Toshiba A09-01P User Manual

FILE NO : A09-01P
Quick reference
AIR TO WATER HEAT PUMP
Quick Reference Guide - Page 2
Estia System
Estia Outdoor Unit
HWS-802H-E 8.0kW Inverter (use Hydro Unit: HWS-802XWH**-E) HWS-1102H-E 11.2kW Inverter (use Hydro Unit: HWS-1402XWH**-E) HWS-1402H-E 14.0kW Inverter (use Hydro Unit: HWS-1402XWH**-E)
Estia Hydro Unit
HWS-802XWHM3-E Plate Heat exchanger and 3kW Backup Heater HWS-802XWHT6-E Plate Heat exchanger and 6kW Backup Heater HWS-1402XWHM3-E Plate Heat exchanger and 3kW Backup Heater HWS-1402XWHT6-E Plate Heat exchanger and 6kW Backup Heater HWS-1402XWHT9-E Plate Heat exchanger and 9kW Backup Heater
Estia Hot Water Cylinder (EU)
HWS-1501CSHM3-E 150L Stainless Steel Tank (with EU Accessories) HWS-2101CSHM3-E 210L Stainless Steel Tank (with EU Accessories) HWS-3001CSHM3-E 300L Stainless Steel Tank (with EU Accessories)
Estia Hot Water Cylinder (UK)
HWS-1501CSHM3-UK 150L Stainless Steel Tank (with UK Accessories) HWS-2101CSHM3-UK 210L Stainless Steel Tank (with UK Accessories) HWS-3001CSHM3-UK 300L Stainless Steel Tank (with UK Accessories)
Note:
Under floor heating, Fan Coil units, Radiators, valves and Hot Water Piping are procured locally.
Outdoor unit
Hydro unit
Domestic Hot Water
Hot water cylinder
Space Conditioning
Radiator
Fan coil unit
(Heating or Cooling)
Under floor heating
(Zone Control)
Quick Reference Guide - Page 3
Notes on System Design
• The input water temperature to the Hydro Unit must be 55°C or less. Especially, be careful when there is an external heating source such as a boiler. When hot water over 55°C returns, it may result in a failure of the unit or water leakage.
• The flow rate of the circulating water must meet the following range:-
11 and 14 kW 17.5 L/minute or more 8 kW 13 L/minute or more
If the flow rate becomes less than the minimum, the protective device is activated to stop operation. Ensure the flow rate with a bypass valve, etc. when you use a flow rate valve for the Hydro Unit.
• Do not drive water by power other than the pump built in the Hydro Unit.
• The backup heater operates supplementary to exert a prescribed capacity when the heat pump cannot exert its capacity at a low outside temperature.
• Install the Hydro Unit and water pipes in a place in which they do not freeze.
• Make the water circuit closed. Never use it as an open circuit.
• To prevent damage to the system during outdoor defrost the circulating water must be 20 litres or more. If total water amount is not enough, the unit may not function fully due to protective
operation.
Options required for each function
Purpose
Space Heating - -
Space Heating &
Space Cooling
(All Rooms)
Space Heating &
Space Cooling
(partly heating only)
150L Hot water cylinder HWS-1501CSHM3-E 150L Hot water cylinder HWS-1501CSHM3-UK
Domestic Hot Water
2-zone control - -
Interlocking with
boiler
Interlocking with
booster heater
210L Hot water cylinder HWS-2101CSHM3-E 210L Hot water cylinder HWS-2101CSHM3-UK 300L Hot water cylinder HWS-3001CSHM3-E 300L Hot water cylinder HWS-3001CSHM3-UK
Output control board kit
Part name Model code Part name
(1)
Toshiba Supply Procure locally
- - Fan coil(s) only
- -
- - Electric heater
Radiator(s),
Fan coil(s),
Under floor heating
Fan coil(s) plus
Radiator(s)
or Under floor heating
Motorized 2-way
valve
Motorized 3-way
valve
Earth leakage breaker
Motorized mixing
valve
Circulator pump
Buffer tank
TBC-PCIN3E Boiler
Quick Reference Guide - Page 4
Installation Examples
Space Cooling and Space Heating with Domestic Hot Water
When both cooling and heating are used, install a 2-way valve (for cooling) to the pipe to the room for heating only.
Quick Reference Guide - Page 5
Installation Examples (cont.)
2-Zone Space Heating with Domestic Hot Water
The following shows an example of the 2-zone temperature control. A buffer tank and a water pump are required for the 2-zone temperature control. This example is Heating only, if the Fan Coils are to be used for Cooling then a 2-Way valve must be fitted.
Hydro Unit – Exploded View
Quick Reference Guide - Page 6
1 : Expansion vessel 2 : Hi pressure switch (4.15 MPa) 3 : Temperature sensor (for Heat pump outlet -TWO) 4 : Pressure sensor 5 : Heat exchanger 6 : Flow switch (13.0 L/min 17.5 L/min) 7 : Temperature sensor (for refrigerant -TC) 8 : Temperature sensor (for water inlet -TWI) 9 : Drain nipple 10 : Water inlet connection 11 : Refrigerant liquid connection 12 : Air relief valve 13 : Pressure relief valve (0.3 MPa (3 bar)) 14 : Thermal protector (auto) 15 : Temperature sensor (for water outlet THO) 16 : Thermal protector (Single operation) 17 : Water pump 18 : Backup heater (3 kW, 3 kW x 2, 3 kW x 3) 19 : Manometer 20 : Water outlet connection 21 : Refrigerant gas connection
Quick Reference Guide - Page 7
Refrigerant Piping
Refrigerant Pipe Lengths and Height
The length and height of the refrigeration pipe must be within the following values.
Minimum Pipe Length
HWS-802H-E : 5 m HWS-1102H-E : 3 m HWS-1402H-E : 3 m
Maximum Pipe Length and Height
H: Max. ±30 m (above or below) L: Max. 30 m
Note
The maximum pipe length cannot be increased using additional refrigerant.
Refrigeration and Water Cycle Diagrams Hydro Unit
Refrigerant pipe at gas side (Outer ø15.88)
Refrigerant pipe at liquid side (Outer ø9.52)
Expansion vessel
Hi_P_Switch
P_Sensor
TC Sensor
Water Heat exchanger
Thermal
Protector
TWO Sensor
Air vent valve
Backup heater
Pressure relief valve
THO Sensor
Flow_Switch
Pressure Gauge
Pump
Water Out (1 1/4")
TWI Sensor
Water IN (1 1/4")
Outdoor Unit HWS-802H-E
Quick Reference Guide - Page 8
HWS-1102H-E, 1402H-E
Quick Reference Guide - Page 9
Water Piping
• Install water pipes according to the regulations of respective countries.
• Install water pipes in a freeze-free place.
• Make sure that water pipes have sufficient pressure resistance (The setting value of the pressure relief valve is 0.3 MPa).
• Do not use zinc plated water pipes. When steel pipes are used, insulate both ends of the pipes.
Water Connections
Install a strainer with 30 to 40 meshes (procure locally) at
the water inlet of the Hydro Unit.
Install drain cocks (procure locally) for water charge and
discharge at the lower part of the Hydro Unit.
Water Piping Limitations
Design the water pipe length within the QH characteristics of the pump (flow-rate and pump head).
The maximum height difference for the water pipes i 7 metres.
Piping to hot water tank (option
Water supplied to the hot water cylinder is branched by a motorized 3-way valve (procured locally). Connect the hot water cylinder to port A (open when energized) of the valve.
)
Piping to 2-zone operation (option)
To perform 2-zone temperature control circulate water using another pump (procured locally) through a motorized mixing valve (procured locally) and a buffer tank (procured locally).
s
Quick Reference Guide - Page 10
Checking water volume and initial pressure of expansion vessel
The expansion vessel of the Hydro Unit has a capacity of 12 litres. The initial pressure of the expansion vessel is 0.1 MPa (1 bar). The suggested initial water charge is 0.2MPa (2 bar). The pressure of the safety valve is 0.3 MPa (3 bar). Verify whether the capacity of the expansion vessel is sufficient using the following expression. If the volume is insufficient, install an appropriate external expansion vessel.
V Action
< 12 L Internal Expansion Vessel Size OK
> 12 L
Internal Expansion Vessel Size too small.
Install appropriate external expansion vessel
V: Necessary total vessel capacity (L)
Ɛ: Water expansion coefficient at average hot water temperature Vs: Total water volume in the closed system (Do not include Hot Water Cylinder) P1: System pressure at tank setting position (Mpa_abs*).
(Pipe inner pressure during pump operation before heating device operates = water supply pressure)
P2: Maximum pressure used during operation at tank setting position (MPa_abs*).
(= safety valve setting pressure)
* The absolute pressure value (abs.) is obtained by adding the atmospheric pressure (0.1 MPa (1 bar)) to the gauge pressure.
Water temperature and expansion coefficient (Ɛ)
Hot water temperature
(°C)
0 0.0002 50 0.0121 4 0.0000 55 0.0145
5 0.0000 60 0.0171 10 0.0003 65 0.0198 15 0.0008 70 0.0229 20 0.0017 75 0.0258 25 0.0029 80 0.0292 30 0.0043 85 0.0324 35 0.0050 90 0.0961 40 0.0078 95 0.0967 45 0.0100 - -
Expansion rate
(Ɛ)
Water temperature and expansion coefficient (Ɛ)
Hot water temperature
(°C)
Expansion rate
(Ɛ)
Example
Maximum Hot Water temperature: 55°C, initial water charge: 0.2MPa and system volume: 200 L.
The calculated Vessel capacity (V) is 11.6 L:-
11.6
=
0.0145
1
x
-
In this case V < 12 L therefore the internal expansion vessel is sufficient. There is no need to install an external expansion vessel.
200 (0.2+0.1) (0.3+0.1)
Quick Reference Guide - Page 11
Pump operation / configuration
Change Pump speed, so that water flow is always greater than the minimum flow rate. If water flow
is lower than the minimum rate during operation, the unit detects error.
Water charging
Charge water until the pressure gauge shows 0.2 MPa (2 bar). Hydraulic pressure may drop when the trial run begins. In that case, add water.
Air may enter if the charged hydraulic pressure is low. Loosen the purge valve cap by two turns to release air. Loosen the cap of the pressure relief valve to release air. Water may come out of the pressure relief valve. Release the air completely from the water circuit. Failure to do so may disable correct operation.
Water quality
The water used must satisfy EN directive 98/83 EC.
Piping insulation
It is recommended that insulation treatment be applied to all pipes. To perform optional cooling operation, apply insulation treatment of 20 t or more to all pipes.
Electrical Connections
E Box layout
Quick Reference Guide - Page 12
Terminal Block Connections
Power Lines Schematic
Quick Reference Guide - Page 13
Control Lines Schematic
Electrical supply / cable specifications
Wiring specifications (power line)
Quick Reference Guide - Page 14
Description
POWER SUPPLY
Maximum current
Installation fuse rating
Cable size
14 kW 230 V ~ 50 Hz 22.8 A 25 A 2.5 mm² or more
Outdoor unit power
11 kW 230 V ~ 50 Hz 22.8 A 25 A 2.5 mm² or more
8 kW 230 V ~ 50 Hz 20.8 A 25 A 2.5 mm² or more
Outdoor-Hydro 1.5 mm² or more
3 kW 230 V ~ 50 Hz 13 A 16 A 1.5 mm² or more
Hydro inlet heater power
6 kW 400 V 3N ~ 50 Hz 15 A (13 A x 2P) 25 A 2.5 mm² or more
9 kW 400 V 3N ~ 50 Hz 23 A (13 A x 3P) 25 A 2.5 mm² or more
Hydro cylinder heater power 230 V ~ 50 Hz 12 A 16 A 1.5 mm² or more
Hydro - cylinder 12 A 1.5 mm² or more
Wiring specification (control line)
Description
Line spec
Maximum current
3-way valve control 2 line or 3 line 100 mA 12 m 0.75 mm² or more
Mixing valve control 3 line 100 mA 12 m 0.75 mm² or more
2-zone thermo sensor 2 line 100 mA 5 m 0.75 mm² or more
Cylinder thermo sensor
2+GND (shield wire)
100 mA 5 m 0.75 mm² or more
Second remote controller 2 line 50 mA 50 m 0.75 mm² or more
Maximum length
Cable Size
Control parts specifications
Maximum
Description Power
current
Type
Connection destination
L
, N
1
, 2 , 3
L
, N (TB02)
L1
, L2 , L3
N
(TB02)
L
1
TB03)
, N (
, 2 (TB03)
Connection destination
7
, 8 , 9
(TB05)
1
, 2 , 3
or
2
, 3 , 4
(TB04)
C
, D (TB06)
A
, B (TB06)
1
, 2 (TB07)
Motorized 3-way valve (for hot water)
Motorized 2-way valve (for cooling)
Motorized mixing valve type 1 (for 2-zone)
AC 230 V 100 mA
AC 230 V 100 mA spring return type (normally open )
AC 230 V 100 mA
Spring return type Note: 3-wire SPST and SPDT type can be used by changing the function code.
60 sec 90º. SPDT type Note: SPST and 20 to 240 sec type can be used by changing the function code.
Output line specifications
Description
Output
Maximum current
External pump No. 1 AC230V 1 A 12 m
External booster heater AC230V 1 A 12 m
Boiler control
ALARM Output
Operation Output
Defrost Output
Non­voltage contacts Non­voltage contacts Non­voltage contacts Non­voltage contacts
0.5 A AC230 V 12 m
1 A DC24 V 12 m
0.5 A AC230 V 12 m
1 A DC24 V 12 m
0.5 A AC230 V 12 m
1 A DC24 V 12 m
0.5 A AC230 V 12 m
1 A DC24 V 12 m
Max voltage
Maximum length
Interlocked with the Hydro Unit pump
Output as required when outdoor air temperature is -20°C or less
Output as required when outdoor air temperature is -10°C or less
Quick Reference Guide - Page 15
Input line specifications
Description
Emergency stop control Non-voltage 12 m
Cylinder thermostat input Non-voltage 12 m
Cooling thermostat input Non-voltage 12 m
Heating thermostat input Non-voltage 12 m
Input
Maximum length
CAUTION
Earthing arrangements
The Hydro Unit and related equipment must be earthed in accordance with your local and national electrical regulations. It is essential that the equipment is earthed to prevent the electric shock and damage to the equipment.
Electrical connection to hydro unit
• Remove the front cover and the electrical box cover from the Hydro Unit.
• The Hydro Unit power cable must be sized in accordance with refer to “Electrical supply/cable specifications”.
• Connect the Hydro Unit power cable to Terminal 02 as shown below. Single Phase Units: Live conductor – Terminal L1
Neutral conductor – Terminal L2 Earth conductor – Earth terminal
Three Phase Units: Phase 1 conductor – Terminal L1
Phase 2 conductor – Terminal L2 Phase 3 conductor – Terminal L3 Neutral conductor – Terminal N Earth conductor – Earth
• Ensure the Hydro Unit power cable is secured using the cable clamp fitted in the electrical box.
• Ensure the Hydro Unit power cable connection terminals are tight.
Outdoor unit to hydro unit electrical connection
• Ensure electrical circuits are isolated before commencing work.
• The Outdoor Unit to Hydro Unit interconnecting cable must be sized in accordance with refer to
“Electrical supply/cable specifications”.
• Connect the Outdoor Unit to Hydro Unit interconnecting cable as shown in the diagram above.
• Ensure the Outdoor Unit to Hydro Unit interconnecting cable is secured using the cable clamp
fitted in the electrical box.
• Ensure the Outdoor Unit to Hydro Unit interconnecting cable connection terminals are tight.
Quick Reference Guide - Page 16
Electrical connection for external booster heater
CAUTION
The maximum current available from the booster heater output is 1 A. Do not connect the booster heater directly to Terminal Block 05 on the Hydro Unit. The AC230 V 1 A output from the Hydro Unit must only be used to energize an external contactor (Supplied locally).
• The booster heater can be installed only for room heating and cannot be used for hot water
supply.
• Install the booster heater downstream of the 3-way valve on the indoor unit side.
• The booster heater is an external heater, supplied locally, used to assist the Hydro Unit during
low ambient conditions.
• The output from the Hydro Unit is only enabled when the outdoor air temperature is less than -
20°C.
• Ensure the external booster heater is installed and set up in accordance with all Local, National
and International regulations.
• Connect the coil, of the field supplied contactor, to terminals 5 & 6 on Terminal Block 05. The
contactor will energize in the event of low ambient conditions.
• A separate dedicated electrical supply must be used for the external booster heater. This must
be connected through the contacts on the field supplied contactor (see diagram below):-
Electrical connection for external additional pump (P2)
CAUTION
The maximum current available from the additional pump output is 1 A. Do not connect the additional pump directly to Terminal Block 05 on the Hydro Unit. The AC230 V 1 A output from the Hydro Unit must only be used to energize an external contactor (Supplied locally).
• The Hydro Unit has the facility to connect an additional circulating pump, if required, into the
heating or cooling system.
• Install the external pump so that its motive power does not affect the internal pump.
• The output for the pump is synchronized with the operation of the main circulating pump (P1)
inside the Hydro Unit.
• Connect the coil, of the field supply contactor, to terminals 1 & 2 on Terminal Block 05.
• A separate dedicated electrical supply must be used for the additional pump. This must be
connected through the contacts on the field supplied contactor (see diagram below):-
Quick Reference Guide - Page 17
2-way valve (for cooling) connection
Required Valve Specification:
Electrical Specification: 230 V; 50 Hz; <100 mA Return Mechanism: 2-wire spring return.
• The Hydro Unit has the facility to connect a 2-way valve to
isolate Space Conditioning Units that do not perform cooling, when Cooling Mode is selected.
• Connect the 2-way valve in accordance with the diagram
(opposite):-
3-way valve (diverter) connection
Required Valve Specification:
Electrical Specification: 230 V; 50 Hz; <100 mA Valve Diameters: Port A, Port B: Ø 1 1/4" Return Mechanism: 3 types of 3-way valve (diverter) can be used. Set the 3-way valve in use with the DIP switch SW13-1 on the Hydro Unit board.
Diverter Valve Description
Type 1 2-wire spring return OFF Type 2 3-wire SPST OFF Type 3 3-wire SPDT ON
Continuous operation of the valve motor at the fully open position is not recommended.
• The 3-way diverter valve is used to select either domestic hot water or space heating.
• Connect the 3-way diverter valve in accordance with the diagram below:-
SW13-1
Quick Reference Guide - Page 18
3-way mixing valve connection
Required Actuator Specification
Electrical Specification:230 V; 50 Hz; <100 mA The 3-way mixing valve is used to achieve the temperature differential needed in a 2-zone heating system.
• Connect the 3-way mixing valve in accordance with the diagrams below:-
Hot water cylinder connection (optional)
• Please refer to “Electrical supply/cable specifications” for fuse/cable size and for
connection details. Electrical Connection (Hot Water Cylinder Electric Heater)
• The electric heater, incorporated in the hot water cylinder, requires a separate supply to Hydro
Unit.
• Connect the hot water cylinder heater electrical supply in accordance with shown below:
Live conductor: Terminal L on Terminal Block 03 Neutral conductor: Terminal N on Terminal Block 03 Earth Conductor: Earth terminal on Terminal Block 03
• Connect the hot water cylinder heater to the Hydro Unit as shown below:
Live conductor to hot water cylinder: Terminal 1 on Terminal Block 03 Neutral conductor to hot water cylinder: Terminal 2 on Terminal Block 03 Earth conductor to hot water cylinder: Earth terminal on Terminal Block 03
Electrical Connection (Hot Water Cylinder temperature Sensor)
• Connect the hot water cylinder temperature sensor as shown below to terminals A & B on
Terminal Block 06 in the Hydro Unit.
• Please ensure that the interconnecting cable, between the Hydro Unit and the hot water cylinder,
is connected to earth at both ends of the cable using the shield wire.
Setting DIP Switches on the Board in the Hydro Unit
• Detach the front cover and the electric parts box cover of
the Hydro Unit.
• Set the DIP switches on the main board.
Quick Reference Guide - Page 19
SW10 Description
1
3 External P2 pump operation Continuous operation OFF ON
SW11 Description
1
2
3 Booster heater operation Operate
SW12 Description
1 Hot water supply operation Valid
2 Zone 1 operation Valid
3 Zone 2 operation Invalid
SW13 Description
1 Type of motorized 3-way valve
2 Interlocking with boiler Invalid
3 Auto restart for power failure Auto restart
SW02 Description
4 Room thermostat Invalid
Internal pump P1 operating mode
Internal backup heater operation Hot water cylinder heater operation
Continuous operation OFF ON HP synchronized
Operate
Operate
• 2-wire spring return type
• 3-wire SPST type
Default setting Alternate
Default setting Alternate
Default setting Alternate
Default setting Alternate
Default setting Alternate
Switch mode
Switch mode
OFF ON Not operate
OFF ON Not operate
OFF ON Not operate
Switch mode
OFF ON Invalid
OFF ON Invalid
OFF ON Valid
Switch mode
OFF ON 3-wire SPDT type
OFF ON Valid
OFF ON Manual restart
Switch mode
OFF ON Valid
Interlocked with the internal pump synchronized with P1.
Hydro Unit Remote Control
Buttons and Functions
1. TEMP. button:
2. SCHEDULE button:
3. TIME button:
4. SET button:
Changes the set temperature for each operation mode (ZONE1/2 hot water) by 1°C step.
Sets the current time and scheduled weekly operation.
Changes time for current time setting and scheduled weekly operation setting with and buttons.
Determines the entered current time setting and scheduled weekly operation setting.
10. NIGHT button:
11. AUTO TEMP. button:
12. OPERATE MODE button:
13. ZONE1, 2 button:
Quick Reference Guide - Page 20
Controls the night set back operation.
Switches setting temperature automatically according to outside temperature. (Pressing this button long changes the mode to data setting mode).
Selects ZONE1/2 operation mode (heating or cooling).
Turns on/off the zone (floor heating/radiator/FCU) operation.
5. CL button:
6. DAY button:
7. STEP button:
8. TEST button:
9. FROST PROTECTION button:
Clears settings for the current time and scheduled weekly operation.
Sets days of the week for current time setting and scheduled weekly operation setting.
Specifies switching STEP number in a day for weekly schedule.
Used for test run or service.
Controls minimum operation for unused period (going out, absence,etc.) for anti freezing.
14. ANTI BACTERIA button:
15. HOT WATER BOOST button:
16. HOT WATER button:
17. SELECT button:
Regularly increases the hot water temperature in the tank for sterilization. (Pressing this button long changes the mode to data setting mode).
Boosts boiling when high tapping temperature is required temporarily.
Turns on/off hot water operation.
Selects an operation mode when changing the set temperature of each operation mode.
NOTE
Some functions are not provided depending on the system specification in use.
Display Explanation
Quick Reference Guide - Page 21
18: ZONE1, ZONE2
Display Description Display Description
Lights when floor heater or radiator is connected (when the system has
floor heater or radiator).
ZONE1 selected for Temperature
to be changed.
Lights when system configured to
have 2 zones.
ZONE2 selected for Temperature
to be changed.
Lights during heating or cooling
operation using the heat pump.
Lights when the internal heater is
energized during heating
operation.
Lights when heating is selected.
20: HOT WATER
Lights when hot water supply system is
connected (when the system has hot
water supply).
HOT WATER selected for Temperature
Lights when hot water supply operation
Lights when the internal heater is
energized during hot water supply
Lights during hot water supply operation.
to be changed.
is performed by heat pump.
operation.
Lights while hot water boost is activated.
Lights when the ANTI BACTERIA button is pressed and goes out when the button
is pressed again.
Lights when unit enters the data set
mode.
Displays hot water set temperature.
(40 to 80°C, factory setting: 65°C)
Lights when the set temperature or
sensor's water temperature is displayed
with the 7-segment indicator.
°C
Lights when cooling is selected.
Lights when the FROST
PROTECTION button is pressed
and goes out when the button is
pressed again.
Lights when Auto operation is
selected.
Displays heating/cooling set temperature. (Heating: 20 to 55°C, factory setting: Auto, cooling: 10 to
30°C) Goes out when Auto
operation is selected.
Lights when the set temperature or
sensor's water temperature is
displayed with the 7-segment
indicator.
°C
Quick Reference Guide - Page 22
Display Explanation (cont.)
19: TIMER
Display Description Display Description
21: OPERATION
Clock: Displays the current time (AM or PM).
Displays days of the week (Sunday to Saturday).
Lights when the NIGHT button is pressed and goes out when the button is pressed again.
Lights when night time quiet operation is set.
Indicates scheduled operation 1 status (including setting time).
Displays the scheduled operation step when the scheduled operation STEP1-5 program is set.
Lights during time setting and scheduled operation setting.
Lights while internal pump (P1) or external pump (P2) is driven.
Lights during backup operation only by the heater.
Lights when the unit enters the data set mode and goes out when the unit exits the data set mode.
Lights when the unit enters the service mode and goes out when the unit exits the service mode.
Lights when an error occurs and goes out when the error is cleared.
Lights for two seconds when settings are completed.
Lights for two seconds when settings failed.
Function Code Access
Set function codes for various operation modes, input using the remote controller. There are 2 types of settings:-
1) Hydro Unit function code setting.
2) Remote controller function code setting.
Setting procedure for Hydro Unit function code
1. Press the TEST + SET + SELECT buttons
for four seconds or more to enter the hydro unit function code setting mode.
2. Set the function code number with the TEMP. buttons (CODE No.: 01 to 91).
3. Set data (DATA) with the TIME buttons .
4. Press the SET button to confirm the settings.
5. The CL button is enabled only before the SET button is pressed and the function code is changed.
6. Press the TEST button to finish the settings.
Setting procedure for Remote Controller function code
1. Press the TEST + CL TEMP. buttons for four seconds or more to enter the ote controller function code setting mode.
2. Set the function code number with the TEMP. buttons (CODE No.: 01 to 13).
3. Set data (DATA) with .
4. Press the SET button to determine the settings.
rem
the TIME buttons
+
5. The CL button is enabled only before the SET button is pressed and the function code is changed.
6. Press the TEST button to end the settings.
Quick Reference Guide - Page 23
Main setting items
) Setting Hot Water Temperature Range (functi on code 18 to 1F)
(1
• Set the temperature range for heating (zone 1, zone 2), cooling, and h
• The upper-limit and lower-limit temperatures of each mode can be set.
) Setting Heat Pump Operation Conditions for Hot Water Supply (func(2
• Set the heat pump start water temperature and heat pump stop water temperature.
is recommended that the default value be used.
3) Compensating Hot Water Temperature (fun(
• Compensate the target temperature from the remote controller set tempe temperature lowers below the set outside air temperature.
4) Setting Hot Water Boost (function code 08 and 09) (
• Set the control time and target temperature when the HO controller is pressed.
5) Setting Anti-Bacte(
• Set the control for the hot
• Set the target temperature, control period, start time (24-hour not nd target temperature retention period.
this control setting according to regulations and rules of respective countries. • Make
6) Setting Priority Mode Temperature (
• Set the outside air temperature that change
• Hot Water - Heating Switching Temperature
• Boiler HP Switching Temperature
made.
7) Sett(
• Compensate the target temperature when Auto is set for temperature set
• The outside air temperature can be set to one of three points (T1, T2, and T3) within a range of -20 to 2
• The target temperature can be set to a value from 20 to 55°C.
• However, A > B > C > D > E.
ing Heating Auto Mode Temperature (function code 27 to 31)
ria
water cylinder when ANTI BACTERIA
t temperature, the HP operation stops and the external bWhen the temperature lowers the se
ction code 24 and 25)
T WATER BOOST
s the preferred operation mode.
temperature lowers the set tempeHeating operation takes precedence when the
ot water.
ation), a
tion code 20 and 21)
rt water tempe• The heat pump starts working when the water temperature lowers below the set sta
rature when the hot water
button on the remote
is set with the remote controller.
rature.
ting on the remote controller.
rature. It
oiler output is
0°C.
• The entire curve can be adjusted plus and minus 5°C by function code 27.
) Setting Frost Protection Temperature (function code 3A to 3B) (8
• Set the function when the FROST PROTECTION
• Set enabling/disabling of this function and the targe ater temperature.
• If disabling is set, the frost protection operation is not performed even wh is pressed.
(9) Setting
• The increase/decrease time is used to set the response time.
10)Setting Night Setback (function code 26. remote control(
• Set the function when the NIGHT
• If disabling is set, the night setback operation is not performed even when the NIGHT
Frequency of Output to Internal Heater (function code 33 to 34)
button on the remote controller is pressed.
ion, re e. • Set enabling/disabling of this funct duction temperature, start time, and end tim
button on the remote controller is pressed.
t w
en the FROST PROTECTION
ler function code 0F to 11)
button is pressed.
button
Quick Reference Guide - Page 24
Main setting item (cont.)
1)Setting 2-Way Valve (for Cooling) Operation (function code 3C)
(1
• When using both cooling and heating operations and there is an indoor heating), install the 2-way valve and set this function code.
2)Setting 3-Way Valve Operation (function code 54)
(1
• This setting is not necessary for normal installation. Make A and B of the 3-way valve are wrongly attached and it cannot be rectified on site.
(1
3)Mixing valve types and setting
• Set the time period from full close to the actual time.
(1
4)Setting Heating/Hot Water Switching when Boiler Is Used (function code 3E)
• When boiler is used, make this setting to operate the Hydro Unit by the instruction from
(1
5)Setting Heat Pump Operating Time for Hot Water Supply Operation
• Set the time period from the start of heat pump run to the start of heater ene water supply operation. If a long period is set, it takes long time for heating water.
(1
6)Setting Cooling ON/OFF
• Set this function when perform
(1
7)Remote controller time indication
• 24-hour or 12-hour notation is selected for the timer.
(1
8)Setting Nighttimes Quiet Operation
• Issue an instruction for low-noise mode op time, and end time can be set.
(1
9)Setting Alarm Tone
• The remote controller ala
rm tone can be set.
full open of the 2-zone control mixing valve. Set a value that is 1/10 of
ing cooling operation.
eration to the outdoor unit. Enabling/disabling of this function, start
this setting to invert the logic circuit in case ports
unit only for heating (such as floor
rgization at the beginning of hot
Function Code List
Zone 1 - heating upper temperature limit °C Zone 1 - heating lower temperature limit °C
Setting
mperatu
Te re
Range
Hot Water
Operation
Hot Water
T
emperature
Compensation
Hot Water Boost
Anti - Bacteria
Priority Mode
Zone 2 - heating upper limit temperature °C Zone 2 - heating lower limit temperature °C Cooling mode - upper temperature limit °C Cooling mode - lower temperature limit °C Hot water - upper temperature limit °C Hot water - lower temperature limit °C Heat pump start temperature °C Heat pump stop temperature °C
Temperature compensation - start outside air temperature °C
Compensation te Operation time x 10 min Setting temperature °C Setting temperature °C Start cycle (day) Start time (hour) Operation time (m
Hot water and heating switching temperature °C Boiler and heat p temperature °C
Function
mperature °C
in)
ump switching
Function Code
Number
o Rem
Hydr ote
Unit ontroller
1A - 37 ~55 55 1B - 20 ~ 37 20 1C - 37 ~55 55 1D - 20 ~ 37 20 18 - 18 ~ 30 25 19 - 10 ~ 18 10 1E - 50 ~ 75 75 1F - 40 ~ 60 40 20 - 20 ~ 45 38 21 - 40 ~ 50 45
24 - -20 ~ 10 0
25 - 0 ~ 15 3 08 - 3 ~ 18 6 09 - 40 ~ 75 75 0A - 70 ~ 75 75
- 0D 0 ~ 10 7
- 0C 0 ~ 23 22
0B
22 - ~ 20 0
23 - -20 ~ 20 -10
C
the boiler.
Range Default
- 0 ~ 60 30
-20
Function Code List (cont.)
Function Hydro Unit
Outside temperature T1 °C
Outside temperature T2 °C
Outside air temperature T3 °C
Setting temperature A at -20 °C
Heating
Auto Curve
Settings
Frost Protection
Back Up Heater
Control
Setting temperature B at T1°C
Setting temperature C at T2°C
Setting temperature D at T3°C
Setting temperature E at +20°C
Ratio of Zone 2 in Zone 1 Auto mode (%)
Temperature shift of entire Auto curve (°C)
Function 0 = Valid; 1 = Invalid
Setting temperature °C
Back up heater downtime. 0=5min; 1=10min; 2=15min; 3=20min
Back up heater uptim 2=30min; 3=40min
e. 0=10min; 1=20min;
Quick Reference Guide - Page 25
Function Code Number
Remote
C
ontroller
29 - -15 ~ 0 -10
- - 0 0
2B 0 ~ 15
2C - 20 ~ 55 40
2D - 20 ~ 55 35
2E - 20 ~ 55 30
2F - 20 ~ 55 25
30 - 20 ~ 55 20
31 - 0 ~ 100 80
27 - -5 ~ 5 0
3A - 0 ~ 1 1
3B - 8 ~ 20 15
33 - 0 ~ 3 1
34 - 0 ~ 3 0
- 10
Range Default
Night Setback
Room Temperature
Setting
2 Way Valve
peration Contro
O l
3 Way valve
Op ol
eration Contr
2 Zone Mixing
V
alve Drive Time
Boiler & Heat
Pump hronisa
Sync tion
Zone Selection: 0=Zones 1 and Zone 2; 1=Zone 1 Only
Change Setback temperature °C
Start time (hour)
End time (hour) - 0F 0 ~ 23 06
Room temperature control adjustment. 0=Valid; 1=Invalid
Compensation for temperature °C 35 - 1 ~ 5 1
Downtime Zone B (x 5min) 36 -
Uptime Zone C (x5min) 37 -
2 way valve activation for cooling. 0=activated during cooling; 1=not activated during coolin
3 way valve activation. 0=activated during hot w 1=not activated during hot water operatio
Specified Drive Time for Mixing Valve to 90° open (x 10 sec)
Boiler synchronisation with 0=synchronised; 1=not synchronised
g
ater operation;
n
heat pump.
58 - 0 ~ 1 0
26 - 5
- 0E 0 ~ 23 22
- 02 0 ~ 1 0
3C - 0 ~ 1 0
54 - 0 ~ 1 0
0C - 3 ~ 24 6
3E - 0 ~ 1 0
3 ~ 20
1 ~ 24
(5 ~ s) 120min
1 ~ 24
(5 ~ s)
120min
6
6
Maximum
Ope of
ration Time
Hot Water Heat
Pump
Cooling Operation
Maximum heat pump operation time in hot water operation priority mode (minutes)
Activate cooling mode.
e; 02 - 0 ~ 1 1 0=cooling & heating mod
1=heating mode only
07 - 1 ~ 120 30
Quick Reference Guide - Page 26
Function Code List (cont.)
Function Hydro Unit
Remote Controller
Indication
Outdoor Night Time
Low Noise
Operation
Alarm Tone Tone Switching 0: OFF, 1: ON 11 0 ~ 1 1
Pump P2 remote
controller Display
Outdoor Forced
Defrost Mode
Optional ON/OFF
Command
Outdoor Night Time
Mode Button
Control Logic for
Room Thermostat
24 hour or 12 hour remote control display. 0=24hr; 1=12hr
0 = Function invalid 1 = Function valid
Start time (hour) - 0A 0 ~ 23 22
End time (hour) - 0B 0 ~ 23 06
0 = Not Shown; 1 = Shown
0 = Forced Defrost OFF; 1 = Forced Defrost ON
0 = a contact “ON” = Forced stop 1 = b contact “OFF” = Forced stop 2 = ON/OFF = Start / Stop 3= HA Specification
0 = Symbol displayed when mode is valid (controlled by Function Code Only); 1 = Symbol displayed when mode is activated (controlled by Function Code and Button)
0 = Cooling thermo on – contact open; 1 = Cooling thermo on – contact close
Function Code Number
Remote
Controller
- 05 0 ~ 1 0
- 09 0 ~ 1 0
42 - 0 ~ 1 0
46 - 0 ~ 1 0
52 - 0 ~ 3 0
56 - 0 ~ 1 0
57 - 0 ~ 1 0
Range Default
Settings by Purpose
Settings when hot water supply function is not used
• When the hot water supply function is not used, set DIP SW12-1 on the Hydro Unit board to ON.
Setting for cooling
• For Space Conditioning Units that do not perform cooling (radiators and Under floor heating, etc.), procure a motorized 2-way valve (for cooling) locally and attach it to the water pipe that is not used for cooling. Connect the valve cables (as described in Electrical section).
• Press long the TEST + SET + SELECT switches on the remote controller to change the Hydro Unit function code, and change address 02 to 0, and then press the SET button to enable the function.
Press the TEST button to exit the setting mode.
• Stick the optional insulator for cooling to the bottom of the Hydro Unit.
Settings for hot water supply
• Prepare the optional hot water cylinder.
• Procure a motorized 3-way (diverter) valve locally and perform piping. Connect the valve cables (as described in Electrical section).
• Set DIP SW12-1 on the Hydro Unit board to OFF.
• Connect the power supply unit for the hot water cylinder heater to terminals TB03 L and N of the Hydro Unit.
• Connect cables between the Hydro Unit and the hot water cylinder as follows: Hydro Unit terminals TB03 (1), (2), and earth — Hot water cylinder (1), (2), and earth
TB06 A, B, and earth — Hot water cylinder A, B, and earth
Quick Reference Guide - Page 27
Settings by Purpose (cont)
Settings for 2-zone temperature control
• Procure a motorized mixing valve locally and perform piping. Connect the valve cables (as described in Electrical section).
• Procure a buffer tank locally.
• Procure a water pump locally, and connect its cables (as described in Electrical section). To inhibit interlocking the water pump with the internal pump of the Hydro Unit, set DIP SW10-3 on the Hydro Unit board to OFF.
• Set DIP SW12-3 on the Hydro Unit board to ON. Attach the temperature sensor (TFI) connected to terminals TB06 C and D of the Hydro Unit near the hot water inlet of the Hydro Unit.
• Contact the temperature sensor closely with the pipe, fix it with aluminium tape or the like, and then perform insulation treatment for the sensor.
• Fix TFI sensor on the room heating supply pipe by using the connector procured in locally.
• Cover the cables with insulation tube (minimum 1 mm) or conduit so that the user cannot touch them directly.
• Connect the functional earth wire of TFI sensor in the tank unit.
• Cover the TFI sensor's cables and sensor with insulation tube (minimum 1 mm) shown in the diagram on the right.
Test Run
Use operation buttons usually to conduct a test run.
If the outside air temperature or water temperature is outside the setting value range, press the TEST button on the remote controller and then start a test run. Since the protection setting is disabled in the TEST mode, do not continue a test run longer than 10 minutes.
• Press the TEST button on the remote controller. An indication “TEST” appears on the remote controller.
• Press the ZONE1, 2 The pump is activated in 30 seconds. If air is not released completely, the flow rate switch is activated to stop operation. Release air again according to the piping procedure. Little air bite is discharged from the purge valve.
• Check that the air bite sound disappears.
• Check that the hydraulic pressure has become the predetermined pressure 0.1 to 0.2 MPa (1 to 2 bar). If the hydraulic pressure is insufficient, replenish water.
• Heating operation starts. Check that the hydro unit starts heating.
• Press the OPERATE MODE
• Cooling operation starts. Check that the hydro unit starts cooling and that the floor heating system is not cooled.
• Press the ZONE1, 2
• Press the HOT WATER
• Check that there is no air bite.
• Check that hot water is present at the connection port of the hot water cylinder.
button and select “heating” with the OPERATE MODE button.
button and select “cooling.”
button to stop operation.
button to start hot water supply operation.
• Press the HOT WATER
• Press the TEST button to exit the test mode.
button to stop the hot water supply operation.
Quick Reference Guide - Page 28
Sensor Temperature Monitoring Function
The sensor sensing temperature is displayed on the remote controller. This function allows you to make sure whether the sensor is installed properly.
1) Press the TEST + CL buttons for four seconds or more.
2) Select the Code No. with the TEMP. buttons.
3) Press the TEST button to exit the test mode.
Code No. Location Indication
06
08
09 Hydro unit 2-zone sensor temperature °C
0A
0B
60
61
62 Outdoor unit Refrigerant discharge temperature °C
63
6A
70
F4
F5 Operating hours Hot water cylinder heater total operating hours x100 hours
F6
Return water temperature °C
Hot water temperature °C
Hot water cylinder temperature sensor °C
Motorized mixing valve position
Heat exchanger temperature °C
Outside air temperature °C
Refrigerant intake temperature °C
Current value (in the inverter) A
Compressor operating frequency
Hydro unit AC pump total operating hours x100 hours
Hydro unit heater total operating hours x100 hours
Fault Symptoms
Symptom Possible cause Corrective action
Room is not heated or cooled. Water is not hot enough.
Nothing is displayed on the remote controller.
Flow rate switch is activated. Error code [A01]
Hot water leaks from pressure relief valve.
Incorrect remote controller setting
Incorrect function code setting
Backup heater disconnected Check backup heater and bimetal thermostat.
Insufficient capacity Check selection of equipment.
Sensor defect
Power is not supplied. Check power supply wiring.
Incorrect setting
Air bite in the pump Release air completely according to the procedure.
Low hydraulic pressure
Strainer is clogged. Clean the strainer.
Large resistance on the hydro side
Malfunction of motorized 3-way valve for hot water supply
Excessive hydraulic pressure
Insufficient capacity of expansion tank
Expansion tank failure Check the air pressure.
Check remote controller operation and temperature setting
Check function code setting with the function code table.
Check whether temperature sensor is installed at the normal position.
Check DIP switch setting on the Hydro Unit board. Check the setting with the function code table.
Set hydraulic pressure considering pipe height, and replenish water until manometer shows a value of set hydraulic pressure or more.
Widen water path to the hydro unit or adopt a bypass valve.
Check wiring and parts.
Set hydraulic pressure considering pipe height, and replenish water until manometer shows a value of set hydraulic pressure or more. Check expansion tank capacity compared to total water amount. If it is insufficient, install another expansion tank.
Alarm Indications
Quick Reference Guide - Page 29
Alarm
indication
Regular communication error between hydro unit and remote controller (system controller) If there is no
E03
E04
F03 If short-circuit or open-circuit state continues for two seconds, an alarm occurs.
Auto-reset: When normal value is confirmed
F10 If short-circuit or open-circuit state continues for two seconds, an alarm occurs.
Auto-reset: When normal value is confirmed
F11 If short-circuit or open-circuit state continues for two seconds, an alarm occurs.
Auto-reset: When normal value is confirmed
F14 If short-circuit or open-circuit state continues for two seconds, an alarm occurs.
Auto-reset: When normal value is confirmed
F17 If short-circuit or open-circuit state continues for two seconds, an alarm occurs.
Auto-reset: When normal value is confirmed
F18 If short-circuit or open-circuit state continues for two seconds, an alarm occurs.
Auto-reset: When normal value is confirmed
F23 If open-circuit state continues for two seconds, an alarm occurs.
Auto-reset: When normal value is confirmed
F29
(When EEPROM1K is mounted, this alarm cannot be reset.)
F20
regular communication from the remote controller for three minutes, the hydro unit regards it as no remote controller. If there is no communication from both sides, alarm E03 occurs. Auto-reset: When successful regular communication is made Regular communication error between hydro unit and outdoor unit When serial signal from the outdoor unit cannot be received though normal serial signal is sent to the outdoor unit 1) When serial signal cannot be received continuously for 60 seconds (S code communication) 2) Communication is still not successful for 80 seconds through three retries if serial signal cannot be received for 20 seconds after new communication (f code) starts When the remote controller starts operation, serial transmission starts with the new communication format. Auto-reset: When successful regular communication is made
Condensing temperature TC sensor defect
Hydraulic heat exchanger inlet temperature TWI sensor defect
Hydraulic heat exchanger outlet temperature TWO sensor defect
Hot water cylinder temperature TTW sensor defect
Floor inlet temperature TFI sensor defect
Internal heater outlet temperature TWO sensor defect
Low-pressure sensor defect
Hydraulic heat exchanger EEPROM defect One mismatch is detected if there is no verification ACK after data write to the EEPROM Reset condition: This alarm is inhibited while the unit is not working.
Floor inlet temperature TFI sensor disconnection or wrong installation (This alarm is reset by stopping operation and is checked again.)
Alarm description and generation/reset conditions
F30 Onboard expansion IC defect This alarm is not reset automatically.
L07
This alarm is not reset automatically. (This alarm is inhibited while the unit is not working, but occurs
L09
A01 Pump defect or abnormal flow rate This alarm is not reset automatically.
A02 Excessive water temperature increase by the heating heater Auto-reset:
A03 Excessive water temperature increase in the hot water cylinder
A04 Freezing is detected. Auto-reset:
A07 High-pressure switch malfunction This alarm is not reset automatically.
A08 Low-pressure sensor malfunction This alarm is not reset automatically.
Group line in an hydro unit This alarm is checked during initial communication immediately after power-on. This alarm occurs immediately after operation start.
again after the unit operates.) Hydro unit capacity has not been set. This alarm is checked immediately after power-on. This alarm is not reset automatically. (This alarm is inhibited while the unit is not working, but occurs again after the unit operates.)
Quick Reference Guide - Page 30
Alarm Indications (cont)
A09 Overheat preventive operation malfunction Auto-reset: When operation mode is changed
A11
P31
Release preventive operation malfunction This alarm occurs when the Hydro Unit enters the forced­stop zone 10 times.
Self-hydro unit is stopped due to alarm of other hydro unit. When alarm occurs in an hydro unit in the group, other hydro units must also be stopped with refrigerant control. When alarm E03, L03 or L07 occurs in the header unit in the group, other hydro units must also be stopped because they do not know which header unit (remote controller) to follow. Auto-reset: When the first alarm is reset
Outdoor Alarm indication
Alarm
indication
F04
F06
F08
H01 Compressor breakdown
H02 Compressor locked When compressor lock is detected
H03 Current detector defect
H06 Low-pressure system defect Ps pressure sensor defect or low-pressure protective operation
L29 Other outdoor unit faults
L31 Phase sequence error, etc.
P03
P04
P22 Outdoor unit fan defect When over current or lock in outdoor unit fan drive circuit is detected
P26 Inverter Idc operation
P29 Position detection error When compressor motor position detection error is detected
Main failure part Description
Outdoor unit discharge temperature sensor TD defect
Outdoor unit temperature sensor TE or TS defect
Outdoor unit outside air temperature sensor TO defect
Abnormal outdoor unit discharge temperature
High-pressure system defect
When open- or short-circuit of discharge temperature sensor TD is detected
When open- or short-circuit of heat exchanger temperature sensor TE or TS is detected
When open- or short-circuit of outside air temperature sensor TO is detected
When min-Hz is reached by current release control or when short­circuit current (Idc) is detected after direct current excitation
When abnormal current is detected in AC-CT or phase loss is detected
Other outdoor unit faults: 1) Inter-MCU communication error between IPDU and CDB 2) abnormal GBT heat sink temperature
When phase sequence of 3-phase power supply is incorrect (thermostat OFF operation continued), etc.
When abnormal temperature is detected by discharge temperature release control
When high-pressure switch , IOL is activated or when abnormality is detected by high-pressure release control by TE
When short-circuit protection is activated for compressor driver devices (G-Tr, IGBT)
Quick Reference Guide - Page 31
A
Outdoor Fault Diagnosis
You can perform fault diagnosis of the outdoor unit with the LED's on the P.C. board of the outdoor unit in addition to check codes displayed on the wired remote controller of the hydro unit. Use the LED’s and check codes for various checks.
Check of the current abnormal status
1. Check that DIP switch SW803 is set to all OFF.
2. Jot down the states of LED800 to LED804. (Display mode 1)
3. Press SW800 for at least one second. The LED status changes to display mode 2.
4. Check the code whose display mode 1 equals the jotted LED status and display mode 2 equals the current flashing status of LED800 to LED804 from the following table to identify the cause.
Check of the abnormal status in the past although the abnormal status is not occurred now.
1. Set bit 1 of DIP switch SW803 to ON.
2. Jot down the states of LED800 to LED804. (Display mode 1)
3. Press SW800 for at least one second. The LED status changes to display mode 2.
4. Find an error whose display mode 1 equals the jotted LED status and display mode 2 equals the current flashing status of LED800 to LED804 from the following table to identify the error.
• An outside air temperature (TO) sensor error can be checked only while
an error occurs.
DISPLAY MODE 1 DISPLAY MODE 2
No. Cause D800 D801 D802 D803 D804 D800 D801 D802 D803 D804
1 Normal 2 Discharge sensor (TD) error 3 Heat exchanger sensor (TE) error 4 Heat exchanger sensor (TL) error
Outside air temperature sensor (TO)
5
error
6 Suction sensor (TS) error 7 Heat sink sensor (TH) error
Outdoor temperature sensor (TE/TS)
8
connection error
9 Outdoor EEPROM error 10 Compressor lock 11 Compressor lock 12 Current detect circuit error 13 Thermostat for compressor activated
Model data not set (on the service P.C.
14
board)
15 MCU-MCU communication error 16 Discharge temperature error
bnormal power (open phase detected
17
or abnormal voltage) 18 Heat sink overheat 19 refrigerant leak detected 20 4-way valve reverse error 21 High pressure release operation 22 Outdoor fan motor error
Compressor driver short circuit 23
protection
Position detect circuit error in one-line 24
display
● ○ ● ○ ● ○
● ○
● ○ ● ○
◎ ○
● ○
● ○ ◎ ○ ◎ ○
: ON
: OFF
: FLASHING
Loading...