Thermon FLX Self-Regulating Installation Procedures Manual

TM
FLX
Self-Regulating
Winterization/Freeze Protection
INSTALLATION PROCEDURES
FLX
FLX
TM
TM
Refer to the “FLX Cable Testing Report” for required recording of test data and circuit information.
Upon Receiving Cable . . .
1. Upon receiving heating cable, check to make sure the proper type and output have been received. All cables are printed on the outer jacket with part number, voltage rating and watt output.
2. Visually inspect cable for any damage incurred during ship­ment. The heating cable should be tested to ensure electri­cal integrity with at least a 500 Vdc megohmmeter (meg­ger) between the heating cable bus wires and the heating cable metallic braid. IEEE 515.1 recommends that the test voltage for polymer insulated heating cables be 2500 Vdc. Minimum resistance should be 20 megohms. (Record 1 on Cable Testing Report.)
Typical Heat Tracing Installation . . .
A complete electric heat tracing system will typically in­clude the following components:
1. Electric heat tracing cable.
2. Power connection kit.
3. Control thermostat (may be remote ambient sensing control.)
4. In-line/T-splice kit (permits two or three cables to be spliced together).
5. Cable end termination.
6. Attachment tape (use on 12” intervals or as required by code or specication).
7. “Electric Heat Tracing” label (peel-and-stick label attaches to insulation vapor barrier on 10’ intervals or as required by code or specication).
4
7
6
8
5
1
Connect the positive lead of the megger to the cable bus wires and the negative lead to the metallic braid.
CAUTION: DO NOT connect power to heating cable while it is on reel or in shipping carton.
Before Installing Cable . . .
1. Be sure all piping and equipment to be traced is completely installed and pressure tested.
2. Surface areas where heat tracing is to be installed must be reasonably clean. Remove dirt, rust and scale with a wire brush and oil and grease lms with a suitable solvent.
8. Thermal insulation and vapor barrier (by others).
The absence of any of these items can cause a system to malfunction or represent a safety hazard.
The National Electric Code and Canadian Electrical Code require ground-fault protection be provided for all electric heat tracing.
3
2
2
Initial Installation . . .
INSTALLATION PROCEDURES
1. Begin temporary installation at the proposed end-of-circuit location and lay out heating circuit on the pipe, allowing ex­tra cable for the power connection and for any splice loca­tions. Refer to illustration below for temporary installation.
Temporary Installation
Proposed Power
Connection Location
Cable Allowance for
In-Line Heat Sinks
Installation on Fittings and Equipment . . .
2. Make heating cable allowances for valves, anges, elbows and supports as per the applicable drawings and table on pages 2 and 3 of these installation procedures. See product specications sheet for heating cable minimum bend radius.
Proposed End-of-Circuit
Location
Pipe Support
1. Install heating cable in accordance with illustrations below. Secure heating cable to piping using attachment tape.
2. Elbows: Locate the cable on the outside radius of an elbow to provide sucient heat to compensate for the added pip-
3. Pipe Supports: Insulated pipe supports require no additional heating cable. For uninsulated supports, allow two times the length of the pipe support plus an additional 15” (40 cm) of heating cable.
ing material. Secure the cable to the pipe on each side of the elbow with attachment tape.
Pipe Elbow Pipe Support
Heating Cable
Attachment Tape
(Typical)
Heating Cable
3” Min.
(8 cm)
Attachment Tape
(Typical)
3” Min.
(8 cm)
Support
Length
3
FLX
TM
4. Flanges: Allow cable to be looped around pipe on each side of and adjacent to the ange. Heating cable must maintain contact with ange when bending around pipe anges to compensate for additional heat loss.
Typical Flange Detail
Heating Cable
12” Max.
Note: Flange allowance will vary based on method of insulating ange and adjacent piping.
(30 cm)
Attachment Tape
(Typical)
5. Additional cable is required to provide extra heat at valves, pumps and miscellaneous equipment to oset the in­creased heat loss associated with these items. Refer to Table 1 for estimated cable requirements for installation on typical valves and pumps.
6. Install heating cable on valves and pumps utilizing a looping technique (this allows the valve or pump to be removed if required).
Typical Valve Details
Heating Cable
Temporary Loop of Cable on Valve
Attachment Tape
(Typical)
Table 1: Valve and Pump Allowances
Pipe Size
½" 6" 1' 0 1' 2'
¾" 9" 1'-6" 0 1'-6" 3'
1" 1' 2' 1' 2' 4'
1¼" 1'-6" 2' 1' 3' 4'-6"
1½" 1'-6" 2'-6" 1'-6" 3' 5'
2" 2' 2'-6" 2' 4' 5'-6"
3" 2'-6" 3'-6" 2'-6" 5' 7'
4" 4' 5' 3' 8' 10'
6" 7' 8' 3'-6" 14' 16'
8" 9'-6" 11' 4' 19' 22'
10" 12'-6" 14' 4' 25' 28'
12" 15' 16'-6" 5' 30' 33'
14" 18' 19'-6" 5'-6" 36' 39'
16" 21'-6" 23' 6' 43' 46'
18" 25'-6" 27' 6'-6" 51' 54'
20" 28'-6" 30' 7' 57' 60'
24" 34' 36' 8' 68' 72'
30" 40' 42' 10' 80' 84'
Screwed Flanged Welded
Valve Type
Pump Type
Screwed Flanged
Heating Cable Attachment Tape
Heating Cable Serpentined on Valve
(Typical)
Typical Pump Detail
Heating Cable
Heating Cable Serpentined on Pump
Attachment Tape
(Typical)
4
INSTALLATION PROCEDURES
Completing the Installation . . .
1. Begin nal cable attachment by securing the end-of-circuit termination kit and working back toward the power supply.
• Flexible heating cables are to be installed using attachment
tape. Circumferential bands of tape should be installed at 12” (30 cm) intervals to keep the cable in proper contact with the pipe. Refer to Table 2 below to calculate the num­ber of rolls of attachment tape required based on the pipe diameter 1.
• If applicable, refer to installation details provided with the
project drawings or contact Thermon for additional infor­mation regarding installation.
2. In addition to the circumferential tape requirements, a continuous covering of aluminum foil tape may be required when:
• Spray or foam urethane2 thermal insulation is applied.
• Heat tracing nonmetallic piping.
• Design requirements dictate the use of aluminum tape to
improve heat transfer.
3. Complete splice connections (if required) in accordance with the installation instructions provided with the splice kit.
4. Install power connection kit in accordance to the detailed installation instructions provided with the kit.
5. Before making power connections, repeat the megger test with at least a 500 Vdc megohmmeter (megger) between the heating cable bus wires and the heating cable metallic braid. IEEE 515.1 recommends that the test voltage for polymer insulated heating cables be 2500 Vdc. The mini­mum acceptable level for the megger reading for any polymer-insulated heat tracing cable is 20 megohms. (Record 2 on Cable Testing Report)
Temperature Control . . .
1.
When a line sensing controller is specied, the sensor should be placed at least 90° around the circumference from the heating cable, or at least 2" (5 cm) from the cable.
Heating Cable vs. Sensor Location
Optional Second
Heating Cable
Temperature
Sensor
90°
2. For pipewall sensing thermostatic control, the heating circuit is to be connected in series with the control contacts as shown in illustration below. The pipewall sensing thermostat may require more than one support point.
Pipewall Sensing Control Connection
L1
L2/N
Power Connection
3. When using an ambient sensing temperature controller, the mounting location should be representative of the coldest
Temperature Sensor End Termination
Heating Cable
region, and the sensing element should not be exposed to direct sunlight or any additional heat source.
Ambient Sensing Control Connection
Ambient Sensing Thermostat
Optional Third Heating Cable
Heating Cable
(Typical)
Notes . . .
1. Table 2 assumes circumferential bands every 12” (30 cm) along the length of the piping.
2. Verify exposure temperature of heating cable versus curing temperature of insulation.
Table 2: Attachment Tape (Value Represents Approximate Linear Pipe Length Allowance Per Roll)
Tape
Length
36 yd
60 yd
½"-1" 1¼" 1½" 2" 3" 4" 6" 8" 10" 12" 14" 16" 18" 20" 24" 30"
130' 115' 110' 95' 75' 65' 50' 40' 35' 30' 26' 23' 21' 19' 16' 13'
215' 195' 180' 160' 125' 105' 80' 65' 55' 50' 43' 38' 35' 31' 27' 22'
L1
L2/N
End Termination
Power Connection
Heating Cable
Pipe Diameter in Inches
5
FLX
TM
Thermal Insulation . . .
1. The need for properly installed and well-maintained thermal insulation cannot be overemphasized. Without insulation, heat losses are generally too high to be oset by a conven­tional heat tracing system.
2. In addition to piping and in-line equipment such as pumps and valves, all heat sinks must be properly insulated. This includes pipe supports, hangers, anges and, in most cases, valve bonnets.
3. Regardless of the type or thickness of insulation used, a protective barrier should be installed. This protects the insulation from moisture intrusion, physical damage and helps ensure the proper performance of the heat tracing system. Seal around all penetrations through the thermal insulation.
4. After the installation of the thermal insulation and weather barrier but BEFORE ENERGIZING THE HEATING CIRCUIT, the megohmmeter test should be repeated. This should call attention to any damage to the heating cable that may have occurred during the insulation installation. (Record 3 on Cable Testing Report)
Final Inspection and Documentation . . .
1. It is recommended that the circuit be temporarily energized so that the volts, amps, pipe temperature and ambient temperature may be recorded. This information may be of value for future reference and should be maintained for the historical operating data log (Record 4 on Cable Testing Report).
2. Once power is connected but before putting the system into operation, verify all heating cable testing and documen­tation have been completed for each heat tracing circuit. This will ensure that the system has been installed per the
manufacturers recommendations.
The National Electric Code and Canadian Electrical Code require ground-fault protection be provided for branch circuits supplying electric heat tracing on xed outdoor electric de-icing and snow-melt­ing equipment.
5. Apply caution labels to insulation weather barrier at required intervals along pipe
Thermal Insulation with Weather Barrier
Thermal
Insulation
Temperature
Sensor
Weather
Barrier
Heating Cable
(Typical)
6
FLX ™ Cable Testing Report
1. Refer to Thermon FLX Installation Procedures, FORM CPD1018, for general installation procedures, requirements and guide­lines.
2. Upon receiving heating cable, check the cable to make sure the proper type and output have been received. All cables are printed on the outer jacket with part number, voltage rating and watt output.
3. Visually inspect cable for any damage incurred during shipment. The heating cable should be tested to ensure electrical integrity with at least a 500 Vdc megohmmeter (megger) between the heating cable bus wires and the heating cable metallic braid. IEEE 515.1 recommends that the test voltage for polymer insulated heating cables be 2500 Vdc. Minimum resistance should be 20 megohms. (Record 1 on Cable Testing Report.)
A. Connect the positive lead of the megger to the cable bus
wires.
B. Connect the negative lead of the megger to the metallic braid.
C. Energize the megger and record the reading. Readings between 20 megohms and innity are acceptable. Readings
below 20 megohms may mean the electrical insulation has been damaged. Recheck the heating cable for physical damage between the braid and the heating element; small cuts or scumarks on the outer jacket will not aect the megger reading unless there was actual penetration through the braid and dielectric insulation jacket.
4. Once the installation is complete, but prior to installation of thermal insulation, recheck the heating cable with at least a 500 Vdc megohmmeter (megger) between the heating cable bus wires and the heating cable metallic braid. IEEE 515.1 recommends that the test voltage for polymer insulated heating cables be 2500 Vdc. Minimum resistance should be 20 megohms. (Record 2 on Cable Testing Report.)
5. After the thermal insulation is installed, the megohmmeter test should be repeated. Minimum resistance should be 20 megohms. (Record 3 on Cable Testing Report.)
6. After the thermal insulation is installed and power supply is completed, record the panel and circuit breaker information. Ensure all junction boxes, temperature controllers, cable glands, etc. are properly secured. Set the temperature controller
NOTE: To ensure the heating cable warranty is maintained through installation, the testing outlined on
this sheet must be completed on the installed heating cables, and the test results recorded and mailed/faxed to:
Thermon Customer Service
100 Thermon Drive San Marcos, Texas 78666 Fax: 512-754-2420
7
FLX ™ Cable Testing Report
Customer: Contractor:
Address: Address:
Phone No: Phone No.
Project Reference:
Record 1: Prior to Installation
Cable Type:
Heater Length:
Heater Number:
Insulation Resistance M Ohms:
Tested By: Date:
Witnessed By: Date:
Record 2: After Installation
Insulation Resistance M Ohms:
Tested By: Date:
Witnessed By: Date:
Record 3: After Thermal Insulation is Installed
Insulation Resistance M Ohms:
Tested By: Date:
Witnessed By: Date:
Record 4: Final Commissioning
Panel Number:
Breaker Number:
Volts:
Ambient Temperature (deg. F):
Recorded Amps:
Tested By: Date:
Witnessed By: Date:
Other Products . . .
Thermon oers additional cut-to-length cables or
complete turn-key systems for the following applications:
• Hot Water Temperature Maintenance
• Freezer Floor Frost Heave Prevention
• Tank and Hopper Heating
• Instrument Tubing Bundles
• Control and Monitoring Systems
Thermon . . . The Heat Tracing Specialists
100 Thermon Dr. PO Box 609 San Marcos, TX 78667-0609 Phone: (512) 396-5801 Facsimile: (512) 396-3627 800-820-HEAT www.thermon.com In Canada call 800-563-8461
Form CPD1018-0716 © Thermon Manufacturing Co. Printed in U.S.A.
Loading...