1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com
CPC-2 SOFTWARE VERSION 3.02.02 ADDENDUM
1. New Data Display -| V 0.00 0.00I | Data on this line.
| | Messages on this line.
" " = key pad open; "F" = fault; " " = Inducer is in manual mode
2. New Fault Bandwidth - While the CPC-2 continues to maintain the setpoint pressure
within +/-0.01" w.c., a fault will now occur after the actual pressure is +0.05" w.c. or
-0.02"w.c. away from setpoint for a duration of 90 seconds.
3. New Appliance Staging - Automatically stages appliances for a minimum of 10 seconds
when multiple appliances "call" simultaneously. Pressure must reach and remain within
bandwidth of pressure setpoint for 4 seconds before next appliance is allowed to fire.
4. Control Algorithm Change - The speed of acceleration towards the setpoint (gain) has
been increased to improve the CPC-2 response time. The control architecture will now allow
over shoot into the above setpoint region, resulting in fewer faults.
5. Control Algorithm Change - At start up, the computer program now has continuous
Inducer acceleration towards the setpoint. Originally, the program increased the Inducers
RPMs in four steps. That approach prevented over shooting the setpoint but it took longer to
get there.
6. Restart Function - After a fault the CPC-2 will shut down the appliance(s). After a period
of 60 seconds it will attempt a restart. If fault occurs again, then the CPC-2 will lock the
appliances out until serviced. (Mechanical faults are excluded from restart).
7. Transducer Pressure Range Change - The model TD-2 transducer will now sense
between +0.15" w.c. and -0.60" w.c. This increases the gain when operating at low system
setpoints.
8. Fault Codes Expanded - New fault codes and messages let the service person know what is
wrong and when it happened. The last four faults are automatically stored chronologically.
The fault duration has been expanded to 90 seconds from 60 seconds.
1601 Ninth Street • White Bear Lake, MN 55110-6794
PHONE (800) 255-4208 • (651) 426-2993 • FAX (651) 426-9547
Visit our web site • www.tjernlund.com
MODEL
CPC-2
CONSTANT PRESSURE CONTROLLER
For Controlling Variable Speed Auto-Draft®Venters, Combustion Air
IN-FORCERTMS, Power Venters and Draft Inducers with multiple appliances
OWNER INSTRUCTIONS, DO NOT DESTROY
!
Recognize this symbol as an indication of important Safety Information!
THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED, LICENSED
SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND
OPERATION OF THIS UNIT. READ THESE INSTRUCTIONS THOROUGHLY
BEFORE ATTEMPTING INSTALLATION OR OPERATION. FAILURE TO FOLLOW
THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION, ADJUSTMENT, SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE, ELECTRICAL SHOCK, CARBON MONOXIDE POISONING, EXPLOSION, OR PERSONAL
INJURY OR PROPERTY DAMAGE.
Description and Operation...............................................................................................................................................1
Installation of CPC-2, Transducer & Balancing Dampers...............................................................................................2
CPC-2 Circuit Board Features & Circuit Board Layout................................................................................................2-4
Modes of Operation and Programming CPC-2 Controller...........................................................................................5-7
Initial System Power Up and Setup of CPC-2 .............................................................................................................7-9
Replacement Parts & Warranty.....................................................................................................................................14
Tjernlund Products welcomes your comments and questions. Call us at 800-255-4208, Fax 651-426-9547, Email us at
fanmail@tjfans.com or write to: Customer Service, Tjernlund Products, Inc., 1601 Ninth Street, White Bear Lake, MN 55110-6794.
DESCRIPTION AND OPERATION
The CPC-2 controls the motor speed of Tjernlund variable speed Auto-Draft® Venters, Draft Inducers, Power Venters and Combustion
Air In-Forcers. It requires a Pressure Transducer and a Tjernlund Variable Frequency Drive (VFD) to automatically modulate motor
speed. The installer/user may select a pressure set point via the key pad on the CPC-2. The transducer outputs a signal to the CPC-2
proportional to the pressure or draft that it senses. The CPC-2 outputs a proportional signal to the VFD, which modulates the frequency of the voltage to the motor, causing it to speed up or slow down so that the pressure or draft set point is maintained.
Integral to the CPC-2 are two heating appliance interlock circuits. When an appliance calls for heat the burner control signal is intercepted, causing the Auto-Draft® Venter, Draft Inducer, Power Venter or Combustion Air In-Forcer to speed up until the pressure set
point is reached. If the set point is not reached within CPC-2 allowable limits (See Modes of Operation), the interlocked appliance(s)
will not fire.
When a pre-purge time is selected the controller will not allow the appliance(s) to operate until the pressure set point is reached and
the pre-purge time has elapsed. When a post-purge time is selected the appliances are deactivated as soon as the call for heat is
satisfied, but the Auto-Draft® Venter, Draft Inducer, Power Venter or Combustion Air In-Forcer will continue to maintain the pressure
set point until the post-purge time has elapsed. The secondary Fan Prover Switch model PSA-1 is adjusted by the installer to the vent
system draft set point and wires into a terminal strip on the CPC-2. The Transducer in conjunction with the CPC-2 Controller is
considered the primary draft proving control.
The CPC-2 can also be operated in the Manual mode, regulating the motor at a constant, user set speed. The Venter Only mode
allows the user to regulate the motor at a constant, user set speed, but will not allow any interlocked heating appliances to operate.
COMPLETE AUTO-DRAFT® VENT SYSTEM SOLUTIONS
This installation manual does not contain any system design documentation. Installation and use of Auto-Draft® Venters or EXP-4
Appliance Interlock Expansion boards are not covered by this manual. Please refer to those accessory installation manuals.
SPECIFICATIONS
1
CAUTIONS
1. Failure to install, maintain and/or operate the CPC-2 in accordance with manufacturer’s instructions may result in conditions that
can produce bodily injury and property damage.
2. The safety interlock and system operation performance checks must be performed on each appliance interlocked with the
CPC-2 in accordance with the Auto-Draft® Venter, IN-FORCER Combustion Air Intake, Power Venter or Draft Inducer installation
instructions.
INSTALLATION AND LOCATION OF CPC-2, TRANSDUCER AND BALANCING DAMPERS
MOUNTING OF THE CPC-2
CPC-2 and transducer should be mounted conveniently inside mechanical
room where access is not restricted. Since set up requires adjustment of
draft settings, close proximity to heating equipment is suggested.
MOUNTING OF THE TRANSDUCER
The transducer must be mounted indoors within six (6) feet of the vent or
chimney transducer sampling tube.
MOUNTING OF TRANSDUCER SAMPLING TUBE
The CPC-2 operates best when the transducer sampling tube measures
static pressure, not velocity pressure. The best position to measure static
pressure is in an extension off of the back end of a horizontal manifold,
(See Diagram A). At this position the probe is not influenced by the velocity of the flue gases being exhausted. Do not use an elbow to connect
the last appliance (furthest from venter) to the common manifold. The
elbow will not allow the sampling tube to measure static pressure. If necessary, “T” off manifold as close to last appliance as possible preferably
using the same diameter pipe as manifold and a clean, burr free transition.
Drill 1/4” sampling hole in vent or chimney for sampling tube. Insert stainless steel sampling tube through 1/4” hole just enough to penetrate interior
of vent pipe and lock in place with compression nut, (See Diagram A).
With the Venter on, a reading with a draft gauge can be used to determine
when interior of pipe has been penetrated.
CONNECTING TRANSDUCER TO SAMPLING TUBE
The transducer - negative pressure front port (closest to cover) is connected to the transducer sampling tube. Make sure the silicone tubing has no
sharp bends or kinks in it. The high pressure rear port (closest to mounting bracket) must be left open to room atmosphere, (See Diagram B).
DIAGRAM A
DIAGRAM B
COMPRESSION NUT
COMPRESSION FERRULE
SAMPLING PORT CENTERED
OVER 1/4” HOLE
1/4” STAINLESS STEEL
SAMPLING TUBE BEND MUST
FACE UPWARDS.
INDIVIDUAL APPLIANCE
BALANCING DAMPERS ARE
NECESSARY. MAKE SURE
THEY DO NOT INTERFERE
WITH FLUE DAMPERS.
FRONT NEGATIVE PRESSURE
PORT CLOSEST TO JUNCTION
BOX COVER MUST BE CONNECTED TO SAMPLING PORT WITH
SILICONE TUBING.
REAR HIGH PRESSURE PORT
CLOSEST TO MOUNTING BRACKET MUST BE LEFT OPEN TO
ROOM ATMOSPHERE.
BALANCING DAMPER INSTALLATION
Balancing dampers are necessary on each appliance vent riser into the common vent manifold. Since the Venter will pull flue gases
from the point of least resistance, those appliances connected closest to the venter will tend to overdraft. Balancing dampers can be
adjusted to match each individual appliance draft requirement, (See Diagram A). Care should be taken so balancing dampers do not
interfere with flue dampers if on equipment. Tjernlund’s ABD-Series (4-10”, 12” & 14” diameter) balancing dampers are constructed
out of 304 stainless steel and feature a tamper proof locking adjustment.
CPC-2 CIRCUIT BOARD FEATURES
Two closed loop channels allowing independent variable speed control of both venting and combustion air systems.
Two appliance interlocks for control circuit voltages between 18 & 240 VAC plus two sets of dry contacts for activation by gas pres-
sure switch or boiler sequencer dry contacts. Additional appliances can be interlocked by using the optional EXP-4 expansion board.
Up to three EXP-4 expansion boards can be connected to interlock up to 14 appliances into a single CPC-2.
Switchable 120/230 VAC 50/60 Hz. fused power supply.
Dry Contact alarm circuit that reacts to motor high limits, tilt switches, prover faults, under pressure conditions.
LED lights displayed for Venter Check circuit, appliance call for heat, prover circuit completed and CPC-2 power supplied to board.
See CPC-2 Circuit Board Call Outs for LED indicator light status.
Serial Port interface.
All sensor connections to the CPC-2 control must only be connected to Tjernlund approved components. Failure to install, maintain
and/or operate the CPC-2 in accordance with manufacturer’s instructions may result in conditions that can produce bodily injury and
property damage.
2
CPC-2 CIRCUIT BOARD CALL OUTS
1) ALARM: Dry contacts will close with a Venter Fault or any fault that requires manual resetting. These faults include the Venter,
Start-up, Prover 1 or Prover 2 Faults. Connect to aux. alarm or building mgmt. system. Rated for 1/4 h.p. @ 120 VAC.
2) SERIAL PORT: For inputting future program updates and outputting stored data.
3) PROVER 2: Connection to auxiliary prover for second CPC-2 controlled device. (i.e. Combustion Air In-Forcer or future needs)
4) VENTER 2: Connection to VFD of second CPC-2 controlled device. (i.e. Combustion Air In-Forcer) (0-10 VDC output)
5) SENSOR 1: Connection to vent pressure Transducer to regulate Venter / Inducer speed. (0-10 VDC input)
6) SENSOR 2: Connection to secondary vent pressure Transducer that communicates with CPC-2 to regulate motor speed of
secondary device. (i.e. Combustion Air In-Forcer) (1-12 VDC input)
7) SENSOR 3: Connection to future sensor (open connection, not currently programmed) (0-10 VDC input)
8) SENSOR 4: Connection to future sensor (open connection, not currently programmed) (0-10 VDC input)
9) VENTER 1: Connection to VFD of Venter / Inducer. (1-10 VDC output)
10) PROVER 1: Connection to secondary Fan Prover, i.e. PSA-1 adjustable Fan Prover.
11) MOTOR SENSOR: Green LED indicates that Venter check circuit, i.e. motor limits, housing access limits, high limits, etc.,
are closed and in an acceptable condition.
12) DISPLAY: CPC-2 connection to ribbon cable from display. Ribbon cable printing must face towards top of CPC-2 electrical box.
13) MOTOR SENSOR TERMINAL STRIP: Connects to terminal strip of VFD to lock out interlocked appliances if any motor limit
14) 18-130 VAC JUMPER TAB: Jumper tab must be removed for 230 VAC interlock with appliance #1.
15) CALL 1: Yellow LED indicates that 1st interlocked appliance is calling for heat.
16) APPLIANCE ON 1: Green LED indicates that vent pressure set point has been reached/maintained and the interlocked
appliance call for heat signal has been delivered to the burner control circuit.
17) RESET BUTTON: Used to soft boot CPC-2 control.
18) CALL 2: Yellow LED indicates that 2nd interlocked appliance is calling for heat.
19) APPLIANCE ON 2: Green LED indicates that vent pressure set point has been reached/maintained and the interlocked
appliance call for heat signal has been delivered to the burner control circuit.
20) DRY CONTACT JUMPER TAB: Jumper tab must be installed if using dry contacts for interlock with appliance #1. Important:
Do not use appliance #1 interlock terminal strip (position 30) if using dry contact actuation.
21) APPLIANCE #1 INTERLOCK JUMPER: Routes intercepted control circuit “hot” voltage from position #1 to position #3, completing
circuit back to appliance through position #4 when all safeties are closed. Normally
kept in place. If removed user can actuate the CPC-2 with one voltage and actuate
the appliance control circuit with another.
22) DRY CONTACT JUMPER TAB: Jumper tab must be installed if using dry contacts for interlock with appliance #2. Important:
Do not use appliance #2 interlock terminal strip (position 32) if using dry contact actuation.
23) 18-130 VAC JUMPER TAB: Jumper tab must be removed for 230 VAC interlock with appliance #2.
24) APPLIANCE #2 INTERLOCK JUMPER: Routes intercepted control circuit “hot” voltage from position #1 to position #3, completing
circuit back to appliance through position #4 when all safeties are closed. Normally
kept in place. If removed user can actuate the CPC-2 with one voltage and actuate
the appliance control circuit with another.
25) KEYPAD: CPC-2 connection to ribbon cable from keypad.
26) SYSTEM POWER LIGHT: Red LED indicates that the CPC-2 has power.
27) VOLTAGE SELECTION SWITCH: Allows the installer to select between 115 VAC and 230 VAC for the main power input to the CPC-2.
28) ON/OFF SWITCH: Turns power to CPC-2 on or off.
29) APPLIANCE #1 DRY CONTACT INTERLOCK TERMINAL: For dry contact actuation of CPC-2. Must install jumper at position 20.