Thermon FLX User Manual

TM
FLX
Self-Regulating
Winterization/Freeze Protection
INSTALLATION PROCEDURES
FLX
TM
Self-Regulating
INSTALLATION PROCEDURES
Refer to the “FLX Cable Testing Report” for required recording of test data and circuit information.
Upon Receiving Cable . . .
1. Upon receiving heating cable, check to make sure the proper type and output have been received. All cables are printed on the outer jacket with part number, voltage rating and watt output.
2. Visually inspect cable for any damage incurred during ship­ment. The heating cable should be tested to ensure electri­cal integrity with at least a 500 Vdc megohmmeter (meg­ger) between the heating cable bus wires and the heating cable metallic braid. IEEE 515.1 recommends that the test voltage for polymer insulated heating cables be 2500 Vdc. Minimum resistance should be 20 megohms. (Record 1 on Cable Testing Report.)
Typical Heat Tracing Installation . . .
A complete electric heat tracing system will typically include the following components:
1. Electric heat tracing cable.
2. Power connection kit.
3. Control thermostat (may be remote ambient sens­ing control.)
4. In-line/T-splice kit (permits two or three cables to be spliced together).
5. Cable end termination.
6. Attachment tape (use on 12” intervals or as required by code or specification).
7. “Electric Heat Tracing” label (peel-and-stick label attaches to insulation vapor barrier on 10’ intervals or as required by code or specification).
4
7
8
5
6
1
Connect the positive lead of the megger to the cable bus wires and the negative lead to the metallic braid.
CAUTION: DO NOT connect power to heating cable while it is on reel or in shipping carton.
Before Installing Cable . . .
1. Be sure all piping and equipment to be traced is completely installed and pressure tested.
2. Surface areas where heat tracing is to be installed must be reasonably clean. Remove dirt, rust and scale with a wire brush and oil and grease films with a suitable solvent.
8. Thermal insulation and vapor barrier (by others).
The absence of any of these items can cause a system to malfunction or represent a safety hazard.
The National Electric Code and Canadian Electrical Code require ground-fault protection be provided for all electric heat tracing.
3
2
1
FLX
Self-Regulating
Initial Installation . . .
TM
1. Begin temporary installation at the proposed end-of-circuit location and lay out heating circuit on the pipe, allowing ex­tra cable for the power connection and for any splice loca­tions. Refer to illustration below for temporary installation.
Temporary Installation
Proposed Power
Connection Location
Cable Allowance for
In-Line Heat Sinks
Installation on Fittings and Equipment . . .
2. Make heating cable allowances for valves, flanges, elbows and supports as per the applicable drawings and table on pages 2 and 3 of these installation procedures. See product specifications sheet for heating cable minimum bend radius.
Proposed End-of-Circuit
Location
Pipe Support
1. Install heating cable in accordance with illustrations below. Secure heating cable to piping using attachment tape.
2. Elbows: Locate the cable on the outside radius of an elbow to provide sufficient heat to compensate for the added pip-
3. Pipe Supports: Insulated pipe supports require no additional heating cable. For uninsulated supports, allow two times the length of the pipe support plus an additional 15” (40 cm) of heating cable.
ing material. Secure the cable to the pipe on each side of the elbow with attachment tape.
Pipe Elbow Pipe Support
Heating Cable
Attachment Tape
(Typical)
Heating Cable
3” Min.
(8 cm)
Attachment Tape
(Typical)
3” Min.
(8 cm)
Support
Length
2
INSTALLATION PROCEDURES
4. Flanges: Allow cable to be looped around pipe on each side of and adjacent to the flange. Heating cable must maintain contact with flange when bending around pipe flanges to compensate for additional heat loss.
Typical Flange Detail
Heating Cable
12” Max.
Note:
Flange allowance will vary based on method of insulating flange and adjacent piping.
(30 cm)
Attachment Tape
(Typical)
5. Additional cable is required to provide extra heat at valves, pumps and miscellaneous equipment to offset the in­creased heat loss associated with these items. Refer to Table 1 for estimated cable requirements for installation on typical valves and pumps.
6. Install heating cable on valves and pumps utilizing a looping technique (this allows the valve or pump to be removed if required).
Typical Valve Details
Heating Cable
Temporary Loop of Cable on Valve
Attachment Tape
(Typical)
Table 1: Valve and Pump Allowances
Pipe Size
½" 6" 1' 0 1' 2'
¾" 9" 1'-6" 0 1'-6" 3'
1" 1' 2' 1' 2' 4'
1¼" 1'-6" 2' 1' 3' 4'-6"
1½" 1'-6" 2'-6" 1'-6" 3' 5'
2" 2' 2'-6" 2' 4' 5'-6"
3" 2'-6" 3'-6" 2'-6" 5' 7'
4" 4' 5' 3' 8' 10'
6" 7' 8' 3'-6" 14' 16'
8" 9'-6" 11' 4' 19' 22'
10" 12'-6" 14' 4' 25' 28'
12" 15' 16'-6" 5' 30' 33'
14" 18' 19'-6" 5'-6" 36' 39'
16" 21'-6" 23' 6' 43' 46'
18" 25'-6" 27' 6'-6" 51' 54'
20" 28'-6" 30' 7' 57' 60'
24" 34' 36' 8' 68' 72'
30" 40' 42' 10' 80' 84'
Screwed Flanged Welded
Valve Type
Pump Type
Screwed Flanged
Heating Cable Attachment Tape
Heating Cable Serpentined on Valve
(Typical)
Typical Pump Detail
Heating Cable
Heating Cable Serpentined on Pump
Attachment Tape
(Typical)
3
FLX
TM
Self-Regulating
Completing the Installation . . .
1. Begin final cable attachment by securing the end-of-circuit termination kit and working back toward the power supply.
•Flexibleheatingcablesaretobeinstalledusingattachment
tape. Circumferential bands of tape should be installed at 12” (30 cm) intervals to keep the cable in proper contact with the pipe. Refer to Table 2 below to calculate the num­ber of rolls of attachment tape required based on the pipe diameter 1.
•Ifapplicable,refertoinstallationdetailsprovidedwiththe
project drawings or contact Thermon for additional infor­mation regarding installation.
2. In addition to the circumferential tape requirements, a continuous covering of aluminum foil tape may be required when:
•Sprayorfoamurethane2 thermal insulation is applied.
•Heattracingnonmetallicpiping.
•Designrequirementsdictatetheuseofaluminumtapeto
improve heat transfer.
3. Complete splice connections (if required) in accordance with the installation instructions provided with the splice kit.
4. Install power connection kit in accordance to the detailed installation instructions provided with the kit.
5. Before making power connections, repeat the megger test with at least a 500 Vdc megohmmeter (megger) between the heating cable bus wires and the heating cable metallic braid. IEEE 515.1 recommends that the test voltage for polymer insulated heating cables be 2500 Vdc. The mini­mum acceptable level for the megger reading for any polymer-insulated heat tracing cable is 20 megohms. (Record 2 on Cable Testing Report)
Temperature Control . . .
1.
When a line sensing controller is specified, the sensor should be placed at least 90° around the circumference from the heating cable, or at least 2" (5 cm) from the cable.
Heating Cable vs. Sensor Location
Optional Second
Heating Cable
Temperature
Sensor
90°
2. For pipewall sensing thermostatic control, the heating circuit is to be connected in series with the control contacts as shown in illustration below. The pipewall sensing thermostat may require more than one support point.
Pipewall Sensing Control Connection
L1
L2/N
Power Connection
Temperature Sensor End Termination
Heating Cable
3. When using an ambient sensing temperature controller, the mounting location should be representative of the coldest region, and the sensing element should not be exposed to direct sunlight or any additional heat source.
Ambient Sensing Control Connection
Ambient Sensing Thermostat
Optional Third
Heating Cable
Heating Cable
(Typical)
Notes . . .
1. Table 2 assumes circumferential bands every 12” (30 cm) along the length of the piping.
2. Verify exposure temperature of heating cable versus curing temperature of insulation.
Table 2: Attachment Tape (Value Represents Approximate Linear Pipe Length Allowance Per Roll)
Tape
Length
36 yd
60 yd
½"-1" 1¼" 1½" 2" 3" 4" 6" 8" 10" 12" 14" 16" 18" 20" 24" 30"
130' 115' 110' 95' 75' 65' 50' 40' 35' 30' 26' 23' 21' 19' 16' 13'
215' 195' 180' 160' 125' 105' 80' 65' 55' 50' 43' 38' 35' 31' 27' 22'
Pipe Diameter in Inches
L1
L2/N
End Termination
Power Connection
Heating Cable
4
INSTALLATION PROCEDURES
Thermal Insulation . . .
1. The need for properly installed and well-maintained thermal insulation cannot be overemphasized. Without insulation, heat losses are generally too high to be offset by a conven­tional heat tracing system.
2. In addition to piping and in-line equipment such as pumps and valves, all heat sinks must be properly insulated. This includes pipe supports, hangers, flanges and, in most cases, valve bonnets.
3. Regardless of the type or thickness of insulation used, a protective barrier should be installed. This protects the insulation from moisture intrusion, physical damage and helps ensure the proper performance of the heat tracing system. Seal around all penetrations through the thermal insulation.
4. After the installation of the thermal insulation and weather barrier but BEFORE ENERGIZING THE HEATING CIRCUIT, the megohmmeter test should be repeated. This should call attention to any damage to the heating cable that may have occurred during the insulation installation. (Record 3 on Cable Testing Report)
Final Inspection and Documentation . . .
1. It is recommended that the circuit be temporarily energized so that the volts, amps, pipe temperature and ambient temperature may be recorded. This information may be of value for future reference and should be maintained for the historical operating data log (Record 4 on Cable Testing Report).
2. Once power is connected but before putting the system into operation, verify all heating cable testing and documen­tation have been completed for each heat tracing circuit. This will ensure that the system has been installed per the
manufacturers recommendations.
The National Electric Code and Canadian Electrical Code require ground-fault protection be provided for branch circuits supplying electric heat tracing on fixed outdoor electric de-icing and snow-melt­ing equipment.
5. Apply caution labels to insulation weather barrier at required intervals along pipe
Thermal Insulation with Weather Barrier
Thermal
Insulation
Temperature
Sensor
Weather
Barrier
Heating Cable
(Typical)
5
FLX
Self-Regulating
Installation Guidelines for Fire Protection Systems
1. Where above ground water-filled supply pipes, risers, sys­tem risers or feed mains pass through open areas, cold rooms, passageways, or other areas exposed to freezing temperatures, the pipe shall be protected against freezing in accordance with NPFA 13, "Standard for the Installation of Sprinkler Systems".
2. Thermon's FLX Self-Regulating Heating Cables are UL Listed for use on Fire Protection System Piping feed mains, risers, and cross mains (excluding branch lines). This application approval includes piping which connects between build­ings in unheated areas, piping located in unheated areas or piping through coolers or freezers. As with all heat traced piping systems, thermal insulation is required to ensure the heating system can compensate for heat losses.
3. In accordance with IEEE 515.1 guidelines, the use of ambi­ent sensing control with low temperature and continuity monitoring as a minimum for all fire protection piping heat tracing systems is required; Thermon recommends the use of an electronic controller with RTD sensing be considered for these applications.
TM
PCS-COM
Heater
Feed Main
End
Termination
Riser
RTD
Cold Room
PCA-COM
Branch Line
Cross Main
Conditioned
Area
Electronic Controller
(Recommended)
THE NFPA DEFINES THE FOLLOWING:
Branch Lines—The pipes in which the sprinklers are placed,
either directly or through risers.
Cross Mains—The pipes supplying the branch lines, either directly or through risers.
Feed Mains—The pipes supplying cross mains, either directly or through risers.
Risers—The vertical supply pipes in a sprinkler system.
6
FLX ™ Cable Testing Report
1. Refer to Thermon FLX Installation Procedures, FORM CPD0000, for general installation procedures, requirements and guide­lines.
2. Upon receiving heating cable, check the cable to make sure the proper type and output have been received. All cables are printed on the outer jacket with part number, voltage rating and watt output.
3. Visually inspect cable for any damage incurred during shipment. The heating cable should be tested to ensure electrical integrity with at least a 500 Vdc megohmmeter (megger) between the heat­ing cable bus wires and the heating cable metallic braid. IEEE 515.1 recommends that the test voltage for polymer insulated heating cables be 2500 Vdc. Minimum resistance should be 20 megohms. (Record 1 on Cable Testing Report.)
A. Connect the positive lead of the megger to the cable bus wires.
B. Connect the negative lead of the megger to the metallic braid.
C. Energize the megger and record the reading. Readings between 20 megohms and infinity are acceptable. Readings below
20 megohms may mean the electrical insulation has been damaged. Recheck the heating cable for physical damage between the braid and the heating element; small cuts or scuffmarks on the outer jacket will not affect the megger reading unless there was actual penetration through the braid and dielectric insulation jacket.
4. Once the installation is complete, but prior to installation of thermal insulation, recheck the heating cable with at least a 500 Vdc megohmmeter (megger) between the heating cable bus wires and the heating cable metallic braid. IEEE 515.1 recommends that the test voltage for polymer insulated heating cables be 2500 Vdc. Minimum resistance should be 20 megohms. (Record 2 on
Cable Testing Report.)
5. After the thermal insulation is installed, the megohmmeter test should be repeated. Minimum resistance should be 20 meg­ohms. (Record 3 on Cable Testing Report.)
6. After the thermal insulation is installed and power supply is completed, record the panel and circuit breaker information. Ensure all junction boxes, temperature controllers, cable glands, etc. are properly secured. Set the temperature controller (if applica­ble) to the manual setting and apply rated voltage to the heat tracing circuit(s) for 10 minutes. Record the ambient temperature, measure and record the circuit(s) voltage and current. (Record 4 on Cable Testing Report.)
NOTE: To ensure the heating cable warranty is maintained through installation, the testing outlined on
this sheet must be completed on the installed heating cables, and the test results recorded and mailed/faxed to:
Thermon Customer Service
100 Thermon Drive San Marcos, Texas 78666 Fax: 512-754-2420
7
FLX ™ Cable Testing Report
Customer: Contractor: Address: Address:
Phone No: Phone No. Project Reference:
Record 1: Prior to Installation
Cable Type: Heater Length: Heater Number: Insulation Resistance M Ohms: Tested By: Date: Witnessed By: Date:
Record 2: After Installation
Insulation Resistance M Ohms: Tested By: Date: Witnessed By: Date:
Record 3: After Thermal Insulation is Installed
Insulation Resistance M Ohms: Tested By: Date: Witnessed By: Date:
Record 4: Final Commissioning
Panel Number: Breaker Number: Volts: Ambient Temperature (deg. F): Recorded Amps: Tested By: Date: Witnessed By: Date:
Other Products . . . Thermon offers additional cut-to-length cables or
complete turn-key systems for the following applications:
•HotWaterTemperatureMaintenance
•FreezerFloorFrostHeavePrevention
•TankandHopperHeating
•InstrumentTubingBundles
•ControlandMonitoringSystems
Thermon . . . The Heat Tracing Specialists
100 Thermon Dr. PO Box 609 San Marcos, TX 78667-0609 Phone: (512) 396-5801 Facsimile: (512) 396-3627 800-820-HEAT www.thermon.com In Canada call 800-563-8461
Form CPD1018-1008 © Thermon Manufacturing Co. Printed in U.S.A.
Loading...