Please make sure to read this handbook before working with the MEC 320
set to be controlled. Failure to do this could result in
1. About this document
This chapter includes general user information about this handbook concerning the general
purpose, the intended users and the overall contents and structure.
General purpose
This document is the Peak Plus Reference Handbook for Thomson Technology’s Automatic Genset Controller, the MEC 320. The document mainly includes functional descriptions, presentation of
display unit and menu structure, the procedure for parameter setup and complete standard
parameter lists.
The general purpose of the Reference Handbook is to provide useful overall information about the
functionality of the unit in the AMF/Load Take Over applications. This handbook also offers the
user the information he needs in order to successfully set up the parameters needed.
controller and the genhuman injury or damage to the equipment.
Intended users
The handbook is mainly intended for the person responsible for the unit parameter setup. In most
cases, this would be a panel builder designer. Naturally, other users might also find useful
information in this handbook.
Contents/overall structure
This Reference Handbook is divided into chapters and in order to make the structure of the
document simple and easy to use, each chapter will begin from the top of a new page. The
following will outline the contents of each of the chapters.
About this document
This first chapter includes general information about this handbook as a document. It deals with the
general purpose and the intended users of the Reference Handbook. Furthermore, it outlines the
overall contents and structure of the document.
Warnings and legal information
The second chapter includes information about general legal issues and safety precautions
relevant in the handling of Thomson Technology products. Furthermore, this chapter will introduce
note and warning symbols, which will be used throughout the handbook.
General product information
The third chapter will deal with the unit in general and its place in the Thomson Technology
product range.
Functional descriptions
This chapter will include functional descriptions of the standard functions as well as illustrations of
the Peak Plus application types. Flowcharts and single-line representations will be used in order to
simplify the information.
PM079 Rev 0 07/06/08 4 Thomson Technology
MEC 320 GENSET CONTROLLER
Display unit and menu structure
This chapter deals with the display unit including the push-button and LED functions. In addition,
the unit menu structure will be presented. Furthermore, the selection of unit mode and password
will be illustrated.
Additional functions
This chapter describes the additional functions of the unit.
Procedure for parameter setup
This chapter deals with the procedure to be followed, when the parameters are set up or changed.
By use of various illustrations this chapter will guide the user through the procedure for parameter
setup step by step.
Parameter list
This chapter includes a complete standard parameter list for setup. Therefore, this chapter is to be
used for reference, when information about specific parameters is needed.
PM079 Rev 0 07/06/08 5 Thomson Technology
MEC 320 GENSET CONTROLLER
The notes provide general information which will be helpful for the reader to
ult in
death, personal injury or damaged equipment, if certain guidelines are not
nd voltages. Do not touch any AC
2. Warnings and legal information
This chapter includes important information about general legal issues relevant in the handling of
THOMSON TECHNOLOGY products. Furthermore, some overall safety precautions will be
introduced and recommended. Finally, the highlighted notes and warnings, which will be used
throughout this handbook, are presented.
Legal information and responsibility
THOMSON TECHNOLOGY takes no responsibility for installation or operation of the generator set.
If there is any doubt about how to install or operate the generator set controlled by the unit, the
company responsible for the installation or the operation of the set must be contacted.
The units are not to be opened by unauthorized personnel. If opened anyway, the
Electrostatic discharge awareness
Sufficient care must be taken to protect the terminals against static discharges during the
installation. Once the unit is installed and connected, these precautions are no longer necessary.
warranty will be void.
Safety issues
Installing the unit implies work with dangerous currents and voltages. Therefore, the installation
should only be carried out by authorized personnel who understand the risks involved in working
with live electrical equipment.
Be aware of the hazardous live currents a
measurement inputs as this could lead to injury or death.
Definitions
Throughout this document a number of notes and warnings will be presented. To ensure that these
are noticed, they will be highlighted in order to separate them from the general text.
Notes
Warnings
bear in mind.
The warnings indicate a potentially dangerous situation which could res
followed.
PM079 Rev 0 07/06/08 6 Thomson Technology
MEC 320 GENSET CONTROLLER
Vision or the Graphical Display Unit (GDU) by use of a modem. To avoid
3. General product information
This chapter will deal with the unit in general and its place in the THOMSON TECHNOLOGY
product range.
Introduction
The MEC 320 is part of the THOMSON TECHNOLOGY product family.
The concept of the MEC 320 is to offer a cost-effective solution to gen-set builders, who need a
flexible generator protection and control unit for medium to large gen-set applications. Being part
of the THOMSON TECHNOLOGY product family, the standard functions can be supplemented
with a variety of optional functions.
Type of product
The Automatic Gen-set Controller is a micro-processor based control unit containing all
necessary functions for protection and control of a gen-set.
It contains all necessary 3-phase measuring circuits, and all values and alarms are presented on
the LCD display
PC utility software warning
It is possible to remote control the gen-set from the PC utility software M-
personal injury make sure that it is safe to remote control the gen-set.
PM079 Rev 0 07/06/08 7 Thomson Technology
MEC 320 GENSET CONTROLLER
4. Functional descriptions
This chapter includes functional descriptions of standard functions as well as illustrations of the
relevant application types. Flowcharts and single-line diagrams will be used in order to simplify
the information.
Standard functions
In the following paragraphs the standard functions are listed.
Operation modes
Automatic Mains Failure
•
Load take over
•
Engine control
Start/stop sequences
•
Fuel solenoid selection
•
Relay outputs for governor control
•
Protections (ANSI)
Overcurrent, 2 levels (51)
•
Reverse power (32)
•
4-20mA inputs
•
PT100 or VDO inputs
•
Digital inputs
•
Display
•
•
•
•
M-logic
•
•
•
Prepared for remote mounting
Push-buttons for start and stop
Push-buttons for breaker operations
Status texts
This section about applications is to be used for reference using the particular
set mode as starting point. It is not suitable for reading from beginning to
end.
Applications
The unit can be used for the applications listed in the table below.
Application Comment
Load take over Standard
Automatic Mains Failure (no back sync. /
Open Transition)
Automatic Mains Failure (with back sync. /
Closed Transition)
Gen-set mode Running mode
Load take over X X X X X
Automatic Mains Failure (no back sync. /
Open Transition)
Closed Transition)
gen-
Standard
Standard
Auto Semi Test Man Block
X X X X X
X X X X X
See mode overview in chapter 6 on page 46 for short description.
The flowcharts below illustrate the full functionality of the mentioned genmodes.
Load take over
Auto mode description
Back synchronizing ON (Closed Transition)
The purpose of the load take over mode is to transfer the load imported from the mains to the
gen-set for operation on generator supply only.
When the start command is given, the gen-set will start and synchronize the generator breaker
to the mains. When the generator breaker is closed, the imported load is decreased (the power
is being transferred to the gen-set), until the load is at the open breaker point. Then the mains
breaker opens.
When the stop command is given, the mains breaker is synchronized to the generator and after
closure the gen-set is deloaded, cooled down and stopped.
A 4-20mA transducer is used for indication of the power imported from the mains.
PM079 Rev 0 07/06/08 9 Thomson Technology
kW
Start signal Stop signal
Generator power
MB opens GB opens
t
The load take over mode can be combined with the short time parallel. In that
case, the generator and the mains breakers will never be closed at the same
set an alarm appears, and
set power, an alarm appears
Diagram, load take over - example
time for a longer period than the adjusted ‘short time parallel’ time.
If the imported load is higher than the nominal genand the load take over sequence is paused.
MEC 320 GENSET CONTROLLER
Mains power
Back synchronizing OFF (Open Transition)
When the start command is given, the gen-set will start. When the frequency and voltage is OK,
the mains breaker is opened and the generator breaker is closed. Now the generator supplies
the load, until the stop command is given. Then the generator breaker opens and the mains
breaker closes. The gen-set cools down and stops.
A 4-20mA transducer is used for indication of the power imported from the mains.
If the imported load is higher than the nominal genthe load take over sequence is paused.
Semi-auto mode
When the generator breaker is closed, and the mains breaker is opened, the unit will use the
nominal frequency as set point for the speed governor.
When the generator is paralleled to the mains, it will be controlled, so the imported power from
the mains will be kept at 0 kW.
See general semi-auto mode description on page 12.
Test mode description
See general test mode description valid for all gen-set modes on page 13.
Manual mode description
See general manual mode description valid for all gen-set modes on page 13.
PM079 Rev 0 07/06/08 10 Thomson Technology
MEC 320 GENSET CONTROLLER
Block mode description
AMF (no back Synchronization / Open Transition)
Auto mode description
The unit automatically starts the gen-set and switches to generator supply at a mains failure
after an adjustable delay time. It is possible to adjust the unit to change to gen-set operation in
two different ways.
In both cases, the generator breaker will be closed, when the generator voltage and frequency is
OK, and the mains breaker is open.
When the mains returns, the unit will switch back to mains supply and cool down and stop the
gen-set. The switching back to mains supply is done without back Synchronization (Open
Transition), when the adjusted ‘mains OK delay’ has expired.
See general block mode description valid for all gen-set modes on page 14.
1. The mains breaker will be opened at gen-set start-up.
2. The mains breaker will remain closed, until the gen-set is running, and the gen-set
voltage and frequency is OK.
Semi-auto mode description
When the generator breaker is closed, the unit will use the nominal frequency as the set point for
the speed governor.
Test mode description
Manual mode description
Block mode description
See general semi-auto mode description on page 12.
See general test mode description valid for all gen-set modes on page 13.
See general manual mode description valid for all gen-set modes on page 13.
See general block mode description valid for all gen-set modes on page 14.
PM079 Rev 0 07/06/08 11 Thomson Technology
MEC 320 GENSET CONTROLLER
ins failure mode can be combined with the short time parallel
function. In that case, the generator breaker and the mains breaker will never be
closed at the same time for a longer period than the adjusted ‘short time parallel’
AMF (with back Synchronization/Closed Transition)
Auto mode description
The unit automatically starts the gen-set and switches to generator supply at a mains failure
after an adjustable delay time. It is possible to adjust the unit to change to gen-set operation in
two different ways:
1. The mains breaker will be opened at gen-set start-up.
2. The mains breaker will remain closed until the gen-set is running and the gen-set
voltage and frequency is OK.
In both cases, the generator breaker will be closed, when the generator voltage and frequency is
OK, and the mains breaker is open.
When the mains returns, the unit will synchronize the mains breaker to the generator, when the
‘mains OK delay’ has expired. Then the gen-set cools down and stops.
The automatic ma
time.
Semi-auto description
When the generator breaker is closed and the mains breaker is opened, the unit will use the
nominal frequency as the set point for the speed governor.
When the generator is paralleled to the mains, the governor regulation will not be active.
Test mode description
Manual mode description
Block mode description
See general semi-auto mode description on page 12.
See general test mode description valid for all gen-set modes on page 13.
See general manual mode description valid for all gen-set modes on page 13.
See general block mode description valid for all gen-set modes on page 14.
PM079 Rev 0 07/06/08 12 Thomson Technology
MEC 320 GENSET CONTROLLER
auto is
lator is
General semi-auto mode description
The unit can be operated in semi-automatic mode. Semi-auto means that the unit will not initiate
any sequences automatically, as is the case with the auto mode. It will only initiate sequences, if
external signals are given.
An external signal may be given in three ways:
1. Push-buttons on the display are used
2. Digital inputs are used
3. Modbus command.
When the gen-set is running in semi-auto mode, the unit will control the speed governor.
The following sequences can be activated in semi-auto:
Command Description Comment
Start The start sequence is initiated and continues until the gen-
Stop The gen-set will be stopped. After disappearance of the
Close GB The unit will close the generator breaker, if the mains
Open GB The unit will ramp down and open the generator breaker at
Close MB The unit will close the mains breaker, if the generator
Open MB The unit opens the mains breaker instantly.
Manual
GOV UP
Manual
GOV DOWN
It is possible to manually increase and decrease the speed when semiselected. When the digital up/down input is activated, then the regu
deactivated as long as the manual up/down inputs are activated.
set starts or the maximum number of start attempts has
been reached. The frequency will be regulated to make the
GB ready to close.
running signal, the stop sequence will continue to be active
in the ‘extended stop time’ period. The gen-set is stopped
without cooling-down time.
When AMF mode
breaker is open, synchronize and close the generator
breaker, if the mains breaker is closed.
the breaker open point, if the mains breaker is closed.
breaker is open, synchronize and close the mains breaker,
if the generator breaker is closed.
The regulator is deactivated and the governor output is
activated as long as the GOV input is ON.
The regulator is deactivated and the governor output is
activated as long as the GOV input is ON.
is selected, the
unit will not regu-
late after breaker
closure.
PM079 Rev 0 07/06/08 13 Thomson Technology
MEC 320 GENSET CONTROLLER
If short time parallel is activated, the test will be terminated immediately after
set will cool down
and stop.
reaker or the mains breaker
in manual mode.
It is necessary to configure the digital inputs through the PC utility software to
use the manual commands. The number of configurable digital inputs is option
MAN mode cannot be selected, when AUTO mode is selected. To go from AUTO
General test mode description
The test mode function is activated by selecting test with the MODE push-button on the display
or by activating a digital input, if one of them is configured to ‘test’. The test mode will only test
synchronizing, if the ‘Sync. to mains’ function is enabled. If this is the case, the gen-set will start,
and the unit will synchronize and close the generator breaker to let the gen-set run in parallel,
until the test time expires. If the ‘Sync. to mains’ function is not activated, then the gen-set will
start and run at the nominal frequency with the generator breaker open.
The settings for the test function are set up in menu
Set point: Load set point when paralleling to mains.
•
Timer: Engine run time during the test period
•
Return: When the test is completed, the unit will return to the selected mode
•
(semi-auto or auto).
General manual mode description
When manual mode is selected, the gen-set can be controlled with digital inputs. The following
commands are possible:
the short time parallel time has expired. This means the gen-
Command Comment
Start Gen-set starts.
Stop Gen-set opens GB and stops
Manual increase speed Unit gives increase signal to
Manual decrease speed Unit gives decrease signal to
dependent.
It is not possible to open and close the generator b
to MAN it is necessary to go to SEMI-AUTO to make MAN available.
6540 Test running
without cooling-down.
speed governor.
speed governor.
.
PM079 Rev 0 07/06/08 14 Thomson Technology
MEC 320 GENSET CONTROLLER
ted from the local engine control panel, if such is
installed. Therefore, Thomson Technology recommends to avoid local
If block mode is selected using the display after the digital block input is
activated, the MEC 320 will stay in block mode after the block input is
e display. The block
mode can only be changed locally by display or digital input.
Before the running mode is changed it is important to check that persons are
The flowcharts below are for guidance only. For illustrative purposes the
General block mode description
When the block mode is selected, the unit is locked for certain actions. This means that it cannot
start the gen-set or perform any breaker operations.
To change the running mode from the display, the user will be asked for a password, before the
change can be made. It is not possible to select ‘block mode’, when running feedback is present.
The purpose of the block mode is to make sure that the gen-set does not start for instance
during maintenance work.
If the digital inputs are used to change the mode, then it is important to know that the input
configured to block mode is a constant signal. So, when it is ON the unit is in a blocked state,
and when it is OFF, it returns to the mode it was in before block mode was selected.
deactivated. The block mode must now be changed using th
clear of the gen-set and that the gen-set is ready for operation.
Alarms are not influenced by block mode selection.
The gen-set can be star
cranking and starting of the gen-set.
Flowcharts
Using flowcharts, the principles of the most important functions will be illustrated in the next
sections. The functions included are:
Mode shift
•
MB open sequence
•
GB open sequence
•
Stop sequence
•
Start sequence
•
MB close sequence
•
GB close sequence
•
Load take over
•
Automatic Mains Failure
•
Test sequence
•
flowcharts are simplified in some extent.
PM079 Rev 0 07/06/08 15 Thomson Technology
Mode shift
MEC 320 GENSET CONTROLLER
Start
Mode shift
enabled
Yes
Load take over
and AMF
Yes
mains failure
Yes
initiate AMF
sequence
No
No
No
No
mains OK timer
timed out
PM079 Rev 0 07/06/08 16 Thomson Technology
Yes
initiate mains
return
sequence
MB close
sequence
continue in
selected mode
END
MB open sequence
MB closed
load take over
Yes
MEC 320 GENSET CONTROLLER
Start
No
Yes
No
mains failure
deload MB
load = 0
Yes
open MB
MB opened
Yes
No
No
No
load too high
alarm 'MB
open failure'
Yes
alarm
END
PM079 Rev 0 07/06/08 17 Thomson Technology
GB open sequence
MEC 320 GENSET CONTROLLER
Start
stop conditions
OK
Yes
is GB closed
Yes
Soft open
Yes
deload DG
load< open set
point
No
No
No
No
fail class
shutdown
No
ramp down
timer expired
Yes
open GB
No
GB openedAlarm
Yes
end
Yes
PM079 Rev 0 07/06/08 18 Thomson Technology
Stop sequence
MEC 320 GENSET CONTROLLER
Start
No
stop
conditio
ns OK
Yes
GB open
seq OK
Yes
AUTO
mode
cooldown
timer run
out
Yes
No
No
No
Yes
run coil
Yes
deactivate
'stop' relay
genset
stopped
Yes
end
No
stop relay
activate stop
relay
No
alarm
PM079 Rev 0 07/06/08 19 Thomson Technology
Start sequence
No
Start
start condition
OK
Yes
start prepare
timer
Yes
Start relay ON
start relay timer
timeout
Yes
off relay ON
stop relay timer
timed out
Yes
max start
attempts
Yes
Start failure
alarm
MEC 320 GENSET CONTROLLER
No
No
NoNo
genset started
Yes
run feedback
detected
No
f/U OK
ready to close
GB
end
No
Alarm
Yes
No
Yes
PM079 Rev 0 07/06/08 20 Thomson Technology
MB close sequence
alarm GB open
is MB open
voltage on
mains/bus
voltage on gen
Yes
GB cl osed
Yes
back sync ON
Yes
sync MB
synchronised
Yes
close MB
MB closed
Yes
Start
end
Yes
Yes
No
No
No
No
No
No
No
MEC 320 GENSET CONTROLLER
direct cl ose OK
No
Yes
No
sync ti mer
runout
Yes
close failure
alarm
GB open
sequence
alarm sync.
failure
failure
PM079 Rev 0 07/06/08 21 Thomson Technology
GB close sequence
Start
is GB open
Yes
No
Start seq OK
No
Yes
single DG
application
No
Yes
island mode
voltage on bus
No
Yes
No
YesYes
MB close
MEC 320 GENSET CONTROLLER
No
voltage on
busbar
Yes
MB open
No
DG freq match
No
All GBs OFF
Yes
TB Present
Yes
TB open
Yes
No
No
No
Yes
direct closing
OK
Sync GB
BB freq
Yes
close GB
GB closedalarm
Yes
end
time runout
No
No
No
Yes
alarm sync
failure
PM079 Rev 0 07/06/08 22 Thomson Technology
Load take over
Start
Activate start
input
start sequence
MEC 320 GENSET CONTROLLER
GB close
sequence
Mains load
= 0 kW
Yes
MB open
sequence
deactivate start
input
No
ramp-up
genset load
genset
operation
MB close
sequence
GB open
sequence
stop sequenceend
PM079 Rev 0 07/06/08 23 Thomson Technology
Automatic Mains Failure
Start
MEC 320 GENSET CONTROLLER
mains failure
#6595: start
eng+open MB
No
Yes
No
Yes
open MB
start sequence
open MBstart sequence
GB close
sequence
No
GB close
sequence
mains ok
Yes
time out
MB close
sequence
end
PM079 Rev 0 07/06/08 24 Thomson Technology
Test sequence
Start
select test
mode
start sequence
test timer
timer run out
Yes
stop sequence
engine stopped
No
return to
running mode,
menu 6544
end
MEC 320 GENSET CONTROLLER
No
No
engine running
Yes
No
freq/voltage OK
Yes
Sync of GB
allowed
Yes
sync GB
ramp up to P
set point
No
PM079 Rev 0 07/06/08 25 Thomson Technology
MEC 320 GENSET CONTROLLER
1 2
OFF
OFF
formation about the required breaker
wiring.
Sequences
The following contains information about the sequences of the engine, the generator breaker
and, the mains breaker. These sequences are automatically initiated if the auto mode is
selected, or if the commands are selected in the semi-auto mode.
In the semi-auto mode the selected sequence is the only sequence initiated (e.g. press the
START push-button: The engine will start, but no subsequent synchronizing is initiated).
The following sequences will be illustrated below:
START sequence
•
STOP sequence
•
Breaker sequences
•
START sequence
The drawings illustrate the start sequences of the gen-set.
Refer to our ‘Application Notes’ for in
Start sequence:
Run coil
Start attempts
Running feedback
PM079 Rev 0 07/06/08 26 Thomson Technology
MEC 320 GENSET CONTROLLER
1 2
Start sequence:
Stop coil
Stop output
Start attempts
Running feedback
4 different types of running feedback can be used to detect if the motor is running. Refer to
menu 4300 for selection of the running feedback type.
The running detection is made with a built-in safety routine. The running feedback selected in
menu 4300 is the primary feedback. At all times all the types of running feedback is used for
running detection. If for some reason the primary choice is not detecting any running feedback,
the starter relay will stay activated for additionally 1 second. If a running feedback is detected
based on one of the secondary choices, the gen-set will start. This way the gen-set will still be
functional even though a tacho sensor is damaged or dirty.
As soon as the gen-set is running, no matter if the gen-set is started based on the primary or
secondary feedback, the running detection will be made based on all 4 types.
The sequence is shown in the diagram below.
PM079 Rev 0 07/06/08 27 Thomson Technology
MEC 320 GENSET CONTROLLER
1 2
OFF
OFF
3
Running feed
back
OFF
OFF
1
sec
t
Alarm
Start attempts
Primary Running
Running feedback error:
Run coil
Secondary
Engine running
PM079 Rev 0 07/06/08 28 Thomson Technology
MEC 320 GENSET CONTROLLER
gen-set is running.
If the tacho input is to be used to remove the starter, it has to be set up in menu
6161. If the digital input is to be used as running feedback, then terminal 115
has to be used.
nce
when the ‘fire pump’ input is activated, are the digital input ‘emergency stop’
and the tacho alarm ‘overspeed 2’. Both of these must have the fail class ‘shut
Interruption of start sequence
The start sequence is interrupted in the following situations:
Event Comment
Stop signal
Start failure
Remove starter
Tacho set point.
feedback
Running feedback Digital input.
Running feedback Tacho set point.
Running feedback Frequency measurement above 32Hz.
The frequency measurement requires a voltage measurement of 30%
* U
.
NOM
The running detection based on the frequency measurement can
replace the running feedback based on tacho or digital input or engine
communication.
Emergency stop
Alarm Alarms with ‘shutdown’ or ‘trip and stop’ fail class.
Stop push-button on
Only in semi-auto or manual mode.
display
Modbus stop command Semi-auto or manual mode.
Binary stop input Semi-auto or manual mode.
Deactivate the ‘auto
Auto mode in the load take over mode.
start/stop’
Running mode It is not possible to change the running mode to ‘block’ as long as the
The only protections that can stop the gen-set/interrupt the start seque
Start failure alarm
down’.
(6180 Start attempts)
The start failure alarm occurs, if the gen-set has not started after the last start attempt. Output A
(OA) and output B (OB) in this menu indicate the relay output(s) which will be activated at a start
failure alarm.
Start prepare
(6170 Starter)
The start prepare timer can be used for start preparation purposes, e.g. pre-lubrication or preglowing.
PM079 Rev 0 07/06/08 29 Thomson Technology
MEC 320 GENSET CONTROLLER
t
Coolin
g-down time
Stop sequence
/STOP coil
t
t
Stop sequence
The drawings illustrate the stop sequence.
Stop sequence
/RUN coil
Cooling-down time
Running feedback
COOL
EXT
Stop coil
EXT
Running feedback
PM079 Rev 0 07/06/08 30 Thomson Technology
MEC 320 GENSET CONTROLLER
When the engine is stopped, then the speed governor output is reset to the
offset value if option E1 or EF2 is selected, or the initial value if option EF3 is
riptions of the
Stop sequence, description
The stop sequence will be activated, if a stop command is given. The stop sequence includes
the cooling-down time, if the stop is a normal or controlled stop.
Description Cooling-down Stop Comment
Auto mode stop X X
Trip and stop alarm X X
Stop button on display X Semi-auto or manual.
Remove ‘auto start/stop’ X X Auto mode: load take over.
Emergency stop X Engine shuts down and GB opens.
The stop sequence can only be interrupted during the cooling-down period. Interruptions can occur
in these situations:
Event Comment
Mains failure AMF mode selected (or mode shift selected ON) and auto
mode selected.
Start button is pressed Semi-auto mode: Engine will run in idle speed.
Binary start input Auto mode: load take over.
GB close button is pressed Semi-auto mode only.
The stop sequence can only be interrupted during the cooling-down period.
selected and the PWM output is used. Please refer to the desc
mentioned options.
Stop failure alarm
A stop failure alarm will occur, if the running feedback or the generator voltage and frequency are
still active. The stop failure timer is adjusted in
in this menu indicate the relay output(s) that will be activated at a stop failure alarm.
Breaker sequences
The breaker sequences will be activated depending on the selected mode:
Mode Gen-set mode Breaker control
Auto All Controlled by the unit
Semi-auto All Push-button
Manual All None
Block All None
6220 Stop failure
. Output A (OA) and output B (OB)
PM079 Rev 0 07/06/08 31 Thomson Technology
MEC 320 GENSET CONTROLLER
ted the MEC 320 will start synchronizing, if
Before closing the breakers it must be checked that the voltage and frequency are OK. The limits
are adjusted in
2040 Sync. blackout
.
MEC 320 without back Synchronization:
The GB can only be closed, if the mains breaker is open.
The MB can only be closed, if the generator breaker is open.
MEC 320 with back Synchronization:
If the GB or MB push-button is activa
the generator or mains voltage is present.
The GB can close directly, if the MB is open.
The MB can close directly, if the GB is open.
AMF MB opening function
(6590 Mains failure voltage)
It is possible to select the functionality of the mains breaker closing function. This is necessary, if
the unit operates in Automatic Mains Failure (AMF).
The possibilities are:
Start engine and open mains breaker
When a mains failure occurs, the mains breaker
opens, and the engine starts at the same time.
Start engine When a mains failure occurs, the engine starts.
When the generator is running and the frequency
and voltage are OK, the MB opens and the GB
closes.
AMF timers
The time charts describe the functionality at a mains failure and at mains return. Back
Synchronization is deactivated. The timers used by the AMF function are indicated in the table
below:
Timer Description Menu number
tFD Mains failure delay
6600 Mains failure
frequency
Mains failure
6590
voltage
tFU Frequency/voltage OK
t
Mains failure OK delay
FOD
6190 f/U OK
6600 Mains failure
frequency
Mains failure
6590
voltage
t
GB ON delay
GBC
t
MB ON delay
MBC
6250 GB control
6610 Mains breaker
control
The timer t
control)
is only active, if back Synchronization is deactivated
MBC
.
(6610 Mains breaker
PM079 Rev 0 07/06/08 32 Thomson Technology
MEC 320 GENSET CONTROLLER
detected
FD
FOD
Gen running
MCB
FU
t
GBC
detected
Gen start seq
tFD
Gen
stop seq
Mains OK
t
FOD
tFU
t
MBC
Gen running
Gen f/U OK
Example 1 (6590 Mains failure voltage)
Start engine and open MB:
Mains OK
MB On
GB On
Gen start seq
t
Gen stop seq
Gen f/U OK
t
Mains failure
Example 2 (6590 Mains failure voltage)
Start engine:
Conditions for breaker operations
Mains OK
MB On
GB On
t
t
Mains OK
Mains failure
The breaker sequences react depending on the breaker positions and the frequency/voltage
measurements.
PM079 Rev 0 07/06/08 33 Thomson Technology
MEC 320 GENSET CONTROLLER
The conditions for the ON and OFF sequences are described in the table below:
Conditions for breaker operations
Sequence Condition
GB ON, direct closing Running feedback
Generator frequency/voltage OK
MB open
MB ON, direct closing Mains frequency/voltage OK
GB open
GB ON, synchronizing Running feedback
Generator frequency/voltage OK
MB closed
No generator failure alarms
MB ON, synchronizing Mains frequency/voltage OK
GB closed
No generator failure alarms
GB OFF, direct opening MB open
MB OFF, direct opening Alarms with fail classes:
This chapter deals with the display unit including the push-button and LED functions. In addition,
the unit menu structure will be presented.
Display unit
The display has 4 different lines, each with 20 characters, and holds a number of push-button
functions.
Push-button functions
The display unit holds a number of push-button functions which are presented below.
INFO: Shifts the display 3 lower lines to show the alarm list.
JUMP: Enters a specific menu number selection. All settings have a specific number
VIEW: Shifts the first line displaying in the setup menus.
LOG: Shifts the display 3 lower lines to show the event and alarm list. The list holds
Display dimensions are H x W = 115 x 220 mm (4.528” x 9.055”).
attached to them. The JUMP button enables the user to select and display any
setting without having to navigate through the menus (see later).
150 events. The events are not deleted when the auxiliary supply is switched
off.
: Moves the cursor left for maneuvering in the menus.
: Increases the value of the selected set point (in the setup menu). In the daily
use display, this button function is used for scrolling the second line displaying
SEL: Is used to select the underscored entry in the fourth line of the display.
of generator values.
: Decreases the value of the selected set point (in the setup menu). In the daily
use display, this button function is used for scrolling the second line displaying
of generator values.
: Moves the cursor right for maneuvering in the menus.
BACK: Jumps one step backwards in the menu (to previous display or to the entry
START: Start of the gen-set
STOP: Stop of the gen-set
(GB) ON: Manual activation of close breaker and open breaker sequence
(MB) ON: Manual activation of close breaker and open breaker sequence
window).
is selected
is selected
if ‘SEMI-AUTO’ or ‘MANUAL’ is selected
if ‘SEMI-AUTO’ or ‘MANUAL’ is selected
.
.
if ‘SEMI-AUTO’
.
if ‘SEMI-AUTO’
.
MODE: Changes the menu line (line 4) in the display to mode selection.
PM079 Rev 0 07/06/08 35 Thomson Technology
MEC 320 GENSET CONTROLLER
ALARM STATUS:
AUTO:
.
Shifts the first line
displaying in the setup
menus.
d
Selects the underscored entry in the fourth
The push-buttons are placed as follows:
GB: TRIP/CLOSE
Opens the GB, if it is closed.
Closes (sync.) the GB, if it is opened.
MB:
Opens the MB, if it is closed.
Closes (sync.) the MB, if it is opened.
OFF:
Stop of the gen-set
if ‘SEMI-AUTO’ or
Place the gen-set in ‘AUTO’
RUN:
Manual start and run the gen-set.
ENTER:
display line.
Shifts the display three lower lines to show the alarm list.
RESET:
Reset alarms on the controller.
EVENT LOG:
Shifts the display three lower lines to show the event an
alarm list.
JUMP:
Enters a specific menu number selection.
VIEW:
EXIT:
Jumps one step
backwards in the menu.
PM079 Rev 0 07/06/08 36 Thomson Technology
MEC 320 GENSET CONTROLLER
LED functions
The display unit holds 10 LED functions. The colour is green or red or a combination in different
situations.
Alarm/ShutDown: LED flashing indicates that unacknowledged alarms are present.
LED fixed light indicates that ALL alarms are acknowledged.
Power: LED indicates that the auxiliary supply is switched on.
Self check OK: LED indicates that the self check is OK.
Alarm inh: Gen-set is stopped:
LED fixed light indicates that the unit does not receive a running signal.
The inhibit lamp will be switched off when the run status timer times out
(6150 Running status).
Gen-set is running:
LED fixed light indicates that the digital input is activated.
Run: LED indicates that the generator is running.
(Gen.) OK: LED green light indicates that the voltage/frequency is present and OK.
(GB) ON: LED green light indicates that the generator breaker is closed.
LED yellow light indicates that the generator breaker has received a
command to close on a black BUS, but the breaker is not yet closed
due to interlocking of the GB.
(MB) ON: LED indicates that the mains breaker is closed.
(Mains) OK: LED is green, if the mains is present and OK.
LED is red at a measured mains failure.
LED is flashing green when the mains returns during the ‘mains OK
delay’ time.
The display includes two menu systems which can be used without password entry:
View menu system
This is the commonly used menu system. 15 windows are configurable and can be
entered by using the arrow push-buttons.
Setup menu system
This menu system is used for setting up the unit, and if the user needs detailed
information that is not available in the view menu system.
Changing of parameter settings is password protected.
Entry window
When the unit is powered up, an entry window appears. The entry window is the turning point in
the menu structure and as such the gateway to the other menus. It can always be reached by
pressing the EXIT push-button 3 times.
The event and alarm list will appear at power up, if an alarm is present.
PM079 Rev 0 07/06/08 39 Thomson Technology
MEC 320 GENSET CONTROLLER
View menu
The view menus (V1, V2 and V3) are the most commonly used menus of the unit.
First display line
Operational status or measurements Measurements relating to operational status
Second and third display line
Fourth display line
Selection of setup and view menus
In the view menus various measured values are on display.
View window configuration
The individual view windows need to be configured through the PC software in the dialog box
illustrated below.
Use this button to go to the configuration.
Select the view window to be configured.
PM079 Rev 0 07/06/08 40 Thomson Technology
MEC 320 GENSET CONTROLLER
–
Click here to change the configuration.
The selectable values and measurements are presented in the table on page 44 in this
handbook.
If the text ‘no text’ is selected in all 3 lines in a window, it will not be displayed. This is to get a
continuous displaying, if a window is not to be used.
It is only possible to configure the view windows via the PC software
configuration via the display unit is not possible.
There is a maximum of 15 configurable view windows in V1.
The menu navigating starts from the fourth display line in the entry window and is carried out
using the , , and push-buttons.
The entry window displays view 3, (in the illustration above the window where ‘manual’ is
displayed).
Moving the cursor left or right offers the following possibilities.
Setup menu – access to the following sub-menus:
•
- Protection setup
- Control setup
- I/O setup
- System setup
View 3 – window displays operational status and selectable measurements
•
View 2 – window displays selectable measurements
•
View 1 – access to up to 15 selectable windows displaying selectable measurements
•
PM079 Rev 0 07/06/08 43 Thomson Technology
MEC 320 GENSET CONTROLLER
Setup menu
The setup menu system is used for parameter setup of the unit, and if the user needs detailed
information that is not available in the view menu system. So, this menu can be used for both
daily use and setup purposes. The menu is entered from the entry window by selecting the entry
SETUP in the fourth display line.
First display line
(Daily use) The first line is used to display generator and BUS values
Second display line
(Daily use) Various values can be displayed
(Menu system) Information about the selected channel number
(Alarm/event list) The latest alarm/event is displayed
Third display line
(Daily use) Explanation for the fourth line cursor selection
(Setup menu) Presents setting of the selected function, and, if
changes are made, the possible max. and min. values
for the setting
Fourth display line
(Daily use) Entry selection for the setup menu. Press SEL to enter the underscored menu
(Setup menu) Sub-functions for the individual parameters, e.g. limit
Possible values in second display line
View line/second display line configuration
For generator For bus/mains For analogue input Communication/
other
Voltage L1 L2 L3 (V AC) Voltage L1 L2 L3 (V AC) Analog 98 PID Value #1.1
Voltage L1-N (V AC) Voltage L1-N (V AC) Analog 100 (oil press.) PID Value #1.2
Voltage L2-N (V AC) Voltage L2-N (V AC) PID value #1.3
Voltage L3-N (V AC) Voltage L3-N (V AC) Analog 102 (fuel level) PID value #1.4
Voltage L1-L2 (V AC) Voltage L1-L2 (V AC) Analog 104 PID value #1.5
Voltage L2-L3 (V AC) Voltage L2-L3 (V AC) Analog 91 PID value #1.6
Voltage L3-L1 (V AC) Voltage L3-L1 (V AC) Analog 93 PID value #1.7
Voltage max. (V AC) Voltage max. (V AC) Analog 95 PID value #1.8
Voltage min. (V AC) Voltage min. (V AC) Analog 97 PID value #2.1
Current L1 L2 L3 (A) Frequency (Hz) PT100 no. 106 PID value #2.2
Current L1 (A) Frequency/voltage L1 (Hz/
V AC)
Current L2 (A) Tacho PID value #2.4
Current L3 (A) Voltage angle between L1-
L2 (deg.)
Frequency/voltage L1 (Hz/V
AC)
VDO 105 (temperature) PID value #2.6
PT100 no. 109 PID value #2.3
VDO 104 (pressure) PID value #2.5
PM079 Rev 0 07/06/08 44 Thomson Technology
MEC 320 GENSET CONTROLLER
MEC 320
View line/second display line configuration
For generator For bus/mains For analogue input Communication/
other
Frequency L1 (Hz) VDO 106 (fuel level) PID value #2.7
Frequency L2 (Hz) PID value #2.8
Frequency L3 (Hz)
Power factor/active power
(PF/kW)
Active power (kW) Mains power (kW) Date and time
Reactive power/apparent
power
(kvar)/ (kVA) Negative current
Reactive power (kvar) Zero voltage
Apparent power (kVA) Zero current
Energy counter (kWh)
Power factor
Voltage angle between L1L2 (deg.)
Voltage angle between L2L3 (deg.)
Voltage angle between L3L1 (deg.)
Absolute run time (h)
Relative run time (h)
Next priority shift (h and
min.)
Fire run
Number of GB operations
Number of MB operations
Next service
G 439 440 440V
PROTECTION SETUP
SET POINT 1 SETUP
PROT1 PROT2
G 439 440 440V
CONTROL SETUP
SYNCHRONICE SETUP
SYNC REG
G 439 440 440V
INPUT/OUTPUT SETUP
BINARY INPUT SETUP
BIN AIN OUT
G 439 440 440V
SYSTEM SETUP
GENERAL SETUP
GEN MAINS COMM PM
Setup example
The following example illustrates how a specific setting is changed in the setup menu. In this
case
Reverse power
is the selected parameter.
PM079 Rev 0 07/06/08 45 Thomson Technology
DECREASE NO
G 439 440 440V
PROTECTION SETUP
SET POINT 1 SETUP
PROT1 PROT2
MEC 320 GENSET CONTROLLER
SELBACK
G 439 440 440V
1010 Reverse Power
Setpoint -5.0 %
LIM DEL OA OB ENA FC
BACKSEL
first entry
No
G 439 440 440V
1011 Reverse power
-50.0 -5.0 0.0%
RESET SAVE
Yes
G 439 440 440V
1020 Over current 1
Setpoint 115.0 %
LIM DEL OA OB ENA FC
G 439 440 440V
Enter passw. 1999
ENTER
Increase setting
Decrease setting
moves the cursor
INCREASE NO
Mode overview
The unit has four different running modes and one block mode. For detailed information see
page 9.
Auto
In auto mode the unit will operate automatically, and the operator cannot initiate any sequences
manually.
Semi-auto
In semi-auto mode the operator has to initiate all sequences. This can be done via the pushbutton functions, modbus commands or digital inputs. When started in semi-automatic mode,
the gen-set will run at nominal values.
Test
The test sequence will start when the test mode is selected.
Manual
When manual mode is selected, the binary increase/decrease inputs can be used (if they have
been configured) as well as the start and stop push-buttons. When starting in manual mode, the
gen-set will start without any subsequent regulation.
PM079 Rev 0 07/06/08 46 Thomson Technology
MEC 320 GENSET CONTROLLER
set.
Block
When the block mode is selected, the unit is not able to initiate any sequences, e.g. the start
sequence.
Block mode must be selected, when maintenance work is carried out on the gen-
Mode selection
The following drawings illustrate how the mode selection is carried out.
Pushing the MODE push-button will change the displayed text. After pushing ‘MODE’, the fourth
display line indicates the selectable modes. In the third display line, the underscored (fourth line)
selection will be displayed.
Two possibilities are now available:
If ‘BACK’ is pushed, the display returns to the original text without changing the mode.
MEC 320 V. 2.10.0
2005-01-01 13 : 45 : 18
SETUP MENU
SETUP V3 V2 V1
MEC 320 V. 2.10.0
2005-01-01 13 : 45 : 18
SEMI-AUTO MODE
SEMI TST AUT MAN BLK
or
G 0 0 0V
f-L1 0.00Hz
SEMI-AUTO MODE
SEMI TST AUT MAN BLK
MEC 320 V. 2.10.0
2005-01-01 13 : 45 : 18
SEMI-AUTO MODE
SEMI TST AUT MAN BLK
or
G 0 0 0V
f-L1 0.00Hz
SEMI-AUTO MODE
SEMI TST AUT MAN BLK
2. push
‘BACK’
2. push
‘BACK’
4. push
‘SEL’
4. push
‘SEL’
PM079 Rev 0 07/06/08 47 Thomson Technology
MEC 320 GENSET CONTROLLER
Password
The unit includes three password levels. All levels can be adjusted in the PC software.
Available password levels:
Access Password level Factory setting
Customer Service Master
Customer 2000 X
Service 2001 X X
Master 2002 X X X
A parameter cannot be entered with a too low ranking password. But the settings can be
displayed without password entry.
Each parameter can be protected at a specific password level. To do so, the PC utility software
must be used. Enter the parameter to be configured and select the correct password level.
PM079 Rev 0 07/06/08 48 Thomson Technology
MEC 320 GENSET CONTROLLER
The master password can be changed in menu 9118 page
115.
set is not
It is not possible to change the password at a higher level than the password
Parameter access
To get access to adjust the parameters, the password level must be entered:
If the password level is not entered, it is not possible to enter the parameters.
The customer password can be changed in menu 9116 page 115.
The service password can be changed in menu 9117 page 115.
The factory passwords must be changed, if the operator of the genallowed to change the parameters.
entered.
PM079 Rev 0 07/06/08 49 Thomson Technology
MEC 320 GENSET CONTROLLER
The short time paralleling function is only available in the automatic mains
The same time delay is used for both generator and mains breaker
The time delay typed in the set point is a maximum time. This means that if 0.10
seconds are used, the two breakers will never be closed at the same time for a
longer delay than the set point.
6. Additional functions
This chapter describes the additional functions.
Short time parallel
The purpose of the
between the generator and the mains supply.
The function is typically used, if there are local requirements to maximum allowed paralleling
time.
failure and load take over gen-set modes.
short time parallel
function is to be able to define a maximum paralleling time
MB
tt
GB
t
The diagram shows that when the generator breaker is synchronized, the mains breaker will be
opened automatically after a time delay (t). Later the mains breaker is synchronized, and the
generator breaker is opened after the time delay (t).
The time delay is measured in seconds and can be adjusted from 0.10 to 99.90 seconds.
The short time parallel function is set up in
synchronization.
2700 Short time paralleling.
PM079 Rev 0 07/06/08 50 Thomson Technology
MEC 320 GENSET CONTROLLER
oftware when setting up the time dependent
The derate function is typically used when cooling problems are expected.
nfigured with different minimum
and maximum settings. In this case the settings ‘start derate point’ and
‘slope’ use these new settings.
Time dependent start/stop
The purpose of the time dependent start/stop function is to be able to start and stop the gen-set
automatically at specific times each weekday or certain weekdays. Auto mode must be activated
for this function. Up to 8 commands can be used for either start or stop. The settings are set up
through the PC utility software. Each command can be set for the following time periods:
Individual days (MO, TU, WE, TH, FR, SA, SU)
•
MO, TU, WE, TH
•
MO, TU, WE, TH, FR
•
MO, TU, WE, TH, FR, SA, SU
•
SA, SU
•
It is necessary to use the PC utility s
start/stop function.
Derate gen-set
The purpose of the derate function is to be able to reduce the maximum output power of the
gen-set, if specific conditions require this. An example of such a condition is the ambient
temperature. If the ambient temperature increases to a level where the cooling water coolers
decrease in cooling capacity, it will be necessary to reduce the power of the gen-set.
If the gen-set is not derated, alarms and shutdown events will very likely occur.
Input selection
The derate function can be configured to one of the following inputs:
Input
Engine interface
selection
Analogue input 100 X
VDO input 105 X
VDO input 106 X
Select the needed input in 6260
Pnom derate
.
Refer to the type label for information about engine interface selection.
Derate parameters
The parameters that define the derate characteristics are the following:
Start derate point
(6260 P
derate ):
nom
This is the setting where the derating must start. The setting can be in mA (max. 20mA) or
in centigrades ºC (max 200ºC).
Slope
( 6260 P
derate ):
nom
Adjust the derating speed. The adjustment is in percent per unit, i.e. if the 4…20mA input is
used (analogue 100), then the derating will be in %/mA, and if the PT100/VDO input is
used, then the derating will be in %/C.
Be aware that the 4…20mA input can be co
PM079 Rev 0 07/06/08 51 Thomson Technology
MEC 320 GENSET CONTROLLER
P
P
LIMIT
P
derate
P
P
LIMIT
P
increase
Derate limit
( 6260 P
derate):
nom
This is the lowest derate level.
NOM
Start
Derate characteristic
It can be selected whether the characteristic of the derating should be proportional or inverse
proportional. The drawing above shows the inverse characteristic.
The proportional characteristic is illustrated below.
NOM
Start
The gen-set is derated when the control value is lower than the set point (in the example above
the control value is an mA signal).
The derate characteristic is selected in
6260 Pnom derate
.
Setting OFF: Inverse characteristic
Setting ON: Proportional characteristic
PM079 Rev 0 07/06/08 52 Thomson Technology
MEC 320 GENSET CONTROLLER
In addition to the actions defined by the fail classes, it is possible to activate
set before opening the
Fail class
All activated alarms must be configured with a fail class. The fail classes define the category of
the alarms and the subsequent alarm action.
Six different fail classes can be used. The tables below illustrate the action of each fail class
when the engine is running or stopped.
Engine running
Action
Fail class
1 Alarm X X
2 Warning X X
3 Trip of GB X X X
4 Trip and stop X X (X) X X X
5 Shutdown X X X X
6 Trip of MB X X X
The table illustrates the action of the fail classes. If, for instance, an alarm has been configured
with the ‘shutdown’ fail class, the following actions occur.
Engine stopped
Action
Fail class
1 Alarm X
2 Warning
3 Trip of GB X X
4 Trip and stop X X
5 Shutdown X X
6 Trip of MB X
The alarm horn relay will activate
•
The alarm will be displayed in the alarm info screen
•
The generator breaker will open instantly
•
The gen-set is stopped instantly
•
The gen-set cannot be started from the unit (see next table)
•
The fail class ‘trip and stop’ will only deload the genbreaker, if option G5 (power management) is included.
one or two relay outputs, if additional relays are available in the unit.
The fail class can be selected for each alarm function either via the display or the PC software.
To change the fail class via the PC software, the alarm function to be configured must be
selected. Select the desired fail class in the fail class roll-down panel.
down panel is acti-
of GB’ fail class.
Service timers
The unit is able to monitor the maintenance intervals. The menu is available in the system setup.
6090 Service timerThe function is based on running hours. When the adjusted time expires, the
unit will display an alarm. The ‘alarm acknowledge’ function resets this alarm.
When acknowledging the alarm, the timer will be reset and a new service timer alarm will only
reoccur after the adjusted time has elapsed. The running hours is counting, when the running
feedback is present.
Wire break detection
If it is necessary to supervise the sensors/wires connected to the analogue inputs (4-20mA,
VDO and PT100), then it is possible to use the menus 4370-4430 depending on the HW options
available in the unit. If the measured value on the input is outside the normal dynamic area of
the input, it will be detected, as if the wire has made a short circuit or a break. An alarm with a
configurable fail class will be activated.
The illustration below shows that when the wire of the input breaks, the measured value will drop
to zero. Then the alarm will occur.
Input signal
(mA, °C, b, %)
Upper failure
limit
Lower failure
limit
t
Wire break
VDO settings
The alarm set point of the VDO inputs can be calculated in percent like this:
VDO 104, oil pressure:
100*240/%settingdeviation
VDO 105, cooling temp.:
100*530/%settingdeviation
VDO 106, fuel level:
%
settingdeviation
100*240/
The deviation is the alarm value entered in percent, and the setting is the required alarm setting
in ohms.
Example:
Required set point of VDO104 is 180. The adjustment must be:
deviation
deviation
%
%75
%
=
100*240/180
PM079 Rev 0 07/06/08 55 Thomson Technology
MEC 320 GENSET CONTROLLER
If the VDO input is used as a level switch, then be aware that no voltage must be
ts, then it will be
VDO inputs
There are three VDO inputs in the unit. The inputs have different functions, as the hardware
design allows for several VDO types.
VDO input 104: Oil pressure
VDO input 105: Cooling water temperature
VDO input 106: Fuel level sensor
VDO input 104
This VDO input is used for measuring the lubricating oil pressure.
VDO sensor type
Pressure Type 1 Type 2 Type configurable
Bar
0 10.0 10.0 Point 1
0.5 27.2
1.0 44.9 31.3
1.5 62.9
2.0 81.0 51.5
2.5 99.2 Point 2
3.0 117.1 71.0
3.5 134.7
4.0 151.9 89.6
4.5 168.3
5.0 184.0 107.3 Point 3
6.0 124.3 Point 4
7.0 140.4 Point 5
8.0 155.7 Point 6
9.0 170.2 Point 7
10.0 184.0 Point 8
Level switch type
The configurable type is configurable with 8 points.
VDO sensor type
Type level switch
Resistance Function
>200Normal situation, no alarm
<200Alarm situation
connected to the input. If any voltage is applied to the VDO inpu
damaged. Refer to the Application Notes for further wiring information.
PM079 Rev 0 07/06/08 56 Thomson Technology
MEC 320 GENSET CONTROLLER
If the VDO input is used as a level switch, then be aware that no voltage must be
o the VDO inputs, then it will be
If the VDO input is used as a level switch, then be aware that no voltage must be
e is applied to the VDO inputs, then it will be
VDO input 105
This VDO input is used for measuring the cooling water temperature.
VDO sensor
type
Temperature Type 1 Type 2 Type 3 Type 4
°C
40 291.5 480.7 69.3 Point 1
50 197.3 323.6 Point 2
60 134.0 222.5 36.0 Point 3
70 97.1 157.1 Point 4
80 70.1 113.2 19.8 Point 5
90 51.2 83.2 Point 6
100 38.5 62.4 11.7 Point 7
110 29.1 47.6 Point 8
120 22.4 36.8 7.4
130 28.9
140 22.8
150 18.2
Level switch type
The configurable type is configurable with 8 points.
VDO sensor type
Type 3
Resistance Function
<1.7kNormal situation, no alarm
>1.7kAlarm situation
connected to the input. If any voltage is applied t
damaged. Refer to the Application Notes for further wiring information.
VDO input 106
This VDO input is used for the fuel level sensor.
VDO sensor type
Type 1
Value Resistance
0% 78.8
100% 1.6
VDO sensor type
Type 2
Value Resistance
0% 3
100% 180
PM079 Rev 0 07/06/08 57 Thomson Technology
connected to the input. If any voltag
damaged. Refer to the Application Notes for further wiring information.
MEC 320 GENSET CONTROLLER
7 6 5 4 3 2 1
C or %)
VDO sensor
type
Value Type
configurable
% Resistance
0 Point 1
10
20
30
40 Point 2
50 Point 3
60 Point 4
70 Point 5
80 Point 6
90 Point 7
100 Point 8
VDO usage
The VDO inputs are used as alarm inputs and can be configured in the following menus:
The configurable type is configurable with 8 points.
VDO input 104: Lubricating oil pressure – alarm settings in menus 4170/4180.
VDO input 105: Cooling water temperature – alarm settings in menus 4190/4200.
VDO input 106: Fuel level switch – alarm settings in menus 4210/4220.
Illustration of configurable inputs
Resistance
()
Set point 8
Set point 7
Set point 6
Set point 5
Set point 4
Set point 3
Set point 2
Set point 1
Value
(bar, °
8
Set points
Configuration
PM079 Rev 0 07/06/08 58 Thomson Technology
MEC 320 GENSET CONTROLLER
The 8 curve settings for the configurable VDO inputs cannot be changed in the display, but
in the PC utility software. The alarm settings can be changed both in the display and in the PC
utility software. In the PC utility software the configurable inputs are adjusted in this dialog box:
Adjust the resistance of the VDO sensor at the specific measuring value. In the example above
the adjustment is 10 at 0.0 bar.
only
Language selection
The unit has the possibility to display different languages. English is the default language, and it
cannot be changed. In addition to the master language 11 different languages can be
configured. This is done via the PC utility software.
The languages are selected in the system setup
The language can be changed when connected to the PC utility software. It is not possible to
make language configuration from the display, but the already configured languages can be
selected.
(6130 Language)
Buttons used in the PC utility software
Retrieve languages from the device:
Activating this button will retrieve the configured languages from the device.
Send languages to the device:
Activating this button will send the content of the 11 language frames to the device.
Synchronize a language file with the device:
Activating this button will synchronize a language file from a previous version of the
software with a newer version. New functions that are not translated will be marked.
Copy master language to other languages:
Activating this button will send the master language to the 11 language frames
(except for the already configured texts).
PM079 Rev 0 07/06/08 59 Thomson Technology
MEC 320 GENSET CONTROLLER
Language configuration
Besides the master language 11 empty language shells are available. These empty shells can
be filled in via the PC utility software.
In the PC utility software the language is configured in the
by pressing the
Translations
icon (see below):
Translations
menu. Activate the menu
All configurable entries are indicated in the left side column. The list can be scrolled with page
DOWN/UP.
Example:
Language 1 = Spanish.
Tacho name is changed in this example:
’Tacho’ is changed to ’ ’
•
‘RPM’ is changed to ‘ ’
•
Select the line which needs to be edited.
PM079 Rev 0 07/06/08 60 Thomson Technology
MEC 320 GENSET CONTROLLER
d will
in this case use up 5 characters. It is not possible to change the number of
Select the text to be
configured:
Tacho
Select language 1 and write the relevant text.
Write the relevant text here.
In this example:
Omdr pr min#####omdr
When the relevant texts have been configured, they can be downloaded to the unit.
The symbol ‘#####’ indicates the measured value (in this case the actual RPM).
There is a maximum of 20 characters/text. The symbol ##### is included an
characters in the measurement symbol (#####).
PM079 Rev 0 07/06/08 61 Thomson Technology
MEC 320 GENSET CONTROLLER
Translation status
To give an overview of the translated menus, a status indication can be given for each
parameter. The check mark is green, and the cross is red.
Symbols
The following symbols can be used for this function:
! “ # $ % & ´ ( ) * + , - . /
0 1 2 3 4 5 6 7 8 9 : ; < = > ?
@ A B C D E F G H I J K L M N O
P Q R S T U V W X Y Z [ \ ] ^ _
` a b c d e f g h i j k l m n o
p q r s t u v w x y z { | } ~
Texts in status line
The status texts must be self-explaining. If the operator does something wrong, then the status
line must indicate it. The table below indicates the texts in the status line.
Status text Condition Comment
BLOCK
Simple TEST The TEST is activated. The
gen-set will be started, but it is
not allowed to close the
generator breaker.
Load TEST The TEST is activated. The
gen-set will be started, and
the generator breaker will be
synchronized/closed.
ISLAND MANUAL
ISLAND SEMI-AUTO
ISLAND AUTO
AMF MANUAL
AMF SEMI-AUTO
AMF AUTO
FIXED MANUAL
FIXED SEMI-AUTO
FIXED AUTO
Peak shave MANUAL
Peak shave SEMI-AUTO
Peak shave AUTO
LTO MANUAL
If the gen-set is stopped, or if
it is running and no other
action takes place.
The test will be parallel to
mains.
PM079 Rev 0 07/06/08 62 Thomson Technology
MEC 320 GENSET CONTROLLER
Status text Condition Comment
LTO SEMI-AUTO
LTO AUTO
MPE MANUAL
MPE SEMI-AUTO
MPE AUTO
PM MANUAL
PM SEMI-AUTO
PM AUTO
Fire pump If the configurable input is
active.
Display locked If the ‘Access lock’ input is
activated, and the operator
tries to activate one of the
blocked keys.
GB tripped externally This info. will be shown, if
some external equipment has
An external trip is logged in
the event log.
tripped the breaker.
MB tripped externally This info. will be shown, if
some external equipment has
An external trip is logged in
the event log.
tripped the breaker.
TB tripped externally This info. will be shown, if
some external equipment has
An external trip is logged in
the event log.
tripped the breaker.
Power derate If the ‘power derate’ function
is activated and the nominal
power set point has been
decreased, this info. will
appear.
Idle run If the ‘Idle run’ function is
active, this info. will appear to
inform the user that the gen-
set will not stop, until a timer
has expired.
Idle run ###.#min. If the timers in the ‘Idle run’
function are active, this info.
will appear to inform the user
that the gen-set will not
start/stop, until a timer has
expired.
Compensation freq. Compensation is active. To inform the user that there
is a reason why the frequency
is not at the nominal setting.
Aux. test ###V ####s This info. is shown during a
battery test.
Deload This info. is shown when
decreasing the load of the
gen-set.
Starting DG(s) ###s When the start gen-set set
point is exceeded, this info. is
shown with the countdown of
the timer.
Stopping DG(s) ###s When the stop gen-set set
point is exceeded, this info. is
shown with the countdown of
the timer.
Start prepare This info. is shown during the
time the start prepare relay is
activated.
PM079 Rev 0 07/06/08 63 Thomson Technology
MEC 320 GENSET CONTROLLER
Status text Condition Comment
Start ON This info. is shown during the
time the start relay is activated
during the start sequence.
Start OFF This info. is shown during the
time the start prepare relay is
deactivated.
Mains failure This text appears as soon as
a frequency or voltage
measurement is outside the
limits.
Mains failure in ###s This text appears as soon as
a frequency or voltage
measurement is outside the
limits. The timer shown is the
mains failure delay.
Mains U OK del ####s When the mains voltage is OK
after a mains failure, this info.
is shown with the countdown
of the timer.
Mains f OK del ####s When the mains frequency is
OK after a mains failure, this
info. is shown with the
countdown of the timer.
Volt./freq. OK in ###s As soon as the voltage and
frequency on the gen-set are
OK, this text is shown until it is
allowed to operate the
generator breaker.
Cooling down ###s When the cooling down period
is started, this info. is shown
with the countdown of the
timer.
Gen-set stopping This info. is shown when cool
down has finished.
Ext. stop t. ###s
Blackout enable This info. is shown, if a CAN
Option G5 must be available.
failure is present in a power
management application.
Programming language This info. is shown, if the
language file is downloaded
from the PC utility software.
PM079 Rev 0 07/06/08 64 Thomson Technology
MEC 320 GENSET CONTROLLER
Service menu
The purpose of the service menu is to give information about the present operating condition of
the gen-set. The service menu is entered using the ‘JUMP’ push-button
(9120 Service menu)
.
Use the service menu for easy trouble shooting in connection with the event log (see page 35).
Entry window
The entry shows the possible selections in the service menu.
G 400 400 400V
9120 Service menu
ALARM
ALARM IN OUT MISC
Available selections:
Alarm
Shows the alarm timer and the remaining time. The indicated remaining time is minimum
remaining time. The timer will count downwards when the set point has been exceeded.
G 400 400 400V
1010 Reverse power
Remaining time 10.0s
UP DOWN
IN (digital input)
Shows the status of the digital inputs.
G 400 400 400V
Running
Input = ON
UP DOWN
OUT (digital output)
Shows the status of the digital outputs.
G 400 400 400V
Horn
Output = OFF
UP DOWN
MISC (miscellaneous)
Shows miscellaneous messages.
G 400 400 400V
M-logic Enabled
Various = OFF
UP DOWN
PM079 Rev 0 07/06/08 65 Thomson Technology
MEC 320 GENSET CONTROLLER
Event log
The event log holds up to 150 events, and they can be viewed in the display or in the PC utility
software. When more than 150 events have occurred, each new event will overwrite the oldest
event following the ‘first in – first out’ principle.
Display
In the display it looks like this when the ‘LOG’ push-button is pressed (example):
G 400 400 400V
4170 Fuel level
06-24 15:24:10.3
INFO FIRST LAST
The specific alarm or event is shown in the second line. In the example above the fuel level
alarm has occurred. The third line shows the time stamp.
If the cursor is moved to ‘INFO’, the actual value can be read when pressing ‘SEL’:
G 400 400 400V
4170 Fuel level
VALUE 8 %
INFO FIRST LAST
The first event in the list will be displayed, if the cursor is placed below ‘FIRST’ and ‘SEL’ is
pressed.
The last event in the list will be displayed, if the cursor is placed below ‘LAST’ and ‘SEL’ is
pressed.
The keyUP and keyDOWN push-buttons are used for navigating in the list.
PC utility software
Using the PC utility software the entire log stack of the last 150 events can be retrieved by
activating the log button on the horizontal toolbar.
The alarms and events are displayed as indicated below. The actual alarms are displayed in the
text column together with selected measurements.
In the right side column additional data is indicated. This is specific data for the most important
measurements. The data is logged for each specific event and is used for troubleshooting after
each alarm.
PM079 Rev 0 07/06/08 66 Thomson Technology
MEC 320 GENSET CONTROLLER
The entire log can be saved in Excel format and in that particular program.
Counters
Counters for various values are included, and some of these can be adjusted if necessary, for
instance if the unit is installed on an existing gen-set or a new circuit breaker has been installed.
The table shows the adjustable values and their function:
Description Function Comment
6081 Running time Offset adjustment of the total running
hours counter.
6082 GB operations Offset adjustment of the number of
generator breaker operations.
6083 MB operations Offset adjustment of the number of
mains breaker operations.
6084 kWh reset Resets the kWh counter. Automatically resets to OFF
6085 Attempts Offset adjustment of the number of
start attempts.
6086 Running time FP The running hour counter for the fire
pump operation can be reset in this
menu.
Counting when the running
feedback is present.
Counting at each GB close
command.
Counting at each MB close
command.
after the reset. The reset
function cannot be left active.
Counting at each start
attempt.
The running hour counter is
shown in the display.
PM079 Rev 0 07/06/08 67 Thomson Technology
MEC 320 GENSET CONTROLLER
7. Procedure for parameter setup
This chapter deals with the procedure to be followed when the parameters of the unit are set up
from the initial point of finding the individual parameter description in this handbook to the actual
setup. By use of various illustrations the following will guide the user through the whole procedure
for parameter setup step by step.
Finding the selected parameter
The first step in the parameter setup is finding the correct parameter descriptions. All parameter
descriptions are located in chapter 8 ‘Parameter list’ which is intended for reference purposes. The
descriptions are structured according to their parameter titles and the main parameter group to
which they belong.
Find the individual parameter title in the overview list on page 71.
In the overview list you will find the page location of the parameter description you are looking for.
PM079 Rev 0 07/06/08 68 Thomson Technology
MEC 320 GENSET CONTROLLER
indicated
in display
display
Default set point
Parameter
number
Small differences due to the character of the parameters may exist between the
Parameter descriptions
In chapter 8 each parameter description is structured according to the same principles. Under the
parameter title heading, the detailed parameter descriptions are illustrated and presented. First, a
table indicating the parameter facts related to the individual parameter title is presented:
Menu
number
title and
menu
Changeable
settings
indicated in
Min. – max.
set points
from factory
1010 Reverse power
No. Setting Min.
setting
1011 Reverse power Set point -50.0% 0.0% - -5.0%
1012 Reverse power Timer 0.1 s 100.0 s - 10.0 s
1013 Reverse power Relay output A R0 (none) R3
1014 Reverse power Relay output B R0 (none) R3
1015 Reverse power Enable OFF ON RUN ON
1016 Reverse power Fail class 1 5 - 3
The first column indicates the menu number in the display.
The second column indicates the changeable setting in the display.
The third and fourth columns indicate the minimum/maximum set point available for this setting.
The sixth column indicates the default set point of the unit from the factory. When it is necessary,
additional information will be supplied after the table in order to make the individual parameter
descriptions as informative as possible.
individual tables.
Max.
setting
(relay 3)
(relay 3)
Third
setting
- R0 (none)
- R0 (none)
Factory
setting
Setup
At this point of the process you will have located the specific parameter description that you were
looking for. Now, follow the menu structure presented earlier in this handbook in order to set up the
individual parameters. (In this overall example we have chosen to change the set point of the
parameter
Step 1: Enter the ‘setup’ menu via SETUP in the fourth display line in the entry window
Step 2: Enter the ‘protection’ menu via PROT in the fourth display line in the setup menu
Step 3: Enter the ‘set point 1’ menu via PROT1 in the fourth display line in the setup menu
Step 4: Use JUMP or the and
Step 5: Enter the ‘set point’ menu via LIM in the fourth display line
Step 6: Enter password to change the set point
Step 7: Use the and
Step 8: Use the ’underscore’ to save the new set point setting
PM079 Rev 0 07/06/08 69 Thomson Technology
1010 Reverse power
).
push-buttons to locate the selected parameter
push-buttons to increase/decrease the set point setting
MEC 320 GENSET CONTROLLER
ue to the character of the parameters may exist between the
8. Parameter list
This chapter includes a complete standard parameter list. Therefore, this part of the handbook is
to be used for reference when specific information about the individual parameters is needed for
the unit setup. An overview list can be seen on the next page.
The table consists of the following possible adjustments:
Set point: The alarm set point is adjusted in the set point menu. The setting is a
Timer: The timer setting is the time that must expire from the alarm level is reached
Relay output A: A relay can be activated by output A.
Relay output B: A relay can be activated by output B.
Enable: The alarm can be activated or deactivated. ON means always activated, RUN
Fail class: When the alarm occurs the unit will react depending on the selected fail class.
It is also possible to configure the parameters by using the PC utility software. It will be possible
to make the same configurations as described above.
By using the PC utility software some extra functionalities are available. For all the protections it
is possible to make an automatic acknowledgement of the alarm. Usually it is important when
the mains protections are used, as the sequences are blocked until the alarm is acknowledged.
The parameter lists for the available options are presented in the documents
Description of Options describing the individual options in detail.
Parameter table description
percentage of the nominal values.
until the alarm occurs.
means that the alarm has run status. This means it is activated when the
running signal is present.
2510 Frequency controller p.76 6070 Date and time (internal clock) setting p.87
2520 Power controller p.76 6080 Counters p.87
2530 Power ramp up p.76 6090 Service timer p.87
2540 Power ramp down p.76 6110 Battery low voltage alarm p.88
2560 Governor regulation failure p.76 6120 Battery high voltage alarm p.88
2640 Relay control p.77 6130 Language p.88
2690 Delay regulation p.77 6140 Alarm horn p.88
2700 Short time paralleling p.77 6150 Running status p.88
6160 Remove starter p.88
4370 Wire failure analogue input 98 p.83 911X User password p.93
4380 Wire failure analogue input 100 p.83 9120 Service menu p.93
4390 Wire failure analogue input 102 p.83 9130 Single phase/split phase/three phase p.93
4410 Wire failure VDO input 104 p.83
Output setup
5090 Relay 9 p.85
General setup
p.75 6030 Transformer gen. p.86
6060 Gen-set modes p.87
6170 Starter p.88
6420 Voltage trip p.90
Mains setup
p.82 6600 Mains failure frequency p.92
Jump menus
p.83 9020 Service port p.93
PM079 Rev 0 07/06/08 71 Thomson Technology
MEC 320 GENSET CONTROLLER
Protection
1010 Reverse power
No. Setting Min.
setting
1011 Reverse power Set point -50.0% 0.0% - -5.0%
1012 Reverse power Timer 0.1 s 100.0 s - 10.0 s
1013 Reverse power Relay output A R0 (none) - R0 (none)
1014 Reverse power Relay output B R0 (none)
1015 Reverse power Enable OFF ON RUN ON
1016 Reverse power Fail class Alarm (1) Trip MB (6) - Trip GB (3)
1020 Overcurrent 1
No. Setting Min.
setting
1021 Overcurrent 1 Set point 50.0% 200.0% - 115.0%
1022 Overcurrent 1 Timer 0.1 s 100.0 s - 10.0 s
1023 Overcurrent 1 Relay output A R0 (none) - R0 (none)
1024 Overcurrent 1 Relay output B R0 (none)
1025 Overcurrent 1 Enable OFF ON RUN ON
1026 Overcurrent 1 Fail class Alarm (1) Trip MB (6) - Warning (2)
Max.
setting
Option
dependent
Max.
setting
Option
dependent
Third
setting
- R0 (none)
Third
setting
- R0 (none)
Factory
setting
Factory
setting
1030 Overcurrent 2
No. Setting Min.
setting
1031 Overcurrent 2 Set point 50.0% 200.0% - 120.0%
1032 Overcurrent 2 Timer 0.1 s 100.0 s - 5.0 s
1033 Overcurrent 2 Relay output A R0 (none) - R0 (none)
1034 Overcurrent 2 Relay output B R0 (none)
1035 Overcurrent 2 Enable OFF ON RUN ON
1116 Overcurrent 2 Fail class Alarm (1) Trip MB (6) - Trip GB (3)
Max.
setting
Option
dependent
Third
setting
- R0 (none)
Factory
setting
PM079 Rev 0 07/06/08 72 Thomson Technology
MEC 320 GENSET CONTROLLER
Control
This setup menu consists of the synchronization setup and the regulation setup.
Synchronization
2010 Synchronization type
No. Setting First setting Second
setting
2011 Sync. type Sync. type Static sync. Dynamic
sync.
If dynamic synchronization is chosen, the next menu will be
static synchronization is chosen, the next menu will be
2020 Dynamic Synchronization
2030 Static Synchronization
2020 Dynamic Synchronization
No. Setting Min. setting Max. setting Factory
2021 Dynamic sync. df max. 0.0Hz 0.5Hz 0.3Hz
2022 Dynamic sync. df min. -0.5Hz 0.5Hz 0.0Hz
2023 Dynamic sync. dU max. 2% 10% 5%
2024 Dynamic sync. Breaker delay 40 ms 300 ms 50 ms
Factory
setting
Dynamic
sync.
.
setting
. If
2030 Static Synchronization
No. Setting Min. setting Max. setting Factory
setting
2031 Static sync. Maximum df 0.00Hz 0.50Hz 0.10Hz
2032 Static sync. Maximum dU 2% 10% 5%
2033 Static sync. Close window 0.1 deg. 20.0 deg. 10.0 deg.
2034 Static sync. Phase KP 0 1000 10
2035 Static sync. Phase KI 0 1000 10
2040 Sync. blackout
No. Setting Min. setting Max. setting Factory
Settings are accepted limits (generator voltage and frequency) for closing the generator and
mains breaker. The values are according to nominal values.
and U
= 50 Hertz and 400 volts.
NOM
Example:
f
NOM
With factory settings the breaker is able to close, if the frequency is between 47 and 53 Hertz
and the voltage is between 380 and 420 volts.
PM079 Rev 0 07/06/08 73 Thomson Technology
MEC 320 GENSET CONTROLLER
2070 GB general failure
- Synchronization time Adjustable time delay channel 2071
- Breaker ON/OFF feedback fail. 1 second fixed time delay
- Phase sequence error 1 second fixed time delay
No. Setting Min. setting Max. setting Factory
setting
2071 GB general fail. Delay 30.0 s 300.0 s 60.0 s
2072 GB general fail. Relay output A R0 (none) R0 (none)
2073 GB general fail. Relay output B R0 (none)
Option
dependent
R0 (none)
The general failure alarms cannot be disabled.
2080 MB general failure
- Synchronization time Adjustable time delay channel 2081
- Breaker ON/OFF feedback fail. 1 second fixed time delay
- Phase sequence error 1 second fixed time delay
No. Setting Min. setting Max. setting Factory
setting
2081 MB general fail. Delay 30.0 s 300.0 s 60.0 s
2082 MB general fail. Relay output A R0 (none) R0 (none)
2083 MB general fail. Relay output B R0 (none)
Option
dependent
R0 (none)
The general failure alarms cannot be disabled.
2090 Breaker failure alarms
The fail class of the breaker open and close failure alarms can be adjusted in this menu.
No. Setting Min. setting Max. setting Factory
setting
2091 MB open failure Fail class 1 6 2 (warning)
2092 MB close failure Fail class 1 6 2 (warning)
2093 GB open failure Fail class 1 6 2 (warning)
2094 GB close failure Fail class 1 6 2 (warning)
See page 53 regarding fail class selection.
2100 Separate Synchronization relay
No. Setting Min. setting Max. setting Factory
setting
2101 Generator breaker Relay output A R0 (none) R0 (none)
2102 Mains breaker Relay output B R0 (none)
Option
dependent
R0 (none)
2110 Close before excitation
No. Setting Min. setting Max. setting Factory
setting
2111 Close bf. excit. Set point 0 RPM 4000 RPM 400 RPM
2112 Close bf. excit. Timer 0.0 s 999.0 s 5.0 s
2113 Close bf. excit. Relay output A R0 (none) R0 (none)
2114 Close bf. excit. Relay output B R0 (none)
Option
dependent
R0 (none)
2115 Close bf. excit. Enable OFF ON OFF
PM079 Rev 0 07/06/08 74 Thomson Technology
MEC 320 GENSET CONTROLLER
2120 Breaker sequence
No. Setting Min. setting Max. setting Factory
setting
2121 Breaker seq. Break Close GB Close GB+TB Close GB
2122 Breaker seq. Timer 0.0 s 999.0 s 5.0 s
2123 Breaker seq. Run 90 0 RPM 4000 RPM 1450 RPM
2130 Excitation failure
No. Setting Min. setting Max. setting Factory
setting
2131 Excit. failure Timer 0.0 s 999.0 s 5.0 s
2132 Excit. failure Relay output A R0 (none) R0 (none)
2133 Excit. failure Relay output B R0 (none)
2134 Excit. failure Enable OFF ON OFF
2135 Excit. failure Fail class Alarm (1) Trip MB (6) Warning (2)
Option
dependent
R0 (none)
PM079 Rev 0 07/06/08 75 Thomson Technology
MEC 320 GENSET CONTROLLER
Regulation
2510 Frequency controller
No. Setting Min. setting Max. setting Factory
setting
2511 Freq. control Dead band 0.2% 10.0% 1.0%
2512 Freq. control F KP 0 1000 10
2513 Freq. control F KI 0 1000 10
Frequency % settings relate to nominal generator frequency (setting 6011). It is used for frequency
control (fixed frequency or load sharing) when the breaker is closed, and for synchronizing if the
breaker is open.
2520 Power controller
No. Setting Min. setting Max. setting Factory
setting
2521 Power control Dead band 0.2% 10.0% 2.0%
2522 Power control P KP 0 1000 10
2523 Power control P KI 0 1000 10
Power % settings relate to nominal generator power.
2530 Power ramp up
No. Setting Min. setting Max. setting Factory
setting
2531 Power ramp up Speed 1.0%/s 20.0%/s 2.0%/s
2532 Power ramp up Delay point 1% 100% 10%
2533 Power ramp up Delay time 0.0 s 180.0 s 10.0 s
The delay point determines when the generator will make a temporary stop ramping up after
closing of the generator breaker to preheat the engine before commencing load taking. The time
duration of this point is determined by the delay time setting. If the delay function is not needed,
set this time to 0. Power % settings relate to nominal generator power.
2540 Power ramp down
No. Setting Min. setting Max. setting Factory
setting
2541 Power ramp down Speed 0.1%/s 20.0%/s 10.0%/s
2542 Power ramp down Breaker open set point 1% 20% 5%
2543 Power ramp down Fail class 1 6 2 (warning)
The breaker open point determines when the ‘open breaker’ relay output is activated to open the
generator breaker before reaching 0 kW. Power % settings relate to nominal generator power.
2560 Governor regulation failure
No. Setting Min. setting Max. setting Factory
setting
2561 Governor reg. failure Reg. error 1.0% 100.0% 30.0%
2562 Governor reg. failure Timer 10.0 s 360.0 s 60.0 s
2563 Governor reg. failure Output A R0 (none) R0 (none)
2564 Governor reg. failure Output B R0 (none)
The alarm is activated, if the difference between the measured value and the set point is outside
the set point for a longer time period than specified by the timer set point.
Option
dependent
R0 (none)
PM079 Rev 0 07/06/08 76 Thomson Technology
MEC 320 GENSET CONTROLLER
2640 Relay control
No. Setting Min. setting Max. setting Factory
setting
2641 Relay control GOV ON time 10 ms 3000 ms 500 ms
2642 Relay control GOV per. time 50 ms 15000 ms 2500 ms
2690 Delay regulation
No. Setting Min. setting Max. setting Factory
setting
2691 Delay regulation Timer 0 s 9900 s 0 s
2692 Delay regulation Output A R0 (none) R0 (none)
2693 Delay regulation Output B R0 (none)
2694 Delay regulation Enable OFF ON OFF
2700 Short time paralleling
No. Setting Min. setting Max. setting Factory
2701 Short paralleling Enable OFF ON OFF
2702 Short paralleling Timer 0.10 s 99.90 s 0.30 s
Option
dependent
R0 (none)
setting
PM079 Rev 0 07/06/08 77 Thomson Technology
MEC 320 GENSET CONTROLLER
Input/output
This menu consists of parameters for configuration of the inputs and outputs.
Binary input setup
3260 Dig. input no. 110
No. Setting Min.
setting
3261 Dig. input no. 110 Timer 0.0 s 100.0 s - 10.0 s
3262 Dig. input no. 110 Relay output A R0 (none) - R0 (none)
3263 Dig. input no. 110 Relay output B R0 (none)
3264 Dig. input no. 110 Enable OFF ON RUN OFF
3265 Dig. input no. 110 Fail class Alarm (1) Trip MB (6) - Warning (2)
3266 Dig. input no. 110 Type N/O N/C - N/O
3270 Dig. input no. 111
No. Setting Min.
setting
3271 Dig. input no. 111 Timer 0.0 s 100.0 s - 10.0 s
3272 Dig. input no. 111 Relay output A R0 (none) - R0 (none)
3273 Dig. input no. 111 Relay output B R0 (none)
3274 Dig. input no. 111 Enable OFF ON RUN OFF
3275 Dig. input no. 111 Fail class Alarm (1) Trip MB (6) - Warning (2)
3276 Dig. input no. 111 Type N/O N/C - N/O
Max.
setting
Option
dependent
Max.
setting
Option
dependent
Third
setting
- R0 (none)
Third
setting
- R0 (none)
Factory
setting
Factory
setting
3280 Dig. input no. 112
No. Setting Min.
setting
3281 Dig. input no. 112 Timer 0.0 s 100.0 s - 10.0 s
3282 Dig. input no. 112 Relay output A R0 (none) - R0 (none)
3283 Dig. input no. 112 Relay output B R0 (none)
3284 Dig. input no. 112 Enable OFF ON RUN OFF
3285 Dig. input no. 112 Fail class Alarm (1) Trip MB (6) - Warning (2)
3286 Dig. input no. 112 Type N/O N/C - N/O
3290 Dig. input no. 113
No. Setting Min.
setting
3291 Dig. input no. 113 Timer 0.0 s 100.0 s - 10.0 s
3292 Dig. input no. 113 Relay output A R0 (none) - R0 (none)
3293 Dig. input no. 113 Relay output B R0 (none)
3294 Dig. input no. 113 Enable OFF ON RUN OFF
3295 Dig. input no. 113 Fail class Alarm (1) Trip MB (6) - Warning (2)
3296 Dig. input no. 113 Type N/O N/C - N/O
3300 Access lock (binary input 114)
No. Setting Min.
setting
3301 Access lock Timer 0.0 s 180.0 s - 10.0 s
3302 Access lock Relay output A R0 (none) - R0 (none)
3303 Access lock Relay output B R0 (none)
3304 Access lock Enable OFF ON RUN OFF
3305 Access lock Fail class Alarm (1) Trip MB (6) - Warning (2)
3306 Access lock Type N/O N/C - N/O
Max.
setting
Option
dependent
Max.
setting
Option
dependent
Max.
setting
Option
dependent
Third
setting
- R0 (none)
Third
setting
- R0 (none)
Third
setting
- R0 (none)
Factory
setting
Factory
setting
Factory
setting
PM079 Rev 0 07/06/08 78 Thomson Technology
MEC 320 GENSET CONTROLLER
3310 Running feedback (binary input 115)
No. Setting Min.
setting
3311 Run. feedback Timer 0.0 s 180.0 s - 10.0 s
3312 Run. feedback Relay output A R0 (none) - R0 (none)
3313 Run. feedback Relay output B R0 (none)
3314 Run. feedback Enable OFF ON RUN OFF
3315 Run. feedback Fail class Alarm (1) Trip MB (6) - Warning (2)
3316 Run. feedback Type N/O N/C - N/O
3320 Ext. engine failure (binary input 116)
No. Setting Min.
setting
3321 Engine failure Timer 0.0 s 180.0 s - 10.0 s
3322 Engine failure Relay output A R0 (none) - R0 (none)
3323 Engine failure Relay output B R0 (none)
3324 Engine failure Enable OFF ON RUN OFF
3325 Engine failure Fail class Alarm (1) Trip MB (6) - Shutdown (5)
3326 Engine failure Type N/O N/C - N/O
3330 Ext. emergency stop (binary input 117)
No. Setting Min.
setting
3331 Emergency STOP Timer 0.0 s 60.0 s - 0.0 s
3332 Emergency STOP Relay output A R0 (none)
3333 Emergency STOP Relay output B R0 (none)
3334 Emergency STOP Enable OFF ON RUN OFF
3335 Emergency STOP Fail class Alarm (1) Trip MB (6) - Shutdown (5)
3336 Emergency STOP Type N/O N/C - N/O
Max.
setting
Option
dependent
Max.
setting
Option
dependent
Max.
setting
Option
dependent
Third
setting
- R0 (none)
Third
setting
- R0 (none)
Third
setting
- R0 (none)
- R0 (none)
Factory
setting
Factory
setting
Factory
setting
3340 Dig. input no. 118
No. Setting Min.
setting
3341 Dig. input no. 118 Timer 0.0 s 100.0 s - 10.0 s
3342 Dig. input no. 118 Relay output A R0 (none)
3343 Dig. input no. 118 Relay output B R0 (none)
3344 Dig. input no. 118 Enable OFF ON RUN OFF
3345 Dig. input no. 118 Fail class Alarm (1) Trip MB (6) - Warning (2)
3346 Dig. input no. 118 Type N/O N/C - N/O
Max.
setting
Option
dependent
Third
setting
- R0 (none)
- R0 (none)
Factory
setting
PM079 Rev 0 07/06/08 79 Thomson Technology
MEC 320 GENSET CONTROLLER
The input is not configurable in the peak shaving mode, load takeover mode and
urable in the peak shaving mode, load takeover mode and
Analogue input setup
4090 4…20mA input 98.1
No. Setting Min.
4091 4…20mA input 98.1 Set point 4mA 20mA - 10mA
4092 4…20mA input 98.1 Timer 0.0 s 600.0 s - 120.0 s
4093 4…20mA input 98.1 Relay output A R0 (none)
4094 4…20mA input 98.1 Relay output B R0 (none)
4095 4…20mA input 98.1 Enable OFF ON RUN OFF
4096 4…20mA input 98.1 Fail class Alarm (1) Trip MB (6) - Warning (2)
4100 4…20mA input 98.2
No. Setting Min.
4101 4…20mA input 98.2 Set point 4mA 20mA - 10mA
4102 4…20mA input 98.2 Timer 0.0 s 600.0 s - 120.0 s
4103 4…20mA input 98.2 Relay output A R0 (none)
4104 4…20mA input 98.2 Relay output B R0 (none)
4105 4…20mA input 98.2 Enable OFF ON RUN OFF
4106 4…20mA input 98.2 Fail class Alarm (1) Trip MB (6) - Warning (2)
mains power export, because it is used as a mains power input.
Max.
setting
The input is not config
mains power export, because it is used as a mains power input.
setting
setting
Option
dependent
Max.
setting
Option
dependent
Third
setting
- R0 (none)
- R0 (none)
Third
setting
- R0 (none)
- R0 (none)
Factory
setting
Factory
setting
4110 Oil pressure 1
No. Setting Min.
4111 Oil pressure 1 Set point 0 bar 50 bar - 10 bar
4112 Oil pressure 1 Timer 0.0 s 180.0 s - 5.0 s
4113 Oil pressure 1 Relay output A R0 (none) - R0 (none)
4114 Oil pressure 1 Relay output B R0 (none)
4115 Oil pressure 1 Enable OFF ON RUN OFF
4116 Oil pressure 1 Fail class Alarm (1) Trip MB (6) - Warning (2)
4120 Oil pressure 2
No. Setting Min.
4121 Oil pressure 2 Set point 0 bar 50 bar - 10 bar
4122 Oil pressure 2 Timer 0.0 s 180.0 s - 5.0 s
4123 Oil pressure 2 Relay output A R0 (none) - R0 (none)
4124 Oil pressure 2 Relay output B R0 (none)
4125 Oil pressure 2 Enable OFF ON RUN OFF
4126 Oil pressure 2 Fail class Alarm (1) Trip MB (6) - Warning (2)
(4…20mA input 100.1)
(4…20mA input 100.2)
setting
setting
Max.
setting
Option
dependent
Max.
setting
Option
dependent
Third
setting
- R0 (none)
Third
setting
- R0 (none)
Factory
setting
Factory
setting
PM079 Rev 0 07/06/08 80 Thomson Technology
MEC 320 GENSET CONTROLLER
4130 Fuel level 1
No. Setting Min.
(4…20mA input 102.1)
setting
Max.
setting
Third
setting
Factory
setting
4131 4…20mA input 102.1 Set point 0% 120% - 10%
4132 4…20mA input 102.1 Timer 0.0 s 600.0 s - 120.0 s
4133 4…20mA input 102.1 Relay output A R0 (none) - R0 (none)
4134 4…20mA input 102.1 Relay output B R0 (none)
Option
dependent
- R0 (none)
4135 4…20mA input 102.1 Enable OFF ON RUN OFF
4136 4…20mA input 102.1 Fail class Alarm (1) Trip MB (6) - Warning (2)
4140 Fuel level 2
No. Setting Min.
(4…20mA input 102.2)
setting
Max.
setting
Third
setting
Factory
setting
4141 4…20mA input 102.2 Set point 0% 120% - 10%
4142 4…20mA input 102.2 Timer 0.0 s 600.0 s - 120.0 s
4143 4…20mA input 102.2 Relay output A R0 (none) - R0 (none)
4144 4…20mA input 102.2 Relay output B R0 (none)
Option
dependent
- R0 (none)
4145 4…20mA input 102.2 Enable OFF ON RUN OFF
4146 4…20mA input 102.2 Fail class Alarm (1) Trip MB (6) - Warning (2)
4170 VDO 104.1
No. Setting Min.
setting
Max.
setting
Third
setting
Factory
setting
4171 VDO 104.1 Set point 0.0 bar 10.0 bar - 4.0 bar
4172 VDO 104.1 Timer 0.0 s 100.0 s - 5.0 s
4173 VDO 104.1 Relay output A R0 (none) - R0 (none)
4174 VDO 104.1 Relay output B R0 (none)
Option
dependent
- R0 (none)
4175 VDO 104.1 Enable OFF ON RUN OFF
4176 VDO 104.1 Fail class Alarm (1) Trip MB (6) - Warning (2)
4180 VDO 104.2
No. Setting Min.
setting
Max.
setting
Third
setting
Factory
setting
4181 VDO 104.2 Set point 0.0 bar 10.0 bar - 5.0 bar
4182 VDO 104.2 Timer 0.0 s 100.0 s - 5.0 s
4183 VDO 104.2 Relay output A R0 (none) - R0 (none)
4184 VDO 104.2 Relay output B R0 (none)
Option
dependent
- R0 (none)
4185 VDO 104.2 Enable OFF ON RUN OFF
4186 VDO 104.2 Fail class Alarm (1) Trip MB (6) - Trip/stop (4)
4190 VDO 105.1
No. Setting Min.
setting
Max.
setting
Third
setting
Factory
setting
4191 VDO 105.1 Set point 40 deg. 150 deg. - 100 deg.
4192 VDO 105.1 Timer 0.0 s 100.0 s - 5.0 s
4193 VDO 105.1 Relay output A R0 (none) - R0 (none)
4194 VDO 105.1 Relay output B R0 (none)
Option
dependent
- R0 (none)
4195 VDO 105.1 Enable OFF ON RUN OFF
4196 VDO 105.1 Fail class Alarm (1) Trip MB (6) - Warning (2)
PM079 Rev 0 07/06/08 81 Thomson Technology
MEC 320 GENSET CONTROLLER
4200 VDO 105.2
No. Setting Min.
setting
Max.
setting
Third
setting
Factory
setting
4201 VDO 105.2 Set point 40 deg. 150 deg. - 110 deg.
4202 VDO 105.2 Timer 0.0 s 100.0 s - 5.0 s
4203 VDO 105.2 Relay output A R0 (none) - R0 (none)
4204 VDO 105.2 Relay output B R0 (none)
Option
dependent
- R0 (none)
4205 VDO 105.2 Enable OFF ON RUN OFF
4206 VDO 105.2 Fail class Alarm (1) Trip MB (6) - Trip/stop (4)
4210 VDO 106.1
No. Setting Min.
setting
Max.
setting
Third
setting
Factory
setting
4211 VDO 106.1 Set point 0% 100% - 10%
4212 VDO 106.1 Timer 0.0 s 100.0 s - 10.0 s
4213 VDO 106.1 Relay output A R0 (none) - R0 (none)
4214 VDO 106.1 Relay output B R0 (none)
Option
dependent
- R0 (none)
4215 VDO 106.1 Enable OFF ON RUN OFF
4216 VDO 106.1 Fail class Alarm (1) Trip MB (6) - Warning (2)
4220 VDO 106.2
No. Setting Min.
setting
Max.
setting
Third
setting
Factory
setting
4221 VDO 106.2 Set point 0% 100% - 5%
4222 VDO 106.2 Timer 0.0 s 100.0 s - 10.0 s
4223 VDO 106.2 Relay output A R0 (none) - R0 (none)
4224 VDO 106.2 Relay output B R0 (none)
Option
dependent
- R0 (none)
4225 VDO 106.2 Enable OFF ON RUN OFF
4226 VDO 106.2 Fail class Alarm (1) Trip MB (6) - Trip/stop (4)
4300 Running detection
This set point is used to define the level where the gen-set is recognised as running. When this
RPM level is reached, the automatic running detection is enabled
(6150 Running status)
.
Also take notice of the menu ‘remove starter’ set point
(6160 Remove starter)
.
No. Setting Min. setting Max. setting Factory
setting
4301 Running detection Set point 1 RPM 4000 RPM 1000 RPM
4302 Running detection Type Frequency detection X
Running detection Type Tacho Running detection Type Binary input Running detection Type Engine I/F communication
4310 Overspeed 1
No. Setting Min. setting Max. setting Factory
setting
4311 Overspeed 1 Set point 1 RPM 4000 RPM 1450 RPM
4312 Overspeed 1 Timer 0.0 s 100.0 s 5.0 s
4313 Overspeed 1 Relay output A R0 (none) R0 (none)
4314 Overspeed 1 Relay output B R0 (none)
Option
dependent
R0 (none)
4315 Overspeed 1 Enable OFF ON OFF
4316 Overspeed 1 Fail class Alarm (1) Trip MB (6) Warning (2)
PM079 Rev 0 07/06/08 82 Thomson Technology
MEC 320 GENSET CONTROLLER
4320 Overspeed 2
No. Setting Min. setting Max. setting Factory
setting
4321 Overspeed 2 Set point 1 RPM 4000 RPM 1750 RPM
4322 Overspeed 2 Timer 0.0 s 100.0 s 1.0 s
4323 Overspeed 2 Relay output A R0 (none) R0 (none)
4324 Overspeed 2 Relay output B R0 (none)
Option
dependent
R0 (none)
4325 Overspeed 2 Enable OFF ON OFF
4326 Overspeed 2 Fail class Alarm (1) Trip MB (6) Shutdown (5)
4431 W. fail. VDO 106 Max. 60% 100% 100%
4432 W. fail. VDO 106 Min. 0% 40% 0%
4433 W. fail. VDO 106 Output A R0 (none) R0 (none)
4434 W. fail. VDO 106 Output B R0 (none)
4435 W. fail. VDO 106 Enable OFF ON OFF
4436 W. fail. VDO 106 Fail class Alarm (1) Trip MB (6) Warning (2)
Option
dependent
R0 (none)
PM079 Rev 0 07/06/08 84 Thomson Technology
MEC 320 GENSET CONTROLLER
If the transistor outputs are set to ‘Continues’, external relays are needed due to
Output setup
5090 Relay 9
The relay 9 is available, if options D1 are not selected and analogue governor outputs are not
used.
No. Setting First/min.
setting
5091 Relay 9 Function Alarm Limit Horn Alarm
5092 Relay 9 Off delay 0.0 s 999.9 s - 5.0 s
5100 Relay 10
The relay 10 is available, if options D1 are not selected and analogue governor outputs are not
used.
No. Setting First/min.
setting
5101 Relay 10 Function Alarm Limit Horn Alarm
5102 Relay 10 Off delay 0.0 s 999.9 s - 5.0 s
5110 Relay 11
No. Setting First/min.
setting
5111 Relay 11 Function Alarm Limit Horn Alarm
5112 Relay 11 Off delay 0.0 s 999.9 s - 5.0 s
Second/max.
setting
Second/max.
setting
Second/max.
setting
Third
setting
Third
setting
Third
setting
Factory
setting
Factory
setting
Factory
setting
5120 Relay 12
The relay 12 is available, if ‘Continues’ is selected in menu 5491.
No. Setting First/min.
setting
5121 Relay 12 Function Alarm Limit Horn Alarm
5122 Relay 12 Off delay 0.0 s 999.9 s - 5.0 s
5130 Relay 13
The relay 13 is available, if ‘Continues’ is selected in menu 5492.
No. Setting First/min.
setting
5131 Relay 13 Function Alarm Limit Horn Alarm
5132 Relay 13 Off delay 0.0 s 999.9 s - 5.0 s
5490 Transistor setup
The transistor outputs on terminals 20 and 21 can be configured as constant or pulse signals. If
‘Continues’ is selected, the relays 12 and 13 will be available.
6021 Nominal settings 2 Frequency 48.0Hz 62.0Hz 60.0Hz
6022 Nominal settings 2 Generator power 10kW 20000kW 285kW
6023 Nominal settings 2 Generator current 0A 9000A 345A
6024 Nominal settings 2 Generator volt. 100V 25000V 480V
6025 Nominal settings 2 Set OFF 2 OFF
6030 Transformer gen.
No. Setting Min. setting Max. setting Factory
setting
6031 Transformer gen. Volt. prim. 100V 25000V 400V
6032 Transformer gen. Volt. sec. 100V 690V 400V
6033 Transformer gen. Current prim. 5A 9000A 1000A
6034 Transformer gen. Current sec. 1A 5A 5A
6040 Transformer bus.
No. Setting Min. setting Max. setting Factory
6041 Transformer bus. Volt. prim. 100V 25000V 400V
6042 Transformer bus. Volt. sec. 100V 690V 400V
6050 Engine type
No. Setting First setting Second
6051 Engine type Engine type Diesel
set to generator nominal value.
If no voltage transform
set to generator nominal value.
It is only possible to select diesel engine.
engine
setting
Factory
setting
None Diesel
setting
engine
PM079 Rev 0 07/06/08 86 Thomson Technology
MEC 320 GENSET CONTROLLER
The date and time can easily be synchronized with the present time and date
6060 Gen-set modes
No. Setting Setting Factory
setting
6061 Gen-set mode Island operation Island operation Gen-set mode AMF AMF AMF
Gen-set mode Peak shaving Peak shaving Gen-set mode Fixed power Fixed power Gen-set mode Mains power export Mains power export Gen-set mode Load take over Load take over -
6070 Date and time (internal clock) setting
No. Setting Min. setting Max. setting Factory
6071 Date and time Year 2001 2100
6072 Date and time Month 1 12
6073 Date and time Day 1 31
6074 Date and time Weekday 1 7
6075 Date and time Hour 0 23
6076 Date and time Minute 0 59
from the utility software.
setting
Depending on
the software
version
6080 Counters
The settings below (except kWh) are offset values that need to be adjusted at the
commissioning if the display is used for reading the values. A breaker operation is counted each
time the breaker closes.
The setting ‘reset kWh counter’ resets the value of the produced kWh.
No. Setting Min. setting Max. setting Factory
setting
6081 Counters Running time 0 20000 0
6082 Counters GB operations 0 20000 0
6083 Counters MB operations 0 20000 0
6084 Counters kWh OFF ON OFF
6085 Counters Start attempts 0 20000 0
6090 Service timer
The function of the service timer enables the user to get an alarm when service of the gen-set is
needed. The timer is reset when the alarm is acknowledged or when the timer is disabled and
enabled again.
No. Setting Min. setting Max. setting Factory
setting
6091 Service timer Set point 0 h 9000 h 500 h
6092 Service timer Relay output A R0 (none) R0 (none)
6093 Service timer Relay output B R0 (none)
6094 Service timer Enable OFF ON ON
6095 Service timer Fail class Alarm (1) Trip MB (6) Warning (2)
Option
dependent
R0 (none)
PM079 Rev 0 07/06/08 87 Thomson Technology
MEC 320 GENSET CONTROLLER
6110 Battery low voltage alarm
No. Setting Min. setting Max. setting Factory
setting
6111 Battery low V Set point 8/15.0V 32.0V 18.0V
6112 Battery low V Timer 0.0 s 999.0 s 1.0 s
6113 Battery low V Relay output A R0 (none) R0 (none)
6114 Battery low V Relay output B R0 (none)
Option
dependent
R0 (none)
6115 Battery low V Enable OFF ON ON
The alarm is for the auxiliary power supply measured on terminal 1 and 2.
6120 Battery high voltage alarm
No. Setting Min. setting Max. setting Factory
setting
6121 Battery high V Set point 12.0V 36.0V 30.0V
6122 Battery high V Timer 0.0 s 999.0 s 1.0 s
6123 Battery high V Relay output A R0 (none) R0 (none)
6124 Battery high V Relay output B R0 (none)
Option
dependent
R0 (none)
6125 Battery high V Enable OFF ON ON
The alarm is for the auxiliary power supply measured on terminals 1 and 2.
6130 Language
No. Setting Setting Factory setting
6130 Language Selection display - 6131 Language English English English
Language 1-11 -
6140 Alarm horn
No. Setting Min. setting Max. setting Factory
setting
6141 Alarm horn Timer 0.0 s 990.0 s 20.0 s
The setting is the maximum time the horn relay activates at an alarm. If the setting is adjusted to
0 s, the horn relay will be activated continuously until the alarm is acknowledged.
6150 Running status
No. Setting Min. setting Max. setting Factory
setting
6151 Run status Timer 0.0 s 300.0 s 5.0 s
6152 Run status Relay output A R0 (none) R0 (none)
6153 Run status Relay output B R0 (none)
Option
dependent
R0 (none)
6154 Run status Enable OFF ON OFF
6160 Remove starter
No. Setting Min. setting Max. setting Factory
setting
6161 Remove starter Set point 1 RPM 2000 RPM 400 RPM
6162 Remove starter Number of teeth 0 teeth 500 teeth 0 teeth
6170 Starter
No. Setting Min. setting Max. setting Factory
setting
6171 Starter Start prepare 0.0 s 600.0 s 5.0 s
6172 Starter Start ON time 1.0 s 30.0 s 5.0 s
6173 Starter Start OFF time 1.0 s 99.0 s 5.0 s
PM079 Rev 0 07/06/08 88 Thomson Technology
MEC 320 GENSET CONTROLLER
of start attempts adjusted in menu 6184 Fire start attempt, is used
R0 (none)
6184 Start attempts Fire start attempt 1 10 7
6185 Start attempts FP cool down 0.0 s 990.0 s 30.0 s
The number
when the digital input ‘fire pump’ is used instead of the setting 6181.
6190 f/U OK
No. Setting Min. setting Max. setting Factory
setting
6191 f/U OK Timer 1.0 s 99.0 s 5.0 s
6200 f/U failure
No. Setting Min. setting Max. setting Factory
setting
6201 f/U failure Timer 1.0 s 99.0 s 30.0 s
6202 f/U failure Relay output A R0 (none) R0 (none)
6203 f/U failure Relay output B R0 (none)
Option
dependent
R0 (none)
6210 Stop
No. Setting Min. setting Max. setting Factory
setting
6211 Stop Cool down time 0.0 s 990.0 s 240.0 s
6212 Stop Extended STOP 1.0 s 99.0 s 5.0 s
6213 Stop Coil type STOP RUN RUN
6220 Stop failure
No. Setting Min. setting Max. setting Factory
setting
6221 Stop failure Timer 10.0 s 120.0 s 30.0 s
6222 Stop failure Relay output A R0 (none) R0 (none)
6223 Stop failure Relay output B R0 (none)
Option
dependent
R0 (none)
6250 GB control
No. Setting Min. setting Max. setting Factory
setting
6251 GB control Timer t
6260 P
derate
nom
0.0 s 30.0 s 2.0 s
GBC
No. Setting Min. setting Max. setting Factory
setting
6261 P
6262 P
6263 P
6264 P
6265 P
6266 P
derate Input 4…20mA VDO/PT100 4…20mA
nom
derate Start derate 0 20000 16 units
nom
derate Derate slope 0.1%/U 100.0%/U 5.0%/U
nom
derate Proportional OFF ON OFF
nom
derate Enable OFF ON OFF
nom
derate Derate limit 0.0% 100.0% 80.0%
nom
PM079 Rev 0 07/06/08 89 Thomson Technology
MEC 320 GENSET CONTROLLER
6310 Idle running
No. Setting Min. setting Max. setting Factory
setting
6311 Idle running Start timer 0.0 min 999.9 min 300.0 min
6312 Idle running Enable start timer OFF ON OFF
6313 Idle running Stop timer 0.0 min 999.9 min 300.0 min
6314 Idle running Enable stop timer OFF ON OFF
6315 Idle running Idle relay Option dependent R0 (none)
6316 Idle running Enable OFF ON OFF
6400 Master clock
No. Setting Min. setting Max. setting Factory
setting
6401 Master clock Start hour 0 23 8
6402 Master clock Stop hour 0 23 8
6403 Master clock Difference 0.1Hz 1.0Hz 0.1Hz
6404 Master clock Set point 1 s 999 s 20 s
6405 Master clock Enable OFF ON OFF
6410 Battery test
No. Setting Min. setting Max. setting Factory
setting
6411 Battery test Set point 8.0V DC 32.0V DC 18.0V DC
6412 Battery test Delay 1 s 300 s 20 s
6413 Battery test Output A R0 (none)
6414 Battery test Output B
Option dependent
R0 (none)
6415 Battery test Enable OFF ON OFF
6420 Voltage trip
No. Setting Min. setting Max. setting Factory
setting
6421 Voltage trip Type Phase-phase Phase-neutral Phase-phase
PM079 Rev 0 07/06/08 90 Thomson Technology
MEC 320 GENSET CONTROLLER
Transducer max. equals 20mA, and Transducer min. equals 4mA. Both settings
Mains setup
6500 Mains power
No. Setting Min. setting Max. setting Factory
setting
6501 Mains power Day -20000 kW 20000 kW 750 kW
6502 Mains power Night -20000 kW 20000 kW 1000 kW
6503 Mains power Transducer max 0 kW 20000 kW 1500 kW
6504 Mains power Transducer min -20000 kW 0 kW -1500 kW
6510 Daytime period
The period outside the daytime period is defined as the nighttime period.
No. Setting Min. setting Max. setting Factory
6511 Daytime period Start hour 0 h 23 h 8 h
6512 Daytime period Start minute 0 min 59 min 0 min
6513 Daytime period Stop hour 0 h 23 h 16 h
6514 Daytime period Stop minute 0 min 59 min 0 min
must be adjusted.
setting
6520 Start gen-set
The set point refers to the mains power set points in
No. Setting Min. setting Max. setting Factory
6521 Start generator Set point 5% 100% 80%
6522 Start generator Timer 0.0 s 990.0 s 10.0 s
6523 Start generator Minimum load 0% 100% 5%
6530 Stop gen-set
The set point refers to the mains power set points in
No. Setting Min. setting Max. setting Factory
6531 Stop generator Set point 0% 80% 60%
6532 Stop generator Timer 0.0 s 990.0 s 30.0 s
6540 Test running
No. Setting Min. setting Max. setting Factory
6541 Test Set point 1% 100% 80%
6542 Test Timer 0.5 min 999.0 min 5.0 min
6543 Test Return Semi-auto Auto Auto
6550 Fixed power set point
No. Setting Min. setting Max. setting Factory
6551 Fixed power set point P set point 0% 100% 100%
6500 Mains power
6500 Mains power
.
setting
.
setting
setting
setting
PM079 Rev 0 07/06/08 91 Thomson Technology
MEC 320 GENSET CONTROLLER
6590 Mains failure voltage
No. Setting Min. setting Max. setting Factory
setting
6591 Mains failure U Fail. delay 1.0 s 990.0 s 5.0 s
6592 Mains failure U Mains OK delay 10 s 9900 s 60 s
6593 Mains failure U Low voltage 80% 100% 90%
6594 Mains failure U High voltage 100% 120% 110%
6595 Mains failure U Mains fail. control Start eng. +
open MB
Start eng. Start eng. +
open MB
6600 Mains failure frequency
No. Setting Min. setting Max. setting Factory
setting
6601 Mains failure f Fail. delay 1.0 s 990.0 s 5.0 s
6602 Mains failure f Mains OK delay 10 s 9900 s 60 s
6603 Mains failure f Low frequency 80.0% 100.0% 95.0%
6604 Mains failure f High frequency 100.0% 120.0% 105.0%
6610 Mains breaker control
No. Setting Min. setting Max. setting Factory
setting
6611 MB control Function Mode shift
OFF
6612 MB control Timer t
6613 MB control Back synchroni-
0.0 s 30.0 s 0.5 s
MBC
OFF ON OFF
Mode-AMFMode
Mode shift
OFF
sation
6614 MB control Sync. to mains OFF ON ON
PM079 Rev 0 07/06/08 92 Thomson Technology
MEC 320 GENSET CONTROLLER
It is recommended to change the password levels of the user, service and
Jump menus
A number of menus can only be entered using the jump menu.
9000 Software version
Information about the actual software downloaded to the unit. Please check this before
contacting THOMSON TECHNOLOGY regarding service and support matters.
9020 Service port
The RS232 service port can be set up to use the ASCII communication. The ASCII
communication is used when the utility software is connected through a modem.
911X User password
The user password menu can only be entered using the “JUMP” push-button.
Selection ‘0’ must be used for cable connection between the MEC 320 and the PC.
Selection ‘1’ must be used for modem connection between the MEC 320 and the PC.
setting
master password, if access to parameter settings must be restricted.
9120 Service menu
The service menu can only be entered using the ‘JUMP’ push-button. This menu is used in
service situations.
In the alarm selection you can see all the alarm timers and their remaining time if they are
counting.
The input and output selections show the present status of the inputs and outputs. E.g. mode
inputs, relay outputs and load sharing lines.
No. Setting Description
9121 Service menu Alarm Shows remaining alarm delay time
9122 Service menu Digital input Shows digital input status
9123 Service menu Digital output Shows digital output status
9124 Service menu Miscellaneous Shows miscellaneous information
9130 Single phase/split phase/three phase
No. Setting Description
9131 Mode Mode 0 = Three phase system
1 = Split phase system
2 = Single phase system
THOMSON TECHNOLOGY reserves the right to change any of the above
PM079 Rev 0 07/06/08 93 Thomson Technology
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.