Thermo King SR-3 Manual To Simple Operation

Simple to Start:
1. Press the ON Key.
2. A series of start-up screens will appear.
3. The Standard Display appears showing setpoint and box temperature when the unit is running.
4. The Standard Display defaults to the “Temperature Watch” screen after 2 1/2 minutes. This screen displays same setpoint and box temperature in larger font.
NOTE: For more detailed information, see the Operation chapter in the appropriate unit operating manual.
Simple to Set:
CYCLE-SENTRY or Continuous Run
1. Return to the Standard Display.
2. Press the MODE SELECTION Key.
3. The “Programming Continuous Mode” or “Programming CYCLE­SENTRY Mode” screen briefly appears.
4. The “New System Mode is Continuous” screen or the “New System Mode CYCLE­SENTRY” screen briefly appears.
5. The Standard Display appears and the heading on top of screen reads the new mode.
6. Pressing the MODE SELECTION Key again will change the unit back to the previous mode.
NOTE: For more detailed information, see the Operation chapter in
the appropriate unit operating manual.
3
1
4
1
2 & 6
5
5
Simple to Set:
Setpoint Temperature
1. Return to the Standard Display.
2. Press the SETPOINT Key on the Standard Display.
3. Press the + or - Keys to change the setpoint reading.
4. Press the YES or NO key accordingly.
5. The Standard Display appears with setpoint changed to the new setpoint.
NOTE: For more detailed information, see the Operation chapter in the appropriate unit operating manual.
Simple to Check:
Gauges
1. Return to the Standard Display.
2. Press the GAUGES Key.
3. Press BACK or NEXT Keys to scroll through following gauges: Coolant
Temperature, Coolant Level, Engine Oil, Pressure, Amps, Battery Voltage, Engine RPM, Discharge Pressure, Suction Pressure, ETV Position, I/O. If no keys are pressed within 30 seconds, the screen will return to the Standard Display.
4. Press the LOCK Key to display any gauge screen for an indefinite period. Press the key again to unlock the screen.
5. Press the EXIT Key to return to the Standard Display.
NOTE: For more detailed information, see the Operation chapter in the appropriate unit operating manual.
2
1
4
3
5
1
2
5 4 3 3
Simple to Defrost:
Initiate Manual Defrost
1. Return to the Standard Display.
2. Press the DEFROST Key.
3. Miscellaneous defrost programming screens appear.
4. A modified Standard Display screen appears. The bar indicator will fill in showing the time remaining to complete the Defrost cycle. When the Defrost cycle is complete the display returns to Standard Display screen.
NOTE: For more detailed information, see the Operation chapter in the appropriate unit operating manual.
Simple to Access:
Sensors
1. Return to the Standard Display.
2. Press the SENSORS Key.
3. Press the BACK or NEXT Keys to scroll through the following sensor screens: Control Return Air
Temperature,Display Return Air Temperature, Control Discharge Air Temperature, Display Discharge Air Temperature, Temperature Differential, Evaporator Coil Temperature, Ambient Air Temperature, Spare 1 Temperature, Datalogger Temperature Sensors 1-6 and the Board Temperature Sen so r. If no keys are pressed within 30 seconds, the screen will return to the Standard Display.
4. Press the LOCK Key to display any sensor screen for an indefinite period. Press the key again to unlock the screen.
5. Press the EXIT Key to return to the Standard Display.
NOTE: For more detailed information, see the Operation chapter in the appropriate unit operating manual.
2
1
3
4
2
1
5 4 3 3
Simple to Check:
Pretrip Test
1. Clear all alarm codes.
2. Return to the Standard Display.
3. Press the MENU key.
4. Press the NEXT Key as required to show the Pretrip Menu.
5. Press the SELECT Key to start a Pretrip Test.
6. If the unit is not running, a Full Pretrip will be initiated. If the unit is running in either diesel or electric mode, a Running Pretrip will be performed.
7. When all tests are complete, the results are reported a s PASS, CHECK or FAIL. If the results are CHECK or FAIL, the accompanying alarm codes will direct the technician to the cause of the problem.
NOTE: For more detailed information, see the Operation chapter in the appropriate unit operating manual.
Simple to Check:
Hourmeters
1. Return to the Standard Display screen.
2. Press the MENU Key.
3. Scroll through Main Menu by repeatedly pressing the NEXT and BACK Keys until the hourmeters Main Menu Screen appears.
4. Press the SELECT Key to enter the Hourmeters Menu.
5. Press the NEXT and BACK Keys to view the Hourmeter Displays.
NOTE: For more detailed information, see the Operation chapter in the appropriate unit operating manual.
3
2
5
4
7
2
1
4 3 & 5 3 & 5
Simple to View:
Cause of Alarm
1. Return to the Standard Display Screen.
2. Press the MENU Key.
3. Press the NEXT Key until the Alarm Menu appears.
4. Press the SELECT Key. The Alarm Display will appear
5. If no alarms are present, Alarm 00 is shown.
6. Press the EXIT Key to return to the Standard Display.
7. If alarms are present, the quantity of alarms and the most recent alarm code number will be shown.
8. If there is more than one alarm, press the NEXT Key to view each alarm.
9. If a serious alarm occurs, the unit will be shut down to prevent damage to the unit or the load. If this occurs, the display will show that the unit is shut down and display the alarm code that caused the shutdown.
NOTE: For more detailed information, see the Operation chapter in the appropriate unit operating manual.
Simple to View:
Clearing Alarm Codes
1.Press the CLEAR Key to
clear an alarm.
2. The display screen will
return to the Standard Display when the alarms are cleared.
3. Press the HELP key for
additional information regarding the alarm shown on the display. Also see the complete Alarm Code list in the next column.
NOTE: For more detailed information, see the Operation chapter in the appropriate unit operating manual.
2
1
7
4
3
6
5
1 3
2
Simple to Determine:
Cause of Alarm
0 No Alarms Exist 2 Evaporator Coil Sensor 3 Control Return Air Sensor 4 Control Discharge Air Sensor 5 Ambient Air Sensor 6 Coolant Temp Sensor 7 Engine RPM Sensor 9 High Evaporator Temperature 10 High Discharge Pressure 11 Unit Controlling on Alternate Sensor 12 Sensor or Digital Input Shutdown 13 Sensor Check 15 Check Glow Plugs/Intake Air Heater 17 Engine Failed to Crank 18 High Engine Coolant Temperatu r e 19 Low Engine Oil Pressure 20 Engine Failed to Start 21 Cooling Cycle Check 22 Heating Cycle Check 23 Cooling Cycle Fault 24 Heating Cycle Fault 25 Alternator Check 26 Refrigeration Capacity 28 Pretrip or Self Check Abort 29 Defrost Damper Circuit 30 Defrost Damper Stuck 31 Oil Pressure Switch 32 Refrigeration Capacity Low 33 Check Engine RPM 35 Run Relay Circuit 36 Electric Motor Failed to Run 37 Engine Coolant Level 38 Electric Phase Reversed 39 Water Valve Circuit 40 High Speed Circuit 41 Check Engine Coolant Temperature 42 Unit Forced to Low Speed 43 Unit Forced to Low Speed Modulation 44 Check Fuel System 45 Hot Gas Bypass or Hot Gas Bypass Circuit 46 Check Air Flow 48 Check Belts/Clutch 50 Reset Clock 52 Heat Circuit 54 Test Mode Time-out 61 Low Battery Voltage 62 Ammeter Out of Calibration 63 Engine Stopped 64 Pretrip Reminder 65 Abnormal Temperature Differential 66 Low Engine Oil Level 67 Liquid Line Solenoid Circuit 68 Internal Controller Fault 70 Hourmeter Failure 74 Controller Reset to Defaults 77 Controller EPROM Checksum Failure 79 Internal Data Logger Overflow 80 Compressor Temp Sensor 81 High Compressor Temp 82 High Compressor Temperature Shutdown 83 Low Engine Coolant Temperature 84 Restart Null 85 Forced Unit Operation 86 Discharge Pressure Sensor 87 Suction Pressure Sensor
89 Check Electronic Throttling Valve Circuit 90 Electric Overload 91 Electric Ready Input 92 Sensor Grades Not Set 93 Low Compressor Suction Pressure 94 Loader #1 Circuit 95 Loader #2 Circuit 96 Low Fuel Level 98 Fuel Level Sensor 99 High Compressor Pressure Ratio 108 Door Open Time-out 111 Unit Not Configured Correctly 113 Electric Heat Circuit 114 Multiple Alarms - Cannot Run 117 Auto switch from Diesel to Electric 118 Auto switch from Electric to Diesel 120 Alternator Exciter Circuit 121 Liquid Injection Circuit 122 Diesel/Electric Relay Circuit 127 Setpoint Not Entered 128 Engine Run Time Maintenance Reminder #1 129 Engine Run Time Maintenance Reminder #2 130 Electric Run Time Maintenance Reminder #1 131 Electric Run Time Maintenance Reminder #2 132 Total Unit Run Time Maintenance Reminder #1 133 Total Unit Run Time Maintenance Reminder #2 134 Controller Power On Hours 135 Check Spare Digital Inputs 136 Check Spare Digital Outputs 137 Check Damper Motor Heater Output 141 Autoswitch Diesel to Electric Disabled 145 Loss of Controller "On" Feedback Signal 146 Software Version Mismatch 148 Autoswitch Electric to Diesel Disabled 149 Alarm Not Identified 150 Out of Range Low 151 Out of Range High 157 OptiSet Plus Mismatch 203 Display Return Air Sensor 204 Display Discharge Air Sensor 252 Check Fresh Air Exchange Circuit
SR-3
Smart Reefer 3
Microprocessor
Driver Guide to
Simple
Operation
TK 55072-2-PC (Rev. 0, 04/11) ©Thermo King Corporation
Loading...