Toshiba HFC series Installation Manual

Page 1
AIR TO WATER HEAT PUMP
Hydro Unit
Model name:
HWS-P804XWHM3-E HWS-P804XWHT6-E HWS-P804XWHT9-E HWS-P1104XWHM3-E HWS-P1104XWHT6-E HWS-P1104XWHT9-E
English
Page 2
Hydro Unit
Please read this Installation Manual carefully before installing the Air to Water Heat Pump.
• This Manual describes the installation method of the hydro unit.
• For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit.
Installation Manual
REFRIGERANT
This Air to Water Heat Pump uses an HFC refrigerant (R410A) in order to prevent destruction of the ozone layer.

Contents

1 General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 Accessory parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 Preparations for installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4 Precautions for safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5 Example of Hydro Unit installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6 Main components of Hydro Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7 Hydro Unit installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8 Start up and configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
9 Test run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
10 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
11 Sensor temperature monitoring function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
12 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
1-EN
–1–
Page 3
Hydro Unit

1 General information

System combination
Outdoor Unit
Hydro Unit HWS-P804HR-E HWS-P1104HR-E Backup heater
HWS-P804XWHM3-E ~, 3kW
HWS-P804XWHT6-E 3N ~, 6kW
HWS-P804XWHT9-E 3N~, 9kW
HWS-P1104XWHM3-E ~, 3kW
HWS-P1104XWHT6-E 3N~, 6kW
HWS-P1104XWHT9-E 3N~, 9kW
220-230V model
General specifications
Installation Manual
Outdoor Unit
Single Phase model
Outdoor unit HWS-P804HR-E HWS-P1104HR-E
Power supply 220-230V ~ 50Hz
Type INVERTER
Function Heating & Cooling
Capacity (kW) 8.0 11.2
Heating
Cooling
Refrigerant R410A
Dimension HxWxD (mm) 1,340x900x320
Input (kW) 1.68 2.30
COP (W/W) 4.76 4.88
Capacity (kW) 6.0 10.0
Input (kW) 1.64 3.33
EER (W/W) 3.66 3.00
–2–
2-EN
Page 4
Hydro Unit
Installation Manual
Hydro Unit
80 class
Hydro Unit HWS-P804XWHM3-E HWS-P804XWHT6-E HWS-P804XWHT9-E
Back up heater capacity 3.0 6.0 9.0
Power supply
Leaving water temperature
for back up heater 220-230V ~ 50Hz 380-400V 3N~ 50Hz 380-400V 3N~ 50Hz
for hot water cylinder heater (option)
Heating (°C) 20-60
Cooling (°C) 7-25
220-230V ~ 50Hz
112 class
Hydro Unit HWS-P1104XWHM3-E HWS-P1104XWHT6-E HWS-P1104XWHT9-E
Back up heater capacity 3.0 6.0 9.0
Power supply
Leaving water temperature
for back up heater 220-230V ~ 50Hz 380-400V 3N~ 50Hz 380-400V 3N~ 50Hz
for hot water cylinder heater (option)
Heating (°C) 20-60
Cooling (°C) 7-25
220-230V ~ 50Hz
Hot Water Cylinder (option)
Hot water cylinder (option)
Water volume (liter) 150 210 300
Power supply 220-230V ~ 50Hz
Max water temperature (°C) 75
Electric heater (kW) 2.7
Height (mm) 1,090 1,474 2,040
Diameter (mm) 550
Material Stainless steel
HWS-1501CSHM3-E
HWS-1501CSHM3-UK
HWS-2101CSHM3-E
HWS-2101CSHM3-UK
HWS-3001CSHM3-E
HWS-3001CSHM3-UK

2 Accessory parts

No. Parts name Quantity
1 Installation Manual (this document) 1
2 Owner’s Manual 1
Insulator for cooling
3-EN
3
5
Insulator
–3–
Page 5
Hydro Unit
Installation Manual

3 Preparations for installation

Parts required to connect this product (Common items)
Category Part Specification Quantity
Strainer (water filter) 1 1/4" 30 to 40 meshes 1
Water piping
Electrical system
Options required for each function
Drain cock (for water charge) 1
Isolating ball valves
Earth leakage breaker for main power supply 30 mA 1
Earth leakage breaker for backup heater 30 mA 1
(Option) Earth leakage breaker for hot water cylinder heater
1 1/4" for service 1 1/4"
30 mA 1
2
Purpose
Heating
Heating &Cooling (all rooms)
Heating & Cooling (partly heating only)
Hot water supply
2-zone control
Interlocking with boiler
In the Hydro Unit Purchased part
Part name Model name Part name Prescribed specification
Fan coil(s)
––
Hot water cylinder
150 L
210 L
300 L
Output control board kit (1)
HWS-1501CSHM3-E
HWS-1501CSHM3-UK
HWS-2101CSHM3-E
HWS-2101CSHM3-UK
HWS-3001CSHM3-E
HWS-3001CSHM3-UK
TBC-PCIN3E Boiler
Radiator(s), Fan coil(s), Under floor heating
Motorized 2-way valve (for cooling)
Motorized 3-way valve Earth leakage breaker
Motorized mixing valve
Circulator pump Other power supply
Buffer tank
Refer to “Control parts specifications” on page 20.
Refer to “Control parts specifications” on page 20.
Refer to “Control parts specifications” on page 20.
Other power supply. Signal 12 V input function is required for boiler.
Optional parts
No. Part name Model name Application Remarks
Boiler-linked output, Alarm output
1 External output board TCB-PCIN3E
2 External input board TCB-PCMO3E
Defrost signal output, compressor operation signal output
Cooling/heating thermostat input
Emergency stop signal input.
Use specified products for the outdoor unit, Hydro Unit, and hot water cylinder. Do not use commercially available products. Use parts that conform to prescribed specifications for parts to be connected to the Hydro Unit. If unspecified products or parts are used, a malfunction, failure or fire may be caused.
–4–
Up to two boards (according to applications)
Up to two boards (according to applications)
4-EN
Page 6
Hydro Unit
Installation Manual

4 Precautions for safety

General safety precautions
Ensure that all Local, National and International regulations are satisfied.
• Read the “Precautions for safety” carefully before installation.
• The precautions described below include the important items regarding safety – Observe them without fail.
• After the installation work has been completed, perform a test run to check for any problems. Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.
• Turn off the main power supply switch (or breaker) before unit maintenance.
• Ask the customer to keep the Installation Manual along with the Owner’s Manual.
Refrigerant precautions
• If a refrigerant leak is suspected contact the dealer who supplied the system, in the case of a recharge of refrigerant ask service personnel for details of the leak and confirmation of the repairs completed. The refrigerant used in the system is harmless.
• Generally the refrigerant does not leak, however, if the refrigerant should leak into a room and a heater or stove burner in the room is lit, toxic gas may be generated.
• Do not install the system in a location subject to a risk of exposure to a combustible gas. If a combustible gas leaks and stays around the unit a fire may occur.
• Install the refrigerant pipe securely during installation and before operation. If the compressor is operated with no pipe work connected and valves open the compressor will suck air which would result in over pressurization of the system which may result in bursting or injury. Observe the same precautions for refrigerant recovery work (pump back procedure to outdoor unit) and do not disconnect pipe work until refrigerant is recovered and valves closed.
WARNING
Installation precautions
• Ask an authorized dealer or qualified installation professional to install/maintain the Air to Water Heat Pump System. Inappropriate installation may result in water leaks, electric shock or fire.
• Electrical work must be performed by a qualified electrician in accordance with the installation manual. An inappropriate power supply capacity or installation may result in fire.
• When completing any electrical works to the system ensure that all Local, National and International regulations are satisfied. Inappropriate grounding may result in electric shock.
• Ensure all electrical cables, used for the ESTIA installation, comply with all Local and National regulations. Check all electrical terminations are secure and tight.
• Earth wire connections.
• Install an earth leakage breaker without fail. Incomplete grounding can cause electric shock. Do not earth wires to gas pipes, water pipes, lightning rods or telephone cable earth wires.
• This unit must be connected to the main power supply using a circuit breaker or switch with a contact separation of at least 3 mm.
• Be sure to turn off all main power supply switches or the circuit breaker before starting any electrical work. Ensure all power switches are off, failure to do so can cause electric shock. Use an exclusive power circuit for the Air to Water Heat Pump system using the rated voltage.
• Ensure correct connection of interconnecting wire between Outdoor Unit and Hydro Unit. Incorrect connection of the interconnecting cable may result in the damage of electrical parts.
• Ensure refrigeration system remains sealed to external gases and air. Should air or other gases contaminate the refrigeration circuit, high system pressures could result in burst pipes and injuries.
• Do not modify or bypass any of safety guards or switches in this system.
• After unpacking the outdoor unit, examine the unit carefully for any possible damage.
• Do not install in any place that might increase the vibration of the unit.
• To avoid personal injury (with sharp edges), be careful when handling parts.
5-EN
–5–
Page 7
Hydro Unit
• Perform installation work properly in accordance with the installation manual. Inappropriate installation may result in water leaks, electric shock or fire.
• Tighten all flare nuts with a torque wrench in the specified manner. Excessive tightening of the flare nut may result in cracking of the pipe work or flare nut which may result in a refrigerant leakage.
• Wear heavy duty gloves during installation work to avoid injury.
• Install the outdoor unit securely in a location where the base can sustain the weight adequately.
• In enclosed areas, if the refrigerant leaks during installation vacate and ventilate immediately.
• After installation is complete ensure and confirm that refrigerant does not leak. If refrigerant leaks into a room and flows near a fire source noxious gas may be generated.
• Do not block any drain hoses. Hoses may come off and electric shocks may occur.
• Do not hit the manometer, because it is made of glass. It is breakable.
Installation Manual
Notes on system design
• The inlet water temperature to the Hydro Unit must be 60°C or less. Especially, be careful when there is an external heating source such as a boiler. When hot water over 60°C returns, it may result in a failure of the unit or water leakage.
• The flow rate of the circulating water must meet the following range. 11 kW 18 L/minute or more 8 kW 13 L/minute or more If the flow rate becomes less than the minimum, the protective device is activated to stop the operation. To ensure the minimum flow rate of the water system, install a bypass valve on one water circuit. Please note this circuit must contain a minimum of 20 liters. If total water amount is not enough, the unit may not function fully due to protective operation.
• Do not drive water by power other than the pump built in the Hydro Unit.
• The back up heaters, in the hydro unit, are designed to assist the heat pump during periods of low ambient conditions.
• Ensure the Hydro unit and the connecting water pipes are installed in a location that is not exposed to low ambient temperatures which could result in the water circuit freezing.
• The system operation is designed around a closed water circuit. Do not use an open circuit design.
• Circulating water must be 20 liters or more.
• Please turn on the main power supply to up to 12 hours before the start of the operation, and don’t turn off the power all the time during the period of use.
–6–
6-EN
Page 8
Hydro Unit
Installation Manual

5 Example of Hydro Unit installation

Example of installation for cooling and heating
When both cooling and heating modes are required a 2-way valve must be installed to isolate the radiator or under­floor heating circuit.
Fig. 5-01
Strainer (40 mesh / 0.4 mm)
Drain Cock for water Charge and Drain
Indirect Sanitary Hot Water Cylinder
TTW
Isolating Ball Valves
M
Fan Coil Units (Cooling or Heating)
Diverting 3-Way Valve for Sanitary Hot Water Cylinder
2-Way
M
Valve
Use the 2­way valve to isolate the heating circuit when in cooling mode.
2-Way
M
Valve
Radiators (Heating Only) [2-Way Valve Control]
Use it when do not operate cooling.
7-EN
Alternative to Radiators
Under-floor Heating (Heating Only) [2-Way Valve Control]
–7–
Page 9
Hydro Unit
Installation Manual
Example of 2-zone temperature control and hot water supply
system
The following shows an example of the 2-zone temperature control. A buffer tank and a water pump are required for the 2-zone temperature control.
Fig. 5-02
Hi-Pressure By-Pass Valve
Temperature Regulating Valve (Mechanical)
TRV
Temp. Regulating Valve (Mechanical)
Strainer (40 mesh / 0.4 mm)
Drain Cock for water Charge and Drain
TTW
Isolating Valves (Service)
Diverting 3-Way Valve for Sanitary Hot Water Cylinder
M
TRV
Zone 1
Fan Coil Unit (Heating or Cooling)
Motorized 2-Way Valve is required if fan coil
M
units are in cooling operation.
Mixing 3-Way
M
Valve for Under Floor Heating
External Pump for Under Floor Heating
Indirect Sanitary Hot Water Cylinder
–8–
TFI
Direct Buffer tank for Under Floor Heating
Zone 2
Under-floor Heating (2-Way Valve Control)
8-EN
Page 10
Hydro Unit

6 Main components of Hydro Unit

Exploded view and description for Hydro Unit
Fig. 6-01
Installation Manual
1
2
3 4 5
6 7
8 9
10
1 : Expansion vessel 2 : Temperature sensor (for Heat pump outlet -TWO) 3 : Pressure sensor 4 : Heat exchanger 5 : Flow switch (13 L/min (8 kW), 18 L/min (11 kW)) 6 : Temperature sensor (for refrigerant -TC) 7 : Temperature sensor (for water inlet -TWI) 8 : Drain nipple 9 : Water inlet connection 10 : Refrigerant liquid connection 11 : Air relief valve 12 : Pressure relief valve (0.3 MPa (3 bar)) 13 : Thermal protector (auto) 14 : Temperature sensor (for water outlet THO) 15 : Thermal protector (Single operation) 16 : Water pump 17 : Backup heater (3 kW, 3 kW x 2, 3 kW x 3) 18 : Manometer 19 : Water outlet connection 20 : Refrigerant gas connection
11 12
13 14
15
16
17 18
19 20
9-EN
–9–
Page 11
Hydro Unit
E-box layout
Fig. 6-02
Installation Manual
Main P.C. board
MCC-1511
Trans former
External output P.C. board MCC­1217 (Option)
External output P.C. board MCC­1217 (Option)
Relay P.C. board MCC-1431
Fuse
(
F9 F10
Relay
(RY06)
)
MG-SW (RY05)
Relay
(RY03)
Relay
(RY01)
Fuse
MG-SW (RY04)
MG-SW (RY02)
External input P.C. board MCC­1214 (Option)
–10–
TB 07
TB07
10-EN
Page 12
Hydro Unit
Installation Manual
7 Hydro Unit
installation
WARNING
• To protect yourself from injury, always use PPE (Personal Protective Equipment), that is, wear gloves.
• Install the Hydro Unit by at least two persons.
• Install the Hydro Unit in a place strong enough to withstand the following weights: Hydro Unit weight with no water 60 (P1104) Hydro Unit weight with full water 80 (P1104)
CAUTION
• Do not install the unit in a place where water freezes.
• Do not install the Hydro Unit in a place where combustible gas may leak.
• Do not install the Hydro Unit in a place exposed to rain or water.
• Do not install the Hydro Unit near equipment which generates heat.
• Do not install the Hydro Unit to a movable object.
• Do not install the Hydro Unit in a place exposed to vibration.
• The unit must be installed in accordance with national wiring regulation.
• The Hydro Unit must not be installed in a high humidity condition area.
kg (P804) 65 kg
kg (P804) 85 kg
Positioning
Service space
Secure a service space for the Hydro Unit.
• Do not install the Hydro Unit in a place where heat stagnates.
Fig. 7-01
200 mm
100 mm
500 mm
350 mm
Mounting
Install M10 bolts at the positions shown below and secure them with nuts.
Fig. 7-02
380 mm
500 mm
M10
Handling, unpacking, and
checking the Hydro Unit
• The unit should be checked when it is delivered, and any damage reported immediately to the courier claims the department.
960 mm
NOTE
If customer worried about vibration of ESTIA, please insert vibration isolating material between the product and the wall, when installing the product.
11-EN
–11–
Page 13
Hydro Unit
Installation Manual
The Hydro Unit can be installed directly without using the fixing angles. However, the back side of the Hydro Unit can be highly heated, therefore, the installing surface must be heat­resistant.
Fig. 7-03
Remove the M5a screws to detach the fixing angles.
Fig. 7-04
380
Fig. 7-05
M10
860
M10
Refrigerant piping
WARNING
• THIS SYSTEM ADOPTS HFC REFRIGERANT (R410A) WHICH DOES NOT DESTROY THE OZONE LAYER.
• The characteristics of R410A refrigerant are: ease to absorb water, oxidizing membrane or oil, and its pressure is approximately 1.6 times higher that of R22. Accompanied with the new refrigerant the oil has also been changed. Therefore during installation work prevention of the invasion of water, dust, former refrigerant or oil is of a paramount importance. To prevent the charging of incorrect refrigerants into the system the service valve connection ports have also increased in size.
• The use of R410A tools is required for correct installation of the system.
• The use of the correct pipe sizes and wall thicknesses of copper pipe work is required for the correct installation of the system.
CAUTION
• Ensure all refrigerant pipes are protected from the invasion of dust and water.
• Ensure all pipe work connections are tightened to the required torque settings detailed in this section.
• Perform an air tight using Oxygen Free Nitrogen (OFN) only.
• Evacuate the air in the pipe work using a vacuum pump.
• Check for refrigerant gas leaks at all connections throughout the pipe work.
Secure the Hydro Unit with plain washers and nuts.
Install the Hydro Unit so that its tilting angle falls within the range below.
Fig. 7-06
± 1°
Fig. 7-07
± 1°
NOTE
The Air to Water Heat Pump system uses R410A refrigerant. It is important that copper pipes used for refrigerant piping have the following wall thickness:
• 0.8 mm for Ø6.4 mm, Ø9.5 mm and Ø12.7 mm
• 1.0 mm for Ø15.9 mm
–12–
12-EN
Page 14
Hydro Unit
Installation Manual
Refrigeration pipe
The length and height of the refrigeration pipe must be within the following values. As long as the Hydro Unit is installed within these ranges, no additional refrigerant is required.
Fig. 7-08
Outdoor unit
L
H
H: Max. ±30 m (above or below) L: Max. 30 m
Min. 5 m
Refrigerant pipe sizes
Hydro Unit Model Gas Side (mm)
8 & 11 kW Hydro Unit Ø 15.88 Ø 9.52
Liquid Side
(mm)
Flaring
• Cut the refrigerant pipes to the correct length using a pipe cutter. Remove any burrs that may be on the pipes as these may cause refrigerant leaks or component failure in the refrigeration cycle.
• Place the correct size flare nuts onto the pipes (use the flare nuts supplied with the Hydro Unit or use flare nuts designed specifically for R410A refrigerant) and then flare the pipes using the correct flaring tool.
Tightening
• Connect the refrigerant pipes, from the outdoor unit, to the Hydro Unit as shown below.
Fig. 7-09
Gas line Ø 15.88
Liquid line Ø 9.52
• Align the flare connection on each pipe with the corresponding outlet connection on the Hydro Unit. Tighten the flare nuts, using fingers, to secure the pipes in place.
• Tighten the flare nuts, using a torque wrench, to the tightening torques shown below:
Outer Ø of Copper Pipe
(mm)
9.5 33 to 42
15.9 63 to 77
Tightening Torque (N/m)
• To prevent damage, to the refrigerant pipes, use two spanners to tighten the flare nut connections to the required torque.
Water pipe
13-EN
WARNING
• Install water pipes according to the regulations of respective countries.
• Install water pipes in a freeze-free place.
• Make sure that water pipes have sufficient pressure resistance. The setting value of the pressure relief valve is 0.3 MPa. (3 bar)
CAUTION
• Do not use zinc plated water pipes. When steel pipes are used, insulate both ends of the pipes.
–13–
Page 15
Hydro Unit
Installation Manual
• The water to be used must meet the water quality standard specified in EN directive 98/83 EC.
Water pipe
Design the water pipe length within the QH characteristics of the pump (Refer to “Fig. 7-16” and “Fig. 7-17” on page 16). The height of the pipe must be 7 m or less.
Fig.7-10
H < 7 m
Fig. 7-11
Attention To avoid water leak, exchange the seal tapes to new one.
Attention Water (used at test in factory before shipping) may be found in the caps.
Hot water outlet connection 1 1/4"
Water circuit
• Install a strainer with 30 to 40 meshes (locally procured) at the water inlet of the Hydro Unit.
• Install drain cocks (locally procured) for water charge and discharge at the lower part of the Hydro Unit.
• Make the piping route a closed circuit. (An open water circuit may cause a failure.)
Water inlet connection 1 1/4"
Fig. 7-12
Inlet
Isolating Ball Valve
Strainer (30 to 40 meshes)
Drain cock for water charge and discharge
–14–
Local arrangement
14-EN
Page 16
Hydro Unit
0
Installation Manual
Piping to hot water cylinder (option)
Water supplied to the hot water cylinder is branched by a motorized 3-way valve (locally procured). For the specifications of the motorized 3-way valve, refer to “Control parts specifications” on page 20. Connect the hot water cylinder to port A (open when energized) of the valve.
Fig. 7-13
to hydro unit
room heating or cooling
Open when de­energized
B
to hot water cylinder
AB
A
Open when energized
Piping to 2-zone operation
To perform 2-zone temperature control, circulate water by another pump (locally procured) through a motorized mixing valve (locally procured) and a buffer tank (locally procured). For the specifications of the motorized mixing valve, Refer to “Control parts specifications” on page 20.
Fig. 7-14
Motorized mixing valve (locally procured)
Water pump (locally procured)
Zone 2
AB
A
B
from hydro unit
Expression for expansion vessel selection
V: Necessary total tank capacity ( )
: Water expansion coefficient at each hot water
temperature Vs: Total water amount in the system P1: System pressure at tank setting position
(MPaabs.)
= water supply pressure = 0.3 (MPaabs.)
(recommended valve) P2: Maximum pressure used during operation at tank
setting position (MPaabs.)
= safety valve setting pressure = 0.4 (MPaabs.) * The absolute pressure value (abs.) is obtained by
adding the atmospheric pressure (0.1 MPa (1 bar)) to the gauge pressure.
Tank selection method
Water temperature and expansion coefficient
Hot water
temperature
(°C)
0 0.0002 50 0.0121
4 0.0000 55 0.0145
5 0.0000 60 0.0171
10 0.0003 65 0.0198
15 0.0008 70 0.0229
20 0.0017 75 0.0258
25 0.0029 80 0.0292
30 0.0043 85 0.0324
35 0.0050 90 0.0361
40 0.0078
45 0.0100
Expansion
rate
Hot water
temperature
(°C)
Expansion
rate
15-EN
Buffer tank (locally
to hydro unit
procured)
Checking water volume and initial pressure of expansion vessel
The expansion vessel of the Hydro Unit has a capacity of 12 liters. The initial pressure of the expansion vessel is
0.15 MPa (1.5 bar). The pressure of the safety valve is 0.3 MPa (3 bar). Verify whether the capacity of the expansion vessel is sufficient using the following expression. If the volume is insufficient, add the capacity locally.
–15–
Fig. 7-15
18
16
14
12
10
8
6
4
2
0
0 50 100 150
Vs: Total water amount in the system( )
V: Necessary total tank capacity( )
250200 30
*In case the maximum hot water temperature is 60ºC
Install an external expansion vessel when the capacity of the expansion vessel is insufficient.
Page 17
Hydro Unit
Pump operation/configuration
Fig. 7-16
Hydraulic heat exchanger (8 kW) QH characteristics
10
Installation Manual
Minimum flow rate
Fig. 7-17
9
8
7
6
5
Head [m]
4
3
2
1
0
0 5 10 15 20 25 30 35
Hydraulic heat exchanger (11 kW) QH characteristics
10
9
8
7
6
Out of range
Pump duty
60 %
Out of range
Pump duty
100 %
Pump duty
Flow rate [L/min]
Minimum flow rate
Hydro unit QH­Characteristics (220/230 V)
80 %
Hydro unit QH­Characteristics (220/230 V)
Pump duty
100 %
5
Head [m]
4
3
Pump duty
2
1
0
0 1020304050
60 %
Pump duty
80 %
Flow rate [L/min]
–16–
16-EN
Page 18
Hydro Unit
Installation Manual
Water charging
Charge water until the pressure gauge shows recommended valve 0.2 MPa (2 bar). Hydraulic pressure may drop when the trial run begins. In that case, add water. Air may enter if the charged hydraulic pressure is low. Loosen the purge valve cap by two turns to release air.
Fig. 7-18
Loosen 2 turns for proper venting
Loosen the air vent screw of the pump, pull out air in the pump, and tighten again. Loosen the cap of the pressure relief valve to release air. Water may come out of the pressure relief valve. Release the air completely from the water circuit. Failure to do so may disable correct operation.
Electrical installation
WARNING
• Ensure electrical circuits are isolated before commencing the electrical installation.
• The electrical installation must be completed by a qualified electrician.
• The electrical installation must comply to all Local, National and International electrical installation regulations.
• This product must be earthed in accordance with Local, National and International electrical installation regulations.
CAUTION
• The Hydro Unit must be connected to a dedicated power supply for the back up heater circuit.
• The electrical supply must be protected by a suitably sized over current protection device (fuse, MCB etc) and an earth leakage protection device.
• The Hydro Unit must be connected to the mains power supply using a isolating switch which disconnects all poles and has a contact separation of at least 3 mm.
• The cord clamps, attached to the Hydro Unit, must be used to secure the electrical cables.
• Wrong connection of electrical cables may result in electrical component failure or fire.
• Ensure the electrical cables are sized in accordance with the installation instructions.
17-EN
Water quality
The water used must satisfy EN directive 98/83 EC.
Piping insulation
It is recommended that insulation treatment be applied to all pipes. To perform optional cooling operation, apply insulation treatment of 20 t or more to all pipes.
–17–
Page 19
Hydro Unit
Control line
Fig. 7-19
Installation Manual
Pump (local)
Max 12 m 230 V 100 mA
0.75 mm² or more
Booster heater (local)
Max 12 m 230 V 1 A
0.75 mm² or more
2Way-Valve for cooling stop
Max 12 m 230 V 1 A
0.75 mm² or more
3Way-Valve for hot water cylinder
Mixing-Valve type 2 for 2 zone control
4
2
3
1
TB04
1 2
3 4
TB05
5 6
7 8
CN208
OPTION OPTION
9
PJ20
2
1
3
Mixing-Valve type 1 for 2 zone control
N
CW
4
2
3
1
TB06
TB07
1 2
CN209
PJ20
2
1
4
3
Max 12 m 230 V 100 mA
0.75 mm² or more
Max 5 m shielded wire
0.75 mm² or more
CCW
A B
C D
Temp sensor for 2 zone control
2nd remote controller
4
Temp sensor in hot water cylinder
A B
Max 5 m shielded wire 0.75 mm² or more
Max 50 m shielded wire
0.50 mm² or more
Max 12 m non voltage 0.75 mm² or more
Fig. 7-20
TB03
TB01
Alert output (local)
Boiler operation (local)
Defrost output (local)
Compressor operation output (local)
3WV
1
11 12
2
TB 01
59
3
13
43
41
42
MIXV
TB 04
31 32
HOT WATER CYLINDER
Hot water cylinder
44
L
N
TB 03
Input power 220-230 V ~ 50 Hz
L3
N
L2L1
L
N
TB 02
Input power 220-230 V ~ 50 Hz
TB02
L3
L1 L2
Input power 380-400 V 3N ~ 50 Hz
N
55
53
51
52
WPM
TB 05
TTW
54
2WV
6B6A 6D
6C
TF1
TB 06
565758
BH
Don't apply 220-240V or breakdown will occur.
to Outdoor unit
Sensor connection
Outdoor unit connection
Hot water cylinder power supply
–18–
Backup heater power supply
18-EN
Page 20
Hydro Unit
Installation Manual
Electrical supply/cable specifications
Wiring specifications
Description
Outdoor unit power
Hydro inlet heater power
Outdoor-Hydro unit Connection 1.5 mm² or more , ,
Hydro -Cylinder Connection 1.5 mm² or more , TB03
Power input
Power input for backup heater
Power input for cylinder heater
Model name HWS-
P1104HR-E
P804HR-E
P1104XWHM3-E
P1104XWHT6-E
P1104XWHT9-E
P804XWHM3-E
P804XWHT6-E
P804XWHT9-E
POWER SUPPLY
220-230 V ~ 50 Hz
220-230 V ~ 50 Hz
220-230V ~ 50Hz
380-400V 3N~ 50Hz
380-400V 3N~ 50Hz
220-230V ~ 50Hz
380-400V 3N~ 50Hz
380-400V 3N~ 50Hz
220-230V ~ 50Hz
Maximum current
22.8 A 25 A 2.5 mm² or more
22.8 A 25 A 2.5 mm² or more
13 A 16 A 1.5 mm² or more ,
13 A(13 A x 2P) 16 A 1.5 mm² or more
13 A(13 A x 3P) 16 A 1.5 mm² or more
13 A 16 A 1.5 mm² or more
13 A(13 A x 2P) 16 A 1.5 mm² or more
13 A(13 A x 3P) 16 A 1.5 mm² or more
12 A 16 A 1.5 mm² or more
Installation fuse rating
Power wire Connection destination
,
, , ,
,
, , ,
,
TB02
TB03
Wiring specifications (control line)
Description Line spec
Maximum current
Maximum length
3-way valve control 2 line or 3 line 100 mA 12 m 0.75 mm² or more
2-way valve control 2 line 100 mA 12 m 0.75 mm² or more , (TB05)
Mixing valve control 3 line 100 mA 12 m 0.75 mm² or more
2-zone thermo sensor 2 line 100 mA 5 m 0.75 mm² or more , (TB06)
Cylinder thermo sensor
2+GND(shielded wire)
100 mA 5 m 0.75 mm² or more , (TB06)
Second remote controller 2 line 50 mA 50 m 0.5 mm² or more , (TB07)
Connection destination
, ,
(TB05)
, ,
or
, ,
(TB04)
19-EN
–19–
Page 21
Hydro Unit
Control parts specifications
Power Maximum current Type
Motorized 3-way valve (for hot water)
Motorized 2-way valve (for cooling)
Motorized mixing valve (for 2-zone)
AC 230 V 100 mA
AC 230 V 100 mA spring return type (normally open)
AC 230 V 100 mA
Output line specifications
Installation Manual
Default: 2-wire spring return valve or 3 wire SPST valve Note: 3 wire SPDT valve can be used by changing DIP switch
13_1.
Default: Drive time = 60sec to 90° Note: 3 wire SPST or SPDT valves, with drive times between 30 and 240 seconds, can be used. Valve drive time can be changed using function code 0C
Description Output
External pump No.1 AC230V 1 A 12 m
External boost heater AC230V 1 A 12 m
Boiler control
ALARM Output
Compressor operation output
Defrost Output
Non-voltage contacts
Non-voltage contacts
Non-voltage contacts
Non-voltage contacts
Maximum current
0.5 A AC230 V 12 m Output as required when outdoor air
1 A DC24 V 12 m
0.5 A AC230 V 12 m
1 A DC24 V 12 m
0.5 A AC230 V 12 m
1 A DC24 V 12 m
0.5 A AC230 V 12 m
1 A DC24 V 12 m
Max voltage
Maximum length
Output as required when outdoor air temperature is -20°C or less
temperature is -10°C or less. The outdoor air temperature, when the boiler output is enabled, can be changed using function code 23.
Input line specifications
Description Input Maximum length
Emergency stop control Non-voltage 12 m
Cooling thermostat input Non-voltage 12 m
Heating thermostat input Non-voltage 12 m
CAUTION
Earthing arrangements
The Hydro Unit and related equipment must be earthed in accordance with your local and national electrical regulations. It is essential that the equipment is earthed to prevent the electric shock and damage to the equipment.
–20–
20-EN
Page 22
Hydro Unit
Installation Manual
Electrical connection to hydro unit
• Remove the front cover and the electrical box cover from the Hydro Unit.
• The Hydro Unit power cable must be sized in accordance with refer to “Electrical supply/cable specifications”.
• Connect the Hydro Unit power cable to Terminal 02 as shown below.
Fig. 7-21
Backup heater 220-230V ~ type (3 kW type)
Input power 220-230V 50Hz
Leakage breaker 30mA
L N L1 L2 L3 N
• Ensure the Hydro Unit power cable is secured using the cable clamp fitted in the electrical box.
• Ensure the Hydro Unit power cable connection terminals are tight.
Backup heater 380-400V 3N~ type (6,9 kW type)
Input power 220-230V 3N~ 50Hz
Leakage breaker 30mA
TB02TB02
Outdoor unit to hydro unit electrical connection
Fig. 7-22
1
Input power 220­230V~ 50Hz
Leakage breaker 30mA
L
N
Outdoor unit Hydro unit
• Ensure electrical circuits are isolated before commencing work.
• The Outdoor Unit to Hydro Unit interconnecting cable must be sized in accordance with refer to “Electrical supply/cable specifications”.
• Connect the Outdoor Unit to Hydro Unit interconnecting cable as shown in the diagram above.
• Ensure the Outdoor Unit to Hydro Unit interconnecting cable is secured using the cable clamp fitted in the electrical box.
• Ensure the Outdoor Unit to Hydro Unit interconnecting cable connection terminals are tight.
1
2
2
TB01
3
3
21-EN
–21–
Page 23
Hydro Unit
Installation Manual
Electrical connection for external booster heater
CAUTION
• The maximum current available from the booster heater output is 1 the booster heater directly to Terminal Block 05 on the Hydro Unit. A separate contactor, supplied locally, must be used to supply the booster heater.
• The booster heater can be installed only for room heating and cannot be used for hot water supply.
• Install the booster heater downstream of the 3-way valve on the indoor unit side. The booster heater is an external heater, supplied locally, used to assist the Hydro Unit during low ambient conditions.
• The AC230 be used to energize an external contactor. (Supplied locally)
• The output from the Hydro Unit is only enabled when the outdoor air temperature is less than -20°C.
• Ensure the external booster heater is installed and set up in accordance with all Local, National and International regulations.
V 1 A output from the Hydro Unit must only
• Connect the external booster heater to the Hydro Unit in accordance with the diagram shown below.
• Connect the coil, of the field supplied contactor, to terminals 5 & 6 on Terminal Block 05. The contactor will energize in the event of low ambient conditions.
• A separate dedicated electrical supply must be used for the external booster heater. This must be connected through the contacts on the field supplied contactor.
A. Do not connect
Electrical connection for external additional pumps
• The Hydro Unit has the facility to connect an additional circulating pump, if required, into the heating or cooling system.
• There is an output available from the Hydro Unit. AC230 V 1 A (maximum) is available from each output. The output for each additional pump is synchronized with the operation of the main circulating pump inside the Hydro Unit.
• Connect the additional pumps as shown in the diagram below.
• Connect external pump 1 to terminals 1 & 2 on Terminal Block 05.
• Install external pumps so that their motive power does not affect the internal pump.
Fig. 7-24
Pump
01
Terminal Block 05
1234567 8 9
Fig. 7-23
Booster Heater
1234567 8 9
Terminal Block 05
–22–
22-EN
Page 24
Hydro Unit
Installation Manual
3-way valve (diverter) connection
Required Valve Specification:
Electrical Specification: 230 V; 50 Hz; <100 mA Valve Diameters: Port A, Port B: Ø 1 1/4" Return Mechanism: 3 types of 3-way valve (diverter) can be used. Set the 3-way valve in use with the DIP switch SW13­1 on the Hydro Unit board.
SW13-1
Type 1 2-wire spring return OFF
Type 2 3-wire SPST OFF
Type 3 3-wire SPDT ON
NOTE
Continuous operation of the valve motor at the fully open position is not recommended.
• The 3-way diverter valve is used to select either domestic hot water or space heating.
• Connect the 3-way diverter valve to terminals 7, 8 and 9 on Terminal Block 05.
• Connect the 3-way diverter valve in accordance with the diagram below:
Fig. 7-25
Type 1: SPRING RETURN
port “A” to Hot water cylinder
Hydro Unit
Fig. 7-26
Type 2: SPST
port “A” to Hot water cylinder
port “AB” to Hydro unit
Fig. 7-27
Typ e 3: SPDT
port “AB” to Hydro unit
port “A” close
port “B” to Room heating or cooling
port “A” to Hot water cylinder
port “A” close
open
open
Hydro Unit
TB 05
7
8
9
Hydro Unit
TB 05
7
8
9
port “AB” to Hydro unit
port “A” open
port “B” to Room heating or cooling
7
8
9
TB 05
port “B” to Room heating or cooling
23-EN
–23–
Page 25
Hydro Unit
Installation Manual
3-way mixing valve connection
Required Actuator Specification
Electrical Specification:230 V; 50 Hz; <100 mA The 3-way mixing valve is used to achieve the temperature differential needed in a 2-zone heating system.
• Connect the 3-way mixing valve to terminals 2, 3 and 4 on Terminal Block 04 (for Type 1 mixing valve) or on terminals 1, 2 and 3 on Terminal Block 04 (for Type 2 mixing valve).
• Connect the 3-way mixing valve in accordance with the diagrams below:
Fig. 7-28
Type 1: SPDT
port “A” to Zone 2 Heating
port “AB” to Hydro unit
open
Hydro Unit TB 04
1
2
3
port “A” close
4
Hot water cylinder connection (optional)
• Please refer to “Electrical supply/cable specifications” for fuse/cable size and for connection details.
Electrical Connection (Hot Water Cylinder Electric Heater)
• The electric heater, incorporated in the hot water cylinder, requires a separate supply to Hydro Unit.
• Connect the hot water cylinder heater electrical supply in accordance with shown below: Live conductor: Terminal L on Terminal Block 03 Neutral conductor: Terminal N on Terminal Block 03 Earth Conductor: Earth terminal on Terminal Block 03
• Connect the hot water cylinder heater to the Hydro Unit as shown below: Live conductor to hot water cylinder: Terminal 1 on Terminal Block 03 Neutral conductor to hot water cylinder: Terminal 2 on Terminal Block 03 Earth conductor to hot water cylinder: Earth terminal on Terminal Block 03
Fig. 7-30
Earth leakage breaker
INPUT Power 220-230 V ~ 50 Hz
port “B” BLANK OFF
Fig. 7-29
Type 2: SPST
port “A” to Zone 2 Heating
port “AB” to Hydro unit
port “B” BLANK OFF
port “A” close
open
Hydro Unit TB 04
1
2
3
4
2
1
Hot water cylinder
12 LN
Terminal block 03
–24–
24-EN
Page 26
Hydro Unit
Installation Manual
Electrical Connection (Hot Water Cylinder temperature Sensor)
• Connect the hot water cylinder temperature sensor as shown below to terminals A & B on Terminal Block 06 in the Hydro Unit.
• Please ensure that the interconnecting cable, between the Hydro Unit and the hot water cylinder, is connected to earth at both ends of the cable using the shield wire.
Fig. 7-31
Additional hydro unit outputs
Alarm and Boiler Outputs
Alarm Output: L1: Alarm output
• Output enabled when the system is in alarm/fault condition.
• Volt free contact - specification shown below: AC230 V; 0.5 A (maximum) DC24 V; 1 A (maximum)
• Connection details: Terminals 1 and 2 (OPERATION) on MCC-1217 TB (Refer to “Fig. 7­32”)
Boiler Control Output: L2: Boiler drive permission output
• Output enabled when outdoor ambient temperature <-10°C
• Volt free contact - specification shown below: AC230 V; 0.5 A (maximum) DC24 V; 1 A (maximum)
• Connection details: Terminals 3 and 4 (EMG) on MCC-1217 TB (Refer to “Fig. 7-32”)
Fig. 7-32
Connection Cable
Hydro unit
Power Supply
L2
Power Supply
L1
Locally procured
Boiler control output
Alarm output
CN208
Hydro unit main control board
TCB-PCIN3E
Display Relay K1
PJ20
OPERATION
Display Relay K2
EMG
4
3
2
1
Defrost and Compressor operation Outputs
Defrost output
• Display relay is ON when the system defrost.
• Volt free contact AC230 V; 0.5 A (maximum) DC24 V; 1 A (maximum)
• Connection details: Terminals 1 and 2 (OPERATION) on MCC-1217 TB (Refer to “Fig. 7­33”)
25-EN
–25–
Page 27
Hydro Unit
Installation Manual
Compressor operation output
• Display relay is ON with outdoor unit compressor operation.
• Volt free contact AC230 V; 0.5 A (maximum) DC24 V; 1 A (maximum)
• Connection details: Terminals 3 and 4 (EMG) on MCC-1217 TB (Refer to “Fig. 7-33”)
Fig. 7-33
Connection Cable
CN209
Hydro unit main control board
TCB-PCIN3E
Display Relay K1
PJ20
OPERATION
Display Relay K2
EMG
4
3
2
1
Power Supply
L2
Power Supply
L1
Locally procured
Compressor operation output
Defrost output
*1:Available to change the output signal by function
code 67.
Default (FC67 = 0) Setting value (FC67 = 1)
1 - 2 = Defrost output 3 - 4 = Compressor
operation output
1 - 2 = Alarm output 3 - 4 = During operation
Optional inputs to hydro unit
Room Thermostat Input:
2–3: Room thermostat input for cooling mode 1–3: Room thermostat input for heating mode
• Output enabled when either heating or cooling mode selected on room thermostat. (locally supplied)
• Volt free contacts
• Connection details: Cooling Connection: Terminals 3 (COM) and 2 (COOL) on MCC-1214TB (Refer to “Fig. 7-34”) Heating Connection: Terminals 3 (COM) and 1 (HEAT) on MCC-1214TB (Refer to “Fig. 7-34”)
Fig. 7-34
*1
CN211
Thermostat operation
2 - 3 open close
1 - 3 close open
TCB-PCMO3E
COM
3
PJ17
COOL
HEAT
2
1
Connection Cable
Cooling Heating
on off on off
Locally procured Thermostat
Cool
Hot
CAUTION
• Be sure to prepare a non-voltage contact for each terminal.
• Display Relay capacity of “EMG” and “OPERATION”. Below AC230 V 0.5 A (COS When connecting loads such as relay coil to “L1, L2” load, insert noise surge absorber. Below DC24 V 1 A (Non-inductive load) When connecting load such as relay coil to “L1, L2” load, insert the bypass circuit.
Ø = 100 %)
CAUTION
• Be sure to prepare a non-voltage continuous contact for each terminal.
• Supplementary Insulation must be added to user touchable part of switches.
–26–
26-EN
Page 28
Hydro Unit
Installation Manual
Emergency Shutdown input
S2: Emergency stop input, Tempo* control input This function can be switched over with FC21 and FC61.
• Non-voltage contacts
• Connection details: Emergency stop, Tempo* control ON: Terminals 3 (COM) and 1 (HEAT) on MCC-1214TB (Refer to “Fig. 7-35”)
* a price contract provided by French electric power
company EDF
Hot water tank thermostat input
S1: Local hot water tank thermostat input This function is used with DIP switch 2_3 is “ON”, when
the customer use the local hot water tank. * Close: Not reached setting temperature. * Open: Reached setting temperature.
(Refer to “Fig. 7-35”)
Control of force stop and restart
S1: Hot water supply control S2: Heating control
• This function is valid only when DIP switch 2_3 is “OFF”, FC61 is set to “3” and FCB6 is set to “1”.
• Operation by external input can be switched over with FC52.
Fig. 7-35
TCB-PCMO3E
CN210
Connection Cable
PJ17
COM
3
2
1
Locally procured
S2S1
Earth continuity test
On completion of the electrical installation a resistance test should be completed on the earth conductor to ensure continuity between all pieces of equipment on the earth conductor.
Insulation resistance test
This test must be completed using a 500 V D.C. insulation resistance tester. Insulation resistance tests should be completed between each live terminal and earth.
Second remote controller
Installation place
• Install the remote controller 1 m - 1.5 m above floor level (average room temperature area).
• Do not install the remote controller in a place exposed to direct sunlight or outside air (such as a window, etc.).
• Do not install the remote controller where ventilation is poor.
• Do not install the remote controller in a freezing or refrigerated area - the remote controller is not water or splash-proof.
• Install the remote controller in a vertical position.
Remote controller installation dimension
Be sure to follow the installation dimension as shown in the figure 1 when you install the remote controller on the wall.
(mm)
120
62
18
27-EN
CAUTION
• Be sure to prepare a non-voltage continuous contact for each terminal.
• Supplementary Insulation must be added to user touchable part of switches.
Electrical safety checks
The electrical safety checks must be completed before turning on the electrical supplies to the Air to Water heat pump system. The electrical safety checks should be completed by a qualified electrician. All results measured should comply with your local/national electrical installation regulations.
–27–
120
84
Page 29
Hydro Unit
Installation Manual
Remote controller installation
NOTE
• The remote controller wire should not be bundled with other wires (mains, etc.), or installed with other wires in the same conduit, as malfunction may result.
• Install the remote controller away from sources of electrical interference and electromagnetic fields.
• If electrical interference is unavoidable, countermeasures such as appropriate filtering should be employed.
<Remote controller (Rear)>
Wiring slot
Wood screws
Remote controller wiring
Connection diagram
*Use 0.5 mm * Can not use the closed end
wire joint.
Wood screws
A
B
Terminal block (TB07) for remote controller wiring in Hydro unit
* Terminals A and B are non-
polar.
2
wire
Remote controller
A
B
Remote controller wiring (Locally procured)
Second remote controller installation requirements
Remote controller
Cover
Lower case (Rear case)
1. For removal of the remote controller’s lower case (rear case), insert the tip of a straight blade screwdriver, or the like, into the two openings at the bottom of the remote controller to open the lower case.
2. Fix the remote controller’s rear case by wood screws (2 pcs.). Do not over tighten, as it may damage the rear case.
3. Connect the wires from the Hydro unit to the remote controller terminal block. (Refer to “How to wire the remote controller”.) Connect the wires of the remote controller following the terminal numbering convention of the Hydro unit to prevent miss wiring. (Do not apply AC 208-230V mains voltage to the remote controller as it will be damaged.)
Remote controller (inside, rear)
DIP switch DIP switch DIP switch
Header remote controller/Hot water temperature
DIP switch
Header remote controller/ Room temperature
Second remote controller/Hot water temperature
Second remote controller/ Room temperature
Installation
For a dual remote controller system, install the remote controllers in the following way.
1. Set one of remote controllers as the header remote controller. (Remote controller of hydro unit is preset as Header (DIP SW1 = OFF).)
2. Set the DIP switch on all other remote controller P.C. boards to Second. (Optional remote controller is preset as Second (DIP SW1 = ON).)
–28–
28-EN
Page 30
Hydro Unit
• Set DIP SW2 to ON (Room temperature) on the remote controller which you will control the room temperature with. DIP SW2 of optional remote controller is preset to ON (Room temperature). Either one of header or second remote controller must be set as room temperature control.
• To control room temperature instead of water temperature with this remote controller, set function code “40” of hydro unit to “1”.

8 Start up and configuration

Set the DIP switches and function codes.
Setting DIP switches on the board in the Hydro Unit
Installation Manual
• Detach the front cover and the electrical control box cover of the Hydro Unit.
• Set the DIP switches on the main board.
Fig. 8-01
ON
OFF
SW No. DIP No. Description Default
Boiler install location
1
OFF = Heating side after 3 way valve ON = Before 3 way valve
2 Not Used
Used to when an external cylinder thermostat is
02
10
connected
3
OFF = No external cylinder thermostat; ON = External tank thermostat connected
Used to when an external room thermostat is connected
4
OFF = No external room thermostat; ON = External room thermostat connected
P1 Pump operation for hot water
1
OFF = synchronised with heat pump ON = Normally run
P1 Pump operation for heating
2
OFF = Normally run ON = Stopped at the outside temperature over 20°C
Synchronisation of Pump P2. OFF = P1 synchronised with pump P1
3
ON = P2 continuous operation (pump off when remote controller switched off)
Pump P1 power of regular, When long-term thermo­off.
4
OFF = None operation ON = regular power
SW10 SW11 SW12 SW13
ON
1
ON
4
3
2
3
2
1
ON
4
1
OFF
OFF
OFF
OFF
OFF
OFF
OFF
4
3
2
After
Commissioning
ON
4
3
2
1
Change 1 Change 2 Change 3
29-EN
–29–
Page 31
Hydro Unit
Installation Manual
SW No. DIP No. Description Default
Used to activate Hydro Unit back up heaters.
1
11
12
13
OFF = Back up heaters activated; ON = back up heaters de-activated
Used to activate hot water cylinder electrical heater.
2
OFF = hot water cylinder heater activated; ON = hot water cylinder heater de-activated
Used to activate external booster heater output.
3
OFF = external booster heater output activated; ON = external booster heater output de-activated
4 Not Used
Used when a hot water cylinder is connected to system.
1
OFF = hot water cylinder connected; ON = hot water cylinder not connected
Used to activate Zone 1 Operation.
2
OFF = Zone 1 activated; ON = Zone 1 de-activated
Used to activate Zone 2 Operation.
3
OFF = Zone 2 de-activated; ON = Zone activated
4 Not Used
Used to determine type of 3 way diverting valve used on system.
1
OFF = 2 wire/spring return or SPST type valve; ON = SPDT type valve
Used to activate external boiler output.
2
OFF = external boiler output de-activated; ON = external boiler output activated
Used to activate system auto restart after power failure.
3
OFF = auto restart activated; ON = auto restart de-activated
4 Not Used ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
After
Commissioning
Change 1 Change 2 Change 3
Setting DIP switches on the board in second remote controller
(option)
• Detach the front cover of the Remote controller.
• Set the DIP switches on the main board
DIP No. Description Default
Used to when a second remote controller is connected
1
OFF=Header remote controller; ON=Second remote controller
Used to determine control target when use second remote controller
2
OFF=water temperature; ON=room temperature
3 Not Used
4 Not Used
OFF –––
OFF –––
After
Commissioning
Change 1 Change 2 Change 3
–30–
30-EN
Page 32
Hydro Unit
Installation Manual
Setting function codes for
Hydro Unit and remote controller
Set function codes for various operation modes with the remote controller.
There are two types of setting.
1) Hydro Unit function code setting
2) Remote controller function code setting
Setting remote controller mode
<Setting Hydro Unit Function Code>
1 Press the TEST + SET + SELECT
buttons for four seconds or more to enter the remote controller function code setting mode.
2 Set the function code (CODE No.) with the
TEMP. buttons. (CODE No.: 01 to
13)
3 Set data (DATA) with the TIME
buttons.
4 Press the SET button to determine the
settings.
5 The CL button is enabled only before the
SET button is pressed and the function code is changed.
6 Press the TEST button to end the
settings.
2 Set the function code (CODE No.) with the
TEMP. buttons. (CODE No.: 01 to
91)
3 Set data (DATA) with the TIME
buttons.
4 Press the SET button to determine the
settings.
5 The CL button is enabled only before the
SET button is pressed and the function code is changed.
6 Press the TEST button to end the
settings.
<Setting Remote controller Function Code>
1 Press the TEST + CL + TEMP.
buttons for four seconds or more to enter the remote controller function code setting mode.
31-EN
–31–
Page 33
Hydro Unit
Installation Manual
Main setting items
(1) Setting Temperature Range (function code 18 to
1F)
• Set the temperature range for heating (zone 1, zone 2), cooling, and hot water.
• The upper-limit and lower-limit temperatures of each mode can be set.
(2) Setting Heat Pump Operation Conditions for Hot
Water Supply (function code 20 and 21)
• Set the heat pump start water temperature and heat pump stop water temperature.
• The heat pump starts working when the water temperature lowers below the set start water temperature. It is recommended that the default value be used.
(3) Compensating Hot Water Temperature
(function code 24 and 25)
• Compensate the target temperature from the remote controller set temperature when the hot water temperature lowers below the set outside air temperature.
(4) Setting Hot Water Boost (function code 08 and
09)
• Set the control time and target temperature when the HOT WATER BOOST button on the remote controller is pressed.
(5) Setting Anti-Bacteria
• Set the control for the hot water cylinder when ANTI BACTERIA is set with the remote controller.
• Set the target temperature, control period, start time (24-hour notation), and target temperature retention period.
• Make this control setting according to regulations and rules of respective countries.
(6) Setting Priority Mode Temperature
• Set the outside air temperature that changes the preferred operation mode.
• Hot Water - Heating Switching Temperature Heating operation takes precedence when the temperature lowers the set temperature.
• Boiler HP Switching Temperature When the temperature lowers the set temperature the external boiler output is made.
(7) Setting Heating Auto Mode Temperature
(function code 27 to 31, A1 to A5)
• Compensate the target temperature when Auto is set for temperature setting on the remote controller.
• The outside air temperature (T0, T1 and T3) can be set individually.
• The target temperature can be set to a value from 20 to 60°C.
• However, A > B > C > D > E.
Fig. 8-02
<Zone 1>
Default setting
(FC2C)
(FC2D)
(FC2E)
(FC2F)
(FC30)
(40)
(35)
(30)
(25)
(20)
A
B
C
D
E
T0 T1 T2
(-20)
(FCA1) (FC29) (FC2B)
Outdoor Temperature (°C)
(-10)
Auto curve shift adjust ± 5°C (FC27)
0
T3
(10)
20-25
• The entire curve can be adjusted plus and minus 5°C by function code 27.
<Zone 2>
You can choose either a percentage or a fixed value as the setting method of zone 2
FCA2 = “0” : percentage (FC31) FCA2 = “1” : fixed value (FCA3), (FCA4), (FCA5)
However, zone 1 zone 2
Auto curve shift
(FCA3)
(FCA4)
(FCA5)
(40)
(35)
(20)
A’
B’
E’
T0 T1 20-25
(-20)
(FCA1) (FC29)
Outdoor Temperature (°C)
(-10)
adjust ± 5°C (FC27)
(8) Setting Frost Protection Temperature (function
code 3A to 3B)
• Set the function when the FROST PROTECTION button on the remote controller is pressed.
• Set enabling/disabling of this function and the target water temperature.
• If disabling is set, the frost protection operation is not performed even when the FROST PROTECTION button is pressed.
(9) Setting Frequency of Output to Internal Heater
(function code 33 to 34)
• The increase/decrease time is used to set the response time.
–32–
32-EN
Page 34
Hydro Unit
Installation Manual
(10)Setting Night Setback (function code 26.
remote controller function code 0E to 0F)
• Set the function when the NIGHT button on the remote controller is pressed.
• Set enabling/disabling of this function, reduction temperature, start time, and end time.
• If disabling is set, the night setback operation is not performed even when the NIGHT button is pressed.
(12)Hydro 2-Way Diverting valve operation. control
• When using both cooling and heating operations and there is an indoor unit only for heating (such as floor heating), install the 2-way valve and set this function code.
(13)Setting 3way Valve Operation (function code
54)
• This setting is not necessary for normal installation. Make this setting to invert the logic circuit in case ports A and B of the 3-way valve are wrongly attached and it cannot be rectified on site.
(14)Mixing valve operation setting
• Set the time period from full close to full open of the 2-zone control mixing valve. Set a value that is 1/10 of the actual time. And. setting the interval control time. (minutes)
(15)Setting Heating/Hot Water Switching when
Boiler Is Used (function code 3E)
• When boiler is used, make this setting to operate the Hydro Unit by the instruction from the boiler.
(16)Setting Heat Pump Operating Time for Hot
Water Supply Operation
• Set the time period from the start of heat pump run to the start of heater energization at the beginning of hot water supply operation. If a long period is set, it takes long time for heating water.
(17)Setting Cooling ON/OFF
• Set this function when performing cooling operation.
(18)Remote controller time indication
• 24-hour or 12-hour notation is selected for the timer.
(19)Setting Nighttime Quiet Operation
• Issue an instruction for low-noise mode operation to the outdoor unit. Enabling/disabling of this function, start time, and end time can be set.
(20)Setting Alarm Tone
• The remote controller alarm tone can be set.
(21)Second Remote controller and room
temperature thermostat
• Set the initial temperature setting.
(22)Selection of mode of operation by external
input
• Select the logic of an external input signal (option)
(23)Hydro Unit Capacity setting
(24)Second Remote controller target temperature
setting
(25)Room temperature sensor setting
(26)Synchronization control at low outside
temperature
(27)P1 pump speed control
33-EN
–33–
Page 35
Hydro Unit
Function code settings
Heating Upper Limit - Zone 1 1A 37~60°C 60°C
Heating Lower Limit - Zone 1 1B 20~37°C 20
Heating Upper Limit - Zone 2 1C 37~60°C 60
Setting
1
Temperature Range
Hot Water
2
Operation
Hot Water
3
Temperature Compensation
4 Hot Water Boost
5 Anti Bacteria
6 Priority Mode
Heating Auto
7
Curve Settings
Heating Lower Limit - Zone 2 1D 20~37°C 20
Cooling - Upper Limit 18 18~30°C 25
Cooling - Lower Limit 19 7~20°C 7
Hot Water - Upper limit 1E 60~75°C 75
Hot Water - Lower limit 1F 40~60°C 40
Heat Pump Start Temperature 20 20~45°C 38
Heat Pump Stop Temperature 21 40~50°C 45
Temperature Compensation Outside Air Temperature (°C)
Compensation Temperature (°C)
Operation Time (x10 min) 08 3~18 6
Setting Temperature (°C) 09 40~75°C 75
Setting Temperature (°C) 0A 65~75°C 75
Start Cycle (Day) 0D 1~10 7
Start Time (Hour) 0C 0~23 22
Operation Time (min) 0B 0~60 30
Hot Water & Heating Switching Temperature (°C)
Boiler & Heat Pump Switching Temperature (°C)
Outside Temperature T0 (°C) A1 -30~-20°C -20
Outside Temperature T1 (°C) 29 -15~0°C -10
Outside Temperature T2 (°C) 0 0
Outside Temperature T3 (°C) 2B 0~15°C 10
Setting Temperature A at T0 (°C) - ZONE 1
Setting Temperature B at T1 (°C) - ZONE 1
Setting Temperature C at T2 (°C) - ZONE 1
Setting Temperature D at T3 (°C) - ZONE 1
Setting Temperature E at 20°C (°C) - ZONE 1
ZONE2 temperature setting 0 = Percentage (FC 31) 1 = Fixed value (FCA3~A5)
Ratio Of Zone 2 In Zone 1 Auto Mode (%)
Setting Temperature A’ at T0 (°C) - ZONE 2
Setting Temperature B’ at T1 (°C) - ZONE 2
Setting Temperature E’ at 20°C (°C) - ZONE 2
Auto Curve - Temperature Shift (°C)
Location & FC
Number
FC Description Hydro RC Range Default
24 -20~10°C 0
25 0~15°C 3
22 -20~20 0
23 -20~20 -10
2C 20~60°C 40
2D 20~60°C 35
2E 20~60°C 30
2F 20~60°C 25
30 20~60°C 20
A2 0~1 0
31 0~100% 80
A3 20~60°C 40
A4 20~60°C 35
A5 20~60°C 20
27 -5~5°C 0
After
Commissioning
Installation Manual
Change 1Change
2
–34–
34-EN
Page 36
Hydro Unit
Location & FC
Number
FC Description Hydro RC Range Default
Function 0=Invalid; 1=Valid 3A 0~1 1
Frost Protection Setting
8 Frost Protection
Back Up Heater
9
Control
10 Night Setback
Hydro 2 Way
12
Valve Operation Control
Hydro 3 Way
13
Diverting Valve Operation Control
2 Zone Mixing
14
Valve Drive Time
Boiler/Heat Pump
15
Synchronisation
Maximum Operation Time Of
16
Hot Water Heat Pump
17 Cooling Operation
Remote controller
18
Indication
CDU Night Time
19
Low Noise Operation
20 Alarm Tone Tone Switching 0=OFF; 1=ON 11 0~1 1
Second Remote controller and
21
room temperature thermostat
Temperature (°C)
Schedule date 12 0~20 0
Schedule time 13 0~23 0
Downtime Back Up Heater 0=5min; 1=10min;2=15min;3=20min
Uptime Back Up Heater 0=10min; 1=20min; 2=30min; 3=40min
Change Setback Temperature 26 3~20°C 5
Zone selection 0=Zone 1 & 2; 1= Zone 1 Only
Start Time (Hour) 0E 0~23 22
End Time (Hour) 0F 0~23 06
Cooling 2 Way Valve ­Operation Logic 0=Activated during cooling; 1=Not activated during cooling
3 Way Diverting Valve Operation Logic 0=Activated during hot water operation; 1=not activated during hot water operation
Specified Drive Time for Mixing Valve (x10sec)
Mixing valve OFF (control time
- mins)
External Boiler/Heat Pump Synchronisation 0=Synchronised; 1=Not synchronised
Maximum Heat Pump Operation Time In Hot Water Operation Priority Mode (minutes)
0=Cooloing & Heating Operation; 1=Heating Only Operation
24h or 12h Time Indication 0= 24h; 1=12h
Low Noise Operation 0=Invalid; 1=Valid
Start Time (Hour) 0A 0~23 22
End Time (Hour) 0B 0~23 06
Choice of the initial setting temperature 0=The fixed temperature by FC9D 1=The calculated temperature by Auto curve
Fixed initial temperature setting
3B 10~20°C 15
33 0~3 1
34 0~3 0
58 0~1 0
3C 0~1 0
54 0~1 0
0C 3~24 6
59 1~30 4
3E 0~1 0
07 1~120 30
02 0~1 0
–050~10
–090~10
B5 0~1 0
9D 20~60°C 40
After
Commissioning
Installation Manual
Change 1Change
2
35-EN
–35–
Page 37
Hydro Unit
Operation by
22
external input (option)
Hydro Unit
23
Capacity Setting
Second Remote controller
24
Target temperature Setting
Room
25
Temperature Sensor Setting
Synchronization control at low
26
outside temperature
P1 pump speed
27
control (duty of the PWM)
Location & FC
Number
FC Description Hydro RC Range Default
0 = Contacts low > high system stop. System restart with remote controller 1 = Contacts high > low system stop. System restart with remote controller
2 = Contacts high > low system stop. Contacts low > high system restart 3 = Contacts low > high system stop. Contacts low > high (second time) system restart
0 = Restart hot water and heating
1 = Restart in the mode when stopping 2 = Restart hot water 3 = Restart heating 4 = Tempo control 1; without heater 5 = Tempo control 2; without HP and heater
Changing the control of S1 (CN210) 0 = none 1 = Hot water supply control In addition, it is enabled only when switch 2_3 is set to “OFF” and FC61 is set to “3”.
0012 = P804XWH** 0015 = P1104XWH** Factory set but function code
is needed for PCB replacement or function code reset procedure has been completed.
0=Water temperature 1=Room thermo temperature
Temperature shift for heating 02 -10~10 -1
Temperature shift for cooling 03 -10~10 -1
0 = HP + Boiler 1 = Boiler 2 = Backup heater 3 = Boiler (Pump P1:stop)
0=100%, 1=90%, 2=80% 3=70%, 4=60%, 5=50%
52 0~3 0
61 0~5 0
B6 0~1 0
01
40 0~1 0
5B 0~3 3
A0
0012 or
0015
100% ~50%
Depends on Hydro
Unit
0
After
Commissioning
Installation Manual
Change 1Change
2
Settings by purpose
Settings when hot water supply function is not used
• When the hot water supply function is not used, set DIP SW12-1 on the Hydro Unit board to ON. (Refer to page 29.)
Setting for cooling
• For Hydro Units that do not perform cooling (those for floor heating, etc.), procure a motorized 2-way valve (for cooling) (refer to “Control parts specifications” on page 20 for the details.) locally and attach it to the water pipe that is not used for cooling. Connect the valve cables to terminals TB05 (3) and (4) of the Hydro Unit.
–36–
36-EN
Page 38
Hydro Unit
I
)
Installation Manual
• Stick the optional insulator for cooling to the bottom of the Hydro Unit.
Settings for hot water supply
• Prepare the optional hot water cylinder.
• Procure a motorized 3-way valve (refer to “Control parts specifications” on page 20 for the details.) locally and perform piping. Connect the valve cables to terminals TB05 (7), (8) and (9) of the Hydro Unit.
• Set DIP SW12-1 on the Hydro Unit board to OFF. (Refer to page 29.)
• Connect the power supply unit for the hot water cylinder heater to terminals TB03 L and N of the Hydro Unit.
• Connect cables between the Hydro Unit and the hot water cylinder as follows: Hydro Unit terminals TB03 (1), (2), and earth — Hot water cylinder (1), (2), and earth TB06 A, B, and earth — Hot water cylinder A, B, and earth
Settings for 2-zone temperature control
• Procure a motorized mixing valve (refer to “Control parts specifications” on page 20 for the details.) locally and perform piping. Connect the valve cables to terminals TB04 (1), (2), (3) and (4) of the Hydro Unit.
• Procure a buffer tank locally.
• Procure a water pump locally, and connect its cables to terminals TB05 (1) and (2) of the Hydro Unit.
To inhibit interlocking the water pump with the internal pump of the Hydro Unit, set DIP SW10-3 on the Hydro Unit board to OFF.
• Set DIP SW12-3 on the Hydro Unit board to ON. (Refer to page 29.) Attach the temperature sensor (TFI) connected to terminals TB06 C and D of the Hydro Unit near the hot water inlet of the Hydro Unit.
• Fix TFI sensor on the room heating supply pipe by using the connector procured in locally.
• Cover the cables with insulation tube (minimum 1 mm) or conduit so that the user cannot touch them directly.
• Cover the TFI sensor's cables and sensor with insulation tube (minimum 1 mm) shown in the diagram on the right.
Fig. 8-03
M
TFI
Direct Buffer tank for Under Floor Heating
Zone 2
Under-floor Heating (2-Way Valve Control)
Fig. 8-04
nsulation tube (minimum 1 mm
2 Zone hot water supply pipe
TFI Sensor
Tying up
More than 4 mm
Setting for second remote controller
• Prepare the optional second remote controller.
• Connect the cable to terminals TB07 A,B of the Hydro unit and remote controller.
• Set DIP switch1 on the second remote controller board to ON.
• <Room thermo control> Press long the TEST + SET + SELECT
switches on the remote controller to change the Hydro Unit function code, and change address 40 to 1,and then press the SET button to enable the function.
37-EN
–37–
Page 39
Hydro Unit
Installation Manual

9 Test run

Use operation buttons usually to conduct a test run. If the outside air temperature or water temperature is
outside the setting value range, press the TEST button on the remote controller and then start a test run. Since the protection setting is disabled in the TEST mode, do not continue a test run longer than 10 minutes.
• Press the TEST button on the remote controller. An indication “TEST” appears on the remote controller.
• Press the ZONE1, 2 button and select “heating” with the OPERATE MODE button. The pump is activated in 30 seconds. If air is not released completely, the flow rate switch is activated to stop operation. Release air again according to the piping procedure. Little air bite is discharged from the purge valve.
• Check that the air bite sound disappears.
• Check that the hydraulic pressure has become the predetermined pressure 0.1 to 0.2 MPa (1 to 2 bar). If the hydraulic pressure is insufficient, replenish water.
• Heating operation starts. Check that the hydro unit starts heating.
• Press the OPERATE MODE button and select “cooling.”
• Cooling operation starts. Check that the hydro unit starts cooling and that the floor heating system is not cooled.
• Press the ZONE1, 2 button to stop operation.
• Press the HOT WATER button to start hot water supply operation.
• Check that there is no air bite.
• Check that hot water is present at the connection port of the hot water cylinder.
• Press the HOT WATER button to stop the hot water supply operation.
• Press the TEST button to exit the test mode.

10Maintenance

Execute periodic maintenance at least once a year.
Check points
• Check all electrical connections and make adjustments if they are necessary.
• Check the water pipes of the heating systems in particular any evidence of leakage.
• Check the expansion tank inner pressure. If it is insufficient, enclose nitrogen or dry air in the tank.
• Check that the hydraulic pressure is 0.1 MPa (1 bar) or more with a water manometer. If it is insufficient, replenish tap water.
• Pull the lever of the pressure relief valve and check operation.
• Clean the strainer.
• Check the pump for an abnormal sound or other abnormalities.
–38–
38-EN
Page 40
Hydro Unit
Installation Manual

11Sensor temperature monitoring function

The sensor sensing temperature is displayed on the remote controller.
This function allows you to make sure whether the sensor is installed properly. Press the TEST + CL buttons for four seconds or more. Select the function code with the TEMP. buttons.
Press the TEST button to exit the test mode.
Item
code
00 Control temperature (Hot water cylinder) °C
01 Control temperature (Zone1) °C
02 Control temperature (Zone2) °C
03 Remote controller sensor temperature °C
04 Condensed temperature (TC) °C
06 Water inlet temperature (TWI) °C
07 Water outlet temperature (TWO) °C
Hydro unit data
08 Water heater outlet temperature (THO) °C
09 Floor inlet temperature (TFI) °C
0A Hot water cylinder temperature (TTW) °C
0B Mixing valve position step
0E Low pressure (Ps) × 10kPa
Data name Unit
Item
code
F0 Micro computer energized accumulation time × 100h
F1 Hot water compressor ON accumulation time × 100h
F2 Cooling compressor ON accumulation time × 100h
F3 Heating compressor ON accumulation time × 100h
Built-in AC pump operation accumulation
F4
Service data
time
Hot water cylinder heater operation
F5
accumulation time
F6 Backup heater operation accumulation time × 100h
F7 Booster heater operation accumulation time × 100h
Data name Unit
× 100h
× 100h
Item
code
60 Heat exchange temperature (TE) °C
61 Outside air temperature (TO) °C
62 Discharge temperature (TD) °C
63 Suction temperature (TS) °C
65 Heat sink temperature (THS) °C
6A Current A
6D Heat exchanger coil temperature (TL) °C
70 Compressor operation Hz Hz
Outdoor unit data
Number of revolutions of outdoor fan
72
(lower)
Number of revolutions of outdoor fan
73
(upper)
74 Outdoor PMV position × 1/10 pls
7A Discharge pressure (PD) × 10kPa
Data name Unit
rpm
rpm
39-EN
–39–
Page 41
Hydro Unit

12Troubleshooting

Fault symptoms
Symptom Possible cause Corrective action
Check remote controller operation and temperature setting
Check whether temperature sensor is installed at the normal position.
Check DIP switch setting on the Hydro Unit board. Check the setting with the function code table.
Set hydraulic pressure considering pipe height, and replenish water until manometer shows a value of set hydraulic pressure or more.
Widen water path to the hydro unit or adopt a bypass valve.
Check wiring and parts.
Set hydraulic pressure considering pipe height, and replenish water until manometer shows a value of set hydraulic pressure or more.
Check expansion tank capacity compared to total water amount. If it is insufficient, install another expansion tank.
Room is not heated or cooled.
Water is not hot enough.
Nothing is displayed on the remote controller.
Flow rate switch is activated.
Error code [A01]
Hot water leaks from pressure relief valve.
Incorrect remote controller setting
Incorrect function code setting Check function code setting with the function code table.
Backup heater disconnected Check backup heater and bimetal thermostat.
Insufficient capacity Check selection of equipment.
Sensor defect
Power is not supplied. Check power supply wiring.
Incorrect setting
Air bite in the pump Release air completely according to the procedure.
Low hydraulic pressure
Strainer is clogged. Clean the strainer.
Large resistance on the hydro side
Malfunction of motorized 3-way valve for hot water supply
Excessive hydraulic pressure
Insufficient capacity of expansion tank
Expansion tank failure Check the air pressure.
Installation Manual
Defect mode detected by the Hydro Unit
Check
code
A01
A02
A03
Pump or flowing quantity error
1) Detected by TC sensor
2)Detected by flow switch abnormality
3) Detection of chattering abnormality in the flow switch input
4) Disconnection of the flow switch connector
Temperature increase error (heating) (TWI, TWO, THO)
Temperature increase error (hot water supply)
(TTW)
Diagnostic functional operation
Operational cause
Backup present
Heating
Hot water
Heating
Hot water
Automatic
reset
1. Almost no or little water flow.
• Not enough vent air
• Dirt clogging in the water piping system.
××
O
O
×
O
O
• The water piping is too long.
• Installation of buffer tank and secondary pump
1. Disconnection of the flow switch connector.
2. Defect of the flow switch.
1. Check the water inlet, water outlet and heater outlet (TWI, TWO, THO) sensors.
2.Defect of the backup heater (defect automatic reset thermostat).
1. Check the hot water cylinder sensor (TTW).
2. Check the hot water cylinder thermal cut-out.
×
O ... Possible
× .... Not possible
Determination and action
–40–
40-EN
Page 42
Hydro Unit
Installation Manual
O ... Possible
× .... Not possible
Check
code
A04
A05
A08
A09
A10
A11
A12
E03
E04
F03
F10
F11
Diagnostic functional operation
Operational cause
Antifreeze operation
Piping antifreeze operation
Low pressure sensor operation error
Overheat protection operation
(Thermostat of the backup heater)
Antifreeze operation 2
Operation of the release protection
Heating, hot water heater error
Regular communication error between hydro unit and remote controller
Regular communication error between hydro unit and outdoor unit
TC sensor error
TWI sensor error
TWO sensor error
Backup present
O
Automatic
reset
×
OO
O
O
×
×
××
Heating Cooling
×
Hot water
O
OO
×
× O
OO
OO
OO
× O
Determination and action
1. Almost no or little water flow.
• Dirt clogging in the water piping system.
• The water piping is too long or too short.
2. Check the heater power circuit.
• Power supply voltage, breaker, power supply
connection
3. Set the presence of the backup heater.
4. Check the water inlet, water outlet and heat exchange (TWI, TWO, TC) sensors and Flow Switch.
1. Check the heater power circuit.
• Power supply voltage, breaker, power supply
connection
2. Check the water inlet, water outlet and heater outlet sensors (TWI, TWO, THO).
3. Disconnection of the backup heater.
1. Almost no or little water flow.
2. Defect of the flow switch.
3. On-load cooling or prolonged defrosting (a lot of frost formation) under the above conditions.
4. Defect in the low pressure sensor.
5. Check the refrigeration cycle (gas leak).
1. No water (heating without water) or no water flow.
2. Defect of the flow switch.
3. Defect of the backup heater (poor automatic reset thermostat).
1. Almost no or little water flow.
2. Check the water inlet, water outlet and heat exchange (TWO, TC) sensors.
1. Almost no water flow.
2. Defect of the flow switch.
3. Check the water outlet temperature sensor (TWO).
1. Activated by a large load of heating or hot water supply.
2. Check the heater power circuit (backup or hot water cylinder heater).
• Power supply voltage, breaker, power supply
connection
1. Check remote controller connection.
2. Defect in the remote controller.
1. Check the serial circuit.
• Miswiring of the crossover between the hydro unit and
the outdoor unit
1. Check the resistance value and connection of the heat exchange temperature sensor (TC).
1. Check the resistance value and connection of the water inlet temperature sensor (TWI).
1. Check the resistance value and connection of the water outlet temperature sensor (TWO).
41-EN
–41–
Page 43
Hydro Unit
Installation Manual
O ... Possible
× .... Not possible
Check
code
TTW sensor error
F14
TFI sensor error
F17
THO sensor error
F18
Detection of THO disconnection
F19
error
TFI sensor error
F20
Low pressure sensor error
F23
F29 EEROM error
F30 Extended IC error
L02 Combination error
L07 Communication error
Communication error
L09
Setting error
L16
When ZONE1 has not been set, while ZONE2 has been set.
Diagnostic functional operation
Operational cause
Backup present
Automatic
reset
× O
× O
× O
××
××
OO
1. Check the resistance value and connection of the hot water cylinder sensor (TTW).
1. Check the resistance value and connection of the floor-inlet temperature sensor (TFI).
1. Check the resistance value and connection of the heater outlet temperature sensor (THO).
1. Check for any disconnection of the heater outlet temperature sensor (THO).
1. Check the connection of the floor-inlet temperature sensor (TFI).
1. Check the connection (body or connection wiring) of the low pressure sensor.
2. Check the resistance value of the low pressure sensor.
Determination and action
××1. Replace the P.C. board. (Hydro unit) ××1. Replace the P.C. board. (Hydro unit) ××1. Check the model name of the outdoor unit. ××1. Replace the P.C. board. (Hydro unit)
1. Check the setting of the FC01 capability
××
specifications.
HWS-P804xx-E = 0012
HWS-P1104xx-E = 0015
××1. Check the body DP-SW12_2,3.
Defect mode detected by the Outdoor Unit
Check
code
TD sensor error
F04
TE sensor error
F06
TL sensor error
F07
TO sensor error
F08
TS sensor error
F12
TH sensor error
F13
TE, TS sensors error
F15
PD sensor error
F24
F31 EEPROM error O
Diagnostic functional operation
Operational cause
Backup present
O ×
O
O ×
O ×
O ×
O ×
O
O
Automatic
reset
×
×
×
×
Determination and action
1. Check the resistance value and connection of the discharge sensor (TD).
1. Check the resistance value and connection of the heat exchange temperature sensor (TE).
1. Check the resistance value and connection of the heat exchange temperature sensor (TL).
1. Check the resistance value and connection of the outdoor temperature sensor (TO).
1. Check the resistance value and connection of the suction temperature sensor (TS).
1. Check the resistance value and connection of the heat-sink temperature sensor (TH).
1. Check for any wrong installation of the heat exchange temperature sensor (TE) and the suction temperature sensor (TS).
1. Check the value of PD sensor by the remote controller.
–42–
42-EN
Page 44
Hydro Unit
Installation Manual
Check
code
Compressor breakdown
H01
Compressor lock
H02
Defect in the current detection
H03
circuit
Operation of case thermostat
H04
Unset service PC board jumper
L10
Jumpers have not been cut.
L15 Combination error O
The communication between the
L29
outdoor PC board MUCs error
The outlet temperature error
P03
P04 The high pressure switch error O P05 The power supply voltage error O × 1. Check the power supply voltage.
Overheating of heat-sink error
P07
Detection of gas leak
P15
Diagnostic functional operation
Operational cause
Backup present
O ×
O
O
O
O
O
O
O
O ×
Automatic
Determination and action
reset
1. Check the power supply voltage.
2. Over-loaded condition of the refrigeration cycle.
3. Check that the service valve is fully open.
1. Defect of compressor (lock)
×
– Replace the compressor.
2. Defect of compressor wiring (open phase).
× 1. Replace the outdoor inverter control board.
1. Check the refrigeration cycle (gas leak).
2. Check the case thermostat and connector.
×
3. Check that the service valve is fully open.
4. Defect of the pulse motor valve.
5. Check for kinked piping.
× 1. Cut outdoor PC board jumper wire (for service).
× 1. Check the model name of the hydro unit.
× 1. Replace the outdoor control board.
1. Check the refrigeration cycle (gas leak).
×
2. Defect of the pulse motor valve.
3. Check the resistance value of the discharge temperature sensor (TD).
×
1. Check the thread fastening and heat-sink grease between the outdoor control board and the heat-sink.
×
2. Check the heat-sink fan duct.
3. Check the resistance value of the heat-sink temperature sensor (TH).
1. Check the refrigeration cycle (gas leak).
2. Check that the service valve is fully open.
3. Defect of the pulse motor valve.
4. Check for kinked piping.
5. Check the resistance value of the discharge temperature sensor (TD), the suction temperature sensor (TS).
6. Check the value of PD sensor by the remote controller.
43-EN
–43–
Page 45
Hydro Unit
Installation Manual
Check
code
P19
P20
P22
P26
P29
Diagnostic functional operation
Operational cause
The 4-way valve inversion error
High pressure protection operation
Outdoor fan system error
Short circuit of the compressor driver element error
Compressor rotor position error
Backup present
O ×
O
O
O
O
Automatic
reset
×
×
×
×
Determination and action
1. Check the operation of the 4-way valve unit or the coil characteristics.
2. Defect of the pulse motor valve.
3. Check the resistance value of the heat exchange temperature sensor (TE) and the suction temperature sensor (TS).
1. Check that the service valve is fully open.
2. Defect of the pulse motor valve.
3. Check the outdoor fan system (including clogging).
4. Over-filling of refrigerant.
5. Check the resistance value of the heat exchange temperature sensor (TL) and the water outlet temperature sensor (TWO).
6. Check the value of PD sensor by the remote controller.
1. Check the lock status of the motor fan.
2. Check the connection of the fan motor cable connector.
3. Check the power supply voltage.
1. Abnormality occurs when operating with the compressor wiring disconnected … Check the control board.
2. No abnormality occurs when operating with the compressor wiring disconnected … Compressor rare short.
1. Even if the connection lead wire of the compressor is disconnected, it stops due to an abnormality in the position detection … Replace the inverter control board.
2. Check the wire wound resistor of the compressor. Short circuit … Replace the compressor.
–44–
44-EN
Page 46
Hydro Unit
Defect mode detected by the remote controller
Diagnostic functional operation
Check code
Not
displaying at
all
(cannot operate by the remote
controller)
E01
E02
E09
Operational cause
No communication between hydro unit an remote controller
No communication between hydro unit and remote controller
Defect in the signal transmission to the hydro unit.
(Detected on the remote controller side)
Several remote controller base units
(Detected on the remote controller side)
Status of air­conditioning
Stop Defect in the remote controller power
Stop (Automatic reset)
Stop (Automatic reset)
Stop (The handset continues)
Condition
Displayed when the abnormality is detected.
Displayed when the abnormality is detected.
Displayed when the abnormality is detected.
Installation Manual
Determination and action
supply
1. Check the remote controller wiring.
2. Check the remote controller.
3. Check the hydro unit power supply wiring.
4. Check the water heat exchange control board.
Defect in the reception of the remote controller
1. Check the remote controller crossover.
2. Check the remote controller.
3. Check the hydro power supply wiring.
4. Check the water heat exchanger board.
Defect in the transmission of the remote controller
1. Check the transmitter circuit inside the remote controller.
… Replace the remote controller.
1.2 Check several base units with the
remote controller
… The base unit is only one, and others
are handsets.
45-EN
–45–
Page 47
EF99808601
Loading...