Thermo King SB-210+, SB-310+ Operator's Manual

Operator’s Manual
Operator’s Manual
TK 53942-2-OP (Rev. 1, 11/09)
Copyright© 2009 Thermo King Corp., Minneapolis, MN, USA
Printed in USA
SB-210+/SB-310+
TK 53942-2-OP (Rev. 1, 11/09)
Copyright© 2009 Thermo King Corp., Minneapolis, MN, USA
Printed in USA
SB-210+/SB-310+
TK 53942-2-OP (Rev. 1, 11/09)
Disclaimer
This manual is published for informational purposes only. Thermo King Corporation makes no representations or warranties, express or implied, with respect to the information, recommendations and descriptions contained in this manual and such information, recommendations and descriptions should not be regarded as all-inclusive or covering all contingencies. If you have questions or require further information, please contact your local Thermo King dealer.
The procedures described herein should be undertaken only by qualified personnel. Failure to implement these procedures correctly may cause damage to the Thermo King unit or other property or personal injury.
Thermo King Corporation and its affiliates shall have no liability in contract or tort (including negligence and/or strict liability) or otherwise, to any person or entity for any personal injury, property damage or any other direct, indirect, special or consequential damage or liability whatsoever, arising out of or resulting from any actions by any person that are contrary to this manual or any of the information, recommendations or descriptions contained herein or the failure of any person to implement the procedures described herein correctly or to follow caution and safety decals located on the Thermo King unit.
Disclaimer
This manual is published for informational purposes only. Thermo King Corporation makes no representations or warranties, express or implied, with respect to the information, recommendations and descriptions contained in this manual and such information, recommendations and descriptions should not be regarded as all-inclusive or covering all contingencies. If you have questions or require further information, please contact your local Thermo King dealer.
The procedures described herein should be undertaken only by qualified personnel. Failure to implement these procedures correctly may cause damage to the Thermo King unit or other property or personal injury.
Thermo King Corporation and its affiliates shall have no liability in contract or tort (including negligence and/or strict liability) or otherwise, to any person or entity for any personal injury, property damage or any other direct, indirect, special or consequential damage or liability whatsoever, arising out of or resulting from any actions by any person that are contrary to this manual or any of the information, recommendations or descriptions contained herein or the failure of any person to implement the procedures described herein correctly or to follow caution and safety decals located on the Thermo King unit.
3
Table of Contents
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
List of Figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . 13
General Safety Practices . . . . . . . . . . . . . . . . . . . . . . 13
Automatic Start/Stop Operation . . . . . . . . . . . . . . . . . 14
Electrical Hazard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Refrigerant Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
First Aid–Refrigerant . . . . . . . . . . . . . . . . . . . . . . . 15
First Aid–Refrigerant Oil . . . . . . . . . . . . . . . . . . . . 15
Safety Decals and Locations . . . . . . . . . . . . . . . . . . . 16
EPA Emission Control System Warranty
Statement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Responsibilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Thermo King Corporation Responsibilities . . . . . .20
Owner Responsibilities . . . . . . . . . . . . . . . . . . . . .21
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Unit Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Design Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Diesel Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
ELC (Extended Life Coolant) . . . . . . . . . . . . . . . . . . . .27
EMI 3000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Thermo King X430L Reciprocating Compressor . . . . .28
Electronic Throttling Valve . . . . . . . . . . . . . . . . . . . . . .28
SMART REEFER 2 (SR-2) Control System . . . . . . . . .29
CYCLE-SENTRY Operation . . . . . . . . . . . . . . . . .29
Continuous Run Operation . . . . . . . . . . . . . . . . . .29
CYCLE-SENTRY Start-Stop Controls . . . . . . . . . .30
Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
OptiSet Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
FreshSet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
3
Table of Contents
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
List of Figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . 13
General Safety Practices . . . . . . . . . . . . . . . . . . . . . . 13
Automatic Start/Stop Operation . . . . . . . . . . . . . . . . . 14
Electrical Hazard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Refrigerant Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
First Aid–Refrigerant . . . . . . . . . . . . . . . . . . . . . . . 15
First Aid–Refrigerant Oil . . . . . . . . . . . . . . . . . . . . 15
Safety Decals and Locations . . . . . . . . . . . . . . . . . . . 16
EPA Emission Control System Warranty
Statement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Responsibilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Thermo King Corporation Responsibilities . . . . . .20
Owner Responsibilities . . . . . . . . . . . . . . . . . . . . .21
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Unit Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Design Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Diesel Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
ELC (Extended Life Coolant) . . . . . . . . . . . . . . . . . . . .27
EMI 3000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Thermo King X430L Reciprocating Compressor . . . . .28
Electronic Throttling Valve . . . . . . . . . . . . . . . . . . . . . .28
SMART REEFER 2 (SR-2) Control System . . . . . . . . .29
CYCLE-SENTRY Operation . . . . . . . . . . . . . . . . .29
Continuous Run Operation . . . . . . . . . . . . . . . . . .29
CYCLE-SENTRY Start-Stop Controls . . . . . . . . . .30
Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
OptiSet Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
FreshSet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Table of Contents
4
Opening the Front Doors . . . . . . . . . . . . . . . . . . . . . . .34
Opening the Secondary Door Latch . . . . . . . . . . .34
Closing the Front Doors . . . . . . . . . . . . . . . . . . . . . . . . 35
Engine Compartment Components . . . . . . . . . . . . . . .36
Unit Protection Devices . . . . . . . . . . . . . . . . . . . . . . . .37
Remote Status Display (Optional) . . . . . . . . . . . . . . 41
Manual Pretrip Inspection
(Before Starting the Unit) . . . . . . . . . . . . . . . . . . . . . 45
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . 47
SMART REEFER 2 (SR-2) Controller Overview . . . . .47
HMI Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Control Panel Display . . . . . . . . . . . . . . . . . . . . . . 49
Control Panel Keys . . . . . . . . . . . . . . . . . . . . . . . . 50
Turning Unit On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Turning Unit Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Standard Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Standard Display Variations . . . . . . . . . . . . . . . . . . . . 55
Temperature Watch Display . . . . . . . . . . . . . . . . . . . .56
Alarm Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Starting the Diesel Engine . . . . . . . . . . . . . . . . . . . . . .58
Unit Fails To Start . . . . . . . . . . . . . . . . . . . . . . . . .58
After Start Inspection . . . . . . . . . . . . . . . . . . . . . . 59
Electric Standby Operation . . . . . . . . . . . . . . . . . . . . . 60
Starting the Unit on Electric Standby Operation . 61
Unit Fails to Start . . . . . . . . . . . . . . . . . . . . . . . . . 62
Switching from Diesel to Electric . . . . . . . . . . . . . 63
Switching from Electric to Diesel . . . . . . . . . . . . . 64
Changing the Setpoint . . . . . . . . . . . . . . . . . . . . . . . . 65
Selection of Operating Modes . . . . . . . . . . . . . . . . . . 68
Selecting CYCLE-SENTRY or Continuous Mode . . . 69
Initiating a Manual Defrost Cycle . . . . . . . . . . . . . . . . 71
Terminating a Defrost Cycle . . . . . . . . . . . . . . . . . . . . 72
Viewing Gauge Readings . . . . . . . . . . . . . . . . . . . . . . 73
Viewing Sensor Readings . . . . . . . . . . . . . . . . . . . . . 75
Navigating the Main Menu . . . . . . . . . . . . . . . . . . . . . 79
Main Menu Choices . . . . . . . . . . . . . . . . . . . . . . . 80
Language Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Alarms Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Important Alarm Notes . . . . . . . . . . . . . . . . . . . . . 86
Datalogger Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Initiating a Start of Trip . . . . . . . . . . . . . . . . . . . . . 88
Printing a Trip Report . . . . . . . . . . . . . . . . . . . . . . 90
Hourmeters Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Mode Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Turning CYCLE-SENTRY On or Off . . . . . . . . . . 97
Table of Contents
4
Opening the Front Doors . . . . . . . . . . . . . . . . . . . . . . .34
Opening the Secondary Door Latch . . . . . . . . . . .34
Closing the Front Doors . . . . . . . . . . . . . . . . . . . . . . . . 35
Engine Compartment Components . . . . . . . . . . . . . . .36
Unit Protection Devices . . . . . . . . . . . . . . . . . . . . . . . .37
Remote Status Display (Optional) . . . . . . . . . . . . . . 41
Manual Pretrip Inspection
(Before Starting the Unit) . . . . . . . . . . . . . . . . . . . . . 45
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . 47
SMART REEFER 2 (SR-2) Controller Overview . . . . .47
HMI Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Control Panel Display . . . . . . . . . . . . . . . . . . . . . . 49
Control Panel Keys . . . . . . . . . . . . . . . . . . . . . . . . 50
Turning Unit On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Turning Unit Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Standard Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Standard Display Variations . . . . . . . . . . . . . . . . . . . . 55
Temperature Watch Display . . . . . . . . . . . . . . . . . . . .56
Alarm Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Starting the Diesel Engine . . . . . . . . . . . . . . . . . . . . . .58
Unit Fails To Start . . . . . . . . . . . . . . . . . . . . . . . . .58
After Start Inspection . . . . . . . . . . . . . . . . . . . . . . 59
Electric Standby Operation . . . . . . . . . . . . . . . . . . . . . 60
Starting the Unit on Electric Standby Operation . 61
Unit Fails to Start . . . . . . . . . . . . . . . . . . . . . . . . . 62
Switching from Diesel to Electric . . . . . . . . . . . . . 63
Switching from Electric to Diesel . . . . . . . . . . . . . 64
Changing the Setpoint . . . . . . . . . . . . . . . . . . . . . . . . 65
Selection of Operating Modes . . . . . . . . . . . . . . . . . . 68
Selecting CYCLE-SENTRY or Continuous Mode . . . 69
Initiating a Manual Defrost Cycle . . . . . . . . . . . . . . . . 71
Terminating a Defrost Cycle . . . . . . . . . . . . . . . . . . . . 72
Viewing Gauge Readings . . . . . . . . . . . . . . . . . . . . . . 73
Viewing Sensor Readings . . . . . . . . . . . . . . . . . . . . . 75
Navigating the Main Menu . . . . . . . . . . . . . . . . . . . . . 79
Main Menu Choices . . . . . . . . . . . . . . . . . . . . . . . 80
Language Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Alarms Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Important Alarm Notes . . . . . . . . . . . . . . . . . . . . . 86
Datalogger Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Initiating a Start of Trip . . . . . . . . . . . . . . . . . . . . . 88
Printing a Trip Report . . . . . . . . . . . . . . . . . . . . . . 90
Hourmeters Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Mode Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Turning CYCLE-SENTRY On or Off . . . . . . . . . . 97
Table of Contents
5
Selecting Keypad Lockout . . . . . . . . . . . . . . . . . . 99
Selecting Sleep Mode . . . . . . . . . . . . . . . . . . . . . 101
Pretrip Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Initiating a Pretrip Test . . . . . . . . . . . . . . . . . . . . 106
Stopping a Pretrip Test . . . . . . . . . . . . . . . . . . . . 107
Electric Standby/Diesel Mode . . . . . . . . . . . . . . . . . . 109
Adjust Brightness Menu . . . . . . . . . . . . . . . . . . . . . . 111
Time Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
OptiSet Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Selecting a Named Product . . . . . . . . . . . . . . . . 117
Changing the Setpoint for a Named Product . . . 122
Selecting a Setpoint . . . . . . . . . . . . . . . . . . . . . . 125
Optional Rear Remote Control Panel . . . . . . . . . . 129
Rear Remote Control Panel Functions . . . . . . . . . . . 130
Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Stand By . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Reading a Typical Remote Standard Display . . . . . . 135
Remote Control Panel Lockout . . . . . . . . . . . . . . . . . 135
Turning the Unit On or Off (Configured for STAND BY
Operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Turning the Unit On and Off (Configured for RUN
Operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .136
Changing the Setpoint . . . . . . . . . . . . . . . . . . . . . . . .137
Selecting Cycle-Sentry or Continuous Mode . . . . . . .138
Displaying the Discharge Air Temperature . . . . . . . .139
Viewing and Clearing Alarm Codes . . . . . . . . . . . . . .140
Starting a Manual Defrost Cycle . . . . . . . . . . . . . . . .141
Sending a Start of Trip Marker . . . . . . . . . . . . . . . . . .142
Running a Pretrip Test . . . . . . . . . . . . . . . . . . . . . . . .143
Alarm Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Alarm Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Corrective Action . . . . . . . . . . . . . . . . . . . . . . . . . . . .148
Loading and Enroute Inspections . . . . . . . . . . . . .165
Pre-Loading Inspection . . . . . . . . . . . . . . . . . . . . . . .165
Post-Loading Inspection . . . . . . . . . . . . . . . . . . . . . .167
Enroute Inspections . . . . . . . . . . . . . . . . . . . . . . .168
Jump Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .171
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .175
Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .175
Belt Tension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .178
Table of Contents
5
Selecting Keypad Lockout . . . . . . . . . . . . . . . . . . 99
Selecting Sleep Mode . . . . . . . . . . . . . . . . . . . . . 101
Pretrip Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Initiating a Pretrip Test . . . . . . . . . . . . . . . . . . . . 106
Stopping a Pretrip Test . . . . . . . . . . . . . . . . . . . . 107
Electric Standby/Diesel Mode . . . . . . . . . . . . . . . . . . 109
Adjust Brightness Menu . . . . . . . . . . . . . . . . . . . . . . 111
Time Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
OptiSet Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Selecting a Named Product . . . . . . . . . . . . . . . . 117
Changing the Setpoint for a Named Product . . . 122
Selecting a Setpoint . . . . . . . . . . . . . . . . . . . . . . 125
Optional Rear Remote Control Panel . . . . . . . . . . 129
Rear Remote Control Panel Functions . . . . . . . . . . . 130
Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Stand By . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Reading a Typical Remote Standard Display . . . . . . 135
Remote Control Panel Lockout . . . . . . . . . . . . . . . . . 135
Turning the Unit On or Off (Configured for STAND BY
Operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Turning the Unit On and Off (Configured for RUN
Operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .136
Changing the Setpoint . . . . . . . . . . . . . . . . . . . . . . . .137
Selecting Cycle-Sentry or Continuous Mode . . . . . . .138
Displaying the Discharge Air Temperature . . . . . . . .139
Viewing and Clearing Alarm Codes . . . . . . . . . . . . . .140
Starting a Manual Defrost Cycle . . . . . . . . . . . . . . . .141
Sending a Start of Trip Marker . . . . . . . . . . . . . . . . . .142
Running a Pretrip Test . . . . . . . . . . . . . . . . . . . . . . . .143
Alarm Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Alarm Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Corrective Action . . . . . . . . . . . . . . . . . . . . . . . . . . . .148
Loading and Enroute Inspections . . . . . . . . . . . . .165
Pre-Loading Inspection . . . . . . . . . . . . . . . . . . . . . . .165
Post-Loading Inspection . . . . . . . . . . . . . . . . . . . . . .167
Enroute Inspections . . . . . . . . . . . . . . . . . . . . . . .168
Jump Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .171
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .175
Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .175
Belt Tension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .178
Table of Contents
6
Electrical Control System . . . . . . . . . . . . . . . . . . . . . 179
Electric Standby (Model 50 Units Only) . . . . . . . . . . .180
Electric Fuel Heater (Optional) . . . . . . . . . . . . . . . . . 181
Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . .182
Maintenance Inspection Schedule . . . . . . . . . . . . . 183
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Serial Number Locations . . . . . . . . . . . . . . . . . . . . 201
Emergency Cold Line . . . . . . . . . . . . . . . . . . . . . . . 205
Recover Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . 206
CALIFORNIA
Proposition 65 Warning . . . . . . . . . . . . . . . . . . . . . 207
Table of Contents
6
Electrical Control System . . . . . . . . . . . . . . . . . . . . . 179
Electric Standby (Model 50 Units Only) . . . . . . . . . . .180
Electric Fuel Heater (Optional) . . . . . . . . . . . . . . . . . 181
Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . .182
Maintenance Inspection Schedule . . . . . . . . . . . . . 183
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Serial Number Locations . . . . . . . . . . . . . . . . . . . . 201
Emergency Cold Line . . . . . . . . . . . . . . . . . . . . . . . 205
Recover Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . 206
CALIFORNIA
Proposition 65 Warning . . . . . . . . . . . . . . . . . . . . . 207
7
List of Figures
Figure 1:ELC (Extended Life Coolant) Nameplate
(Located on expansion tank in units
equipped with ELC) . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 2:Belt Warning
(Located on condenser housing) . . . . . . . . . . . . . 16
Figure 3:Belt Replacement Caution
(Located on condenser housing) . . . . . . . . . . . . . 16
Figure 4:Automatic Start Caution
(Locations vary depending on model. Decals are located near areas that contain moving parts which can cause severe injuries if hands or clothing become
tangled when unit automatically starts.) . . . . . . . . 17
Figure 5:Fan Caution
(Locations vary depending on model. Decals are located near areas that contain fans which can ca use severe injuries when unit automatically starts.) . . 17
Figure 6:Door Latch Warning
(Located on curbside door) . . . . . . . . . . . . . . . . . . 18
Figure 7:Front View . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 8:TK486V (TK486VH is Similar) Tier 2 . . . . . . 26
Figure 9:Compressors . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 10:HMI Controller and Data Ports . . . . . . . . . . .31
Figure 11:Door Latch Location . . . . . . . . . . . . . . . . . . .34
Figure 12:Opening Secondary Door Latch . . . . . . . . .34
Figure 13:Engine Compartment . . . . . . . . . . . . . . . . . .36
Figure 14:Control Box With Service Door Open . . . . .39
Figure 15:Control Box With Control Box Door Open . .40
Figure 16:Interface Board . . . . . . . . . . . . . . . . . . . . . .40
Figure 17:Remote Status Display (All LEDs Shown) . .41
Figure 18:Normal Operation No Alarms . . . . . . . . . . . .41
Figure 19:Check Alarm . . . . . . . . . . . . . . . . . . . . . . . .42
Figure 20:Shutdown Alarm . . . . . . . . . . . . . . . . . . . . .42
Figure 21:Remote Status Display with Fuel Level . . . .43
Figure 22:Remote Status Display
with Fuel Level and Temperature . . . . . . . . . . . . .43
Figure 23:SR-2 HMI Control Panel . . . . . . . . . . . . . . .47
Figure 24:Control Box With Service Door Open . . . . .48
Figure 25:Control Panel Display and Keys . . . . . . . . .49
Figure 26:Press On Key . . . . . . . . . . . . . . . . . . . . . . . .51
Figure 27:Turning Unit On Screen Sequence . . . . . . .52
Figure 28:Press Off Key . . . . . . . . . . . . . . . . . . . . . . . .53
Figure 29:Turning Unit Off Screen Sequence . . . . . . .53
7
List of Figures
Figure 1:ELC (Extended Life Coolant) Nameplate
(Located on expansion tank in units
equipped with ELC) . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 2:Belt Warning
(Located on condenser housing) . . . . . . . . . . . . . 16
Figure 3:Belt Replacement Caution
(Located on condenser housing) . . . . . . . . . . . . . 16
Figure 4:Automatic Start Caution
(Locations vary depending on model. Decals are located near areas that contain moving parts which can cause severe injuries if hands or clothing become
tangled when unit automatically starts.) . . . . . . . . 17
Figure 5:Fan Caution
(Locations vary depending on model. Decals are located near areas that contain fans which can ca use severe injuries when unit automatically starts.) . . 17
Figure 6:Door Latch Warning
(Located on curbside door) . . . . . . . . . . . . . . . . . . 18
Figure 7:Front View . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 8:TK486V (TK486VH is Similar) Tier 2 . . . . . . 26
Figure 9:Compressors . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 10:HMI Controller and Data Ports . . . . . . . . . . .31
Figure 11:Door Latch Location . . . . . . . . . . . . . . . . . . .34
Figure 12:Opening Secondary Door Latch . . . . . . . . .34
Figure 13:Engine Compartment . . . . . . . . . . . . . . . . . .36
Figure 14:Control Box With Service Door Open . . . . .39
Figure 15:Control Box With Control Box Door Open . .40
Figure 16:Interface Board . . . . . . . . . . . . . . . . . . . . . .40
Figure 17:Remote Status Display (All LEDs Shown) . .41
Figure 18:Normal Operation No Alarms . . . . . . . . . . . .41
Figure 19:Check Alarm . . . . . . . . . . . . . . . . . . . . . . . .42
Figure 20:Shutdown Alarm . . . . . . . . . . . . . . . . . . . . .42
Figure 21:Remote Status Display with Fuel Level . . . .43
Figure 22:Remote Status Display
with Fuel Level and Temperature . . . . . . . . . . . . .43
Figure 23:SR-2 HMI Control Panel . . . . . . . . . . . . . . .47
Figure 24:Control Box With Service Door Open . . . . .48
Figure 25:Control Panel Display and Keys . . . . . . . . .49
Figure 26:Press On Key . . . . . . . . . . . . . . . . . . . . . . . .51
Figure 27:Turning Unit On Screen Sequence . . . . . . .52
Figure 28:Press Off Key . . . . . . . . . . . . . . . . . . . . . . . .53
Figure 29:Turning Unit Off Screen Sequence . . . . . . .53
List of Figures
8
Figure 30:Standard Display . . . . . . . . . . . . . . . . . . . . .54
Figure 31: Standard Display Variations . . . . . . . . . . . .55
Figure 32:Temperature Watch Display . . . . . . . . . . . . 56
Figure 33:Alarm Display . . . . . . . . . . . . . . . . . . . . . . . 57
Figure 34:Electric Power Receptacle . . . . . . . . . . . . . 60
Figure 35:Electric Standby Detected Screen . . . . . . . .61
Figure 36:Electric Motor Starting Screen . . . . . . . . . . . 62
Figure 37:Electric Standby Detected Screen . . . . . . . .63
Figure 38:Programming Electric Standby Screen . . . .63
Figure 39:Electric Standby Undetected Screen . . . . . .64
Figure 40:Programming Diesel Mode Screen . . . . . . .64
Figure 41:Changing Setpoint . . . . . . . . . . . . . . . . . . . . 65
Figure 42:Changing the Setpoint Screen Sequence . .67
Figure 43:Changing Mode . . . . . . . . . . . . . . . . . . . . . .69
Figure 44:Screen Sequence for Changing from
CYCLE-SENTRY Mode to Continuous Mode . . . .70
Figure 45:Screen Sequence for Changing from
Continuous Mode to CYCLE-SENTRY Mode . . . .70
Figure 46:Initiating a Manual Defrost Cycle . . . . . . . . . 71
Figure 47:Initiating Manual Defrost Screen Sequence 72
Figure 48:Viewing Gauges . . . . . . . . . . . . . . . . . . . . . 73
Figure 49:Viewing Gauges Screen Sequence . . . . . . .74
Figure 50:Viewing Sensors . . . . . . . . . . . . . . . . . . . . . 75
Figure 51:Viewing Sensors Screen Sequence (continued
on next page) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Figure 52:Viewing Sensors Screen Sequence (continued
from previous page) . . . . . . . . . . . . . . . . . . . . . . . 78
Figure 53:Accessing Main Menu . . . . . . . . . . . . . . . . 79
Figure 54:Main Menu Choices . . . . . . . . . . . . . . . . . . 80
Figure 55:Standard Display . . . . . . . . . . . . . . . . . . . . 82
Figure 56:Standard Display . . . . . . . . . . . . . . . . . . . . 83
Figure 57:Change Language Screen Sequence . . . . 84
Figure 58:Standard Display . . . . . . . . . . . . . . . . . . . . 85
Figure 59:Viewing and Clearing Alarms Screen Sequence
87
Figure 60:Standard Display . . . . . . . . . . . . . . . . . . . . 88
Figure 61:Start of Trip Screen Sequence . . . . . . . . . . 89
Figure 62:Printer Port Location . . . . . . . . . . . . . . . . . 90
Figure 63:Standard Display . . . . . . . . . . . . . . . . . . . . 91
Figure 64:Print Report Screen Sequence . . . . . . . . . 92
Figure 65:Standard Display . . . . . . . . . . . . . . . . . . . . 93
Figure 66:Viewing Hourmeters Screen Sequence
(continued on next page) . . . . . . . . . . . . . . . . . . . 94
Figure 67:Viewing Hourmeters Screen Sequence
(continued from previous page) . . . . . . . . . . . . . . 95
Figure 68:Standard Display . . . . . . . . . . . . . . . . . . . . 97
Figure 69:Selecting Mode Screen Sequence . . . . . . . 98
Figure 70:Standard Display . . . . . . . . . . . . . . . . . . . . 99
List of Figures
8
Figure 30:Standard Display . . . . . . . . . . . . . . . . . . . . .54
Figure 31: Standard Display Variations . . . . . . . . . . . .55
Figure 32:Temperature Watch Display . . . . . . . . . . . . 56
Figure 33:Alarm Display . . . . . . . . . . . . . . . . . . . . . . . 57
Figure 34:Electric Power Receptacle . . . . . . . . . . . . . 60
Figure 35:Electric Standby Detected Screen . . . . . . . .61
Figure 36:Electric Motor Starting Screen . . . . . . . . . . . 62
Figure 37:Electric Standby Detected Screen . . . . . . . .63
Figure 38:Programming Electric Standby Screen . . . .63
Figure 39:Electric Standby Undetected Screen . . . . . .64
Figure 40:Programming Diesel Mode Screen . . . . . . .64
Figure 41:Changing Setpoint . . . . . . . . . . . . . . . . . . . . 65
Figure 42:Changing the Setpoint Screen Sequence . .67
Figure 43:Changing Mode . . . . . . . . . . . . . . . . . . . . . .69
Figure 44:Screen Sequence for Changing from
CYCLE-SENTRY Mode to Continuous Mode . . . .70
Figure 45:Screen Sequence for Changing from
Continuous Mode to CYCLE-SENTRY Mode . . . .70
Figure 46:Initiating a Manual Defrost Cycle . . . . . . . . . 71
Figure 47:Initiating Manual Defrost Screen Sequence 72
Figure 48:Viewing Gauges . . . . . . . . . . . . . . . . . . . . . 73
Figure 49:Viewing Gauges Screen Sequence . . . . . . .74
Figure 50:Viewing Sensors . . . . . . . . . . . . . . . . . . . . . 75
Figure 51:Viewing Sensors Screen Sequence (continued
on next page) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Figure 52:Viewing Sensors Screen Sequence (continued
from previous page) . . . . . . . . . . . . . . . . . . . . . . . 78
Figure 53:Accessing Main Menu . . . . . . . . . . . . . . . . 79
Figure 54:Main Menu Choices . . . . . . . . . . . . . . . . . . 80
Figure 55:Standard Display . . . . . . . . . . . . . . . . . . . . 82
Figure 56:Standard Display . . . . . . . . . . . . . . . . . . . . 83
Figure 57:Change Language Screen Sequence . . . . 84
Figure 58:Standard Display . . . . . . . . . . . . . . . . . . . . 85
Figure 59:Viewing and Clearing Alarms Screen Sequence
87
Figure 60:Standard Display . . . . . . . . . . . . . . . . . . . . 88
Figure 61:Start of Trip Screen Sequence . . . . . . . . . . 89
Figure 62:Printer Port Location . . . . . . . . . . . . . . . . . 90
Figure 63:Standard Display . . . . . . . . . . . . . . . . . . . . 91
Figure 64:Print Report Screen Sequence . . . . . . . . . 92
Figure 65:Standard Display . . . . . . . . . . . . . . . . . . . . 93
Figure 66:Viewing Hourmeters Screen Sequence
(continued on next page) . . . . . . . . . . . . . . . . . . . 94
Figure 67:Viewing Hourmeters Screen Sequence
(continued from previous page) . . . . . . . . . . . . . . 95
Figure 68:Standard Display . . . . . . . . . . . . . . . . . . . . 97
Figure 69:Selecting Mode Screen Sequence . . . . . . . 98
Figure 70:Standard Display . . . . . . . . . . . . . . . . . . . . 99
List of Figures
9
Figure 71:Mode Menu Display . . . . . . . . . . . . . . . . . . 99
Figure 72:Keypad Lockout Display . . . . . . . . . . . . . . 100
Figure 73:Standard Display . . . . . . . . . . . . . . . . . . . 101
Figure 74:Selecting Sleep Mode Screen Sequence . 103
Figure 75:Standard Display . . . . . . . . . . . . . . . . . . . 106
Figure 76:No Pretrip Alarm Active Display . . . . . . . . 106
Figure 77:Pretrip Test Screen Sequence . . . . . . . . . 108
Figure 78:Standard Display . . . . . . . . . . . . . . . . . . . 109
Figure 79:Programming Diesel Mode . . . . . . . . . . . . 110
Figure 80:Programming Electric Standby Mode . . . . 111
Figure 81:Standard Display . . . . . . . . . . . . . . . . . . . 112
Figure 82:Adjusting Display Brightness Screen Sequence
113
Figure 83:Time and Date Screens . . . . . . . . . . . . . . 114
Figure 84:Standard Display with Product Soft Key . . 115 Figure 85:Standard Display with
Product/Setpoint Soft Key . . . . . . . . . . . . . . . . . 116
Figure 86:Selecting Named Product . . . . . . . . . . . . . 117
Figure 87:Selecting or Changing Named Product Screen
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Figure 88:Selecting Setpoint for Named Product Screen
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Figure 89:Changing Setpoint for Named Product . . . 122 Figure 90:Changing Setpoint for Named Product Screen
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124
Figure 91:Selecting or Changing Setpoint . . . . . . . . .125
Figure 92:Selecting or Changing Numeric Setpoint
Screen Sequence . . . . . . . . . . . . . . . . . . . . . . . .127
Figure 93:Rear Remote Control Panel . . . . . . . . . . . .129
Figure 94:Rear Remote Control Panel Display . . . . .131
Figure 95:Unit HMI Control Panel Display . . . . . . . . .131
Figure 96:Press Select Key . . . . . . . . . . . . . . . . . . . .132
Figure 97:Rear Remote Control Panel . . . . . . . . . . . .133
Figure 98:Rear Remote Control Panel . . . . . . . . . . . .134
Figure 99:Remote Standard Display . . . . . . . . . . . . .135
Figure 100:Remote Lock Out Display . . . . . . . . . . . .135
Figure 101:Stand By Display . . . . . . . . . . . . . . . . . . .136
Figure 102:Standard Display . . . . . . . . . . . . . . . . . . .136
Figure 103:Press Up or Down Arrow Keys . . . . . . . .137
Figure 104:Press Enter Key . . . . . . . . . . . . . . . . . . . .137
Figure 105:Press Select Key . . . . . . . . . . . . . . . . . . .138
Figure 106:Press Up or Down Arrow Keys . . . . . . . .138
Figure 107:Press Enter Key . . . . . . . . . . . . . . . . . . . .138
Figure 108:Press Select Key Twice . . . . . . . . . . . . . .139
Figure 109:Press Select Key Three Times . . . . . . . .140
Figure 110:Press Enter Key . . . . . . . . . . . . . . . . . . . .140
Figure 111:No Alarms Display . . . . . . . . . . . . . . . . . .140
Figure 112:Press Defrost Key . . . . . . . . . . . . . . . . . .141
List of Figures
9
Figure 71:Mode Menu Display . . . . . . . . . . . . . . . . . . 99
Figure 72:Keypad Lockout Display . . . . . . . . . . . . . . 100
Figure 73:Standard Display . . . . . . . . . . . . . . . . . . . 101
Figure 74:Selecting Sleep Mode Screen Sequence . 103
Figure 75:Standard Display . . . . . . . . . . . . . . . . . . . 106
Figure 76:No Pretrip Alarm Active Display . . . . . . . . 106
Figure 77:Pretrip Test Screen Sequence . . . . . . . . . 108
Figure 78:Standard Display . . . . . . . . . . . . . . . . . . . 109
Figure 79:Programming Diesel Mode . . . . . . . . . . . . 110
Figure 80:Programming Electric Standby Mode . . . . 111
Figure 81:Standard Display . . . . . . . . . . . . . . . . . . . 112
Figure 82:Adjusting Display Brightness Screen Sequence
113
Figure 83:Time and Date Screens . . . . . . . . . . . . . . 114
Figure 84:Standard Display with Product Soft Key . . 115 Figure 85:Standard Display with
Product/Setpoint Soft Key . . . . . . . . . . . . . . . . . 116
Figure 86:Selecting Named Product . . . . . . . . . . . . . 117
Figure 87:Selecting or Changing Named Product Screen
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Figure 88:Selecting Setpoint for Named Product Screen
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Figure 89:Changing Setpoint for Named Product . . . 122 Figure 90:Changing Setpoint for Named Product Screen
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124
Figure 91:Selecting or Changing Setpoint . . . . . . . . .125
Figure 92:Selecting or Changing Numeric Setpoint
Screen Sequence . . . . . . . . . . . . . . . . . . . . . . . .127
Figure 93:Rear Remote Control Panel . . . . . . . . . . . .129
Figure 94:Rear Remote Control Panel Display . . . . .131
Figure 95:Unit HMI Control Panel Display . . . . . . . . .131
Figure 96:Press Select Key . . . . . . . . . . . . . . . . . . . .132
Figure 97:Rear Remote Control Panel . . . . . . . . . . . .133
Figure 98:Rear Remote Control Panel . . . . . . . . . . . .134
Figure 99:Remote Standard Display . . . . . . . . . . . . .135
Figure 100:Remote Lock Out Display . . . . . . . . . . . .135
Figure 101:Stand By Display . . . . . . . . . . . . . . . . . . .136
Figure 102:Standard Display . . . . . . . . . . . . . . . . . . .136
Figure 103:Press Up or Down Arrow Keys . . . . . . . .137
Figure 104:Press Enter Key . . . . . . . . . . . . . . . . . . . .137
Figure 105:Press Select Key . . . . . . . . . . . . . . . . . . .138
Figure 106:Press Up or Down Arrow Keys . . . . . . . .138
Figure 107:Press Enter Key . . . . . . . . . . . . . . . . . . . .138
Figure 108:Press Select Key Twice . . . . . . . . . . . . . .139
Figure 109:Press Select Key Three Times . . . . . . . .140
Figure 110:Press Enter Key . . . . . . . . . . . . . . . . . . . .140
Figure 111:No Alarms Display . . . . . . . . . . . . . . . . . .140
Figure 112:Press Defrost Key . . . . . . . . . . . . . . . . . .141
List of Figures
10
Figure 113:Press Enter Key . . . . . . . . . . . . . . . . . . . 141
Figure 114:Defrost Icon Displayed . . . . . . . . . . . . . . 141
Figure 115:Press TK Logo Key . . . . . . . . . . . . . . . . . 142
Figure 116:Press Enter Key . . . . . . . . . . . . . . . . . . . 142
Figure 117:Press Pretrip Key . . . . . . . . . . . . . . . . . . 143
Figure 118:Press Enter Key . . . . . . . . . . . . . . . . . . . 143
Figure 119:Pretrip Display . . . . . . . . . . . . . . . . . . . . . 144
Figure 120:Pass Pretrip Display . . . . . . . . . . . . . . . .144
Figure 121:Log Alarms Screen . . . . . . . . . . . . . . . . . 145
Figure 122:Alarm Display . . . . . . . . . . . . . . . . . . . . . 146
Figure 123:Shutdown Alarm Display . . . . . . . . . . . . . 147
Figure 124:Loading Considerations . . . . . . . . . . . . . . 166
Figure 125:Unit Battery . . . . . . . . . . . . . . . . . . . . . . . 172
Figure 126:Sequence for Connecting Jumper Cables . . .
172
Figure 127:Unit Engine . . . . . . . . . . . . . . . . . . . . . . .173
Figure 128:Sequence for Disconnecting Jumper Cables
174 Figure 129:Compressor Serial Number Location . . . 202
Figure 130:Engine Serial Number Location . . . . . . . . 202
Figure 131:Unit Serial Number Plate Locations
(on the bulkhead above compressor inside
curbside door and on roadside of evaporator) . .203
Figure 132:Unit Serial Number Plate . . . . . . . . . . . . .203
List of Figures
10
Figure 113:Press Enter Key . . . . . . . . . . . . . . . . . . . 141
Figure 114:Defrost Icon Displayed . . . . . . . . . . . . . . 141
Figure 115:Press TK Logo Key . . . . . . . . . . . . . . . . . 142
Figure 116:Press Enter Key . . . . . . . . . . . . . . . . . . . 142
Figure 117:Press Pretrip Key . . . . . . . . . . . . . . . . . . 143
Figure 118:Press Enter Key . . . . . . . . . . . . . . . . . . . 143
Figure 119:Pretrip Display . . . . . . . . . . . . . . . . . . . . . 144
Figure 120:Pass Pretrip Display . . . . . . . . . . . . . . . .144
Figure 121:Log Alarms Screen . . . . . . . . . . . . . . . . . 145
Figure 122:Alarm Display . . . . . . . . . . . . . . . . . . . . . 146
Figure 123:Shutdown Alarm Display . . . . . . . . . . . . . 147
Figure 124:Loading Considerations . . . . . . . . . . . . . . 166
Figure 125:Unit Battery . . . . . . . . . . . . . . . . . . . . . . . 172
Figure 126:Sequence for Connecting Jumper Cables . . .
172
Figure 127:Unit Engine . . . . . . . . . . . . . . . . . . . . . . .173
Figure 128:Sequence for Disconnecting Jumper Cables
174 Figure 129:Compressor Serial Number Location . . . 202
Figure 130:Engine Serial Number Location . . . . . . . . 202
Figure 131:Unit Serial Number Plate Locations
(on the bulkhead above compressor inside
curbside door and on roadside of evaporator) . .203
Figure 132:Unit Serial Number Plate . . . . . . . . . . . . .203
11
Introduction
There is nothing complicated about operating and maintaining
your Thermo King unit, but a few minutes studying this
manual will be time well spent.
Performing pre-trip checks and enroute inspections on a
regular basis will minimize on-the-road operating problems . A
regular maintenance program will also help to keep your unit
in top operating condition. If factory recommended procedures
are followed, you will find that you have purchased the most
efficient and dependable temperature control system available.
All service requirements, major and minor, should be handled
by a Thermo King dealer for four very important reasons:
They are equipped with the factory recommended tools to perform all service functions
They have factory trained and certified technicians
They have genuine Thermo King replacement parts
The warranty on your new unit is valid only when the repair and replacement of component parts is performed by an authorized Thermo King dealer.
IMPORTANT: This manual is published for informational purposes only and the information furnished herein should not be considered as all-inclusive or meant to cover all contingencies. If more information is required, consult your Thermo King Service Directory for the location and telephone number of the local dealer.
11
Introduction
There is nothing complicated about operating and maintaining your Thermo King unit, but a few minutes studying this manual will be time well spent.
Performing pre-trip checks and enroute inspections on a regular basis will minimize on-the-road operating problems . A regular maintenance program will also help to keep your unit in top operating condition. If factory recommended procedures are followed, you will find that you have purchased the most efficient and dependable temperature control system available.
All service requirements, major and minor, should be handled by a Thermo King dealer for four very important reasons:
They are equipped with the factory recommended tools to perform all service functions
They have factory trained and certified technicians
They have genuine Thermo King replacement parts
The warranty on your new unit is valid only when the repair and replacement of component parts is performed by an authorized Thermo King dealer.
IMPORTANT: This manual is published for informational purposes only and the information furnished herein should not be considered as all-inclusive or meant to cover all contingencies. If more information is required, consult your Thermo King Service Directory for the location and telephone number of the local dealer.
Introduction
12
Introduction
12
13
Safety Precautions
Thermo King recommends that servicing be done only by a Thermo King dealer. However , you should be aware of several safety practices. This chapter gives basic safety precautions for working with Thermo King units and describes the safety stickers on your unit that you should be familiar with.
General Safety Practices
DANGER: NEVER operate the unit with the compressor discharge valve closed. Doing so could cause the compressor to explode, causing death or serious injury.
WARNING: Always wear goggles or safety glasses when working with or around the refrigeration system or battery. Refrigerant or battery acid can cause permanent damage if it comes in contact with your eyes.
WARNING: Keep hands and loose clothing clear of fans and belts at all times when the unit is operating or when opening or closing compressor service valves.
WARNING: Exposed coil fins can cause painful lacerations. Service work on the evaporator or condenser coils should be done by a certified Thermo King technician.
WARNING: Do not apply heat to a closed cooling system. Before applying heat to a cooling system, drain it. Then flush it with water and drain the water. Antifreeze contains water and ethylene glycol. The ethylene glycol is flammable and can ignite if the antifreeze is heated enough to boil off the water.
13
Safety Precautions
Thermo King recommends that servicing be done only by a Thermo King dealer. However , you should be aware of several safety practices. This chapter gives basic safety precautions for working with Thermo King units and describes the safety stickers on your unit that you should be familiar with.
General Safety Practices
DANGER: NEVER operate the unit with the compressor discharge valve closed. Doing so could cause the compressor to explode, causing death or serious injury.
WARNING: Always wear goggles or safety glasses when working with or around the refrigeration system or battery. Refrigerant or battery acid can cause permanent damage if it comes in contact with your eyes.
WARNING: Keep hands and loose clothing clear of fans and belts at all times when the unit is operating or when opening or closing compressor service valves.
WARNING: Exposed coil fins can cause painful lacerations. Service work on the evaporator or condenser coils should be done by a certified Thermo King technician.
WARNING: Do not apply heat to a closed cooling system. Before applying heat to a cooling system, drain it. Then flush it with water and drain the water. Antifreeze contains water and ethylene glycol. The ethylene glycol is flammable and can ignite if the antifreeze is heated enough to boil off the water.
Safety Precautions
14
Automatic Start/Stop Operation
This unit is capable of automatic operation and could start at any time without warning.
Electrical Hazard
Refrigerant
Although fluorocarbon refrigerants are classified as safe, use caution when working with refrigerants or in areas where they are being used.
CAUTION: Use extreme caution when drilling holes in the unit. Drilling into electrical wiring or refrigerant lines could cause a fire. Do not drill into structural components.
WARNING: The unit can start at any time without warning. Press the O
FF
key on the HMI control panel and place the microprocessor On/Off switch in the Off position before inspecting or servicing any part of the unit.
CAUTION: Turn off the high voltage power supply and disconnect the electric cable before working on the unit. Units with electric standby present a potential electrical hazard.
DANGER: Fluorocarbon refrigerants can produce toxic gases. In the presence of an open flame or electrical short, these gases are severe respiratory irritants CAPABLE OF CAUSING DEATH.
DANGER: Fluorocarbon refrigerants tend to displace air and can cause oxygen depletion which could result in DEA TH BY SUFFOCA TION. Provide adequate ventilation in enclosed or confined areas.
WARNING: Fluorocarbon refrigerants evaporate rapidly, freezing anything they contact if accidentally released into the atmosphere from the liquid state.
Safety Precautions
14
Automatic Start/Stop Operation
This unit is capable of automatic operation and could start at any time without warning.
Electrical Hazard
Refrigerant
Although fluorocarbon refrigerants are classified as safe, use caution when working with refrigerants or in areas where they are being used.
CAUTION: Use extreme caution when drilling holes in the unit. Drilling into electrical wiring or refrigerant lines could cause a fire. Do not drill into structural components.
WARNING: The unit can start at any time without warning. Press the O
FF
key on the HMI control panel and place the microprocessor On/Off switch in the Off position before inspecting or servicing any part of the unit.
CAUTION: Turn off the high voltage power supply and disconnect the electric cable before working on the unit. Units with electric standby present a potential electrical hazard.
DANGER: Fluorocarbon refrigerants can produce toxic gases. In the presence of an open flame or electrical short, these gases are severe respiratory irritants CAPABLE OF CAUSING DEATH.
DANGER: Fluorocarbon refrigerants tend to displace air and can cause oxygen depletion which could result in DEA TH BY SUFFOCA TION. Provide adequate ventilation in enclosed or confined areas.
WARNING: Fluorocarbon refrigerants evaporate rapidly, freezing anything they contact if accidentally released into the atmosphere from the liquid state.
Safety Precautions
15
Refrigerant Oil
Observe the following precautions when working with or around refrigerant oil:
First Aid
First Aid–Refrigerant
Eyes: For contact with liquid, immediately flush eyes with
large amounts of water. Get prompt medical attention.
Skin: Flush areas with large amounts of warm water. Do not apply heat. Wrap burns with dry, sterile, bulky dressing to protect from infection or injury. Get prompt medical attention.
Inhalation: Move victim to fresh air and restore breathing if necessary. Stay with victim until emergency personnel arrive.
First Aid–Refrigerant Oil
Eyes: Immediately flush eyes with large amounts of water for
at least 15 minutes while holding the eyelids open. Get prompt medical attention.
Skin: Remove contaminated clothing. Wash thoroughly with soap and water. Get medical attention if irritation persists.
Inhalation: Move victim to fresh air and restore breathing if necessary. Stay with victim until emergency personnel arrive.
Ingestion: Do not induce vomiting. Immediately contact local poison control center or physician.
WARNING: Always wear goggles or safety glasses to protect eyes from refrigerant oil contact.
WARNING: Protect skin and clothing from prolonged or repeated contact with refrigerant oil. Rubber gloves are recommended.
WARNING: W ash thoroughly immediately after handling refrigerant oil to prevent irritation.
Safety Precautions
15
Refrigerant Oil
Observe the following precautions when working with or around refrigerant oil:
First Aid
First Aid–Refrigerant
Eyes: For contact with liquid, immediately flush eyes with
large amounts of water. Get prompt medical attention.
Skin: Flush areas with large amounts of warm water. Do not apply heat. Wrap burns with dry, sterile, bulky dressing to protect from infection or injury. Get prompt medical attention.
Inhalation: Move victim to fresh air and restore breathing if necessary. Stay with victim until emergency personnel arrive.
First Aid–Refrigerant Oil
Eyes: Immediately flush eyes with large amounts of water for
at least 15 minutes while holding the eyelids open. Get prompt medical attention.
Skin: Remove contaminated clothing. Wash thoroughly with soap and water. Get medical attention if irritation persists.
Inhalation: Move victim to fresh air and restore breathing if necessary. Stay with victim until emergency personnel arrive.
Ingestion: Do not induce vomiting. Immediately contact local poison control center or physician.
WARNING: Always wear goggles or safety glasses to protect eyes from refrigerant oil contact.
WARNING: Protect skin and clothing from prolonged or repeated contact with refrigerant oil. Rubber gloves are recommended.
WARNING: W ash thoroughly immediately after handling refrigerant oil to prevent irritation.
Safety Precautions
16
Safety Decals and Locations
Figure 1: ELC (Extended Life Coolant) Nameplate
(Located on expansion tank in units
equipped with ELC)
Figure 2: Belt Warning
(Located on condenser housing)
Figure 3: Belt Replacement Caution
(Located on condenser housing)
AJA1947
AKB65
AKB66
Safety Precautions
16
Safety Decals and Locations
Figure 1: ELC (Extended Life Coolant) Nameplate
(Located on expansion tank in units
equipped with ELC)
Figure 2: Belt Warning
(Located on condenser housing)
Figure 3: Belt Replacement Caution
(Located on condenser housing)
AJA1947
AKB65
AKB66
Safety Precautions
17
Figure 4: Automatic Start Caution
(Locations vary depending on model. Decals are
located near areas that contain moving parts which
can cause severe injuries if hands or clothing become
tangled when unit automatically starts.)
Figure 5: Fan Caution
(Locations vary depending on model. Decals are
located near areas that contain f ans which can cause
severe injuries when unit automatically starts.)
AKB67 AKB68
Safety Precautions
17
Figure 4: Automatic Start Caution
(Locations vary depending on model. Decals are
located near areas that contain moving parts which
can cause severe injuries if hands or clothing become
tangled when unit automatically starts.)
Figure 5: Fan Caution
(Locations vary depending on model. Decals are
located near areas that contain f ans which can cause
severe injuries when unit automatically starts.)
AKB67 AKB68
Safety Precautions
18
Figure 6: Door Latch Warning
(Located on curbside door)
WARNING
ATENCIÓN
NEW DOOR LATCH DESIGN
REQUIRES DOOR TO BE SLAMMED
SHUT BEFORE MOVING TRAILER.
FAILURE TO CLOSE DOOR FIRMLY CAN ALLOW WIND TO TEAR DOOR
FROM REFRIGERATION UNIT AND
CAUSE INJURY TO OTHERS.
NUEVO DESEÑO DE CERRADURA
REQUIERE ASOTAR LA PUERTA ANTES
DE CONDUCIR EL TRAILER.
AL NO CERRAR LA PUERTA CON
FIRMEZA EL VIENTO PODRÍA
DESPRENDER LA PUERTA DE LA
UNIDAD DE REFRIGERACIÓN Y
CAUSAR DAÑOS A OTROS.
AEA2422
Safety Precautions
18
Figure 6: Door Latch Warning
(Located on curbside door)
WARNING
ATENCIÓN
NEW DOOR LATCH DESIGN
REQUIRES DOOR TO BE SLAMMED
SHUT BEFORE MOVING TRAILER.
FAILURE TO CLOSE DOOR FIRMLY CAN ALLOW WIND TO TEAR DOOR
FROM REFRIGERATION UNIT AND
CAUSE INJURY TO OTHERS.
NUEVO DESEÑO DE CERRADURA
REQUIERE ASOTAR LA PUERTA ANTES
DE CONDUCIR EL TRAILER.
AL NO CERRAR LA PUERTA CON
FIRMEZA EL VIENTO PODRÍA
DESPRENDER LA PUERTA DE LA
UNIDAD DE REFRIGERACIÓN Y
CAUSAR DAÑOS A OTROS.
AEA2422
19
EPA Emission Control System Warranty Statement
Thermo King warrants to the initial owner and each subsequent owner that the certified, non-road diesel engine in your unit is:
1. Designed, built and equipped so as to conform, at the time of sale, with all applicable regulations adopted by the United States Environmental Protection Agency (EPA).
2. Free from defects in materials and workmanship in specific emission related parts for a period of five years or 3,000 hours of operation, whichever comes first, after date of delivery to the initial owner.
If an emission-related part or component fails during the warranty period, it will be repaired or replaced. Any such part or component repaired or replaced under warranty is warranted for the warranty period.
During the term of this warranty, Thermo King will provide, through a Thermo King authorized service dealer or other establishment authorized by Thermo King, repair or replacement of any warranted part at no charge to the non-road engine owner.
In emergency, repairs may be performed at any service establishment, or by the owner, using any replacement part. Thermo King will reimburse the owner for their expenses, including diagnostic charges for such emergency repair. These expenses shall not exceed Thermo King’ s suggested retail price for all warranted parts replaced, and labor changes based on Thermo King’s recommended time allowance for the warranty repair and the geographically appropriate hourly labor rate.
19
EPA Emission Control System Warranty Statement
Thermo King warrants to the initial owner and each subsequent owner that the certified, non-road diesel engine in your unit is:
1. Designed, built and equipped so as to conform, at the time of sale, with all applicable regulations adopted by the United States Environmental Protection Agency (EPA).
2. Free from defects in materials and workmanship in specific emission related parts for a period of five years or 3,000 hours of operation, whichever comes first, after date of delivery to the initial owner.
If an emission-related part or component fails during the warranty period, it will be repaired or replaced. Any such part or component repaired or replaced under warranty is warranted for the warranty period.
During the term of this warranty, Thermo King will provide, through a Thermo King authorized service dealer or other establishment authorized by Thermo King, repair or replacement of any warranted part at no charge to the non-road engine owner.
In emergency, repairs may be performed at any service establishment, or by the owner, using any replacement part. Thermo King will reimburse the owner for their expenses, including diagnostic charges for such emergency repair. These expenses shall not exceed Thermo King’ s suggested retail price for all warranted parts replaced, and labor changes based on Thermo King’s recommended time allowance for the warranty repair and the geographically appropriate hourly labor rate.
EPA Emission Control System Warranty Statement
20
Any replacement part can be used for maintenance or repairs. The owner should ensure that such parts are equivalent in design and durability to genuine Thermo King parts. However, Thermo King is not liable for parts that are not genuine Thermo King parts.
A part not being available within 30 days or repair not being completed within 30 days constitutes an emergency.
As a condition of reimbursement, replaced parts and received invoices must be presented at a place of business of a Thermo King authorized service dealer or other establishment authorized by Thermo King.
This warranty covers the following emission-related parts and components:
Fuel Injection System
Intake Manifold
Exhaust Manifold
Miscellaneous hoses, clamps, connectors and sealing devices used in the above systems.
If failure of one of these parts or components results in failure of another part or component, both will be covered by this warranty.
Responsibilities
This warranty is subject to the following:
Thermo King Corporation Responsibilities
During the emission warranty period, if a defect in material or workmanship of a warranted part or component is found, Thermo King will provide:
New, remanufactured, or repaired parts or components required to correct the defect.
NOTE: Items replaced under this warranty become the property of Thermo King.
Labor, during normal working hours, required to make the warranty repair. This includes diagnosis and labor to remove and install the engine, if necessary.
EPA Emission Control System Warranty Statement
20
Any replacement part can be used for maintenance or repairs. The owner should ensure that such parts are equivalent in design and durability to genuine Thermo King parts. However, Thermo King is not liable for parts that are not genuine Thermo King parts.
A part not being available within 30 days or repair not being completed within 30 days constitutes an emergency.
As a condition of reimbursement, replaced parts and received invoices must be presented at a place of business of a Thermo King authorized service dealer or other establishment authorized by Thermo King.
This warranty covers the following emission-related parts and components:
Fuel Injection System
Intake Manifold
Exhaust Manifold
Miscellaneous hoses, clamps, connectors and sealing devices used in the above systems.
If failure of one of these parts or components results in failure of another part or component, both will be covered by this warranty.
Responsibilities
This warranty is subject to the following:
Thermo King Corporation Responsibilities
During the emission warranty period, if a defect in material or workmanship of a warranted part or component is found, Thermo King will provide:
New, remanufactured, or repaired parts or components required to correct the defect.
NOTE: Items replaced under this warranty become the property of Thermo King.
Labor, during normal working hours, required to make the warranty repair. This includes diagnosis and labor to remove and install the engine, if necessary.
EPA Emission Control System Warranty Statement
21
Owner Responsibilities
During the emission warranty period, the owner is responsible for:
The performance of all required maintenance. A warranty claim will not be denied because the scheduled maintenance was not performed. However, if the lack of required maintenance was the reason for the repair, then the claim will be denied.
Premium of overtime cost.
Cost to investigate complaints that are not caused by defects in Thermo King material or workmanship.
Providing timely notice of a warrantable failure and promptly making the product available for repair.
Limitations
Thermo King is not responsible for resultant damages to an emission-related part or component resulting from:
Any application or installation Thermo King deems improper as explained in this Operator’s Manual, or any other manuals provided for the unit.
Attachments, accessory items, or parts not authorized for use by Thermo King.
Improper off-road engine maintenance, repair or abuse.
Owners unreasonable delay in making the product available after being notified of a potential product problem.
This warranty is in addition to Thermo King’s standard warranty applicable to the off-road engine product involved.
Remedies under this warranty are limited to the provision of material and services as specified herein. Thermo King is not responsible for incidental or consequential damages such as downtime or loss of engine powered equipment.
EPA Emission Control System Warranty Statement
21
Owner Responsibilities
During the emission warranty period, the owner is responsible for:
The performance of all required maintenance. A warranty claim will not be denied because the scheduled maintenance was not performed. However, if the lack of required maintenance was the reason for the repair, then the claim will be denied.
Premium of overtime cost.
Cost to investigate complaints that are not caused by defects in Thermo King material or workmanship.
Providing timely notice of a warrantable failure and promptly making the product available for repair.
Limitations
Thermo King is not responsible for resultant damages to an emission-related part or component resulting from:
Any application or installation Thermo King deems improper as explained in this Operator’s Manual, or any other manuals provided for the unit.
Attachments, accessory items, or parts not authorized for use by Thermo King.
Improper off-road engine maintenance, repair or abuse.
Owner’s unreasonable delay in making the product available after being notified of a potential product problem.
This warranty is in addition to Thermo King’s standard warranty applicable to the off-road engine product involved.
Remedies under this warranty are limited to the provision of material and services as specified herein. Thermo King is not responsible for incidental or consequential damages such as downtime or loss of engine powered equipment.
EPA Emission Control System Warranty Statement
22
EPA Emission Control System Warranty Statement
22
23
Unit Description
Unit Overview
The Thermo King SB-210+/310+ is a one piece, self-contained, diesel powered, air cooling/heating unit operating under the control of a SMART REEFER 2 (SR-2) programmable microprocessor controller. The unit mounts on the front of the trailer with the evaporator extending through an opening in the front wall.
The SB-210+/310+ features cooling and heating using a quiet running engine from the Thermo King TK486 engine family.
The SB-210+ and SB-310+ are available in the following three models:
SB-210+ 30: Cooling and heating on diesel engine operation.
SB-210+ 50: Cooling and heating on diesel engine operation and electric standby operation.
SB-310+ 30: High capacity cooling and heating on diesel engine operation. Designed for engine operation at a high speed of 2600 rpm.
The Electronic Throttling Valve (ETV) provides enhanced control of the refrigeration system. The ETV is optional on the SB-210+ and standard on the SB-310+. See “Electronic Throttling Valve” on page 28.
Figure 7: Front View
23
Unit Description
Unit Overview
The Thermo King SB-210+/310+ is a one piece, self-contained, diesel powered, air cooling/heating unit operating under the control of a SMART REEFER 2 (SR-2) programmable microprocessor controller. The unit mounts on the front of the trailer with the evaporator extending through an opening in the front wall.
The SB-210+/310+ features cooling and heating using a quiet running engine from the Thermo King TK486 engine family.
The SB-210+ and SB-310+ are available in the following three models:
SB-210+ 30: Cooling and heating on diesel engine operation.
SB-210+ 50: Cooling and heating on diesel engine operation and electric standby operation.
SB-310+ 30: High capacity cooling and heating on diesel engine operation. Designed for engine operation at a high speed of 2600 rpm.
The Electronic Throttling Valve (ETV) provides enhanced control of the refrigeration system. The ETV is optional on the SB-210+ and standard on the SB-310+. See “Electronic Throttling Valve” on page 28.
Figure 7: Front View
Unit Description
24
In addition to the quiet TK486 engine, the SB-210+/310+ includes other sound deadening components as standard and optional equipment. Among them are a special exhaust system, sound-proof insulation, special door gaskets and sound-absorbing doors. See the Design Features list below.
Design Features
The following chart lists key design features and options.
Standard Features Option/Factory installed ❏ Option/Dealer Installed
SB-210+/310+ Key Features & Options
SB-210+
Model
30
SB-210+
Model
50
SB-310+
Model
30
SMART REEFER SR-2 Controller
●●●
OptiSet™ Plus with FreshSet™ Programmable Modes
●●●
ETV (Electronic Throttling Valve)
❍❍
ServiceWatch Data Logger
●●●
CargoWatch™ Data Logger
●●●
CargoWatch Accessories:
• Door Switches / ❏❍ / ❏❍ /
• Temperature Sensor Kits
/ ❏❍ / ❏❍ / ❏
EMI-3000
●●●
High-Capacity Condenser Coil
●●●
Whisper Quiet Technology
❍❍❍
Easy-access door design
●●●
Composite Exterior Panels
●●●
SB-210+/310+ Key Features & Options
SB-210+
Model
30
SB-210+
Model
50
SB-310+
Model
30
Unit Description
24
In addition to the quiet TK486 engine, the SB-210+/310+ includes other sound deadening components as standard and optional equipment. Among them are a special exhaust system, sound-proof insulation, special door gaskets and sound-absorbing doors. See the Design Features list below.
Design Features
The following chart lists key design features and options.
Standard FeaturesOption/Factory installedOption/Dealer Installed
SB-210+/310+ Key Features & Options
SB-210+
Model
30
SB-210+
Model
50
SB-310+
Model
30
SMART REEFER SR-2 Controller
●●●
OptiSet™ Plus with FreshSet™ Programmable Modes
●●●
ETV (Electronic Throttling Valve)
❍❍●
ServiceWatch™ Data Logger
●●●
CargoWatch™ Data Logger
●●●
CargoWatch™ Accessories:
• Door Switches / ❏❍ / ❏❍ /
• Temperature Sensor Kits
/ ❏❍ / ❏❍ / ❏
EMI-3000
●●●
High-Capacity Condenser Coil
●●●
Whisper Quiet Technology
❍❍❍
Easy-access door design
●●●
Composite Exterior Panels
●●●
SB-210+/310+ Key Features & Options
SB-210+
Model
30
SB-210+
Model
50
SB-310+
Model
30
Unit Description
25
Long-Life Coolant/Silicone Hoses
●●●
Remote Status Display
/ ❏❍ / ❏❍ /
Remote Status Display with Fuel Level
❏❏
Remote Status Display with Fuel Level and Temperature
❏❏
Standard Unit Color White
●●●
Standard Grille Color Black
●●●
Directional Air Delivery
●●●
Vibration Isolation System
●●●
Aluminum Undermount Fuel Tank 50 Gal. (186 Liter)
●●●
Fuel Level Sensor
●●●
Fuel Heater
❍❍❍
SB-210+/310+ Key Features & Options
SB-210+
Model
30
SB-210+
Model
50
SB-310+
Model
30
Frost Plug Heater
❍❍❍
Alternator, 65 Amp, 12 Vdc
❍❍❍
24 Horsepower Electric Motor
Special Color Grills
❍❍❍
Fresh Air Exchange
❍❍❍
i-Box™ Interface
/ ❏❍ / ❏❍ /
PrimAirbulkhead and duct system
❏❏❏
Rear Remote Control
❏❏❏
Humidity Sensor ❏❏❏ Megatech Battery,
12 Volt, Wet Cell
❏❏❏
EON Battery, 12 Volt, Dry Cell
❏❏❏
SB-210+/310+ Key Features & Options
SB-210+
Model
30
SB-210+
Model
50
SB-310+
Model
30
Unit Description
25
Long-Life Coolant/Silicone Hoses
●●●
Remote Status Display
/ ❏❍ / ❏❍ / ❏
Remote Status Display with Fuel Level
❏❏❏
Remote Status Display with Fuel Level and Temperature
❏❏❏
Standard Unit Color White
●●●
Standard Grille Color Black
●●●
Directional Air Delivery
●●●
Vibration Isolation System
●●●
Aluminum Undermount Fuel Tank 50 Gal. (186 Liter)
●●●
Fuel Level Sensor
●●●
Fuel Heater
❍❍❍
SB-210+/310+ Key Features & Options
SB-210+
Model
30
SB-210+
Model
50
SB-310+
Model
30
Frost Plug Heater
❍❍❍
Alternator, 65 Amp, 12 Vdc
❍❍❍
24 Horsepower Electric Motor
Special Color Grills
❍❍❍
Fresh Air Exchange
❍❍❍
i-Box™ Interface
/ ❏❍ / ❏❍ / ❏
PrimAirbulkhead and duct system
❏❏❏
Rear Remote Control
❏❏❏
Humidity Sensor ❏❏❏ Megatech Battery,
12 Volt, Wet Cell
❏❏❏
EON Battery, 12 Volt, Dry Cell
❏❏❏
SB-210+/310+ Key Features & Options
SB-210+
Model
30
SB-210+
Model
50
SB-310+
Model
30
Unit Description
26
Diesel Engine
The Thermo King TK486 family of engines are 4-cylinder, water cooled, direct injection diesel engines. The engine is coupled directly to the compressor on the Model 30. A centrifugal clutch transfers power from the engine to the compressor on the Model 50. Belts transmit power to the unit fans, alternator and water pump.
The SB-210+ uses a TK486V (Tier2), which is designed to run with a high speed of 2200 rpm.
The SB-310+ uses a TK486VH (Tier2), which is designed to run with a high speed of 2600 rpm.
Figure 8: TK486V (TK486VH is Similar) Tier 2
Unit Description
26
Diesel Engine
The Thermo King TK486 family of engines are 4-cylinder, water cooled, direct injection diesel engines. The engine is coupled directly to the compressor on the Model 30. A centrifugal clutch transfers power from the engine to the compressor on the Model 50. Belts transmit power to the unit fans, alternator and water pump.
The SB-210+ uses a TK486V (Tier2), which is designed to run with a high speed of 2200 rpm.
The SB-310+ uses a TK486VH (Tier2), which is designed to run with a high speed of 2600 rpm.
Figure 8: TK486V (TK486VH is Similar) Tier 2
Unit Description
27
ELC (Extended Life Coolant)
ELC (Extended Life Coolant) is standard equipment. The maintenance interval for ELC is five years or 12,000 hours. A nameplate on the coolant expansion tank identifies units with ELC (see “Safety Decals and Locations”). The new engine coolant, Chevron Extended Life Coolant, is RED in color instead of the previous GREEN or BLUE-GREEN colored conventional coolants.
NOTE: The use of 50/50% pre-mixed ELC is recommended to assure that de-ionized water is being used. If 100% full strength concentrate is used, de-ionized or distilled water is recommended instead of tap water to insure the integrity of the cooling system is maintained.
EMI 3000
EMI 3000 is an extended maintenance interval package. It is standard equipment. The EMI 3000 package consists of the following key components:
EMI 3000-Hour Cyclonic Air Cleaner Assembly and Air Cleaner Element
EMI 3000-Hour Fuel Filter (black with gold lettering)
EMI 3000-Hour Dual Element Oil Filter (black with gold lettering)
API Rating CI-4 Mineral Oil
Five Year or 12,000 Hour ELC (Extended Life Coolant)
The EMI package allows standard maintenance intervals to be extended to 3,000 hours, or 2 years, whichever occurs first.
NOTE: Units equipped with the EMI 3000 package do require regular inspection in accordance with Thermo King's maintenance recommendations.
NOTE: The new EMI 3000 oil filters and new EMI 3000 air cleaners are NOT interchangeable with the older style oil filters and air cleaners.
CAUTION: Do not add “GREEN” or “BLUE-GREEN” conventional coolant to cooling systems using “RED” Extended Life Coolant, except in an emergency. If conventional coolant is added to Extended Life Coolant, the coolant must be changed after 2 years instead of 5 years.
Unit Description
27
ELC (Extended Life Coolant)
ELC (Extended Life Coolant) is standard equipment. The maintenance interval for ELC is five years or 12,000 hours. A nameplate on the coolant expansion tank identifies units with ELC (see “Safety Decals and Locations”). The new engine coolant, Chevron Extended Life Coolant, is RED in color instead of the previous GREEN or BLUE-GREEN colored conventional coolants.
NOTE: The use of 50/50% pre-mixed ELC is recommended to assure that de-ionized water is being used. If 100% full strength concentrate is used, de-ionized or distilled water is recommended instead of tap water to insure the integrity of the cooling system is maintained.
EMI 3000
EMI 3000 is an extended maintenance interval package. It is standard equipment. The EMI 3000 package consists of the following key components:
EMI 3000-Hour Cyclonic Air Cleaner Assembly and Air Cleaner Element
EMI 3000-Hour Fuel Filter (black with gold lettering)
EMI 3000-Hour Dual Element Oil Filter (black with gold lettering)
API Rating CI-4 Mineral Oil
Five Year or 12,000 Hour ELC (Extended Life Coolant)
The EMI package allows standard maintenance intervals to be extended to 3,000 hours, or 2 years, whichever occurs first.
NOTE: Units equipped with the EMI 3000 package do require regular inspection in accordance with Thermo King's maintenance recommendations.
NOTE: The new EMI 3000 oil filters and new EMI 3000 air cleaners are NOT interchangeable with the older style oil filters and air cleaners.
CAUTION: Do not add “GREEN” or “BLUE-GREEN” conventional coolant to cooling systems using “RED” Extended Life Coolant, except in an emergency. If conventional coolant is added to Extended Life Coolant, the coolant must be changed after 2 years instead of 5 years.
Unit Description
28
Thermo King X430L Reciprocating Compressor
The unit is equipped with a Thermo King X430L reciprocating compressor with 30 cu. in. (492 cm
3
) displacement.
Electronic Throttling Valve
The Electronic Throttling Valve (ETV) is optional on the SB-210+ and standard on the SB-310+.
The ETV provides enhanced control of the refrigeration system as follows:
Allows the refrigeration system to fully utilize the power capabilities of the engine under varying conditions
Provides an additional measure of protection against high discharge pressures
Protects the engine from high coolant temperature shutdowns
Provides a means of precise temperature control.
You can tell if the unit has an ETV by looking at the compressor. Units with an ETV have a suction valve adapter. Units without an ETV have a mechanical throttling valve.
1. Suction Valve Adapter (Has ETV)
2. Mechanical Throttling Valve (No ETV)
Figure 9: Compressors
1 2
Unit Description
28
Thermo King X430L Reciprocating Compressor
The unit is equipped with a Thermo King X430L reciprocating compressor with 30 cu. in. (492 cm
3
) displacement.
Electronic Throttling Valve
The Electronic Throttling Valve (ETV) is optional on the SB-210+ and standard on the SB-310+.
The ETV provides enhanced control of the refrigeration system as follows:
Allows the refrigeration system to fully utilize the power capabilities of the engine under varying conditions
Provides an additional measure of protection against high discharge pressures
Protects the engine from high coolant temperature shutdowns
Provides a means of precise temperature control.
You can tell if the unit has an ETV by looking at the compressor. Units with an ETV have a suction valve adapter. Units without an ETV have a mechanical throttling valve.
1. Suction Valve Adapter (Has ETV)
2. Mechanical Throttling Valve (No ETV)
Figure 9: Compressors
1 2
Unit Description
29
SMART REEFER 2 (SR-2) Control System
The SR-2 controller is a microprocessor control system designed for transport refrigeration. The SR-2 integrates the following functions: changing setpoint and operating mode, viewing gauge, sensor and hourmeter readings, initiating defrost cycles, and viewing and clearing alarms.
The microprocessor components are located inside the control box, which is located inside the lower roadside service door. The microprocessor is connected to an HMI (Human Machine Interface) Control Panel. It is used to operate the unit. The HMI control panel is mounted on the face of the control box. It is clearly visible through an opening in the lower roadside service door.
See “Operating Instructions” for more information about the SR-2 controller.
Depending on the air temperature in the trailer, as sensed by the microprocessor controller, the unit will typically operate in one of the following modes:
CYCLE-SENTRY Operation
High Speed Cool
Low Speed Cool
Null (Engine Off)
Low Speed Heat
High Speed Heat
•Defrost
Continuous Run Operation
High Speed Cool
Low Speed Cool
Low Speed Modulated Cool (Optional SB-210+)
Low Speed Modulated Heat (Optional SB-210+)
Low Speed Heat
High Speed Heat
•Defrost
Unit Description
29
SMART REEFER 2 (SR-2) Control System
The SR-2 controller is a microprocessor control system designed for transport refrigeration. The SR-2 integrates the following functions: changing setpoint and operating mode, viewing gauge, sensor and hourmeter readings, initiating defrost cycles, and viewing and clearing alarms.
The microprocessor components are located inside the control box, which is located inside the lower roadside service door. The microprocessor is connected to an HMI (Human Machine Interface) Control Panel. It is used to operate the unit. The HMI control panel is mounted on the face of the control box. It is clearly visible through an opening in the lower roadside service door.
See “Operating Instructions” for more information about the SR-2 controller.
Depending on the air temperature in the trailer, as sensed by the microprocessor controller, the unit will typically operate in one of the following modes:
CYCLE-SENTRY Operation
High Speed Cool
Low Speed Cool
Null (Engine Off)
Low Speed Heat
High Speed Heat
•Defrost
Continuous Run Operation
High Speed Cool
Low Speed Cool
Low Speed Modulated Cool (Optional SB-210+)
Low Speed Modulated Heat (Optional SB-210+)
Low Speed Heat
High Speed Heat
•Defrost
Loading...
+ 179 hidden pages