MODEL PS1505 FAN PROVING SWITCH DESIGNED FOR TJERNLUND AUTO-DRAFT
PURPOSE
The Tjernlund PS1505 Fan Prover has been designed to monitor the pressure within the fan housing only. A motor or wheel failure will decrease housing pressure and deactivate the pressure switch, thus preventing combustion
TYPICAL INSTALLATION
FLUE PIPE OR BREECHING
1/4” ALUMINUM TUBING
PS1505
SENSING PORT
®
INDUCERS
DRAFT INDUCER
FURNACE PLENUM, WALL OR JOIST MOUNTING. DIAPHRAGM MUST BE VERTICAL.
SPECIFICATIONS
Voltage: 125VA pilot duty at 24 volts AC
300VA pilot duty at 115 to 277 volts AC 15 amps non-inductive to 277 volts AC
Electric Switch: SPST, normally open snap acting contacts Electric Connectors: #6-32 screw terminals with cup washer Control Set Point: Nonadjustable Operating Pressure: On increasing vacuum pressure rise,
.05 + .02” W.C. with diaphragm in vertical position
Maximum Pressure: 1/2 psi Operating Temperature Range: -400to 1900F. Mounting Position: Diaphragm vertical Dimensions: 5” diam., 5 1/2” across mounting bracket, 3” high Weight: 1 Lb. 2 oz. Finish: Zinc plated steel
TYPICAL OIL WIRING
FEATURES
Simple Installation Mounting Hardware Furnished Fixed Set Point
TYPICAL GAS WIRING
TJERNLUND PRODUCTS, INC.
1601 Ninth Street • White Bear Lake, MN 55110-6794 PHONE (651) 426-2993 • (800) 255-4208 • FAX (651) 426-9547 Visit our web site • www.tjernlund.com