Thermo King SB-210+, SB-310+ Operator's Manual

Page 1
Operator’s Manual
Operator’s Manual
TK 53942-2-OP (Rev. 1, 11/09)
Page 2
Copyright© 2009 Thermo King Corp., Minneapolis, MN, USA
Printed in USA
SB-210+/SB-310+
TK 53942-2-OP (Rev. 1, 11/09)
Copyright© 2009 Thermo King Corp., Minneapolis, MN, USA
Printed in USA
SB-210+/SB-310+
TK 53942-2-OP (Rev. 1, 11/09)
Page 3
Disclaimer
This manual is published for informational purposes only. Thermo King Corporation makes no representations or warranties, express or implied, with respect to the information, recommendations and descriptions contained in this manual and such information, recommendations and descriptions should not be regarded as all-inclusive or covering all contingencies. If you have questions or require further information, please contact your local Thermo King dealer.
The procedures described herein should be undertaken only by qualified personnel. Failure to implement these procedures correctly may cause damage to the Thermo King unit or other property or personal injury.
Thermo King Corporation and its affiliates shall have no liability in contract or tort (including negligence and/or strict liability) or otherwise, to any person or entity for any personal injury, property damage or any other direct, indirect, special or consequential damage or liability whatsoever, arising out of or resulting from any actions by any person that are contrary to this manual or any of the information, recommendations or descriptions contained herein or the failure of any person to implement the procedures described herein correctly or to follow caution and safety decals located on the Thermo King unit.
Disclaimer
This manual is published for informational purposes only. Thermo King Corporation makes no representations or warranties, express or implied, with respect to the information, recommendations and descriptions contained in this manual and such information, recommendations and descriptions should not be regarded as all-inclusive or covering all contingencies. If you have questions or require further information, please contact your local Thermo King dealer.
The procedures described herein should be undertaken only by qualified personnel. Failure to implement these procedures correctly may cause damage to the Thermo King unit or other property or personal injury.
Thermo King Corporation and its affiliates shall have no liability in contract or tort (including negligence and/or strict liability) or otherwise, to any person or entity for any personal injury, property damage or any other direct, indirect, special or consequential damage or liability whatsoever, arising out of or resulting from any actions by any person that are contrary to this manual or any of the information, recommendations or descriptions contained herein or the failure of any person to implement the procedures described herein correctly or to follow caution and safety decals located on the Thermo King unit.
Page 4
3
Table of Contents
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
List of Figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . 13
General Safety Practices . . . . . . . . . . . . . . . . . . . . . . 13
Automatic Start/Stop Operation . . . . . . . . . . . . . . . . . 14
Electrical Hazard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Refrigerant Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
First Aid–Refrigerant . . . . . . . . . . . . . . . . . . . . . . . 15
First Aid–Refrigerant Oil . . . . . . . . . . . . . . . . . . . . 15
Safety Decals and Locations . . . . . . . . . . . . . . . . . . . 16
EPA Emission Control System Warranty
Statement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Responsibilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Thermo King Corporation Responsibilities . . . . . .20
Owner Responsibilities . . . . . . . . . . . . . . . . . . . . .21
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Unit Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Design Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Diesel Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
ELC (Extended Life Coolant) . . . . . . . . . . . . . . . . . . . .27
EMI 3000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Thermo King X430L Reciprocating Compressor . . . . .28
Electronic Throttling Valve . . . . . . . . . . . . . . . . . . . . . .28
SMART REEFER 2 (SR-2) Control System . . . . . . . . .29
CYCLE-SENTRY Operation . . . . . . . . . . . . . . . . .29
Continuous Run Operation . . . . . . . . . . . . . . . . . .29
CYCLE-SENTRY Start-Stop Controls . . . . . . . . . .30
Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
OptiSet Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
FreshSet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
3
Table of Contents
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
List of Figures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . 13
General Safety Practices . . . . . . . . . . . . . . . . . . . . . . 13
Automatic Start/Stop Operation . . . . . . . . . . . . . . . . . 14
Electrical Hazard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Refrigerant Oil . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
First Aid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
First Aid–Refrigerant . . . . . . . . . . . . . . . . . . . . . . . 15
First Aid–Refrigerant Oil . . . . . . . . . . . . . . . . . . . . 15
Safety Decals and Locations . . . . . . . . . . . . . . . . . . . 16
EPA Emission Control System Warranty
Statement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Responsibilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Thermo King Corporation Responsibilities . . . . . .20
Owner Responsibilities . . . . . . . . . . . . . . . . . . . . .21
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Unit Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Unit Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
Design Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Diesel Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
ELC (Extended Life Coolant) . . . . . . . . . . . . . . . . . . . .27
EMI 3000 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Thermo King X430L Reciprocating Compressor . . . . .28
Electronic Throttling Valve . . . . . . . . . . . . . . . . . . . . . .28
SMART REEFER 2 (SR-2) Control System . . . . . . . . .29
CYCLE-SENTRY Operation . . . . . . . . . . . . . . . . .29
Continuous Run Operation . . . . . . . . . . . . . . . . . .29
CYCLE-SENTRY Start-Stop Controls . . . . . . . . . .30
Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
OptiSet Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
FreshSet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Page 5
Table of Contents
4
Opening the Front Doors . . . . . . . . . . . . . . . . . . . . . . .34
Opening the Secondary Door Latch . . . . . . . . . . .34
Closing the Front Doors . . . . . . . . . . . . . . . . . . . . . . . . 35
Engine Compartment Components . . . . . . . . . . . . . . .36
Unit Protection Devices . . . . . . . . . . . . . . . . . . . . . . . .37
Remote Status Display (Optional) . . . . . . . . . . . . . . 41
Manual Pretrip Inspection
(Before Starting the Unit) . . . . . . . . . . . . . . . . . . . . . 45
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . 47
SMART REEFER 2 (SR-2) Controller Overview . . . . .47
HMI Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Control Panel Display . . . . . . . . . . . . . . . . . . . . . . 49
Control Panel Keys . . . . . . . . . . . . . . . . . . . . . . . . 50
Turning Unit On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Turning Unit Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Standard Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Standard Display Variations . . . . . . . . . . . . . . . . . . . . 55
Temperature Watch Display . . . . . . . . . . . . . . . . . . . .56
Alarm Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Starting the Diesel Engine . . . . . . . . . . . . . . . . . . . . . .58
Unit Fails To Start . . . . . . . . . . . . . . . . . . . . . . . . .58
After Start Inspection . . . . . . . . . . . . . . . . . . . . . . 59
Electric Standby Operation . . . . . . . . . . . . . . . . . . . . . 60
Starting the Unit on Electric Standby Operation . 61
Unit Fails to Start . . . . . . . . . . . . . . . . . . . . . . . . . 62
Switching from Diesel to Electric . . . . . . . . . . . . . 63
Switching from Electric to Diesel . . . . . . . . . . . . . 64
Changing the Setpoint . . . . . . . . . . . . . . . . . . . . . . . . 65
Selection of Operating Modes . . . . . . . . . . . . . . . . . . 68
Selecting CYCLE-SENTRY or Continuous Mode . . . 69
Initiating a Manual Defrost Cycle . . . . . . . . . . . . . . . . 71
Terminating a Defrost Cycle . . . . . . . . . . . . . . . . . . . . 72
Viewing Gauge Readings . . . . . . . . . . . . . . . . . . . . . . 73
Viewing Sensor Readings . . . . . . . . . . . . . . . . . . . . . 75
Navigating the Main Menu . . . . . . . . . . . . . . . . . . . . . 79
Main Menu Choices . . . . . . . . . . . . . . . . . . . . . . . 80
Language Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Alarms Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Important Alarm Notes . . . . . . . . . . . . . . . . . . . . . 86
Datalogger Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Initiating a Start of Trip . . . . . . . . . . . . . . . . . . . . . 88
Printing a Trip Report . . . . . . . . . . . . . . . . . . . . . . 90
Hourmeters Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Mode Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Turning CYCLE-SENTRY On or Off . . . . . . . . . . 97
Table of Contents
4
Opening the Front Doors . . . . . . . . . . . . . . . . . . . . . . .34
Opening the Secondary Door Latch . . . . . . . . . . .34
Closing the Front Doors . . . . . . . . . . . . . . . . . . . . . . . . 35
Engine Compartment Components . . . . . . . . . . . . . . .36
Unit Protection Devices . . . . . . . . . . . . . . . . . . . . . . . .37
Remote Status Display (Optional) . . . . . . . . . . . . . . 41
Manual Pretrip Inspection
(Before Starting the Unit) . . . . . . . . . . . . . . . . . . . . . 45
Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . 47
SMART REEFER 2 (SR-2) Controller Overview . . . . .47
HMI Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Control Panel Display . . . . . . . . . . . . . . . . . . . . . . 49
Control Panel Keys . . . . . . . . . . . . . . . . . . . . . . . . 50
Turning Unit On . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Turning Unit Off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Standard Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
Standard Display Variations . . . . . . . . . . . . . . . . . . . . 55
Temperature Watch Display . . . . . . . . . . . . . . . . . . . .56
Alarm Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Starting the Diesel Engine . . . . . . . . . . . . . . . . . . . . . .58
Unit Fails To Start . . . . . . . . . . . . . . . . . . . . . . . . .58
After Start Inspection . . . . . . . . . . . . . . . . . . . . . . 59
Electric Standby Operation . . . . . . . . . . . . . . . . . . . . . 60
Starting the Unit on Electric Standby Operation . 61
Unit Fails to Start . . . . . . . . . . . . . . . . . . . . . . . . . 62
Switching from Diesel to Electric . . . . . . . . . . . . . 63
Switching from Electric to Diesel . . . . . . . . . . . . . 64
Changing the Setpoint . . . . . . . . . . . . . . . . . . . . . . . . 65
Selection of Operating Modes . . . . . . . . . . . . . . . . . . 68
Selecting CYCLE-SENTRY or Continuous Mode . . . 69
Initiating a Manual Defrost Cycle . . . . . . . . . . . . . . . . 71
Terminating a Defrost Cycle . . . . . . . . . . . . . . . . . . . . 72
Viewing Gauge Readings . . . . . . . . . . . . . . . . . . . . . . 73
Viewing Sensor Readings . . . . . . . . . . . . . . . . . . . . . 75
Navigating the Main Menu . . . . . . . . . . . . . . . . . . . . . 79
Main Menu Choices . . . . . . . . . . . . . . . . . . . . . . . 80
Language Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Alarms Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Important Alarm Notes . . . . . . . . . . . . . . . . . . . . . 86
Datalogger Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Initiating a Start of Trip . . . . . . . . . . . . . . . . . . . . . 88
Printing a Trip Report . . . . . . . . . . . . . . . . . . . . . . 90
Hourmeters Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Mode Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Turning CYCLE-SENTRY On or Off . . . . . . . . . . 97
Page 6
Table of Contents
5
Selecting Keypad Lockout . . . . . . . . . . . . . . . . . . 99
Selecting Sleep Mode . . . . . . . . . . . . . . . . . . . . . 101
Pretrip Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Initiating a Pretrip Test . . . . . . . . . . . . . . . . . . . . 106
Stopping a Pretrip Test . . . . . . . . . . . . . . . . . . . . 107
Electric Standby/Diesel Mode . . . . . . . . . . . . . . . . . . 109
Adjust Brightness Menu . . . . . . . . . . . . . . . . . . . . . . 111
Time Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
OptiSet Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Selecting a Named Product . . . . . . . . . . . . . . . . 117
Changing the Setpoint for a Named Product . . . 122
Selecting a Setpoint . . . . . . . . . . . . . . . . . . . . . . 125
Optional Rear Remote Control Panel . . . . . . . . . . 129
Rear Remote Control Panel Functions . . . . . . . . . . . 130
Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Stand By . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Reading a Typical Remote Standard Display . . . . . . 135
Remote Control Panel Lockout . . . . . . . . . . . . . . . . . 135
Turning the Unit On or Off (Configured for STAND BY
Operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Turning the Unit On and Off (Configured for RUN
Operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .136
Changing the Setpoint . . . . . . . . . . . . . . . . . . . . . . . .137
Selecting Cycle-Sentry or Continuous Mode . . . . . . .138
Displaying the Discharge Air Temperature . . . . . . . .139
Viewing and Clearing Alarm Codes . . . . . . . . . . . . . .140
Starting a Manual Defrost Cycle . . . . . . . . . . . . . . . .141
Sending a Start of Trip Marker . . . . . . . . . . . . . . . . . .142
Running a Pretrip Test . . . . . . . . . . . . . . . . . . . . . . . .143
Alarm Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Alarm Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Corrective Action . . . . . . . . . . . . . . . . . . . . . . . . . . . .148
Loading and Enroute Inspections . . . . . . . . . . . . .165
Pre-Loading Inspection . . . . . . . . . . . . . . . . . . . . . . .165
Post-Loading Inspection . . . . . . . . . . . . . . . . . . . . . .167
Enroute Inspections . . . . . . . . . . . . . . . . . . . . . . .168
Jump Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .171
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .175
Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .175
Belt Tension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .178
Table of Contents
5
Selecting Keypad Lockout . . . . . . . . . . . . . . . . . . 99
Selecting Sleep Mode . . . . . . . . . . . . . . . . . . . . . 101
Pretrip Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Initiating a Pretrip Test . . . . . . . . . . . . . . . . . . . . 106
Stopping a Pretrip Test . . . . . . . . . . . . . . . . . . . . 107
Electric Standby/Diesel Mode . . . . . . . . . . . . . . . . . . 109
Adjust Brightness Menu . . . . . . . . . . . . . . . . . . . . . . 111
Time Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
OptiSet Plus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Selecting a Named Product . . . . . . . . . . . . . . . . 117
Changing the Setpoint for a Named Product . . . 122
Selecting a Setpoint . . . . . . . . . . . . . . . . . . . . . . 125
Optional Rear Remote Control Panel . . . . . . . . . . 129
Rear Remote Control Panel Functions . . . . . . . . . . . 130
Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Stand By . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Reading a Typical Remote Standard Display . . . . . . 135
Remote Control Panel Lockout . . . . . . . . . . . . . . . . . 135
Turning the Unit On or Off (Configured for STAND BY
Operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 136
Turning the Unit On and Off (Configured for RUN
Operation) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .136
Changing the Setpoint . . . . . . . . . . . . . . . . . . . . . . . .137
Selecting Cycle-Sentry or Continuous Mode . . . . . . .138
Displaying the Discharge Air Temperature . . . . . . . .139
Viewing and Clearing Alarm Codes . . . . . . . . . . . . . .140
Starting a Manual Defrost Cycle . . . . . . . . . . . . . . . .141
Sending a Start of Trip Marker . . . . . . . . . . . . . . . . . .142
Running a Pretrip Test . . . . . . . . . . . . . . . . . . . . . . . .143
Alarm Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Alarm Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
Corrective Action . . . . . . . . . . . . . . . . . . . . . . . . . . . .148
Loading and Enroute Inspections . . . . . . . . . . . . .165
Pre-Loading Inspection . . . . . . . . . . . . . . . . . . . . . . .165
Post-Loading Inspection . . . . . . . . . . . . . . . . . . . . . .167
Enroute Inspections . . . . . . . . . . . . . . . . . . . . . . .168
Jump Starting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .171
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .175
Engine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .175
Belt Tension . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .178
Page 7
Table of Contents
6
Electrical Control System . . . . . . . . . . . . . . . . . . . . . 179
Electric Standby (Model 50 Units Only) . . . . . . . . . . .180
Electric Fuel Heater (Optional) . . . . . . . . . . . . . . . . . 181
Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . .182
Maintenance Inspection Schedule . . . . . . . . . . . . . 183
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Serial Number Locations . . . . . . . . . . . . . . . . . . . . 201
Emergency Cold Line . . . . . . . . . . . . . . . . . . . . . . . 205
Recover Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . 206
CALIFORNIA
Proposition 65 Warning . . . . . . . . . . . . . . . . . . . . . 207
Table of Contents
6
Electrical Control System . . . . . . . . . . . . . . . . . . . . . 179
Electric Standby (Model 50 Units Only) . . . . . . . . . . .180
Electric Fuel Heater (Optional) . . . . . . . . . . . . . . . . . 181
Refrigeration System . . . . . . . . . . . . . . . . . . . . . . . . .182
Maintenance Inspection Schedule . . . . . . . . . . . . . 183
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Serial Number Locations . . . . . . . . . . . . . . . . . . . . 201
Emergency Cold Line . . . . . . . . . . . . . . . . . . . . . . . 205
Recover Refrigerant . . . . . . . . . . . . . . . . . . . . . . . . 206
CALIFORNIA
Proposition 65 Warning . . . . . . . . . . . . . . . . . . . . . 207
Page 8
7
List of Figures
Figure 1:ELC (Extended Life Coolant) Nameplate
(Located on expansion tank in units
equipped with ELC) . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 2:Belt Warning
(Located on condenser housing) . . . . . . . . . . . . . 16
Figure 3:Belt Replacement Caution
(Located on condenser housing) . . . . . . . . . . . . . 16
Figure 4:Automatic Start Caution
(Locations vary depending on model. Decals are located near areas that contain moving parts which can cause severe injuries if hands or clothing become
tangled when unit automatically starts.) . . . . . . . . 17
Figure 5:Fan Caution
(Locations vary depending on model. Decals are located near areas that contain fans which can ca use severe injuries when unit automatically starts.) . . 17
Figure 6:Door Latch Warning
(Located on curbside door) . . . . . . . . . . . . . . . . . . 18
Figure 7:Front View . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 8:TK486V (TK486VH is Similar) Tier 2 . . . . . . 26
Figure 9:Compressors . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 10:HMI Controller and Data Ports . . . . . . . . . . .31
Figure 11:Door Latch Location . . . . . . . . . . . . . . . . . . .34
Figure 12:Opening Secondary Door Latch . . . . . . . . .34
Figure 13:Engine Compartment . . . . . . . . . . . . . . . . . .36
Figure 14:Control Box With Service Door Open . . . . .39
Figure 15:Control Box With Control Box Door Open . .40
Figure 16:Interface Board . . . . . . . . . . . . . . . . . . . . . .40
Figure 17:Remote Status Display (All LEDs Shown) . .41
Figure 18:Normal Operation No Alarms . . . . . . . . . . . .41
Figure 19:Check Alarm . . . . . . . . . . . . . . . . . . . . . . . .42
Figure 20:Shutdown Alarm . . . . . . . . . . . . . . . . . . . . .42
Figure 21:Remote Status Display with Fuel Level . . . .43
Figure 22:Remote Status Display
with Fuel Level and Temperature . . . . . . . . . . . . .43
Figure 23:SR-2 HMI Control Panel . . . . . . . . . . . . . . .47
Figure 24:Control Box With Service Door Open . . . . .48
Figure 25:Control Panel Display and Keys . . . . . . . . .49
Figure 26:Press On Key . . . . . . . . . . . . . . . . . . . . . . . .51
Figure 27:Turning Unit On Screen Sequence . . . . . . .52
Figure 28:Press Off Key . . . . . . . . . . . . . . . . . . . . . . . .53
Figure 29:Turning Unit Off Screen Sequence . . . . . . .53
7
List of Figures
Figure 1:ELC (Extended Life Coolant) Nameplate
(Located on expansion tank in units
equipped with ELC) . . . . . . . . . . . . . . . . . . . . . . . 16
Figure 2:Belt Warning
(Located on condenser housing) . . . . . . . . . . . . . 16
Figure 3:Belt Replacement Caution
(Located on condenser housing) . . . . . . . . . . . . . 16
Figure 4:Automatic Start Caution
(Locations vary depending on model. Decals are located near areas that contain moving parts which can cause severe injuries if hands or clothing become
tangled when unit automatically starts.) . . . . . . . . 17
Figure 5:Fan Caution
(Locations vary depending on model. Decals are located near areas that contain fans which can ca use severe injuries when unit automatically starts.) . . 17
Figure 6:Door Latch Warning
(Located on curbside door) . . . . . . . . . . . . . . . . . . 18
Figure 7:Front View . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 8:TK486V (TK486VH is Similar) Tier 2 . . . . . . 26
Figure 9:Compressors . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 10:HMI Controller and Data Ports . . . . . . . . . . .31
Figure 11:Door Latch Location . . . . . . . . . . . . . . . . . . .34
Figure 12:Opening Secondary Door Latch . . . . . . . . .34
Figure 13:Engine Compartment . . . . . . . . . . . . . . . . . .36
Figure 14:Control Box With Service Door Open . . . . .39
Figure 15:Control Box With Control Box Door Open . .40
Figure 16:Interface Board . . . . . . . . . . . . . . . . . . . . . .40
Figure 17:Remote Status Display (All LEDs Shown) . .41
Figure 18:Normal Operation No Alarms . . . . . . . . . . . .41
Figure 19:Check Alarm . . . . . . . . . . . . . . . . . . . . . . . .42
Figure 20:Shutdown Alarm . . . . . . . . . . . . . . . . . . . . .42
Figure 21:Remote Status Display with Fuel Level . . . .43
Figure 22:Remote Status Display
with Fuel Level and Temperature . . . . . . . . . . . . .43
Figure 23:SR-2 HMI Control Panel . . . . . . . . . . . . . . .47
Figure 24:Control Box With Service Door Open . . . . .48
Figure 25:Control Panel Display and Keys . . . . . . . . .49
Figure 26:Press On Key . . . . . . . . . . . . . . . . . . . . . . . .51
Figure 27:Turning Unit On Screen Sequence . . . . . . .52
Figure 28:Press Off Key . . . . . . . . . . . . . . . . . . . . . . . .53
Figure 29:Turning Unit Off Screen Sequence . . . . . . .53
Page 9
List of Figures
8
Figure 30:Standard Display . . . . . . . . . . . . . . . . . . . . .54
Figure 31: Standard Display Variations . . . . . . . . . . . .55
Figure 32:Temperature Watch Display . . . . . . . . . . . . 56
Figure 33:Alarm Display . . . . . . . . . . . . . . . . . . . . . . . 57
Figure 34:Electric Power Receptacle . . . . . . . . . . . . . 60
Figure 35:Electric Standby Detected Screen . . . . . . . .61
Figure 36:Electric Motor Starting Screen . . . . . . . . . . . 62
Figure 37:Electric Standby Detected Screen . . . . . . . .63
Figure 38:Programming Electric Standby Screen . . . .63
Figure 39:Electric Standby Undetected Screen . . . . . .64
Figure 40:Programming Diesel Mode Screen . . . . . . .64
Figure 41:Changing Setpoint . . . . . . . . . . . . . . . . . . . . 65
Figure 42:Changing the Setpoint Screen Sequence . .67
Figure 43:Changing Mode . . . . . . . . . . . . . . . . . . . . . .69
Figure 44:Screen Sequence for Changing from
CYCLE-SENTRY Mode to Continuous Mode . . . .70
Figure 45:Screen Sequence for Changing from
Continuous Mode to CYCLE-SENTRY Mode . . . .70
Figure 46:Initiating a Manual Defrost Cycle . . . . . . . . . 71
Figure 47:Initiating Manual Defrost Screen Sequence 72
Figure 48:Viewing Gauges . . . . . . . . . . . . . . . . . . . . . 73
Figure 49:Viewing Gauges Screen Sequence . . . . . . .74
Figure 50:Viewing Sensors . . . . . . . . . . . . . . . . . . . . . 75
Figure 51:Viewing Sensors Screen Sequence (continued
on next page) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Figure 52:Viewing Sensors Screen Sequence (continued
from previous page) . . . . . . . . . . . . . . . . . . . . . . . 78
Figure 53:Accessing Main Menu . . . . . . . . . . . . . . . . 79
Figure 54:Main Menu Choices . . . . . . . . . . . . . . . . . . 80
Figure 55:Standard Display . . . . . . . . . . . . . . . . . . . . 82
Figure 56:Standard Display . . . . . . . . . . . . . . . . . . . . 83
Figure 57:Change Language Screen Sequence . . . . 84
Figure 58:Standard Display . . . . . . . . . . . . . . . . . . . . 85
Figure 59:Viewing and Clearing Alarms Screen Sequence
87
Figure 60:Standard Display . . . . . . . . . . . . . . . . . . . . 88
Figure 61:Start of Trip Screen Sequence . . . . . . . . . . 89
Figure 62:Printer Port Location . . . . . . . . . . . . . . . . . 90
Figure 63:Standard Display . . . . . . . . . . . . . . . . . . . . 91
Figure 64:Print Report Screen Sequence . . . . . . . . . 92
Figure 65:Standard Display . . . . . . . . . . . . . . . . . . . . 93
Figure 66:Viewing Hourmeters Screen Sequence
(continued on next page) . . . . . . . . . . . . . . . . . . . 94
Figure 67:Viewing Hourmeters Screen Sequence
(continued from previous page) . . . . . . . . . . . . . . 95
Figure 68:Standard Display . . . . . . . . . . . . . . . . . . . . 97
Figure 69:Selecting Mode Screen Sequence . . . . . . . 98
Figure 70:Standard Display . . . . . . . . . . . . . . . . . . . . 99
List of Figures
8
Figure 30:Standard Display . . . . . . . . . . . . . . . . . . . . .54
Figure 31: Standard Display Variations . . . . . . . . . . . .55
Figure 32:Temperature Watch Display . . . . . . . . . . . . 56
Figure 33:Alarm Display . . . . . . . . . . . . . . . . . . . . . . . 57
Figure 34:Electric Power Receptacle . . . . . . . . . . . . . 60
Figure 35:Electric Standby Detected Screen . . . . . . . .61
Figure 36:Electric Motor Starting Screen . . . . . . . . . . . 62
Figure 37:Electric Standby Detected Screen . . . . . . . .63
Figure 38:Programming Electric Standby Screen . . . .63
Figure 39:Electric Standby Undetected Screen . . . . . .64
Figure 40:Programming Diesel Mode Screen . . . . . . .64
Figure 41:Changing Setpoint . . . . . . . . . . . . . . . . . . . . 65
Figure 42:Changing the Setpoint Screen Sequence . .67
Figure 43:Changing Mode . . . . . . . . . . . . . . . . . . . . . .69
Figure 44:Screen Sequence for Changing from
CYCLE-SENTRY Mode to Continuous Mode . . . .70
Figure 45:Screen Sequence for Changing from
Continuous Mode to CYCLE-SENTRY Mode . . . .70
Figure 46:Initiating a Manual Defrost Cycle . . . . . . . . . 71
Figure 47:Initiating Manual Defrost Screen Sequence 72
Figure 48:Viewing Gauges . . . . . . . . . . . . . . . . . . . . . 73
Figure 49:Viewing Gauges Screen Sequence . . . . . . .74
Figure 50:Viewing Sensors . . . . . . . . . . . . . . . . . . . . . 75
Figure 51:Viewing Sensors Screen Sequence (continued
on next page) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Figure 52:Viewing Sensors Screen Sequence (continued
from previous page) . . . . . . . . . . . . . . . . . . . . . . . 78
Figure 53:Accessing Main Menu . . . . . . . . . . . . . . . . 79
Figure 54:Main Menu Choices . . . . . . . . . . . . . . . . . . 80
Figure 55:Standard Display . . . . . . . . . . . . . . . . . . . . 82
Figure 56:Standard Display . . . . . . . . . . . . . . . . . . . . 83
Figure 57:Change Language Screen Sequence . . . . 84
Figure 58:Standard Display . . . . . . . . . . . . . . . . . . . . 85
Figure 59:Viewing and Clearing Alarms Screen Sequence
87
Figure 60:Standard Display . . . . . . . . . . . . . . . . . . . . 88
Figure 61:Start of Trip Screen Sequence . . . . . . . . . . 89
Figure 62:Printer Port Location . . . . . . . . . . . . . . . . . 90
Figure 63:Standard Display . . . . . . . . . . . . . . . . . . . . 91
Figure 64:Print Report Screen Sequence . . . . . . . . . 92
Figure 65:Standard Display . . . . . . . . . . . . . . . . . . . . 93
Figure 66:Viewing Hourmeters Screen Sequence
(continued on next page) . . . . . . . . . . . . . . . . . . . 94
Figure 67:Viewing Hourmeters Screen Sequence
(continued from previous page) . . . . . . . . . . . . . . 95
Figure 68:Standard Display . . . . . . . . . . . . . . . . . . . . 97
Figure 69:Selecting Mode Screen Sequence . . . . . . . 98
Figure 70:Standard Display . . . . . . . . . . . . . . . . . . . . 99
Page 10
List of Figures
9
Figure 71:Mode Menu Display . . . . . . . . . . . . . . . . . . 99
Figure 72:Keypad Lockout Display . . . . . . . . . . . . . . 100
Figure 73:Standard Display . . . . . . . . . . . . . . . . . . . 101
Figure 74:Selecting Sleep Mode Screen Sequence . 103
Figure 75:Standard Display . . . . . . . . . . . . . . . . . . . 106
Figure 76:No Pretrip Alarm Active Display . . . . . . . . 106
Figure 77:Pretrip Test Screen Sequence . . . . . . . . . 108
Figure 78:Standard Display . . . . . . . . . . . . . . . . . . . 109
Figure 79:Programming Diesel Mode . . . . . . . . . . . . 110
Figure 80:Programming Electric Standby Mode . . . . 111
Figure 81:Standard Display . . . . . . . . . . . . . . . . . . . 112
Figure 82:Adjusting Display Brightness Screen Sequence
113
Figure 83:Time and Date Screens . . . . . . . . . . . . . . 114
Figure 84:Standard Display with Product Soft Key . . 115 Figure 85:Standard Display with
Product/Setpoint Soft Key . . . . . . . . . . . . . . . . . 116
Figure 86:Selecting Named Product . . . . . . . . . . . . . 117
Figure 87:Selecting or Changing Named Product Screen
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Figure 88:Selecting Setpoint for Named Product Screen
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Figure 89:Changing Setpoint for Named Product . . . 122 Figure 90:Changing Setpoint for Named Product Screen
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124
Figure 91:Selecting or Changing Setpoint . . . . . . . . .125
Figure 92:Selecting or Changing Numeric Setpoint
Screen Sequence . . . . . . . . . . . . . . . . . . . . . . . .127
Figure 93:Rear Remote Control Panel . . . . . . . . . . . .129
Figure 94:Rear Remote Control Panel Display . . . . .131
Figure 95:Unit HMI Control Panel Display . . . . . . . . .131
Figure 96:Press Select Key . . . . . . . . . . . . . . . . . . . .132
Figure 97:Rear Remote Control Panel . . . . . . . . . . . .133
Figure 98:Rear Remote Control Panel . . . . . . . . . . . .134
Figure 99:Remote Standard Display . . . . . . . . . . . . .135
Figure 100:Remote Lock Out Display . . . . . . . . . . . .135
Figure 101:Stand By Display . . . . . . . . . . . . . . . . . . .136
Figure 102:Standard Display . . . . . . . . . . . . . . . . . . .136
Figure 103:Press Up or Down Arrow Keys . . . . . . . .137
Figure 104:Press Enter Key . . . . . . . . . . . . . . . . . . . .137
Figure 105:Press Select Key . . . . . . . . . . . . . . . . . . .138
Figure 106:Press Up or Down Arrow Keys . . . . . . . .138
Figure 107:Press Enter Key . . . . . . . . . . . . . . . . . . . .138
Figure 108:Press Select Key Twice . . . . . . . . . . . . . .139
Figure 109:Press Select Key Three Times . . . . . . . .140
Figure 110:Press Enter Key . . . . . . . . . . . . . . . . . . . .140
Figure 111:No Alarms Display . . . . . . . . . . . . . . . . . .140
Figure 112:Press Defrost Key . . . . . . . . . . . . . . . . . .141
List of Figures
9
Figure 71:Mode Menu Display . . . . . . . . . . . . . . . . . . 99
Figure 72:Keypad Lockout Display . . . . . . . . . . . . . . 100
Figure 73:Standard Display . . . . . . . . . . . . . . . . . . . 101
Figure 74:Selecting Sleep Mode Screen Sequence . 103
Figure 75:Standard Display . . . . . . . . . . . . . . . . . . . 106
Figure 76:No Pretrip Alarm Active Display . . . . . . . . 106
Figure 77:Pretrip Test Screen Sequence . . . . . . . . . 108
Figure 78:Standard Display . . . . . . . . . . . . . . . . . . . 109
Figure 79:Programming Diesel Mode . . . . . . . . . . . . 110
Figure 80:Programming Electric Standby Mode . . . . 111
Figure 81:Standard Display . . . . . . . . . . . . . . . . . . . 112
Figure 82:Adjusting Display Brightness Screen Sequence
113
Figure 83:Time and Date Screens . . . . . . . . . . . . . . 114
Figure 84:Standard Display with Product Soft Key . . 115 Figure 85:Standard Display with
Product/Setpoint Soft Key . . . . . . . . . . . . . . . . . 116
Figure 86:Selecting Named Product . . . . . . . . . . . . . 117
Figure 87:Selecting or Changing Named Product Screen
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Figure 88:Selecting Setpoint for Named Product Screen
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Figure 89:Changing Setpoint for Named Product . . . 122 Figure 90:Changing Setpoint for Named Product Screen
Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .124
Figure 91:Selecting or Changing Setpoint . . . . . . . . .125
Figure 92:Selecting or Changing Numeric Setpoint
Screen Sequence . . . . . . . . . . . . . . . . . . . . . . . .127
Figure 93:Rear Remote Control Panel . . . . . . . . . . . .129
Figure 94:Rear Remote Control Panel Display . . . . .131
Figure 95:Unit HMI Control Panel Display . . . . . . . . .131
Figure 96:Press Select Key . . . . . . . . . . . . . . . . . . . .132
Figure 97:Rear Remote Control Panel . . . . . . . . . . . .133
Figure 98:Rear Remote Control Panel . . . . . . . . . . . .134
Figure 99:Remote Standard Display . . . . . . . . . . . . .135
Figure 100:Remote Lock Out Display . . . . . . . . . . . .135
Figure 101:Stand By Display . . . . . . . . . . . . . . . . . . .136
Figure 102:Standard Display . . . . . . . . . . . . . . . . . . .136
Figure 103:Press Up or Down Arrow Keys . . . . . . . .137
Figure 104:Press Enter Key . . . . . . . . . . . . . . . . . . . .137
Figure 105:Press Select Key . . . . . . . . . . . . . . . . . . .138
Figure 106:Press Up or Down Arrow Keys . . . . . . . .138
Figure 107:Press Enter Key . . . . . . . . . . . . . . . . . . . .138
Figure 108:Press Select Key Twice . . . . . . . . . . . . . .139
Figure 109:Press Select Key Three Times . . . . . . . .140
Figure 110:Press Enter Key . . . . . . . . . . . . . . . . . . . .140
Figure 111:No Alarms Display . . . . . . . . . . . . . . . . . .140
Figure 112:Press Defrost Key . . . . . . . . . . . . . . . . . .141
Page 11
List of Figures
10
Figure 113:Press Enter Key . . . . . . . . . . . . . . . . . . . 141
Figure 114:Defrost Icon Displayed . . . . . . . . . . . . . . 141
Figure 115:Press TK Logo Key . . . . . . . . . . . . . . . . . 142
Figure 116:Press Enter Key . . . . . . . . . . . . . . . . . . . 142
Figure 117:Press Pretrip Key . . . . . . . . . . . . . . . . . . 143
Figure 118:Press Enter Key . . . . . . . . . . . . . . . . . . . 143
Figure 119:Pretrip Display . . . . . . . . . . . . . . . . . . . . . 144
Figure 120:Pass Pretrip Display . . . . . . . . . . . . . . . .144
Figure 121:Log Alarms Screen . . . . . . . . . . . . . . . . . 145
Figure 122:Alarm Display . . . . . . . . . . . . . . . . . . . . . 146
Figure 123:Shutdown Alarm Display . . . . . . . . . . . . . 147
Figure 124:Loading Considerations . . . . . . . . . . . . . . 166
Figure 125:Unit Battery . . . . . . . . . . . . . . . . . . . . . . . 172
Figure 126:Sequence for Connecting Jumper Cables . . .
172
Figure 127:Unit Engine . . . . . . . . . . . . . . . . . . . . . . .173
Figure 128:Sequence for Disconnecting Jumper Cables
174 Figure 129:Compressor Serial Number Location . . . 202
Figure 130:Engine Serial Number Location . . . . . . . . 202
Figure 131:Unit Serial Number Plate Locations
(on the bulkhead above compressor inside
curbside door and on roadside of evaporator) . .203
Figure 132:Unit Serial Number Plate . . . . . . . . . . . . .203
List of Figures
10
Figure 113:Press Enter Key . . . . . . . . . . . . . . . . . . . 141
Figure 114:Defrost Icon Displayed . . . . . . . . . . . . . . 141
Figure 115:Press TK Logo Key . . . . . . . . . . . . . . . . . 142
Figure 116:Press Enter Key . . . . . . . . . . . . . . . . . . . 142
Figure 117:Press Pretrip Key . . . . . . . . . . . . . . . . . . 143
Figure 118:Press Enter Key . . . . . . . . . . . . . . . . . . . 143
Figure 119:Pretrip Display . . . . . . . . . . . . . . . . . . . . . 144
Figure 120:Pass Pretrip Display . . . . . . . . . . . . . . . .144
Figure 121:Log Alarms Screen . . . . . . . . . . . . . . . . . 145
Figure 122:Alarm Display . . . . . . . . . . . . . . . . . . . . . 146
Figure 123:Shutdown Alarm Display . . . . . . . . . . . . . 147
Figure 124:Loading Considerations . . . . . . . . . . . . . . 166
Figure 125:Unit Battery . . . . . . . . . . . . . . . . . . . . . . . 172
Figure 126:Sequence for Connecting Jumper Cables . . .
172
Figure 127:Unit Engine . . . . . . . . . . . . . . . . . . . . . . .173
Figure 128:Sequence for Disconnecting Jumper Cables
174 Figure 129:Compressor Serial Number Location . . . 202
Figure 130:Engine Serial Number Location . . . . . . . . 202
Figure 131:Unit Serial Number Plate Locations
(on the bulkhead above compressor inside
curbside door and on roadside of evaporator) . .203
Figure 132:Unit Serial Number Plate . . . . . . . . . . . . .203
Page 12
11
Introduction
There is nothing complicated about operating and maintaining
your Thermo King unit, but a few minutes studying this
manual will be time well spent.
Performing pre-trip checks and enroute inspections on a
regular basis will minimize on-the-road operating problems . A
regular maintenance program will also help to keep your unit
in top operating condition. If factory recommended procedures
are followed, you will find that you have purchased the most
efficient and dependable temperature control system available.
All service requirements, major and minor, should be handled
by a Thermo King dealer for four very important reasons:
They are equipped with the factory recommended tools to perform all service functions
They have factory trained and certified technicians
They have genuine Thermo King replacement parts
The warranty on your new unit is valid only when the repair and replacement of component parts is performed by an authorized Thermo King dealer.
IMPORTANT: This manual is published for informational purposes only and the information furnished herein should not be considered as all-inclusive or meant to cover all contingencies. If more information is required, consult your Thermo King Service Directory for the location and telephone number of the local dealer.
11
Introduction
There is nothing complicated about operating and maintaining your Thermo King unit, but a few minutes studying this manual will be time well spent.
Performing pre-trip checks and enroute inspections on a regular basis will minimize on-the-road operating problems . A regular maintenance program will also help to keep your unit in top operating condition. If factory recommended procedures are followed, you will find that you have purchased the most efficient and dependable temperature control system available.
All service requirements, major and minor, should be handled by a Thermo King dealer for four very important reasons:
They are equipped with the factory recommended tools to perform all service functions
They have factory trained and certified technicians
They have genuine Thermo King replacement parts
The warranty on your new unit is valid only when the repair and replacement of component parts is performed by an authorized Thermo King dealer.
IMPORTANT: This manual is published for informational purposes only and the information furnished herein should not be considered as all-inclusive or meant to cover all contingencies. If more information is required, consult your Thermo King Service Directory for the location and telephone number of the local dealer.
Page 13
Introduction
12
Introduction
12
Page 14
13
Safety Precautions
Thermo King recommends that servicing be done only by a Thermo King dealer. However , you should be aware of several safety practices. This chapter gives basic safety precautions for working with Thermo King units and describes the safety stickers on your unit that you should be familiar with.
General Safety Practices
DANGER: NEVER operate the unit with the compressor discharge valve closed. Doing so could cause the compressor to explode, causing death or serious injury.
WARNING: Always wear goggles or safety glasses when working with or around the refrigeration system or battery. Refrigerant or battery acid can cause permanent damage if it comes in contact with your eyes.
WARNING: Keep hands and loose clothing clear of fans and belts at all times when the unit is operating or when opening or closing compressor service valves.
WARNING: Exposed coil fins can cause painful lacerations. Service work on the evaporator or condenser coils should be done by a certified Thermo King technician.
WARNING: Do not apply heat to a closed cooling system. Before applying heat to a cooling system, drain it. Then flush it with water and drain the water. Antifreeze contains water and ethylene glycol. The ethylene glycol is flammable and can ignite if the antifreeze is heated enough to boil off the water.
13
Safety Precautions
Thermo King recommends that servicing be done only by a Thermo King dealer. However , you should be aware of several safety practices. This chapter gives basic safety precautions for working with Thermo King units and describes the safety stickers on your unit that you should be familiar with.
General Safety Practices
DANGER: NEVER operate the unit with the compressor discharge valve closed. Doing so could cause the compressor to explode, causing death or serious injury.
WARNING: Always wear goggles or safety glasses when working with or around the refrigeration system or battery. Refrigerant or battery acid can cause permanent damage if it comes in contact with your eyes.
WARNING: Keep hands and loose clothing clear of fans and belts at all times when the unit is operating or when opening or closing compressor service valves.
WARNING: Exposed coil fins can cause painful lacerations. Service work on the evaporator or condenser coils should be done by a certified Thermo King technician.
WARNING: Do not apply heat to a closed cooling system. Before applying heat to a cooling system, drain it. Then flush it with water and drain the water. Antifreeze contains water and ethylene glycol. The ethylene glycol is flammable and can ignite if the antifreeze is heated enough to boil off the water.
Page 15
Safety Precautions
14
Automatic Start/Stop Operation
This unit is capable of automatic operation and could start at any time without warning.
Electrical Hazard
Refrigerant
Although fluorocarbon refrigerants are classified as safe, use caution when working with refrigerants or in areas where they are being used.
CAUTION: Use extreme caution when drilling holes in the unit. Drilling into electrical wiring or refrigerant lines could cause a fire. Do not drill into structural components.
WARNING: The unit can start at any time without warning. Press the O
FF
key on the HMI control panel and place the microprocessor On/Off switch in the Off position before inspecting or servicing any part of the unit.
CAUTION: Turn off the high voltage power supply and disconnect the electric cable before working on the unit. Units with electric standby present a potential electrical hazard.
DANGER: Fluorocarbon refrigerants can produce toxic gases. In the presence of an open flame or electrical short, these gases are severe respiratory irritants CAPABLE OF CAUSING DEATH.
DANGER: Fluorocarbon refrigerants tend to displace air and can cause oxygen depletion which could result in DEA TH BY SUFFOCA TION. Provide adequate ventilation in enclosed or confined areas.
WARNING: Fluorocarbon refrigerants evaporate rapidly, freezing anything they contact if accidentally released into the atmosphere from the liquid state.
Safety Precautions
14
Automatic Start/Stop Operation
This unit is capable of automatic operation and could start at any time without warning.
Electrical Hazard
Refrigerant
Although fluorocarbon refrigerants are classified as safe, use caution when working with refrigerants or in areas where they are being used.
CAUTION: Use extreme caution when drilling holes in the unit. Drilling into electrical wiring or refrigerant lines could cause a fire. Do not drill into structural components.
WARNING: The unit can start at any time without warning. Press the O
FF
key on the HMI control panel and place the microprocessor On/Off switch in the Off position before inspecting or servicing any part of the unit.
CAUTION: Turn off the high voltage power supply and disconnect the electric cable before working on the unit. Units with electric standby present a potential electrical hazard.
DANGER: Fluorocarbon refrigerants can produce toxic gases. In the presence of an open flame or electrical short, these gases are severe respiratory irritants CAPABLE OF CAUSING DEATH.
DANGER: Fluorocarbon refrigerants tend to displace air and can cause oxygen depletion which could result in DEA TH BY SUFFOCA TION. Provide adequate ventilation in enclosed or confined areas.
WARNING: Fluorocarbon refrigerants evaporate rapidly, freezing anything they contact if accidentally released into the atmosphere from the liquid state.
Page 16
Safety Precautions
15
Refrigerant Oil
Observe the following precautions when working with or around refrigerant oil:
First Aid
First Aid–Refrigerant
Eyes: For contact with liquid, immediately flush eyes with
large amounts of water. Get prompt medical attention.
Skin: Flush areas with large amounts of warm water. Do not apply heat. Wrap burns with dry, sterile, bulky dressing to protect from infection or injury. Get prompt medical attention.
Inhalation: Move victim to fresh air and restore breathing if necessary. Stay with victim until emergency personnel arrive.
First Aid–Refrigerant Oil
Eyes: Immediately flush eyes with large amounts of water for
at least 15 minutes while holding the eyelids open. Get prompt medical attention.
Skin: Remove contaminated clothing. Wash thoroughly with soap and water. Get medical attention if irritation persists.
Inhalation: Move victim to fresh air and restore breathing if necessary. Stay with victim until emergency personnel arrive.
Ingestion: Do not induce vomiting. Immediately contact local poison control center or physician.
WARNING: Always wear goggles or safety glasses to protect eyes from refrigerant oil contact.
WARNING: Protect skin and clothing from prolonged or repeated contact with refrigerant oil. Rubber gloves are recommended.
WARNING: W ash thoroughly immediately after handling refrigerant oil to prevent irritation.
Safety Precautions
15
Refrigerant Oil
Observe the following precautions when working with or around refrigerant oil:
First Aid
First Aid–Refrigerant
Eyes: For contact with liquid, immediately flush eyes with
large amounts of water. Get prompt medical attention.
Skin: Flush areas with large amounts of warm water. Do not apply heat. Wrap burns with dry, sterile, bulky dressing to protect from infection or injury. Get prompt medical attention.
Inhalation: Move victim to fresh air and restore breathing if necessary. Stay with victim until emergency personnel arrive.
First Aid–Refrigerant Oil
Eyes: Immediately flush eyes with large amounts of water for
at least 15 minutes while holding the eyelids open. Get prompt medical attention.
Skin: Remove contaminated clothing. Wash thoroughly with soap and water. Get medical attention if irritation persists.
Inhalation: Move victim to fresh air and restore breathing if necessary. Stay with victim until emergency personnel arrive.
Ingestion: Do not induce vomiting. Immediately contact local poison control center or physician.
WARNING: Always wear goggles or safety glasses to protect eyes from refrigerant oil contact.
WARNING: Protect skin and clothing from prolonged or repeated contact with refrigerant oil. Rubber gloves are recommended.
WARNING: W ash thoroughly immediately after handling refrigerant oil to prevent irritation.
Page 17
Safety Precautions
16
Safety Decals and Locations
Figure 1: ELC (Extended Life Coolant) Nameplate
(Located on expansion tank in units
equipped with ELC)
Figure 2: Belt Warning
(Located on condenser housing)
Figure 3: Belt Replacement Caution
(Located on condenser housing)
AJA1947
AKB65
AKB66
Safety Precautions
16
Safety Decals and Locations
Figure 1: ELC (Extended Life Coolant) Nameplate
(Located on expansion tank in units
equipped with ELC)
Figure 2: Belt Warning
(Located on condenser housing)
Figure 3: Belt Replacement Caution
(Located on condenser housing)
AJA1947
AKB65
AKB66
Page 18
Safety Precautions
17
Figure 4: Automatic Start Caution
(Locations vary depending on model. Decals are
located near areas that contain moving parts which
can cause severe injuries if hands or clothing become
tangled when unit automatically starts.)
Figure 5: Fan Caution
(Locations vary depending on model. Decals are
located near areas that contain f ans which can cause
severe injuries when unit automatically starts.)
AKB67 AKB68
Safety Precautions
17
Figure 4: Automatic Start Caution
(Locations vary depending on model. Decals are
located near areas that contain moving parts which
can cause severe injuries if hands or clothing become
tangled when unit automatically starts.)
Figure 5: Fan Caution
(Locations vary depending on model. Decals are
located near areas that contain f ans which can cause
severe injuries when unit automatically starts.)
AKB67 AKB68
Page 19
Safety Precautions
18
Figure 6: Door Latch Warning
(Located on curbside door)
WARNING
ATENCIÓN
NEW DOOR LATCH DESIGN
REQUIRES DOOR TO BE SLAMMED
SHUT BEFORE MOVING TRAILER.
FAILURE TO CLOSE DOOR FIRMLY CAN ALLOW WIND TO TEAR DOOR
FROM REFRIGERATION UNIT AND
CAUSE INJURY TO OTHERS.
NUEVO DESEÑO DE CERRADURA
REQUIERE ASOTAR LA PUERTA ANTES
DE CONDUCIR EL TRAILER.
AL NO CERRAR LA PUERTA CON
FIRMEZA EL VIENTO PODRÍA
DESPRENDER LA PUERTA DE LA
UNIDAD DE REFRIGERACIÓN Y
CAUSAR DAÑOS A OTROS.
AEA2422
Safety Precautions
18
Figure 6: Door Latch Warning
(Located on curbside door)
WARNING
ATENCIÓN
NEW DOOR LATCH DESIGN
REQUIRES DOOR TO BE SLAMMED
SHUT BEFORE MOVING TRAILER.
FAILURE TO CLOSE DOOR FIRMLY CAN ALLOW WIND TO TEAR DOOR
FROM REFRIGERATION UNIT AND
CAUSE INJURY TO OTHERS.
NUEVO DESEÑO DE CERRADURA
REQUIERE ASOTAR LA PUERTA ANTES
DE CONDUCIR EL TRAILER.
AL NO CERRAR LA PUERTA CON
FIRMEZA EL VIENTO PODRÍA
DESPRENDER LA PUERTA DE LA
UNIDAD DE REFRIGERACIÓN Y
CAUSAR DAÑOS A OTROS.
AEA2422
Page 20
19
EPA Emission Control System Warranty Statement
Thermo King warrants to the initial owner and each subsequent owner that the certified, non-road diesel engine in your unit is:
1. Designed, built and equipped so as to conform, at the time of sale, with all applicable regulations adopted by the United States Environmental Protection Agency (EPA).
2. Free from defects in materials and workmanship in specific emission related parts for a period of five years or 3,000 hours of operation, whichever comes first, after date of delivery to the initial owner.
If an emission-related part or component fails during the warranty period, it will be repaired or replaced. Any such part or component repaired or replaced under warranty is warranted for the warranty period.
During the term of this warranty, Thermo King will provide, through a Thermo King authorized service dealer or other establishment authorized by Thermo King, repair or replacement of any warranted part at no charge to the non-road engine owner.
In emergency, repairs may be performed at any service establishment, or by the owner, using any replacement part. Thermo King will reimburse the owner for their expenses, including diagnostic charges for such emergency repair. These expenses shall not exceed Thermo King’ s suggested retail price for all warranted parts replaced, and labor changes based on Thermo King’s recommended time allowance for the warranty repair and the geographically appropriate hourly labor rate.
19
EPA Emission Control System Warranty Statement
Thermo King warrants to the initial owner and each subsequent owner that the certified, non-road diesel engine in your unit is:
1. Designed, built and equipped so as to conform, at the time of sale, with all applicable regulations adopted by the United States Environmental Protection Agency (EPA).
2. Free from defects in materials and workmanship in specific emission related parts for a period of five years or 3,000 hours of operation, whichever comes first, after date of delivery to the initial owner.
If an emission-related part or component fails during the warranty period, it will be repaired or replaced. Any such part or component repaired or replaced under warranty is warranted for the warranty period.
During the term of this warranty, Thermo King will provide, through a Thermo King authorized service dealer or other establishment authorized by Thermo King, repair or replacement of any warranted part at no charge to the non-road engine owner.
In emergency, repairs may be performed at any service establishment, or by the owner, using any replacement part. Thermo King will reimburse the owner for their expenses, including diagnostic charges for such emergency repair. These expenses shall not exceed Thermo King’ s suggested retail price for all warranted parts replaced, and labor changes based on Thermo King’s recommended time allowance for the warranty repair and the geographically appropriate hourly labor rate.
Page 21
EPA Emission Control System Warranty Statement
20
Any replacement part can be used for maintenance or repairs. The owner should ensure that such parts are equivalent in design and durability to genuine Thermo King parts. However, Thermo King is not liable for parts that are not genuine Thermo King parts.
A part not being available within 30 days or repair not being completed within 30 days constitutes an emergency.
As a condition of reimbursement, replaced parts and received invoices must be presented at a place of business of a Thermo King authorized service dealer or other establishment authorized by Thermo King.
This warranty covers the following emission-related parts and components:
Fuel Injection System
Intake Manifold
Exhaust Manifold
Miscellaneous hoses, clamps, connectors and sealing devices used in the above systems.
If failure of one of these parts or components results in failure of another part or component, both will be covered by this warranty.
Responsibilities
This warranty is subject to the following:
Thermo King Corporation Responsibilities
During the emission warranty period, if a defect in material or workmanship of a warranted part or component is found, Thermo King will provide:
New, remanufactured, or repaired parts or components required to correct the defect.
NOTE: Items replaced under this warranty become the property of Thermo King.
Labor, during normal working hours, required to make the warranty repair. This includes diagnosis and labor to remove and install the engine, if necessary.
EPA Emission Control System Warranty Statement
20
Any replacement part can be used for maintenance or repairs. The owner should ensure that such parts are equivalent in design and durability to genuine Thermo King parts. However, Thermo King is not liable for parts that are not genuine Thermo King parts.
A part not being available within 30 days or repair not being completed within 30 days constitutes an emergency.
As a condition of reimbursement, replaced parts and received invoices must be presented at a place of business of a Thermo King authorized service dealer or other establishment authorized by Thermo King.
This warranty covers the following emission-related parts and components:
Fuel Injection System
Intake Manifold
Exhaust Manifold
Miscellaneous hoses, clamps, connectors and sealing devices used in the above systems.
If failure of one of these parts or components results in failure of another part or component, both will be covered by this warranty.
Responsibilities
This warranty is subject to the following:
Thermo King Corporation Responsibilities
During the emission warranty period, if a defect in material or workmanship of a warranted part or component is found, Thermo King will provide:
New, remanufactured, or repaired parts or components required to correct the defect.
NOTE: Items replaced under this warranty become the property of Thermo King.
Labor, during normal working hours, required to make the warranty repair. This includes diagnosis and labor to remove and install the engine, if necessary.
Page 22
EPA Emission Control System Warranty Statement
21
Owner Responsibilities
During the emission warranty period, the owner is responsible for:
The performance of all required maintenance. A warranty claim will not be denied because the scheduled maintenance was not performed. However, if the lack of required maintenance was the reason for the repair, then the claim will be denied.
Premium of overtime cost.
Cost to investigate complaints that are not caused by defects in Thermo King material or workmanship.
Providing timely notice of a warrantable failure and promptly making the product available for repair.
Limitations
Thermo King is not responsible for resultant damages to an emission-related part or component resulting from:
Any application or installation Thermo King deems improper as explained in this Operator’s Manual, or any other manuals provided for the unit.
Attachments, accessory items, or parts not authorized for use by Thermo King.
Improper off-road engine maintenance, repair or abuse.
Owners unreasonable delay in making the product available after being notified of a potential product problem.
This warranty is in addition to Thermo King’s standard warranty applicable to the off-road engine product involved.
Remedies under this warranty are limited to the provision of material and services as specified herein. Thermo King is not responsible for incidental or consequential damages such as downtime or loss of engine powered equipment.
EPA Emission Control System Warranty Statement
21
Owner Responsibilities
During the emission warranty period, the owner is responsible for:
The performance of all required maintenance. A warranty claim will not be denied because the scheduled maintenance was not performed. However, if the lack of required maintenance was the reason for the repair, then the claim will be denied.
Premium of overtime cost.
Cost to investigate complaints that are not caused by defects in Thermo King material or workmanship.
Providing timely notice of a warrantable failure and promptly making the product available for repair.
Limitations
Thermo King is not responsible for resultant damages to an emission-related part or component resulting from:
Any application or installation Thermo King deems improper as explained in this Operator’s Manual, or any other manuals provided for the unit.
Attachments, accessory items, or parts not authorized for use by Thermo King.
Improper off-road engine maintenance, repair or abuse.
Owner’s unreasonable delay in making the product available after being notified of a potential product problem.
This warranty is in addition to Thermo King’s standard warranty applicable to the off-road engine product involved.
Remedies under this warranty are limited to the provision of material and services as specified herein. Thermo King is not responsible for incidental or consequential damages such as downtime or loss of engine powered equipment.
Page 23
EPA Emission Control System Warranty Statement
22
EPA Emission Control System Warranty Statement
22
Page 24
23
Unit Description
Unit Overview
The Thermo King SB-210+/310+ is a one piece, self-contained, diesel powered, air cooling/heating unit operating under the control of a SMART REEFER 2 (SR-2) programmable microprocessor controller. The unit mounts on the front of the trailer with the evaporator extending through an opening in the front wall.
The SB-210+/310+ features cooling and heating using a quiet running engine from the Thermo King TK486 engine family.
The SB-210+ and SB-310+ are available in the following three models:
SB-210+ 30: Cooling and heating on diesel engine operation.
SB-210+ 50: Cooling and heating on diesel engine operation and electric standby operation.
SB-310+ 30: High capacity cooling and heating on diesel engine operation. Designed for engine operation at a high speed of 2600 rpm.
The Electronic Throttling Valve (ETV) provides enhanced control of the refrigeration system. The ETV is optional on the SB-210+ and standard on the SB-310+. See “Electronic Throttling Valve” on page 28.
Figure 7: Front View
23
Unit Description
Unit Overview
The Thermo King SB-210+/310+ is a one piece, self-contained, diesel powered, air cooling/heating unit operating under the control of a SMART REEFER 2 (SR-2) programmable microprocessor controller. The unit mounts on the front of the trailer with the evaporator extending through an opening in the front wall.
The SB-210+/310+ features cooling and heating using a quiet running engine from the Thermo King TK486 engine family.
The SB-210+ and SB-310+ are available in the following three models:
SB-210+ 30: Cooling and heating on diesel engine operation.
SB-210+ 50: Cooling and heating on diesel engine operation and electric standby operation.
SB-310+ 30: High capacity cooling and heating on diesel engine operation. Designed for engine operation at a high speed of 2600 rpm.
The Electronic Throttling Valve (ETV) provides enhanced control of the refrigeration system. The ETV is optional on the SB-210+ and standard on the SB-310+. See “Electronic Throttling Valve” on page 28.
Figure 7: Front View
Page 25
Unit Description
24
In addition to the quiet TK486 engine, the SB-210+/310+ includes other sound deadening components as standard and optional equipment. Among them are a special exhaust system, sound-proof insulation, special door gaskets and sound-absorbing doors. See the Design Features list below.
Design Features
The following chart lists key design features and options.
Standard Features Option/Factory installed ❏ Option/Dealer Installed
SB-210+/310+ Key Features & Options
SB-210+
Model
30
SB-210+
Model
50
SB-310+
Model
30
SMART REEFER SR-2 Controller
●●●
OptiSet™ Plus with FreshSet™ Programmable Modes
●●●
ETV (Electronic Throttling Valve)
❍❍
ServiceWatch Data Logger
●●●
CargoWatch™ Data Logger
●●●
CargoWatch Accessories:
• Door Switches / ❏❍ / ❏❍ /
• Temperature Sensor Kits
/ ❏❍ / ❏❍ / ❏
EMI-3000
●●●
High-Capacity Condenser Coil
●●●
Whisper Quiet Technology
❍❍❍
Easy-access door design
●●●
Composite Exterior Panels
●●●
SB-210+/310+ Key Features & Options
SB-210+
Model
30
SB-210+
Model
50
SB-310+
Model
30
Unit Description
24
In addition to the quiet TK486 engine, the SB-210+/310+ includes other sound deadening components as standard and optional equipment. Among them are a special exhaust system, sound-proof insulation, special door gaskets and sound-absorbing doors. See the Design Features list below.
Design Features
The following chart lists key design features and options.
Standard FeaturesOption/Factory installedOption/Dealer Installed
SB-210+/310+ Key Features & Options
SB-210+
Model
30
SB-210+
Model
50
SB-310+
Model
30
SMART REEFER SR-2 Controller
●●●
OptiSet™ Plus with FreshSet™ Programmable Modes
●●●
ETV (Electronic Throttling Valve)
❍❍●
ServiceWatch™ Data Logger
●●●
CargoWatch™ Data Logger
●●●
CargoWatch™ Accessories:
• Door Switches / ❏❍ / ❏❍ /
• Temperature Sensor Kits
/ ❏❍ / ❏❍ / ❏
EMI-3000
●●●
High-Capacity Condenser Coil
●●●
Whisper Quiet Technology
❍❍❍
Easy-access door design
●●●
Composite Exterior Panels
●●●
SB-210+/310+ Key Features & Options
SB-210+
Model
30
SB-210+
Model
50
SB-310+
Model
30
Page 26
Unit Description
25
Long-Life Coolant/Silicone Hoses
●●●
Remote Status Display
/ ❏❍ / ❏❍ /
Remote Status Display with Fuel Level
❏❏
Remote Status Display with Fuel Level and Temperature
❏❏
Standard Unit Color White
●●●
Standard Grille Color Black
●●●
Directional Air Delivery
●●●
Vibration Isolation System
●●●
Aluminum Undermount Fuel Tank 50 Gal. (186 Liter)
●●●
Fuel Level Sensor
●●●
Fuel Heater
❍❍❍
SB-210+/310+ Key Features & Options
SB-210+
Model
30
SB-210+
Model
50
SB-310+
Model
30
Frost Plug Heater
❍❍❍
Alternator, 65 Amp, 12 Vdc
❍❍❍
24 Horsepower Electric Motor
Special Color Grills
❍❍❍
Fresh Air Exchange
❍❍❍
i-Box™ Interface
/ ❏❍ / ❏❍ /
PrimAirbulkhead and duct system
❏❏❏
Rear Remote Control
❏❏❏
Humidity Sensor ❏❏❏ Megatech Battery,
12 Volt, Wet Cell
❏❏❏
EON Battery, 12 Volt, Dry Cell
❏❏❏
SB-210+/310+ Key Features & Options
SB-210+
Model
30
SB-210+
Model
50
SB-310+
Model
30
Unit Description
25
Long-Life Coolant/Silicone Hoses
●●●
Remote Status Display
/ ❏❍ / ❏❍ / ❏
Remote Status Display with Fuel Level
❏❏❏
Remote Status Display with Fuel Level and Temperature
❏❏❏
Standard Unit Color White
●●●
Standard Grille Color Black
●●●
Directional Air Delivery
●●●
Vibration Isolation System
●●●
Aluminum Undermount Fuel Tank 50 Gal. (186 Liter)
●●●
Fuel Level Sensor
●●●
Fuel Heater
❍❍❍
SB-210+/310+ Key Features & Options
SB-210+
Model
30
SB-210+
Model
50
SB-310+
Model
30
Frost Plug Heater
❍❍❍
Alternator, 65 Amp, 12 Vdc
❍❍❍
24 Horsepower Electric Motor
Special Color Grills
❍❍❍
Fresh Air Exchange
❍❍❍
i-Box™ Interface
/ ❏❍ / ❏❍ / ❏
PrimAirbulkhead and duct system
❏❏❏
Rear Remote Control
❏❏❏
Humidity Sensor ❏❏❏ Megatech Battery,
12 Volt, Wet Cell
❏❏❏
EON Battery, 12 Volt, Dry Cell
❏❏❏
SB-210+/310+ Key Features & Options
SB-210+
Model
30
SB-210+
Model
50
SB-310+
Model
30
Page 27
Unit Description
26
Diesel Engine
The Thermo King TK486 family of engines are 4-cylinder, water cooled, direct injection diesel engines. The engine is coupled directly to the compressor on the Model 30. A centrifugal clutch transfers power from the engine to the compressor on the Model 50. Belts transmit power to the unit fans, alternator and water pump.
The SB-210+ uses a TK486V (Tier2), which is designed to run with a high speed of 2200 rpm.
The SB-310+ uses a TK486VH (Tier2), which is designed to run with a high speed of 2600 rpm.
Figure 8: TK486V (TK486VH is Similar) Tier 2
Unit Description
26
Diesel Engine
The Thermo King TK486 family of engines are 4-cylinder, water cooled, direct injection diesel engines. The engine is coupled directly to the compressor on the Model 30. A centrifugal clutch transfers power from the engine to the compressor on the Model 50. Belts transmit power to the unit fans, alternator and water pump.
The SB-210+ uses a TK486V (Tier2), which is designed to run with a high speed of 2200 rpm.
The SB-310+ uses a TK486VH (Tier2), which is designed to run with a high speed of 2600 rpm.
Figure 8: TK486V (TK486VH is Similar) Tier 2
Page 28
Unit Description
27
ELC (Extended Life Coolant)
ELC (Extended Life Coolant) is standard equipment. The maintenance interval for ELC is five years or 12,000 hours. A nameplate on the coolant expansion tank identifies units with ELC (see “Safety Decals and Locations”). The new engine coolant, Chevron Extended Life Coolant, is RED in color instead of the previous GREEN or BLUE-GREEN colored conventional coolants.
NOTE: The use of 50/50% pre-mixed ELC is recommended to assure that de-ionized water is being used. If 100% full strength concentrate is used, de-ionized or distilled water is recommended instead of tap water to insure the integrity of the cooling system is maintained.
EMI 3000
EMI 3000 is an extended maintenance interval package. It is standard equipment. The EMI 3000 package consists of the following key components:
EMI 3000-Hour Cyclonic Air Cleaner Assembly and Air Cleaner Element
EMI 3000-Hour Fuel Filter (black with gold lettering)
EMI 3000-Hour Dual Element Oil Filter (black with gold lettering)
API Rating CI-4 Mineral Oil
Five Year or 12,000 Hour ELC (Extended Life Coolant)
The EMI package allows standard maintenance intervals to be extended to 3,000 hours, or 2 years, whichever occurs first.
NOTE: Units equipped with the EMI 3000 package do require regular inspection in accordance with Thermo King's maintenance recommendations.
NOTE: The new EMI 3000 oil filters and new EMI 3000 air cleaners are NOT interchangeable with the older style oil filters and air cleaners.
CAUTION: Do not add “GREEN” or “BLUE-GREEN” conventional coolant to cooling systems using “RED” Extended Life Coolant, except in an emergency. If conventional coolant is added to Extended Life Coolant, the coolant must be changed after 2 years instead of 5 years.
Unit Description
27
ELC (Extended Life Coolant)
ELC (Extended Life Coolant) is standard equipment. The maintenance interval for ELC is five years or 12,000 hours. A nameplate on the coolant expansion tank identifies units with ELC (see “Safety Decals and Locations”). The new engine coolant, Chevron Extended Life Coolant, is RED in color instead of the previous GREEN or BLUE-GREEN colored conventional coolants.
NOTE: The use of 50/50% pre-mixed ELC is recommended to assure that de-ionized water is being used. If 100% full strength concentrate is used, de-ionized or distilled water is recommended instead of tap water to insure the integrity of the cooling system is maintained.
EMI 3000
EMI 3000 is an extended maintenance interval package. It is standard equipment. The EMI 3000 package consists of the following key components:
EMI 3000-Hour Cyclonic Air Cleaner Assembly and Air Cleaner Element
EMI 3000-Hour Fuel Filter (black with gold lettering)
EMI 3000-Hour Dual Element Oil Filter (black with gold lettering)
API Rating CI-4 Mineral Oil
Five Year or 12,000 Hour ELC (Extended Life Coolant)
The EMI package allows standard maintenance intervals to be extended to 3,000 hours, or 2 years, whichever occurs first.
NOTE: Units equipped with the EMI 3000 package do require regular inspection in accordance with Thermo King's maintenance recommendations.
NOTE: The new EMI 3000 oil filters and new EMI 3000 air cleaners are NOT interchangeable with the older style oil filters and air cleaners.
CAUTION: Do not add “GREEN” or “BLUE-GREEN” conventional coolant to cooling systems using “RED” Extended Life Coolant, except in an emergency. If conventional coolant is added to Extended Life Coolant, the coolant must be changed after 2 years instead of 5 years.
Page 29
Unit Description
28
Thermo King X430L Reciprocating Compressor
The unit is equipped with a Thermo King X430L reciprocating compressor with 30 cu. in. (492 cm
3
) displacement.
Electronic Throttling Valve
The Electronic Throttling Valve (ETV) is optional on the SB-210+ and standard on the SB-310+.
The ETV provides enhanced control of the refrigeration system as follows:
Allows the refrigeration system to fully utilize the power capabilities of the engine under varying conditions
Provides an additional measure of protection against high discharge pressures
Protects the engine from high coolant temperature shutdowns
Provides a means of precise temperature control.
You can tell if the unit has an ETV by looking at the compressor. Units with an ETV have a suction valve adapter. Units without an ETV have a mechanical throttling valve.
1. Suction Valve Adapter (Has ETV)
2. Mechanical Throttling Valve (No ETV)
Figure 9: Compressors
1 2
Unit Description
28
Thermo King X430L Reciprocating Compressor
The unit is equipped with a Thermo King X430L reciprocating compressor with 30 cu. in. (492 cm
3
) displacement.
Electronic Throttling Valve
The Electronic Throttling Valve (ETV) is optional on the SB-210+ and standard on the SB-310+.
The ETV provides enhanced control of the refrigeration system as follows:
Allows the refrigeration system to fully utilize the power capabilities of the engine under varying conditions
Provides an additional measure of protection against high discharge pressures
Protects the engine from high coolant temperature shutdowns
Provides a means of precise temperature control.
You can tell if the unit has an ETV by looking at the compressor. Units with an ETV have a suction valve adapter. Units without an ETV have a mechanical throttling valve.
1. Suction Valve Adapter (Has ETV)
2. Mechanical Throttling Valve (No ETV)
Figure 9: Compressors
1 2
Page 30
Unit Description
29
SMART REEFER 2 (SR-2) Control System
The SR-2 controller is a microprocessor control system designed for transport refrigeration. The SR-2 integrates the following functions: changing setpoint and operating mode, viewing gauge, sensor and hourmeter readings, initiating defrost cycles, and viewing and clearing alarms.
The microprocessor components are located inside the control box, which is located inside the lower roadside service door. The microprocessor is connected to an HMI (Human Machine Interface) Control Panel. It is used to operate the unit. The HMI control panel is mounted on the face of the control box. It is clearly visible through an opening in the lower roadside service door.
See “Operating Instructions” for more information about the SR-2 controller.
Depending on the air temperature in the trailer, as sensed by the microprocessor controller, the unit will typically operate in one of the following modes:
CYCLE-SENTRY Operation
High Speed Cool
Low Speed Cool
Null (Engine Off)
Low Speed Heat
High Speed Heat
•Defrost
Continuous Run Operation
High Speed Cool
Low Speed Cool
Low Speed Modulated Cool (Optional SB-210+)
Low Speed Modulated Heat (Optional SB-210+)
Low Speed Heat
High Speed Heat
•Defrost
Unit Description
29
SMART REEFER 2 (SR-2) Control System
The SR-2 controller is a microprocessor control system designed for transport refrigeration. The SR-2 integrates the following functions: changing setpoint and operating mode, viewing gauge, sensor and hourmeter readings, initiating defrost cycles, and viewing and clearing alarms.
The microprocessor components are located inside the control box, which is located inside the lower roadside service door. The microprocessor is connected to an HMI (Human Machine Interface) Control Panel. It is used to operate the unit. The HMI control panel is mounted on the face of the control box. It is clearly visible through an opening in the lower roadside service door.
See “Operating Instructions” for more information about the SR-2 controller.
Depending on the air temperature in the trailer, as sensed by the microprocessor controller, the unit will typically operate in one of the following modes:
CYCLE-SENTRY Operation
High Speed Cool
Low Speed Cool
Null (Engine Off)
Low Speed Heat
High Speed Heat
•Defrost
Continuous Run Operation
High Speed Cool
Low Speed Cool
Low Speed Modulated Cool (Optional SB-210+)
Low Speed Modulated Heat (Optional SB-210+)
Low Speed Heat
High Speed Heat
•Defrost
Page 31
Unit Description
30
CYCLE-SENTRY Start-Stop Controls
The CYCLE-SENTRY Start-Stop fuel saving system provides optimum operating economy.
The CYCLE-SENTRY system automatically starts the unit on microprocessor demand, and shuts down the unit after those conditions are satisfied.
The system automatically monitors and maintains the compartment temperature, engine block temperature, and battery charge levels at a condition where quick, easy starts are possible.
WARNING: The unit can start at any time without warning. Press the O
FF
key on the HMI control panel and place the microprocessor On/Off switch in the Off position before inspecting or servicing any part of the unit.
Your Thermo King unit provides a wide range of control and programming flexibility. However, pre-programming of the unit controller may prohibit operation in certain temperature ranges within some modes and may also prohibit certain modes of operation. If you have controller programming questions, contact your supervisor or your Thermo King dealer before requesting service.
Unit Description
30
CYCLE-SENTRY Start-Stop Controls
The CYCLE-SENTRY Start-Stop fuel saving system provides optimum operating economy.
The CYCLE-SENTRY system automatically starts the unit on microprocessor demand, and shuts down the unit after those conditions are satisfied.
The system automatically monitors and maintains the compartment temperature, engine block temperature, and battery charge levels at a condition where quick, easy starts are possible.
WARNING: The unit can start at any time without warning. Press the O
FF
key on the HMI control panel and place the microprocessor On/Off switch in the Off position before inspecting or servicing any part of the unit.
Your Thermo King unit provides a wide range of control and programming flexibility. However, pre-programming of the unit controller may prohibit operation in certain temperature ranges within some modes and may also prohibit certain modes of operation. If you have controller programming questions, contact your supervisor or your Thermo King dealer before requesting service.
Page 32
Unit Description
31
Data Logging
There are two separate data loggers. The data is downloaded through the data ports on the front of the control box using an
IBM
®
PC compatible laptop or desktop computer and Thermo
King WinTrac 4.6 (or higher) software. ServiceWatch™: ServiceWatch™ is standard equipment. It
records operating events, alarm codes and compartment temperatures as they occur and at preset intervals. This information is typically used to analyze unit performance. Use the ServiceWatch Port to downloaded the ServiceWatch data.
CargoWatch™: CargoWatch™ data logging requires the installation of optional sensors. Up to six temperature sensor/probes and four door switches can be installed. CargoW atch als o logs the setpoint. Use the CargoWatch Port to downloaded the CargoWatch data. If optional temperature sensors are installed, their readings are displayed as Datalogger Sensor (1-6) T emperature in the sensor readings. See “Viewing Sensor Readings” on page 75.
A printer can also be used to print a report of the optional sensor readings. See “Printing a Trip Report” on page 90.
1. CargoWatch Port
2. ServiceWatch Port
Figure 10: HMI Controller and Data Ports
21
Unit Description
31
Data Logging
There are two separate data loggers. The data is downloaded through the data ports on the front of the control box using an
IBM
®
PC compatible laptop or desktop computer and Thermo
King WinTrac 4.6 (or higher) software. ServiceWatch™: ServiceWatch™ is standard equipment. It
records operating events, alarm codes and compartment temperatures as they occur and at preset intervals. This information is typically used to analyze unit performance. Use the ServiceWatch Port to downloaded the ServiceWatch data.
CargoWatch™: CargoWatch™ data logging requires the installation of optional sensors. Up to six temperature sensor/probes and four door switches can be installed. CargoW atch als o logs the setpoint. Use the CargoWatch Port to downloaded the CargoWatch data. If optional temperature sensors are installed, their readings are displayed as Datalogger Sensor (1-6) T emperature in the sensor readings. See “Viewing Sensor Readings” on page 75.
A printer can also be used to print a report of the optional sensor readings. See “Printing a Trip Report” on page 90.
1. CargoWatch Port
2. ServiceWatch Port
Figure 10: HMI Controller and Data Ports
21
Page 33
Unit Description
32
OptiSet Plus
OptiSet™ Plus is a group of programmable functions that control how the unit will operate with specific setpoints or named products. This assures that when a particular setpoint or named product is selected, the unit will always operate the same way. This allows an entire fleet to be configured to match the customers’ needs. Contact your Thermo King dealer for information about programming OptiSet Plus.
FreshSet
FreshSet™ is included in OptiSet Plus. FreshSet is a demand base temperature control for fresh products. FreshSet modifies and adjusts unit airflow operation to control temperature and to maximize protection of cargo, while keeping operating costs to a minimum. Contact your Thermo King dealer for information about programming FreshSet.
Defrost
Frost gradually builds-up on evaporator coils as a result of normal operation. The unit uses hot refrigerant to defrost the evaporator coil. Hot refrigerant gas passes through the evaporator coil and melts the frost. The water flows through collection drain tubes onto the ground. The methods of defrost initiation are Automatic, and Manual.
Automatic Defrost: The controller automatically initiates timed or demand defrost cycles. The controller can be programmed to initiate timed defrost cycles at intervals of 2, 4, 6, 8, or 12 hours. Demand defrost cycles occur if the differences between the return air temperature, discharge air temperature, and coil temperature exceed certain limits. The unit can enter defrost cycles as often as every 30 minutes if required.
Manual Defrost: In Manual Defrost mode, the operator initiates a defrost cycle. See “Initiating a Manual Defrost Cycle” on page 71.
Unit Description
32
OptiSet Plus
OptiSet™ Plus is a group of programmable functions that control how the unit will operate with specific setpoints or named products. This assures that when a particular setpoint or named product is selected, the unit will always operate the same way. This allows an entire fleet to be configured to match the customers’ needs. Contact your Thermo King dealer for information about programming OptiSet Plus.
FreshSet
FreshSet™ is included in OptiSet Plus. FreshSet is a demand base temperature control for fresh products. FreshSet modifies and adjusts unit airflow operation to control temperature and to maximize protection of cargo, while keeping operating costs to a minimum. Contact your Thermo King dealer for information about programming FreshSet.
Defrost
Frost gradually builds-up on evaporator coils as a result of normal operation. The unit uses hot refrigerant to defrost the evaporator coil. Hot refrigerant gas passes through the evaporator coil and melts the frost. The water flows through collection drain tubes onto the ground. The methods of defrost initiation are Automatic, and Manual.
Automatic Defrost: The controller automatically initiates timed or demand defrost cycles. The controller can be programmed to initiate timed defrost cycles at intervals of 2, 4, 6, 8, or 12 hours. Demand defrost cycles occur if the differences between the return air temperature, discharge air temperature, and coil temperature exceed certain limits. The unit can enter defrost cycles as often as every 30 minutes if required.
Manual Defrost: In Manual Defrost mode, the operator initiates a defrost cycle. See “Initiating a Manual Defrost Cycle” on page 71.
Page 34
Unit Description
33
NOTE: The unit will not perform a Manual Defrost Cycle unless the unit has been turned on with the O
N
key, the unit is running in Continuous or CYCLE-SENTRY Mode (or shut down in CYCLE-SENTRY Null Mode), and the coil temperature is below 45 F (7 C).
Unit Description
33
NOTE: The unit will not perform a Manual Defrost Cycle unless the unit has been turned on with the O
N
key, the unit is running in Continuous or CYCLE-SENTRY Mode (or shut down in CYCLE-SENTRY Null Mode), and the coil temperature is below 45 F (7 C).
Page 35
Unit Description
34
Opening the Front Doors
Pull the door latch handle to open the door and access the engine compartment.
Opening the Secondary Door Latch
These units are also equipped with a secondary door latch. A secondary door latch nameplate is located below the front doors. After opening the door latch, reach between the front doors and lift the spring latch over the spring catch while opening the door.
1. Door Latch
2. Secondary Door Latch Nameplate
Figure 11: Door Latch Location
1
2
1. Spring Latch
2. Spring Catch
Figure 12: Opening Secondary Door Latch
1
2
Unit Description
34
Opening the Front Doors
Pull the door latch handle to open the door and access the engine compartment.
Opening the Secondary Door Latch
These units are also equipped with a secondary door latch. A secondary door latch nameplate is located below the front doors. After opening the door latch, reach between the front doors and lift the spring latch over the spring catch while opening the door.
1. Door Latch
2. Secondary Door Latch Nameplate
Figure 11: Door Latch Location
1
2
1. Spring Latch
2. Spring Catch
Figure 12: Opening Secondary Door Latch
1
2
Page 36
Unit Description
35
Closing the Front Doors
Slam the door to close it. Do not push the door closed while holding the door latch handle open or the door will not close properly.
Unit Description
35
Closing the Front Doors
Slam the door to close it. Do not push the door closed while holding the door latch handle open or the door will not close properly.
Page 37
Unit Description
36
Engine Compartment Components
The following maintenance items can be checked visually.
Air Filter Restriction Indicator: The air filter restriction indicator is attached to the engine intake manifold. When the diaphragm indicates 25, service the air filter. Press the button on the bottom of the restriction indicator to reset after servicing the air cleaner.
Compressor Oil Sight Glass: Use this sight glass to check the compressor oil level. Check the compressor oil when there is evidence of oil loss (leaks). Refer to the unit Maintenance Manual for the correct procedure.
Engine Oil Dipstick: Use the engine oil dipstick to check the engine oil level.
1. Air Filter Restriction Indicator
2. Receiver Tank Sight Glass
3. Engine Oil Dipstick
4. Compressor Oil Sight Glass
Figure 13: Engine Compartment
21
34
WARNING: The unit can start at any time without warning. Press the O
FF
key on the HMI control panel and place the microprocessor On/Off switch in the Off position before inspecting any part of the unit.
CAUTION: Make sure the engine is turned off before attempting to check the engine oil.
Unit Description
36
Engine Compartment Components
The following maintenance items can be checked visually.
Air Filter Restriction Indicator: The air filter restriction indicator is attached to the engine intake manifold. When the diaphragm indicates 25, service the air filter. Press the button on the bottom of the restriction indicator to reset after servicing the air cleaner.
Compressor Oil Sight Glass: Use this sight glass to check the compressor oil level. Check the compressor oil when there is evidence of oil loss (leaks). Refer to the unit Maintenance Manual for the correct procedure.
Engine Oil Dipstick: Use the engine oil dipstick to check the engine oil level.
1. Air Filter Restriction Indicator
2. Receiver Tank Sight Glass
3. Engine Oil Dipstick
4. Compressor Oil Sight Glass
Figure 13: Engine Compartment
21
34
WARNING: The unit can start at any time without warning. Press the O
FF
key on the HMI control panel and place the microprocessor On/Off switch in the Off position before inspecting any part of the unit.
CAUTION: Make sure the engine is turned off before attempting to check the engine oil.
Page 38
Unit Description
37
Receiver Tank Sight Glass: This sight glass indicates the
level of refrigerant in the receiver tank. Operate the unit in high speed cool for approximately 15
minutes to stabilize operating conditions and temperature before attempting to check the refrigerant.
NOTE: If the ball floats, there is sufficient refrigerant in the unit for that load at that particular trailer temperature. This test does not determine if the unit contains a full charge or an overcharge of refrigerant.
Unit Protection Devices
Fuse Link (Current Limiter): The fuse link is located in the
positive battery cable. The fuse link protects the electric system from a short. If the fuse link burns out, replace it by replacing the positive battery cable.
High Pressure Cutout Switch: The high pressure cutout switch (HPCO) is located on the compressor discharge manifold. If the compressor discharge pressure becomes excessive, the switch opens the circuit to the run relay to stop the unit. The microprocessor will record Alarm Code 10.
High Pressure Relief Valve: This valve is designed to relieve excessive pressure in the refrigeration system. It is located on the receiver tank. If the high pressure relief valve opens, much of the refrigerant will be lost. Take the unit to a Thermo King dealer if this occurs.
Low Oil Level Switch: The low oil level switch closes if the oil drops below an acceptable level. If it stays closed for a specified time, the microprocessor shuts the unit down and records Alarm Code 66.
Low Oil Pressure Switch: The low oil pressure switch closes if the oil pressure drops below an acceptable level. If it stays closed for a specified time, the microprocessor shuts the unit down and records alarm code 19.
Preheat Buzzer: The preheat buzzer sounds when the controller energizes the preheat relay. This warns anyone near the unit that the controller is about to start the engine.
Unit Description
37
Receiver Tank Sight Glass: This sight glass indicates the
level of refrigerant in the receiver tank. Operate the unit in high speed cool for approximately 15
minutes to stabilize operating conditions and temperature before attempting to check the refrigerant.
NOTE: If the ball floats, there is sufficient refrigerant in the unit for that load at that particular trailer temperature. This test does not determine if the unit contains a full charge or an overcharge of refrigerant.
Unit Protection Devices
Fuse Link (Current Limiter): The fuse link is located in the
positive battery cable. The fuse link protects the electric system from a short. If the fuse link burns out, replace it by replacing the positive battery cable.
High Pressure Cutout Switch: The high pressure cutout switch (HPCO) is located on the compressor discharge manifold. If the compressor discharge pressure becomes excessive, the switch opens the circuit to the run relay to stop the unit. The microprocessor will record Alarm Code 10.
High Pressure Relief Valve: This valve is designed to relieve excessive pressure in the refrigeration system. It is located on the receiver tank. If the high pressure relief valve opens, much of the refrigerant will be lost. Take the unit to a Thermo King dealer if this occurs.
Low Oil Level Switch: The low oil level switch closes if the oil drops below an acceptable level. If it stays closed for a specified time, the microprocessor shuts the unit down and records Alarm Code 66.
Low Oil Pressure Switch: The low oil pressure switch closes if the oil pressure drops below an acceptable level. If it stays closed for a specified time, the microprocessor shuts the unit down and records alarm code 19.
Preheat Buzzer: The preheat buzzer sounds when the controller energizes the preheat relay. This warns anyone near the unit that the controller is about to start the engine.
Page 39
Unit Description
38
Overload Relay—Manual Reset (Model 50): An
overload relay protects the standby electric motor. The overload relay opens the circuit to the electric motor if the motor overloads for any reason (e.g., low line voltage or improper power supply) while the unit is on electric standby operation. The microprocessor will record Alarm Code 90. Press the reset button on the high voltage tray to reset the overload relay . The high voltage tray is located behind the lower access panel on the compressor side of the unit.
Smart FETs: Smart FETs in the controller interface board protect some circuits and components from an overcurrent condition.
Fuses: A number of fuses, located on the interface board, protect various circuits and components. The interface board is located inside the control box. Refer to the appropriate Microprocessor Controller Diagnostic Manual for more information about the fuses.
Fuse Size Function
F2 15A 2AB Power F3 40A Fuel Sol Pull-In/Starter Circuit
F4
None2ANo Fuse - All Bosch and Thermo King
Alternators
2A Fuse - All Prestolite Alternators F5 60A Preheat Circuit F6 15A Damper and High Speed Circuits
F7 2A
8XP Circuit - Controller On Feedback to
HMI F8 5A CAN Connector J12
F9 5A CAN Connector J14
F10 10A 8X Power (Install fuse in upper position) F11 10A Power to LLS1 (Not Used) F12 5A CAN Connector J13 F13 2A 8FC Circuit (Remote Lights) F15 P/S On/Off Relay F20 2A Alternator Sense F22 Not Used F23 Not Used
Fuse Size Function
Unit Description
38
Overload Relay—Manual Reset (Model 50): An
overload relay protects the standby electric motor. The overload relay opens the circuit to the electric motor if the motor overloads for any reason (e.g., low line voltage or improper power supply) while the unit is on electric standby operation. The microprocessor will record Alarm Code 90. Press the reset button on the high voltage tray to reset the overload relay . The high voltage tray is located behind the lower access panel on the compressor side of the unit.
Smart FETs: Smart FETs in the controller interface board protect some circuits and components from an overcurrent condition.
Fuses: A number of fuses, located on the interface board, protect various circuits and components. The interface board is located inside the control box. Refer to the appropriate Microprocessor Controller Diagnostic Manual for more information about the fuses.
Fuse Size Function
F2 15A 2AB Power F3 40A Fuel Sol Pull-In/Starter Circuit
F4
None2ANo Fuse - All Bosch and Thermo King
Alternators
2A Fuse - All Prestolite Alternators F5 60A Preheat Circuit F6 15A Damper and High Speed Circuits
F7 2A
8XP Circuit - Controller On Feedback to
HMI F8 5A CAN Connector J12
F9 5A CAN Connector J14
F10 10A 8X Power (Install fuse in upper position) F11 10A Power to LLS1 (Not Used) F12 5A CAN Connector J13 F13 2A 8FC Circuit (Remote Lights) F15 P/S On/Off Relay F20 2A Alternator Sense F22 Not Used F23 Not Used
Fuse Size Function
Page 40
Unit Description
39
F25 7.5A HPCO Switch Circuit
F4 Remove fuse F4 for Model 30 units with Australian Bosch or Thermo King Alternators. Install fuse F4 for Model 50 units with Prestolite Alternator.
F5 The F5 preheat fuse is a “slow blow” type. It is designed for use with the Ya nmar engine air heater. Always replace the fuse with the TK specified fuse. F10 When fuse F10 is installed in the upper position the On/Off keys on the HMI turn the unit on and off. When fuse F10 is installed in the lower position the unit will start and run without the HMI control panel.
F15 The device identified as F15 is a poly switch. These over-current devices reset automatically and are not replaceable.
Fuse Size Function
1. Control Box
Figure 14: Control Box With Service Door Open
1
Unit Description
39
F25 7.5A HPCO Switch Circuit
F4 Remove fuse F4 for Model 30 units with Australian Bosch or Thermo King Alternators. Install fuse F4 for Model 50 units with Prestolite Alternator.
F5 The F5 preheat fuse is a “slow blow” type. It is designed for use with the Ya nmar engine air heater. Always replace the fuse with the TK specified fuse. F10 When fuse F10 is installed in the upper position the On/Off keys on the HMI turn the unit on and off. When fuse F10 is installed in the lower position the unit will start and run without the HMI control panel.
F15 The device identified as F15 is a poly switch. These over-current devices reset automatically and are not replaceable.
Fuse Size Function
1. Control Box
Figure 14: Control Box With Service Door Open
1
Page 41
Unit Description
40
Figure 16: Interface Board
1. Interface Board
Figure 15: Control Box With Control Box Door Open
1
Unit Description
40
Figure 16: Interface Board
1. Interface Board
Figure 15: Control Box With Control Box Door Open
1
Page 42
41
Remote Status Display (Optional)
The remote status display mounts on the cargo box for easy viewing of the unit’s mode.
Figure 17: Remote Status Display (All LEDs Shown)
The remote status display indicates operating status as follows: White Status LEDs: Illuminate the “T” portion of the TK
logo when the unit is functioning properly with no alarm codes.
Figure 18: Normal Operation No Alarms
41
Remote Status Display (Optional)
The remote status display mounts on the cargo box for easy viewing of the unit’s mode.
Figure 17: Remote Status Display (All LEDs Shown)
The remote status display indicates operating status as follows: White Status LEDs: Illuminate the “T” portion of the TK
logo when the unit is functioning properly with no alarm codes.
Figure 18: Normal Operation No Alarms
Page 43
Remote Status Display (Optional)
42
Amber Status LEDs: Illuminate the “K” portion of the TK
logo when the unit has a check alarm code, but is still functioning properly. Check the unit as soon as possible to correct the alarm condition.
Figure 19: Check Alarm
White and Amber Status LEDs: The two bottom LEDs in
the “T” (in white) and the four bottom LEDs in the “K” (in amber) are illuminated when the unit has a shutdown alarm code and the load integrity is at risk. Correct the alarm condition immediately.
Figure 20: Shutdown Alarm
Remote Status Display (Optional)
42
Amber Status LEDs: Illuminate the “K” portion of the TK
logo when the unit has a check alarm code, but is still functioning properly. Check the unit as soon as possible to correct the alarm condition.
Figure 19: Check Alarm
White and Amber Status LEDs: The two bottom LEDs in
the “T” (in white) and the four bottom LEDs in the “K” (in amber) are illuminated when the unit has a shutdown alarm code and the load integrity is at risk. Correct the alarm condition immediately.
Figure 20: Shutdown Alarm
Page 44
Remote Status Display (Optional)
43
Remote status displays that also show the fuel level or the fuel level and the box temperature are also available. The number of white LEDs illuminated in the fuel level indicator show the fuel level. When the fuel level falls below 10%, only the two amber LEDs at the top and bottom of the fuel level indicator are illuminated to indicate the low fuel level.
The temperature display shows the box temperature, except when the unit is in defrost in which case it displays “dF”.
1. Status Indicator
2. Fuel Level Indicator
Figure 21: Remote Status Display with Fuel Level
1
2
1. Status Indicator
2. Fuel Level Indicator
3. Temperature Display
Figure 22: Remote Status Display
with Fuel Level and Temperature
1
2
3
Remote Status Display (Optional)
43
Remote status displays that also show the fuel level or the fuel level and the box temperature are also available. The number of white LEDs illuminated in the fuel level indicator show the fuel level. When the fuel level falls below 10%, only the two amber LEDs at the top and bottom of the fuel level indicator are illuminated to indicate the low fuel level.
The temperature display shows the box temperature, except when the unit is in defrost in which case it displays “dF”.
1. Status Indicator
2. Fuel Level Indicator
Figure 21: Remote Status Display with Fuel Level
1
2
1. Status Indicator
2. Fuel Level Indicator
3. Temperature Display
Figure 22: Remote Status Display
with Fuel Level and Temperature
1
2
3
Page 45
Remote Status Display (Optional)
44
Remote Status Display (Optional)
44
Page 46
45
Manual Pretrip Inspection (Before Starting the Unit)
Pretrip inspections are an important part of a preventative maintenance program designed to minimize operati ng problems and breakdowns. Perform this pretrip inspection before every trip involving refrigerated cargo.
NOTE: Pretrip inspections are not intended to take the place of regular maintenance inspections.
Fuel: Make sure the diesel fuel supply is adequate to guarantee engine operation to the next check point. Allow for maximum fuel consumption of one gallon per hour of engine operation.
Engine Oil: Check the engine oil level. It should be at the Full mark when the dipstick is threaded all the way into the oil pan. Do not overfill.
Engine Coolant: The engine coolant must have antifreeze protection to -30 F (-34 C). Add coolant if Alarm Code 37 is active. Check and add coolant to the expansion tank.
Battery: Make sure the battery terminals are tight and free of corrosion.
Belts: Make sure belts are in good condition and adjusted to the proper tension. For more information about belt tension, see the Specifications chapter.
Electrical: Check the electrical connections to make sure they are securely fastened. Wires and terminals should be free of corrosion, cracks, and moisture.
Structural: Visually inspect the unit for leaks, loose or broken parts, and other damage.
CAUTION: Turn the engine off before checking the engine oil level.
WARNING: Do not remove the expansion tank cap while the coolant is hot.
45
Manual Pretrip Inspection (Before Starting the Unit)
Pretrip inspections are an important part of a preventative maintenance program designed to minimize operati ng problems and breakdowns. Perform this pretrip inspection before every trip involving refrigerated cargo.
NOTE: Pretrip inspections are not intended to take the place of regular maintenance inspections.
Fuel: Make sure the diesel fuel supply is adequate to guarantee engine operation to the next check point. Allow for maximum fuel consumption of one gallon per hour of engine operation.
Engine Oil: Check the engine oil level. It should be at the Full mark when the dipstick is threaded all the way into the oil pan. Do not overfill.
Engine Coolant: The engine coolant must have antifreeze protection to -30 F (-34 C). Add coolant if Alarm Code 37 is active. Check and add coolant to the expansion tank.
Battery: Make sure the battery terminals are tight and free of corrosion.
Belts: Make sure belts are in good condition and adjusted to the proper tension. For more information about belt tension, see the Specifications chapter.
Electrical: Check the electrical connections to make sure they are securely fastened. Wires and terminals should be free of corrosion, cracks, and moisture.
Structural: Visually inspect the unit for leaks, loose or broken parts, and other damage.
CAUTION: Turn the engine off before checking the engine oil level.
WARNING: Do not remove the expansion tank cap while the coolant is hot.
Page 47
Manual Pretrip Inspection (Before Starting the Unit)
46
Damper: Make sure the damper in the evaporator air outlets
move freely, with no sticking or binding. Coils: Make sure the condenser and evaporator coils are clean
and free of debris. Cargo Box: Check the interior and exterior of the cargo box
for damage. Any damage to the walls or insulation must be repaired.
Cargo Doors: Make sure that the cargo doors and weather seals are in good condition. The doors should latch securely and the weather seals should fit tightly.
Defrost Drains: Check the defrost drain hoses and fittings to make sure they are open.
Manual Pretrip Inspection (Before Starting the Unit)
46
Damper: Make sure the damper in the evaporator air outlets
move freely, with no sticking or binding. Coils: Make sure the condenser and evaporator coils are clean
and free of debris. Cargo Box: Check the interior and exterior of the cargo box
for damage. Any damage to the walls or insulation must be repaired.
Cargo Doors: Make sure that the cargo doors and weather seals are in good condition. The doors should latch securely and the weather seals should fit tightly.
Defrost Drains: Check the defrost drain hoses and fittings to make sure they are open.
Page 48
47
Operating Instructions
Figure 23: SR-2 HMI Control Panel
SMART REEFER 2 (SR-2) Controller Overview
Thermo King has applied the latest advances in computer technology to develop a device that controls temperature and unit function, and displays operating information quickly and accurately.
There is nothing complicated about learning to operate the SR-2 Controller, but you will find that a few minutes studying the contents of this manual will be time well spent.
WARNING: Do not operate the unit until you are completely familiar with the location and function of each control.
47
Operating Instructions
Figure 23: SR-2 HMI Control Panel
SMART REEFER 2 (SR-2) Controller Overview
Thermo King has applied the latest advances in computer technology to develop a device that controls temperature and unit function, and displays operating information quickly and accurately.
There is nothing complicated about learning to operate the SR-2 Controller, but you will find that a few minutes studying the contents of this manual will be time well spent.
WARNING: Do not operate the unit until you are completely familiar with the location and function of each control.
Page 49
Operating Instructions
48
The microprocessor components are located inside the control box, which is located inside the lower roadside service door. The microprocessor is connected to an HMI (Human Machine Interface) Control Panel. It is used to operate the unit. The CargoWatch and ServiceWatch ports are used to retrieve data from the data logging system.
Microprocessor On/Off Switch: This switch supplies or removes electrical power to the microprocessor . It is located on the left side of the control box. See Figure 24.
1. Control Box 4. CargoWatch Port
2. Microprocessor On/Off Switch
5. HMI Control Panel
3. ServiceWatch Port
Figure 24: Control Box With Service Door Open
5
2
1
3
4
WARNING: The unit can start at any time without warning. Press the O
FF
key on the HMI control panel and place the microprocessor On/Off switch in the Off position before inspecting or servicing any part of the unit.
Operating Instructions
48
The microprocessor components are located inside the control box, which is located inside the lower roadside service door. The microprocessor is connected to an HMI (Human Machine Interface) Control Panel. It is used to operate the unit. The CargoWatch and ServiceWatch ports are used to retrieve data from the data logging system.
Microprocessor On/Off Switch: This switch supplies or removes electrical power to the microprocessor . It is located on the left side of the control box. See Figure 24.
1. Control Box 4. CargoWatch Port
2. Microprocessor On/Off Switch
5. HMI Control Panel
3. ServiceWatch Port
Figure 24: Control Box With Service Door Open
5
2
1
3
4
WARNING: The unit can start at any time without warning. Press the O
FF
key on the HMI control panel and place the microprocessor On/Off switch in the Off position before inspecting or servicing any part of the unit.
Page 50
Operating Instructions
49
HMI Control Panel
The HMI control panel has a display and eight touch sensitive keys. The display is capable of showing both text and graphics. The four keys on the left and right sides of the display are dedicated keys. The four keys under the display are “soft” keys. The function of “soft” keys change depending on the operation being performed. If a soft key is active, its function will be shown in the display directly above the key.
Control Panel Display
The display is used to supply unit information to the operator. This information includes setpoint, current box temperature operating information, unit gauge readings, system temperatures and other information as selected by the operator.
The default display is called the Standard Display. It is shown in Figure 25 and will be described in detail later in this chapter.
1. On Key (Dedicated Key)
2. Off Key (Dedicated Key)
3. Display
4. Defrost Key (Dedicated Key)
5. Mode Key (Dedicated Key)
6. Soft Keys
Figure 25: Control Panel Display and Keys
1
2
3
4 5
6
Operating Instructions
49
HMI Control Panel
The HMI control panel has a display and eight touch sensitive keys. The display is capable of showing both text and graphics. The four keys on the left and right sides of the display are dedicated keys. The four keys under the display are “soft” keys. The function of “soft” keys change depending on the operation being performed. If a soft key is active, its function will be shown in the display directly above the key.
Control Panel Display
The display is used to supply unit information to the operator. This information includes setpoint, current box temperature operating information, unit gauge readings, system temperatures and other information as selected by the operator.
The default display is called the Standard Display. It is shown in Figure 25 and will be described in detail later in this chapter.
1. On Key (Dedicated Key)
2. Off Key (Dedicated Key)
3. Display
4. Defrost Key (Dedicated Key)
5. Mode Key (Dedicated Key)
6. Soft Keys
Figure 25: Control Panel Display and Keys
1
2
3
4 5
6
Page 51
Operating Instructions
50
Control Panel Keys
The four keys on the left and right sides of the display screen are “dedicated keys” (see Figure 25). Their functions are listed below.
On Key: Press this key to turn the unit on. The Thermo King Logo screen will appear briefly. The display will then show the Standard Display of box temperature and setpoint when the unit is ready to run.
Off Key: Press this key to turn the unit off. The engine will stop immediately. Then the HMI control panel will enter the power-down sequence.
Defrost Key: Press this key to initiate a Manual Defrost cycle.
Mode Key: Press this key to switch back and forth between the CYCLE-SENTRY mode and the Continuous Run mode.
The four “soft” keys under the display are multi-purpose keys (see Figure 25). Their function changes depending on the operation being performed. If a soft key is active, it’s function will be shown in the display directly above the key.
Typical soft key applications:
• Set Point
• Gauges
• Sensors
• Menu
• Next/Back
• Yes/No
• +/–
• Up/Down
• Select/Exit
• Clear/Help
Operating Instructions
50
Control Panel Keys
The four keys on the left and right sides of the display screen are “dedicated keys” (see Figure 25). Their functions are listed below.
On Key: Press this key to turn the unit on. The Thermo King Logo screen will appear briefly. The display will then show the Standard Display of box temperature and setpoint when the unit is ready to run.
Off Key: Press this key to turn the unit off. The engine will stop immediately. Then the HMI control panel will enter the power-down sequence.
Defrost Key: Press this key to initiate a Manual Defrost cycle.
Mode Key: Press this key to switch back and forth between the CYCLE-SENTRY mode and the Continuous Run mode.
The four “soft” keys under the display are multi-purpose keys (see Figure 25). Their function changes depending on the operation being performed. If a soft key is active, it’s function will be shown in the display directly above the key.
Typical soft key applications:
• Set Point
• Gauges
• Sensors
• Menu
• Next/Back
• Yes/No
• +/–
• Up/Down
• Select/Exit
• Clear/Help
Page 52
Operating Instructions
51
Turning Unit On
Complete the following steps to turn on the unit:
1. Press the O
N
key. See Figure 26.
2. The display briefly shows a Thermo King Logo. See Figure 27.
NOTE: With extremely cold ambient temperatures it may take up to 15 seconds for the first display to appear.
3. The “Configuring System” Screen briefly appears while communications are established between the microprocessor and the HMI control panel.
4. The Standard Display showing box temperature and setpoint briefly appears.
5. The “Diesel Engine Starting” Screen briefly appears as the engine preheats and starts.
6. The Standard Display showing box temperature and setpoint reappears when the unit is running.
1. On Key
2. Display
Figure 26: Press On Key
1
2
Operating Instructions
51
Turning Unit On
Complete the following steps to turn on the unit:
1. Press the O
N
key. See Figure 26.
2. The display briefly shows a Thermo King Logo. See Figure 27.
NOTE: With extremely cold ambient temperatures it may take up to 15 seconds for the first display to appear.
3. The “Configuring System” Screen briefly appears while communications are established between the microprocessor and the HMI control panel.
4. The Standard Display showing box temperature and setpoint briefly appears.
5. The “Diesel Engine Starting” Screen briefly appears as the engine preheats and starts.
6. The Standard Display showing box temperature and setpoint reappears when the unit is running.
1. On Key
2. Display
Figure 26: Press On Key
1
2
Page 53
Operating Instructions
52
Figure 27: Turning Unit On Screen Sequence
Operating Instructions
52
Figure 27: Turning Unit On Screen Sequence
Page 54
Operating Instructions
53
Turning Unit Off
Complete the following steps to turn unit off:
1. Press the O
FF
key.
2. The engine will immediately shut off.
3. The “System is Powering Down” Screen will briefly appear.
4. The Off Screen will briefly appear.
5. The screen goes blank when the unit power is off.
Figure 29: Turning Unit Off Screen Sequence
1. Off Key
2. Display
Figure 28: Press Off Key
1
2
Operating Instructions
53
Turning Unit Off
Complete the following steps to turn unit off:
1. Press the O
FF
key.
2. The engine will immediately shut off.
3. The “System is Powering Down” Screen will briefly appear.
4. The Off Screen will briefly appear.
5. The screen goes blank when the unit power is off.
Figure 29: Turning Unit Off Screen Sequence
1. Off Key
2. Display
Figure 28: Press Off Key
1
2
Page 55
Operating Instructions
54
Standard Display
The Standard Display is the default display. It appears if no other display function is selected. The Standard Display shows the box temperature and setpoint. The box temperature is measured by the controlling sensor . The return air sens or is the controlling sensor except when the controller is programmed to use the discharge air sensor as the controlling sensor during modulation. The box temperature shown below in Figure 30 is
35.5 F. The setpoint shown is 35 F. The CYCLE-SENTRY Icon in the upper right corner of the display shows the unit is operating in the CYCLE-SENTRY mode. The arrow pointing down indicates the unit is cooling.
NOTE: The CYCLE-SENTRY icon will appears when the unit is operating in CYCLE-SENTRY mode as shown below. If the CYCLE-SENTRY icon is not present the unit is operating in Continuous mode.
1. Box Temperature 3. CYCLE-SENTRY Icon
2. Cooling 4. Setpoint
Figure 30: Standard Display
1
4
3
2
Operating Instructions
54
Standard Display
The Standard Display is the default display. It appears if no other display function is selected. The Standard Display shows the box temperature and setpoint. The box temperature is measured by the controlling sensor . The return air sens or is the controlling sensor except when the controller is programmed to use the discharge air sensor as the controlling sensor during modulation. The box temperature shown below in Figure 30 is
35.5 F. The setpoint shown is 35 F. The CYCLE-SENTRY Icon in the upper right corner of the display shows the unit is operating in the CYCLE-SENTRY mode. The arrow pointing down indicates the unit is cooling.
NOTE: The CYCLE-SENTRY icon will appears when the unit is operating in CYCLE-SENTRY mode as shown below. If the CYCLE-SENTRY icon is not present the unit is operating in Continuous mode.
1. Box Temperature 3. CYCLE-SENTRY Icon
2. Cooling 4. Setpoint
Figure 30: Standard Display
1
4
3
2
Page 56
Operating Instructions
55
Standard Display Variations
The Standard Display has variations. A display showing any of the following variations is still considered a Standard Display (see Figure 31).
The top of the display may show a named product if the controller has been programmed with OptiSet Plus temperature profiles. The far left soft key may display P
RODUCT
or
P
RODUCT/SETPOINT
if the controller has been programmed with OptiSet Plus temperature profiles. See “OptiSet Pluson page 115 for information about selecting or changing the named product or the setpoint if the controller has been programmed with OptiSet Plus temperature profiles. Contact your Thermo King dealer for information about programming the controller with OptiSet Plus temperature profiles.
The temperature can be displayed in degrees Fahrenheit (F) or degrees Celsius (C). An arrow pointing upwards indicates the unit is heating. An arrow pointing downwards indicates the unit is cooling.
1. Named Product
2. Heating
3. P
RODUCT
or P
RODUCT/SETPOINT
Soft Key
4. Degrees Celsius
5. Cooling
6. Degrees Fahrenheit
Figure 31: Standard Display Variations
4
2
1
6
5
3
Operating Instructions
55
Standard Display Variations
The Standard Display has variations. A display showing any of the following variations is still considered a Standard Display (see Figure 31).
The top of the display may show a named product if the controller has been programmed with OptiSet Plus temperature profiles. The far left soft key may display P
RODUCT
or
P
RODUCT/SETPOINT
if the controller has been programmed with OptiSet Plus temperature profiles. See “OptiSet Plus” on page 115 for information about selecting or changing the named product or the setpoint if the controller has been programmed with OptiSet Plus temperature profiles. Contact your Thermo King dealer for information about programming the controller with OptiSet Plus temperature profiles.
The temperature can be displayed in degrees Fahrenheit (F) or degrees Celsius (C). An arrow pointing upwards indicates the unit is heating. An arrow pointing downwards indicates the unit is cooling.
1. Named Product
2. Heating
3. P
RODUCT
or P
RODUCT/SETPOINT
Soft Key
4. Degrees Celsius
5. Cooling
6. Degrees Fahrenheit
Figure 31: Standard Display Variations
4
2
1
6
5
3
Page 57
Operating Instructions
56
Temperature Watch Display
The Standard Display defaults to the Temperature Watch Display after about 2-1/2 minutes of non-use (when no keys are pressed). The Temperature Watch Display shows the same box temperature and setpoint but in larger fonts. This creates easy operator viewing from a distance. To return to the Standard Display press the M
ENU
soft key (or any of the other
three soft keys that are not assigned).
NOTE: A named product may appear above the temperature reading if the controller has been programmed with OptiSet Plus temperature profiles and a named product has been selected.
NOTE: The CYCLE-SENTRY icon will appear in the Temperature Watch display when the unit is operating in CYCLE-SENTRY mode as shown below. If the CYCLE-SENTRY icon is not present the unit is operating in Continuous mode.
1. Named Product (If Selected)
2. CYCLE-SENTRY Icon
3. Menu Soft Key
Figure 32: Temperature Watch Display
2
3
1
Operating Instructions
56
Temperature Watch Display
The Standard Display defaults to the Temperature Watch Display after about 2-1/2 minutes of non-use (when no keys are pressed). The Temperature Watch Display shows the same box temperature and setpoint but in larger fonts. This creates easy operator viewing from a distance. To return to the Standard Display press the M
ENU
soft key (or any of the other
three soft keys that are not assigned).
NOTE: A named product may appear above the temperature reading if the controller has been programmed with OptiSet Plus temperature profiles and a named product has been selected.
NOTE: The CYCLE-SENTRY icon will appear in the Temperature Watch display when the unit is operating in CYCLE-SENTRY mode as shown below. If the CYCLE-SENTRY icon is not present the unit is operating in Continuous mode.
1. Named Product (If Selected)
2. CYCLE-SENTRY Icon
3. Menu Soft Key
Figure 32: Temperature Watch Display
2
3
1
Page 58
Operating Instructions
57
Alarm Display
If a unit alarm condition occurs the large Alarm Icon will appear on the Standard Display as shown below in Figure 33.
NOTE: A shutdown alarm will also cause the display and backlight to flash on and off, and the display will switch from normal video to reverse video and back to normal video (light areas become dark and dark areas become light).
See “Alarms Menu” on page 85 for information about displaying and clearing alarms.
1. Alarm Icon
2. Named Product (If Selected)
Figure 33: Alarm Display
1
2
Operating Instructions
57
Alarm Display
If a unit alarm condition occurs the large Alarm Icon will appear on the Standard Display as shown below in Figure 33.
NOTE: A shutdown alarm will also cause the display and backlight to flash on and off, and the display will switch from normal video to reverse video and back to normal video (light areas become dark and dark areas become light).
See “Alarms Menu” on page 85 for information about displaying and clearing alarms.
1. Alarm Icon
2. Named Product (If Selected)
Figure 33: Alarm Display
1
2
Page 59
Operating Instructions
58
Starting the Diesel Engine
Diesel engine preheats and starts automatically in both Continuous Mode and CYCLE-SENTRY mode. The engine will preheat and start if necessary when the unit is turned on. The engine preheat and start will be delayed in CYCLE-SENTRY mode if there is no current need for the engine to run. If a key or sequence of keys are pressed on the controller before the engine starts, the engine will preheat and start approximately 10 seconds after pressing the last key.
See “Turning Unit On” on page 51.
NOTE: Run a pretrip test if the unit has not been used recently. See “Pretrip Tests” on page 104.
Unit Fails To Start
If the engine does not start and the Alarm Icon appears on the display, take the following steps.
1. Check for and correct any alarm conditions. See “Viewing and Clearing Alarms Screen Sequence” on page 87.
2. Clear all alarms. See “Viewing and Clearing Alarms Screen Sequence” on page 87.
3. Press the O
FF
key to turn the unit off.
4. Press the O
N
key to turn the unit on.
5. The controller will go through the start up screens and then after a 10 second delay the unit will start automatically.
6. If the engine will still not start, turn the unit off. Determine and correct the cause for not starting.
7. Repeat the procedure.
CAUTION: The engine may start automatically any time the unit is turned on.
WARNING: Never use starting fluid.
Operating Instructions
58
Starting the Diesel Engine
Diesel engine preheats and starts automatically in both Continuous Mode and CYCLE-SENTRY mode. The engine will preheat and start if necessary when the unit is turned on. The engine preheat and start will be delayed in CYCLE-SENTRY mode if there is no current need for the engine to run. If a key or sequence of keys are pressed on the controller before the engine starts, the engine will preheat and start approximately 10 seconds after pressing the last key.
See “Turning Unit On” on page 51.
NOTE: Run a pretrip test if the unit has not been used recently. See “Pretrip Tests” on page 104.
Unit Fails To Start
If the engine does not start and the Alarm Icon appears on the display, take the following steps.
1. Check for and correct any alarm conditions. See “Viewing and Clearing Alarms Screen Sequence” on page 87.
2. Clear all alarms. See “Viewing and Clearing Alarms Screen Sequence” on page 87.
3. Press the O
FF
key to turn the unit off.
4. Press the O
N
key to turn the unit on.
5. The controller will go through the start up screens and then after a 10 second delay the unit will start automatically.
6. If the engine will still not start, turn the unit off. Determine and correct the cause for not starting.
7. Repeat the procedure.
CAUTION: The engine may start automatically any time the unit is turned on.
WARNING: Never use starting fluid.
Page 60
Operating Instructions
59
After Start Inspection
After the unit is running, check the following items to confirm that the unit is running properly.
Oil Pressure: Check the engine oil pressure by pressing the G
AUGES
soft key. See “Viewing Gauge Readings” on page 73.
The Engine Oil Pressure Display should indicate OK not LOW .
Ammeter: Check the ammeter reading by pressing the G
AUGES
soft key. See “Viewing Gauge Readings” on page 73. The Amps Display should indicate a positive charge amperage rate to the battery. A negative (-) number indicates a discharge condition.
Compressor Oil: The compressor oil level should be visible in the compressor sight glass after 15 minutes of operation. If not, check the compressor oil level using the procedure in the appropriate maintenance manual.
Pre-Cooling: Make sure that the setpoint is at the desired temperature. See “Changing the Setpoint” on page 65. Allow the unit to run for a minimum of 30 minutes (longer if possible) before loading the trailer.
This provides a good test of the refrigeration system while removing residual heat and the moisture from the trailer interior to prepare it for a refrigerated load.
Defrost: When the unit has finished pre-cooling the trailer interior, manually initiate a Defrost cycle. See “Initiating a Manual Defrost Cycle” on page 71. This will remove the frost that builds up while running the unit to pre-cool the trailer.
Operating Instructions
59
After Start Inspection
After the unit is running, check the following items to confirm that the unit is running properly.
Oil Pressure: Check the engine oil pressure by pressing the G
AUGES
soft key. See “Viewing Gauge Readings” on page 73. The Engine Oil Pressure Display should indicate OK not LOW .
Ammeter: Check the ammeter reading by pressing the G
AUGES
soft key. See “Viewing Gauge Readings” on page 73. The Amps Display should indicate a positive charge amperage rate to the battery. A negative (-) number indicates a discharge condition.
Compressor Oil: The compressor oil level should be visible in the compressor sight glass after 15 minutes of operation. If not, check the compressor oil level using the procedure in the appropriate maintenance manual.
Pre-Cooling: Make sure that the setpoint is at the desired temperature. See “Changing the Setpoint” on page 65. Allow the unit to run for a minimum of 30 minutes (longer if possible) before loading the trailer.
This provides a good test of the refrigeration system while removing residual heat and the moisture from the trailer interior to prepare it for a refrigerated load.
Defrost: When the unit has finished pre-cooling the trailer interior, manually initiate a Defrost cycle. See “Initiating a Manual Defrost Cycle” on page 71. This will remove the frost that builds up while running the unit to pre-cool the trailer.
Page 61
Operating Instructions
60
Electric Standby Operation
Model 50 units are equipped with Electric Standby. This feature allows the unit to operate on electric power as well as be powered by the standard diesel engine.
During Electric Standby operation, power to the unit is supplied by an electric motor connected to a high voltage power source. The required voltage is shown on a decal on the unit’s electric power receptacle.
Electric Power Receptacle: The electric power receptacle is used to connect the unit to an appropriate electric power source for electric standby operation. The electric power receptacle is located next to the HMI Control Panel. Make sure the unit and the power supply are turned off before connecting or disconnecting a power cord.
Figure 34: Electric Power Receptacle
W ARNING: Units equipped with electric standby may start at any time when the unit is connected to live electric power and the controller is turned on.
CAUTION: Always turn the electric power supply off when handling, connecting, or disconnecting high voltage power cords.
CAUTION: Do not start the electric drive motor unless the diesel engine is completely stopped.
Operating Instructions
60
Electric Standby Operation
Model 50 units are equipped with Electric Standby. This feature allows the unit to operate on electric power as well as be powered by the standard diesel engine.
During Electric Standby operation, power to the unit is supplied by an electric motor connected to a high voltage power source. The required voltage is shown on a decal on the unit’s electric power receptacle.
Electric Power Receptacle: The electric power receptacle is used to connect the unit to an appropriate electric power source for electric standby operation. The electric power receptacle is located next to the HMI Control Panel. Make sure the unit and the power supply are turned off before connecting or disconnecting a power cord.
Figure 34: Electric Power Receptacle
W ARNING: Units equipped with electric standby may start at any time when the unit is connected to live electric power and the controller is turned on.
CAUTION: Always turn the electric power supply off when handling, connecting, or disconnecting high voltage power cords.
CAUTION: Do not start the electric drive motor unless the diesel engine is completely stopped.
Page 62
Operating Instructions
61
Starting the Unit on Electric Standby Operation
Units equipped with the Electric Standby option only. Electric motor starting is automatic in both Continuous Mode
and Cycle Sentry Mode. The motor will start as required when the unit is turned on. If any keys are being pressed on the HMI control panel prior to the motor start, the motor start will be delayed until 10 seconds after the last key is pressed. Start the unit on Electric Standby operation as follows:
1. Press the controller O
FF
key to make sure the unit is
turned off.
2. Connect the unit electric power receptacle to an
appropriate electric power supply.
3. Press the controller O
N
key.
4. If a screen asking if you wish to switch to Electric Standby
appears, press the Y
ES
soft key. This screen does not appear if the controller is programmed to automatically switch from Diesel to Electric Standby, or if the unit was in Electric Standby when it was turned off.
Figure 35: Electric Standby Detected Screen
CAUTION: The motor may start automatically any time the unit is turned on.
Operating Instructions
61
Starting the Unit on Electric Standby Operation
Units equipped with the Electric Standby option only. Electric motor starting is automatic in both Continuous Mode
and Cycle Sentry Mode. The motor will start as required when the unit is turned on. If any keys are being pressed on the HMI control panel prior to the motor start, the motor start will be delayed until 10 seconds after the last key is pressed. Start the unit on Electric Standby operation as follows:
1. Press the controller O
FF
key to make sure the unit is
turned off.
2. Connect the unit electric power receptacle to an appropriate electric power supply.
3. Press the controller O
N
key.
4. If a screen asking if you wish to switch to Electric Standby
appears, press the Y
ES
soft key. This screen does not appear if the controller is programmed to automatically switch from Diesel to Electric Standby, or if the unit was in Electric Standby when it was turned off.
Figure 35: Electric Standby Detected Screen
CAUTION: The motor may start automatically any time the unit is turned on.
Page 63
Operating Instructions
62
5. If the microprocessor determines that the unit should cool or heat, the motor start screen appears as shown below. The preheat buzzer sounds for 20 seconds before the electric motor starts. It may not start if the return air sensor temperature is within a few degrees of setpoint. The electric motor cycles on and off in CYCLE-SENTRY Mode and runs continuously in Continuous Mode.
Figure 36: Electric Motor Starting Screen
6. Complete an After Start Inspection (see page 59).
Unit Fails to Start
If the electric motor does not start and the Alarm Icon appears on the display, take the following steps.
1. Check for and correct any alarm conditions. See “Viewing and Clearing Alarms Screen Sequence” on page 87.
2. Clear all alarms. See “Viewing and Clearing Alarms Screen Sequence” on page 87.
3. Press the Controller O
FF
key.
4. Press the Controller O
N
key.
5. If the unit still does not start, repeat the above steps.
ELECTRIC MOTOR STARTING
ARA909
Operating Instructions
62
5. If the microprocessor determines that the unit should cool or heat, the motor start screen appears as shown below. The preheat buzzer sounds for 20 seconds before the electric motor starts. It may not start if the return air sensor temperature is within a few degrees of setpoint. The electric motor cycles on and off in CYCLE-SENTRY Mode and runs continuously in Continuous Mode.
Figure 36: Electric Motor Starting Screen
6. Complete an After Start Inspection (see page 59).
Unit Fails to Start
If the electric motor does not start and the Alarm Icon appears on the display, take the following steps.
1. Check for and correct any alarm conditions. See “Viewing and Clearing Alarms Screen Sequence” on page 87.
2. Clear all alarms. See “Viewing and Clearing Alarms Screen Sequence” on page 87.
3. Press the Controller O
FF
key.
4. Press the Controller O
N
key.
5. If the unit still does not start, repeat the above steps.
ELECTRIC MOTOR STARTING
ARA909
Page 64
Operating Instructions
63
Switching from Diesel to Electric
Units equipped with the Electric Standby option only If the Diesel to Electric Autoswitch Enabled feature in
Guarded Access is set YES then the unit will automatically switch to Electric Mode operation when standby power is connected and available.
If the Diesel to Electric Autoswitch Enabled feature in Guarded Access is set NO, then the prompt screen shown below will appear when standby power is connected and available.
Figure 37: Electric Standby Detected Screen
If YES is selected then the display will briefly show the screen below.
Figure 38: Programming Electric Standby Screen
Electric Mode operation will briefly be confirmed. If unit operation is required the electric motor will start as shown in “Starting the Unit on Electric Standby Operation” on page 61.
Operating Instructions
63
Switching from Diesel to Electric
Units equipped with the Electric Standby option only If the Diesel to Electric Autoswitch Enabled feature in
Guarded Access is set YES then the unit will automatically switch to Electric Mode operation when standby power is connected and available.
If the Diesel to Electric Autoswitch Enabled feature in Guarded Access is set NO, then the prompt screen shown below will appear when standby power is connected and available.
Figure 37: Electric Standby Detected Screen
If YES is selected then the display will briefly show the screen below.
Figure 38: Programming Electric Standby Screen
Electric Mode operation will briefly be confirmed. If unit operation is required the electric motor will start as shown in “Starting the Unit on Electric Standby Operation” on page 61.
Page 65
Operating Instructions
64
Switching from Electric to Diesel
Units equipped with the Electric Standby option only If the Electric to Diesel Autoswitch Enabled feature in
Guarded Access is set YES then the unit will automatically switch to Diesel Mode operation when standby power is turned off or is no longer available.
If the Electric to Diesel Autoswitch Enabled feature in Guarded Access is set NO then the prompt screen shown below will appear when standby power is turned off or is no longer available.
Figure 39: Electric Standby Undetected Screen
If YES is selected then the display will briefly show the screen below.
Figure 40: Programming Diesel Mode Screen
Diesel Mode operation will briefly be confirmed. If unit operation is required the diesel engine will start as shown in “Starting the Diesel Engine” on page 58.
ELECTRIC STANDBY UNDETECTED
DO YOU WISH TO SWITCH TO
DIESEL?
NOYES
ARA910
PROGRAMMING DIESEL MODE
PLEASE WAIT
ARA911
Operating Instructions
64
Switching from Electric to Diesel
Units equipped with the Electric Standby option only If the Electric to Diesel Autoswitch Enabled feature in
Guarded Access is set YES then the unit will automatically switch to Diesel Mode operation when standby power is turned off or is no longer available.
If the Electric to Diesel Autoswitch Enabled feature in Guarded Access is set NO then the prompt screen shown below will appear when standby power is turned off or is no longer available.
Figure 39: Electric Standby Undetected Screen
If YES is selected then the display will briefly show the screen below.
Figure 40: Programming Diesel Mode Screen
Diesel Mode operation will briefly be confirmed. If unit operation is required the diesel engine will start as shown in “Starting the Diesel Engine” on page 58.
ELECTRIC STANDBY UNDETECTED
DO YOU WISH TO SWITCH TO
DIESEL?
NOYES
ARA910
PROGRAMMING DIESEL MODE
PLEASE WAIT
ARA911
Page 66
Operating Instructions
65
Changing the Setpoint
To change the setpoint complete the following steps.
NOTE: If the S
ETPOINT
soft key (far left) displays P
RODUCT
or P
RODUCT/SETPOINT
, the controller has been programmed
with OptiSet Plus temperature profiles. See “OptiSet Plus on page 115 for information about selecting or changing the named product or the setpoint.
1. Begin at the Standard Display. If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display.
2. Press the S
ETPOINT
soft key on the Standard Display. See Figure 41. The “Setpoint” Screen briefly appears, then the “Current Setpoint” Screen appears. See Figure 42.
3. Press the + or - soft keys to change the setpoint reading.
See Figure 42.
4. Press the Y
ES
or NOsoft key accordingly as described
below. See Figure 42.
•If the N
O
key is pressed the setpoint change made with the
“+” or “-” soft keys will not be accepted, the setpoint will not be changed and the display will return to the Standard Display.
•If the Y
ES
soft key is pressed, the setpoint change made with the “+” or “-” soft keys will be accepted, and the following screens will appear.
1. Standard Display
2. Setpoint Soft Key
Figure 41: Changing Setpoint
1
2
Operating Instructions
65
Changing the Setpoint
To change the setpoint complete the following steps.
NOTE: If the S
ETPOINT
soft key (far left) displays P
RODUCT
or P
RODUCT/SETPOINT
, the controller has been programmed
with OptiSet Plus temperature profiles. See “OptiSet Plus” on page 115 for information about selecting or changing the named product or the setpoint.
1. Begin at the Standard Display. If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display.
2. Press the S
ETPOINT
soft key on the Standard Display. See Figure 41. The “Setpoint” Screen briefly appears, then the “Current Setpoint” Screen appears. See Figure 42.
3. Press the + or - soft keys to change the setpoint reading.
See Figure 42.
4. Press the Y
ES
or NOsoft key accordingly as described
below. See Figure 42.
•If the N
O
key is pressed the setpoint change made with the
“+” or “-” soft keys will not be accepted, the setpoint will not be changed and the display will return to the Standard Display.
•If the Y
ES
soft key is pressed, the setpoint change made with the “+” or “-” soft keys will be accepted, and the following screens will appear.
1. Standard Display
2. Setpoint Soft Key
Figure 41: Changing Setpoint
1
2
Page 67
Operating Instructions
66
NOTE: Alarm Code 127 “Setpoint Not Entered” may be generated if the + or - soft keys are used to change the setpoint, but the Y
ES
or NO soft keys are not used to
accept or decline the new setpoint.
5. The “Programming New Setpoint” Screen will appear. See Figure 42.
6. The “New Setpoint Is XX” Screen briefly appears. See Figure 42.
7. The Standard Display appears with setpoint changed to the new setpoint. See Figure 42.
Operating Instructions
66
NOTE: Alarm Code 127 “Setpoint Not Entered” may be generated if the + or - soft keys are used to change the setpoint, but the Y
ES
or NO soft keys are not used to
accept or decline the new setpoint.
5. The “Programming New Setpoint” Screen will appear. See Figure 42.
6. The “New Setpoint Is XX” Screen briefly appears. See Figure 42.
7. The Standard Display appears with setpoint changed to the new setpoint. See Figure 42.
Page 68
Operating Instructions
67
Figure 42: Changing the Setpoint Screen Sequence
If YES Key was pressed If NO Key was pressed
S
ETPOINT
Key
+ or Key
Y
ES
or NO Key
Operating Instructions
67
Figure 42: Changing the Setpoint Screen Sequence
If YES Key was pressed If NO Key was pressed
S
ETPOINT
Key
+ or Key
Y
ES
or NO Key
Page 69
Operating Instructions
68
Selection of Operating Modes
The Thermo King CYCLE-SENTRY system is designed to save refrigeration fuel costs. The savings vary with the commodity, ambient temperatures and trailer insulation. However, not all temperature controlled products can be properly transported using CYCLE-SENTRY operation. Certain highly sensitive products normally require continuous air circulation.Use the following guidelines to select the proper operating mode to protect the commodity you are transporting.
Examples of products normally acceptable for CYCLE-SENTRY Operation:
Frozen foods (in adequately insulated trailers)
Boxed or processed meats Poultry
•Fish
Dairy products
Candy
Chemicals
•Film
All non-edible products.
Examples of products normally requiring Continuous Run Operation for air flow:
Fresh fruits and vegetables, especially asparagus, bananas, broccoli, carrots, citrus, green peas, lettuce, peaches, spinach, strawberries, sweet corn, etc.
Non-processed meat products (unless pre-cooled to recommended temperature).
Fresh flowers and foliage.
The above listings are not all inclusive. Consult your grower or shipper if you have any questions about the operating mode selection of your type of load.
Operating Instructions
68
Selection of Operating Modes
The Thermo King CYCLE-SENTRY system is designed to save refrigeration fuel costs. The savings vary with the commodity, ambient temperatures and trailer insulation. However, not all temperature controlled products can be properly transported using CYCLE-SENTRY operation. Certain highly sensitive products normally require continuous air circulation.Use the following guidelines to select the proper operating mode to protect the commodity you are transporting.
Examples of products normally acceptable for CYCLE-SENTRY Operation:
Frozen foods (in adequately insulated trailers)
Boxed or processed meats Poultry
•Fish
Dairy products
Candy
Chemicals
•Film
All non-edible products.
Examples of products normally requiring Continuous Run Operation for air flow:
Fresh fruits and vegetables, especially asparagus, bananas, broccoli, carrots, citrus, green peas, lettuce, peaches, spinach, strawberries, sweet corn, etc.
Non-processed meat products (unless pre-cooled to recommended temperature).
Fresh flowers and foliage.
The above listings are not all inclusive. Consult your grower or shipper if you have any questions about the operating mode selection of your type of load.
Page 70
Operating Instructions
69
Selecting CYCLE-SENTRY or Continuous Mode
When CYCLE-SENTRY mode is selected the unit will start and stop automatically to maintain the setpoint, keep the engine warm, and the battery charged. When Continuous mode is selected, the unit will start automatically and run continuously to maintain setpoint and provide constant airflow. CYCLE-SENTRY or Continuous may not be available if OptiSet Plus is in use.
If allowed by OptiSet Plus, complete the following steps to change modes:
NOTE: The mode can also be changed using the Mode Menu Screen in the Main Menu. See “Turning CYCLE-SENTRY On or Off” on page 97.
1. Press the M
ODE
key. See Figure 43.
2. The “Programming Continuous Mode” or “Programming CYCLE-SENTRY Mode” Screen briefly appears. See Figure 44 and Figure 45.
3. The “New System Mode is Continuous” Screen or the “New System Mode CYCLE-SENTRY” Screen briefly appears. See Figure 44 and Figure 45.
4. The Standard Display appears showing the new mode. See Figure 44 and Figure 45.
5. Press the M
ODE
key again to change the unit back to the
previous mode.
1. CYCLE-SENTRY Icon Shows Mode Selected Displayed for CYCLE-SENTRY Mode Not Displayed for Continuous Mode
2. Mode Key
Figure 43: Changing Mode
1
2
Operating Instructions
69
Selecting CYCLE-SENTRY or Continuous Mode
When CYCLE-SENTRY mode is selected the unit will start and stop automatically to maintain the setpoint, keep the engine warm, and the battery charged. When Continuous mode is selected, the unit will start automatically and run continuously to maintain setpoint and provide constant airflow. CYCLE-SENTRY or Continuous may not be available if OptiSet Plus is in use.
If allowed by OptiSet Plus, complete the following steps to change modes:
NOTE: The mode can also be changed using the Mode Menu Screen in the Main Menu. See “Turning CYCLE-SENTRY On or Off” on page 97.
1. Press the M
ODE
key. See Figure 43.
2. The “Programming Continuous Mode” or “Programming CYCLE-SENTRY Mode” Screen briefly appears. See Figure 44 and Figure 45.
3. The “New System Mode is Continuous” Screen or the “New System Mode CYCLE-SENTRY” Screen briefly appears. See Figure 44 and Figure 45.
4. The Standard Display appears showing the new mode. See Figure 44 and Figure 45.
5. Press the M
ODE
key again to change the unit back to the
previous mode.
1. CYCLE-SENTRY Icon Shows Mode Selected Displayed for CYCLE-SENTRY Mode Not Displayed for Continuous Mode
2. Mode Key
Figure 43: Changing Mode
1
2
Page 71
Operating Instructions
70
Figure 44: Screen Sequence for Changing from
CYCLE-SENTRY Mode to Continuous Mode
Figure 45: Screen Sequence for Changing from
Continuous Mode to CYCLE-SENTRY Mode
Operating Instructions
70
Figure 44: Screen Sequence for Changing from
CYCLE-SENTRY Mode to Continuous Mode
Figure 45: Screen Sequence for Changing from
Continuous Mode to CYCLE-SENTRY Mode
Page 72
Operating Instructions
71
Initiating a Manual Defrost Cycle
Defrost cycles are usually initiated automatically based on time or temperature. Manual Defrost is also available if the unit is running and the coil temperature is less than 45 F (7 C). Other features such as door switch settings may not allow Manual Defrost to be initiated.
Use the following steps to initiate a Manual Defrost:
1. Press the D
EFROST
key. See Figure 46.
2. The “Defrost” Screen briefly appears. See Figure 47.
3. The “Programming Defrost” Screen briefly appears. See Figure 47.
4. The “Defrost Started” Screen briefly appears. See Figure
47.
1. St andard Display
2. Defrost Key
Figure 46: Initiating a Manual Defrost Cycle
1
2
Operating Instructions
71
Initiating a Manual Defrost Cycle
Defrost cycles are usually initiated automatically based on time or temperature. Manual Defrost is also available if the unit is running and the coil temperature is less than 45 F (7 C). Other features such as door switch settings may not allow Manual Defrost to be initiated.
Use the following steps to initiate a Manual Defrost:
1. Press the D
EFROST
key. See Figure 46.
2. The “Defrost” Screen briefly appears. See Figure 47.
3. The “Programming Defrost” Screen briefly appears. See Figure 47.
4. The “Defrost Started” Screen briefly appears. See Figure
47.
1. St andard Display
2. Defrost Key
Figure 46: Initiating a Manual Defrost Cycle
1
2
Page 73
Operating Instructions
72
5. A modified Standard Display appears. The bar indicator will fill in showing time remaining to complete the Defrost cycle. The bar indicator in the figure shows that the Defrost cycle is 50% complete. When the Defrost cycle is complete the display returns to the Standard Display . See Figure 47.
If the unit is prevented from going into a Manual Defrost (IE: Coil temperature more than 45 F (7 C) or on economy mode etc.). A “Defrost Unavailable” Screen briefly appears. The display returns to the Standard Display. See Figure 47.
Terminating a Defrost Cycle
The Defrost cycle will terminate automatically when the coil temperature reaches 58 F (14 C), or when the defrost timer expires. The defrost timer is normally set for 45 minutes, but can be set for 30 minutes. Defrost can also be terminated by turning the unit off.
NOTE: If the defrost timer consistently terminates Defrost because the evaporator coil temperature fails to reach 58 F (14 C), have the unit checked by a Thermo King dealer to see if it is working properly.
Figure 47: Initiating Manual Defrost Screen Sequence
or
Operating Instructions
72
5. A modified Standard Display appears. The bar indicator will fill in showing time remaining to complete the Defrost cycle. The bar indicator in the figure shows that the Defrost cycle is 50% complete. When the Defrost cycle is complete the display returns to the Standard Display . See Figure 47.
If the unit is prevented from going into a Manual Defrost (IE: Coil temperature more than 45 F (7 C) or on economy mode etc.). A “Defrost Unavailable” Screen briefly appears. The display returns to the Standard Display. See Figure 47.
Terminating a Defrost Cycle
The Defrost cycle will terminate automatically when the coil temperature reaches 58 F (14 C), or when the defrost timer expires. The defrost timer is normally set for 45 minutes, but can be set for 30 minutes. Defrost can also be terminated by turning the unit off.
NOTE: If the defrost timer consistently terminates Defrost because the evaporator coil temperature fails to reach 58 F (14 C), have the unit checked by a Thermo King dealer to see if it is working properly.
Figure 47: Initiating Manual Defrost Screen Sequence
or
Page 74
Operating Instructions
73
Viewing Gauge Readings
Use the following steps to view the gauge readings:
1. Begin at the Standard Display.
If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display.
2. Press the G
AUGES
soft key to enter the Gauges Menu. See
Figure 48.
3. Press B
ACK
or N
EXT
soft keys to scroll through following gauges: Coolant Temperature, Coolant Level, Oil Pressure, Oil Level, Amps, Battery Voltage, Engine RPM, Fuel Level Sensor, Discharge Pressure, Suction Pressure, ETV Position, and I/O. Selecting I/O enters a group of screens that are used only by technicians. See Figure 49. If no keys are pressed within 30 seconds, the screen will return to the standard display.
NOTE: Units without an Electronic Throttling Valve (ETV) will not display the Discharge Pressure, Suction Pressure, and ETV Position. See “Electronic Throttling Valve” on page 28 for more information about the ETV and how to tell if the unit has an ETV.
4. Press the L
OCK
soft key to display any Gauge Screen for an indefinite period. Press the key again to unlock the screen.
5. Press the E
XIT
soft key to return to the Standard Display.
1. Standard Display Screen
2. Gauges Soft Key
Figure 48: Viewing Gauges
1
2
Operating Instructions
73
Viewing Gauge Readings
Use the following steps to view the gauge readings:
1. Begin at the Standard Display. If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display.
2. Press the G
AUGES
soft key to enter the Gauges Menu. See
Figure 48.
3. Press B
ACK
or N
EXT
soft keys to scroll through following gauges: Coolant Temperature, Coolant Level, Oil Pressure, Oil Level, Amps, Battery Voltage, Engine RPM, Fuel Level Sensor, Discharge Pressure, Suction Pressure, ETV Position, and I/O. Selecting I/O enters a group of screens that are used only by technicians. See Figure 49. If no keys are pressed within 30 seconds, the screen will return to the standard display.
NOTE: Units without an Electronic Throttling Valve (ETV) will not display the Discharge Pressure, Suction Pressure, and ETV Position. See “Electronic Throttling Valve” on page 28 for more information about the ETV and how to tell if the unit has an ETV.
4. Press the L
OCK
soft key to display any Gauge Screen for an indefinite period. Press the key again to unlock the screen.
5. Press the E
XIT
soft key to return to the Standard Display.
1. Standard Display Screen
2. Gauges Soft Key
Figure 48: Viewing Gauges
1
2
Page 75
Operating Instructions
74
Figure 49: Viewing Gauges Screen Sequence
N
EXT
Key
B
ACK
Key
N
EXT
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
Operating Instructions
74
Figure 49: Viewing Gauges Screen Sequence
N
EXT
Key
B
ACK
Key
N
EXT
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
Page 76
Operating Instructions
75
Viewing Sensor Readings
Use the following steps to view the sensor readings.
1. Begin at the Standard Display. If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display.
2. Press the S
ENSOR
soft key to enter the Sensor Menu. See
Figure 50.
3. Press the B
ACK
or N
EXT
soft keys to scroll through the
following sensor screens:
Control Return Air Temperature
Display Return Air Temperature
Control Discharge Air Temperature
Display Discharge Air Temperature
Temperature Differential – The Temperature Differential is the difference between the Control Return Air Temperature and the Control Discharge Air Temperature.
Evaporator Coil Temperature
Ambient Air Temperature
Spare 1 Temperature
Optional Datalogger Sensor 1-6 Temperatures – The Datalogger Sensor Temperature screens display dashes (– – –) unless optional sensors are installed.
1. Standard Display
2. Sensors Soft Key
Figure 50: Viewing Sensors
1
2
Operating Instructions
75
Viewing Sensor Readings
Use the following steps to view the sensor readings.
1. Begin at the Standard Display. If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display.
2. Press the S
ENSOR
soft key to enter the Sensor Menu. See
Figure 50.
3. Press the B
ACK
or N
EXT
soft keys to scroll through the
following sensor screens:
Control Return Air Temperature
Display Return Air Temperature
Control Discharge Air Temperature
Display Discharge Air Temperature
Temperature Differential – The Temperature Differential is the difference between the Control Return Air Temperature and the Control Discharge Air Temperature.
Evaporator Coil Temperature
Ambient Air Temperature
Spare 1 Temperature
Optional Datalogger Sensor 1-6 Temperatures – The Datalogger Sensor Temperature screens display dashes (– – –) unless optional sensors are installed.
1. Standard Display
2. Sensors Soft Key
Figure 50: Viewing Sensors
1
2
Page 77
Operating Instructions
76
Board Temperature Sensor – The Board Temperature Sensor displays the temperature of the PC board inside the HMI control panel. The controller will turn the HMI display heater on if this temperature goes below a certain point in extremely cold ambient temperatures.
See Figure 51 and Figure 52. If no keys are pressed within 30 seconds, the screen will return to the Standard Display.
4. Press the L
OCK
soft key to display any sensor screen for an
indefinite period. Press the key again to unlock the screen.
5. Press the E
XIT
soft key to return to the Standard Display.
Operating Instructions
76
Board Temperature Sensor – The Board Temperature Sensor displays the temperature of the PC board inside the HMI control panel. The controller will turn the HMI display heater on if this temperature goes below a certain point in extremely cold ambient temperatures.
See Figure 51 and Figure 52. If no keys are pressed within 30 seconds, the screen will return to the Standard Display.
4. Press the L
OCK
soft key to display any sensor screen for an
indefinite period. Press the key again to unlock the screen.
5. Press the E
XIT
soft key to return to the Standard Display.
Page 78
Operating Instructions
77
Figure 51: Viewing Sensors Screen Sequence (continued on next page)
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
Continued on next page
S
ENSORS
Key N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
Operating Instructions
77
Figure 51: Viewing Sensors Screen Sequence (continued on next page)
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
Continued on next page
S
ENSORS
Key N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
Page 79
Operating Instructions
78
Figure 52: Viewing Sensors Screen Sequence (continued from previous page)
N
EXT
Key
B
ACK
Key
Continued from previous page
N
EXT
Key
B
ACK
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
Operating Instructions
78
Figure 52: Viewing Sensors Screen Sequence (continued from previous page)
N
EXT
Key
B
ACK
Key
Continued from previous page
N
EXT
Key
B
ACK
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
Page 80
Operating Instructions
79
Navigating the Main Menu
The Main Menu contains individual menu areas that allow the operator to view information and modify unit operation. Use the following steps to access these menu areas:
1. Begin at the Standard Display. If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display.
2. Press the M
ENU
soft key. See Figure 53.
3. Press N
EXT
and B
ACK
soft keys to scroll up or down
through the main menu areas. See Figure 53 and Figure
54.
4. Press the S
ELECT
soft key to access a specific menu area
when shown on the display screen. See Figure 53.
5. Press the E
XIT
soft key. To return to the Standard Display. The Main Menu choices are shown on the next page. For detailed information on each menu area, see the individual explanations of each menu item on the following pages of this manual.
1. Menu Soft Key 4. Select Soft Key
2. Next Soft Key 5. Exit Soft Key
3. Back Soft Key
Figure 53: Accessing Main Menu
2
1
345
Operating Instructions
79
Navigating the Main Menu
The Main Menu contains individual menu areas that allow the operator to view information and modify unit operation. Use the following steps to access these menu areas:
1. Begin at the Standard Display. If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display.
2. Press the M
ENU
soft key. See Figure 53.
3. Press N
EXT
and B
ACK
soft keys to scroll up or down
through the main menu areas. See Figure 53 and Figure
54.
4. Press the S
ELECT
soft key to access a specific menu area
when shown on the display screen. See Figure 53.
5. Press the E
XIT
soft key. To return to the Standard Display. The Main Menu choices are shown on the next page. For detailed information on each menu area, see the individual explanations of each menu item on the following pages of this manual.
1. Menu Soft Key 4. Select Soft Key
2. Next Soft Key 5. Exit Soft Key
3. Back Soft Key
Figure 53: Accessing Main Menu
2
1
345
Page 81
Operating Instructions
80
Figure 54: Main Menu Choices
Main Menu Choices
1. Language Menu: This menu only appears if the
controller is programmed to activate more than one language. It allows the operator to select which language is used. All other subsequent displays are shown in the selected language. English is the default language. See page 82.
2. Alarms Menu: Shows any active alarms and allows alarms to be cleared. See page 85.
3. Datalogger Menu: Allows the operator to view the datalogger displays. See page 88.
4. Hourmeters Menu: If enabled, allows the operator to view the hourmeter displays. See page 93.
5. Mode Menu: Allows the operator to change unit operating modes between CYCLE-SENTRY mode and Continuous Run mode, select Keypad Lockout, and start Sleep mode. See page 96.
6. Pretrip: Allows the operator to run a Pretrip. See page 104.
LANGUAGE
ALARMS
DATALOGGER
HOURMETERS
MODE
PRETRIP
ELECTRIC STANDBY/DIESEL
ADJUST BRIGHTNESS
TIME
Does not appear unless more than one language activated.
Does not appear on Model 30 units.
Operating Instructions
80
Figure 54: Main Menu Choices
Main Menu Choices
1. Language Menu: This menu only appears if the
controller is programmed to activate more than one language. It allows the operator to select which language is used. All other subsequent displays are shown in the selected language. English is the default language. See page 82.
2. Alarms Menu: Shows any active alarms and allows alarms to be cleared. See page 85.
3. Datalogger Menu: Allows the operator to view the datalogger displays. See page 88.
4. Hourmeters Menu: If enabled, allows the operator to view the hourmeter displays. See page 93.
5. Mode Menu: Allows the operator to change unit operating modes between CYCLE-SENTRY mode and Continuous Run mode, select Keypad Lockout, and start Sleep mode. See page 96.
6. Pretrip: Allows the operator to run a Pretrip. See page 104.
LANGUAGE
ALARMS
DATALOGGER
HOURMETERS
MODE
PRETRIP
ELECTRIC STANDBY/DIESEL
ADJUST BRIGHTNESS
TIME
Does not appear unless more than one language activated.
Does not appear on Model 30 units.
Page 82
Operating Instructions
81
7. Electric Standby/Diesel Mode (Model 50 Only): This
menu only appears on Model 50 units. It allows the operator to manually select Electric Standby or Diesel operation. See page 109.
8. Adjust Brightness: Allows the operator to adjust the display intensity as required by conditions. See page 111.
9. Time: Allows the operator to view the Time and Date. The Time is displayed in 24 hour military time. See page 114.
Operating Instructions
81
7. Electric Standby/Diesel Mode (Model 50 Only): This
menu only appears on Model 50 units. It allows the operator to manually select Electric Standby or Diesel operation. See page 109.
8. Adjust Brightness: Allows the operator to adjust the display intensity as required by conditions. See page 111.
9. Time: Allows the operator to view the Time and Date. The Time is displayed in 24 hour military time. See page 114.
Page 83
Operating Instructions
82
Language Menu
If the Language feature is activated in the controller programming, an alternate language can be selected from the Language Menu. After a new language is chosen all displays will appear in that language. If the language feature is not enabled this menu does not appear.
The languages available are dependant on the HMI control panel software revision. Languages currently supported by software revision 65xx are English, Spanish, French, German, Italian, Dutch, Portuguese, Greek, Turkish, Arabic and Hebrew. Languages currently supported by software revision 66xx are English, Russian, Polish, Hungarian, Romanian, Bulgarian, Czech, Danish, Swedish, Norwegian and Finnish. Other than languages supported, software revisions 65xx and 66xx are identical.
The default language is English. Only languages that have been activated in the controller programming will appear on this menu. Contact your Thermo King dealer for information about programming the controller.
To select an alternate language:
1. Begin at the Standard Display. If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display.
2. Press the M
ENU
soft key on the Standard Display.
3. If enabled, the Language Menu Screen appears. Press the
S
ELECT
soft key to choose the Language Menu Screen.
See Figure 57.
1. Menu Soft Key
Figure 55: Standard Display
1
Operating Instructions
82
Language Menu
If the Language feature is activated in the controller programming, an alternate language can be selected from the Language Menu. After a new language is chosen all displays will appear in that language. If the language feature is not enabled this menu does not appear.
The languages available are dependant on the HMI control panel software revision. Languages currently supported by software revision 65xx are English, Spanish, French, German, Italian, Dutch, Portuguese, Greek, Turkish, Arabic and Hebrew. Languages currently supported by software revision 66xx are English, Russian, Polish, Hungarian, Romanian, Bulgarian, Czech, Danish, Swedish, Norwegian and Finnish. Other than languages supported, software revisions 65xx and 66xx are identical.
The default language is English. Only languages that have been activated in the controller programming will appear on this menu. Contact your Thermo King dealer for information about programming the controller.
To select an alternate language:
1. Begin at the Standard Display. If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display.
2. Press the M
ENU
soft key on the Standard Display.
3. If enabled, the Language Menu Screen appears. Press the
S
ELECT
soft key to choose the Language Menu Screen.
See Figure 57.
1. Menu Soft Key
Figure 55: Standard Display
1
Page 84
Operating Instructions
83
4. The “NEW LANGUAGE WILL BE” Screen will appear. See Figure 57.
5. Press the + or - soft keys to select the desired language. German is shown in Figure 57.
6. When the desired language is shown, press the Y
ES
soft
key to confirm the choice.
7. The “PROGRAMMING LANGUAGE PLEASE WAIT” Screen briefly appears.
8. The “LANGUAGE SELECTED IS XXX” Screen briefly appears.
9. The display returns to Language Menu Screen, but will show the new language. German is shown in Figure 57.
NOTE: Exercise care when changing languages, as once changed all HMI Control panel displays will be in the new language. If the user is not familiar with the new language, problems may be experienced returning to the default language.
10. Repeat the process to select a different language. Press the
N
EXT
soft key to select a different Main Menu item. Press
the E
XIT
soft key to return to the Standard Display.
NOTE: English and all other enabled languages may be accessed from the Standard Display. When the Standard Display is shown press and hold the first and last soft key for 5 seconds as shown below in Figure 56.
1. Press These Soft Keys
Figure 56: Standard Display
1
Operating Instructions
83
4. The “NEW LANGUAGE WILL BE” Screen will appear. See Figure 57.
5. Press the + or - soft keys to select the desired language. German is shown in Figure 57.
6. When the desired language is shown, press the Y
ES
soft
key to confirm the choice.
7. The “PROGRAMMING LANGUAGE PLEASE WAIT” Screen briefly appears.
8. The “LANGUAGE SELECTED IS XXX” Screen briefly appears.
9. The display returns to Language Menu Screen, but will show the new language. German is shown in Figure 57.
NOTE: Exercise care when changing languages, as once changed all HMI Control panel displays will be in the new language. If the user is not familiar with the new language, problems may be experienced returning to the default language.
10. Repeat the process to select a different language. Press the
N
EXT
soft key to select a different Main Menu item. Press
the E
XIT
soft key to return to the Standard Display.
NOTE: English and all other enabled languages may be accessed from the Standard Display. When the Standard Display is shown press and hold the first and last soft key for 5 seconds as shown below in Figure 56.
1. Press These Soft Keys
Figure 56: Standard Display
1
Page 85
Operating Instructions
84
Figure 57: Change Language Screen Sequence
HAUPTMENU
SPRACHE
BEENDEN WEITERAUSWHAL
ARA820
NEW LANGUAGEWILL BE
DEUTSCH
-
YES NO
+
USE +/- TO CHANGE
OK?
ARA819
S
ELECT
Key
Y
ES
Key
+ or - Key
Operating Instructions
84
Figure 57: Change Language Screen Sequence
HAUPTMENU
SPRACHE
BEENDEN WEITERAUSWHAL
ARA820
NEW LANGUAGEWILL BE
DEUTSCH
-
YES NO
+
USE +/- TO CHANGE
OK?
ARA819
S
ELECT
Key
Y
ES
Key
+ or - Key
Page 86
Operating Instructions
85
Alarms Menu
If an alarm condition occurs the large Alarm Icon will appear on the Standard Display. See “Alarm Display” on page 57.
Alarms are viewed and cleared using the Alarm Menu as follows:
1. Begin at the Standard Display. If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display.
2. Press the M
ENU
soft key on the Standard Display.
3. The Language Menu or Alarm Menu will appear. If the
Language Menu appears, press the N
EXT
soft key until the
Alarm Menu appears.
4. Press the S
ELECT
soft key . The Alarm Display will appear.
See Figure 59.
5. If no alarms are present, the “No Alarm” Screen is shown.
Press the E
XIT
soft key to return to the Standard Display.
6. If alarms are present, the quantity of alarms (if more than one), the alarm code number and alarm description will be shown on the display. In the following example (see Figure 59), there are two alarms present. The most recent is Alarm Code 6. This alarm code indicates a problem with the coolant temperature sensor.
NOTE: If a serious alarm occurs, the unit will be shut down to prevent damage to the unit or the load. If this occurs, the display will show that the unit is shut down and display the alarm code that caused the shutdown.
1. Menu Soft Key
Figure 58: Standard Display
1
Operating Instructions
85
Alarms Menu
If an alarm condition occurs the large Alarm Icon will appear on the Standard Display. See “Alarm Display” on page 57.
Alarms are viewed and cleared using the Alarm Menu as follows:
1. Begin at the Standard Display. If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display.
2. Press the M
ENU
soft key on the Standard Display.
3. The Language Menu or Alarm Menu will appear. If the
Language Menu appears, press the N
EXT
soft key until the
Alarm Menu appears.
4. Press the S
ELECT
soft key . The Alarm Display will appear.
See Figure 59.
5. If no alarms are present, the “No Alarm” Screen is shown.
Press the E
XIT
soft key to return to the Standard Display.
6. If alarms are present, the quantity of alarms (if more than one), the alarm code number and alarm description will be shown on the display. In the following example (see Figure 59), there are two alarms present. The most recent is Alarm Code 6. This alarm code indicates a problem with the coolant temperature sensor.
NOTE: If a serious alarm occurs, the unit will be shut down to prevent damage to the unit or the load. If this occurs, the display will show that the unit is shut down and display the alarm code that caused the shutdown.
1. Menu Soft Key
Figure 58: Standard Display
1
Page 87
Operating Instructions
86
7. After the alarm situation is resolved press the C
LEAR
key
to clear the alarm. To display the next alarm, press the
N
EXT
key (see Figure 59).
NOTE: For additional information regarding the alarm shown on the display press the H
ELP
soft key. A help
message will appear.
Important Alarm Notes
If an alarm will not clear, it may still exist. If the alarm is not corrected, it will not clear.
If an alarm cannot be cleared from the Main menu, the
C
LEAR
key will not appear. These alarms must be cleared
from the Guarded Access Menus.
All alarms must be viewed before any of the alarms can be cleared.
Check Alarm Code 96 (Low Fuel Level) is set when the fuel level falls to 15%. The controller can be programmed to set a shutdown Alarm Code 44 (Out of Fuel) when the fuel level falls to 5%. Shutdown Alarm Code 44 can be manually cleared with the C
LEAR
key. In that case it becomes a check alarm and the unit will continue to run until it runs out of fuel (if it is not refilled). Alarm Code 96 and Alarm Code 44 are both automatically reset when the fuel tank is refilled above 25%.
NOTE: Shutdown Alarm Code 44 reappears when it is manually cleared from the Alarms Menu. However, it changes to a check alarm so the unit will now start after you exit the Alarms Menu.
Contact your supervisor or a Thermo King dealer for information about alarm codes that will not clear.
Operating Instructions
86
7. After the alarm situation is resolved press the C
LEAR
key
to clear the alarm. To display the next alarm, press the
N
EXT
key (see Figure 59).
NOTE: For additional information regarding the alarm shown on the display press the H
ELP
soft key. A help
message will appear.
Important Alarm Notes
If an alarm will not clear, it may still exist. If the alarm is not corrected, it will not clear.
If an alarm cannot be cleared from the Main menu, the
C
LEAR
key will not appear. These alarms must be cleared
from the Guarded Access Menus.
All alarms must be viewed before any of the alarms can be cleared.
Check Alarm Code 96 (Low Fuel Level) is set when the fuel level falls to 15%. The controller can be programmed to set a shutdown Alarm Code 44 (Out of Fuel) when the fuel level falls to 5%. Shutdown Alarm Code 44 can be manually cleared with the C
LEAR
key. In that case it becomes a check alarm and the unit will continue to run until it runs out of fuel (if it is not refilled). Alarm Code 96 and Alarm Code 44 are both automatically reset when the fuel tank is refilled above 25%.
NOTE: Shutdown Alarm Code 44 reappears when it is manually cleared from the Alarms Menu. However, it changes to a check alarm so the unit will now start after you exit the Alarms Menu.
Contact your supervisor or a Thermo King dealer for information about alarm codes that will not clear.
Page 88
Operating Instructions
87
Figure 59: Viewing and Clearing Alarms Screen Sequence
ALARM 6
2 OF 2 ALARMS
COOLANT TEMP SENSOR
NEXTEXIT HELPCLEAR
ARA823
ALARM 5
1 OF 2 ALARMS
AMBIENT TEMP SENSOR
NEXTEXIT HELPCLEAR
ARA824
M
ENU
Key
S
ELECT
Key
S
ELECT
Key
N
EXT
Key
C
LEAR
Key
Operating Instructions
87
Figure 59: Viewing and Clearing Alarms Screen Sequence
ALARM 6
2 OF 2 ALARMS
COOLANT TEMP SENSOR
NEXTEXIT HELPCLEAR
ARA823
ALARM 5
1 OF 2 ALARMS
AMBIENT TEMP SENSOR
NEXTEXIT HELPCLEAR
ARA824
M
ENU
Key
S
ELECT
Key
S
ELECT
Key
N
EXT
Key
C
LEAR
Key
Page 89
Operating Instructions
88
Datalogger Menu
The Datalogger Menu is used to initiate a start of trip, or to print a trip report.
Initiating a Start of Trip
A “Start Of Trip” places a marker in the datalogger memory. It is typically initiated when the cargo is being loaded. The Start Of Trip marker then shows when the trip started in the data that is downloaded or printed from the datalogger. A Start Of Trip can be initiated through the use of WinTrac datalogging software, or manually in the field. The following procedure covers manual initiation. For more information on datalogging, see the WinTrac User Manual included with the WinTrac software.
1. Begin at the Standard Display. If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display. See
Figure 60.
2. Press the M
ENU
soft key on the Standard Display.
3. Press the N
EXT
soft key until the Datalogger Menu
appears. See Figure 61.
4. Press the S
ELECT
soft key on the Datalogger Menu. The
“Start Trip” Screen will appear.
5. Press the S
ELECT
soft key . The “S tart Of T rip” Screen will
appear.
6. Press the S
ELECT
soft key to initiate a start of trip.
7. A Start Of Trip Marker has been inserted into the datalogger memory.
1. Menu Soft Key
Figure 60: Standard Display
1
Operating Instructions
88
Datalogger Menu
The Datalogger Menu is used to initiate a start of trip, or to print a trip report.
Initiating a Start of Trip
A “Start Of Trip” places a marker in the datalogger memory. It is typically initiated when the cargo is being loaded. The Start Of Trip marker then shows when the trip started in the data that is downloaded or printed from the datalogger. A Start Of Trip can be initiated through the use of WinTrac datalogging software, or manually in the field. The following procedure covers manual initiation. For more information on datalogging, see the WinTrac User Manual included with the WinTrac software.
1. Begin at the Standard Display. If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display. See
Figure 60.
2. Press the M
ENU
soft key on the Standard Display.
3. Press the N
EXT
soft key until the Datalogger Menu
appears. See Figure 61.
4. Press the S
ELECT
soft key on the Datalogger Menu. The
“Start Trip” Screen will appear.
5. Press the S
ELECT
soft key . The “S tart Of T rip” Screen will
appear.
6. Press the S
ELECT
soft key to initiate a start of trip.
7. A Start Of Trip Marker has been inserted into the datalogger memory.
1. Menu Soft Key
Figure 60: Standard Display
1
Page 90
Operating Instructions
89
Figure 61: Start of T r ip Screen Sequence
S
ELECT
Key
S
ELECT
Key
S
ELECT
Key
Operating Instructions
89
Figure 61: Start of T r ip Screen Sequence
S
ELECT
Key
S
ELECT
Key
S
ELECT
Key
Page 91
Operating Instructions
90
Printing a Trip Report
This procedure prints the current CargoWatch datalogger record directly to a handheld printer. The printed record shows things such as the unit and controller identification numbers, dates and times, the setpoint, and the data from the optional sensors connected to the CargoWatch datalogger. If no sensors are connected, the printed record shows the same things without the sensor data.
1. Connect the printer to the 6-pin printer port located inside the control box.
NOTE: The printer port can be mounted so it is accessible without opening the control box. It is typically mounted between the CargoWatch Port and the ServiceWatch Port. Contact your Thermo King dealer to make this modification.
2. Begin at the Standard Display. If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display. See
Figure 63.
3. Press the M
ENU
soft key on the Standard Display.
1. CargoWatch Port
2. ServiceWatch Port
3. Printer Port
Figure 62: Printer Port Location
3
1 2
Operating Instructions
90
Printing a Trip Report
This procedure prints the current CargoWatch datalogger record directly to a handheld printer. The printed record shows things such as the unit and controller identification numbers, dates and times, the setpoint, and the data from the optional sensors connected to the CargoWatch datalogger. If no sensors are connected, the printed record shows the same things without the sensor data.
1. Connect the printer to the 6-pin printer port located inside the control box.
NOTE: The printer port can be mounted so it is accessible without opening the control box. It is typically mounted between the CargoWatch Port and the ServiceWatch Port. Contact your Thermo King dealer to make this modification.
2. Begin at the Standard Display. If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display. See
Figure 63.
3. Press the M
ENU
soft key on the Standard Display.
1. CargoWatch Port
2. ServiceWatch Port
3. Printer Port
Figure 62: Printer Port Location
3
1 2
Page 92
Operating Instructions
91
4. Press the N
EXT
soft key until the Datalogger Menu
appears. See Figure 64.
5. Press the S
ELECT
soft key on the Datalogger Menu. The
“Start Trip” Screen will appear.
6. Press the N
EXT
soft key. The “Print/View” Screen will
appear.
7. Press the S
ELECT
soft key. The “Delivery Ticket” Screen
will appear. Press the S
ELECT
soft key to print a delivery
report.
8. Press the N
EXT
soft key to go to the “Trip Ticket” Screen.
Press the S
ELECT
soft key to print a trip report.
1. Menu Soft Key
Figure 63: Standard Display
1
Operating Instructions
91
4. Press the N
EXT
soft key until the Datalogger Menu
appears. See Figure 64.
5. Press the S
ELECT
soft key on the Datalogger Menu. The
“Start Trip” Screen will appear.
6. Press the N
EXT
soft key. The “Print/View” Screen will
appear.
7. Press the S
ELECT
soft key. The “Delivery Ticket” Screen
will appear. Press the S
ELECT
soft key to print a delivery
report.
8. Press the N
EXT
soft key to go to the “Trip Ticket” Screen.
Press the S
ELECT
soft key to print a trip report.
1. Menu Soft Key
Figure 63: Standard Display
1
Page 93
Operating Instructions
92
Figure 64: Print Report Screen Sequence
S
ELECT
Key
N
EXT
Key
S
ELECT
Key
N
EXT
Key
S
ELECT
Key
S
ELECT
Key
Operating Instructions
92
Figure 64: Print Report Screen Sequence
S
ELECT
Key
N
EXT
Key
S
ELECT
Key
N
EXT
Key
S
ELECT
Key
S
ELECT
Key
Page 94
Operating Instructions
93
Hourmeters Menu
The Hourmeters are programmable to be visible or hidden in the controller. Hourmeters that are visible are displayed. Hourmeters that are hidden are not displayed, but they do count hours. The default setting for Model 30 units is to display only the Engine Hours. The default setting for Model 50 units is to display T otal Run T ime Hours, Engine Hours, and Electric Run Hours. The Hourmeters Menu will not appear if all hourmeters are hidden. Contact your Thermo King dealer for information about programming the controller.
Hourmeters can be viewed in the Hourmeters Menu as follows:
1. Begin at the Standard Display.
If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display.
2. Press the M
ENU
soft key on the Standard Display.
3. Press the N
EXT
soft key until the Hourmeters Menu
appears. See Figure 66.
4. Press the S
ELECT
soft key to enter the Hourmeters Menu.
5. Press the N
EXT
and B
ACK
soft keys to view the hourmeter
displays.
1. Menu Soft Key
Figure 65: Standard Display
1
Operating Instructions
93
Hourmeters Menu
The Hourmeters are programmable to be visible or hidden in the controller. Hourmeters that are visible are displayed. Hourmeters that are hidden are not displayed, but they do count hours. The default setting for Model 30 units is to display only the Engine Hours. The default setting for Model 50 units is to display T otal Run T ime Hours, Engine Hours, and Electric Run Hours. The Hourmeters Menu will not appear if all hourmeters are hidden. Contact your Thermo King dealer for information about programming the controller.
Hourmeters can be viewed in the Hourmeters Menu as follows:
1. Begin at the Standard Display.
If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display.
2. Press the M
ENU
soft key on the Standard Display.
3. Press the N
EXT
soft key until the Hourmeters Menu
appears. See Figure 66.
4. Press the S
ELECT
soft key to enter the Hourmeters Menu.
5. Press the N
EXT
and B
ACK
soft keys to view the hourmeter
displays.
1. Menu Soft Key
Figure 65: Standard Display
1
Page 95
Operating Instructions
94
Figure 66: Viewing Hourmeters Screen Sequence (continued on next page)
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
Continued on next page
S
ELECT
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
Operating Instructions
94
Figure 66: Viewing Hourmeters Screen Sequence (continued on next page)
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
Continued on next page
S
ELECT
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
Page 96
Operating Instructions
95
Figure 67: Viewing Hourmeters Screen Sequence (continued from previous page)
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
Continued from previous page
B
ACK
Key
Operating Instructions
95
Figure 67: Viewing Hourmeters Screen Sequence (continued from previous page)
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
N
EXT
Key
B
ACK
Key
Continued from previous page
B
ACK
Key
Page 97
Operating Instructions
96
Mode Menu
Various operating modes can be selected using the Mode menu. Not all modes may be available, depending on OptiSet Plus usage and settings of other programmable features. The following modes may be available.
Turn CYCLE-SENTRY On or Off
The CYCLE-SENTRY Mode can be turned On or Off. If CYCLE-SENTRY is turned off the unit runs in Continuous mode. Either CYCLE-SENTRY or Continuous operation may be disabled via OptiSet Plus. See “Turning CYCLE-SENTRY On or Off” on page 97.
Keypad Lockout
If enabled in Guarded Access, the keypad can be locked to prevent unauthorized use. If the keypad is locked only the On and Off keys function. The keypad will remain locked even if the unit is turned off and back on. If Keypad Lockout is active, press and hold any soft key for 5 seconds to deactivate the feature. See “Selecting Keypad Lockout” on page 99.
Sleep Mode
If enabled in Guarded Access, Sleep Mode is used to keep the engine warm and the battery charged when the unit is not in use. When the unit is in Sleep Mode the display will show “SLEEP” and the current time. See “Selecting Sleep Mode” on page 101.
Program W akeup T ime: This feature allows a wakeup time to be specified. When the selected time is reached the unit will start and resume normal operation.
If Wakeup Time is selected:
Day to Wake Up: This feature allows the day the unit
is to wake up to be specified.
Hour to Wake Up: This feature allows the hour the
unit is to wake up to be specified.
Minute to Wake Up: This feature allows the minute
the unit is to wake up to be specified.
Run Pretrip on W ake Up: This feature allows a Pretrip
Test to be automatically run when the unit wakes up.
Operating Instructions
96
Mode Menu
Various operating modes can be selected using the Mode menu. Not all modes may be available, depending on OptiSet Plus usage and settings of other programmable features. The following modes may be available.
Turn CYCLE-SENTRY On or Off
The CYCLE-SENTRY Mode can be turned On or Off. If CYCLE-SENTRY is turned off the unit runs in Continuous mode. Either CYCLE-SENTRY or Continuous operation may be disabled via OptiSet Plus. See “Turning CYCLE-SENTRY On or Off” on page 97.
Keypad Lockout
If enabled in Guarded Access, the keypad can be locked to prevent unauthorized use. If the keypad is locked only the On and Off keys function. The keypad will remain locked even if the unit is turned off and back on. If Keypad Lockout is active, press and hold any soft key for 5 seconds to deactivate the feature. See “Selecting Keypad Lockout” on page 99.
Sleep Mode
If enabled in Guarded Access, Sleep Mode is used to keep the engine warm and the battery charged when the unit is not in use. When the unit is in Sleep Mode the display will show “SLEEP” and the current time. See “Selecting Sleep Mode” on page 101.
Program W akeup T ime: This feature allows a wakeup time to be specified. When the selected time is reached the unit will start and resume normal operation.
If Wakeup Time is selected:
Day to Wake Up: This feature allows the day the unit
is to wake up to be specified.
Hour to Wake Up: This feature allows the hour the
unit is to wake up to be specified.
Minute to Wake Up: This feature allows the minute
the unit is to wake up to be specified.
Run Pretrip on W ake Up: This feature allows a Pretrip
Test to be automatically run when the unit wakes up.
Page 98
Operating Instructions
97
Turning CYCLE-SENTRY On or Off
The easiest way to switch between CYCLE-SENTRY and Continuous Run is to press the Mode key (see page 69). But, you can also switch modes in the Mode Menu as follows:
1. Begin at the Standard Display. If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display.
2. Press the M
ENU
soft key on the Standard Display.
3. Press the N
EXT
soft key until the Mode Menu appears.
4. Press S
ELECT
soft key to enter the Mode Menu. See Figure
69.
5. Press the S
ELECT
soft key, to switch between modes.
6. The new mode is then confirmed for 10 seconds.
7. The display then returns to the Mode Menu. Press the
S
ELECT
soft key again to change the mode again.
CAUTION: If the unit is in CYCLE-SENTRY null and the mode is switched to Continuous mode, the unit will start automatically.
1. CYCLE-SENTRY Icon Shows Current Mode Displayed for CYCLE-SENTRY Mode Not Displayed for Continuous Mode
2. Mode Key
3. Menu Soft Key
Figure 68: Standard Display
1
2
3
Operating Instructions
97
Turning CYCLE-SENTRY On or Off
The easiest way to switch between CYCLE-SENTRY and Continuous Run is to press the Mode key (see page 69). But, you can also switch modes in the Mode Menu as follows:
1. Begin at the Standard Display. If the Temperature Watch Display is showing, press the
M
ENU
soft key once to return to the Standard Display.
2. Press the M
ENU
soft key on the Standard Display.
3. Press the N
EXT
soft key until the Mode Menu appears.
4. Press S
ELECT
soft key to enter the Mode Menu. See Figure
69.
5. Press the S
ELECT
soft key, to switch between modes.
6. The new mode is then confirmed for 10 seconds.
7. The display then returns to the Mode Menu. Press the
S
ELECT
soft key again to change the mode again.
CAUTION: If the unit is in CYCLE-SENTRY null and the mode is switched to Continuous mode, the unit will start automatically.
1. CYCLE-SENTRY Icon Shows Current Mode Displayed for CYCLE-SENTRY Mode Not Displayed for Continuous Mode
2. Mode Key
3. Menu Soft Key
Figure 68: Standard Display
1
2
3
Page 99
Operating Instructions
98
Figure 69: Selecting Mode Screen Sequence
S
ELECT
Key
S
ELECT
Key
S
ELECT
Key
Operating Instructions
98
Figure 69: Selecting Mode Screen Sequence
S
ELECT
Key
S
ELECT
Key
S
ELECT
Key
Page 100
Operating Instructions
99
Selecting Keypad Lockout
This feature must be enabled in Guarded Access to be available. See “Keypad Lockout” on page 96 for mo re information about Keypad Lockout. Use the following steps to select Keypad Lockout:
1. Begin at the Standard Display. If the Temperature Watch Display is showing, press any soft key to return to the Standard Display.
2. Press the M
ENU
soft key on the Standard Display.
3. Press the N
EXT
soft key until the Mode Menu appears.
4. Press the S
ELECT
soft key to enter the Mode Menu. The
Turn CYCLE-SENTRY On/Off Screen will appear.
5. Press the N
EXT
soft key until the Keypad Lockout Display
appears.
1. Press Menu Soft Key
Figure 70: Standard Display
1
1. Press Select Soft Key
Figure 71: Mode Menu Display
OFF
ON
MAIN MENU
MODE
NEXTEXIT BACKSELECT
ARA832
1
Operating Instructions
99
Selecting Keypad Lockout
This feature must be enabled in Guarded Access to be available. See “Keypad Lockout” on page 96 for mo re information about Keypad Lockout. Use the following steps to select Keypad Lockout:
1. Begin at the Standard Display. If the Temperature Watch Display is showing, press any soft key to return to the Standard Display.
2. Press the M
ENU
soft key on the Standard Display.
3. Press the N
EXT
soft key until the Mode Menu appears.
4. Press the S
ELECT
soft key to enter the Mode Menu. The
Turn CYCLE-SENTRY On/Off Screen will appear.
5. Press the N
EXT
soft key until the Keypad Lockout Display
appears.
1. Press Menu Soft Key
Figure 70: Standard Display
1
1. Press Select Soft Key
Figure 71: Mode Menu Display
OFF
ON
MAIN MENU
MODE
NEXTEXIT BACKSELECT
ARA832
1
Loading...