site.
(14)Mixing valve operation setting
• Set the time period from full close to full open of
the 2-zone control mixing valve. Set a value that
is 1/10 of the actual time. And. setting the
interval control time. (minutes)
(15)Setting Heating/Hot Water Switching when
Boiler Is Used (function code 3E)
• When boiler is used, make this setting to operate
the Hydro Unit by the instruction from the boiler.
(16)Setting Heat Pump Operating Time for Hot
Water Supply Operation
• Set the time period from the start of heat pump
run to the start of heater energization at the
beginning of hot water supply operation. If a long
period is set, it takes long time for heating water.
(17)Setting Cooling ON/OFF
• Set this function when performing cooling
operation.
(18)Remote controller time indication
• 24-hour or 12-hour notation is selected for the
timer.
(19)Setting Nighttime Quiet Operation
• Issue an instruction for low-noise mode
operation to the outdoor unit. Enabling/disabling
of this function, start time, and end time can be
set.
(20)Setting Alarm Tone
• The remote controller alarm tone can be set.
(21)Second Remote controller and room
temperature thermostat
• Set the initial temperature setting.
(22)Selection of mode of operation by external
input
• Select the logic of an external input signal
(option)
(23)Hydro Unit Capacity setting
(24)Second Remote controller target temperature
setting
(25)Room temperature sensor setting
(26)Synchronization control at low outside
temperature
(27)P1 pump speed control
33-EN
–33–
Page 35
Hydro Unit
Function code settings
Heating Upper Limit - Zone 11A–37~60°C60°C
Heating Lower Limit - Zone 11B–20~37°C20
Heating Upper Limit - Zone 21C–37~60°C60
Setting
1
Temperature
Range
Hot Water
2
Operation
Hot Water
3
Temperature
Compensation
4Hot Water Boost
5Anti Bacteria
6Priority Mode
Heating Auto
7
Curve Settings
Heating Lower Limit - Zone 21D–20~37°C20
Cooling - Upper Limit18–18~30°C25
Cooling - Lower Limit19–7~20°C7
Hot Water - Upper limit1E–60~75°C75
Hot Water - Lower limit1F–40~60°C40
Heat Pump Start Temperature20–20~45°C38
Heat Pump Stop Temperature21–40~50°C45
Temperature Compensation
Outside Air Temperature (°C)
Compensation Temperature
(°C)
Operation Time (x10 min)08–3~186
Setting Temperature (°C)09–40~75°C75
Setting Temperature (°C)0A–65~75°C75
Start Cycle (Day)–0D1~107
Start Time (Hour)–0C0~2322
Operation Time (min)0B–0~6030
Hot Water & Heating
Switching Temperature (°C)
Boiler & Heat Pump Switching
Temperature (°C)
Outside Temperature T0 (°C)A1–-30~-20°C-20
Outside Temperature T1 (°C)29–-15~0°C-10
Outside Temperature T2 (°C)––00
Outside Temperature T3 (°C)2B–0~15°C10
Setting Temperature A at T0
(°C) - ZONE 1
Setting Temperature B at T1
(°C) - ZONE 1
Setting Temperature C at T2
(°C) - ZONE 1
Setting Temperature D at T3
(°C) - ZONE 1
Setting Temperature E at 20°C
(°C) - ZONE 1
ZONE2 temperature setting
0 = Percentage (FC 31)
1 = Fixed value (FCA3~A5)
Ratio Of Zone 2 In Zone 1 Auto
Mode (%)
Setting Temperature A’ at T0
(°C) - ZONE 2
Setting Temperature B’ at T1
(°C) - ZONE 2
Setting Temperature E’ at
20°C (°C) - ZONE 2
Auto Curve - Temperature
Shift (°C)
Location & FC
Number
FC DescriptionHydroRCRangeDefault
24–-20~10°C0
25–0~15°C3
22–-20~200
23–-20~20-10
2C–20~60°C40
2D–20~60°C35
2E–20~60°C30
2F–20~60°C25
30–20~60°C20
A2–0~10
31–0~100%80
A3–20~60°C40
A4–20~60°C35
A5–20~60°C20
27–-5~5°C0
After
Commissioning
Installation Manual
Change 1Change
2
–34–
34-EN
Page 36
Hydro Unit
Location & FC
Number
FC DescriptionHydroRCRangeDefault
Function 0=Invalid; 1=Valid3A–0~11
Frost Protection Setting
8Frost Protection
Back Up Heater
9
Control
10 Night Setback
Hydro 2 Way
12
Valve Operation
Control
Hydro 3 Way
13
Diverting Valve
Operation Control
2 Zone Mixing
14
Valve Drive Time
Boiler/Heat Pump
15
Synchronisation
Maximum
Operation Time Of
16
Hot Water Heat
Pump
17 Cooling Operation
Remote controller
18
Indication
CDU Night Time
19
Low Noise
Operation
20 Alarm ToneTone Switching 0=OFF; 1=ON–110~11
Second Remote
controller and
21
room temperature
thermostat
Temperature (°C)
Schedule date–120~200
Schedule time–130~230
Downtime Back Up Heater
0=5min;
1=10min;2=15min;3=20min
Uptime Back Up Heater
0=10min; 1=20min; 2=30min;
3=40min
Change Setback Temperature26–3~20°C5
Zone selection 0=Zone 1 & 2;
1= Zone 1 Only
Start Time (Hour)–0E0~2322
End Time (Hour)–0F0~2306
Cooling 2 Way Valve Operation Logic 0=Activated
during cooling; 1=Not
activated during cooling
3 Way Diverting Valve
Operation Logic 0=Activated
during hot water operation;
1=not activated during hot
water operation
Maximum Heat Pump
Operation Time In Hot Water
Operation Priority Mode
(minutes)
0=Cooloing & Heating
Operation; 1=Heating Only
Operation
24h or 12h Time Indication 0=
24h; 1=12h
Low Noise Operation
0=Invalid; 1=Valid
Start Time (Hour)–0A0~2322
End Time (Hour)–0B0~2306
Choice of the initial setting
temperature
0=The fixed temperature by
FC9D
1=The calculated temperature
by Auto curve
Fixed initial temperature
setting
3B–10~20°C15
33–0~31
34–0~30
58–0~10
3C–0~10
54–0~10
0C–3~246
59–1~304
3E–0~10
07–1~12030
02–0~10
–050~10
–090~10
B5–0~10
9D–20~60°C40
After
Commissioning
Installation Manual
Change 1Change
2
35-EN
–35–
Page 37
Hydro Unit
Operation by
22
external input
(option)
Hydro Unit
23
Capacity Setting
Second Remote
controller
24
Target
temperature
Setting
Room
25
Temperature
Sensor Setting
Synchronization
control at low
26
outside
temperature
P1 pump speed
27
control (duty of the
PWM)
Location & FC
Number
FC DescriptionHydroRCRangeDefault
0 = Contacts low > high
system stop. System restart
with remote controller
1 = Contacts high > low
system stop. System restart
with remote controller
2 = Contacts high > low
system stop. Contacts low >
high system restart
3 = Contacts low > high
system stop. Contacts low >
high (second time) system
restart
0 = Restart hot water and
heating
1 = Restart in the mode when
stopping
2 = Restart hot water
3 = Restart heating
4 = Tempo control 1; without
heater
5 = Tempo control 2; without
HP and heater
Changing the control of S1
(CN210)
0 = none
1 = Hot water supply control
In addition, it is enabled only
when switch 2_3 is set to
“OFF” and FC61 is set to “3”.
0012 = P804XWH**
0015 = P1104XWH**
Factory set but function code
is needed for PCB
replacement or function code
reset procedure has been
completed.
Settings when hot water supply function is
not used
• When the hot water supply function is not used, set
DIP SW12-1 on the Hydro Unit board to ON. (Refer
to page 29.)
Setting for cooling
• For Hydro Units that do not perform cooling (those
for floor heating, etc.), procure a motorized 2-way
valve (for cooling) (refer to “Control parts
specifications” on page 20 for the details.) locally and
attach it to the water pipe that is not used for cooling.
Connect the valve cables to terminals TB05 (3) and
(4) of the Hydro Unit.
–36–
36-EN
Page 38
Hydro Unit
I
)
Installation Manual
• Stick the optional insulator for cooling to the bottom
of the Hydro Unit.
Settings for hot water supply
• Prepare the optional hot water cylinder.
• Procure a motorized 3-way valve (refer to “Control
parts specifications” on page 20 for the details.)
locally and perform piping. Connect the valve cables
to terminals TB05 (7), (8) and (9) of the Hydro Unit.
• Set DIP SW12-1 on the Hydro Unit board to OFF.
(Refer to page 29.)
• Connect the power supply unit for the hot water
cylinder heater to terminals TB03 L and N of the
Hydro Unit.
• Connect cables between the Hydro Unit and the hot
water cylinder as follows: Hydro Unit terminals
TB03 (1), (2), and earth — Hot water cylinder (1), (2),
and earth
TB06 A, B, and earth — Hot water cylinder A, B, and
earth
Settings for 2-zone temperature control
• Procure a motorized mixing valve (refer to “Control
parts specifications” on page 20 for the details.)
locally and perform piping. Connect the valve cables
to terminals TB04 (1), (2), (3) and (4) of the Hydro
Unit.
• Procure a buffer tank locally.
• Procure a water pump locally, and connect its cables
to terminals TB05 (1) and (2) of the Hydro Unit.
To inhibit interlocking the water pump with the
internal pump of the Hydro Unit, set DIP SW10-3 on
the Hydro Unit board to OFF.
• Set DIP SW12-3 on the Hydro Unit board to ON.
(Refer to page 29.)
Attach the temperature sensor (TFI) connected to
terminals TB06 C and D of the Hydro Unit near the
hot water inlet of the Hydro Unit.
• Fix TFI sensor on the room heating supply pipe by
using the connector procured in locally.
• Cover the cables with insulation tube (minimum 1
mm) or conduit so that the user cannot touch them
directly.
• Cover the TFI sensor's cables and sensor with
insulation tube (minimum 1 mm) shown in the
diagram on the right.
▼ Fig. 8-03
M
TFI
Direct Buffer tank for
Under Floor Heating
Zone 2
Under-floor Heating
(2-Way Valve Control)
▼ Fig. 8-04
nsulation tube (minimum 1 mm
2 Zone hot water supply pipe
TFI Sensor
Tying up
More than 4 mm
Setting for second remote controller
• Prepare the optional second remote controller.
• Connect the cable to terminals TB07 A,B of the
Hydro unit and remote controller.
• Set DIP switch1 on the second remote controller
board to ON.
• <Room thermo control>
Press long the TEST + SET + SELECT
switches on the remote controller to
change the Hydro Unit function code, and change
address 40 to 1,and then press the SET button
to enable the function.
37-EN
–37–
Page 39
Hydro Unit
Installation Manual
9Test run
Use operation buttons usually to conduct a test run.
If the outside air temperature or water temperature is
outside the setting value range, press the TEST
button on the remote controller and then start a test
run. Since the protection setting is disabled in the
TEST mode, do not continue a test run longer than 10
minutes.
• Press the TEST button on the remote controller.
An indication “TEST” appears on the remote
controller.
• Press the ZONE1, 2 button and select
“heating” with the OPERATE MODE button.
The pump is activated in 30 seconds.
If air is not released completely, the flow rate switch
is activated to stop operation. Release air again
according to the piping procedure.
Little air bite is discharged from the purge valve.
• Check that the air bite sound disappears.
• Check that the hydraulic pressure has become the
predetermined pressure 0.1 to 0.2 MPa (1 to 2 bar).
If the hydraulic pressure is insufficient, replenish
water.
• Heating operation starts. Check that the hydro unit
starts heating.
• Press the OPERATE MODE button and
select “cooling.”
• Cooling operation starts. Check that the hydro unit
starts cooling and that the floor heating system is not
cooled.
• Press the ZONE1, 2 button to stop
operation.
• Press the HOT WATER button to start hot
water supply operation.
• Check that there is no air bite.
• Check that hot water is present at the connection
port of the hot water cylinder.
• Press the HOT WATER button to stop the
hot water supply operation.
• Press the TEST button to exit the test mode.
10Maintenance
Execute periodic maintenance at least once a year.
Check points
• Check all electrical connections and make
adjustments if they are necessary.
• Check the water pipes of the heating systems in
particular any evidence of leakage.
• Check the expansion tank inner pressure. If it is
insufficient, enclose nitrogen or dry air in the tank.
• Check that the hydraulic pressure is 0.1 MPa (1 bar)
or more with a water manometer. If it is insufficient,
replenish tap water.
• Pull the lever of the pressure relief valve and check
operation.
• Clean the strainer.
• Check the pump for an abnormal sound or other
abnormalities.
–38–
38-EN
Page 40
Hydro Unit
Installation Manual
11Sensor temperature monitoring function
The sensor sensing temperature is displayed on the
remote controller.
This function allows you to make sure whether the
sensor is installed properly.
Press the TEST + CL buttons for four seconds
or more.
Select the function code with the TEMP.
buttons.
Press the TEST button to exit the test mode.
Item
code
00Control temperature (Hot water cylinder)°C
01Control temperature (Zone1)°C
02Control temperature (Zone2)°C
03Remote controller sensor temperature°C
04Condensed temperature (TC)°C
06Water inlet temperature (TWI)°C
07Water outlet temperature (TWO)°C
Hydro unit data
08Water heater outlet temperature (THO)°C
09Floor inlet temperature (TFI)°C
0AHot water cylinder temperature (TTW)°C
0BMixing valve positionstep
0ELow pressure (Ps)× 10kPa
Data nameUnit
Item
code
F0Micro computer energized accumulation time × 100h
F1Hot water compressor ON accumulation time × 100h
Check remote controller operation and temperature
setting
Check whether temperature sensor is installed at the
normal position.
Check DIP switch setting on the Hydro Unit board.
Check the setting with the function code table.
Set hydraulic pressure considering pipe height, and
replenish water until manometer shows a value of set
hydraulic pressure or more.
Widen water path to the hydro unit or adopt a bypass
valve.
Check wiring and parts.
Set hydraulic pressure considering pipe height, and
replenish water until manometer shows a value of set
hydraulic pressure or more.
Check expansion tank capacity compared to total water
amount. If it is insufficient, install another expansion
tank.
Room is not heated or
cooled.
Water is not hot enough.
Nothing is displayed on the
remote controller.
Flow rate switch is
activated.
Error code [A01]
Hot water leaks from
pressure relief valve.
Incorrect remote controller setting
Incorrect function code settingCheck function code setting with the function code table.
Backup heater disconnectedCheck backup heater and bimetal thermostat.
Insufficient capacityCheck selection of equipment.
Sensor defect
Power is not supplied.Check power supply wiring.
Incorrect setting
Air bite in the pumpRelease air completely according to the procedure.
Low hydraulic pressure
Strainer is clogged.Clean the strainer.
Large resistance on the hydro side
Malfunction of motorized 3-way valve
for hot water supply
Excessive hydraulic pressure
Insufficient capacity of expansion tank
Expansion tank failureCheck the air pressure.
Installation Manual
Defect mode detected by the Hydro Unit
Check
code
A01
A02
A03
Pump or flowing quantity error
1) Detected by TC sensor
2)Detected by flow switch abnormality
3) Detection of chattering abnormality
in the flow switch input
4) Disconnection of the flow switch
connector
Temperature increase error
(heating)
(TWI, TWO, THO)
Temperature increaseerror (hot
water supply)
(TTW)
Diagnostic functional operation
Operational cause
Backup
present
Heating
Hot water
Heating
Hot water
Automatic
reset
1. Almost no or little water flow.
• Not enough vent air
• Dirt clogging in the water piping system.
××
O
O
×
O
O
• The water piping is too long.
• Installation of buffer tank and secondary pump
1. Disconnection of the flow switch connector.
2. Defect of the flow switch.
1. Check the water inlet, water outlet and heater outlet
(TWI, TWO, THO) sensors.
2.Defect of the backup heater (defect automatic
reset thermostat).
1. Check the hot water cylinder sensor (TTW).
2. Check the hot water cylinder thermal cut-out.
×
O ... Possible
× .... Not possible
Determination and action
–40–
40-EN
Page 42
Hydro Unit
Installation Manual
O ... Possible
× .... Not possible
Check
code
A04
A05
A08
A09
A10
A11
A12
E03
E04
F03
F10
F11
Diagnostic functional operation
Operational cause
Antifreeze operation
Piping antifreeze operation
Low pressure sensor operation
error
Overheat protection operation
(Thermostat of the backup heater)
Antifreeze operation 2
Operation of the release protection
Heating, hot water heater error
Regular communication error
between hydro unit and remote
controller
Regular communication error
between hydro unit and outdoor
unit
TC sensor error
TWI sensor error
TWO sensor error
Backup
present
O
Automatic
reset
×
OO
O
O
×
×
××
Heating
Cooling
×
Hot water
O
OO
×
×O
OO
OO
OO
×O
Determination and action
1. Almost no or little water flow.
• Dirt clogging in the water piping system.
• The water piping is too long or too short.
2. Check the heater power circuit.
• Power supply voltage, breaker, power supply
connection
3. Set the presence of the backup heater.
4. Check the water inlet, water outlet and heat exchange
(TWI, TWO, TC) sensors and Flow Switch.
1. Check the heater power circuit.
• Power supply voltage, breaker, power supply
connection
2. Check the water inlet, water outlet and heater outlet
sensors (TWI, TWO, THO).
3. Disconnection of the backup heater.
1. Almost no or little water flow.
2. Defect of the flow switch.
3. On-load cooling or prolonged defrosting (a lot of frost
formation) under the above conditions.
4. Defect in the low pressure sensor.
5. Check the refrigeration cycle (gas leak).
1. No water (heating without water) or no water flow.
2. Defect of the flow switch.
3. Defect of the backup heater (poor automatic reset
thermostat).
1. Almost no or little water flow.
2. Check the water inlet, water outlet and heat exchange
(TWO, TC) sensors.
1. Almost no water flow.
2. Defect of the flow switch.
3. Check the water outlet temperature sensor (TWO).
1. Activated by a large load of heating or hot water
supply.
2. Check the heater power circuit (backup or hot water
cylinder heater).
• Power supply voltage, breaker, power supply
connection
1. Check remote controller connection.
2. Defect in the remote controller.
1. Check the serial circuit.
• Miswiring of the crossover between the hydro unit and
the outdoor unit
1. Check the resistance value and connection of the
heat exchange temperature sensor (TC).
1. Check the resistance value and connection of the
water inlet temperature sensor (TWI).
1. Check the resistance value and connection of the
water outlet temperature sensor (TWO).
41-EN
–41–
Page 43
Hydro Unit
Installation Manual
O ... Possible
× .... Not possible
Check
code
TTW sensor error
F14
TFI sensor error
F17
THO sensor error
F18
Detection of THO disconnection
F19
error
TFI sensor error
F20
Low pressure sensor error
F23
F29EEROM error
F30Extended IC error
L02Combination error
L07Communication error
Communication error
L09
Setting error
L16
When ZONE1 has not been set, while
ZONE2 has been set.
Diagnostic functional operation
Operational cause
Backup
present
Automatic
reset
×O
×O
×O
××
××
OO
1. Check the resistance value and connection of the hot
water cylinder sensor (TTW).
1. Check the resistance value and connection of the
floor-inlet temperature sensor (TFI).
1. Check the resistance value and connection of the
heater outlet temperature sensor (THO).
1. Check for any disconnection of the heater outlet
temperature sensor (THO).
1. Check the connection of the floor-inlet temperature
sensor (TFI).
1. Check the connection (body or connection wiring) of
the low pressure sensor.
2. Check the resistance value of the low pressure
sensor.
Determination and action
××1. Replace the P.C. board. (Hydro unit)
××1. Replace the P.C. board. (Hydro unit)
××1. Check the model name of the outdoor unit.
××1. Replace the P.C. board. (Hydro unit)
1. Check the setting of the FC01 capability
××
specifications.
HWS-P804xx-E = 0012
HWS-P1104xx-E = 0015
××1. Check the body DP-SW12_2,3.
Defect mode detected by the Outdoor Unit
Check
code
TD sensor error
F04
TE sensor error
F06
TL sensor error
F07
TO sensor error
F08
TS sensor error
F12
TH sensor error
F13
TE, TS sensors error
F15
PD sensor error
F24
F31EEPROM errorO
Diagnostic functional operation
Operational cause
Backup
present
O×
O
O×
O×
O×
O×
O
O
Automatic
reset
×
×
×
×
Determination and action
1. Check the resistance value and connection of the
discharge sensor (TD).
1. Check the resistance value and connection of the
heat exchange temperature sensor (TE).
1. Check the resistance value and connection of the
heat exchange temperature sensor (TL).
1. Check the resistance value and connection of the
outdoor temperature sensor (TO).
1. Check the resistance value and connection of the
suction temperature sensor (TS).
1. Check the resistance value and connection of the
heat-sink temperature sensor (TH).
1. Check for any wrong installation of the heat exchange
temperature sensor (TE) and the suction temperature
sensor (TS).
1. Check the value of PD sensor by the remote
controller.
–42–
42-EN
Page 44
Hydro Unit
Installation Manual
Check
code
Compressor breakdown
H01
Compressor lock
H02
Defect in the current detection
H03
circuit
Operation of case thermostat
H04
Unset service PC board jumper
L10
Jumpers have not been cut.
L15Combination errorO
The communication between the
L29
outdoor PC board MUCs error
The outlet temperature error
P03
P04The high pressure switch errorO
P05The power supply voltage errorO×1. Check the power supply voltage.
Overheating of heat-sink error
P07
Detection of gas leak
P15
Diagnostic functional operation
Operational cause
Backup
present
O×
O
O
O
O
O
O
O
O×
Automatic
Determination and action
reset
1. Check the power supply voltage.
2. Over-loaded condition of the refrigeration cycle.
3. Check that the service valve is fully open.
1. Defect of compressor (lock)
×
– Replace the compressor.
2. Defect of compressor wiring (open phase).
×1. Replace the outdoor inverter control board.
1. Check the refrigeration cycle (gas leak).
2. Check the case thermostat and connector.
×
3. Check that the service valve is fully open.
4. Defect of the pulse motor valve.
5. Check for kinked piping.
×1. Cut outdoor PC board jumper wire (for service).
×1. Check the model name of the hydro unit.
×1. Replace the outdoor control board.
1. Check the refrigeration cycle (gas leak).
×
2. Defect of the pulse motor valve.
3. Check the resistance value of the discharge
temperature sensor (TD).
×
1. Check the thread fastening and heat-sink grease
between the outdoor control board and the heat-sink.
×
2. Check the heat-sink fan duct.
3. Check the resistance value of the heat-sink
temperature sensor (TH).
1. Check the refrigeration cycle (gas leak).
2. Check that the service valve is fully open.
3. Defect of the pulse motor valve.
4. Check for kinked piping.
5. Check the resistance value of the discharge
temperature sensor (TD), the suction temperature
sensor (TS).
6. Check the value of PD sensor by the remote
controller.
43-EN
–43–
Page 45
Hydro Unit
Installation Manual
Check
code
P19
P20
P22
P26
P29
Diagnostic functional operation
Operational cause
The 4-way valve inversion error
High pressure protection operation
Outdoor fan system error
Short circuit of the compressor
driver element error
Compressor rotor position error
Backup
present
O×
O
O
O
O
Automatic
reset
×
×
×
×
Determination and action
1. Check the operation of the 4-way valve unit or the coil
characteristics.
2. Defect of the pulse motor valve.
3. Check the resistance value of the heat exchange
temperature sensor (TE) and the suction temperature
sensor (TS).
1. Check that the service valve is fully open.
2. Defect of the pulse motor valve.
3. Check the outdoor fan system (including clogging).
4. Over-filling of refrigerant.
5. Check the resistance value of the heat exchange
temperature sensor (TL) and the water outlet
temperature sensor (TWO).
6. Check the value of PD sensor by the remote
controller.
1. Check the lock status of the motor fan.
2. Check the connection of the fan motor cable
connector.
3. Check the power supply voltage.
1. Abnormality occurs when operating with the
compressor wiring disconnected … Check the
control board.
2. No abnormality occurs when operating with the
compressor wiring disconnected … Compressor rare
short.
1. Even if the connection lead wire of the compressor is
disconnected, it stops due to an abnormality in the
position detection … Replace the inverter control
board.
2. Check the wire wound resistor of the compressor.
Short circuit
… Replace the compressor.
–44–
44-EN
Page 46
Hydro Unit
Defect mode detected by the remote controller
Diagnostic functional operation
Check code
Not
displaying at
all
(cannot
operate by
the remote
controller)
E01
E02
E09
Operational cause
No communication between hydro
unit an remote controller
No communication between hydro
unit and remote controller
Defect in the signal transmission
to the hydro unit.
(Detected on the remote controller
side)
Several remote controller base
units
(Detected on the remote controller
side)
Status of airconditioning
Stop–Defect in the remote controller power
Stop
(Automatic reset)
Stop
(Automatic reset)
Stop
(The handset
continues)
Condition
Displayed when
the abnormality
is detected.
Displayed when
the abnormality
is detected.
Displayed when
the abnormality
is detected.
Installation Manual
Determination and action
supply
1. Check the remote controller wiring.
2. Check the remote controller.
3. Check the hydro unit power supply
wiring.
4. Check the water heat exchange
control board.
Defect in the reception of the remote
controller
1. Check the remote controller
crossover.
2. Check the remote controller.
3. Check the hydro power supply wiring.
4. Check the water heat exchanger
board.
Defect in the transmission of the remote
controller
1. Check the transmitter circuit inside the
remote controller.
… Replace the remote controller.
1.2 Check several base units with the
remote controller
… The base unit is only one, and others
are handsets.
45-EN
–45–
Page 47
EF99808601
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.