Thermador REF30, RES30, RDF30, RDFS30, RDSS30 INSTALLATION INSTRUCTIONS MANUAL

UL LISTED #159J FILE # E8719
INSTALLATION INSTRUCTIONS MANUAL
30" FREE-STANDING and SLIDE-IN RANGES
ELECTRIC MODELS REF30, RES30
DUAL-FUEL MODELS RDF30, RDFS30 & RDSS30
PLEASE READ ENTIRE INSTRUCTIONS BEFORE PROCEEDING.
IMPORTANT: Save these instructions for the local electrical inspector’s use.
OWNER: Please retain these instructions for future reference.
WARNING: Before installing turn power OFF at the service panel. Lock service panel to prevent
power from being turned ON accidentally.
AVERTISSEMENT: Avant l’installation, COUPER au tableau de service, et fermer a clef le tableau de service
pour empecher l’alimination d’etre allumée per hasard.
IMPORTANT:
AND GROUNDING MUST COMPLY WITH ALL APPLICABLE CODES.
Check your local building codes for the proper method of installation. In the U.S.A., if there are no applicable local codes, this unit should be installed in accordance with the National Fuel Gas Code #Z223.1-Current Issue, and the National Electrical Code ANSI/NFPA No. 70 Current Issue. (In Canada, installation must be in accordance with the CAN 1-B149.1 and .2 - Installation Codes for Gas Burning Appliances and/ or local codes).
WARNING: If the information in this manual
is not followed exactly, a fire or explosion may
result causing property damage, personal
injury or death.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in your building.
Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions.
LOCAL CODES VARY. INSTALLATION, ELECTRICAL CONNECTIONS
MOBILE home installation must conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280 {formerly the Federal Standard for Mobile Home Construction and Safety, Title 24, HUD (Part 280)} or, when such standard is not applicable, the Standard for Manufactured Home Installations, ANSI A255.1 / NFPA501A, or with local codes.
AVERTISSEMENT: Si l'information dans ce manuel n'est pas suivie exactement, un feu ou une explosion peut résulter et causer des dégâts matèriels et des risques d'accidents, ou la mort.
Ne pas emmagasiner ou utiliser de l’essence ou des autres vapeurs inflammables et liquides aux endroits de celui-ci ou aucun autre appareil.
CE QUI FAIRE SI VOUS SENTEZ LE GAZ
Ne pas essayer d’allumer aucun appareil
Ne pas toucher aucun interrupteur électrique; ne pas utiliser aucun téléphone dans votre bâtiment.
Appeler immédiatement votre fournisseur de gaz du téléphone d’un voisin. Suivre l’instruction du fournisseur de gaz.
If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Si vous ne pouvez pas contacter votre fournisseur, téléphoner le service des incendies.
L’installation et le service doivent être exécutés par un installateur qualifié, une agence de service ou le fournisseur de gaz.
1
SAFETY INSTRUCTION
WARNING: Improper installation, adJustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency, manufacturer (dealer) or the gas supplier.
WARNING: This unit is designed as a cooking appliance. Based on safety considerations, never use it for warming or heating a room.
NOTICE: DO NOT LIFT RANGE BY DOOR HANDLE. Remove the door for easier handling and
installation. See ‘Do-It Yourself Maintenance: Removing the Oven Door’ in the Care and Use Manual.
TABLE OF CONTENTS
Safety Instructions and Applicable Codes ......................................................................................... 1, 2
Ventilation and Cabinet Considerations ............................................................................................ 2, 3
Gas Connections (Models RDF/RDFS/RDSS only) ......................................................................... 3, 4
Electrical Connections ........................................................................................................................... 5, 6
Anti-Tip Warning ......................................................................................................................................... 7
Range Installation ........................................................................................................................................ 8
ADVERTISSEMENT: L’installation inexacte, l’ajustment, la modification, le service ou I’entretien peut causer la blessure ou la propriété endommagee. Se référer â ce manuel. Pour l‘assistance ou l‘information additionnelle consulter un installateur qualifié, une agence de service, le fabricant (le marchand) ou le fournisseur de gaz.
ADVERTISSEMENT: L’appareil est pour la cuisson. Basé sur les considerations de securité, ne jamais utiliser le Cooktop pour chauffer une chambre.
VENTILATION AND CABINET CONSIDERATIONS
OVERHEAD VENTILATION
It is strongly recommended to install a hood above this range. For most kitchens with a wall mounted hood, a certified hood rating of not less than 350 CFM is recommended. Thermador hoods rated at 350 CFM or more when operated on High meet the above requirement and are recommended for this purpose. The range hood must be installed according to instructions furnished with the hood.
CABINET
This unit is designed for installation in a countertop near adjacent walls and projecting surfaces constructed of combustible materials. There must be a minimum clearance of 30 inches between the top of the cooking surface and the bottom of an unprotected wood or metal cabinet; or 24 inches when bottom of wood or metal cabinet is protected by not less than 1/4" of flame retardant material covered with not less than No. 28 MSG sheet metal, 0.015 inch stainless steel’ or 0.024 inch aluminum or copper. (See Figure I). The minimum horizontal distance(s) from the side and back edge of the unit to adjacent vertical combustible walls are as follows: Zero clearance is permitted on rear, right and left walls.
For the cabinets over the cooking surface and the adjacent cabinets, the maximum cabinet depth from back wall is 13 inches.
Instructions were determined using Standard American base cabinets measuring 36" high x 24" deep (see Figures 2 & 3).
When installed, the range must extend beyond the cabinet doors/drawers. In an layout a notch on the countertop on each side so the back of the notches line up with the front of the cabinet doors. (See NOTCH INSERT in Figure 3).
island or peninsula installation, first
2
VENTILATION AND CABINET CONSIDERATIONS
Layout the remaining dimensions positioned from the back of these notches.
If nonstandard cabinets are used, care should be taken to alter dimensions accordingly.
NOTICE: Some cabinet flnishes cannot survive the temperatures allowed by U.L., particularly self­cleaning ovens; the cabinets may discolor or stain. This is most noticeable with laminated cabinets. If your cabinet company does not approve a temperature of 180° F., the range should be installed such that the oven front frame does NOT line up BEHIND the pane of the front of the cabinet doors.
CAUTION: To eliminate the risk of burns or flre by reaching over heated surface units, cabinet storage space located above the surface units should be avoided. If cabinet storage is to be provided, the risk can be reduced by installing a range hood that projects horizontally a minimum of 5 inches beyond the bottom of the cabinets.
ATTENTION: Pour élimıner le risque de brûlures ou d’incendie en atteindrant sur les unités de la surface chauffés, I’espace d’emmagasinage de l’armoire localisée audessus des unités de la surface doit être evitée. Si l’emmagasinage de l’amoire est d’être fourni, le risque peut être réduit par l’installation d’un capot de la cuisiniêre qui projette horizontalement un minimum de 5 pouces au delâ du fond des armoires.
GAS CONNECTION (MODELS RDF30, RDFS30 & RDSS30)
Be sure the unit being installed is compatible with the type of gas available. The range is shipped from the
factory for use with natural gas.
Conversion for use with propane gas can be made by using a kit, NLPK1T 6, P/N 35-00-688. Only a qualified technician or installer should convert the range.
This kit includes instructions for adjusting valves and pressure regulator and contains new burner jets. The RDFS and RDSS models are equipped with an intermittent/interrupted ignition device (ExtraLow®).
NATURAL GAS
The range is shipped from the factory for use with natural gas only. The gas supply to the appliance regulator must be a minimum of 6.0" water column. The maximum gas pressure to the appliance regulator shall not exceed 14" W. C..
PROPANE GAS
CAUTION: When connecting unit to propane gas,
make certain the propane gas tank is equipped with its own high pressure regulator in addition to the pressure regulator supplied with the appliance. The gas supply to the appliance regulator must be a minimum of 11.0" water column. The maximum gas pressure to the appliance regulator is not to exceed
14.0" water column from the propane gas tank.
ATTENTION: En branchant l’appareil au gaz de propane, soyez certain que le réservoir de gaz du propane est équipé avec son régulateur de haute pression en addition du régulateur de pression fourni avec cet appareil. La fourniture de gaz au régulateur de l’appareil doit être un minimum de 11.0" colonne d’eau. La pression de gaz maximale â cet appareil ne doit pas excéder une colonne d’eau de 14.0 pouces du régulateur du reservoir de gaz du propane.
3