Toshiba HFC series Installation Manual

AIR TO WATER HEAT PUMP
Hydro Unit
Model name:
HWS-P804XWHM3-E HWS-P804XWHT6-E HWS-P804XWHT9-E HWS-P1104XWHM3-E HWS-P1104XWHT6-E HWS-P1104XWHT9-E
English
Hydro Unit
Please read this Installation Manual carefully before installing the Air to Water Heat Pump.
• This Manual describes the installation method of the hydro unit.
• For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit.
Installation Manual
REFRIGERANT
This Air to Water Heat Pump uses an HFC refrigerant (R410A) in order to prevent destruction of the ozone layer.

Contents

1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Accessory parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 Preparations for installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4 Precautions for safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5 Example of Hydro Unit installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6 Main components of Hydro Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7 Hydro Unit installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8 Start up and configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
9 Test run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
11 Sensor temperature monitoring function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
12 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
1-EN
–1–
Hydro Unit

1 General information

System combination
Outdoor Unit
Hydro Unit HWS-P804HR-E HWS-P1104HR-E Backup heater
HWS-P804XWHM3-E ~, 3kW
HWS-P804XWHT6-E 3N ~, 6kW
HWS-P804XWHT9-E 3N~, 9kW
HWS-P1104XWHM3-E ~, 3kW
HWS-P1104XWHT6-E 3N~, 6kW
HWS-P1104XWHT9-E 3N~, 9kW
220-230V model
General specifications
Installation Manual
Outdoor Unit
Single Phase model
Outdoor unit HWS-P804HR-E HWS-P1104HR-E
Power supply 220-230V ~ 50Hz
Type INVERTER
Function Heating & Cooling
Capacity (kW) 8.0 11.2
Heating
Cooling
Refrigerant R410A
Dimension HxWxD (mm) 1,340x900x320
Input (kW) 1.68 2.30
COP (W/W) 4.76 4.88
Capacity (kW) 6.0 10.0
Input (kW) 1.64 3.33
EER (W/W) 3.66 3.00
–2–
2-EN
Hydro Unit
Installation Manual
Hydro Unit
80 class
Hydro Unit HWS-P804XWHM3-E HWS-P804XWHT6-E HWS-P804XWHT9-E
Back up heater capacity 3.0 6.0 9.0
Power supply
Leaving water temperature
for back up heater 220-230V ~ 50Hz 380-400V 3N~ 50Hz 380-400V 3N~ 50Hz
for hot water cylinder heater (option)
Heating (°C) 20-60
Cooling (°C) 7-25
220-230V ~ 50Hz
112 class
Hydro Unit HWS-P1104XWHM3-E HWS-P1104XWHT6-E HWS-P1104XWHT9-E
Back up heater capacity 3.0 6.0 9.0
Power supply
Leaving water temperature
for back up heater 220-230V ~ 50Hz 380-400V 3N~ 50Hz 380-400V 3N~ 50Hz
for hot water cylinder heater (option)
Heating (°C) 20-60
Cooling (°C) 7-25
220-230V ~ 50Hz
Hot Water Cylinder (option)
Hot water cylinder (option)
Water volume (liter) 150 210 300
Power supply 220-230V ~ 50Hz
Max water temperature (°C) 75
Electric heater (kW) 2.7
Height (mm) 1,090 1,474 2,040
Diameter (mm) 550
Material Stainless steel
HWS-1501CSHM3-E
HWS-1501CSHM3-UK
HWS-2101CSHM3-E
HWS-2101CSHM3-UK
HWS-3001CSHM3-E
HWS-3001CSHM3-UK

2 Accessory parts

No. Parts name Quantity
1 Installation Manual (this document) 1
2 Owner’s Manual 1
Insulator for cooling
3-EN
3
5
Insulator
–3–
Hydro Unit
Installation Manual

3 Preparations for installation

Parts required to connect this product (Common items)
Category Part Specification Quantity
Strainer (water filter) 1 1/4" 30 to 40 meshes 1
Water piping
Electrical system
Options required for each function
Drain cock (for water charge) 1
Isolating ball valves
Earth leakage breaker for main power supply 30 mA 1
Earth leakage breaker for backup heater 30 mA 1
(Option) Earth leakage breaker for hot water cylinder heater
1 1/4" for service 1 1/4"
30 mA 1
2
Purpose
Heating
Heating &Cooling (all rooms)
Heating & Cooling (partly heating only)
Hot water supply
2-zone control
Interlocking with boiler
In the Hydro Unit Purchased part
Part name Model name Part name Prescribed specification
Fan coil(s)
––
Hot water cylinder
150 L
210 L
300 L
Output control board kit (1)
HWS-1501CSHM3-E
HWS-1501CSHM3-UK
HWS-2101CSHM3-E
HWS-2101CSHM3-UK
HWS-3001CSHM3-E
HWS-3001CSHM3-UK
TBC-PCIN3E Boiler
Radiator(s), Fan coil(s), Under floor heating
Motorized 2-way valve (for cooling)
Motorized 3-way valve Earth leakage breaker
Motorized mixing valve
Circulator pump Other power supply
Buffer tank
Refer to “Control parts specifications” on page 20.
Refer to “Control parts specifications” on page 20.
Refer to “Control parts specifications” on page 20.
Other power supply. Signal 12 V input function is required for boiler.
Optional parts
No. Part name Model name Application Remarks
Boiler-linked output, Alarm output
1 External output board TCB-PCIN3E
2 External input board TCB-PCMO3E
Defrost signal output, compressor operation signal output
Cooling/heating thermostat input
Emergency stop signal input.
Use specified products for the outdoor unit, Hydro Unit, and hot water cylinder. Do not use commercially available products. Use parts that conform to prescribed specifications for parts to be connected to the Hydro Unit. If unspecified products or parts are used, a malfunction, failure or fire may be caused.
–4–
Up to two boards (according to applications)
Up to two boards (according to applications)
4-EN
Hydro Unit
Installation Manual

4 Precautions for safety

General safety precautions
Ensure that all Local, National and International regulations are satisfied.
• Read the “Precautions for safety” carefully before installation.
• The precautions described below include the important items regarding safety – Observe them without fail.
• After the installation work has been completed, perform a test run to check for any problems. Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.
• Turn off the main power supply switch (or breaker) before unit maintenance.
• Ask the customer to keep the Installation Manual along with the Owner’s Manual.
Refrigerant precautions
• If a refrigerant leak is suspected contact the dealer who supplied the system, in the case of a recharge of refrigerant ask service personnel for details of the leak and confirmation of the repairs completed. The refrigerant used in the system is harmless.
• Generally the refrigerant does not leak, however, if the refrigerant should leak into a room and a heater or stove burner in the room is lit, toxic gas may be generated.
• Do not install the system in a location subject to a risk of exposure to a combustible gas. If a combustible gas leaks and stays around the unit a fire may occur.
• Install the refrigerant pipe securely during installation and before operation. If the compressor is operated with no pipe work connected and valves open the compressor will suck air which would result in over pressurization of the system which may result in bursting or injury. Observe the same precautions for refrigerant recovery work (pump back procedure to outdoor unit) and do not disconnect pipe work until refrigerant is recovered and valves closed.
WARNING
Installation precautions
• Ask an authorized dealer or qualified installation professional to install/maintain the Air to Water Heat Pump System. Inappropriate installation may result in water leaks, electric shock or fire.
• Electrical work must be performed by a qualified electrician in accordance with the installation manual. An inappropriate power supply capacity or installation may result in fire.
• When completing any electrical works to the system ensure that all Local, National and International regulations are satisfied. Inappropriate grounding may result in electric shock.
• Ensure all electrical cables, used for the ESTIA installation, comply with all Local and National regulations. Check all electrical terminations are secure and tight.
• Earth wire connections.
• Install an earth leakage breaker without fail. Incomplete grounding can cause electric shock. Do not earth wires to gas pipes, water pipes, lightning rods or telephone cable earth wires.
• This unit must be connected to the main power supply using a circuit breaker or switch with a contact separation of at least 3 mm.
• Be sure to turn off all main power supply switches or the circuit breaker before starting any electrical work. Ensure all power switches are off, failure to do so can cause electric shock. Use an exclusive power circuit for the Air to Water Heat Pump system using the rated voltage.
• Ensure correct connection of interconnecting wire between Outdoor Unit and Hydro Unit. Incorrect connection of the interconnecting cable may result in the damage of electrical parts.
• Ensure refrigeration system remains sealed to external gases and air. Should air or other gases contaminate the refrigeration circuit, high system pressures could result in burst pipes and injuries.
• Do not modify or bypass any of safety guards or switches in this system.
• After unpacking the outdoor unit, examine the unit carefully for any possible damage.
• Do not install in any place that might increase the vibration of the unit.
• To avoid personal injury (with sharp edges), be careful when handling parts.
5-EN
–5–
Hydro Unit
• Perform installation work properly in accordance with the installation manual. Inappropriate installation may result in water leaks, electric shock or fire.
• Tighten all flare nuts with a torque wrench in the specified manner. Excessive tightening of the flare nut may result in cracking of the pipe work or flare nut which may result in a refrigerant leakage.
• Wear heavy duty gloves during installation work to avoid injury.
• Install the outdoor unit securely in a location where the base can sustain the weight adequately.
• In enclosed areas, if the refrigerant leaks during installation vacate and ventilate immediately.
• After installation is complete ensure and confirm that refrigerant does not leak. If refrigerant leaks into a room and flows near a fire source noxious gas may be generated.
• Do not block any drain hoses. Hoses may come off and electric shocks may occur.
• Do not hit the manometer, because it is made of glass. It is breakable.
Installation Manual
Notes on system design
• The inlet water temperature to the Hydro Unit must be 60°C or less. Especially, be careful when there is an external heating source such as a boiler. When hot water over 60°C returns, it may result in a failure of the unit or water leakage.
• The flow rate of the circulating water must meet the following range. 11 kW 18 L/minute or more 8 kW 13 L/minute or more If the flow rate becomes less than the minimum, the protective device is activated to stop the operation. To ensure the minimum flow rate of the water system, install a bypass valve on one water circuit. Please note this circuit must contain a minimum of 20 liters. If total water amount is not enough, the unit may not function fully due to protective operation.
• Do not drive water by power other than the pump built in the Hydro Unit.
• The back up heaters, in the hydro unit, are designed to assist the heat pump during periods of low ambient conditions.
• Ensure the Hydro unit and the connecting water pipes are installed in a location that is not exposed to low ambient temperatures which could result in the water circuit freezing.
• The system operation is designed around a closed water circuit. Do not use an open circuit design.
• Circulating water must be 20 liters or more.
• Please turn on the main power supply to up to 12 hours before the start of the operation, and don’t turn off the power all the time during the period of use.
–6–
6-EN
Hydro Unit
Installation Manual

5 Example of Hydro Unit installation

Example of installation for cooling and heating
When both cooling and heating modes are required a 2-way valve must be installed to isolate the radiator or under­floor heating circuit.
Fig. 5-01
Strainer (40 mesh / 0.4 mm)
Drain Cock for water Charge and Drain
Indirect Sanitary Hot Water Cylinder
TTW
Isolating Ball Valves
M
Fan Coil Units (Cooling or Heating)
Diverting 3-Way Valve for Sanitary Hot Water Cylinder
2-Way
M
Valve
Use the 2­way valve to isolate the heating circuit when in cooling mode.
2-Way
M
Valve
Radiators (Heating Only) [2-Way Valve Control]
Use it when do not operate cooling.
7-EN
Alternative to Radiators
Under-floor Heating (Heating Only) [2-Way Valve Control]
–7–
Hydro Unit
Installation Manual
Example of 2-zone temperature control and hot water supply
system
The following shows an example of the 2-zone temperature control. A buffer tank and a water pump are required for the 2-zone temperature control.
Fig. 5-02
Hi-Pressure By-Pass Valve
Temperature Regulating Valve (Mechanical)
TRV
Temp. Regulating Valve (Mechanical)
Strainer (40 mesh / 0.4 mm)
Drain Cock for water Charge and Drain
TTW
Isolating Valves (Service)
Diverting 3-Way Valve for Sanitary Hot Water Cylinder
M
TRV
Zone 1
Fan Coil Unit (Heating or Cooling)
Motorized 2-Way Valve is required if fan coil
M
units are in cooling operation.
Mixing 3-Way
M
Valve for Under Floor Heating
External Pump for Under Floor Heating
Indirect Sanitary Hot Water Cylinder
–8–
TFI
Direct Buffer tank for Under Floor Heating
Zone 2
Under-floor Heating (2-Way Valve Control)
8-EN
Hydro Unit

6 Main components of Hydro Unit

Exploded view and description for Hydro Unit
Fig. 6-01
Installation Manual
1
2
3 4 5
6 7
8 9
10
1 : Expansion vessel 2 : Temperature sensor (for Heat pump outlet -TWO) 3 : Pressure sensor 4 : Heat exchanger 5 : Flow switch (13 L/min (8 kW), 18 L/min (11 kW)) 6 : Temperature sensor (for refrigerant -TC) 7 : Temperature sensor (for water inlet -TWI) 8 : Drain nipple 9 : Water inlet connection 10 : Refrigerant liquid connection 11 : Air relief valve 12 : Pressure relief valve (0.3 MPa (3 bar)) 13 : Thermal protector (auto) 14 : Temperature sensor (for water outlet THO) 15 : Thermal protector (Single operation) 16 : Water pump 17 : Backup heater (3 kW, 3 kW x 2, 3 kW x 3) 18 : Manometer 19 : Water outlet connection 20 : Refrigerant gas connection
11 12
13 14
15
16
17 18
19 20
9-EN
–9–
Hydro Unit
E-box layout
Fig. 6-02
Installation Manual
Main P.C. board
MCC-1511
Trans former
External output P.C. board MCC­1217 (Option)
External output P.C. board MCC­1217 (Option)
Relay P.C. board MCC-1431
Fuse
(
F9 F10
Relay
(RY06)
)
MG-SW (RY05)
Relay
(RY03)
Relay
(RY01)
Fuse
MG-SW (RY04)
MG-SW (RY02)
External input P.C. board MCC­1214 (Option)
–10–
TB 07
TB07
10-EN
Hydro Unit
Installation Manual
7 Hydro Unit
installation
WARNING
• To protect yourself from injury, always use PPE (Personal Protective Equipment), that is, wear gloves.
• Install the Hydro Unit by at least two persons.
• Install the Hydro Unit in a place strong enough to withstand the following weights: Hydro Unit weight with no water 60 (P1104) Hydro Unit weight with full water 80 (P1104)
CAUTION
• Do not install the unit in a place where water freezes.
• Do not install the Hydro Unit in a place where combustible gas may leak.
• Do not install the Hydro Unit in a place exposed to rain or water.
• Do not install the Hydro Unit near equipment which generates heat.
• Do not install the Hydro Unit to a movable object.
• Do not install the Hydro Unit in a place exposed to vibration.
• The unit must be installed in accordance with national wiring regulation.
• The Hydro Unit must not be installed in a high humidity condition area.
kg (P804) 65 kg
kg (P804) 85 kg
Positioning
Service space
Secure a service space for the Hydro Unit.
• Do not install the Hydro Unit in a place where heat stagnates.
Fig. 7-01
200 mm
100 mm
500 mm
350 mm
Mounting
Install M10 bolts at the positions shown below and secure them with nuts.
Fig. 7-02
380 mm
500 mm
M10
Handling, unpacking, and
checking the Hydro Unit
• The unit should be checked when it is delivered, and any damage reported immediately to the courier claims the department.
960 mm
NOTE
If customer worried about vibration of ESTIA, please insert vibration isolating material between the product and the wall, when installing the product.
11-EN
–11–
Hydro Unit
Installation Manual
The Hydro Unit can be installed directly without using the fixing angles. However, the back side of the Hydro Unit can be highly heated, therefore, the installing surface must be heat­resistant.
Fig. 7-03
Remove the M5a screws to detach the fixing angles.
Fig. 7-04
380
Fig. 7-05
M10
860
M10
Refrigerant piping
WARNING
• THIS SYSTEM ADOPTS HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY THE OZONE LAYER.
• The characteristics of R410A refrigerant are: ease to absorb water, oxidizing membrane or oil, and its pressure is approximately 1.6 times higher that of R22. Accompanied with the new refrigerant the oil has also been changed. Therefore during installation work prevention of the invasion of water, dust, former refrigerant or oil is of a paramount importance. To prevent the charging of incorrect refrigerants into the system the service valve connection ports have also increased in size.
• The use of R410A tools is required for correct installation of the system.
• The use of the correct pipe sizes and wall thicknesses of copper pipe work is required for the correct installation of the system.
CAUTION
• Ensure all refrigerant pipes are protected from the invasion of dust and water.
• Ensure all pipe work connections are tightened to the required torque settings detailed in this section.
• Perform an air tight using Oxygen Free Nitrogen (OFN) only.
• Evacuate the air in the pipe work using a vacuum pump.
• Check for refrigerant gas leaks at all connections throughout the pipe work.
Secure the Hydro Unit with plain washers and nuts.
Install the Hydro Unit so that its tilting angle falls within the range below.
Fig. 7-06
± 1°
Fig. 7-07
± 1°
NOTE
The Air to Water Heat Pump system uses R410A refrigerant. It is important that copper pipes used for refrigerant piping have the following wall thickness:
• 0.8 mm for Ø6.4 mm, Ø9.5 mm and Ø12.7 mm
• 1.0 mm for Ø15.9 mm
–12–
12-EN
Hydro Unit
Installation Manual
Refrigeration pipe
The length and height of the refrigeration pipe must be within the following values. As long as the Hydro Unit is installed within these ranges, no additional refrigerant is required.
Fig. 7-08
Outdoor unit
L
H
H: Max. ±30 m (above or below) L: Max. 30 m
Min. 5 m
Refrigerant pipe sizes
Hydro Unit Model Gas Side (mm)
8 & 11 kW Hydro Unit Ø 15.88 Ø 9.52
Liquid Side
(mm)
Flaring
• Cut the refrigerant pipes to the correct length using a pipe cutter. Remove any burrs that may be on the pipes as these may cause refrigerant leaks or component failure in the refrigeration cycle.
• Place the correct size flare nuts onto the pipes (use the flare nuts supplied with the Hydro Unit or use flare nuts designed specifically for R410A refrigerant) and then flare the pipes using the correct flaring tool.
Tightening
• Connect the refrigerant pipes, from the outdoor unit, to the Hydro Unit as shown below.
Fig. 7-09
Gas line Ø 15.88
Liquid line Ø 9.52
• Align the flare connection on each pipe with the corresponding outlet connection on the Hydro Unit. Tighten the flare nuts, using fingers, to secure the pipes in place.
• Tighten the flare nuts, using a torque wrench, to the tightening torques shown below:
Outer Ø of Copper Pipe
(mm)
9.5 33 to 42
15.9 63 to 77
Tightening Torque (N/m)
• To prevent damage, to the refrigerant pipes, use two spanners to tighten the flare nut connections to the required torque.
Water pipe
13-EN
WARNING
• Install water pipes according to the regulations of respective countries.
• Install water pipes in a freeze-free place.
• Make sure that water pipes have sufficient pressure resistance. The setting value of the pressure relief valve is 0.3 MPa. (3 bar)
CAUTION
• Do not use zinc plated water pipes. When steel pipes are used, insulate both ends of the pipes.
–13–
Hydro Unit
Installation Manual
• The water to be used must meet the water quality standard specified in EN directive 98/83 EC.
Water pipe
Design the water pipe length within the QH characteristics of the pump (Refer to “Fig. 7-16” and “Fig. 7-17” on page 16). The height of the pipe must be 7 m or less.
Fig.7-10
H < 7 m
Fig. 7-11
Attention To avoid water leak, exchange the seal tapes to new one.
Attention Water (used at test in factory before shipping) may be found in the caps.
Hot water outlet connection 1 1/4"
Water circuit
• Install a strainer with 30 to 40 meshes (locally procured) at the water inlet of the Hydro Unit.
• Install drain cocks (locally procured) for water charge and discharge at the lower part of the Hydro Unit.
• Make the piping route a closed circuit. (An open water circuit may cause a failure.)
Water inlet connection 1 1/4"
Fig. 7-12
Inlet
Isolating Ball Valve
Strainer (30 to 40 meshes)
Drain cock for water charge and discharge
–14–
Local arrangement
14-EN
Loading...
+ 32 hidden pages