The Thomson Technology MPC-ETN is a multi-protocol converter and Serial –Ethernet media converter. This Quick
Installation Guide will describe the method to interface a PC to either a MEC 20 or TSC 800 controller over an
RS485/232 serial interface.
Check Components:
Unpack and ensure that all components are in good condition.
Qty Description
Gateway Utility Software – Download the latest from www.thomsontechnology.com
Customer Required Components:
Qt
Description
1 Ethernet Cable
1 24VDC power supply (min 12Vdc, max
30Vdc), 100mA max.
NOTES:
1. Your IT SUPPORT GROUP must assign a ‘Static IP Address’ to the MPC-ETN. The ‘Static IP Address’ is
required so that the MPC-ETN device will work correctly on your Ethernet Network.
2. Modscan32 software is needed for Check/Verification of the MPC-ETN setup. Download Modscan32 from the
following link - http://www.win-tech.com/html/demos.htm - ModScan32.zip (851K) . Follow the Setup Wizard
for the installation of the Modscan32 Software.
• Connect 24VDC to the power input connector on the MPC-STD. Make sure that the Protective Earth of the
power supply is connected to the Earth connection of the MPC-ETN
• Power up the MPC-ETN and start Modbus™ communications with the Thomson Technology device (i.e.
MEC20 or TSC800).
• Refer to the MPC-ETN default Modbus™ map for MEC20/TSC800 parameter addresses found on included
CD-ROM.
• Modbus map mec20-R*.pdf
• Modbus map tsc800-R*.pdf
NOTE: Only used for Programming MPC-ETN. Refer to Step 4 of ‘Setting the Modbus™ node address
(default 1) and TCP/IP address:’
Press the Extended Setup
button for the TCP/IP setup.
Enter the TCP/IP information
and press the OK button.
NOTE:
• Your IT SUPPORT GROUP must assign a ‘Static IP Address’ to the MPC-ETN. The ‘Static
IP Address’ is required so that the MPC-ETN device will work correctly on your Ethernet
Network.
4. Connect the PC end of the programming cable to the PC and connect the MPC-COM1 end of the
programming cable to the MPC-ETN COM1 port.
5. Press the Download button of the Gateway Utility Software toolbar.
list. Power up the MPC-ETN.
The green OK light will blink
This indicates that the MPCETN is in upload/download
mode. If the light stops
blinking before an upload or a
download is conducted then
the power to the MPC-ETN
must be cycled to put it back
into upload/download mode.
Click the Select AllDownload. (Cycle power to the
MPC-ETN if necessary.)
6. Once download is complete a confirmation will appear. Click OK to re-start the Gateway.
For MEC20 – Enter
Address: ‘1001’
Length: ‘5’
’03:HOLDING REGISTER’
For TSC800 – Enter
Address: ‘6001’
Length: ‘5’
’03:HOLDING REGISTER’
NOTE:
• When comm./setup/configuration is correct the program will increment both counters
(Number of Polls and Valid Slave Responses) at the same rate. You may notice that the
two numbers are at a different value but both will count up at the same time.
• If there is any issues with comm./setup/configuration, you may see the following messages
o **Data Un-Initialized**
o **Device NOT CONNECTED!**
o **MODBUS Message TIME-OUT**
o **MODBUS Exception Response from Slave Device**