THERMEx THW20, THW40, THW60, THW80, THW100 Product Manual

...
Models
Heat Pump Manual
Thermex Solutions
PRODUCT MANUAL
HEAT PUMPS Document 001-D135 11 May 2015
THW20 THW40 THW60 THW80 THW100 THW150
THWW20 THWW40 THWW50 THWW60 THWW80 THWW100
THWP20 THWP40 THWP60
2
Heat Pump Manual
Terms and Conditions
Listed below are some basic operational and installation conditions that must be adhered to for Thermex Solutions warranty to remain valid and more importantly for trouble free heat pump operation
· If the heat pump is supplied without a pump then the minimum flow rate specified in the manual must be maintained through the units at all times.
· The heat pump must be commissioned in accordance with the instruction in the manual and the heat pump must be commissioned under normal operating conditions
· The operational settings on the controller must not be altered without first consulting Thermex
· The temperature cut out set point must never be set above 61°C without first consulting
Thermex Solutions
· The heat pump must be installed on level surface
· The heat pump must be powered up for at least 4 hours before starting the heat pump to allow
for the sump heater to warm the compressor oil.
· The pressure in the sealed refrigeration system must be checked by a refrigeration mechanic before starting the heat pump to ensure that the pressure on the suction side is at least 200 kPa
· For any service work not carried out by Thermex Solutions, Thermex Solutions will only cover costs of refrigerant to the value of the specified charge in the units.
· It is not Thermex Solutionss responsibility to connect the heat pump to the BMS unless agreed to before delivery of the heat pump
· The heat pump must not be installed too close to walls and other heat pumps with clearances to be at least what is specified in the manual
· The heat pump must be installed with proper, neat access to facilitate servicing in a manner that is compliant with safe work practices. Additional charges may apply for site where access to the heat pump is unsafe or restricted
· Thermex Solutions will manufacture the heat pump to the specification provided to the sales department. If the information supplied is incorrect Thermex Solutions takes no responsibility for wear on the heat pump for short cycling in the case where the heat pump is over sized for the heat load or the heat pump unable to maintain temperature when the heat pump is too small for the heat load
· Thermex Solutions takes no responsibility for repairs carried out on the heat pump by un- authorised service agents or if parts are installed that are not from Thermex Solutionss approved supplier list
· Costs for installations where a crane lift is required to undertake major repairs will not be covered by Thermex Solutions
· All dimensions, technical specifications and software operation are correct at the time of writing. However with constant development some of these specifications may change without written notice
3
Heat Pump Manual
FOREWARD This manual is designed to explain the installation, operation and the basic maintenance of
the product. It is recommended that for service issues Thermex Pty Ltd be contacted before and work commences. A comprehensive service manual is available to be down loaded from the website.
CONTACT DETAILS Thermex Solutions Pty Ltd
161 Orchard Road Chester Hill NSW 2162 Australia
Toll Free 1800649233 or +612 9721 9300 Fax + 612 9721 9344
www.thermex.com.au
CONTENTS Safety 4
Marking 6 Certification 6 Warranty 7 General Information 7 Intended Use 7 Water Circuit 7 Technical Data 8 Heating System Schematic 16 Dimensions 17 Transport and Storage 19 Installation – electrical, water connection, water treatment, control circuit and final checks Operation 27 Control 29 Service and Maintenance 31 Wiring 37 Pump Curves N/A Critical Spares 38 Trouble Shooting 39 Release Notes 40 Commissioning 41 Site Inspection 44
19
Heat Pump Manual
SAFETY THE UNIT IS DESIGNED FOR OUTDOOR USE.
- This unit is designed to be safe in the use for which it was planned provided that it is installed, started up and maintained in accordance with the instructions contained in this manual.
- The unit contains electrical components that operate at line voltage and contains moving parts. It therefore must be isolated from the electrical supply before being worked on. All maintenance operations that require access to the unit must be carried out by suitably qualified technicians who have a thorough understanding of all necessary precautions associated with refrigeration and electrical machinery.
- The liquids to be heated must be compatible with the materials used in the constructions of this unit. These liquids can be water or mixtures of glycol and water for example. The liquids to be heated must not be flammable.
- All panels must be re-installed after carrying out any maintenance work.
- The unit is not to be used by the infirmed or children unless they are supervised by responsible persons qualified to carry out the supervision.
- The unit should be secured to prevent it from toppling over.
WARNING
The unit is only to be installed, operated, maintained and serviced by qualified persons only. Operation of units such as these can be hazardous and should be serviced by persons with the proper training and qualifications.
The unit and the Product Manual have markings, warning and instructions on the safe operation of the unit and they must be adhered to.
WARNING
All wiring must be performed by qualified electricians. Improperly installed wiring and grounding may result in electrocution and fire hazards
To avoid these hazards all wiring must be installed in accordance with all the local relevant safety standards for wiring
WARNING
The heat pump contains refrigerants under high pressure. The system also contains oils under high pressure. Before the refrigeration circuit can be opened, the refrigerant should be reclaimed to reduce pressure in the system.
Failure to recover the refrigerant to relieve pressure or the use of refrigerants or refrigerant substitutes that are not specified for the unit may result in system rupture and explosion.
- Where the above symbol is shown there are live electrical parts and the utmost care should be taken. .
- Always isolate power from the unit when working on it.
- Maximum temperature setting is 60 degrees on the unit. Any higher than this may cause problems with the condenser and/ or the water system over heating which may become dangerous
Refrigerants have a narcotic effect when inhaled in high quantities. Should a leak occur of the refrigerants then the room should be vacated and should only be re-entered after suitable ventilation.
5
Heat Pump Manual
SAFETY First Aid
- Eye Contact. Immediately flush with tepid water or sterile saline solution. Hold eyelids apart for 15 minutes while irrigating. Seek medical attention.
- Inhalation. Remove from area of exposure immediately and if you are assisting a victim avoid being exposed. Breathing apparatus must be worn in the presence of high concentration of refrigerants. If victim is not breathing then apply artificial respiration and seek urgent medical help. Give oxygen is available.
- Skin Contact. Cold Burns. Remove contaminated clothing and gently flush affected area with warm water (30C) for 15 minutes. Apply sterile dressing and treat as for a thermal burn. For large burns immerse in water for 15 minutes. DO NOT apply any form if direct heat. Seek medical attention.
- Ingestion. For advice contact the poisons centre on 131126 in Australia. If swallowed do not induce vomiting. Ingestion is considered unlikely due to product form.
- Advice to Doctor. Use of adrenaline and other catacholamines may be contraindicted due to possible cardiac sensation. Treatment for asphyxia.
R134a HazChem code 2RE R134a is non – flammable. Disposal The unit must be disposed of in a proper fashion. The refrigerants in the system must be
reclaimed by a qualified refrigeration mechanic and disposed of in accordance with the statutory requirements. The compressor contains oil that must not be dumped.
Manual Handling The unit weights approximately 650 kg. Do not try to move the unit manually. The unit can be
lifted with a crane (the centre of gravity is towards the front of the unit), a forklift or a pallet jack.
6
All Thermex products are manufactured by Aqua Cooler in
Heat Pump Manual
MARKING The units have various markings on them. There is a marking plate on the unit, an example is
shown below giving regulatory requirements. There will be a wiring diagram as shown in the wiring diagram section of this document provided in a larger scale for ease of maintenance.
A four digit serial number sticker will also be placed under the marking plate. With this number Thermex can trace the date of manufacture of the product and details on the unit.
The wiring diagram will show the model of the unit and the options installed. CERTIFICATION All the electrical components in the heat pump have certification for electrical safety. All the
exposed components are rated to IP66 against weather ingress.
Australia. Aqua Cooler is an accredited participant in the WaterMark QA scheme and is audited annually by SAI Global The Watermark scheme cover all products that are connected to the town water supply.
7
Heat Pump Manual
WARRANTY Thermex offers a full comprehensive 12 month parts warranty, 5 years on the compressor
and the condenser. Any claim under this warranty must be made within 12 months of the date of purchase of the
product. To make a claim under the warranty, return the product (with proof of purchase) to the supplier where you purchased the product or contact Thermex regarding warranty conditions.
Thermex will pay your reasonable, direct expenses of claiming under this warranty. You may submit details and proof of your expense claim to Thermex Pty Ltd for consideration.
This warranty is given by Thermex Pty Ltd, ABN 13 245 994 351, of 161 Orchard Rd, Chester Hill, NSW 2162 – Ph 02 9721 9310.
This warranty is provided in addition to other rights and remedies you have under law: Our goods come with guarantees which cannot be excluded under the Australian Consumer Law. You are entitled to replacement or refund for a major failure and to compensation for other reasonably foreseeable loss or damage. You are also entitled to have the goods repaired or replaced if the goods fail to be of acceptable quality and the failure does not amount to a major failure.
Attached to this document is a comprehensive commissioning procedure. This must be carried out in accordance with the procedure and returned to Thermex or Thermex can do the commissioning, otherwise the warranty will be voided.
GENERAL INFORMATION The heat pump is designed to heat water to feed a central storage system. It has either an air
cooled copper and aluminium fin or a coaxial copper water sourced evaporator, a plate heat condenser and a scroll compressor to circulate the refrigerant gas. Water is circulated out of the unit via a pump which is not supplied with the unit. The unit has a microprocessor controller to maintain temperature, control additional heat pumps and monitor flow through the unit for safety reasons.
INTENDED USE The heat pump is design to be installed outdoors and heat water to be storage in a remote
central storage location. The wetted parts in the heat pump are food grade however Thermex takes no responsibility for the quality of the water being heated. Any other use of this water heat pump is a not as it is intended.
8
Heat Pump Manual
HOT WATER CIRCUIT The hot water circuit consists of
1. Condenser heat exchanger – this may be a plate heat exchanger, a coaxial heat exchanger or shell and tube
2. Flow switch or flow meter
3. Copper pipe work
The heat pump will run whenever called unless the controller detects a drop in flow. It is important to ensure that any water treatment is passive to the wetted parts of the system
which include
· Stainless Steel
· Copper
· High Density Polyethylene
· Brass
· ABS Plastic
· Nitrile Rubber
The water to water models have a water sourced evaporator that is connected to – typically – the return condenser water from the installed chillers. This evaporator can have either a plate heat exchanger or a coaxial heat exchanger. These heat exchangers have water flowing through them that must be passive to the materials used. These include
· Stainless steel – 316
· Copper
· Brass
9
Model
THW07
Nomina
l heating capacity
– kW
7
Rated duty point
– in red
45°C 50°C 55°C 60°C 65°C 70°C
5.48 5.37 5.27 5.19 5.16 5.13
1.51 1.67
1.85 2.05 2.13 2.19
3.63 3.22 2.85 2.53 2.42 2.34
6.43 6.27 6.10 5.99 5.95 5.91
1.53 1.69 1.88 2.08 2.16 2.22
4.20 3.71 3.24 2.88 2.75 2.66
7.52 7.31
7.12 6.92 6.84 6.78
1.54 1.71 1.90 2.10 2.18 2.24
4.88 4.27 3.75 3.30 3.14 3.02
Model
THW10 and THWDW10
Nominal heating capacity
– kW
10
Rated duty point
– in red
45°C
50°C 55°C 60°C 65°C 70°C
8.11 7.94 7.79 7.65 7.59 7.55
2.19 2.43 2.69 2.97 3.08 3.17
3.70 3.27 2.90 2.58 2.46 2.38
9.51 9.27 9.05 8.83 8.74 8.67
2.21 2.45 2.72 3.01 3.13 3.22
4.30 3.78 3.33 2.93 2.80 2.69
11.15 10.84 10.51 10.22 10.10 10.01
2.23 2.48 2.74 3.04 3.16 3.26
5.00 4.37 3.84 3.36 3.20 3.07
Mo
del
THW12 and THWDW12
Nominal heating capacity
– kW
12
Rated duty point
– in red
45°C 50°C 55°C 60°C 65°C 70°C
10.59 10.39 10.29 9.86 9.69
9.55
2.69 2.99 3.34 3.71 3.86 3.98
3.94 3.47 3.08 2.66 2.51 2.40
12.41 12.16 11.91 11.69 11.60 11.53
2.71 3.01 3.35 3.74 3.90 4.02
4.58 4.04 3.56 3.13 2.98 2.87
14.55 14.20 13.83 13.51 13.38 13.28
2.75 3.05 3.38 3.76 3.91 4.03
5.29 4.66 4.09 3.59 3.42 3.29
Heat Pump Manual
TECHNICAL DATA
AIR TO WATER HEAT PUMPS
All units have a details data sheet available – the information supplied below is intended as a guide only – please contact Thermex for a copy of the individual model data sheets
20°C Ambient conditions 45°C Water supply 60% RH
Water Supply Temperature
Heating Capacity kW 10°C Ambient
Power Input – kW
COP
Heating capacity kW 20°C Ambient
Power Input – kW
COP
Heating Capacity kW 30°C Ambien t
Power Input – kW
COP
20°C Ambient conditions 45°C Water supply 60% RH
Water Supply Temperature
Heating Capacity kW 10°C Ambient
Power Input – kW
COP
Heating capacity kW 20°C Ambient
Power Input – kW
COP
Heating Capacity kW 30°C Ambien t
Power Input – kW
COP
Water Supply Temperature
Heating Capacity kW 10°C Ambient
Power Input – kW
COP
Heating capacity kW 20°C Ambient
Power Input – kW
COP
Heating Capacity kW 30°C Ambient
Power Input – kW
COP
20°C Ambient conditions 45°C Water suppl y 60% RH
10
Model
Nominal heating capacity
Rated duty point
– in red
45°C 50°C 55°C 60°C 65°C 70°C
18.62 18.18 17.78 17.40 17.25 17.13
4.77 5.28 5.83 6.40 6.63 6
.81
3.90 3.44 3.05 2.72 2.60 2.51
21.86 21.27 20.67 20.07 19.83 19.64
4.81 5.32 5.87 6.47 6.71 6.90
4.54 4.00 3.52 3.10 2.96 2.85
25.50 24.71 23.92 23.17 22.87 22.63
4.80 5.31 5.87 6.47 6.71 6.90
5.31 4.65 4.07 3.58 3.41 3.28
THW30 and THWDW30
THW30H and THWDW30
Nominal heating capacity
Rated duty point
– in red
45°C 50°C 55°C 60°C 65°C 7C
6.30 7.05 7.80 8.55 8.85 9.09
4.05 3.52 3.09 2.74 2.62 2.53
29.30 28.45 27
.50 26.45 26.03 25.69
6.30 7.05 7.80 8.55 8.85 9.09
4.65 4.04 3.53 3.09 2.94 2.83
Ambient
6.30 7.00 7.75 8.50 8.80 9.04
5.30 4.61 4.02 3.51 3.33 3.19
Model
THW40 and THWDW40
THW40H and THWDW40H
Nominal heating capacity
Rated duty point
– in red
45°C 50°C 55°C 60°C 65°C 7C
32
.70 31.95 30.90 29.95 29.57 29.27
3.99 3.45 3.00 2.66 2.54 2.45
39.05 37.10 36.00 34.70 34.18 33.76
7.55 9.30 10.30 11.50 11.98 12.36
5.17 3.99 3.50
3.02 2.85 2.73
43.90 42.85 41.30 40.20 39.76 39.41
8.40 9.35 10.30 11.50 11.98 12.36
5.23 4.58 4.01 3.50 3.32 3.19
Heat Pump Manual
TECHNICAL DATA
AIR TO WATER HEAT PUMPS
kW
20°C Ambient conditions 45°C Water suppl y 60% RH
Water Supply Temperature
Heating Capacity kW 10°C Ambient
Power Input
COP
Heating capacity kW 20°C Ambient
Power Input
COP
Heating Capacity kW 30°C Ambient
Power Input
COP
Model
kW
Water Supply Temperature
Heating Capacity kW 10°C Ambient Power Input
COP
Heating capacity kW 20°C Ambient
Power Input
COP
Heating Capacity kW 30°C
Power Input
COP
THW20 and THWDW20
20
30
20°C Ambient conditions 45°C Water suppl y 60% RH
25.50 24.85 24.10 23.45 23.19 22.98
33.40 32.30 31.15 29.80 29.26 28.83
kW
Water Supply Temperature
Heating Capacity kW 10°C Ambient
Power Input
COP
Heating capacity kW 20°C Ambient
Power Input
COP
Heating Capacity kW 30°C Ambien t
Power Input
COP
40
20°C Ambient conditions 45°C Water suppl y 60% RH
8.20 9.25 10.30 11.25
11.63 11.93
11
THW50 and THWDW50
THW50H* and THWDW50H
Nominal heating capacity
– kW
50
Rated duty point
– in red
4C 5C 55°C 60°C 65°C 70°C
42.50 41.90 41.40 41.00 40.84
40.71
11.00 12.20 13.60 15.10 15.70 16.18
3.86 3.43 3.04 2.72 2.60 2.52
49.60 48.80 48.20 47.30 46.94 46.65
11.10 12.30 13.70 15.30 15.94 16.45
4.47 3.97 3.52 3.09 2.94 2.84
58.20 57.00 55.80 54.90 54.54 54.25
11.20 12.50 13.80 15.40 16.04 16.55
5.20 4.56 4.04 3.56 3.40 3.28
Model
THW60 and THWDW60
THW60H and THWDW60H*
Nominal heating capacity
– kW
60
Rated duty point
in red
45°C 50°C 5C 60°C 65°C 70°C
52.65 52.05 51.40 50.70 50.42 50.20
13.75 15.35 17.10 19.00 19.76 20.37
3.83 3.39 3.01 2.67 2.55 2.46
61.90 60.80 59.85 59.10 58.80 58.56
13.90 15.45 17.20 19.15 19.93 20.55
4.45 3.94 3.48 3.09 2.95 2.85
72.35 70.80 69.45 68.20 67.70 67.30
14.05 15.60 17.35 19.30 20.08 20.70
5.15 4.54 4.00 3.53 3.37 3.25
Model
THW80 and THWDW80
THW80H and THWDW80H
Nominal heating capacity
– kW
80
Rated duty point
– in red
45°C 50°C 55°C 60°C 65°C 70°C
65.6 63.9 61.8 59.6 56.54 52.6
16.6 18.5 20.6 22.8 24.0 23.7
3.95 3.45 3.0 2.61 2.36 2.22
76.1 74.2 72.0 69.4 66.5 65.2
16.7 18.6 20.6 22.1 22.8 22.9
4.56 3.99 3.50 3.02 2.92 2.85
87.8 85.7 82.6 80.4 77.5 76.1
16.8 18.7 20.6 23.0 25.1 25.7
5.23 4.58 4.01 3.50 3.09 2.96
Heat Pump Manual
TECHNICAL DATA
AIR TO WATER HEAT PUMPS
Model
Water Supply Temperature Heating Capacity kW 10°C Ambient Power Input COP Heating capacity kW 20°C Ambient Power Input COP Heating Capacity kW 30°C Ambient Power Input COP
Water Supply Temperature
Heating Capacity kW 10°C Ambient
Power Input
COP
Heating capacity kW 20°C Ambient
Power Input
COP
Heating Capacity kW 30°C Ambien t
Power Input
COP
20°C Ambient conditions 45°C Water supply 60% RH
20°C Ambient conditions 45°C Water supply 60% RH
Water Supply Temperature
Heating Capacity kW 10°C Ambient
Power Input
COP
Heating capacity kW 20°C Ambient
Power Input
COP
Heating Capacity kW 30°C Ambient
Power Input
COP
20°C Ambient conditions 45°C Water supply 60% RH
12
THW100 and THWDW100
THW100H and
Nominal heating capacity
– kW
100
Duty point in red
45°C 50°C 55°C 60°C 65°C 70°C
85.00 83.80 82.80 81.80 81.40 81.08
22.00 24.40 27.20 30.00 31.12 32.02
3.86 3.43 3.04 2.73 2.62 2.53
99.20 97.60 96.40 94.60 93.88 93.30
22.20 24.60 27.40 30.60 31.88 32.90
4.47 3.97 3.52 3.09 2.94 2.84
116.40
114.00
111.60
109.80
109.08
108.50
22.40 25.00 27.60 30.80 32.08 33.10
5.20 4.56 4.04 3.56 3.40 3.28
THW150 and THWDW150
Nominal
heating capacity
– kW
150
4C 50°C 55°C 60°C 65°C 70°C
131.2 127.8 123.6 118.8 113.4 107.4
33.2 37 41.2 45.8 50.8 56.4
3.69 3.45 3.00 2.59 2.23 1.90
152.2 148.4 144.0 138.8 133.0 126.6
35.8 37.2 41.2 46.0 51.6 58.0
4.25 3.99 3.50 3.02 2.58 2.18
175.6 171.4 166.4 160.6 154.2 147.0
36.0 37.2 41.4 46.0 51.0 55.4
4.88 4.61 4.02 3.49 3.02 2.65
Minimum flow requirements across the unit
- litres/ second
7 and 10kW
1.0 2.4 0.8 20kW
1.0 2.4 0.8
30kW
1.5 3.6 1.2 40kW
2.0 4.8 1.6 50kW
2.4 6.0 1.9 60kW
2.9 7.2 2.3 80kW
3.8 9.5 3.0 100kW
4.8 11.8 3.8 130kW
6.2 15.5 5.0 150kW
7.2 18.0 5.8 200kW
9.6 23.5 7.7
TECHNICAL DATA
AIR TO WATER HEAT PUMPS
Model
Water Supply Temperature
Heating Capacity kW 10°C Ambient
Power Input
COP
Heating capacity kW 20°C Ambient
Power Input
COP
Heating Capacity kW 30°C Ambient
Power Input
COP
Model
Water Supply Temperature
Heating Capacity kW 10°C Ambient
Power Input
COP
Heating capacity kW 20°C Ambient
Power Input
COP
Heating Capacity kW 30°C Ambient
Power Input
COP
Heat Pump Manual
THWDW100H
20°C Ambient conditions 45°C Water supply 60% RH
Model Across condenser Across condenser high
water temperature units >60C
Across evaporator – water to water units
13
Electrical Data
– All units
10kW
13.1 19.4 105
20kW
15.7 22.0 111
17.5 24.5 118
27.1 38.0 173
33.6 47.0 225
38.0 49.0 272
51.2 76.0 173
56.6 94.3 225
130kW
86.2 98.2 272
150kW
103.0
144.0
173
142.0
181.5
225
380/415 V 3 Phase 50 hz + N and E
Delta Δ
Direct on line
Water Connections
– All units
- all female BSP brass fittings
Model
Supply/ Return
Evaporator water
– water to water units
20kW
1 1 30kW
1 ½
1 ½
40kW
1 ½
1 ½
50kW
1 ½
1 ½
60kW
2 2
80kW
2 2
100kW
2 2
130kW
2 2
150kW
2 2
200kW
2 ½
2 ½
Swimming pool heat pumps
2 PVC screwed connection
PERFORMANCE DATA
Model
THWW20 THWW40 THWW50 THWW60 THWW80
Nominal heating
Heating Capacity
4.8 4.8 9.5 9.5 12.2 12.2 15.1 15.1 17.9 17.9
4.6 3.5 4.0 3.1 4.1 3.2 4.1 3.2 4.3 3.2
8.1 7.1 7.3 7.3 7.5
TECHNICAL DATA
Heat Pump Manual
Model Maximum A/ Phase Maximum continuous
current
30kW 40kW 50kW 60kW 80kW 100kW
200kW Power requirement Compressor wiring Compressor start method
Locked rotor amps ­per compressor
WATER TO WATER HEAT PUMPS
Performance Chart at 40/45°C Water Return/ Supply
50°C Condensing temperature – 20°C/ 15°C evaporator water
capacity – kW
– kW
Power Input
COP
Total unit COP
20 40 50 60 80
Heating
Capacity
Cooling
21.9 17.0 38.1 29.7 49.6 38.5 61.9 48 76.1 59.4
Side
Heating
Capacity
Cooling
Side
Heating
Capacity
Coolin
g Side
Heating
Capacity
Cooling
Side
Heating
Capacity
Cooling
Side
14
PERFORMANCE DATA
Pe
rformance Chart at 40/45
°C Water Return/ Supply
Model
THWW100
THWW1
50 THWW200
THWW250
Nominal
Heating
Cooling
Side Heating
Cooling
Side Heating
Cooling
Side Heating
Cooling
Side Heating
Power
4.1 3.2 3.9 3.3 4.0 3.1 4.1 3.2
Total Unit
GENERAL INFORMATION
Model
THWW20
THWW40
THWW50
THWW60
THWW80
kPa 50 50 50 50 50
kPa075
dB at 3m
60 60 60 61 62 GENERAL INFORMATION
Model
THWW100
THWW150
THWW200
THWW250
Pressure drop across
kPa 50 50 50 50
Pressure drop across
kPa 50 50 50 50
dB at
TECHNICAL DATA
50°C Condensing temperature – 20°C/ 15°C evaporator water
Heat Pump Manual
heating capacity – kW
Capacity – kW
Input COP
COP
100 150 200 250
Capacity
99.2 77 152.2 118.8 198.4 154 247.6 192
24.4 24.4 35.8 35.8 49.2 49.2 60.4 60.4
7.3 7.2 7.1 7.3
Pressure drop across condenser
Pressure drop across evaporator
condenser (heating side)
(cold side)
Noise rating at 3m
evaporator (cold side)
Noise rating at 3m
3m
Capacity
Capacity
Capacity
50 50 50 50 50
62 63 63 64
15
valve
Heat Pump Manual
HEATING SYSTEM SCHEMATIC
THW20, THW40 and THW60
Heating System Schematic Symbols
Liquid receiver
Pump
Compressor
Sight glass
THW80 and THW120
Air Cooled
Evaporator
One way valve
TX valve
Drier
Pressure
transducer
Ball valve
Flow meter
Pressure
gauge
Low pressure switch
Motorised ball valve
Pressure relief valve
Hot gas bypass
valve
Drain
Expansion tank
Strainer
Isolation valve
Thermowell
Water
regulating
High pressure
switch
Plate heat
exchanger
16
Heat Pump Manual
DIMENSIONS .dxf and .dwg files are available for all models – please contact Thermex for details
THW07
THW20
17
DIMENSIONS
Heat Pump Manual
THW30 and THW40
THW50 and THW60
18
DIMENSIONS
Heat Pump Manual
THW80
THW100 AND THW130
Loading...
+ 40 hidden pages