Please follow the instructions in this manual to obtain the optimum results from this unit.
We also recommend that you keep this manual handy for future reference.
Be sure to leave system installations, adjustments, and data settings to the dealer from whom
you have purchased.
VS-900SC Site Connector ......................................................................................... 56
YC-303 Main Frame Wall Mounting Bracket .............................................................. 56
Page 4
4
When Installing the Unit
[Applicable to the exchange and the station]
• Do not expose the unit to rain or an environment
where it may be splashed by water or other liquids,
as doing so may result in fire or electric shock.
• Do not cut, kink, otherwise damage nor modify the
power supply cord and connection cord. In
addition, avoid using the cords in close proximity to
heaters, and never place heavy objects -- including
the unit itself -- on the cords, as doing so may
result in fire or electric shock.
[Applicable to the exchange]
• Use the unit only with the voltage specified on the
unit. Using a voltage higher than that which is
specified may result in fire or electric shock.
• Be sure to ground to the safety ground (earth)
terminal to avoid electric shock. Never ground to a
gas pipe as a catastrophic disaster may result.
• Owing to the unit's size and weight, be sure that at
least two persons are available to install the unit.
Failure to do so could result in personal injury.
• (When mounted on a wall)
Refer all installation work to the dealer from whom
the unit was purchased. Installation requires
extensive technical knowledge and experience.
The unit may fall off if incorrectly installed, resulting
in possible personal injury.
• (When mounted on a wall)
Install the unit only in a location that can
structurally support the weight of the unit and the
mounting bracket. Doing otherwise may result in
the unit falling down and causing personal injury
and/or property damage.
When the Unit is in Use
[Applicable to the exchange]
• Should the following irregularity be found during
use, immediately switch off the power, disconnect
the power supply plug from the AC outlet and
contact your nearest TOA dealer. Make no further
attempt to operate the unit in this condition as this
may cause fire or electric shock.
· If you detect smoke or a strange smell coming
from the unit.
· If water or any metallic object gets into the unit
• To prevent a fire or electric shock, never open nor
remove the unit case as there are high voltage
components inside the unit. Refer all servicing to
your nearest TOA dealer.
• Do not place cups, bowls, or other containers of
liquid or metallic objects on top of the unit. If they
accidentally spill into the unit, this may cause a fire
or electric shock.
• Do not touch the power cord during thunder and
lightning, as this may result in electric shock.
WARNING
Indicates a potentially hazardous situation which, if mishandled, could
result in death or serious personal injury.
Indicates a potentially hazardous situation which, if mishandled, could
result in moderate or minor personal injury, and/or property damage.
WARNING
CAUTION
1. SAFETY PRECAUTIONS
• Before installation or use, be sure to carefully read all the instructions in this section for correct and safe
operation.
• Be sure to follow all the precautionary instructions in this section, which contain important warnings and/or
cautions regarding safety.
• After reading, keep this manual handy for future reference.
Safety Symbol and Message Conventions
Safety symbols and messages described below are used in this manual to prevent bodily injury and property
damage which could result from mishandling. Before operating your product, read this manual first and
understand the safety symbols and messages so you are thoroughly aware of the potential safety hazards.
Page 5
5
When Installing the Unit
[Applicable to the exchange and the station]
• Avoid installing the unit in humid or dusty locations,
in locations exposed to the direct sunlight, near the
heaters, or in locations generating sooty smoke or
steam as doing otherwise may result in fire or
electric shock.
[Applicable to the exchange]
• Do not block the ventilation slots in the unit's cover.
Doing so may cause heat to build up inside the unit
and result in fire.
When the Unit is in Use
[Applicable to the exchange]
• Do not place heavy objects on the unit as this may
cause it to fall or break which may result in
personal injury and/or property damage. In
addition, the object itself may fall off and cause
injury and/or damage.
• Contact your TOA dealer as to the cleaning. If dust
is allowed to accumulate in the unit over a long
period of time, a fire or damage to the unit may
result.
CAUTION
Page 6
6
WARNING (For U.S.A. only)
This equipment generates, uses, and can radiate radio frequency energy and, if not installed and
used in accordance with the instructions manual, may cause interference to radio communications. It
has been tested and found to comply with the limits for a Class A computing device pursuant to
Subject J of Part 15 of the FCC Rules, which are designed to provide reasonable protection such
interference when operated in a commercial environment.
Operation of this equipment in a residential area is likely to cause interference, in which case the user
at his own expense will be required to take whatever measures may be required to correct the
interference.
2. FCC REQUIREMENTS
(1) This equipment compiles with Part 68 of the FCC rules. On the front panel of this equipment is a label that
contains, among other information, the FCC registration number and ringer equivalence number (REN) for
this equipment. If requested, this information must be provided to the telephone company.
(2) USOC Jack RJ11C or RJ11W
(3) This Equipment is designed to be connected to the telephone network or premises wiring using a
compatible modular jack that is Part 68 compliant. See this manual (VS-900 INSTALLATION MANUAL)
for details.
(4) The REN is used to determine the quantity of devices that may be connected to the telephone line.
Excessive REN's on the telephone line may result in the devices not ringing in response to an incoming
call. Typically, the sum of REN's should not exceed five (5.0). To be certain of the number of devices that
may be connected to a line (as determined by the total REN's), contact the local telephone company.
(5) If this equipment VS-900 causes harm to the telephone network, the telephone company will notify you in
advance that temporary discontinuance of service may be required. But if advance notice isn't practical,
the telephone company will notify the customer as soon as possible. Also, you will be advised of your right
to file a complaint with the FCC if you believe it is a necessary.
(6) The telephone company may make changes in it's facilities, equipment, operations, or procedures that
could affect the operation of the equipment. If this happens, the telephone company will provide advance
notice in order for you to make the necessary modifications in order to maintain uninterrupted service.
(7) If trouble is experienced with this equipment VS-900, please contact TOA Electronics, Inc., 601 Gateway
Boulevard, Suite 300, South San Francisco, CA. 94080, phone (650) 588-2538 for repair and warranty
information. If the trouble is causing harm to the telephone network, the telephone company may request
you remove the equipment from the network until the problem is resolved.
(8) This equipment may not be used on coin service provided by the telephone company. Connection to party
lines is subject to state tariffs.
(9) This equipment is hearing aid compatible.
Page 7
7
3. INDUSTRIAL CANADA REQUIREMENTS
EQUIPMENT ATTACHMENT LIMITATIONS
"NOTICE: The Industry Canada label identifies certified equipment. This certification means that the
equipment meets telecommunications network protective, operational and safety requirements as prescribed
in the appropriate Terminal Equipment Technical Requirements document(s). The Department does not
guarantee the equipment will operate to the user's satisfaction.
Before installing this equipment, users should ensure that it is permissible to be connected to the facilities of
the local telecommunications company. The equipment must also be installed using an acceptable method of
connection. The customer should be aware that compliance with the above conditions may not prevent
degradation of service in some situations.
Repairs to certified equipment should be coordinated by a representative designated by the supplier. Any
repairs or alterations made by the user to this equipment, or equipment malfunctions, may give the
telecommunications company cause to request the user to disconnect the equipment.
Users should ensure for their own protection that the electrical ground connections of the power utility,
telephone lines and internal metallic water pipe system, if present, are connected together. This precaution
may be particularly important in rural areas.
Caution: Users should not attempt to make such connections themselves, but should contact the appropriate
electric inspection authority, or electrician, as appropriate."
"NOTICE: The Ringer Equivalence Number (0.4) assigned to each terminal device provides an indication of
the maximum number of terminals allowed to be connected to a telephone interface. The termination on an
interface may consist of any combination of devices subject only to the requirement that the sum of the Ringer
Equivalence Numbers of all the devices does not exceed 5."
RESTRICTIONS CONCERNANT LE RACCORDEMNT DE MATÉRIEL
"AVIS: L'étiquette d'Industrie Canada identifie le matériel homologué. Cette étiquette cetifie que le matériel est
conforme aux normes de protection, d'exploitation et de sécurité des réseaux de télécommunications, comme
le prescrivent les documents concernant les exigences techniques relatives au matériel terminal. Le Ministère
n'assure toutefois pas que le matériel fonctionnera à la satisfaction de l'utilisateur.
Avant d'installer ce matériel, l'utilisateur doit s'assurer qu'il est permis de le raccorder aux installations de
l'entreprise locale de télécommunication. Le matériel doit également être installé en suivant une méthode
acceptée de raccordement. L'abonné ne doit pas oublier qu'il est possible que la conformité aux conditions
énoncées ci-dessus n'empêche pas la dégradation du service dans certaines situations.
Les réparations de matériel homologué doivent être coordonnées par un représentant désigné par le
fournisseur. L'entreprise de télécommunications peut demander à l'utilisateur de débrancher un appareil à la
suite de réparations ou de modifications effectuées par l'utilisateur ou à cause de mauvais fonctionnement.
Pour sa propre protection, l'utilisateur doit s'assurer que tous les fils de mise à la terre de la source d'énergie
électrique, des lignes téléphoniques et des canalisations d'eau métalliques, s'il y en a, sont raccordés
ensemble. Cette précaution est particulièrement importante dans les régions rurales.
Avertissement: L'utilisateur ne doit pas tenter de faire ces raccordements lui-même; il doit avoir recours à un
service d'inspection des installations électriques, ou à un électricien, selon le cas."
"AVIS: L'indice d'équivalence de la sonnerie (0.4) assigné à chaque dispositif terminal indique le nombre
maximal de terminaux qui peuvent être raccordés à une interface. La terminaison d'une interface téléphonique
peut consister en une combinaison de quelques dispositifs, à la seule condition que la somme d'indices
d'équivalence de la sonnerie de tous les dispositifs n'excède pas 5."
This Class A digital apparatus complies with Canadian ICES-003.
Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada.
Page 8
8
4. GENERAL DESCRIPTION
The VS-900 Security System is a voice communication system that permits calls to be quickly and easily
made - even in emergency situations - with the touch of single button. The system can record conversations,
and features external equipment sync output and operation log output. These features combine to make the
VS-900 an ideal system for voice security applications.
5. FEATURES
• Modular construction facilitates installation, maintenance, and system expansion.
• Rack- or wall-mountable exchange.
• Up to 4 master stations (or commercial telephone sets) and 64 substations can be connected per exchange.
• Up to 2 outside telephone (C/O) lines can be connected per exchange.
• Station paging (by means of the substation speaker) and external paging functions.
• External sound source distribution capability.
• Up to 19 paging zones can be established.
• Emergency Paging function.
• By connecting an external recording device, the conversations at the master station (or telephone set) and
at the outside line telephone can be recorded.
• Exchange operating log can be transmitted to a PC.
• Tie-line possible for up to 16 exchanges.
• 24 V DC input for connection of backup power supply.
• Make sure that the power is switched OFF during installation work. Switch on the power after the installation
work is completed.
• To prevent the unit's failure, be sure to switch off its power when inserting or removing the card.
• When mounting each card, fully insert it into the Main Frame. After all cards are mounted, secure them with
the card fixing bracket.
• Do not use the unit near heaters or in locations exposed to sunlight. The unit's plastic parts may be
deformed or its finish discolored.
• Avoid installing the unit in humid or dusty locations, as doing otherwise may cause the unit's failure.
• When the unit gets dirty with dust or oil, wipe down with a soft, dry cloth. Never use a chemically-treated
cleaning cloth or volatile liquids, such as benzine and thinner, because the unit's plastic parts may be
deformed or its finish discolored.
Page 9
9
7. SYSTEM CONFIGURATION AND EQUIPMENT FUNCTIONS
7.1. System Configuration
VS-900 Exchange (1)
Rack Mount Panel
PN-100B
Power Transformer
Uint PU-200
Power Transformer
Uint PU-200
Main Frame VS-900MF/
Main Frame Mounting
Bracket YC-303
Master Station
Interface Card
VS-900MS (1)
Telephone Interface
Card VS-900AL (2)
Substation Interface
Card VS-900RS (1)
Substation Interface
Card VS-910RS (4)
Outside Line
Interface Card
VS-900CO
Master station MS-900 (2 units)
Recording voice output (for each station)
Recording control output (for each station)
Telephone (2 units)
Recording voice output (for each telephone)
Recording control output (for each telephone)
Substation RS-150, RS-160, RS-170 or
RS-180 (16 units)
Paging output (to an amplifier)
Paging input (from an amplifier)
Full-duplex substation RS-190* (16 units)
* The RS-191 is connectable.
Outside line (2 lines)
Recording voice output (for each line)
Recording control output (for each line)
VS-900 Exchange (2)
VS-900 Exchange (16)
Audio Function Card
VS-900AF
Tie-line Interface
Card VS-900TI
External paging voice output
External paging control output (16 channels)
Voice input for external source distribution
Control input for external source distribution
(4 channels)
Input and output for exchange interconnection
(4 voice lines, 1 data line)
Page 10
10
7.2. Equipment Functions
• VS-900MF Main Frame
The VS-900MF accommodates the following cards: Up to 2 VS-900MS or VS-900AL Cards (both cards may
be mixed), up to 4 VS-900RS or VS-910RS Cards (both cards may be mixed), 1 VS-900CO Card, 1 VS900AF Card, and 1 VS-900TI Card.
The Main Frame has 2 RS-232C ports; one for programming and the other for operation log output.
• VS-900MS Master Station Interface Card
The VS-900MS is used for master station connection. Up to 2 master stations can be connected per card,
and an external recording device can be connected to each line.
• VS-900AL Telephone Interface Card
The VS-900AL is used for connecting telephone sets (in compliance with the FCC Regulation Part 68). Up to
2 telephones can be connected per card, and an external recording device can be connected to each line.
• VS-900RS Substation Interface Card
The VS-900RS is used for substation connection. Up to 16 substations can be connected per card. The
Substation Interface Card has 2 speech links, one of which also functions as a paging link with the paging
input/output connected to an external amplifier.
• VS-910RS Substation Interface Card
The VS-910RS is used for connecting full-duplex substations and option handsets. Up to 16 substations can
be connected per card. The Substation Interface Card has 2 speech links, one of which also functions as a
paging link with the paging input/output connected to an external amplifier.
• VS-900CO Outside Line Interface Card
The VS-900CO is used for outside line connection. Up to 2 outside lines can be connected per card, and an
external recording device can be connected to each line.
• VS-900AF Audio Function Card
The VS-900AF enables Conference, External Amplifier Paging, and External Source Distribution functions.
The Audio Function Card has 1 conference link (maximum 4 stations), 1 audio output and 16 control outputs
for external amplifier paging, and 1 audio input and 4 control inputs for external source distribution.
• VS-900TI Tie-Line Interface Card
The VS-900TI is used to interconnect multiple exchanges. The Tie-Line Interface Card can connect up to 4
links made up by 1 pair of data lines and 2 pairs of voice lines.
• VS-900SC Site Connector
When tie-line connecting VS-900 system exchanges, fiber optic cables can be used to extend the audio line
longer than the maximum distance* possible using twisted pair cable. TOA's VS-900 Site Connector is used
to connect the VS-900 system exchanges to the fiber optic interface as shown in the following figure.
* 1.5 km when an AWG20 twisted pair cable is used.
• PU-200 Power Transformer Unit
The wall-mountable PU-200 has 2 20V/2.5A AC outputs. One PU-200 unit is required when up to 2
VS-900RS Cards are installed, and 2 PU-200 units are required when 3 or more VS-900RS Cards are
installed.
• YC-303 Main Frame Wall Mounting Bracket
The YC-303 is used when mounting the main frame on the wall.
• PN-100B Rack Mount Panel
The PN-100B provides side-by-side rack mounting capability for up to 2 PU-200 transformer units.
• MS-900 Master Station
The MS-900 can make calls to or receive calls from the substation. It utilizes 2 pairs of twisted cables.
• RS-150 Substation (Indoor Type)
The RS-150 can call and converse with the registered master stations. It utilizes a single-pair shielded cable.
Page 11
11
• RS-160 Substation (Indoor Vandal-Resistant Type)
The RS-160 can call and converse with the registered master stations. It utilizes a single-pair shielded cable.
• RS-170 Substation (Outdoor Vandal-Resistant Type)
The RS-170 can call and make converse with the registered master stations. It utilizes a single-pair shielded
cable.
• RS-180 Substation (for Emergency Use)
The RS-180 can call and converse with the registered master stations. It has an indicator lamp and a control
output channel, and utilizes a single-pair shielded cable.
• RS-190 Substation (Full-Duplex Type)
The RS-190 can call and converse with the registered master stations. It has an indicator lamp and a control
output channel, and utilizes 2 pairs of twisted cables.
• RS-191 Option Handset (Indoor Type)
The RS-191 is used in combination with the RS-190. Lifting the handset permits handset conversation.
Page 12
12
8. VS-900MF MAIN FRAME NOMENCLATURE AND FUNCTIONS
1. AC Input Connectors
Connect to the AC output terminal of the PU-200
power transformer unit. (See p. 46.)
2. 24 V DC Input Connector
Connects to a battery (24 V DC). (See p. 46.)
3. Power Switch
Power is switched on (I) and off (O) with each
depression of this switch.
4. Backup Battery Socket
Insert the CR2032 data backup battery into this
socket. (See p. 22.)
10.1.2. Wall mounting (Optional YC-303 Wall Mounting Frame is required.)
Step 1. Mount the YC-303 bracket to the wall.
Step 2. Remove the VS-900MF's front panel, then mount the VS-900MF on the YC-303.
78 78 7855.2
Knockout (for wiring)
391.4
440.6
Wood screw 5.1 x 38
(accessory)
Mounting dimensions
290
Unit: mm
30
200
141.3
Tapping screw 4 x 12
(supplied with the YC-303)
Page 16
16
10.2. PU-200 Power Transformer Unit
10.2.1. Rack mounting
Step 1. Remove the 4 mounting screws, and attach the supplied wall mounting brackets to the transformer
unit using the removed screws.
Step 2. Attach the PU-200 to the PN-100B Rack Mount Panel.
Step 3. Mount the PN-100B in an equipment rack.
Note
Perform terminal wiring before mounting.
Wall mounting bracket (accessory)
Mounting screw
PN-100B
Flange nut M3
(supplied with the PN-100B)
PU-200
Fiber washer
(supplied with the PN-100B)
Machine screw M3 x 8
(supplied with the PN-100B)
Binding head self tapping screw 5 x 12
(supplied with the PN-100B)
Page 17
17
10.2.2. Wall mounting
Step 1. Remove the 4 mounting screws, and attach the supplied wall mounting brackets to the transformer
using the removed screws.
Step 2. Fix the unit on the wall. Use the supplied wood screws (3.5 x 25) as appropriate for mounting.
Wall mounting bracket (accessory)
Mounting screw
140
Wood screw 3.5 x 25
(accessory)
120
Unit: mm
11525
Page 18
18
10.3. RS-150, RS-160, RS-170, RS-180 and RS-190 Substations
Mount the substation to an electrical box mounted in the wall.
Dimensional diagram
Accessory screws
The RS-150, RS-160, RS-170, RS-180 and RS-190 come with 2 types of screws: oval head combination
screw M4 x 25 and oval head slotted screw UNC No.6 x 18.
For the electrical box provided with unified threads, use the oval head slotted screws UNC No.6 x 18.
2-gang electrical box
YC-302 (optional)
RS-150/-160/-170/-180/-190
Oval head combination screw
M4 x 25 (accessory)
Unit: mm
120
83.5
1
46
120
37
18.2
52.5
*
2, *3
1
3
*
2 (RS-150, RS-190)
*
2
43.5 (RS-150)
*
3
53 (RS-190)
*
Page 19
19
10.4. RS-191 Option Handset (Indoor type)
10.4.1. Wall mounting
Mount the option handset to an electrical box mounted in the wall.
10.4.2. RS-190 and RS-191 connection
Plug out the jumper from the connector on the RS-190's side panel, then plug the RS-191's connection cable
instead as illustrated below.
Accessory screws
The RS-191 comes with 2 types of screws: oval head
combination screw M4 x 25 and oval head slotted screw
UNC No.6 x 18.
For the electrical box provided with unified threads, use
the oval head slotted screws UNC No.6 x 18.
2-gang electrical box
YC-302 (optional)
Oval head combination screw
M4 x 25 (accessory)
RS-191
Connection cable
RS-191
RS-190
Jumper
Page 20
20
10.5. Master Station
10.5.1. Desk-top mounting
Connect the supplied modular-plug cord.
10.5.2. Wall mounting
Pull out, rotate, and reset the cradle hook, then mount the station on the wall using the supplied wall mounting
frame. Use the supplied wood screws as appropriate.
Remove the cradle hook.
Cradle hook
Pull out the cradle hook, then
replace it after changing the
direction as illustrated.
Wood screw 3.5 x 25
(supplied with the MS-900)
Page 21
21
10.6. VS-900SC Site Connector
10.6.1. Rack mounting
10.6.2. Mounting to the VS-900MF
10.6.3. Wall mounting
* Use the supplied wood screws as
appropriate.
When using them, mount the unit to
wooden walls stronger than plywood of
over 12 mm in thickness.
VS-900SC
POWER
SITE CONNECTOR VS-900SC
Tapping screw 3 x 12 (accessory)
Rack-mounting bracket (accessory)
Fiber washer M5 (accessory)
Rack mounting screw 5 x 12 (accessory)
VS-900SC
POWER
SITE CONNECTOR VS-900SC
Link plate (accessory)
VS-900MF
Tapping screw 3 x 12 (accessory)
Screw 4 x 12 (accessory)
VS-900SC
Wall-mounting bracket (accessory)
Tapping screw 3 x 12 (accessory)
Wood screw 4.1 x 20 (accessory) *
Page 22
22
11. VS-900MF CARD INSTALLATION
11.1. Backup Battery Installation
Caution
All cards contain many CMOS ICs which are easily damaged by static electricity. Do not touch circuit
components.
• Insert the backup battery into the Main Frame mother board before installing any cards.
CR2032
BATT1
VS-900MF
Danger of explosion if battery is incorrectly replaced.
Replace only with the same or equivalent type recommended by the manufacturer.
Dispose of used batteries according to the manufacturer's instructions.
CAUTION
Danger d'explosion lorsque la batterie n'est pas remplacée correctement.
Remplacer uniquement avec des batteries identiques ou d'un type équivalent.
ATTENTION
Battery replacement
As the battery life is rated at about 4 years, replace it with a new one every 4 years.
Follow the replacement procedure below.
Step 1. Switch the Main Frame (VS-900MF) power off.
Step 2. Remove all installed cards.
Step 3. Switch the VS-900MF power on.
Step 4. Replace the battery.
Step 5. Switch the VS-900MF power off.
Step 6. Reinstall the removed cards.
Step 7. Switch the VS-900MF power on.
Important
Be sure to replace the battery while the VS-900MF power is on.
Otherwise, stored date and time data will be lost.
Page 23
23
11.2. Card Installation
Step 1. Remove each card from its static-protective bag, and install it in its designated position in the Main
Frame.
• For the VS-900TI, perform exchange number setting BEFORE installation. Refer to p. 42 "Exchange
Number Setting."
Step 2. After installing all cards, secure them using the supplied fixing bracket.
The top and side panels are omitted to
show the hidden parts.
Page 24
24
12. WIRING
12.1. Wiring from the Station or Outside Line
Step 1. Remove the main frame's bottom panel as shown below.
Step 2. Connect stations or outside lines to their respective cards as shown below.
Page 25
25
12.2. Supplied Connector Connection
Use the supplied connectors for exchange connections as follows.
Step 1. Insert a cable into the connector and tighten the screw.
Step 2. After cable connection is completed, press the connector onto the circuit board's connector.
Page 26
26
12.3. VS-900MS Master Station Interface Card Connection
12.3.1. Master Station and VS-900MS connection
• The VS-900MS can be interfaced with up to 2 MS-900 master stations.
• Because up to 2 VS-900MS cards can be mounted in the VS-900MF Main Frame, up to four master stations
can be connected per frame.
• A station address must be assigned to each connected MS-900 station. Set the station address at each MS900 station after switching ON the power.
[Station Address Setting]
Step 1. Set the Master Station's REGISTER switch to the ON position. The "Reg_mode" indication will be
displayed on the station screen.
Step 2. Press the [XFER] key.
Step 3. According to the following table, enter the station address 1 – 4 through the use of a numeric keypad.
VS-900MSLineStation Address
MS/AL Slot 1
11
22
MS/AL Slot 2
13
24
Step 4. Press the [PTT] key.
Step 5. Set the REGISTER switch to the OFF position to places the station in standby mode.
A
Numeric keys
[0] – [9]
View
ABC
DEF
12
2
13
JKL4GHI6MNO
34
5
TUV7PRS9WXY
56
8
OPER
78
0
#
P T TREDIAL XFER
C
Display panel
Transfer [XFER] key
Press-to-talk [PTT] key
[View ]
A
HANDSET
REGISTER
Do not connect thei jack
to telephone line.
SP. VOL.
OFF ON
MINI. MAX.
LINE
Registration ON/OFF switch
[REGISTER ON/OFF]
Page 27
27
[Connection]
• Connect the MS-900 to the VS-900MS using 2 twisted pair cables as shown below referring to the following
procedures.
1. Fit the 4P connector (supplied with the VS-900MS) to one cable end, and a 6-position 4-contact modular
jack (prepare locally) to the other cable end.
2. Connect the modular jack to the MS-900's modular jack using the modular cord (supplied with the MS-900).
• The table below shows the maximum cable distance.
Cable type AWG24 (0.52 mm)AWG22 (0.65 mm)AWG20 (0.82 mm)
Distance0.9 km1.5 km2.3 km
Connect as shown below.
VS-900MS and MS-900 connection
* Mount the ferrite clamp (supplied with the VS-900MS card)
on the cable in a way that the cable is looped one turn as
illustrated. (This countermeasure is for complying with the
CE marking and FCC requirements.)
Note
When using a shielded cable, connect the shielded wire to the "FG" terminal of the exchange main frame.
Also, connect the unused cables, if included in a bundle of cables, to the same terminal.
Ferrite clamp *
2 twisted pair cables
VS-900MS
CN1
Line 1
for master station
1
2
3
4
LINE
1234
Modular cord
(supplied with
the MS-900)
2 twisted pair cables
LINE
1234
Modular cord
(supplied with the MS-900)
Ferrite clamp *
CN2
CN3
CN4
Line 2
for master station
Front view of
the circuit board
1
2
3
4
Ferrite clamp
SFC-10
VS-900MS card
Page 28
28
12.3.2. External recording device and VS-900MS connection
An external recording device can be connected to each master station line.
[Connection]
To connect the external recording device, use a twisted pair cable for audio output, and a twisted pair cable
for control output. The audio output is 0 dB* and of unbalanced type. The control output is an open collector
output 20 mA, 24 V DC max. Connect as shown below.
* 0 dB = 1 V
External recording device and VS-900MS connection
VS-900MS
CN1
To audio input (HOT)
To audio input (GND)
To recording start input (HOT)
To recording start input (GND)
Recording device
Recording device
2 twisted pair cables
2 twisted pair cables
CN2
CN3
CN4
Line 1 for
recording
Line 2 for
recording
Front view of
the circuit board
HOT
Audio output
GND
HOT
Control output
GND
HOT
Audio output
GND
HOT
Control output
GND
Page 29
29
12.4. MS-900 Master Station Connection and Adjustment
12.4.1. External speaker connection
Follow the procedures below when connecting an external speaker (8 Ω).
Step 1. Remove the MS-900's rear terminal cover and set the internal slide switch to the [EXT. SP] position.
Terminal cover
EXT.SP terminal
Microphone sensitivity control
Internal speaker volume control
Internal/External speaker selection switch
Step 2. Connect the speaker cable to EXT.SP terminal.
Speaker cable
12.4.2. Internal speaker volume and microphone sensitivity adjustment
The MS-900's internal speaker volume and microphone sensitivity can be adjusted by means of their
respective controls located under the terminal cover described above. Both controls are factory-preset to their
maximum positions.
Step 3. Replace the removed terminal cover in place.
The VS-900AL can be interfaced with up to 2 commercial telephone sets. Use the telephone which complies
with the FCC Regulation Part 68.
[Connection]
To connect the telephone set to the VS-900AL, use a twisted pair cable. The connector of the cable end going
to the telephone needs to be the type that can be connected to the telephone connector. Perform wiring as
shown below so that the loop resistance is less than 500 Ω including the telephone resistance.
Telephone and VS-900AL connection
VS-900AL
CN1
CN2
CN3
CN4
1 twisted pair cable
1 twisted pair cable
Telephone set
Telephone set
Line 1
for telephone
Line 2
for telephone
Front view of
the circuit board
Ferrite clamp *
Ferrite clamp *
* Mount the ferrite clamp (supplied with the VS-900AL card) on the cable in a way that the cable is looped one
turn as illustrated. (This countermeasure is for complying with the CE marking and FCC requirements.)
Note
When using a shielded cable, connect the shielded wire to the "FG" terminal of the exchange main frame.
Also, connect the unused cables, if included in a bundle of cables, to the same terminal.
Ferrite clamp
SFC-10
VS-900AL card
Page 31
31
[Setting telephone's talking volume levels]
When the talking volume is low, set it using the switch SW101 (for Line 1) or SW201 (for Line 2) on the VS900AL card as illustrated below.
Setting of telephone volume switches on the VS-900AL card
VS-900AL
SW101
SW201
D210
D110
CN1
Telephone
volume
switch
Telephone's talking volume (Line 1)
Telephone's talking volume (Line 2)
Front view of
the circuit board
12
ON
12
ON
12
ON
Telephone's talking volume setting
Volume "low"
(Factory-preset)
Volume "middle"Volume "high"
Page 32
32
12.5.2. External recording device and VS-900AL connection
An external recording device can be connected to each telephone line.
[Connection]
To connect the external recording device, use a twisted pair cable for audio output, and a twisted pair cable
for control output. The audio output is 0 dB* and of unbalanced type. The control output is an open collector
output of 20 mA, 24 V DC max. Connect as shown below.
The VS-900RS can be interfaced with up to 16 substations.
[Connection]
Use a 2-core shield cable to connect the substation to the VS-900RS. Refer to the following table for the
maximum recommended cable length between the two.
Connection of the RS-150/-160/-170/-180 to the VS-900RS
RS-150, RS-160,
RS-170 or RS-180
To line A (orange)
To line B (brown)
To line C (black)
2-core shielded cable
2-core shielded cable
VS-900RS
CN1
CN2
CN3
CN4
Line 1
Line 2
Line 5
Line 6
Line 9
Line 10
Line 13
Line 14
Line 3
Line 4
Line 7
Line 8
Line 11
Line 12
Line 15
Line 16
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
A
B
C
Front view of
the circuit board
Note
The cables coming from the substations are bared at their ends.
Page 34
34
12.6.2. External amplifier and VS-900RS connection
Electrical characteristics of the CN5 connector
Voice output: Unbalanced, –20 dB*2signals to be sent to a paging amplifier
Voice input: Balanced, acceptable signals on the 25 V line output from a paging amplifier
*1Rated at over 16 W power output (ex. BG-130 30 W amplifier)
*20 dB = 1 V
The VS-910RS can be interfaced with up to 16 RS-190 Substations.
[Connection]
Use 2 pairs of twisted cables to connect the RS-190 and the VS-910RS. Refer to the following table for the
maximum recommended cable length between the two.
Never touch the SW301 switch
(factory-preset to OFF) on the
VS-910RS board.
VS-910RS
CN501
CN551
CN601
CN651
CN701
CN751
CN801
CN851
Line 1
Line 3
Line 5
Line 7
Line 9
Line 11
Line 13
Line 15
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
A
B
C
D
Line 2
Line 4
Line 6
Line 8
Line 10
Line 12
Line 14
Line 16
2 twisted pair cables
Lightening protector *
A
B
C
D
RS-190
A
B
C
D
Lightening protector *
* In case of outdoor aerial wiring, install the
unit near the VS-910RS.
Note
The cable length for outdoor wiring must not
exceed 42 m (140 feet).
The wiring installation shall refer to NEC
Articles 725 and 800.
Front view of
the circuit board
SW301
VS-910RS
Page 36
36
12.8. VS-900CO Outside Line Interface Card Connection
12.8.1. Outside line and VS-900CO connection
The VS-900CO can be interfaced with up to 2 outside lines. Using DTMF tone dialing, it is compatible with
both loop and ground start systems.
[Connection]
Connect as shown below.
Outside line and VS-900CO connection
1 twisted pair cable
1 twisted pair cable
VS-900CO
CN1
CN2
CN3
CN4
GND *1
GND
Front view of
the circuit board
Outside line
Line 1
GND *
1
GND
Outside line
Line 2
Lightening
protector *
2
Lightening
protector *
2
U.S.O.C. *
3
RJ11C or W
C/O Line 1
(or PBX
Extension)
C/O Line 2
(or PBX
Extension)
*1Ground this terminal only when using ground start system.
*2Install a protector if not yet installed by the telephone company.
*3This terminal must be installed by the telephone company.
Page 37
37
12.8.2. External recording device and VS-900CO connection
An external recording device can be connected to each telephone line.
[Connection]
To connect the external recording device, use a twisted pair cable for audio output, and a twisted pair cable
for control output. The audio output is 0 dB* and of unbalanced type. The control output is an open collector
output o f 20 mA, 24 V DC max. Connect as shown below.
* 0 dB = 1 V
External recording device and VS-900CO connection
VS-900CO
CN1
To audio input (HOT)
To audio input (GND)
To recording start input (HOT)
To recording start input (GND)
Recording device
Recording device
2 twisted pair cables
2 twisted pair cables
CN2
CN3
CN4
Line 1 for
recording
Line 2 for
recording
Front view of
the circuit board
HOT
Audio output
GND
HOT
Control output
GND
HOT
Audio output
GND
HOT
Control output
GND
Page 38
38
12.9. VS-900AF Audio Function Card Connection
12.9.1. Amplifier and VS-900AF connection
Paging can be provided through connected external amplifiers using the VS-900AF.
[Connection]
To connect the amplifier to the VS-900AF, use a twisted pair cable for audio output, and a twisted pair cable
for control output. The audio output is 0 dB* and of unbalanced type. The control output is an open collector
output of 20 mA, 24 V DC max., and permits connection of up to 16 channels. Connect as shown below.
* 0 dB = 1 V
External amplifier and VS-900AF connection
To audio input (HOT)
To audio input (GND)
VS-900AF
1 twisted pair cable
Amplifier(1)
Amplifier(2)
To start input (HOT)
To start input (GND)
Amplifier(15)
Amplifier(16)
1 twisted pair cable
CN4
CN5
CN6
CN7
CN8
Audio output
Control output 1
Control output 2
Control output 5
Control output 6
Control output 9
Control output 10
Control output 13
Control output 14
HOT
GND
HOT
GND
HOT
GND
HOT
GND
HOT
GND
HOT
GND
HOT
GND
HOT
GND
HOT
GND
Front view of
the circuit board
HOT
Control output 3
GND
HOT
Control output 4
GND
HOT
Control output 7
GND
HOT
Control output 8
GND
HOT
Control output 11
GND
HOT
Control output 12
GND
HOT
Control output 15
GND
HOT
Control output 16
GND
Page 39
39
12.9.2. External sound source and VS-900AF connection
The External Sound Source Distribution function can be operated using the VS-900AF.
[Connection]
To connect external sound sources to the VS-900AF, use a twisted pair cable for audio input, and a twisted
pair cable for control input (level-operated activation). The audio input is 0 dB* and of unbalanced type. The
start input is a no-voltage make contact of 20 mA, 24 V DC max. Connect as shown below.
Up to 16 exchanges can be tie-line interconnected using the VS-900TI card.
[Connection]
To interconnect the exchanges, use 2 twisted pair cables for lines, and a 2-core shielded cable for data lines.
A maximum of 4 lines can be connected. Refer to the following table for the maximum recommended length
for each cable type between exchanges.
(As to the cable connection, see the figure on the next page.)
When interconnecting three or more exchanges, change the SJP10 connection on each card as shown below,
with the exception of the cards in the rightmost and leftmost exchanges.
VS-900
VS-900TI
VS-900TI
VS-900TI
VS-900TI
VS-900TI
VS-900
VS-900
VS-900
SJP10
SJP10
SJP10
SJP10
SJP10
CN6
R26
SJP10
SW1
Two twist pair cables (voice line)
A 2-core shielded cable (data line)
Factory-preset status of SJP10Termination resistance setting when
interconnecting 3 or 4 exchanges
Page 41
41
Connect as shown below.
Exchange interconnection by means of VS-900TI
2 twisted pair cables
2 twisted pair cables
2 twisted pair cables
VS-900TI
CN1
CN2
CN3
Line 1
Line 2
Line 3
2 twisted pair cables
2-core shielded cable
2 twisted pair cables
2 twisted pair cables
2 twisted pair cables
2 twisted pair cables
CN4
CN6
VS-900TI
CN1
CN2
CN3
CN4
Line 4
Data line
RS-485
Line 1
Line 2
Line 3
Line 4
A
B
GND
GND
2-core shielded cable
CN6
Data line
RS-485
Front view of
the circuit board
A
B
GND
GND
Page 42
42
[Exchange Number Setting]
When interconnecting the exchanges using the VS-900TI, assign the exchange number to each exchange
with the SW1 switch located on the VS-900TI's circuit board. (Refer to the table below.)
Exchange No. setting
Initial status: Exchange No. 1
VS-900TI
CN6
SW1
18
Exchange No. 1
1
2
3
4
5
6
7
8
OFF
ON
OFF
ON
OFF
ON
OFF
ON
2
OFF
OFF
ON
ON
OFF
OFF
ON
ON
3
OFF
OFF
OFF
OFF
ON
ON
ON
ON
4
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
5 – 8
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
9
10
11
12
13
14
15
16
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
12345678
Page 43
43
12.11.1. Exchange connection example
12.11. VS-900SC Site Connector Connection
12.11.2. Power supply connection
Connect the optional PU-200 power transformer unit as shown below:
• For the optical/audio signal converter, prepare one which can transmit a 600 Ω, 0 dBm signal.
• For the optical/digital signal converter, prepare one which can convert an RS-485 signal into an optical
signal.
• Prepare the power source separately.
Connect the backup power supply, if needed, to the VS-900SC's DC input as illustrated.
Note: The backup power supply should be a UL Listed Limited Power Source or Class 2 power supply, rated
24 V DC, 0.2 A.
O.A.L.
PU-200
Power
Transformer
unit
VS-900SC
Power
supply
VS-900TI
Tie-Line unit
VS-900TI
Tie-Line unit
Fiber optic cableFiber optic cable
O.A.L.O.A.L.
O.A.L.
O.D.L.O.D.L.
O.D.L.O.D.L.
VS-900MF
Audio signal line
VS-900TI
Tie-Line unit
Control signal line
VS-900MF
VS-900MF
* O.A.L. (Optical Analog Link): Optical/audio signal converter
O.D.L. (Optical Data Link):
Optical/digital signal converter
VS-900SC (figure of the inside of the front panel)
+
DC 24V IN
-
FROM
FG
PU-200
DC24 V
PU-200
To AC mains
Page 44
44
12.11.3. Connection to the VS-900TI
Connect each connector of the unit's Voice Lines 1 – 4 to the corresponding connector on the VS-900TI's CN
1 – 4. Pins No. 1 and 2 of each connector of Voice Lines 1 – 4 are for receiving ends, while pins No. 3 and 4
are for transmitting ends. Use 2 twisted pair cables for connection as shown below.
• For the VS-900TI, cut SJP of each line to be connected.
Line 1: LINK1-1 (SJP13) and LINK1-2 (SJP14)
Line 2: LINK2-1 (SJP15) and LINK2-2 (SJP16)
Line 3: LINK3-1 (SJP17) and LINK3-2 (SJP18)
Line 4: LINK4-1 (SJP19) and LINK4-2 (SJP20)
VS-900SC (figure of the inside of the front panel)
12.11.4. Connecting the VS-900SC to another VS-900SC unit
Connect individual Voice Lines 1 – 4 connectors to each other.
Pins No. 1 and 2 of each connector of Voice Lines 1 – 4 are for receiving ends, while pins No. 3 and 4 are for
transmitting ends. Use 2 twisted pair cables to make connections as shown below.
12.11.5. Connection to an optical/audio signal converter
Connect the optical/audio signal converter to each connector of Voice Lines 1 – 4.
Pins No. 1 and 2 of each connector of Voice Lines 1 – 4 are for receiving ends, while pins No. 3 and 4 are for
transmitting ends. Use 2 twisted pair cables to make connections according to the specifications of the
equipment to be connected.
VS-900SC (figure of the inside of the front panel)
123
12 34
VOICE LINE1
2 twisted pair cables
VS-900SC (figure of the inside of the front panel)
123
12 34
VOICE LINE1
Page 46
46
12.12. VS-900MF Main Frame and PU-200 Power Transformer Connection
[Connection]
Connect as shown below using 2 parallel pair cables. Use cables with a sufficient current capacity and a
heavier gauge than AWG18. Two PU-200 units are required when using 3 or 4 VS-900RS cards.
Connect the backup power supply, if needed, to the VS-900MF's DC input as illustrated.
VS-900MF and power supply connection
VS-900MF
OUTPUT
20V AC 2.5A 20V AC 2.5A
from PU-200
AC-INAC-IN
12
from PU-200
AC-INAC-IN
34
DC24V IN
G1 FG
OUTPUT
20V AC 2.5A 20V AC 2.5A
24 V DC
Ferrite clamp*
PU-200
To AC mains
Mount the ferrite clamp (supplied with the VS-900MF) on the cable in a way
*
that the cable is looped one turn as illustrated. (This countermeasure is for
complying with the CE marking and FCC requirements.)
PU-200
To AC mains
Ferrite clamp
SFC-10
Page 47
47
13. MAIN FRAME AND PC CONNECTION
13.1. Programming PC Connection
13.1.1. Direct connection by means of RS-232C
Using the RS-232C cable, connect the programming PC to the VS-900MF Main Frame as shown below.
Direct connection by means of RS-232C (Programming PC)
RS-232C straight cable
Front view
CN106
CN108
VS-900MF
DCD
1
2RXD
3TXD
4DTR
5GND
6DSR
7RTS
8CTS
9RI
RS-232C straight cable
PC
1DCD
2RXD
3TXD
4DTR
5GND
6DSR
7RTS
8CTS
9RI
Programming PC
Main Frame VS-900MF
Page 48
48
13.1.2. Connection via modem
Connect as shown below.
Connection via modem (Programming PC)
RS-232C cross cable
VS-900MFModem
1DCD
2RXD
3TXD
4DTR
GND
5
6DSR
GND
DSR
7RTS
CTS
8
RI
9
CTS
RI
1DCD
2RXD
3TXD
4DTR
5
6
7RTS
8
9
CN106
CN108
Front view
Main Frame VS-900MF
RS-232C cross cable
Modem
Page 49
49
13.2. Operation Log PC Connection
13.2.1. Direct connection by means of RS-232C
Using the RS-232C cable, connect the operating log PC to the VS-900MF as shown below.
Direct connection by means of RS-232C (Operation log PC)
RS-232C straight cable
VS-900MFPC
DCD
1
2RXD
3TXD
4DTR
GND
5
6DSR
7RTS
CTS
8
RI
9
GND
CTS
RI
1DCD
2RXD
3TXD
4DTR
5
6DSR
7RTS
8
9
CN106
CN108
Front view
Main Frame VS-900MF
RS-232C straight cable
Operation log PC
Page 50
50
13.2.2. Connection via modem
Connect as shown below.
Connection via modem (Operation log PC)
13.3. System Programming
Use the supplied PC software to perform such system programming as station number and function settings.
For its use and installation, refer to the "VS-900 Setup Software Instruction Manual."
RS-232C cross cable
VS-900MFModem
1DCD
RXD
2
3TXD
4DTR
GND
5
6DSR
GND
DSR
7RTS
CTS
8
RI
9
CTS
RI
1DCD
2RXD
3TXD
4DTR
5
6
7RTS
8
9
CN106
CN108
Modem
RS-232C cross cable
Front view
Main Frame VS-900MF
Page 51
51
14. SPEECH AND FUNCTION TESTS
Using installed equipment, perform both speech and function tests after system programming completion.
14.1. Speech Test
(1) Calls from the substation
• Call the Master Station (telephone) from each substation to check to be sure that a conversation is possible.
Also, check to confirm that the master station (telephone) registered in system programming is correctly
called.
• Check to be sure that the calling substation number (name) is correctly displayed on the Master Station.
(2) Calls from the master station
• Call the substation and Master Station from each Master Station to check to be sure that a conversation is
possible.
• Check to confirm that the designated station is correctly called.
14.2. Function Test
Check each function registered in system programming for correct operation.
For each function's operation, refer to the "VS-900 OPERATING INSTRUCTIONS."
Page 52
52
Power Source 5 V DC, 24 V DC (supplied from the main frame)
Current Consumption 50 mA (5 V DC), 200 mA (24 V DC)
Supply Power 24 V DC, 80 mA
Number of Lines 2 lines
Conversation Recording Output Audio signal:0 dB*, unbalanced
Control signal: Open collector output, withstand voltage: 24 V DC,
control current: 20 mA
OtherMaster station connection monitoring function
Connection Terminal Main frame connection side:DIN connector (64-pin, male)
Line output:4-pin x 2
Recording audio/control output: 4-pin x 2
Operating Temperature 0 to +40°C
Weight 350 g
Note: The design and specifications are subject to change without notice for improvement.
• Accessories
Power Source 20 V AC, 24 V DC
Current Consumption 7 A
Speech Path Configuration Time sharing switch (T1 stage)
Serial portComplies with the RS-232C Standard, D-sub connector (9-pin, female),
2 ports
Installation Method Rack- and wall-mountable
Other Real time clock for time control
Unit's presence/non-presence detection
System programming data maintenance
Power switch
Connection Terminal Bus connector:DIN connector (64-pin, female) x 9
PU-200 connection terminal: 4-pin x 2 (2 PU-200s are connectable.)
24 V DC input terminal:4-pin (with grounding terminal)
Operating Temperature 0 to +40°C
Finish Pre-coated steel plate, black, 30% gloss
Dimensions 420 (w) x 443.7 (h) x 288.3 (d) mm (excluding the rack mounting bracket)
Weight 12.7 kg
Power Source 5 V DC, 15 V DC, 24 V DC (supplied from the main frame)
Current Consumption 150 mA (5 V DC), 30 mA (15 V DC), 200 mA (24 V DC)
Supply Power 24 V DC, 80 mA
Number of Lines 2 lines
Conversation Recording Output
Audio signal:0 dB*, unbalanced
Control signal: Open collector output, withstand voltage: 24 V DC,
control current: 20 mA
Selectable Signal TypeDTMF signal
Monitoring FunctionLine loop detection function
Applicable TerminalTelephone sets to comply with FCC Part 68
Control FunctionCall signal transmission, audible signal transmission,
caller identification signal transmission (Caller ID Function)
Connection Terminal Main frame connection side:DIN connector (64-pin, male)
Line output:2-pin x 2
Recording audio/control output: 4-pin x 2
Operating Temperature0 to +40°C
Weight 400 g
Power Source 5 V DC, 24 V DC (supplied from the main frame)
Current Consumption 200 mA (5 V DC), 600 mA (24 V DC)
Number of Lines Substation 16 lines
Number of Links2 links (One of 2 links is also used as a Paging Link.)
Paging Output–20 dB*, 1 kΩ, unbalanced
Paging Input25 V line, balanced
Conversation Method Half-duplex conversation by voice-operated switch or
simplex conversation by PTT switch
Audio Output Maximum 1 W per substation
Supply Power Maximum 15 V/20 mA per substation
OtherCall button detection function and speech link control function
Connection Terminal Main frame connection side: DIN connector (64-pin, male)
Substation connection side: Two-core shielded cable (3-pin) x 16
Paging input/paging output: 4-pin
Operating Temperature0 to +40°C
Weight 550 g
• Accessories
* 0 dB = 1 V
Note: The design and specifications are subject to change without notice for improvement.
• Accessories
* 0 dB = 1 V
Note: The design and specifications are subject to change without notice for improvement.
Power Source 5 V DC, 15 V DC, 24 V DC (supplied from the main frame)
Current Consumption 300 mA (5 V DC), 50 mA (15 V DC), 50 mA (24 V DC)
Number of Lines 2 lines
Conversation Recording Output Audio signal:0 dB*, unbalanced
Control signal: Open collector output, withstand voltage: 24 V DC,
control current: 20 mA
Selectable Signal TypeDTMF signal
Signal FormatLoop start and Ground start compatible
Main FunctionsDTMF dial signal transmission function, DTMF signal detection function,
call signal (receiving) detection
Connection Terminal Main frame connection side:DIN connector (64-pin, male)
C/O line connection side:4-pin x 2
Recording audio/control output: 4-pin x 2
Operating Temperature 0 to +40°C
Weight 380 g
Power Source 5 V DC, 24 V DC (supplied from the main frame)
Current Consumption 5 V DC: 200 mA
24 V DC: 600 mA (maximum during normal use),
1.5 A (maximum when 16 lines are simultaneously shorted)
Number of Lines Substation 16 lines
Number of Links2 links (one of 2 links is also used as a Paging Link.)
Conversation MethodFull-duplex conversation or Half-duplex conversation by
voice-operated switch
Audio Output Maximum 1 W per substation
Supply Power Maximum 20 V/30 mA per substation
Control SystemTwo-way dial pulse width system (call, restoration, external control, etc.)
by current loop
Connection Terminal Main frame connection side: DIN connector (64-pin, male)
Substation connection side: 4-pin x 16
Connection Monitoring FunctionLine connection detection, line short circuit/open circuit/failure detection,
and communication irregularity detection
Operating Temperature0 to +40°C
Weight 700 g
• Accessories
* 0 dB = 1 V
Note: The design and specifications are subject to change without notice for improvement.
• Accessories
* 0 dB = 1 V
Note: The design and specifications are subject to change without notice for improvement.
Power Source 5 V DC, 15 V DC, 24 V DC (supplied from the main frame)
Current Consumption 170 mA (5 V DC), 50 mA (15 V DC), 30 mA (24 V DC)
Paging Output Audio output:1 output, 0 dB*, unbalanced
Control output: Open collector output, withstand voltage: 24 V DC,
control current: 20 mA
External Source Distribution Audio input:1 input, 0 dB*, unbalanced
Control input: 4 inputs, no-voltage make contact,
open voltage: 24 V DC, short circuit current: 20 mA
Conference Link 1 link (up to 4-party conference)
Connection Terminal Main frame connection side: DIN connector (64-pin, male)
External interface side:Audio output 2-pin
Control output 2-pin x 16
Audio input 2-pin
Control input 2-pin x 4
Operating Temperature 0 to +40°C
Weight 230 g
Power Source 5 V DC, 15 V DC (supplied from the main frame)
Current Consumption 100 mA (5 V DC), 50 mA (15 V DC)
Number of Audio Links4 links
Connection FormatMultidrop system
Transmitting SystemData: RS-485
Voice: Base band
Input/Output Level Data: In compliance with RS-485 Standard
Voice: 0 dB*, balanced
Other Exchange number setting function
Connection Terminal Main frame connection side: DIN connector (64-pin, male)
Tie-line interface side:4-pin x 4 (Voice line), 4-pin x 1 (Data line)
Operating Temperature 0 to +40°C
Weight 320 g
• Accessories
* 0 dB = 1 V
Note: The design and specifications are subject to change without notice for improvement.
• Accessories
* 0 dB = 0.775 V
Note: The design and specifications are subject to change without notice for improvement.
Page 56
Printed in Japan
133-06-231-3G
Wood screw (5.1 x 38) .................................... 4
Tapping screw (4 x 12) ................................... 4
[YC-303 Main Frame Wall Mounting Bracket]
[VS-900SC Site Connector]
Finish Steel, black, electrodeposition paint
Dimensions 391.4 (w) x 440 (h) x 58 (d) mm
Weight 2.1 kg
Power Source 20 V AC (supplied from the power transformer unit, under 250 mA)
24 V DC (UL Listed Limited Power Source or Class 2 power supply,
rated 200 mA)
Name of Links 4 links
Input 0 dB*, 600 Ω, balanced (transformer)
Output 0 dB*, 600 Ω, balanced (transformer)
Installation Method Rack- and wall-mountable
Connection Terminal Voice line side:4-pin x 3 (voice line)/1 link
PU-200 connection terminal: 2-pin
24 V DC input terminal:4-pin
Operating Temperature 0 to +40°C
Finish Panel, Case: Pre-coated steel plate, black
Dimensions 420 (w) x 88.4 (h) x 238 (d) mm
Weight 3.55 kg