Toshiba HFC R-410A User Manual

Ref.-No. SMMS01-AE-01-05
4-way ceiling cassette MMU-AP0091H, AP0121H, AP0151H,
MMU-AP0181H, AP0241H, AP0271H, MMU-AP0301H, AP0361H, AP0481H MMU-AP0561H
Indoor unit
2-way ceiling cassette MMU-AP0071WH, AP0091WH, AP0121WH,
MMU-AP0151WH, AP0181WH, AP0241WH, MMU-AP0271WH, AP0301WH
MMU-AP0151SH, AP0181SH, AP0241SH
Standard ducted unit MMD-AP0071BH, AP0091BH, AP0121BH,
MMD-AP0151BH, AP0181BH, AP0241BH, MMD-AP0271BH, AP0301BH, AP0361BH, MMD-AP0481BH, AP0561BH
High-pressure ducted unit MMD-AP0181H, AP0241H, AP0271H,
MMD-AP0361H, AP0481H, AP0721H, MMD-AP0961H
Super Modular Multi
Design Manual
HFC R-410A
Slim duct unit MMD-AP0071SPH, AP0091SPH, MMD-AP0121SPH, AP0151SPH, MMD-AP0181SPH
Ceiling-suspended unit MMC-AP0151H, AP0181H, AP0241H,
MMC-AP0271H, AP0361H, AP0481H
High-wall unit MMK-AP0071H, AP0091H, AP0121H,
MMK-AP0151H, AP0181H, AP0241H
MMK-AP0072H, AP0092H, AP0122H
Floor-mounted console unit MML-AP0071H, AP0091H, AP0121H,
MML-AP0151H, AP0181H, AP0241H
Concealed chassis unit MML-AP0071BH, AP0091BH, AP0121BH,
MML-AP0151BH, AP0181BH, AP0241BH
Floor-mounted cabinet unit MMF-AP0151H, AP0181H, AP0241H
MMF-AP0271H, AP0361H, AP0481H MMF-AP0561H
COOLING ONLY MODEL
Outdoor unit
Inverter unit MMY-MAP0501T8, MAP0601T8 MMY-MAP0801T8, MAP1001T8 MMY-MAP1201T8
HEAT PUMP MODEL
Inverter unit MMY-MAP0501HT8, MAP0601HT8 MMY-MAP0801HT8, MAP1001HT8 MMY-MAP1201HT8
Super Modular Multi System
Contents
1. Outline of Toshiba Super Modular Multi System (S-MMS) .................................................................................. 4
2. Summary of system equipment ........................................................................................................................... 7
3. Basic system configuration .................................................................................................................................. 13
4. Equipment selection procedure ........................................................................................................................... 19
5. Refrigerant piping design ..................................................................................................................................... 29
6. Wiring design ....................................................................................................................................................... 34
7. Controls ................................................................................................................................................................ 39
8. Accessories .......................................................................................................................................................... 45
9. Technical specifications ....................................................................................................................................... 46
10. Fan characteristics ............................................................................................................................................... 69
11. Dimensional drawings .......................................................................................................................................... 75
This manual is used for both cooling only and heat pump models.
3
1. Outline of Toshiba Super Modular Multi System (S-MMS)
Branching
Combination of line and header branching is highly flexible. This allows for the shortest design route possible, thereby saving on installation time and cost. Line/header branching after header branching is only available with Toshiba Super MMS.
Line branching
Outdoor unit
Branching joint
Indoor unit
Header branching
Outdoor unit
8F
Branching header
Indoor unit
Line and header branching
Outdoor unit
Branching joint
Indoor unit
Header
Line branching after header branching
Outdoor unit
Header
Super MMS
only
Indoor unit
7F
2F
1F
Branching joint
Header branching after header branching
Super MMS
Outdoor unit
Header
only
Header
Indoor unit
4
8F
Non-polarized control wiring between outdoor and indoor units
Outdoor unit
Indoor unit
Wiring diagnosis system
Use the switches on the micro
processor PCB of the outdoor unit.
Detects wiring to the indoor unit a4
which should not be in system A.
b4 is missing in system B.
7F
2F
A system
B system
Outdoor unit
Wiring
Outdoor unit
Height difference between
Height difference between
indoor and outdoor unit: 50 m
Piping
Outdoor unit
indoor units: 30 m
Indoor unit
Allowable pipe length: 175 m equivalent length
1st branching section
1F
From 1st branching to the farthest indoor unit: 65 m
5
Compact
The design of the modular Toshiba Super MMS outdoor unit allows for easy unit manoeuvring into
any standard lift. Its compactness also allows it to be easily installed in limited spaces.
Largest system capacity
Toshiba Super MMS can be combined up to 48 hp (135 kW) as one refrigerant system.
Energy saving design
The units have the best energy efficiency ratio of any VRF unit. Compared with a conventional chiller
fan coil system, a large energy saving can be realized.
Advanced bus communication system
Wiring between indoor and outdoor units is a simple 2-wire system. The communication address is also automatically configured. A default test mode operation is available.
Self-diagnostic system
Comprehensive troubleshooting code enables quick identification of problems arising.
High lift design
An equivalent pipe length of 175 m and vertical lift of 50 m are possible with the Toshiba Super
MMS. The vertical lift between indoor units of 30 m is the highest in the industry. This allows for greater flexibility in the location of the system.
Multiple indoor units
Indoor units with different capacities and configurations can be combined up to 135% of the
outdoor unit capacity. A maximum of 48 indoor units can be combined with the 30-48 hp outdoor units.
Intelligent control
Toshiba Super MMS intelligent controls and modulating valves deliver the required capacity, in
accordance with the load variation from 50% to 100%. The intelligent controls and modulating valves limit or increase the cooling capacity dynamically so
humidity and temperature are kept in the comfort zone.
Wide control applications
Artificial Intelligence Network system
Central control and monitoring system available
Weekly schedule operation through weekly timer
Integration with a Building Management System (BMS) is available.
6
2. Summary of system equipment
Technical specifications - outdoor units
Rating hp 5 6 8 10 12 Cooling only model MMY-MAP 0501T8 0601T8 0801T8 1001T8 1201T8 Heat pump model MMY-MAP 0501HT8 0601HT8 0801HT8 1001HT8 1201HT8
Cooling capacity kW 14.0 16.0 22.4 28.0 33.5 Heating capacity kW 16.0 18.0 25.0 31.5 37.5
Technical specifications - combination of outdoor units
Rating hp 5 6 8 10 12 14 16 Cooling only model MMY-MAP 0501T8 0601T8 0801T8 1001T8 1201T8 1401T8 1601T8 Heat pump model MMY-MAP 0501HT8 0601HT8 0801HT8 1001HT8 1201HT8 1401HT8 1601HT8
Cooling capacity kW 14.0 16.0 22.4 28.0 33.5 38.4 45.0 Heating capacity kW 16.0 18.0 25.0 31.5 37.5 43.0 50.0 Combined outdoor units hp 5 6 8 10 12 8 8
- - - - - 6 8
No. of connectable indoor units 8 10 13 16 20 23 27
Rating hp 18 20 22 22 24 24 26 Cooling only model MMY-MAP 1801T8 2001T8 2201T8 2211T8 2401T8 2411T8 2601T8 Heat pump model MMY-MAP 1801HT8 2001HT8 2201HT8 2211HT8 2401HT8 2411HT8 2601HT8
Cooling capacity kW 50.4 56.0 61.5 61.5 68.0 68.0 73.0 Heating capacity kW 56.5 63.0 69.0 69.0 76.5 76.5 81.5 Combined outdoor units hp 10 10 8 12 8 12 10 8 10 8 10 8 12 8
- - 6 - 8 - 8
No. of connectable indoor units 30 33 37 37 40 40 43
Rating hp 28 30 32 32 34 34 36 Cooling only model MMY-MAP 2801T8 3001T8 3201T8 3211T8 3401T8 3411T8 3601T8 Heat pump model MMY-MAP 2801HT8 3001HT8 3201HT8 3211HT8 3401HT8 3411HT8 3601HT8
Cooling capacity kW 78.5 84.0 90.0 90.0 96.0 96.0 101.0 Heating capacity kW 88.0 95.0 100.0 100.0 108.0 108.0 113.0 Combined outdoor units hp 10 10 8 12 10 12 10 10 10 8 10 8 12 10 8 10 8 10 8 10 8
- - 8 - 8 - 8
No. of connectable indoor units 47 48 48 48 48 48 48
Rating hp 36 38 40 42 44 46 48 Cooling only model MMY-MAP 3611T8 3801T8 4001T8 4201T8 4401T8 4601T8 4801T8 Heat pump model MMY-MAP 3611HT8 3801HT8 4001HT8 4201HT8 4401HT8 4601HT8 4801HT8
Cooling capacity kW 101.0 106.5 112.0 118.0 123.5 130.0 135.0 Heating capacity kW 113.0 119.5 126.5 132.0 138.0 145.0 150.0 Combined outdoor units hp 12 10 10 12 12 12 12 12 10 10 10 12 12 12 12 10 10 10 10 12 12
- 8 10 10 10 10 12
No. of connectable indoor units 48 48 48 48 48 48 48
Branching joints and headers
Model Usage Appearance
Y-shape branching joint (*3) RBM-BY53E Indoor unit capacity code (*1) : Total below 6.4 RBM-BY103E Indoor unit capacity code (*1) : Total 6.4 or more and below 14.2 (*2) RBM-BY203E Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2 (*2) RBM-BY303E Indoor unit capacity code (*1) : Total 25.2 or more (*2) 4-branching header (*4) RBM-HY1043E Indoor unit capacity code (*1) : Total below 14.2 Max.4 RBM-HY2043E Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2 branches 8-branching header (*4) (*5) RBM-HY1083E Indoor unit capacity code (*1) : Total below 14.2 Max.8 RBM-HY2083E Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2 branches T-shape branching joint RBM-BT13E 1 set of 3 types of T-shape joint pipes as described below: (For connection of The required quantity is arranged and they are combined at the site. outdoor units) Connection piping Corresponding dia. (mm) Q’ty Balance pipe Ø3/8” 1 Liquid side piping Ø3/8” to Ø7/8” 1 Gas side piping Ø5/8” to Ø1-5/8” 1
*1 The capacity code can be obtained from page 10 (capacity code is not actual capacity). *2 If total capacity code value of indoor unit exceeds that of outdoor unit, apply capacity code of outdoor unit. *3 When using Y-shape branching joint for 1st branching, select according to capacity code of outdoor unit. *4 Max. 6.0 capacity code in total can be connected. *5 If capacity code of outdoor unit is 26 and more, it is not used for 1st branching. *6 Model names for outdoor and indoor units described in this guide are shortened because of the space constraints.
7
Outdoor unit model line-up - cooling only units
hp Model No. of Inverter Q’ty Inverter Q’ty Inverter Qty Inverter Q’ty Inverter Q’ty (capacity MMY- combined 5 hp used 6 hp used 8 hp used 10 hp used 12 hp used code) units MMY- MMY- MMY- MMY- MMY-
5 hp (5) MAP0501T8 1 MAP0501T8 1 6 hp (6) MAP0601T8 1 MAP0601T8 1 8 hp (8) MAP0801T8 1 MAP0801T8 10 hp (10) MAP1001T8 1 MAP1001T8 1 12 hp (12) MAP1201T8 1 MAP1201T8 1 14 hp (14) AP1401T8 2 MAP0601T8 1 MAP0801T8 16 hp (16) AP1601T8 2 MAP0801T8 2 18 hp (18) AP1801T8 2 MAP0801T8 1 MAP1001T8 1 20 hp (20) AP2001T8 2 MAP1001T8 2 22 hp (22) AP2201T8 3 MAP0601T8 1 MAP0801T8 2 22 hp (22) AP2211T8 2 MAP1001T8 1 MAP1201T8 1 24 hp (24) AP2401T8 3 MAP0801T8 3 24 hp (24) AP2411T8 2 MAP1201T8 2 26 hp (26) AP2601T8 3 MAP0801T8 2 MAP1001T8 1 28 hp (28) AP2801T8 3 MAP0801T8 1 MAP1001T8 2 30 hp (30) AP3001T8 3 MAP1001T8 3 32 hp (32) AP3201T8 4 MAP0801T8 4 32 hp (32) AP3211T8 3 MAP1001T8 2 MAP1201T8 1 34 hp (34) AP3401T8 4 MAP0801T8 3 MAP1001T8 1 34 hp (34) AP3411T8 3 MAP1001T8 1 MAP1201T8 2 36 hp (36) AP3601T8 4 MAP0801T8 2 MAP1001T8 2 36 hp (36) AP3611T8 3 MAP1201T8 3 38 hp (38) AP3801T8 4 MAP0801T8 1 MAP1001T8 3 40 hp (40) AP4001T8 4 MAP1001T8 4 42 hp (42) AP4201T8 4 MAP1001T8 3 MAP1201T8 1 44 hp (44) AP4401T8 4 MAP1001T8 2 MAP1201T8 2 46 hp (46) AP4601T8 4 MAP1001T8 1 MAP1201T8 3 48 hp (48) AP4801T8 4 MAP1201T8 4
1. Product designation
MMY- M AP 000 0 T 8
8: Power supply, 3 ph, 380-415 V, 50 Hz
T: Inverter unit
Development series number
Model size hp x 10
New refrigerant R-410A
M: Single module unit. No mark: Combined model name
Super Modular Multi
2. Combined capacity range
No. of combined units: 1 to 4 units
Capacity of combined units: 14 hp (140 type) to 48 hp (480 type)
3. Rated conditions
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db.
8
Outdoor unit model line-up - heat pump units
hp Model No. of Inverter Q’ty Inverter Q’ty Inverter Qty Inverter Q’ty Inverter Q’ty (capacity MMY- combined 5 hp used 6 hp used 8 hp used 10 hp used 12 hp used code) units MMY- MMY- MMY- MMY- MMY-
5 hp ( 5) MAP0501HT8 1 MAP0501HT8 1 6 hp ( 6) MAP0601HT8 1 MAP0601HT8 1 8 hp ( 8) MAP0801HT8 1 MAP0801HT8 1 10 hp (10) MAP1001HT8 1 MAP1001HT8 1 12 hp (12) MAP1201HT8 1 MAP1201HT8 1 14 hp (14) AP1401HT8 2 MAP0601HT8 1 MAP0801HT8 1 16 hp (16) AP1601HT8 2 MAP0801HT8 2 18 hp (18) AP1801HT8 2 MAP0801HT8 1 MAP1001HT8 1 20 hp (20) AP2001HT8 2 MAP1001HT8 2 22 hp (22) AP2201HT8 3 MAP0601HT8 1 MAP0801HT8 2 22 hp (22) AP2211HT8 2 MAP1001HT8 1 MAP1201HT8 1 24 hp (24) AP2401HT8 3 MAP0801HT8 3 24 hp (24) AP2411HT8 2 MAP1201HT8 2 26 hp (26) AP2601HT8 3 MAP0801HT8 2 MAP1001HT8 1 28 hp (28) AP2801HT8 3 MAP0801HT8 1 MAP1001HT8 2 30 hp (30) AP3001HT8 3 MAP1001HT8 3 32 hp (32) AP3201HT8 4 MAP0801HT8 4 32 hp (32) AP3211HT8 3 MAP1001HT8 2 MAP1201HT8 1 34 hp (34) AP3401HT8 4 MAP0801HT8 3 MAP1001HT8 1 34 hp (34) AP3411HT8 3 MAP1001HT8 1 MAP1201HT8 2 36 hp (36) AP3601HT8 4 MAP0801HT8 2 MAP1001HT8 2 36 hp (36) AP3611HT8 3 MAP1201HT8 3 38 hp (38) AP3801HT8 4 MAP0801HT8 1 MAP1001HT8 3 40 hp (40) AP4001HT8 4 MAP1001HT8 4 42 hp (42) AP4201HT8 4 MAP1001HT8 3 MAP1201HT8 1 44 hp (44) AP4401HT8 4 MAP1001HT8 2 MAP1201HT8 2 46 hp (46) AP4601HT8 4 MAP1001HT8 1 MAP1201HT8 3 48 hp (48) AP4801HT8 4 MAP1201HT8 4
1. Product designation
MMY- M AP 000 0 H T 8
8: Power supply, 3 ph, 380-415 V, 50 Hz
T: Inverter unit
H: Heat pump
Development series number
Model size hp x 10
New refrigerant R-410A
M: Single module unit. No mark: Combined model name
Super Modular Multi
2. Combined capacity range
No. of combined units: 1 to 4 units
Capacity of combined units: 14 hp (140 type) to 48 hp (480 type)
3. Rated conditions
Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db. Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb
9
4. Technical specifications - indoor units
Model type Model Capacity Cooling Heating Height Width Depth Weight name code capacity capacity mm mm mm kg kW kW 4-way ceiling cassette MMU-AP0091H 1 2.8 3.2 256 840 840 20
MMU-AP0121H 1.25 3.6 4.0 MMU-AP0151H 1.7 4.5 5.0 256 840 840 22 MMU-AP0181H 2 5.6 6.3 MMU-AP0241H 2.5 7.1 8.0 256 840 840 23 MMU-AP0271H 3 8.0 9.0 MMU-AP0301H 3.2 9.0 10.0 MMU-AP0361H 4 11.2 12.5 319 840 840 28 MMU-AP0481H 5 14.0 16.0 MMU-AP0561H 6 16.0 18.0 2-way ceiling cassette MMU-AP0071WH 0.8 2.2 2.5 398 830 550 33 MMU-AP0091WH 1 2.8 3.2 MMU-AP0121WH 1.25 3.6 4.0 MMU-AP0151WH 1.7 4.5 5.0 398 1350 550 44 MMU-AP0181WH 2 5.6 6.3 MMU-AP0241WH 2.5 7.1 8.0 398 1350 550 48 MMU-AP0271WH 3 8.0 9.0 MMU-AP0301WH 3.2 9.0 10.0 MMU-AP0481WH 5 14.0 16.0 406 1650 620 52 1-way ceiling cassette MMU-AP0071YH 0.8 2.2 2.5 235 850 400 22 MMU-AP0091YH 1 2.8 3.2 MMU-AP0121YH 1.25 3.6 4.0 MMU-AP0151SH 1.7 4.5 5.0 198 1100 655 27 MMU-AP0181SH 2 5.6 6.3 MMU-AP0241SH 2.5 7.1 8.0 198 1200 655 31 Standard ducted unit MMD-AP0071BH 0.8 2.2 2.5 320 550 800 27 MMD-AP0091BH 1 2.8 3.2 MMD-AP0121BH 1.25 3.6 4.0 MMD-AP0151BH 1.7 4.5 5.0 320 700 800 30 MMD-AP0181BH 2 5.6 6.3 MMD-AP0241BH 2.5 7.1 8.0 320 1000 800 39 MMD-AP0271BH 3 8.0 9.0 MMD-AP0301BH 3.2 9.0 10.0 MMD-AP0361BH 4 11.2 12.5 320 1350 800 51 MMD-AP0481BH 5 14.0 16.0 MMD-AP0561BH 6 16.0 18.0 High-pressure ducted unit MMD-AP0181H 2 5.6 6.3 380 850 660 50 MMD-AP0241H 2.5 7.1 8.0 380 850 660 52 MMD-AP0271H 3 8.0 9.0 MMD-AP0361H 4 11.2 12.5 380 850 660 56 MMD-AP0481H 5 14.0 16.0 380 1200 660 67 MMD-AP0721H 8 22.4 25.0 470 1380 1250 155 MMD-AP0961H 10 28.0 31.5 Slim duct unit MMD-AP0071SPH 0.8 2.2 2.5 210 845 645 22 MMD-AP0091SPH 1 2.8 3.2 22 MMD-AP0121SPH 1.25 3.6 4.0 22 MMD-AP0151SPH 1.7 4.5 5.0 23 MMD-AP0181SPH 2 5.6 6.3 23 Ceiling-suspended unit MMC-AP0151H 1.7 4.5 5.0 210 910 680 21 MMC-AP0181H 2 5.6 6.3 MMC-AP0241H 2.5 7.1 8.0 210 1180 680 25 MMC-AP0271H 3 8.0 9.0 MMC-AP0361H 4 11.2 12.5 210 1595 680 33 MMC-AP0481H 5 14.0 16.0 High-wall unit MMK-AP0071H 0.8 2.2 2.5 368 895 210 18 MMK-AP0091H 1 2.8 3.2 MMK-AP0121H 1.25 3.6 4.0 MMK-AP0151H 1.7 4.5 5.0 368 1055 210 19 MMK-AP0181H 2 5.6 6.3 MMK-AP0241H 2.5 7.1 8.0 368 1430 210 25 MMK-AP0072H 0.8 2.2 2.5 275 790 208 11 MMK-AP0092H 1.0 2.8 3.2 MMK-AP0122H 1.25 3.6 4.0
Floor-mounted console unit MML-AP0071H 0.8 2.2 2.5 630 950 230 37 MML-AP0091H 1 2.8 3.2 MML-AP0121H 1.25 3.6 4.0 MML-AP0151H 1.7 4.5 5.0 MML-AP0181H 2 5.6 6.3 MML-AP0241H 2.5 7.1 8.0 630 950 230 40 Concealed chassis unit MML-AP0071BH 0.8 2.2 2.5 600 745 220 21 MML-AP0091BH 1 2.8 3.2 MML-AP0121BH 1.25 3.6 4.0 MML-AP0151BH 1.7 4.5 5.0 600 1045 220 29 MML-AP0181BH 2 5.6 6.3 MML-AP0241BH 2.5 7.1 8.0 Floor-mounted cabinet unit MMF-AP0151H 1.7 4.5 5.0 1750 600 210 48 MMF-AP0181H 2 5.6 6.3 MMF-AP0241H 2.5 7.1 8.0 1750 600 210 49 MMF-AP0271H 3 8.0 9.0 MMF-AP0361H 4 11.2 12.5 1750 600 390 65 MMF-AP0481H 5 14.0 16.0 MMF-AP0561H 6 16.0 18.0
10
5. Remote controller
Appearance Application Function
Wired remote controller
• Mode change RBC-AMT31E • Temperature adjustment
• Air flow adjustment
• Timer function  Three options are available:
To use, choose one of these options and
• Filter maintenance time Automatically displays the maintenance
Filter LED flashes.
• Self-diagnosis function Pressing the ‘CHECK’ button displays the
• Two controlling positions are available. Two remote controllers can be connected
Simplified remote controller Connected to indoor unit • Start/stop
• Temperature adjustment RBC-AS21E • Air flow adjustment
• Check code display
Connected to indoor unit • Start/stop
On after selected time (one cycle) Off after selected time (one cycle) Off after selected time (re-occurring)
the time delay before it occurs (minimum period is 0.5 hours). Combined with the weekly timer a
weekly operating schedule can be set.
Wired remote controller
Wired remote controller (for control with two controlling positions)
time of the indoor filter.
problem cause using a check code.
to one indoor unit. The indoor unit can then be operated from two separate locations.
Simplified remote controller
Wireless remote controller kit Connected to indoor unit • Start/stop
• Mode change
TCB-AX21U (W)-E • Temperature adjustment RCB-AX22CE • Air flow adjustment TCB-AX21E • Timer function
Three options are available: On after selected time (one cycle) Off after selected time (one cycle)
To use, choose one of these options and
• Two controlling positions are available. Two wireless remote controllers can be
• Check code display.
(For 4-way ceiling cassette)
(For ceiling-suspended unit)
(For all units except high-pressure ducted units)
Off after selected time (re-occurring)
the time delay before it occurs (minimum period is 0.5 hours).
connected to one indoor unit. The indoor unit can then be operated from two separate locations.
TCB-AX21U (W)-E
RBC-AX22CE
TCB-AX21E
11
Appearance Application Function
Infrared remote controller
• Mode change
WH-H2UE • Temperature adjustment
• Air flow adjustment (5 steps)
• Clock
• Timer function
- ON/OFF timer (10 min. steps)
- Daily timer
• High power mode
• ECO mode (sleep timer with ECO-logic)
• One-touch pre-set memory
Weekly timer Connected to central remote • Weekly schedule operation controller, wired remote controller
RBC-EXW21E of the week
Connected to indoor unit • Start/stop
Setting start/stop times for each day
ON/OFF can be set 3 times a day.
 Press ‘CANCEL’ ‘DAY’ button for easy
Central remote controller Connected to outdoor unit, • Individual control of up to 64 indoor units
TCB-SC642TLE divided into 1 to 4 zones.
Up to 16 indoor units for each zone.
• Up to 16 outdoor master units are
• 4 central control setting types to inhibit
• Setting for one of 1 to 4 zones is available.
• Usable with other central control devices
• Two control mode choices
Centrol controller mode Remote controller mode
• Settings of simultaneous ON/OFF 3 times
Wired remote controller
Outdoor unit
Central remote controller
indoor unit • Individual control of max. 64 indoor units
Master
Outdoor unit
Central remote controller
Weekly timer
Weekly timer
Slave
Press ‘CHECK’ ‘PROGRAM’ ‘DAY’
button for easy program copying.
Two schedules a week can be
specified (summer/winter schedule).
holiday override setting.
If power supply fails, the settings are
stored in the memory for 100 hours.
(
connectable.
individual operation by remote controller can be selected.
(up to 10 central control devices in one control circuit).
(
for each day of the week combined with weekly timer.
)
)
12
Central remote controller
Indoor remote controller
3. Basic system configuration
System legend (example) 8 hp system
Max. number of indoor units: 13 units
Indoor unit capacity code: Min. 4 Max. 10.8
Capacity code - total 10.4 Total number of units - 13
Outdoor unit
8HP
Indoor unit
Remote controller
Capacity code over the branch (0.8 + 0.8 = 1.6)
Indoor unit designation
Capacity code
13
10 hp system
Max. number of indoor units: 16 units
Indoor unit capacity code: Min. 5 Max. 13.5
Capacity code - total 12.8 Total number of units - 16
Outdoor unit
10HP
Indoor unit
Remote controller
14
20 hp system
Max. number of indoor units: 33 units
Indoor unit capacity code: Min. 10 Max. 27
Capacity code - total 26.75 Total number of units - 19
Outdoor unit
10HP 10HP
Indoor unit
Remote controller
15
30 hp system
Max. number of indoor units: 48 units
Indoor unit capacity code: Min. 15 Max. 40.5
Capacity code - total 40 Total number of units - 28
Outdoor unit
10HP
10HP 10HP
16
Indoor unit
Remote controller
40 hp system
Max. number of indoor units: 48 units
Indoor unit capacity code: Min. 20 Max. 54
Capacity code - total 53.75 Total number of units - 32
Outdoor unit
10HP
10HP
10HP 10HP
Indoor unit
Remote controller
17
48 hp system
Max. number of indoor units: 48 units
Indoor unit capacity code: Min. 24 Max. 64.8
Capacity code - total 61.9 Total number of units - 40
Outdoor unit
18
Indoor unit
Remote controller
4. Equipment selection procedure
1. Selection flow chart
1. Determination of indoor air conditioning load
2. Preliminary selection of indoor units
3. Preliminary selection of outdoor unit with indoor units
4. Capacity correction for piping length/height between indoor and outdoor units
5. Capacity correction based on indoor and outdoor temperature
6. Validate preliminary selection of indoor units
No
7. Confirmation of selection for indoor unit and outdoor units
End
2. Indoor unit and outdoor unit combination
For indoor unit, the capacity code is decided for each model size.
Model size 007 009 012 015 018 024 027 030 036 048 056 072 096 Cooling capacity, kW 2.2 2.8 3.6 4.5 5.6 7.1 8.0 9.0 11.2 14.0 16.0 22.4 28.0 Capacity code 0.8 1 1.25 1.7 2 2.5 3 3.2 4 5 6 8 10 Note: Model size: corresponding to Btu/h. Capacity code: corresponding to horsepower.
For outdoor unit, maximum number of connectable indoor units and total capacity code of indoor units are decided.
Outdoor unit Outdoor unit Capacity code Max. No. of Total indoor unit (cooling only) (heat pump) of outdoor unit indoor units capacity code
MMY-MAP0501T8 MMY-MAP0501HT8 5 8 2.5 to 6.75 MMY-MAP0601T8 MMY-MAP0601HT8 6 10 3 to 8.1 MMY-MAP0801T8 MMY-MAP0801HT8 8 13 4 to 10.8 MMY-MAP1001T8 MMY-MAP1001HT8 10 16 5 to 13.5 MMY-MAP1201T8 MMY-MAP1201HT8 12 20 6 to 16.2 MMY-AP1401T8 MMY-AP1401HT8 14 23 7 to 18.9 MMY-AP1601T8 MMY-AP1601HT8 16 27 8 to 21.6 MMY-AP1801T8 MMY-AP1801HT8 18 30 9 to 24.3 MMY-AP2001T8 MMY-AP2001HT8 20 33 10 to 27.0 MMY-AP2201T8 MMY-AP2201HT8 22 37 11 to 29.7 MMY-AP2211T8 MMY-AP2211HT8 22 37 11 to 29.7 MMY-AP2401T8 MMY-AP2401HT8 24 40 12 to 32.4 MMY-AP2411T8 MMY-AP2411HT8 24 40 12 to 32.4 MMY-AP2601T8 MMY-AP2601HT8 26 43 13 to 35.1 MMY-AP2801T8 MMY-AP2801HT8 28 47 14 to 37.8 MMY-AP3001T8 MMY-AP3001HT8 30 48 15 to 40.5 MMY-AP3201T8 MMY-AP3201HT8 32 48 16 to 43.2 MMY-AP3211T8 MMY-AP3211HT8 32 48 16 to 43.2 MMY-AP3401T8 MMY-AP3401HT8 34 48 17 to 45.9 MMY-AP3411T8 MMY-AP3411HT8 34 48 17 to 45.9 MMY-AP3601T8 MMY-AP3601HT8 36 48 18 to 48.6 MMY-AP3611T8 MMY-AP3611HT8 36 48 18 to 48.6 MMY-AP3801T8 MMY-AP3801HT8 38 48 19 to 51.3 MMY-AP4001T8 MMY-AP4001HT8 40 48 20 to 54.0 MMY-AP4201T8 MMY-AP4201HT8 42 48 21 to 56.7 MMY-AP4401T8 MMY-AP4401HT8 44 48 22 to 59.4 MMY-AP4601T8 MMY-AP4601HT8 46 48 23 to 62.1 MMY-AP4801T8 MMY-AP4801HT8 48 48 24 to 64.8
50 to 135% of outdoor unit capacity
19
3. Cooling/heating capacity characteristics
Cooling capacity calculation method: Required cooling capacity = cooling capacity x factor (, , , ,
Indoor air wet bulb temperature vs. capacity correction value
Capacity correction value
Indoor air wet bulb temperature (°C)
*1
) kW
Outdoor air dry bulb temperature vs. capacity correction value
Capacity correction value
Outdoor air dry bulb temperature (°C)
Air flow variation ratio of indoor unit vs. capacity correction (for ducted units only)
Capacity correction value
Air flow variation ratio (%)
*1 Outdoor unit capacity correction factor when total capacity of the indoor units is not equal to the outdoor unit capacity.
20
Connecting pipe length and lift difference between indoor and outdoor units vs. capacity correction value
Outdoor unit (5 to 44 hp)
Outdoor unit height H (m)
Pipe length (equivalent length) L (m)
Outdoor unit
Outdoor unit (46 to 48 hp)
Outdoor unit height H (m)
Pipe length (equivalent length) L (m)
Correction of outdoor unit diversity
ho l’o
hb
hc
L’ is the longest dimension of (l’o + l’a, l’o + l’b, l’o + l’c)
H = ho + (longest dimension of ha, hb and hc)
ha
l’a
l’b
l’c
Indoor unit
Correction (%)
Standard capacity ratio
Indoor unit total capacity ratio (%)
21
Heating capacity calculation method: Required heating capacity = heating capacity x factor (, , , , *1, *2) kW
Indoor air dry bulb temperature vs. capacity correction value
Capacity correction value
Indoor air dry bulb temperature (°C)
Outdoor air wet bulb temperature vs. capacity correction value
Capacity correction value
Outdoor air wet bulb temperature (°C)
Air flow variation ratio of indoor unit vs. capacity correction (for ducted units only)
Capacity correction value
Air flow variation ratio (%)
*1 Outdoor unit capacity correction factor when total capacity of the indoor units is not equal to the outdoor unit capacity. *2 Refer to the capacity correction for frosting on the outdoor heat exchanger section on page 24.
22
Connecting pipe length and lift difference between indoor and outdoor units vs. capacity correction value
Outdoor unit (5 to 48 hp)
Outdoor unit height H (m)
Pipe length (equivalent length) L (m)
Outdoor unit
L’ is the longest dimension of (l’o + l’a, l’o + l’b, l’o + l’c)
Correction of outdoor unit diversity
ho
hc
hb
l’o
H = ho + (longest dimension of ha, hb and hc)
ha
l’a
l’b
l’c
Indoor unit
Correction (%)
Standard capacity ratio
Indoor unit total capacity ratio (%)
23
Capacity correction for frosting on the outdoor heat exchanger (heating mode)
Correct the heating capacity when frost was found on the outdoor heat exchanger. Heating capacity = Capacity after correction of outdoor unit × correction value of capacity resulting from frost (Capacity after correction of outdoor unit: Heating capacity calculated in the previous section.)
Capacity correction for frosting on the outdoor heat exchanger
Capacity correction value
Outdoor air wet bulb temperature (°C)
Capacity calculation for each indoor unit
Capacity for each indoor unit =
Capacity after correction of outdoor unit ×
Required standard capacity of indoor unit Total value of standard indoor unit capacity
Operating temperature range
In cooling mode In heating mode
Continuous
Outdoor air dry bulb temperature (°C)
operating
range
Usable range
(in pull-down mode)
Usable range
Outdoor air wet bulb temperature (°C)
Continuous
operating
range
(in warming-up mode)
Indoor air wet bulb temperature (°C)
Rated conditions
Cooling: Indoor air temperature 27°C db/19°C wb. Outdoor air temperature 35°C db. Heating: Indoor air temperature 20°C db. Outdoor air temperature 7°C db/6°C wb.
24
Indoor air dry bulb temperature (°C)
The unit can be operated even if outdoor temperature falls to -20°C. However, the warranty only covers operation down to -15°C, as lower temperatures are outside the operating range.
When the outdoor air temperature falls to below
-15°C, unit operation may reduce the product life.
Example of equipment selection
The following shows an example of equipment selection based upon a building model.
Fig. 1 - Overview of building model
Outside view Floor configuration
Small meeting room Executive rooms
Office rooms (Entire floor)
Office rooms
Stores
Non-air conditioning zone
• Steel frame, reinforced concrete building, four floors above ground. Total floor area : 415 m²
Outdoor unit is installed on the roof.
Indoor design conditions:
Cooling: 27.0/19.0°C db/wb. Heating: 20°C db
Outdoor design conditions:
Cooling: 35°C db (standard condition). Heating: 3°C wb (standard condition: 6°C wb)
Selection criteria for each floor
1F: Outdoor unit capacity exactly matches the total indoor unit capacity.
Total indoor unit hp = Outdoor unit hp Indoor: 2.5 hp x 2 units + 3.2 hp + 2 hp = 10.2 hp
Outdoor: 10 hp Same capacity
2F: Outdoor unit capacity matches the potential total indoor unit capacity with the possibility of future
extension.
Office rooms 2 and 3 are to be used as warehouses at first, so air conditioning is not necessary at present.
However, there is a plan to convert them into offices, so an outdoor module with extra capacity is required.
Piping/wiring are carried out. Indoor unit is not yet installed. When the rooms are used as an office later, the indoor unit is installed.
3F: One indoor unit is connected to one outdoor unit.
The outdoor module should have sufficient capacity to cover the peak demand of the indoor unit connected.
4F: Consider the diversity factor and have the outdoor module match 135% of indoor unit capacity.
This is a typical matching of indoor/outdoor units for a Super MMS system.
• Total indoor unit hp > Outdoor unit hp
Select each indoor unit based on individual peak room load.
Indoor: 2.5 hp + 2.5 hp + 2 hp + 2 hp (capacity difference in each room) + 1.3 hp =
10.3 hp (different capacity) Outdoor: 8 hp (different capacity)
The cooling load profile needs to be taken into consideration.
25
Procedure and result of equipment selection
1. Procedure of equipment selection
a. Calculate cooling for every room. b. Select an indoor unit to match the cooling load for every room from the table on page 10. c. Select the outdoor module to match the indoor units selected in point b. Select the outdoor modules
based on the critical factors and the combination rule. Choose a tentative outdoor module that will match the indoor units, and check whether the selection agrees with the combination rule. Perform the capacity correction based on the pipe length, system lift, indoor set temperature, outdoor temperature.
Then, make sure the corrected system cooling capacity satisfies the cooling load.
2. Equipment selection and capacity check
Air conditioning load Equipment selection Floor Room No. Indoor air conditioning Model Capacity (kW) Model Capacity (kW) Cooling Heating MMU- Cooling Heating
4F 4-1 6.0 (16 o’clock) 5.4 AP0241H 7.1 8.0 AP2801HT8 78.5 88.0 4-2 5.2 (14 o’clock) 4.2 AP0181H 5.6 6.3 4-3 5.0 (14 o’clock) 4.2 AP0181H 5.6 6.3 4-4 3.2 (12 o’clock) 2.7 AP0121H 3.6 4.0 4-5 6.4 (10 o’clock) 5.4 AP0241H 7.1 8.0 3F 3-1 12.7 12.0 AP0481H 14.0 16.0 2F 2-1 4.8 4.5 AP0181H 5.6 6.3 2-2 4.6 4.8 AP0181H 5.6 6.3 2-3 1F 1-1 6.5 6.0 AP0241H 7.1 8.0 1-2 6.5 6.3 AP0241H 7.1 8.0 1-3 7.2 7.0 AP0301H 9.0 10.0 1-4 5.1 4.5 AP0181H 5.6 6.3
Note: ( ): Peak occurrence time
load (kW) Indoor unit Outdoor unit
MMY Cooling Heating
Piping distance Capacity correction Capacity check after correction Floor Room No. Equivalent length (m) difference (m) temp. correction Cooling Heating Cooling Heating
4F 4-1 43 12 0.920 0.957 6.5 6.9 Good 4-2 x x 5.2 5.4 4-3 1.0 1.0 5.2 5.4 4-4 x x 3.3 3.5 4-5 1.0 0.95 6.5 6.9 3F 3-1 = x 12.9 13.8 2F 2-1 0.920 0.95 5.2 5.4 2-2 = 5.2 5.4 2-3 0.864 — 1F 1-1 6.5 6.9 1-2 6.5 6.9 1-3 8.3 8.6 1-4 5.2 5.4
Height Pipe correction x Capacity (kW) Result
26
Example: Equipment selection based on system load profile
Since the five rooms on the 4th floor face different directions, their hourly cooling load profile will also be different. We select each indoor unit based on the individual room peak load. However, we need to use the total load profile on the 4th floor as a base to choose the outdoor module.
Load in each room Total load in all rooms of 4th floor
4-1
Load (kW)
Time
4-2
Total load (kW)
Load (kW)Load (kW)Load (kW)Load (kW)
4-3
4-4
4-5
Time
Time
Time
Time
1. The total load on the 4th floor is calculated by adding up the hourly cooling loads of the five rooms.
2. The maximum value of the total load is used to select the outdoor module.
Time
27
Schematic diagram
MMY-AP2801T8
MMY-AP2801HT8
Outdoor unit
1st branching joint
Indoor unit MMU-AP0241H
2nd branching joint
3rd branching joint
3rd branching joint
2nd branching joint
Indoor unit MMU-AP0181H
4-1 4-2
Indoor unit MMD-AP0481H
4th branching joint
4th branching joint
Indoor unit MMU-AP0181H
5th branching joint
Indoor unit MMU-AP0121H
4-3 4-4
Indoor unit MMU-AP0241H
4-5
3-5
28
Indoor unit MMU-AP0181H
Indoor unit MMU-AP0241H
2-1
Indoor unit MMU-AP0241H
Indoor unit MMU-AP0181H
No air conditioner
Branching header
Indoor unit MMU-AP0301H
2-32-2
Indoor unit MMU-AP0181H
1-41-31-21-1
5. Refrigerant piping design
1. Warnings on refrigerant leakage
Check of concentration limit
The room in which the air conditioner is to be installed requires a design that ensures that the concentration of refrigerant gas will not exceed a set limit if there is a leak.
Refrigerant R-410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws that protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R-410A is almost non­existent. With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power, etc.
Most importantly, the multi air conditioner system is able to contain a large amount of refrigerant compared with conventional individual air conditioners. If a single unit of the multi air conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur).
In a room where the concentration may exceed the limit, create an opening to adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m³)
≤ Concentration limit (kg/m³)
The concentration limit of R-410A which is used in multi air conditioners is 0.3 kg/m³.
Note 1: If there are 2 or more refrigeration systems in a single refrigeration device, the amounts of refrigerant should be as charged in each independent device.
e.g. charged amount (10 kg)
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A, B and C is 10 kg.
The possible amount of leaked refrigerant gas in
Room A
Room B
Room C Room D Room E Room F
rooms D, E and F is 15 kg.
Note 2: The standards for minimum room volume are as follows: (1) No partition (shaded portion)
(2) When there is an effective opening with the adjacent
room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).
Outdoor unit
e.g. charged amount (15 kg)
Indoor unit
Outdoor unit
Refrigerant piping
Indoor unit
(3) If an indoor unit is installed in each partitioned room and
the refrigerant piping is interconnected, the smallest room is the critical room. But when a mechanical ventilation device is installed in combination with a gas leak detector in the smallest room where the density limit is exceeded, the volume of the next smallest room is used.
Very small room
Small
Medium room
room
Mechanical ventilation device - gas leak detector
Large room
Refrigerant piping
Outdoor unit
Indoor unit
29
Note 3: The minimum indoor floor area compared with the amount of refrigerant is roughly as follows (when the ceiling is 2.7 m high):
m
Min. indoor floor area
density limit of
0.3 kg/m3 (countermeasures not needed)
Range above the density limit of
0.3 kg/m3 (countermeasures needed
Range below the
2
Total refrigerant amount
kg
2. Free branching system
Line branching system Header branching system Header branching after line branching Line branching after header branching Header branching after header branching
The above five branching systems are available to increase significantly the flexibility of refrigerant piping design.
Outdoor unit
Line branching system
Indoor unit
Header branching system
Branching joint
Remote controller
Outdoor unit
Branching header
Header branching after line branching
Line branching after header branching
Header branching after header branching
Indoor unit
Remote controller
Outdoor unit
Branching joint
Branching header
Indoor unit
Remote controller
Outdoor unit
Branching header
Branching joint
Indoor unit
Remote controller
30
Loading...
+ 78 hidden pages