Teledyne RCP2-1100, RCP2-1200, FPRC-1200, FPRC-1100 Operation Manual

Redundant System Controllers
RCP2-1100/RCP2-1200
FPRC-1100/FPRC-1200
Operations Manual
RCP2-1100, 1:1 Redundant System Controller
RCP2-1200, 1:2 Redundant System Controller
FPRC-1100, 1:1 Phase Combined System Controller
Teledyne Paradise Datacom LLC Phone: (814) 238-3450 328 Innovation Blvd., Suite 100 Fax: (814) 238-3829 State College, PA 16803 USA Web: www.paradisedata.com Email: sales@paradisedata.com
209351 REV B ECO 17314 08/27/2013
FPRC-1200, 1:2 Phase Combined System Controller
Teledyne Paradise Datacom, a Teledyne Telecommunications company, is a single source for high power solid state amplifiers (SSPAs), Low Noise Amplifiers (LNAs), Block Up Converters (BUCs), and Modem products. Operating out of two primary locations, Witham, United Kingdom, and State College, PA, USA, Teledyne Paradise Datacom has a 20 year history of providing innovative solutions to enable satellite uplinks, battlefield communications, and cellular backhaul.
Teledyne Paradise Datacom Teledyne Paradise Datacom
328 Innovation Blvd., Suite 100 2&3 The Matchyns, London Road, Rivenhall End State College, PA 16803 USA Witham, Essex CM8 3HA United Kingdom (814) 238-3450 (switchboard) +44 (0) 1376 515636 (814) 238-3829 (fax) +44 (0) 1376 533764 (fax)
Information in this document is subject to change without notice. The latest revision of this document may be downloaded from the company web site: http://www.paradisedata.com.
No part of this document may be reproduced or transmitted in any form without the written permission of Teledyne Paradise Datacom.
All rights are reserved in this document, which is property of Teledyne Paradise Datacom. This document contains proprietary information and is supplied on the express condition that it may not be disclosed, reproduced or transmitted in any form without the written permission of Teledyne Paradise Datacom.
All other company names and product names in this document are property of the respective companies.
2 209351 REV B Operations Manual, Redundant System Controllers
© 2013 Paradise Datacom LLC
Printed in the USA
Table of Contents
Table of Contents ..................................................................................................................... 3
Section 1: General Information ............................................................................................... 9
1.0 Introduction ............................................................................................................... 9
1.1 Description ................................................................................................................ 9
1.2 Equipment Supplied .................................................................................................. 9
1.3 Specifications .......................................................................................................... 10
1.3.1 Outline Drawings ...................................................................................... 10
1.4 Safety Considerations ............................................................................................. 11
1.4.1 High Voltage Hazards .............................................................................. 11
1.4.2 High Current Hazards .............................................................................. 11
Section 2: Description ............................................................................................................ 13
2.0 Introduction ............................................................................................................. 13
2.1 Inspection ................................................................................................................ 13
2.2 Mounting ................................................................................................................. 13
2.3 Storage and Shipment ............................................................................................ 13
2.4 Prime Power Connection (J1, J2) ........................................................................... 13
2.5 Cable Connections .................................................................................................. 14
2.6 Removable Power Supply Modules ........................................................................ 18
Section 3: Front Panel Overview & Operation ..................................................................... 21
3.0 Introduction ............................................................................................................. 21
3.1 Local / Remote control ............................................................................................ 24
3.2 Methods of switching .............................................................................................. 24
1.4.3 Electrical Discharge Hazards ................................................................... 12
2.5.1 Control Cable Connector (J3) - MS3112E16-23S .................................... 14
2.5.2 Serial Port, Main (J4) - DB9 (F) ................................................................ 14
2.5.3 Serial Port, Local (J5) - DB9 (M) .............................................................. 15
2.5.4 Program Port (J6) - DB25 (M) .................................................................. 15
2.5.5 Parallel I/O Connector (J7) - DB37 (F) ..................................................... 15
2.5.6 External Alarm Port (J8) - DB9 (F) [IO Board Version 001]...................... 17
2.5.7 Ethernet Port (J9) - RJ45 (F) .................................................................... 17
2.6.1 24V Power Supply Module ....................................................................... 18
2.6.2 24V Power Supply Module, High Power option ....................................... 19
2.6.3 48V Power Supply Module ....................................................................... 20
3.0.1 System Identification ............................................................................... 21
3.0.2 Fault Indicators ........................................................................................ 21
3.0.3 Signal Path Mimic Display ....................................................................... 21
3.0.4 Amplifier Select Keys .............................................................................. 22
3.0.5 Vacuum Fluorescent Display .................................................................. 22
3.0.6 Main Menu Key ....................................................................................... 22
3.0.7 Local / Remote Key ................................................................................. 23
3.0.8 Auto / Manual Key ................................................................................... 23
3.0.9 Display Navigation Keys ......................................................................... 23
3.0.10 Enter Key .............................................................................................. 23
3.2.1 Manual Mode .......................................................................................... 24
Operations Manual, Redundant System Controllers 209351 REV B 3
3.2.2 Auto Mode ............................................................................................... 24
3.2.3 Physically Rotating Transfer Switch ........................................................ 24
3.3 Local (Front Panel) Menu Structure ........................................................................ 25
3.3.1 Sys Info .................................................................................................... 26
3.3.1.1 Sys Info - Page 1 ....................................................................... 27
3.3.1.2 Sys Info - Page 2 ...................................................................... 27
3.3.1.3 Sys Info - Page 3 ..................................................................... 28
3.3.1.4 Sys Info - Page 4 ..................................................................... 29
3.3.1.5 Sys Info - Page 5 ..................................................................... 29
3.3.1.6 Sys Info - Page 6 ..................................................................... 30
3.3.1.7 SSPA Subsystem Information - Pages 1-5............................... 31
3.3.1.8 IP Info - Page 1 ........................................................................ 31
3.3.1.9 IP Info - Page 2 ........................................................................ 31
3.3.1.10 IP Info - Page 3 ...................................................................... 32
3.3.1.11 IP Info - Page 4 ...................................................................... 32
3.3.2 Serial Communication Parameters .......................................................... 33
3.3.2.1 Protocol ................................................................................... 33
3.3.2.2 Baud Rate ............................................................................... 33
3.3.2.3 Sys. Address ............................................................................ 34
3.3.2.4 Interface ................................................................................... 34
3.3.2.5 IP Setup .................................................................................... 34
3.3.3 Operations Menu ...................................................................................... 34
3.3.3.1 System ..................................................................................... 34
3.3.3.2 Buzzer ...................................................................................... 34
3.3.3.3 Control ...................................................................................... 35
3.3.3.4 Switching .................................................................................. 35
3.3.3.5 Priority ..................................................................................... 35
3.3.3.6 Stby. Select ............................................................................. 35
3.3.4 Fault Setup ............................................................................................... 35
3.3.4.1 MjrFaults .................................................................................. 36
3.3.4.2 AuxFaults ................................................................................ 36
3.3.4.3 RFSw.Faults ............................................................................ 36
3.3.4.4 Fault Logic ................................................................................. 36
3.3.4.5 Fault Latch ................................................................................ 36
3.3.5 Options Menu ........................................................................................... 37
3.3.5.1 Backup .................................................................................... 37
3.3.5.2 Restore .................................................................................... 37
3.3.5.3 Lamp Test ............................................................................... 37
3.3.5.4 Password ................................................................................. 37
3.3.5.5 Reset ....................................................................................... 38
3.3.5.6 More ........................................................................................ 38
3.3.5.7 Fault Tolerance ....................................................................... 38
3.3.5.8 Sys ID ...................................................................................... 38
3.3.5.9 VFD Light ................................................................................. 38
3.3.5.10 SSPA ..................................................................................... 38
3.3.6 Calibration Menu ...................................................................................... 39
3.3.6.1 Flt. Window .............................................................................. 39
3.3.6.2 LNA/LNB PS ............................................................................ 39
3.3.6.3 Calibrate .................................................................................. 39
3.3.6.4 View LNA ................................................................................. 40
4 209351 REV B Operations Manual, Redundant System Controllers
Section 4: System Setup & Control with RCP ...................................................................... 41
4.0 Introduction ............................................................................................................. 41
4.1 Operation of 1:1 System with RCP2-1100 .............................................................. 41
4.1.1 LNA / LNB 1:1 Redundant System Operation ......................................... 42
4.1.1.1 LNA/LNB Fault Tracking ............................................................ 43
4.1.1.2 LNA / LNB Current Calibration .................................................. 43
4.1.2 SSPA 1:1 Redundant System Operation ................................................. 44
4.1.2.1 External Alarm Tracking ............................................................ 44
4.2 Operation of 1:2 System with RCP2-1200 .............................................................. 45
4.2.1 LNA / LNB 1:2 Redundant System Operation .......................................... 45
4.2.1.1 LNA/LNB Fault Tracking ............................................................ 47
4.2.1.2 LNA / LNB Current Calibration .................................................. 47
4.2.2 SSPA 1:2 Redundant System Operation ................................................. 48
4.2.2.1 External Alarm Tracking ............................................................ 48
4.3 Operation of 1:1 Fixed Phase Combined System with FPRC-1100 ....................... 49
4.4 Operation of 1:2 Fixed Phase Combined System with FPRC-1200 ....................... 50
4.5 RCP Remote Control of System SSPAs ................................................................. 51
4.5.1 Configuring the RCP for Remote Control Mode ....................................... 52
4.5.2 Using M&C features of RCP to control a SSPA system ........................... 54
4.5.2.1 Change Mute State ................................................................... 54
4.5.2.2 Change Attenuation Level ......................................................... 54
4.5.2.3 Change Switch mute option value ............................................. 55
4.5.2.4 Units .......................................................................................... 55
4.6 View SSPA System Info .......................................................................................... 56
4.7 Advanced system level troubleshooting with RCP .................................................. 57
4.7.1 Scenario 1 ................................................................................................ 57
4.7.2 Scenario 2 ................................................................................................ 58
Section 5: Theory of Operation ............................................................................................. 59
5.0 Design Philosophy .................................................................................................. 59
5.0.1 Redundant Power Supplies ...................................................................... 59
5.0.2 Digital Core Board .................................................................................... 60
5.0.3 I/O Board Assembly ................................................................................. 61
5.0.4 Vacuum Fluorescent Display ................................................................... 61
5.0.5 Front Panel Mimic Display ....................................................................... 62
5.1 Control Cable Considerations ................................................................................. 62
Section 6: Maintenance & Troubleshooting ......................................................................... 65
6.0 Introduction ............................................................................................................. 65
6.1 Fuse Replacement .................................................................................................. 65
6.2 Firmware Programming .......................................................................................... 66
6.2.1 Hardware Interface ................................................................................... 66
6.2.2 RCP Flash Upgrade ................................................................................. 66
6.3 Restoring Factory Pre-set Settings on RCP2/FPRC ............................................... 68
6.3.1 Automatic restore ..................................................................................... 68
6.3.2 Manual restore ......................................................................................... 68
6.4 Identifying and Replacing a Failed Power Supply ................................................... 69
6.4.1 Removing a Faulted Power Supply Module ............................................. 70
6.4.2 Installing a New Power Supply Module .................................................... 70
Operations Manual, Redundant System Controllers 209351 REV B 5
Section 7: Remote Control Interface ..................................................................................... 71
7.0 Overview ................................................................................................................. 71
7.1 Remote Control - Parallel ....................................................................................... 72
7.1.1 Control Outputs ....................................................................................... 72
7.1.2 Control Inputs .......................................................................................... 73
7.2 Serial Communication ............................................................................................. 74
7.2.1 Header Packet ......................................................................................... 74
7.2.1.1 Frame Sync Word ..................................................................... 74
7.2.1.2 Destination Address .................................................................. 74
7.2.1.3 Source Address ......................................................................... 75
7.2.2 Data Packet .............................................................................................. 75
7.2.2.1 Protocol ID ................................................................................. 75
7.2.2.2 Request ID ................................................................................ 75
7.2.2.3 Command .................................................................................. 75
7.2.2.4 Data Tag .................................................................................... 76
7.2.2.5 Data Address / Error Status / Local Port Frame Length ............ 77
7.2.2.6 Data Length ............................................................................... 78
7.2.2.7 Data Field .................................................................................. 78
7.2.3 Trailer Packet ........................................................................................... 79
7.2.3.1 Frame Check Sequence ............................................................ 79
7.2.4 Timing issues ........................................................................................... 80
7.3 Accessing optional SSPA subsystem through Packet Wrapper technique ............. 81
7.4 Examples ................................................................................................................ 86
7.4.1 Example 1 ................................................................................................ 86
7.4.2 Example 2 ................................................................................................ 88
7.4.3 Example 3 ................................................................................................ 89
7.4.4 Example 4 ................................................................................................ 90
7.5 Terminal Mode Serial Protocol ................................................................................ 91
7.6 Ethernet Interface ................................................................................................... 95
7.6.1 Overview .................................................................................................. 95
7.6.2 IPNet Interface ......................................................................................... 95
7.6.2.1 General Concept ....................................................................... 95
7.6.2.2 Setting IPNet interface .............................................................. 96
7.6.3 Using the RCP2 Web Interface ................................................................ 98
7.6.4 SNMP interface ...................................................................................... 100
7.6.4.1 Introduction .............................................................................. 100
7.6.4.2 SNMP MIB tree ....................................................................... 101
7.6.4.3 Description of MIB entities ....................................................... 105
7.6.4.4 Configuring RCP2 unit to work with SNMP protocol ................ 106
7.6.4.5 Connecting to a MIB browser .................................................. 107
Section 8: Maintenance Switch Controller ......................................................................... 109
8.0 Introduction ........................................................................................................... 109
8.1 Operation Modes ................................................................................................. 109
8.1.1 Directing the Output Signal to the System Output ................................. 109
8.1.2 Directing the Output Signal to the Dummy Load .................................. 109
6 209351 REV B Operations Manual, Redundant System Controllers
Appendix A: Ethernet Interface Quick Set-Up ................................................................... 111
Appendix B: Proper 10/100 Base-T Ethernet Cable Wiring .............................................. 115
Appendix C: RCP Control with Paradise Datacom Universal M&C .................................. 119
Appendix D: Firmware Revision History ............................................................................ 123
Appendix E: Documentation ................................................................................................ 125
Figures
Figure 1-1: Outline Drawing, RCP2-1100 Redundant System Controller ..................... 10
Figure 2-1: RCP2/FPRC-1100/1200 Rear Panel .......................................................... 14
Figure 2-2: Rear panel view of J3, MS3112E16-23S .................................................... 14
Figure 2-3: Removable Power Supply Module ............................................................. 18
Figure 2-3: Removable Power Supply Module, High Power Option ............................. 19
Figure 2-5: 48V Removable Power Supply Module ...................................................... 20
Figure 3-1: RCP2/FPRC Front Panel, showing RCP2-1200 Mimic Display.................. 21
Figure 3-2: Fault Indicators ........................................................................................... 21
Figure 3-3: Signal Path Mimic Display .......................................................................... 22
Figure 3-4: Main Menu Initial Menu Selection ............................................................... 25
Figure 3-5: System Information Menu Structure ........................................................... 26
Figure 3-6: Serial Communication Parameters Menu ................................................... 33
Figure 3-7: Operation Parameters Menu ...................................................................... 34
Figure 3-8: Fault Setup Parameters Menu .................................................................... 35
Figure 3-9: Options Parameters Menu .......................................................................... 37
Figure 3-10: Calibration Parameters Menu ................................................................... 39
Figure 4-1: Block Diagram, 1:1 Redundant System ...................................................... 41
Figure 4-2: Indoor/Outdoor Components, 1:1 Redundant System ............................... 42
Figure 4-3: Typical Schematic, 1:1 Redundant LNA System ........................................ 43
Figure 4-4: Schematic, Typical 1:1 Redundant SSPA System ..................................... 44
Figure 4-5: Block Diagram, 1:2 Redundant System ...................................................... 45
Figure 4-6: System Components, 1:2 Redundant LNA System .................................... 46
Figure 4-7: Schematic, Typical 1:2 Redundant LNA System ........................................ 47
Figure 4-8: Block Diagram, 1:2 SSPA Redundant System ........................................... 48
Figure 4-9: Block Diagram, 1:1 Fixed Phase Combined System .................................. 49
Figure 4-10: Block Diagram, 1:2 Fixed Phase Combined System ................................ 50
Figure 5-1: Block Diagram, Power Supply Configuration .............................................. 60
Figure 5-2: Block Diagram, RCP Digital Core Board .................................................... 61
Figure 5-3: Cable Losses to Transfer Switch ................................................................ 63
Figure 6-1: Controller Internal Part Identification and Rear Panel Fuse Location ......... 65
Figure 6-2: Firmware Upgrade Terminal Window ......................................................... 67
Figure 7-1: RCP2 Remote Control Interface Stack ....................................................... 71
Figure 7-2: Parallel I/O Form C Relay .......................................................................... 72
Figure 7-3: Opto-Isolated Parallel I/O Input .................................................................. 73
Figure 7-4: Basic Communication Packet ..................................................................... 74
Figure 7-5: Header Sub-Packet .................................................................................... 74
Figure 7-6: Data Sub-Packet ........................................................................................ 75
Figure 7-7: Trailer Sub-Packet ...................................................................................... 79
Figure 7-8: Packet Wrapper access to SSPA subsystem ............................................. 80
Figure 7-9: Connection Description .............................................................................. 93
Figure 7-10: Communication Port Selection ................................................................. 93
Figure 7-11: Communication Properties ....................................................................... 93
Figure 7-12: ASCII Setup .............................................................................................. 93
Operations Manual, Redundant System Controllers 209351 REV B 7
Tables
Figure 7-13: Terminal Mode Example ........................................................................... 94
Figure 7-14: UDP Redirect Frame Example ................................................................. 96
Figure 7-15: Web interface screen ................................................................................ 98
Figure 7-16: GetIF Application Parameters Tab ......................................................... 107
Figure 7-17: Getif MBrowser window, with update data in output data box ................ 107
Figure 8-1: Press POS1 key to direct signal to system output .................................... 109
Figure 8-2: Press POS2 key to direct signal to dummy load ...................................... 109
Figure A-1: TCP/IP Properties Window ...................................................................... 111
Figure B-1: Modular Plug Crimping Tool ..................................................................... 115
Figure B-2: Transmission Line .................................................................................... 115
Figure B-3: Ethernet Cable Pin-Outs .......................................................................... 116
Figure B-4: Ethernet Wire Color Code Standards ....................................................... 117
Figure B-5: Wiring Using 568A Color Codes .............................................................. 117
Figure B-6: Wiring Using 568A and 568B Color Codes .............................................. 117
Figure C-1: New RCP2 Dialog Window ...................................................................... 119
Figure C-2: Status Window ......................................................................................... 120
Figure C-3: Faults Window ......................................................................................... 120
Figure C-4: Settings Window ...................................................................................... 121
Figure C-5: IP Setup Window ..................................................................................... 121
Table 2-1: J3 Switch Connector, MS3112E16-23S ...................................................... 14
Table 2-2: Main Serial Port Pin Out .............................................................................. 15
Table 2-3: Local Serial Port Pin Out ............................................................................. 15
Table 2-4: Parallel I/O Signals ...................................................................................... 16
Table 2-5: External Alarm Port Pin Out ......................................................................... 17
Table 2-6: Ethernet Port (J9) pin outs ........................................................................... 17
Table 4-1: Compact Outdoor SSPA Wiring ................................................................... 52
Table 4-2: Rack Mount SSPA Wiring ............................................................................ 53
Table 4-3: vBUC Wiring ................................................................................................ 53
Table 5-1: Commonly Used Waveguide Transfer Switches ......................................... 62
Table 5-2: Maximum Cable Length for Selected Switches (Single Switch Systems) .... 63
Table 7-1: Command Byte Values ................................................................................ 76
Table 7-2: Data Tag Byte Values .................................................................................. 77
Table 7-3: Error Status Byte Values ............................................................................. 78
Table 7-4: Request Frame Structure ............................................................................ 81
Table 7-5:. Response Frame Structure ......................................................................... 82
Table 7-6: System Settings Data Values ...................................................................... 83
Table 7-7: System Condition Data Values .................................................................... 84
Table 7-8: System Threshold Data Values ................................................................... 85
Table 7-9: ADC (Analog-Digital Converter) Addressing ................................................ 85
Table 7-10: OSI Model for RM SSPA Ethernet IP Interface ......................................... 97
Table 7-11: Detailed Settings ...................................................................................... 102
Table 7-12: Detailed Thresholds ................................................................................. 103
Table 7-13: Detailed Conditions .................................................................................. 104
Table D-1: Firmware revision history .......................................................................... 123
8 209351 REV B Operations Manual, Redundant System Controllers
Section 1: General Information
1.0 Introduction
This section provides the general information for the Teledyne Paradise Datacom LLC line of Redundant Control Panels. The RCP2-1100 and RCP2-1200 are used for 1:1 and 1:2 redundant systems, respectively. The FPRC-1100 and FPRC-1200 are used for Phase Combined Solid State Power Amplifier (SSPA) systems.
This section describes the supplied equipment and safety precautions.
1.1 Description
The RCP2/FPRC controller is used to monitor and control amplifiers configured in 1:1 and 1:2 redundant systems. The RCP2-1100 and FPRC-1100 controllers provide control of two amplifiers and their corresponding transfer switch. The RCP2-1200 and FPRC-1200 controllers monitor and control three amplifiers and two switches.
The RCP/FPRC Series of redundant controller can be used in LNA, LNB, and SSPA systems as well as frequency converter systems. A mimic display on the front panel indicates the RF path and the fault status of the equipment. User interface and control is provided in three forms:
Front Panel, Local Control
37 pin Parallel Control Port with Contact Closures and Opto-Isolated Inputs
Serial Data Control via RS232 or RS485 (4-wire)
Additional features include:
Universal Input, Power Factor Corrected Power Supply
User Friendly Front Panel LCD Display for Local Monitor & Control
Dual AC Mains Entries with removable power supplies.
1.2 Equipment Supplied
The following equipment is supplied with each unit:
The RCP2/FPRC Redundant Controller
(2) IEC Line Cord Sets
Redundant Controller Operations Manual
Operations Manual, Redundant System Controllers 209351 REV B 9
Optional Equipment includes:
Rack Slides
100 ft. (30 m ) Control Cable
Switch Plate Mating Connector
DC Operation
1.3 Specifications
Refer to the specification sheets in Appendix E for complete specifications on the
RCP2/FPRC Redundant System Controllers.
1.3.1 Outline Drawings Figure 1-1 shows an outline drawing of an RCP2-1100 redundant controller. The
outline drawings for the RCP2-1200 and FPRC units are the same in dimension, with differences only in the signal path mimic display and the number of fault indicators.
Figure 1-1: Outline Drawing, RCP2-1100 Redundant System Controller
10 209351 REV B Operations Manual, Redundant System Controllers
1.4 Safety Considerations
Potential safety hazards exist unless proper precautions are observed when working with this unit. To ensure safe operation, the user must follow the information, cautions and warnings provided in this manual as well as the warning labels placed on the unit.
1.4.1 High Voltage Hazards
High Voltage for the purpose of this section is any voltage in excess of 30 volts. Voltages above this value can be hazardous and even lethal under certain circumstances. Care should be tak­en when working with devices that operate at high voltage.
All probes and tools that contact the equipment should be
properly insulated to prevent the operator from coming in contact with the voltage.
The work area should be secure and free from non-essential items.
Operators should never work alone on high voltage devices. There should always
be another person present in the same work area to assist in the event of an emergency.
Operators should be familiar with procedures to employ in the event of an
emergency, i.e., remove all power, CPR, etc.
An AC powered unit will have 115 VAC or 230 VAC entering through the AC power connector. Caution is required when working near this connector, the AC circuit break­er, or the internal power supply.
1.4.2 High Current Hazards
Many high power devices are capable of producing large surges of current. This is true at all voltages, but needs to be emphasized for low voltage devices. Low voltage devices provide security from high voltage hazards, but also require higher current to provide the same power. High current can cause injury from burns and explosion. The following precautions should be taken on devices capable of discharging high current:
Remove all conductive personal items (rings, watches, medals, etc.)
The work area should be secure and free of non-essential items.
Wear safety glasses and protective clothing.
Operators should never work alone on high risk devices. There should always be
another person present in the work area to assist in the event of an emergency.
Operators should be familiar with procedures to employ in the event of an
emergency, i.e., remove all power, CPR, etc.
Operations Manual, Redundant System Controllers 209351 REV B 11
1.4.3 Electrical Discharge Hazards
A spark can not only create ESD reliability problems, it can also cause serious safety hazards. The following precautions should be taken when there is risk of electrical discharge:
Follow all ESD guidelines
Remove all flammable material and solvents from the area.
All probes and tools that contact the equipment should be properly insulated to
prevent electrical discharge.
The work area should be secure and free from non-essential items.
Operators should never work alone on hazardous equipment. There should always
be another person present in the same work area to assist in the event of an emergency.
Operators should be familiar with procedures to employ in the event of an
emergency, i.e., remove all power, CPR, etc.
12 209351 REV B Operations Manual, Redundant System Controllers
Section 2: Description
2.0 Introduction
This section provides information for the initial inspection, installation, and external connections for the RCP2/FPRC series redundant system controllers.
2.1 Inspection
When the unit is received, an initial inspection should be completed. First ensure that the shipping container is not damaged. If it is, have a representative from the shipping company present when the container is opened. Perform a visual inspection of the equipment to make sure that all items on the packing list are enclosed. If any damage has occurred or if items are missing, contact: Teledyne Paradise Datacom LLC 328 Innovation Blvd., Suite 100 State College, PA 16803 USA Phone: +1 (814) 238-3450 Fax: +1 (814) 238-3829
2.2 Mounting
The Teledyne Paradise Datacom Redundant Control Panel is designed to be mounted in a standard EIA 19 inch equipment rack. The depth of the chassis, excluding rear panel connectors, is 13.19 inches (335 mm). The height of the RCP2/FPRC chassis is
1.7 inches (44 mm) or 1 rack unit. Optional 22 inch (559 mm) rack slides with extensions are available.
2.3 Storage and Shipment
To protect the RCP2/FPRC during storage or shipping, use high quality commercial packing methods. Reliable commercial packing and shipping companies have the facilities and materials to adequately repack the equipment.
2.4 Cable Connections
The RCP2/FPRC controller has a wide range of I/O interconnections available at the
rear panel. The controller rear panel is shown in Figure 2-1.
Figure 2-1: RCP2/FPRC-1100/1200 Rear Panel
Operations Manual, Redundant System Controllers 209351 REV B 13
2.4.1 Control Cable Connector (J3) - MS3112E16-23S
The primary connection between the controller and the LNA/LNB (Low Noise Amplifier/ Low Noise Block Converter) switch plate or SSPA (Solid State Power Amplifier) switch assembly is through J3. The connector is a 23-pin circular connector, type MS3112E16
-23S (See Figure 2-2 and Table 2-1). For external waveguide switches, a standard
100 ft. (30m) cable, L201061 should be used.
Table 2-1: J3 Switch Connector, MS3112E16-23S
Pin Function Pin Function
Power Supply #1 +13-17 VDC, 900mA
Figure 2-2: Rear panel view of J3, MS3112E16-23S.
L
or +26V, 1.5A (-HP version only)
Power Supply #2 +13-17 VDC, 900mA
J
or +26V, 1.5A (-HP version only)
Power Supply #3 +13-17 VDC, 900mA
G
or +26V, 1.5A (-HP version only)
E Switch Common, +26 VDC, 5A max V Switch #2, Position 1 (Rx) (primary)
B AMP Support GND N Switch #2, Position 2 (Rx)
D Switch Common, +26 VDC, 5A max R Switch #2, Position 2 (Rx) (primary)
W Switch #1, Position 1 (Tx) (primary) A AMP Support GND
U Switch #1, Position 1 (Tx) C AMP Support GND
P Switch #1, Position 2 (Tx) K Switch Common, +26 VDC, 5A max
S Switch #1, Position 2 (Tx) (primary) M Switch Common, +26 VDC, 5A max
F Switch Common, +26 VDC, 5A max
H Switch Common, +26 VDC, 5A max
T Switch #2, Position 1 (Rx)
2.4.2 Serial Port, Main (J4) - DB9 (F)
The main serial port is for connection with any host computer. This port contains both RS-232 and RS-485 communication in half duplex. For convenience a set of Form C relay contacts are available at this port as a Service Request. The Service Request is essentially a Summary Alarm for any system faults that occur. The baud rate and other communication parameters are selectable via the front panel menu.
The pin-out is shown in Table 2-2. Note that the pin-out is standard DTE; a null modem
is not required when connecting to a standard PC serial port.
Table 2-2: Main Serial Port (J4) Pin Out
Function Pin Notes
RS-485 TX+ 1 RS-232 Out or RS-485 TX- 2 RS-232 In or RS-485 RX- 3 RS-485 RX+ 4 Ground 5 Service Request 1 6 Closed on Fault Service Request 2 8 Open on Fault Service Request Common 7 Form C Common Termination (120 Ohm) 9 Connect to pin 4 to terminate unit on end of bus
If required, a 120 ohm RS-485 termination resistor is provided at pin 9. It should be connected to pin 4 to provide a 120 ohm termination on the RS-485 bus.
14 209351 REV B Operations Manual, Redundant System Controllers
2.4.3 Serial Port, Local (J5) - DB9 (M)
The local serial port is used to support special transceiver systems and remote control panels. The baud rate of this port is fixed at 9600 Baud and cannot be changed. J5 is
permanently configured for RS-485 half duplex communication. Table 2-3 details the
local serial port pin-out.
Table 2-3: Local Serial Port (J5) Pin Out
Function Pin Notes
RS-485 RX+ 1
RS-485 RX- 2
RS-485 TX- 3
RS-485 TX+ 4
Ground 5
Termination (120 Ohm) 9 Connect to pin 1 to terminate unit on end of bus
2.4.4 Program Port (J6) - DB25 (M)
The program port allows for flash firmware upgrades of the RCP controller. Using the Teledyne Paradise Datacom Flash Upgrade software and a connection between the PC’s printer port and J6 allows the RCP firmware to be easily upgradeable. The
procedures for performing firmware upgrades is covered in Section 6, Maintenance.
2.4.5 Parallel I/O Connector (J7) - DB37 (F)
The RCP controller has a full compliment of parallel monitor and control lines. A 37-pin
D sub-style connector is used for the parallel I/O signals, which are detailed in Table 2-4. Ten Form-C relays are used for converter, switch position, and mode control.
Each Form-C contact has a rating of 30 VDC @ 0.5 A, 110 VDC @ 0.3 A, and 125 VAC @ 0.5 A. The inputs and ground pins are isolated from the rest of the unit’s cir­cuitry. Inputs are activated by pulling it down to the isolated ground pin. In order to fully utilize the built-in inputs protection, it is recommended to keep the input’s ground iso­lated from the chassis ground.
Operations Manual, Redundant System Controllers 209351 REV B 15
Table 2-4: Parallel I/O Signals
Identification Signal Pin Function Notes
1 Closed on Fault Relay Contacts: 30VDC @ 0.5A
Amp 1 Alarm Output
Amp 2 Alarm Output
Amp 3 Alarm Output
Auto / Manual Mode Output
Local / Remote Mode Output
Switch #1 Position Output
Switch #2 Position Output
Power Supply #1 Alarm
Power Supply #2 Alarm
Priority Setting Output
Fault Clear Input 37 Ground to Activate 5mA max current on all inputs
Priority Select Input 17 Ground to Activate Toggle Function
Auto / Manual Input 16 Ground to Activate Toggle Function; Alt Funct.: Ext. Mute Input
Amp 3 Standby Input 36 Ground to Activate
Amp 2 Standby Input 35 Ground to Activate
Amp 1 Standby Input 18 Ground to Activate
Inputs Ground (isolated) Common 19
Output
Output
20 Common
2 Open on Fault
21 Closed on Fault Relay Contacts: 30VDC @ 0.5A
3 Common
22 Open on Fault
4 Closed on Fault
23 Common
5 Open on Fault
24 Closed on Manual
6 Common
25 Closed on Auto
7 Closed on Local
26 Common
8 Closed on Remote
27 Switch #1, Position 1
9 Common
28 Switch #1, Position 2
10 Switch #2, Position 1
29 Common
11 Switch #2, Position 2
30 Closed on Fault
12 Common
31 Open on Fault
13 Closed on Fault
32 Common
14 Open on Fault
33 Closed on Priority 2
15 Common
34 Closed on Priority 1
16 209351 REV B Operations Manual, Redundant System Controllers
2.4.6 External Alarm Port (J8) - DB9 (F) [IO Board Version 001]
An external alarm port is provided to allow maximum flexibility of configurations. This allows the user to interface with the alarm output of other equipment into the RCP controller. Inputs are protected against ESD of ±15 kV using the Human Body model; against ESD of ±8kV using the Contact Discharge method specified in IEC1000-4-2;
and against ESD of ±15 kV using the Air Gap method described in IEC1000-4-2. Table
2-5 shows the external alarm pin-out.
Table 2-5: External Alarm Port (J8) Pin Out
Function Pin Notes
External Alarm 1 1
External Alarm 2 2
External Alarm 3 3
Ground 4,8,9
Auxiliary Alarm 1 5
Auxiliary Alarm 2 6
Auxiliary Alarm 3 7
Closure to Ground, 5mA max short circuit current, 5 VDC open circuit voltage
Closure to Ground, 5mA max short circuit current, 5 VDC open circuit voltage
2.4.7 Ethernet Port (J9) - RJ45 (F)
This is a RJ45 connector with integrated magnetics and LEDs. This port becomes the primary remote control interface when the Interface option is selected to “IPNet” as
described in Section 7.6.2.2. This feature allows the user to connect the RCP to a
10/100 Base-T office Local Area Network and have full-featured Monitor & Control
functions through a web interface. See Table 2-6 for Ethernet pin outs.
Table 2-6: Ethernet Port (J9) pin outs
Pin # Function / Description
1 TX+
2 TX-
3 RX+
6 RX-
4,5,7,8 GND
Note: IP address, Gateway address, Subnet mask, IP port and IP Lock address all need to be properly selected prior to first use (see Appendix B for details).
LED lamps on the connector indicate network status. A steady Green light indicates a valid Ethernet link; a flashing Yellow LED indicates data transfer activity (on either the Transmit and Receive paths).
Operations Manual, Redundant System Controllers 209351 REV B 17
2.5 Prime Power Connection (J1, J2)
Two separate removable power supplies are provided for fully redundant operation. Either of the two supplies is capable of operating the system and its associated switch­es. Two AC power connectors are provided on the rear panel (J1,J2).
2.6 Removable Power Supply Modules
The RCP unit has a redundant power supply array consisting of two modules. A failed power supply module may be removed from the RCP chassis by loosening the two captured thumbscrews and sliding the module out of the chassis, then unplugging the quick-disconnect power pole connectors.
2.6.1 24V Power Supply Module Figure 2-3 shows an outline drawing of a power supply module.
Figure 2-3: Removable Power Supply Module
The following list comprises the specifications for the standard power supply module:
Plug: IEC, 250V, 10A, Male plug with wire-form AC Cable Clamp Fuse: 2 Amp 5x20mm Power Supply: 85-264 V input, 28V output, 175W Connector to RCP chassis: Quick-connect Power pole
See Section 6.4 for directions on identifying and replacing a failed power supply
module.
18 209351 REV B Operations Manual, Redundant System Controllers
2.6.2 24V Power Supply Module, High Power option Figure 2-4 shows an outline drawing of a power supply module for units utilizing the
High Power (-HP) option.
Figure 2-4: Removable Power Supply Module, High Power option
The following list comprises the specifications for the standard power supply module:
Plug: IEC, 250V, 10A, Male plug Fuse: 2 Amp 5x20mm Power Supply: 85-264 V input, 28V output, 175W Fan: 40mm, 24V, 4.9 CFM Connector to RCP chassis: Quick-connect Power pole
See Section 6.4 for directions on identifying and replacing a failed power supply
module.
Operations Manual, Redundant System Controllers 209351 REV B 19
2.6.3 48V Power Supply Module Figure 2-5 shows an outline drawing of a 48V power supply module.
Figure 2-5: 48V Removable Power Supply Module
The following list comprises the specifications for the 48V power supply module:
Plug: MS3112E10-6P Circular MIL connector, 6-pin (MS3116F10-6S mating) Circuit Breaker: 6 Amp Power Supply: 48V, 150W Connector to RCP chassis: Quick-connect Power pole
See Section 6.4 for directions on identifying and replacing a failed power supply
module.
20 209351 REV B Operations Manual, Redundant System Controllers
Section 3: Front Panel Overview & Operation
3.0 Introduction
The front panel is used to locally control the system. Figure 3-1 shows the front panel
of a 1 RU RCP2/FPRC controller.
FAULT INDICATOR PANEL
SIGNAL PATH MIMIC DISPLAY
MAIN MENU KEY
NAVIGATION BUTTONS
SYSTEM IDENTIFICATION LABEL
AMPLIFIER SELECT KEYS
VACUUM FLOURESCENT DISPLAY
AUTO/MANUAL TOGGLE
LOCAL/REMOTE TOGGLE
Figure 3-1: RCP2/FPRC Front Panel, showing RCP2-1200 Mimic Display
3.0.1 System Identification
A label on the lower left hand corner of the controller front panel displays the model number and a brief description of the unit. The serial number is located on the rear panel of the controller.
3.0.2 Fault Indicators
The fault indicator LEDs illuminate RED when the corresponding fault condition occurs. There are fault lights for Summary, Unit 1, Unit 2, and Power Supply faults. The RCP2-
1200 and FPRC-1200 also includes a fault light for Unit 3. See Figure 3-2.
Figure 3-2: Fault Indicators: The image at left shows the fault indicators for models
RCP2-1100 and FPRC-1100; the figure at right shows the fault indicators for models RCP2-1200 and FPRC-1200.
3.0.3 Signal Path Mimic Display
The front panel mimic display provides a visual representation of the redundant system block diagram. Green LEDs indicate the position of the transfer switches showing the
RF signal path from the RF input to the RF output. Figure 3-3 shows the various signal
path mimic displays based on the controller model.
Operations Manual, Redundant System Controllers 209351 REV B 21
RCP2-1100
FPRC-1100
RCP2-1200
FPRC-1200
Figure 3-3: Signal Path Mimic Display
3.0.4 Amplifier Select Keys
The Amplifier Select Keys on the mimic display panel allow the user to select the online converter. These buttons can also be used to manually switch the standby converter on line when in manual mode. The on-line amplifier is designated by the illuminated green LED.
3.0.5 Vacuum Fluorescent Display
The Vacuum Fluorescent Display (VFD) provides a convenient method of selecting various operating parameters of the controller. All internal settings can be achieved via the VFD and menu structure. There is no need to access the interior of the controller to adjust or reconfigure hardware settings. The VFD also provides detailed information about fault conditions.
3.0.6 Main Menu Key
The main menu key is a convenient method for instantly returning to the VFD main menu. No matter what menu screen Is currently displayed on the VFD, pressing this key returns the user to the main menu, eliminating
the need to scroll backward through several menu levels. See Section 3-3, Monitor and Control for information regarding the menu selections.
22 209351 REV B Operations Manual, Redundant System Controllers
3.0.7 Local / Remote Key
The Local / Remote Key selects whether the controller is operational by front panel (local) control or by remote control. Remote control includes both the rear panel parallel control signals as well as the serial communi­cation.
3.0.8 Auto / Manual Key
This key selects between Auto and Manual Switching Mode. In Auto mode a converter failure will result in automatic switching of the system’s transfer switches. In manual mode a converter failure will result in fault alarms but no switchover will occur.
3.0.9 Display Navigation Keys
The display navigation keys allow easy movement through the VFD menu structure. Both right and left as well as up and down movement is available using the triangular shaped keys.
3.0.10 Enter Key
The enter key is used to select a given menu item. In conjunction with the navigation keys, it is easy to locate and select a desired function.
Operations Manual, Redundant System Controllers 209351 REV B 23
3.1 Local / Remote control
Control of the RCP/FPRC can be handled through Front Panel operation, or remotely through Parallel or Serial communication to a computer.
For local (front panel) operation of the controller, simply toggle the Local/Remote key until the yellow LED indicator is illuminated on Local. When in Remote mode the front panel buttons will be inoperative. The indicators and VFD display will still show the sta­tus of the system. The Local/Remote key is always operative so that the appropriate mode can be selected. Remote operation enables the serial communication and parallel I/O control.
3.2 Methods of switching
There are three methods of switching converters in a dual 1:1 redundant system.
1. Manual Mode
2. Automatic Mode
3. Physically Rotating either the Tx or Rx Transfer Switch
3.2.1 Manual Mode
The controller is set to Manual mode by toggling the Auto/Manual key so that the yellow LED is indicating Manual mode. Make sure that the Local/Remote key is on Local mode so that the Auto/Manual key is operative. Either unit can be selected online by pressing the amplifier buttons on the mimic display. The online unit is shown by the green LED embedded in the button.
3.2.2 Auto Mode
Automatic Switch mode is entered by toggling the Auto/Manual key until the yellow LED is indicating Auto mode. The online and standby amplifiers can be selected by pressing the appropriate buttons on the mimic display. This configuration will remain until a fault condition occurs. Upon failure, the appropriate fault light will illuminate and switchover will automatically occur.
3.2.3 Physically Rotating Transfer Switch
It is possible to physically rotate the shaft on either the TX or Rx transfer switch to change the online and standby amplifier positions. This can be done either in manual or automatic mode. When the switch is physically rotated in automatic mode the controller will attempt to return the switch to it previous position.
The controller will make two attempts to return the switch before accepting the new position. The front panel mimic display will show the correct switch path settings even when the switch is physically rotated.
24 209351 REV B Operations Manual, Redundant System Controllers
3.3 Local (Front Panel) Menu Structure
Figure 3-4 shows the VFD Menu Structure hierarchy. There are six main levels of menu
selections.
1. Sys.Info – System Information menu sublevel
2. Com.Setup – Serial Communication related settings
3. Operation – System operation related settings
4. Flt.Setup – Fault handling settings
5. Options – Miscellaneous settings and functions
6. Calibr. – Calibration related functions
r
e
y
a
L
u
n
e
M
o
f
n
I
o
t
k
c
a
B
Informative Menu Layer
Main Menu
2.Com Setup1.Sys Info 3.Operation 4.Fl t. Setup 6.Calibr.
5.Options
Figure 3-4: Main Menu Initial Menu Selection
Main Menu navigation is available by pressing five buttons on the front panel keypad:
the Left Arrow () key, Right Arrow () key, Up Arrow () key, Down Arrow () key and the Enter key. The bottom right corner of the VFD display shows the item
selection. All selectable items have a sequential number.
The user can increment or decrement the selected item number by using Left Arrow () and Right Arrow () keys. Selection is final when the operator presses the Enter key. Pressing the Main Menu key brings the menu level to the main menu page from
any stage of the menu selection.
Some items within the menu structure have alternative methods for value selection. When this type of selection is specified, the selection keys are: Up Arrow () and Down Arrow () keys for selecting numbers in x10 increments and Left Arrow () and Right Arrow () keys for x1 increments. Selection is always specified by special notation on the far right hand side of the VFD.
Note: When the “Fault Latch” option is selected (as described in Section
3.3.4.5), pressing the Enter key will clear all system faults.
Operations Manual, Redundant System Controllers 209351 REV B 25
Main
Menu
Main
Menu
1.Sys.Info
PS1: XXXXXX Sy stem : XXXXXX SW1: XXXXXX PS2: XXXXXX Aux: XXXXXX SW2: XXXXXX
Prtcl: XXXXXX Intfc: XXXXXX Logic: XXX Baud: XXXXX SysAddr: XXX Latch: XXX
Tra ck: XXXXXX Ctrl: XXXXXX Window(% ): XXXX Prior: XXXXXX Mode: XXXXXX Buzzer: XXX
LNA/LNB Faults: XXXXXX PS1Out(V): XXX SSPA Faults: XXXXXX PS2Out(V): XXX
Unit1: XXXXXX Unit2: XXXXXX Unit3: XXXXXX ExtFaults: AUXxxxxx HPAxxx Ux Standby
Operation Mode: XXXXXXXXXXXX Faul t Tolerance: XXXXXXXXXX
Gene ral System Information Menus
Main
Menu
5.Options 6.More
1.SysID
2.Com Setup 5.IP Setup
IPAddr:XXX.XXX.XXX.XXX MAC:XXXXXXXXXXXXXX Subnet :XXX. XXX.XXX.XXX Port:XXXXX
Gateway:XXX.XXX.XXX.XXX LockIP:XXX.XXX.XXX.XXX
CommunityGet:XXXXXXXXXXXXXXXXXXXXXXXX CommunitySet:XXXXXXXXXXXXXXXXXXXXXXXX
WebPassword:XXXXXXXXXXXXXXXXXX XXXXX X
Main
Menu
Atten.(dB): XX.X FrwrdRF(Watts/dBm): XXXX.X Mute: XXX Ref.RF(Watts/dBm): XXXX.X
UnitRF1(dBm): XX.X UnitRF3(dBm): XX.X UnitRF2(dBm): XX.X
5.Options 6.More
3.SSPA
1.IPInfo
IP Se tup Menu
1.SSPA Info
ParadiseDatacom Version X.X.X Digicore XM128- Built YY,MMM DD
SysID Firmware Info Me nu
Unit1(C): XX.X Unit2(C): XX.X Unit3(C): XX.X
UnitDC1(Amp): XX.X UnitDC3(Amp): XX.X UnitDC2(Amp): XX.X
System Ty pe: XXXXXXXXXX SWMute: XXX Offset(dB): U1: XX.X U2: XX.X U3: XX.X
Ambi ent(C): XX.X
SSPA Setup Menu
Figure 3-5: System Information Menu Structure
3.3.1 Sys Info
This is the informative sublevel of the menu structure. This menu consist of six pages of
general system information that can be browsed by pressing buttons the Up Arrow () and Down Arrow () keys on the front panel keypad. The user can also browse between these pages by pressing the Enter key on the keypad.
RCP firmware version 3.40 introduced additional navigational features to the System In­formation Menu. These features allow the user to quickly switch between the general
System Info menus and the SSPA System Info menus by pressing the Left Arrow () and Right Arrow () keys on front panel keypad (See Figure 3-5).
26 209351 REV B Operations Manual, Redundant System Controllers
3.3.1.1 Sys Info - Page 1
This page is the system information page of the Sys Info menu. This page shows the
status of both power supplies PS1 and PS2. The controller monitors the output voltage
of each internal power supply. The power supply voltage is considered “Normal” if its output voltage level is above 23V and “Fault” when output voltage drops below 22V. A power supply fault is always considered a major fault.
Also included on page one of Sys Info is the System status. This is the status of the
system summary alarm. The system status will be “Fault” or “Normal” according to the
state of the various fault monitoring circuitry. Aux is the state of the auxiliary fault input. Auxiliary faults are user configurable.
Depending on the system configuration they may be enabled or disabled and track opposite logic states. When auxiliary faults are enabled, they will always trigger a summary fault.
SW1 and SW2 are the position and fault state indicator of the transfer switch / switches
in the system. The possible states are: POS1 - Switch position 1, POS2 - Switch position 2, and Fault. In a system using only one transfer switch SW2 will be displayed as N/A, not available.
Note on Switch Fault:
If the controller cannot read the position indicator lines on the transfer switch it will be considered to be in a fault condition. This can occur when a transfer switch becomes stuck between valid positions. The Summary fault state may or may not be triggered depending on the user settings. The system default is to consider a switch fault as a minor fault and will not trigger a summary alarm.
3.3.1.2 Sys Info - Page 2
This page of the Sys Info menu pertains to the internal monitor and control settings of the RCP controller.
Prtcl is the serial communication protocol settings. The possible settings are:
Auto - Auto detect either Standard or Locus Communications protocol Standard - Standard extended protocol
Baud is the serial communication Baud rate selection. The available Baud rates include:
2400, 4800, 9600, 19200, and 38400.
Interfc is the physical interface used for serial communication. The available interfaces
include RS-232 and RS-485.
Operations Manual, Redundant System Controllers 209351 REV B 27
SysAddr sets the controller unique network address. The address range is 1 to 255.
As with any RS-485 network the RCP address must be unique within every serial network. The controller will answer on serial commands only if its address matches the address sent in the serial packet.
Logic refers to the fault state logic for the External Alarm Input port, J8. The factory
default setting is a logic high state for external alarm fault status. This is consistent with (contact open = fault ) logic used in most systems. However if used in a system that employ reverse logic, this setting can be used to adjust the RCP controller accordingly.
Latch refers to the fault latching function. The possible states are “Enb” and “Dis” for
fault latching enabled and fault latching disabled. The factory default state is for fault latching to be enabled. This means that after a fault has been detected, the RCP controller will continue to indicate an alarm even after the external fault may have been removed. To clear a latched fault the user must press the “Enter” button when the controller is in the Sys Info page.
3.3.1.3 Sys Info - Page 3
This page pertains to the internal monitor and control settings of the RCP controller.
Track refers to the system fault tracking method. Available selections include LNA, EXT
(External), and Both. This option specifies which elements are to be included into the redundant system. The user can select fault tracking based only on internal current monitoring such as in LNA / LNB systems, by external inputs from External Alarm port, J8, or both.
Prior is the Priority control of the system. This option is only used in 1:2 redundant
systems in which priority must be assigned to polarity 1 or polarity 2 of a given antenna system. This is only used if both on line amplifiers fail in a 1:2 redundant system. The priority setting determines the polarity, or switch position, the system should assign to the standby amplifier.
Ctrl specifies Local or Remote mode of controller operation. This function can also be
accessed by the dedicated Local/Remote key on the front panel. When in Remote mode, all other front panel keys are disabled with exception of the Local/Remote key.
Mode indicates and selects the Automatic or Manual mode of the controller. This
function can be accessed by the dedicated Auto/Manual key on the front panel.
Window allows the user to select the current window setting for fault detection in an
LNA / LNB redundant system. The possible selections are: 8%, 12%, 15%, and 20% of the nominal operating DC bias current. The factory default setting is 12%.
Buzzer allows the user to enable or disable the internal audible alarm. The factory
default setting is enabled.
28 209351 REV B Operations Manual, Redundant System Controllers
3.3.1.4 Sys Info - Page 4
This page pertains to the advanced system diagnostic features of the RCP controller.
LNA/LNB Faults refers to state of the controlled state of the LNA/LNB system. This
item shows the fault state of the individual LNA/LNB. If no faults are detected, the word, “None” will be displayed. If fault tracking wasn’t enabled (e.g., if Track option set to Ext – External faults only), the state will be indicated as “N/A” – Not Available. If any LNA related faults are present in the system, this item will show them in format X-X-X, where X could be the number 1, 2 or 3. For example, if LNA1 is in the fault condition, the display will indicate “1----”; if all three LNAs are faulted, “1-2-3” will be displayed.
SSPA Faults refers to the state of the controlled state of the SSPA system. This item
shows the fault state of each individual SSPA. If no faults are detected, the word, “None” will be displayed. If fault tracking wasn’t enabled (e.g., if Track option set to LNA – LNA/LNB faults only), the state will be indicated as “N/A” – Not Available. If any SSPA faults are present in the system, this item will show them in format X-X-X, where X could be the number 1, 2 or 3. For example: if SSPA1 is in the fault condition, the display will indicate “1----”; if all three SSPAs are faulted, “1-2-3” will be displayed.
PS1Out(V) indicates the output voltage of the RCP’s internal power supply 1. The
indicated value shows an instant reading of the power supply voltage with accuracy of
0.1V. Normally, this value should be in a range from 22V to 27V.
PS2Out(V) indicates the output voltage of the RCP’s internal power supply 2. Indicated
value shows instant reading of the power supply voltage with accuracy of 0.1V. Normally, value should be in range from 22V to 27V.
3.3.1.5 Sys Info - Page 5
This page pertains to the advanced system diagnostic features of the RCP controller
Unit1; Unit2; Unit3 – Items refer to the summary fault state of individual units attached
to the RCP. The possible state is “Normal” for non-fault condition, “Fault” or “N/A” as not available.
ExtFaults refers to the state of individual contacts on the RCP external input port. This
item has a subdivision for Auxiliary faults and major SSPA faults. Auxiliary faults are represented as AuxXXX where X indicates the state of individual auxiliary fault sense contacts and could be “1” for “open” state or “0” for shorted to ground state. The left­most digit indicates the state of Auxiliary Alarm 3 contact and right-most digit shows the state of Auxiliary Alarm 1. For example: if the display shows AUX101, it means Auxiliary ports 1 and 3 are in “open” state (logic “1” state, not connected to the ground) and port 2 is in logic “0” state and are “shorted” to the ground. The actual fault state depends on RCP fault logic and fault handling.
Operations Manual, Redundant System Controllers 209351 REV B 29
Major SSPA faults are represented as HPAXXX, where “X” could be “1” or “0” depending on the state of the individual pin of external faults port. The left-most digit serves as the indicator for SSPA Unit 3 and the right-most for SSPA Unit 1. The fault state of the RCP unit depends on the selected fault logic and selected system type.
For more information about advanced troubleshooting, see Section 4.7. Ux Standby refers to the selected default standby unit. “x” can be a digit from 1 to 3 and
indicates which unit was selected as the default standby unit. This unit is usually selected by the user in the initial RCP setup. The selected unit will remain on standby under RCP manual mode or Auto mode (in condition when all units considered in “Normal” non-faulted condition). Of course, under “Auto” mode, the default standby unit will be put “Online” if required. Under Auto mode, the RCP always keeps track of the unit’s reliability record and can reassign default standby state to the unit with the worst reliability record. The unit will be assigned automatically to the default standby state if its fault state was switched from “Normal” to “Fault” more then 2 times since last user intervention. Any user intervention to the units standby setup will clear all reliability record.
3.3.1.6 Sys Info - Page 6
This page provides additional system information (firmware version 3.7.0 or better).
Operation Mode provides information regarding the current controller operation mode
and switching logic. Indicated status: 1:1 Mode; 1:2 Mode; 1:1 Phase Combined; Dual 1:1 Mode.
Fault Tolerance refers to advanced controller behavior. There are three settings, “None”, “1 Fault” and “2 Faults”, which are set via the Options menu (Section 3.3.5.7).
None” pertains to no fault tolerance schema. Every fault occurred to the online unit will
take this unit offline permanently. Even after the fault condition is cleared, the unit will stay off line until the user selects otherwise, or other control units develop a fault. No fault tolerance schema is implemented to minimize switching, but not establish preferences to the selected system configuration.
1 Fault” is the factory default schema, and pertains to one fault tolerance. A faulted
online unit will be automatically set online after the fault is cleared. In case of two sequential fault occurrences, the unit will be set offline permanently. This configuration provides a balanced compromise between minimal fault switching and favoring a particular unit online/standby selection.
2 Faults” is similar to the “1 Fault” schema, but requires the occurrence of two
sequential faults before changing the favored system configuration.
30 209351 REV B Operations Manual, Redundant System Controllers
3.3.1.7 SSPA Subsystem Information - Pages 1-5
Page 1 (RCP firmware version 3.10 or better) pertains to conditions and settings
common to all SSPAs in a subsystem.
Page 2 (RCP firmware version 3.60 or better) pertains to individual SSPA output power
levels.
Page 3 (RCP firmware version 3.10 or better) pertains to each individual SSPA unit’s
core temperature and ambient temperature.
Page 4 (RCP firmware version 3.60 or better) pertains to individual SSPA unit’s DC
current consumption.
Page 5 (RCP firmware version 3.30 or better) pertains to additional subsystem
settings.
See Section 4.6 for a thorough description of this series of menus.
3.3.1.8 IP Info - Page 1
This page is available through the ComSetup menu, and shows settings related to the IP interface. See Figure 3-5.
IP Address: IP address of the RCP . Consult your network administrator to set
this address according to your LAN configuration.
MAC: Medium Access Control address of the RCP Ethernet controller. This
address is factory preset.
Subnet: IP subnet mask of the RCP. Consult your network administrator to set
this address.
IPPort: IP port value for the RCP. This address is valid only when IPNet
protocol is selected. The port value should not be selected outside the existing services range to avoid access conflict on the M&C PC end.
3.3.1.9 IP Info - Page 2
This page shows RCP settings related to the IP interface.
Gateway: IP Gateway address. This address is used only if access to the RCP is
provided from an outside LAN. If no such access is required, the address must be set to 0.0.0.0
LockIP: This address is used to increase the security measure for the IPNet
protocol. The RCP will answer a request which comes only from a specified IP address. Set this address value to 0.0.0.0 or 255.255.255.255 to disable this feature.
Operations Manual, Redundant System Controllers 209351 REV B 31
3.3.1.10 IP Info - Page 3
This page shows RCP settings related to the IP interface.
CommunityGet: Security string used in SNMP protocol for Get type requests. Set
this value to match the value specified in the NMS or MIB browser. Maximum string length is 20 alpha-numeric characters. The string allows read operation for the RM SSPA SNMP agent.
CommunitySet: Security string used in SNMP protocol for Set type requests. Set
this value to match the value specified in the NMS or MIB browser. For security reasons this string must be different than the Community Get string. Maximum string length is 20 alpha-numeric characters. The string allows write operation for the RM SSPA SNMP agent.
Community strings are essentially passwords. The user should use the same rules for selecting them as for any other passwords: no dictionary words, spouse names, etc. An alphanumeric string with mixed upper- and lower-case letters is generally a good idea.
3.3.1.11 IP Info - Page 4
This page indicates the selected password for the web page interface. A blank space indicates that the web interface will not require a password protected login.
32 209351 REV B Operations Manual, Redundant System Controllers
Mai n Menu
1.Protocol
2.Terminal
1.RS232
2.Com Setup
3.9600
2.LocalIP
2.Baud Rate
2.RS485
3.Operation
3.Sys Addr
4.19200
3.Subnet
1.Community Get
1-255
3.IPNet
4.Flt. Setup
5.38400
4.Gateway
2.Community Set
4.Interface
4.SNMP
5.Options
5.IP Setup
5.LocalPort
3.Lock I P
6.Calibr
6.More
4.Web Password
1.2400
1.Sys Info
1.Normal
2.4800
1.IPInfo
To IP Info Page
Figure 3-6: Serial Communication Parameters Menu
3.3.2 Serial Communication Parameters
This section describes the serial communication parameters that can be selected for the
controller. Press the Main Menu key; select 2.ComSetup and press the Enter key. See Figure 3-6. Changes in Serial Communication settings from the front panel are ef-
fective immediately. Changes to these parameters from the serial interface require that the controller be reset in order to take effect. The controller can be reset ei­ther by cycling power to the unit or by selecting the reset option on the front panel menu
(see Section 3.3.5.5).
3.3.2.1 Protocol
This menu selection allows the user ability to select between the following protocols:
Normal - Selects only the Paradise Datacom protocol Terminal - Selects only the terminal protocol. See Appendix A for more info.
3.3.2.2 Baud Rate
Selects the desired Baud Rate to use for serial communication. Valid options are: 2400, 4800, 9600, 19200 and 38400.
Operations Manual, Redundant System Controllers 209351 REV B 33
3.3.2.3 Sys. Address
Sets the network address of the controller if used in a RS485 network. Address is selectable from 1 to 255
3.3.2.4 Interface
This menu choice provides the selection of the physical interface of the main serial port. Choose between RS-232, RS-485, IPNet (Ethernet) and SNMP interfaces.
3.3.2.5 IP Setup
This menu allows the user to select between the following menu items: IP Info (to
review all IP Net Settings as described in Section 7.6); or any of the following to adjust
the existing settings: Local IP; Subnet Mask; Default Gateway; and Local Port.
Selecting the ‘More’ option allows the user to adjust the settings for the following parameters: Community Get; Community Set; Lock IP and Web Password.
Main Menu
2.Com Setup1.Sys Info
1.System
1. Buzzer On 2. Buzzer Off
1. 1:1 2. 1:2 3. 1:1 Ph. Comb 4. Dual 1:1 5.Sngl Sw
2.Buzzer
3.Operation 4.Flt. Setup 5.Options
3.Control 4.Switching 5.Priority 6.Stby Select
1. Auto 2. Manual
1. Local 2. Remote
1. POL 1 2. POL 2
6.Calibr
1. Unit 1 2. Unit 2 3. Unit 3
Figure 3-7: Operation Parameters Menu
3.3.3 Operations Menu
This section describes the basic setup parameters of the redundant controller. The
operation parameters can be accessed from the main menu. Press the Main Menu key; select 3.Operation and press the Enter key. See Figure 3-7. The following
parameters are selectable.
3.3.3.1 System
Selects the logical state machine used by the controller. Available choices are 1:1 Redundancy; 1:2 Redundancy or 1:2 Phase Combined; Dual 1:1; or Single Switch.
3.3.3.2 Buzzer
Allows the user to enable or disable the audible alarm buzzer. The factory default is to
have the buzzer enabled.
34 209351 REV B Operations Manual, Redundant System Controllers
3.3.3.3 Control
Selects between Local and Remote mode. Note that this is the same function as the
dedicated front panel button.
3.3.3.4 Switching
Selects between Auto and Manual mode. Note that this is the same function as the
dedicated front panel button.
3.3.3.5 Priority
Used in 1:2 redundant systems only. It is used to assign switching priority to either position 1 or position 3 in the event that both amplifiers fail. Priority has no effect in a
FPRC-1200 system.
3.3.3.6 Stby. Select
Selects which unit will be in default standby mode. Note that this is the same function
as on the signal path mimic display on the front panel.
Main Menu
1.Mjr. Faults
1.LNA/LNB 2.External 3.Both
2.Com Setup1.Sys Info 3.Operation 4.Flt. Setup 5.Options
2. Aux. Faults
1.Sys. Fault 2.Alert Only 3.Alternate
3. Sw Faults
1.Fault on High 2.Fault on Low1.Enable 2.Disable 1.Enable 2.Disable
4.Flt. Logic
6.Calibr
5.Latch
Figure 3-8: Fault Setup Parameters Menu
3.3.4 Fault Setup
This section describes the fault tracking capability of the controller. The controller is extremely versatile in its ability to monitor alarms from a large variety and quantity of equipment. The following alarm inputs are provided on the controller:
LNA / LNB Current Monitoring - up to 600mA
(3) External Alarm Inputs
(5) Auxiliary Alarm Inputs
Any combination of the alarm inputs can be used individually or together. From the
main menu screen, select “Flt.Setup”. See Figure 3-8. The following four fault setup
selections are available.
Operations Manual, Redundant System Controllers 209351 REV B 35
3.3.4.1 MjrFaults
Allows user to assign priority and select those inputs that constitute a major fault and cause switchover. Normally only External fault tracking is enabled in a FPRC-1200 Sys­tem.
LNA/LNB - Enables the current monitoring of LNA/LNB to create major fault
alarm
External - Enables the (3) external alarm inputs of J8 Both - Allows both current monitoring and external alarms to create a major fault.
3.3.4.2 AuxFaults
Enables the (5) auxiliary fault inputs of J8 to create a major fault.
3.3.4.3 RFSw.Faults
Determines whether a switch fault should cause a major alarm and attempt to switch or simply alert to the problem on the front panel VFD. The later case being considered a minor alarm.
Sys.Fault - Major Alarm Mode, Summary alarm and switchover triggered. Alert - Minor Alarm Mode, No summary alarm indicated; no switchover occurs. Alternate – Same as Alert, but will alternate functions of the parallel I/O port out-
put for the Switch position indicator form C-relays. Instead of indicating position (either Pos1 or Pos2), relays will indicate RF switch fault or normal status. This option was introduced in RCP firmware rev 3.30 for advanced system integration purposes. This option should not be selected by the customer unless advised by Teledyne Paradise Datacom LLC.
3.3.4.4 Fault Logic
Selects between “Fault on High” and “Fault on Low”.
3.3.4.5 Fault Latch
Determines the alarm reporting condition. A latched alarm will remain indicated on the front panel until the operator clears the alarm by pressing the “Enter” button. Unlatched alarms will allow the summary alarm indicator to stop displaying the alarm condition if the circumstance creating the alarm has be cleared or corrected.
Enable - Keeps alarm condition displayed until operator intervention. Disable - Unlatches the Alarm state
36 209351 REV B Operations Manual, Redundant System Controllers
Main Menu
2.Com Setup1.Sys Info 3.Operation 4.Flt. Setup 5.Options
1.Backup 2.Restore 3.Lam p Test 4.Password 5.Reset 6.More
1.User 2.Factory
1.Set 2.C lear 3.Change
1.Low
0..255
2.Medium 3.High
1.SSPA Info
See Figure
6.Calibr
4.Flt. Tolerance1.Sys ID 2.LCD Light 3.SSPA
1.None 2.1 Fault 2.2 Faults
3.Mute2.Attenuation
ON / OFF0 ... 20 dB
3-5
1.None 2.RM SSPA 3.CO SSPA 4.vBUC
1.dBm 2.Watts
4.Units
5.More
1.Sys. Type 2.Sw. Mute
1.SwMute Off 2.Internal On 3.External On 4.All On
3.Atten Offset
1.Unit 1 2.Unit 2 3.Unit 3
Figure 3-9: Options Parameters Menu
3.3.5 Options Menu
This section describes the features available on the Options menu of the controller. The operation parameters can be accessed from the VFD menu. From the main menu
screen, select “Options”. See Figure 3-9. The following option selections are available.
3.3.5.1 Backup
Allows the user the ability to store all settings to nonvolatile memory.
3.3.5.2 Restore
Restore previously saved settings.
User – Previously saved settings from using the “Backup” selection Factory Default – Original settings as shipped from the factory
3.3.5.3 Lamp Test
Tests all front panel LEDs. The LEDs remain on until the “Enter” key is pressed.
3.3.5.4 Password
Allows the user to set a password that prohibits others from changing settings on the controller.
Set - Enables password protection
Clear– Disables password protection Change – Allows the user to set a numeric password between 1 and 255. Use the Arrow keys to set the numeric password. The Up Arrow () and Down Arrow () keys change the numeric password by factors of 10. The Left Arrow
() and Right Arrow () keys change the password in increments of 1.
Operations Manual, Redundant System Controllers 209351 REV B 37
3.3.5.5 Reset
Forces a reset of the controller’s internal microcontroller.
3.3.5.6 More
This allows access to the menus described in Sections 3.3.5.7, 3.3.5.8 and 3.3.5.9 and
3.3.5.10.
3.3.5.7 Fault Tolerance
Select between None, 1 Fault or 2 Faults. See Section 3.3.1.6 for a description of these
selections.
3.3.5.8 Sys ID
Shows the current firmware version.
3.3.5.9 VFD Light
Adjusts the intensity of the VFD backlight between Low, Medium and High.
3.3.5.10 SSPA
This section deals with settings specific to SSPA systems.
Mute – Toggles the SSPA mute function on/off;
Attenuation – Varies the gain of the SSPA system from its maximum value to
20dB below its maximum value, with 0.1dB steps.
View – Available on newer Paradise Datacom LLC FPRC systems only, this
allows the user to view Attenuation, Mute status, Forward RF, System Type (RCP firmware revision 2.20 and better), Ambient temperature and Core temperature of
SSPA units (RCP firmware rev 3.30 and better). See Section 4.6 for a thorough
description.
More – This selection gives access to the following menu items: Sys.Type – Changes between controlled system type for Compact Outdoor
SSPA, Rack Mount SSPA, vBUC or Not Applicable.
Switch Mute – Changes switch mute option of redundant system. See Section
4.5.2.3 for details. Attenuation Offsets – Allows the operator to equalize the individual SSPA gain
differential. The selected offset is added to the current level of system attenuation. The total of the system attenuation and offset is limited to 20 dB maximum.
38 209351 REV B Operations Manual, Redundant System Controllers
Main Menu
2.Com Setup1.Sys Info 3.Operation 4.Fl t. Setup 5.Options
1.Flt. Window
1.8% 2.12% 3.15% 4.20%
1.13V 900 mA 2.17V 900 mA
2.LNA/LNB PS 3.Cal LNAs 4.View
LNA1 (mA):XXX LNA2( mA):XXX LNA3( mA):XXX
Cal1(mA):XXX Cal2(mA):XXX Cal 3(mA):XXX
PS LNA1(v):XX.X PS LNA3(v):XX.X
3.26V 1500 mA
6.Calibr
PS LN A2(v):XX.X
Figure 3-10: Calibration Parameters Menu
3.3.6 Calibration Menu
When the controller is set up to perform LNA/LNB Fault Tracking, the LNA or LNB nomi­nal current should be calibrated from the controller. First, set the controller for LNA/LNB Fault Tracking by performing the following process:
Press the Main Menu key; select 4.Flt. Setup and press the Enter key; select 1.Mjr.
Faults and press the Enter key; select 1.LNA/LNB and press the Enter key. See Section 3.3.4 and Figure 3-8. The following menu selections allow for calibration of the LNA/LNBs. See Figure 3-10.
3.3.6.1 Flt. Window
Allows the user to select the sensitivity of the alarm detection. Select from four window settings (8%, 12%, 15% or 20%) which are a percentage of the total current being consumed by the LNA/LNB. The 8% setting is the most sensitive and 20% is the least sensitive. The factory default setting is 8%.
3.3.6.2 LNA/LNB PS
Selects between three output voltage ranges for LNA/LNB power supplies: 13V, 17V or 26V (available on RCP2-HP models only) output. Maximum output current at the 13/17V range is 900 mA; and is 1500 mA for 26V output. This option can be used to switch between bands of dual band LNB units or to connect higher power converters. All three channels will switch output voltage simultaneously. For a detailed description of LNB/
LNA power supplies, refer to Section 5.0.1.
Operations Manual, Redundant System Controllers 209351 REV B 39
3.3.6.3 Calibrate
Allows the user to calibrate the system LNAs.
3.3.6.4 View LNA
Allows the user to view information about the system LNAs. The resultant window shows mA values for LNA1, LNA2 and LNA3, as well as the calibration values Cal1, Cal2 and Cal3.
A secondary window, available by pressing the Up Arrow () or Down Arrow ()
keys, displays the Power Supply voltages for LNA1, LNA2 and LNA3.
40 209351 REV B Operations Manual, Redundant System Controllers
Section 4: System Setup & Control with RCP
4.0 Introduction
This section describes various redundant system setups utilizing features available with the Teledyne Paradise Datacom Redundant System Controller.
The controller allows monitor and control of all types of amplifiers, from Low Noise Amplifiers (LNAs), Low Noise Block Converters (LNBs), Solid State Power Amplifiers (SSPA), Solid State Power Amplifiers with Block Up Converters (SSPBs) or vBUC
amplifiers.
4.1 Operation of 1:1 System with RCP2-1100
Figure 4-1 shows the basic block diagram of a 1:1 redundant system. In normal opera-
tion one of the Amplifiers, 1 or 2, is considered the on-line amplifier and the other is in standby. If a fault condition occurs in the on-line amplifier the standby unit can be switched into the circuit by moving the transfer switches on the input and output side of the amplifiers.
Figure 4-1: Block Diagram, 1:1 Redundant System
Operations Manual, Redundant System Controllers 209351 REV B 41
4.1.1 LNA / LNB 1:1 Redundant System Operation
This section covers the operation of the RCP2-1100 controller with a Teledyne Para­dise Datacom LNA or LNB Redundant System. A typical LNA / LNB redundant system consists of an outdoor plate assembly, the RCP2-1100 indoor controller, and an inter-
connecting control cable. Figure 4-2 shows the major components of a typical 1:1 LNA
system.
LNA Plate Assembly
LNA 1
LNA 2
SW 1
PARADISE DATACOM
RCP2-1100
1:1 REDUNDANT
SYSTEM CONTROLLER
Control Cable, L201061
RCP2-1100
Figure 4-2: Indoor/Outdoor Components, 1:1 Redundant System
The LNAs or LNBs are powered by the RCP2-1100 Controller via the control cable. Two power supplies are included in the controller for total system redundancy. The power supplies are diode connected so that only one supply can operate the system.
The RCP2-1100 supplies +15 VDC to power the LNA / LNB and +26 VDC to operate the transfer switch. A failure in an LNA or LNB is typically noted by a change in the DC bias current. The RCP2-1100 has current window comparators that monitor the current drawn by each unit and will report a fault if the current falls outside of the preset cur­rent window. The nominal current and window width setting are factory preset to the particular LNA / LNB system, however both are easily adjustable via the front panel
control. A typical 1:1 Redundant LNA system is shown in Figure 4-3.
42 209351 REV B Operations Manual, Redundant System Controllers
Figure 4-3: Typical Schematic, 1:1 Redundant LNA System
4.1.1.1 LNA/LNB Fault Tracking
To set up the RCP2-1100 for LNA/LNB fault tracking perform the following menu
selections. Press the Main Menu key; select 4.Flt. Setup and press the Enter key; select 1.Mjr. Faults and press the Enter key; select 1.LNA/LNB and press the Enter
key. This puts the RCP2-1100 in LNA/LNB current monitor mode.
4.1.1.2 LNA / LNB Current Calibration
After the RCP2-1100 has been put in the LNA/LNB fault tracking mode, the LNA or LNB nominal current should be calibrated by the controller. To perform the current
calibration, press the Main Menu key; select 6.Calibr and press the Enter key; select
3.Calibrate and press the Enter key. This calibrates the normal current consumption
of the LNA/LNBs.
To select the sensitivity of the alarm detection, select 1.Flt.Window and press the Enter key. Select from four window settings which represent a percentage of the total
current being consumed by the LNA/LNB. The 8% setting is the most sensitive and 20% is the least sensitive. The factory default setting is 8%.
Note: Caution should be used when changing Fault Window settings from the factory
preset. Current variations will occur in equipment naturally as a result of changes in operating temperature. Consideration should be given to environmental conditions and, in particular, to operating temperature extremes.
Operations Manual, Redundant System Controllers 209351 REV B 43
4.1.2 SSPA 1:1 Redundant System Operation
The RCP2-1100 can be configured to accept external fault inputs at connector J8. The external alarm inputs operate with a closure to ground input. The alarm inputs are opto
-isolated inputs, exposing +5 VDC (open circuit voltage) at 5 mA maximum short circuit current. The external alarm inputs can be driven with an appropriate open collector device or relay contacts. Solid state power amplifier redundant systems typically use a form C relay summary alarm output to drive the RCP2 external alarm input. A
schematic representation of such a system is shown in Figure 4-4.
SSPA 2
&
MONITOR CONTROL
C N.C.N.O.
Open on FaultClosed on Fault
RF Input
External Alarm
Cable
Closed on Fault
SSPA 1
a
Open on Fault
bL
MONITOR CONTROL
J8
2
4
RCP2-1100
1
&
J3
P S
F D
U
W
CONTROL CABLE
C
B
A
Transfer Switch
Pos 2
Pos 1
1
2
3
RF Output
4
Figure 4-4: Schematic, Typical 1:1 Redundant SSPA System
The external alarm inputs are not limited to SSPA systems. Any device with the appropriate alarm output circuitry could be connected to the external alarm inputs.
To use the external alarm inputs on the RCP2-1100 they must first be enabled from the front panel using the following procedure.
4.1.2.1 External Alarm Tracking
Press the Main Menu key; select 4.Flt. Setup and press the Enter key; select 1.Mjr. Faults and press the Enter key; select 2.External and press the Enter key. This puts
the RCP2-1100 in external alarm monitor mode
44 209351 REV B Operations Manual, Redundant System Controllers
4.2 Operation of 1:2 System with RCP2-1200
Figure 4-5 shows the basic block diagram of a 1:2 redundant system. In normal oper-
ation amplifiers 1 and 3 are considered the on-line amplifiers while amplifier 2 is in standby. If a fault conditions occurs in either one of the on-line amplifiers, the standby unit can be switched into the circuit by moving the transfer switches on the input and output side of the amplifiers. The amplifiers could be Low Noise Amplifiers (LNAs), Low Noise Block Converters (LNBs), Solid State Power Amplifiers (SSPA), or Solid State Power Amplifiers with Block Up Converters (SSPBs).
Figure 4-5: Block Diagram, 1:2 Redundant System
A priority can be assigned to either the Polarity 1 or Polarity 2 switch path in the event that both online amplifiers were to fail.
4.2.1 LNA / LNB 1:2 Redundant System Operation
This section covers the operation of the RCP2-1200 controller with a Paradise Data­com LNA or LNB Redundant System. A typical LNA / LNB redundant system consists of an outdoor plate assembly, the RCP2-1200 indoor controller, and an interconnecting
control cable. Figure 4-6 shows the major components of a typical 1:2 LNA system.
Operations Manual, Redundant System Controllers 209351 REV B 45
LNA 2
LNA 3
POL 2 INPUTPOL 1 INPUT
LNA Plate Assembly
LNA 1
PARADISE DATACOM
RCP2-1200
1:2 REDUNDANT
SYSTEM CONTROLLER
Control Cable, L201061
RCP2-1200
Figure 4-6: System Components, 1:2 Redundant LNA System
The LNAs or LNBs are powered by the RCP2-1200 Controller via the control cable. Two power supplies are included in the controller for total system redundancy. The power supplies are diode connected so that only one supply can operate the system.
The RCP2-1200 supplies +15 VDC to power the LNA / LNB and +26 VDC to operate the transfer switches.
The RCP2-1200 will keep track of the three independent LNA/LNB systems, keeping the link with the most failures in a given time offline. This is reset each time the user manually overrides the system by selecting one of the units from the front panel of the RCP2-1200.
A failure in an LNA or LNB is typically noted by a change in the DC bias current. The RCP2-1200 has current window comparators that monitor the current drawn by each unit and will report a fault if the current falls outside of the preset current window. The nominal current and window width setting are factory preset to the particular LNA / LNB system, however both are easily adjustable via the front panel control.
A typical 1:2 Redundant LNA System is shown in Figure 4-7.
46 209351 REV B Operations Manual, Redundant System Controllers
Figure 4-7: Schematic, Typical 1:2 Redundant LNA System
4.2.1.1 LNA/LNB Fault Tracking
To set up the RCP2-1200 for LNA/LNB fault tracking perform the following menu
selections. Press the Main Menu key; select 4.Flt. Setup and press the Enter key; select 1.Mjr. Faults and press the Enter key; select 1.LNA/LNB and press the Enter
key. This puts the RCP2-1200 in LNA/LNB current monitor mode
4.2.1.2 LNA / LNB Current Calibration
After the RCP2-1100 has been put in the LNA/LNB fault tracking mode, the LNA or LNB nominal current should be calibrated by the controller. To perform the current
calibration, press the Main Menu key; select 6.Calibr and press the Enter key; select
3.Calibrate and press the Enter key. This calibrates the normal current consumption
of the LNA/LNBs.
To select the sensitivity of the alarm detection, select 1.Flt.Window and press the En- ter key. Select from four window settings which represent a percentage of the total cur-
rent being consumed by the LNA/LNB. The 8% setting is the most sensitive and 20% is the least sensitive. The factory default setting is 8%.
Note: Caution should be used when changing Fault Window settings from the factory
preset. Current variations will occur in equipment naturally as a result of changes in operating temperature. Consideration should be given to environmental conditions and, in particular, to operating temperature extremes.
Operations Manual, Redundant System Controllers 209351 REV B 47
4.2.2 SSPA 1:2 Redundant System Operation
The RCP2-1200 can be configured to accept external fault inputs at connector J8 (See
Section 2.4.6). The external alarm inputs operate with a closure to ground input. The
alarm inputs are opto-isolated inputs that expose +5 VDC, open circuit voltage, at 5 mA maximum short circuit current. The external alarm inputs can be driven by an appropriate open collector device or relay contacts. Redundant systems typically use a form C relay summary alarm output to drive the RCP2 external alarm input. A typical
block diagram representation of such a system is shown in Figure 4-8.
Figure 4-8: Block Diagram, 1:2 SSPA Redundant System
The external alarm inputs are not limited to SSPA systems. Any device with the appropriate alarm output circuitry could be connected to the external alarm inputs.
To use the external alarm inputs on the RCP2-1200 they must first be enabled from the front panel using the following procedure.
4.2.2.1 External Alarm Tracking
Press the Main Menu key; select 4.Flt. Setup and press the Enter key; select 1.Mjr. Faults and press the Enter key; select 2.External and press the Enter key. This puts
the RCP2-1100 in external alarm monitor mode.
48 209351 REV B Operations Manual, Redundant System Controllers
4.3 Operation of 1:1 Fixed Phase Combined System with FPRC-1100
The 1:1 Fixed Phase Combined Redundant System is a popular system architecture that enables two Solid State Power Amplifiers to operate as a normal 1:1 redundant system or a phase combined system. The basic system topology is very similar to a
1:1 redundant system and is shown in Figure 4-9. An additional switch is included
which allows either amplifier to be individually routed to the antenna or connect both amplifiers to a waveguide combiner. The combined system output power is then routed to the antenna. The operation is very similar to the older generation variable phase ratio combiner (VPRC) techniques.
Amp 1
RF Input
RF Output
Amp 2
Figure 4-9: Block Diagram, 1:1 Fixed Phase Combined System
System designers find that the 1:1 Fixed Phase Combined Amplifier System topology is a cost effective solution to realizing higher power amplifier systems. For slightly more investment over a traditional 1:1 redundant system, the operator can have the capabil­ity of doubling the individual amplifier output power when conditions may require addi­tional power. This is helpful when either atmospheric conditions require more power or if additional satellite traffic requires higher power capacity.
The FPRC-1100 controller is specifically designed to handle such an amplifier system. It not only handles all of the traditional fault monitoring and switching duties but also provides an overall system monitor and control facility. The FPRC-1100 can adjust the system gain over a 20 dB range without the need to adjust each of the amplifiers individually. It also provides a convenient display of the overall system output power. Individual amplifier monitor and control can all be achieved through the FPRC-1100 either locally via the front panel or by remote serial communication.
Operations Manual, Redundant System Controllers 209351 REV B 49
4.4 Operation of 1:2 Fixed Phase Combined System with FPRC-1200
The 1:2 Fixed Phase Combined Redundant System is a popular system architecture that enables Solid State Power Amplifiers to achieve higher output power levels while building in a level of redundancy. The basic system topology is similar to a 1:2
redundant system and is shown in Figure 4-10. Amplifiers #1 and #3 are normally
online. The outputs of #1 and #3 are directed by the waveguide switches into a fixed phase combiner such as a waveguide “magic tee” style combiner. In the event of a failure of either on line amplifier, the standby amplifier, #2, can be switched in place of either #1 or #3 and the system maintains full output power.
Amp 1
RF Input
Amp 2
Standby
Amp 3
RF Output
Figure 4-10: Block Diagram, 1:2 Fixed Phase Combined System
System designers find that the 1:2 Fixed Phase Combined Amplifier System topology is a very cost effective solution to realizing higher power amplifier systems. For exam­ple, it is less expensive to configure a 1 kW C-Band redundant system using (3) 500W Compact Outdoor Amplifiers in a 1:2 Fixed Phase Combined redundant system than it is to use (2) 1 kW amplifiers in a traditional 1:1 Redundant System.
The FPRC-1200 controller is specifically designed to handle such an amplifier system. It not only handles all traditional fault monitoring and switching duties but also provides an overall system monitor and control facility. The FPRC-1200 can adjust the system gain over a 20 dB range without the need to adjust each of the three amplifiers individually. It also provides a convenient display of the overall system output power. Individual amplifier monitor and control can also be achieved through the FPRC-1200 either locally via the front panel or by remote serial communication.
50 209351 REV B Operations Manual, Redundant System Controllers
4.5 RCP Remote Control of System SSPAs
RCP units that meet certain conditions are capable of remote control of system SSPAs through the RCP Local Serial Port (J5).
Note: The following features are supported only with RCP2/FPRC/RCPD firmware
version 2.2.00 and above. To verify your unit firmware version browse to the SysID screen on the front panel. If the firmware version is below 2.2.00, the unit’s firmware can be upgraded to the proper version by the user.
Systems may contain up to three amplifiers (consisting of the Teledyne Paradise Datacom Compact Outdoor, Rack Mount SSPAs, or vBUC amplifiers) and a remote RF Power Meter. The SSPAs and RF Power Meter must be connected to the RCP Local Serial Port (J5) via RS485 4-wire or 2-wire interface. All connected components must utilize Teledyne Paradise Datacom String Serial Protocol at 9600 Baud.
If properly configured, the RCP will allow the user to remotely change the Mute Status and Attenuation Level of the connected units, and monitor the Output RF Power. Under such control, all connected units are exclusively controlled by the RCP unit and any new unit added to the system will be automatically adjusted to the selected Attenuation Level and Mute State.
RCP2/FPRC/RCPD units equipped with firmware version 3.30 or later have extended remote system monitoring features, including the ability to monitor and display individual unit temperature and ambient temperature (if the system is equipped with a Teledyne Paradise Datacom remote RF Power Meter). Moreover, the RCP has an additional option to mute a unit sub-system during the period of switchover (see the Switch Mute option description for your particular controller).
Note: The SSPA fault status is not controlled via the serial line, therefore all controlled
SSPA summary alarm lines still have to be connected to the RCP External Alarms Port (J8). A Teledyne Paradise Datacom Remote RF Power Meter can be powered up either from the RCP unit (when remote control mode is enabled, the RCP will automati­cally turn on its 15V Power supplies) or from an external DC power source with the following characteristics: Output voltage +15V (+/- 3V); Minimum Output Current 300 mA.
Starting with RCP firmware version 3.40, the RCP supports External Reflected Power Monitoring. Monitor unit supports measurement of overall system Reflected Power within 20 dBm range with +/-1 dBm accuracy. The current value of the Reflected power can be viewed on the first informative screen of subsystem menus or accessed through the remote control interface. Outside of specified range, the accuracy of meas­urement is not guaranteed. If the supplied system is not equipped with this feature, the monitor value of reflected power on the front panel VFD will indicated as “N/A”.
Operations Manual, Redundant System Controllers 209351 REV B 51
4.5.1 Configuring the RCP for Remote Control Mode
The RCP unit has to be configured to support remote control of the system. To do so, perform the following steps:
1. Press the Main Menu key on the RCP front panel;
2. Select 5.Options and press the Enter key;
3. Select 6.More and press the Enter key;
4. Select 3.SSPA and press the Enter key;
5. Select 3.System Type and press the Enter key;
6. Select 2.RM SSPA if you want to control a system of Rack Mount SSPAs, Select 3.CO SSPA if you want to control a system of Compact Outdoor SSPAs, or Select 4.vBUC if you want to control a system of vBUC amplifi­ers, then press the Enter key. To disable the remote control feature, select
1.None and press the Enter key;
7. Select 4.View and press the Enter key;
Your RCP unit is now ready to control a remote system. After the RCP unit is config-
ured to control a remote system, make sure the system is correctly wired. See Tables
4-1, 4-2 and 4-3 for proper wiring.
Table 4-1: Compact Outdoor SSPA Wiring
RCP2 J5 Serial Local SSPA1 M&C J4* SSP A2 M&C J4 SSPA3 M&C J4
1,9 (RX+; 120 Ohm Termination) T (TX+) T (TX+) T (TX+)
2 (RX-) E (TX-) E (TX-) E (TX-)
3 (TX-) F (RX-) F (RX-) F (RX-)
4 (TX+) U (RX+) U (RX+) U (RX+)
5 (Ground) B,V (Mute In, GND) B,V (Mute In, GND) B,V (Mute In, GND)
RCP2 J8 Ext. Alarm
1 (Ext. Alarm 1) b (Summary open on
2 (Ext. Alarm 2) b (Summary open
3 (Ext. Alarm 3) b (Summary open on
4 (Ground) a (Summary
* If the cable length exceeds 50 ft., a termination resistor of 120 Ohms must be installed between F and U of the SSPA1 M&C J4 connector.
SSPA1 M&C J4 SSPA2 M&C J4 SSPA3 M&C J4
fault)
on fault)
fault)
Common)
a (Summary
Common)
a (Summary
Common)
52 209351 REV B Operations Manual, Redundant System Controllers
Table 4-2: Rack Mount SSPA Wiring
RCP2 J5 Serial Local
1,9 (RX+; 120 Ohm Termination) 1 (TX+) 1 (TX+) 1 (TX+)
2 (RX-) 2 (TX-) 2 (TX-) 2 (TX-)
3 (TX-) 3 (RX-) 3 (RX-) 3 (RX-)
4 (TX+) 4,9 (RX+; 120 Ohm
5 (Ground) 5 (GND) 5 (GND) 5 (GND)
RCP2 J8 Ext. Alarm
1 (Ext. Alarm 1) 8 (Summary open on
2 (Ext. Alarm 2) 8 (Summary open
3 (Ext. Alarm 3) 8 (Summary open on
4 (Ground) 7 (Summary
SSPA1 Serial Main
J4
Termination)
SSPA1 Serial Main
J4
fault)
Common)
SSPA2 Serial Main
J4
4,9 (RX+; 120 Ohm
Termination)
SSPA2 Serial Main
J4
on fault)
7 (Summary
Common)
SSPA3 Serial Main
J4
4,9 (RX+; 120 Ohm
Termination)
SSPA3 Serial Main
J4
fault)
7 (Summary
Common)
Table 4-3: vBUC Wiring
RCP2 J5 Serial Local
1,9 (RX+; 120 Ohm Termination) R (TX+) R (TX+) R (TX+)
2 (RX-) U (TX-) U (TX-) U (TX-)
3 (TX-) U (RX-) U (RX-) U (RX-)
4 (TX+) R (RX+) R (RX+) R (RX+)
5 (Ground) L (Isolated GND);
RCP2 J8 Ext. Alarm
1 (Ext. Alarm 1) D (Summary open on
2 (Ext. Alarm 2) D (Summary open on
3 (Ext. Alarm 3) D (Summary open on
4 (Ground) F (Summary
* If the cable length exceeds 50 ft., a termination resistor of 120 Ohms must be installed between R and U of the vBUC1 M&C J4 connector.
vBUC1 Serial Main
J4*
J,K (Ext. Mute, GND)
vBUC1 M&C J4 vBUC2 M&C J4 vBUC3 M&C J4
fault)
Common)
vBUC2 Serial Main
J4
L (Isolated GND);
J,K (Ext. Mute, GND)
fault)
F (Summary
Common)
vBUC3 Serial Main
J4
L (Isolated GND);
J,K (Ext. Mute, GND)
fault)
F (Summary
Common)
Operations Manual, Redundant System Controllers 209351 REV B 53
All attached units must be properly configured in order to work under RCP Remote Control. The following parameters must be set for each unit:
1. Serial Protocol to “Normal” or “String”;
2. Selected Baud Rate to 9600;
3. Type of Serial Interface to “RS485”;
4. Unique address selected as follows:
A. SSPA1=1; B. SSPA2=2; C. SSPA3=3 D. Remote RF Power Meter=4.
Refer to your amplifier manual for details.
4.5.2 Using M&C features of RCP to control a SSPA system
All SSPA control-related functions are grouped on the same menu, the SSPA control menu. To access the SSPA control menu, perform the following sequence on the RCP front panel:
1. Press the Main Menu key;
2. Select 5.Options and press the Enter key;
3. Select 6.More and press the Enter key;
4. Select 3.SSPA and press the Enter key.
The SSPA control menu will be displayed on the front panel VFD as follows:
1.Mute 3.Sys.Type
2.Attenuation 4.View
All of the following steps describe RCP remote operation of an SSPA, and assume the user has already selected the SSPA control menu.
4.5.2.1 Change Mute State
To change the overall mute state of a controlled SSPA system from the RCP, perform the following steps:
1. Select 1.Mute and press the Enter key;
2. Select desired Mute state and press the Enter key;
54 209351 REV B Operations Manual, Redundant System Controllers
4.5.2.2 Change Attenuation Level
To change the overall attenuation level of a controlled SSPA system from the RCP, perform the following steps:
1. Select 2.Attenuation and press the Enter key;
2. Select the desired level of attenuation and press the Enter key;
3.
4.5.2.3 Change Switch mute option value
The following option was introduced into the RCP control setup to overcome a problem with microwave arcing, which may potentially damage a switching component if switching RF power exceeds 400 Watts. This particular problem becomes a critical issue if coaxial RF pass switches are used.
In general, all Teledyne Paradise Datacom SSPAs are well protected against high reflected power conditions which may take place during output microwave switchover. But with certainty, waveguide or coaxial switches will develop an internal electrical arc during switchover if the output power is significant. Such conditions, will not lead to instant failure, but over time may diminish some critical RF switch characteristics.
If this option is enabled, the system ability to output RF power will be bonded to the switch position sensing circuitry. This circuitry consists of the following components: a RCP electronic switch position detector; a wiring harness between the RCP and RF switch; and RF switch position sensors. Failure of the above components will lead to break in transmission.
Paradise Datacom LLC strongly recommends not to enable this option unless absolutely necessary.
Note: In order to enable switch muting, the system sub type must be selected to
either CO SSPA, RM SSPA or vBUC! If the system type set to “None,” the switch muting setting will be inhibited.
There are four selections under this option: No muting (“1.SWMute OFF”); internal muting (“2.Internal On”); external muting (“3.External On”) or all switch muting is on (“4.All ON”).
Internal muting refers to the particular RCP unit itself. If the position of one of the controlled RF switches changes or is about to change, the RCP will mute the SSPA subsystem by issuing a special “mute command” over the RS485 serial interface.
When the RF switch position indicator detects that the switch reliably reached Posi­tion1 or Position2, a “Mute Off” command will be issued to the SSPA subsystem over the serial interface. If the switch gets stuck between positions, the system will remain muted until the situation is resolved or the Switch Mute option is turned off.
Operations Manual, Redundant System Controllers 209351 REV B 55
4.5.2.4 Units
This option allows the user to select the RF Power measurement units (measured in either dBm or Watts) reported on the front panel and remote interface. Both Forward and Reflected RF power sensor measurements will be affected.
4.6 View SSPA System Info
To verify a selection on the SSPA control menu, select Item“4.View” and press the “Enter” key. The selected attenuation, forward RF power level, system mute state and type of the selected system will be displayed on the front panel VFD.
To return to the SSPA control menu, press the “Up” key; to return to the main menu, press the “Main menu key”.
Note: The Forward RF Power Level can be displayed only if a Paradise Datacom
remote RF Power Meter was included in your system. Otherwise, this item will display “N/A” for not available.
SSPA sub system info page 1 pertains to conditions and settings common to all
SSPAs in a subsystem (RCP firmware version 3.10 or better).
Atten.(dB) is the current level of subsystem attenuation. All SSPAs in the system are
adjusted simultaneously and have same level of attenuation.
Mute – indicates the overall mute state of the subsystem. Mute state is applied to all
connected SSPAs, the mute state of an individual SSPA can’t be different then the system mute state.
FrwrdRF(Watts/dBm) – readout from system forward RF power detector (if equipped).
The readout can be represented in Watts or dBms. (see Units menu selection). If the subsystem is not equipped with this power detector, the readout will display N/A.
Ref.RF(Watts/dBm) (RCP firmware version 3.40 or better) – readout from system
reflected RF power detector (if equipped). The readout can be represented in Watts or dBms. (see Units menu selection). If the subsystem is not equipped with this power detector, readout will display N/A.
SSPA sub system info page 2 (RCP firmware version 3.60 or better) pertains to
individual SSPA output power levels.
UnitRFx(dBm) – is the forward RF output level of each individual SSPA. The readout
can be represented in dBms only. The value of an individual forward RF power is measured on the output flange of a particular SSPA. If the SSPA unit is not present in the system, readout will indicate N/A.
56 209351 REV B Operations Manual, Redundant System Controllers
Important! Real system output power most likely will be different from this parameter.
In 1:1 or 1:2 systems, losses in switching and waveguide systems are not accounted. In phase combined systems, real output power will depend on the combining
configuration. For system output power, refer to FrwrdRF(Watts/dBm) on SSPA
subsystem info page 1.
SSPA sub system info page 3 (RCP firmware version 3.10 or better) pertains to each
individual SSPA unit’s core temperature and ambient temperature.
Ambient(C) – ambient temperature readout in °C. This readout is available only on the
systems equipped with forward RF power sensor, otherwise it will indicate N/A.
Unitx(C) – is an individual SSPA unit’s core temperature in °C. If a unit is not present
in the current system configuration, value will read N/A.
SSPA sub system info page 4 (RCP firmware version 3.60 or better) pertains to
individual SSPA unit’s DC current consumption.
UnitDCx(Amp) – DC current consumption of a SSPA unit, measured in Amperes. If a
unit is not present in the current system configuration, value will read N/A.
SSPA sub system info page 5 (RCP firmware version 3.30 or better) pertains to
additional subsystem settings.
System Type – is the type of connected SSPA subsystem. Possible readout: Compact
– for subsystem of Compact Outdoor SSPAs; RM – for subsystem of Rack Mount SSPAs; and vBUC – for subsystem of vBUC amplifiers.
SWMute – is type of switch muting implemented on the current system. Off – no switch
muting; External – for external switch muting input; Internal – for switching associated with this RCP unit; Both – utilization of switch muting inputs.
Operations Manual, Redundant System Controllers 209351 REV B 57
4.7 Advanced system level troubleshooting with RCP
The RCP controller offers the ability to control various systems, which can include various subcomponents. In some cases it is important to quickly pinpoint a faulty component without system disintegration. The RCP controller offers such capabilities. The following section describes the troubleshooting procedure for some systems.
4.7.1 Scenario 1
A 1:2 system contains devices connected to the RCP external port (SSPA) as well as an array of LNA devices connected to the Plate assembly port. Major faults are configured to track both types of fault. Fault logic is set to “High”. The RCP indicates a Unit1 fault. To determine which component of the controlled setup is failed, scroll down to System Info Page 4 and verify the status of the “LNA faults” and “SSPA faults” items. One or both items should indicate “1----”.
If the faulted element is found in the LNA setup, the user can double-check what
caused it. Perform the following steps: Press the Main Menu key; select 6.Calibration and press the Enter key; select 4.View CalPoints and press the Enter key. The VFD
will display the advanced LNA/LNB debugging screen, which will show calibration points and current consumption for each LNA. Note the difference between the “LNA1 (mA)” and “Cal1(mA)” values displayed on the screen.
If the faulted element is found in the SSPA setup, double-check the fault causing the problem by selecting Info page 5. Note the state of the “ExtFaults” item, which should indicate “Aux-111 HPA001”. This explains why unit 1 was considered as faulted (note logic “high” state “1” in “HPA001 “).
4.7.2 Scenario 2
In a 1:2 SSPA system with 5 auxiliary devices connected to the RCP external faults port, the RCP utilizes “fault on high” logic. Auxiliary faults are enabled.
An auxiliary fault indicates “Fault” condition. To find which auxiliary line indicates fault, browse to Info page 5. Note the value of “ExtFaults” item.
AUX-[Unit 3][Unit 2][Unit 1], where the “#” in “Unit #” is either “1” or “0”. A “0” indicates a fault and “1” indicates no fault.
So if the value shown on the display is “AUX-011 HPA000”, that indicates a fault state for auxiliary devices connected to auxiliary port lines 2 and 1.
58 209351 REV B Operations Manual, Redundant System Controllers
Section 5: Theory of Operation
5.0 Design Philosophy
The RCP series of redundant controllers was designed to achieve a new level in high reliability, maintenance free operation. A tightly integrated modular assembly approach has been used to realize an extremely versatile controller while maintaining its user friendly operator interface. Five basic building blocks are combined in the RCP redundant controller:
1. Redundant Power Supplies
2. Digital Core Board Assembly
3. I/O Board Assembly
4. Vacuum Fluorescent Display
5. Front Panel Mimic Display
5.0.1 Redundant Power Supplies
A block diagram of the controller is shown in Figure 5-1. Two power supplies are
provided in the controller. These supplies can be connected to two independent AC sources for absolute system redundancy. Either supply is capable of operating the controller and its associated transfer switches. Both power supplies have universal input capability operating over an input voltage range of 85 to 265 VAC and line frequencies of 47 to 63 Hz. The power supplies have a power factor of 0.93 ensuring minimum line harmonic products. Each power supply produces +26 VDC.
The RCP2 provides three channel power outputs for connecting external LNA/LNB units. In standard configuration, each LNA/LNB channel can be selected to supply 13V or 17V with up to 900 mA DC current output. Output voltage is user-selectable either from the front panel menu or over the remote control interface. The -HP model provides an additional 26V 1500 mA output option for use with higher power external equipment.
All channels are protected from overload and will reduce output if the maximum power output capacity is exceeded by an external load.
Note for 26V 1500 mA channel output: In order to provide an equal
load to both internal AC/DC supplies, channels derive their power asymmetrically: Channel 1 from PS2, Channel 3 from PS1; and Channel
2 from either PS2 or PS1. See Figure 5-1. This configuration allows
default standby Channel 2 to power up in case one of the AC/DC power supplies fails. In order to conserve power from the remaining power supply, the LNA/LNB channel will reduce its power output to 13V, 900 mA.
Operations Manual, Redundant System Controllers 209351 REV B 59
PS2 26V 6A PS1 26V 6A
26V On/Off Select
26V
1.5A Max
On/Off
26V 5 Amp M ax Outp ut to RF Switch drive
PS Overload Prot ectio n
26V
1.5A Max
On/Off
26V
1.5A Max On/Off
Optiona l ha rd w are , available on -HP models only
To control core
LNA1 PS
13/17V/Off Sel ect
+13/17V 900mA
+13/ 18/ 26 V Out to LNA/LNB Plate
LNA2 PS LNA3 PS
+13/17V 900mA
+13/17V 900mA
Figure 5-1: Block Diagram, Power Supply Configuration
5.0.2 Digital Core Board
The digital core board is the heart of the redundant controller. At the center of the dig­ital core board is the Atmel AVR Mega 103 microcontroller. The microcontroller oper­ates at a clock speed of 7.68 MHz. It provides control functions through the use of an 8 bit wide data bus and 16 bit addressing bus for most of the peripheral devices. A sepa­rate UART and collision detector is provided for extremely robust serial interfacing with multi-host networks. All digital I/O lines are protected by opto-coupling or transient ab­sorbing devices. The power supply lines are protected by current limiting devices. The digital core board also contains the interface circuitry that allows the RCP to be firm­ware upgradeable in the field. A block diagram of the Digital Core Board is shown in
Figure 5-2.
60 209351 REV B Operations Manual, Redundant System Controllers
Figure 5-2: Block Diagram, RCP Digital Core Board
5.0.3 I/O Board Assembly
The I/O Board Assembly contains the primary parallel (hardware) interface circuitry of the controller. It is physically attached to the Digital Core Board by a 40-pin header. The I/O Board provides the +15 VDC supply for the LNB units. Each output can supply up to 600 mA and is completely short circuit protected. The 10 form C relays and opto isolated inputs for the parallel I/O interface are included on this board assembly. A se­ries of rugged N-channel enhancement mode Mosfet devices provide the current sink circuitry to drive either one or two waveguide transfer switches.
5.0.4 Vacuum Fluorescent Display
Rarely found in redundant controllers, the RCP provides a large 2 line by 40 character alphanumeric display. This provides an extremely user friendly interface. The VFD is directly interfaced to the microcontroller via the address and data bus. Virtually all of the controller’s setup and adjustments are accessible from the VFD display. There is no need to access the interior of the controller to make any setup changes.
Operations Manual, Redundant System Controllers 209351 REV B 61
5.0.5 Front Panel Mimic Display
The front panel display is a densely integrated array of LEDs and switches that comprise an important part of the user friendly interface. A great deal of human engineering has gone into the design of this membrane panel. A full complement of alarm indicators are provided along with the mimic display which shows the switch positions of the redundant system. Four separate navigation buttons along with a sep­arate “Enter” button allow the user to easily navigate the firmware menu on the Vacu­um Fluorescent Display. Separate buttons have been provided for frequently used functions further enhancing the controller’s ease of use.
5.1 Control Cable Considerations
The RCP series of redundant controllers is designed to drive negative 28 VDC latching style transfer switches. Latching means that the switch has a self cutoff and does not require continuous current consumption. Some commonly used waveguide transfer
switches used in Paradise Datacom Redundant Systems are given in Table 5-1.
Table 5-1: Commonly Used Waveguide Transfer Switches
Part Number Description Manufacturer Voltage Range Current
75SBOS
10.7-14.5 GHz Sector -20 to -30 VDC 0.80 Amps
Waveguide/Coax
3NBGS
2SBGS
4BF
5.8-6.4 GHz
Waveguide/Coax
3.7-4.2 GHz
Waveguide/Coax
1.7-2.6 GHz Waveguide
Sector -20 to -30 VDC 2 Amps
Sector -20 to -30 VDC 3 Amps
Sector -20 to -30 VDC 4 Amps
As Table 5-1 shows, the switch drive current is dependent on the frequency band which determines the physical size of the switch motor. Therefore the system designer must consider the resistive cable losses when choosing a control cable length.
Similarly, the system designer must ensure use of the proper cable insulation for the particular installation. Paradise Datacom uses both Standard Service and Burial Grade for redundant system control cables. Standard Service cable has a PVC jacket which is ultra violet ray (UV) stable in outdoor use. However, Standard Service cable should not be immersed in water or be buried underground for long periods of time. For such applications, Burial Grade cable should be installed.
The RCP controller sources +26 VDC @ 5 Amps maximum to the transfer switch. A typical -28 VDC waveguide switch will operate over a range of -20 to -30 volts. There­fore, the minimum voltage required at the waveguide switch is -20 VDC. Using this as a design guideline, the control cable should be sized so that it does not drop more than 6 VDC from the controller to the switch.
62 209351 REV B Operations Manual, Redundant System Controllers
Paradise Datacom control cables utilize 20 conductors of #18 AWG stranded wire. The control cable schematic is shown in Figure 5-3. The resistance of #18 AWG stranded wire is 6.5 ohms per 1000 feet. The controller switch connector (J3) allows contacts for 2 wires per switch connection. Therefore, two conductors can be paralleled for both the source and return lines for the transfer switch. With a maximum allowable voltage drop of 6 volts, this equates to a 3 volt drop in the source wires and 3 volt drop in the return
wires. This is shown schematically in Figure 5-3. Using four (4) parallel #18 AWG
conductors gives a resultant cable resistance of 1.6 ohms per 1000 feet, or 0.0016 ohms per foot.
PARADISE DATACOM
RCP2-1200
1:2 REDUNDANT
SYSTEM CONTROLLER
Figure 5-3: Cable Losses to Transfer Switch
To calculate the maximum cable length that can be accommodated to the transfer switch, first consider the current draw by the switch either from the manufacturer’s data
or from Table 5-1. Next divide this current into 6 volts. This gives the maximum cable
resistance to and from the switch. Finally, divide this cable resistance by 0.0016 ohms/ ft. to find the maximum cable length. This is shown in the following example:
Switch Current draw = 3 Amps 6 V / 3 Amps = 2 ohms 2 ohms/1,250 ft. = 0.0016 ohms/ft.; maximum cable length using (4) #18 AWG connectors
Table 5-2 gives the maximum cable length for some popular switches.
Table 5-2: Maximum Cable Length for Selected Switches (Single Switch Systems)
Part Number Description Manufacturer Maximum Cable Length
75SBOS 10.7-14.5 GHz Waveguide/Coax Sector 4,690 ft. (1,430 m)
3NBGS 5.8-6.4 GHz Waveguide/Coax Sector 1,880 ft. (572 m)
2SBGS 3.7-4.2 GHz Waveguide/Coax Sector 1,250 ft. (381 m)
4BF 1.7-2.6 GHz Waveguide Sector 938 ft. (286 m)
Operations Manual, Redundant System Controllers 209351 REV B 63
THIS PAGE LEFT INTENTIONALLY BLANK
64 209351 REV B Operations Manual, Redundant System Controllers
Section 6: Maintenance & Troubleshooting
6.0 Introduction
The RCP series of redundant controllers has been designed to be maintenance free. The only user replaceable parts are the AC input fuses.
6.1 Fuse Replacement
The AC input fuses are 2 Amp Slow Blow style fuses and are accessible at the AC
input entry module. Figure 6-1 shows the location of the input fuses as well as internal
part identification. Note that there is also an on/off switch located on the AC input entry module. The fuse part number is Littlefuse 217002, 2 Amp.
Figure 6-1: Controller Internal Part Identification and Rear Panel Fuse Location
Operations Manual, Redundant System Controllers 209351 REV B 65
6.2 Firmware Programming
The internal firmware is field programmable in the RCP redundant controller. This section details the procedure required to load new firmware into the RCP controller.
6.2.1 Hardware Interface
A connection from J6 of the controller and the parallel (LPT1, LPT2 or LPT3) port of a host PC must be established. This port must be configured for EPP/ECP or bidirection­al mode. Connect using an IEEE-1284 Compliant cable (DB25 Female – DB25 Male straight through. This cable is available for purchase in most electronic supply stores). The PC should be running Windows OS (98, NT, 2000 or XP are supported).
6.2.2 RCP Flash Upgrade
Use RCP Flash Upgrade only if a new official copy of firmware is released. Contact the Paradise Datacom U.S. office if you need to upgrade your unit's firmware.
The RCP firmware can be easily updated from the user's PC. A valid copy of the firmware HEX file must be obtained from Paradise Datacom’s U.S. office.
The following files will be provided for the firmware upgrade:
_code.zip: this zip file contains the programmer software (avreal32.exe); firmware
hex file (~code.hex); executable batch files (prg_LPTx.bat). prg_LPT1.bat for LPT1 prg_LPT2 for LPT2 and prg_LPT3 for LPT3
dlportio.zip: this zip file contains the parallel port drivers required by Windows OS.
DisableWarmBoot.reg and EnableWarmBoot.reg - Parallel port behavior manage-
ment utilities.
Step 1: Unpack dlportio.zip onto the target PC. Run the file, Setup.exe.
Step 2: Run DisableWarmBoot.reg. Select OK to add Windows registry key. The key will forbid the Windows parallel port driver from scanning parallel port after system re­boot. Reboot the computer.
Step 3: Unpack _code.zip into a temporary folder on the PC (for example, C:\temp). After the files are unpacked, locate the \_code subfolder.
Step 4: Turn off the RCP unit. Connect the PC’s LPT port to the Program Port (J6) at the rear of the unit using an IEEE1284 compliant cable (a “straight-through” DB25 fe­male to DB25 male parallel cable). Turn on the unit’s power.
66 209351 REV B Operations Manual, Redundant System Controllers
Figure 6-2: Firmware Upgrade Terminal Window
Step 5: After all connections have been made and all zip files unpacked, locate the batch file within the \_code subfolder which suits your LPT port designation (For example: prg_LPT1.bat for LPT1 parallel port) and run it. The batch file will open a Command prompt console window and execute the firmware update. Do not interfere with the program until the entire process is complete.
A terminal window with a black background will appear (See Figure 6-2). Watch for
messages on that window while your unit is being updated.
The new firmware becomes active immediately.
Step 5: Optional step. To restore default Windows parallel port behavior run the EnableWarmBoot.reg utility.
Operations Manual, Redundant System Controllers 209351 REV B 67
6.3 Restoring Factory Pre-set Settings on RCP2/FPRC
The Teledyne Paradise Datacom Redundant System Controller comes with factory­preset settings specific to the default system specifications. This factory setup can be restored at any time either automatically or manually.
Important: Automatic restoration will restore complete factory setup
(including COM settings and miscellaneous fault handling). Manual resto­ration has to be done one item at a time and only settings critical to sys­tem operation will be restored.
6.3.1 Automatic restore
To restore settings automatically, follow these simple steps:
1. On the front panel keypad, press the Main Menu key;
2. Select menu item 5.Options and press the Enter key;
3. Select menu item 2.Restore and press the Enter key;
4. Select menu item 2.Restore Fctry and press the Enter key;
Default factory setup is now restored; sequentially press "Main Menu" and "Enter" to return back to the informative menu sublevel.
6.3.2 Manual restore
Manual setup restoration is dependant on the makeup of your specific system. To undertake a manual setup restoration, follow these directions:
1. On the front panel keypad, press the Main Menu key;
2. Select menu item 3.Operation and press the Enter key;
3. Select menu item 3.System and press the Enter key;
4. Select the System menu item relevant to your system (i.e. menu item 4 for
Dual 1:1) and press the Enter key;
5. Press the Main Menu key;
6. Select item 4.Flt.Setup and press the Enter key;
7. Select menu item 1.Mjr.Faults and press the Enter key;
8. Select menu item 2.External if the controller is not supplying power to the LNBs; Select menu item 3.Both if the controller must be configured as the
primary power source for LNBs;
9. Press the Enter key;
10. Press the Main Menu key;
11. Select menu item 6.Calibr. and press the Enter
12. Select menu item 2.Fault Logic and press the Enter key;
13. Select menu item 1.Fault High and press the Enter key.
key;
68 209351 REV B Operations Manual, Redundant System Controllers
Skip the following steps if the controller is not configured as a primary power source for the system's LNBs.
Re-calibration of LNB's fault window:
14. Make sure the LNBs are reliably connected to the controller;
15. Make sure that all LNBs are normally operational prior to system calibration;
16. Make sure the controller is configured for tracking both LNA/LNB and external faults, if not sure, repeat steps 8 to 14;
17. Press the Main Menu key;
18. Select menu item 6.Calibr. and press the Enter key;
19. Select item 1.Fault Window and press the Enter key;
20. Select item 1.8% and press the Enter key;
21. Press the Main Menu key;
22. Select menu item 6.Calibr. and press the Enter key;
23. Select item 3.Calibrate LNAs and press the Enter key.
The controller should now be configured to work in a VSAT 1:1 Redundancy system.
6.4 Identifying and Replacing a Failed Power Supply
A power supply fault is always considered a major fault, and will cause the front panel Summary Alarm and Power Supply Alarm LEDs to illuminate. To identify which power supply module is faulted, follow these steps:
1. On the front panel keypad, press the Main Menu key.
2. Select menu item 1.Sys Info and press the Enter key.
3. The resulting screen shows the status of both power supplies PS1 and PS2
on the left side of the display. The controller monitors the output voltage of each power supply module. If the output voltage level for a power supply is
above 23V, the display will read Normal. If the output voltage drops below 22V, the display will read Fault.
When looking at the back panel of the RCP, PS1 is on the left and PS2 is on the right.
6.4.1 Removing a Faulted Power Supply Module
To remove a faulted power supply module from the RCP chassis, perform the following steps:
1. Loosen the two captured thumbscrews securing the module to the chassis;
2. Slide the module out of the chassis;
3. Unplug the quick-disconnect power pole connectors.
Operations Manual, Redundant System Controllers 209351 REV B 69
6.4.2 Installing a New Power Supply Module First, ensure that the new power supply module is the same type as the one
beng replaced! See Section 2.6 to review the different power supply module types.
To install a new power supply module into the RCP chassis, perform the following steps:
1. Plug together the quick-connect power pole connectors;
2. Slide the module into the chassis, taking care not to pinch the power cables;
3. Tighten the two captured thumbscrews to secure the module to the chassis.
70 209351 REV B Operations Manual, Redundant System Controllers
Section 7: Remote Control Interface
7.0 Overview
A system, which includes a RCP2, can be managed from a remote computer over a
variety of remote control interfaces (see Figure 7-1).
Rem ote con trol interface stack
10Base- T IP Inte rface
SNMP
HTTP We b
UDP
Serial Interface
Protocols:
1. Normal
2. Termi nal
RS485
RS232
Alarm Cont a ct
Figure 7-1: RCP2 Remote Control Interface Stack
The parallel port on the RCP unit provides a simple form of remote control. There are 10 form C relay contacts for remote monitoring. There are six opto-isolated inputs for remote control commands. To enable the remote parallel interface simply select remote on the front panel “Local/Remote” button. When in Remote mode all front panel
commands are disabled with the exception of the “Local/Remote” button. See Section
7.1 for details.
The serial interface supports both RS-232 and RS-485 standards. The control protocol
supports two formats: the Normal serial protocol (as detailed in Section 7.2); and an ASCII based protocol suitable for HyperTerminal applications (see Section 7.5).
The Ethernet interface provides the ability to control the system through: IPNet
interface (UDP encapsulated Normal serial protocol – Section 7.6.2); SNMP V1 (Section 7.6.3) or HTTP Web interface (Section 7.6.4).
Operations Manual, Redundant System Controllers 209351 REV B 71
The SSPA subsystem units can also be accessed directly through a packet wrapping
technique described in Section 7.3.1.
Serial protocol format is set at no parity, 8 bit with 1 stop bit. Baud rate is selectable through the front panel.
If using a Terminal mode protocol, the RCP2 provides remote menu access through a HyperTerminal program or through an actual hardware terminal.
The Ethernet interface is fixed to the 10Base-T standard. Normally, straight-through Cat5 cable is used to connect the RCP2 to a network hub, and crossover Cat5 is used to connect directly to a computer’s Ethernet port.
7.1 Remote Control - Parallel
7.1.1 Control Outputs
The hardware behind the form C relay is a single pole, double throw relay. Under normal operation (no alarms) the relays are in an energized state. When a fault occurs or the controller is powered off, the relays are in a de-energized state. The relay contacts are capable of handling a maximum of 30 VDC @ 1A . The form C relay is
shown schematically in Figure 7-2. The form C relay contact outputs are listed in Table 2-2.
Closed on Fault
Common
Open on Fault
Relay Energized
Closed on Fault
Common
Open on Fault
Relay de-Energized
Figure 7-2: Parallel I/O Form C Relay
72 209351 REV B Operations Manual, Redundant System Controllers
7.1.2 Control Inputs
The parallel control inputs are opto-isolated inputs with pull up resistors. To trigger a remote input command, the input should be pulled to ground. The input does not need to be held to ground continuously but it is acceptable to do so. The input only need be pulled low for a minimum of 100 msec. For example, to make amplifier #2 the standby amplifier, pulse pin 36 to ground for 100 msec. If the operator then chooses to make amplifier #1 the standby amplifier, simply pulse pin 37 to ground for 100 msec. The
schematic representation of the control input is shown in Figure 7-3.
The external alarm and auxiliary alarm inputs use the same opto-isolated input circuitry
shown in Figure 7-3.
+5 VDC
3.3K
560
Control Input
Transorb
Figure 7-3: Opto-Isolated Parallel I/O Input
Opto-Isolator
Operations Manual, Redundant System Controllers 209351 REV B 73
7.2 Serial Communication
This section describes the normal communication protocol between the RCP2 and a host computer over RS232/RS485 serial interface. Serial port settings on host computer must be configured for 8-bit data at no parity, with 1 stop bit. Baud rate should match selected baud rate parameter on RCP2 unit.
The unit will only respond to properly formatted protocol packets. Figure 7-4 shows the
basic communication packet. It consists of a Header, Data, and Trailer sub-packet.
HEADER
(4 bytes)
DATA
(6-32 bytes)
TRAILER
(1 byte)
Figure 7-4: Basic Communication Packet
7.2.1 Header Packet
The Header packet is divided into 3 sub-packets which are the Frame Sync,
Destination Address, and Source Address packets, as shown in Figure 7-5.
HEADER
(4 bytes)
DATA
(6-32 bytes)
TRAILER
(1 byte)
Frame Sync (2 bytes)
0xAA5
Destination Address
(1 byte)
Source Address
(1 byte)
Figure 7-5: Header Sub-Packet
7.2.1.1 Frame Sync Word
The Frame Sync word is a two byte field that marks the beginning of a packet. This val­ue is always 0xAA55. This field provides a means of designating a specific packet from others that may exist on the same network. It also provides a mechanism for a node to synchronize to a known point of transmission.
7.2.1.2 Destination Address
The destination address field specifies the node for which the packet is intended. It may be an individual or broadcast address. The broadcast address is 0xFF or 0xAA
(see Section 7.2.5 Multiple Device Access). This is used when a packet of information
is intended for several nodes on the network. The broadcast address can be used in a single device connection when the host needs to determine the address of the amplifier. The RCP2 unit will reply with its unique address.
74 209351 REV B Operations Manual, Redundant System Controllers
7.2.1.3 Source Address
The source address specifies the address of the node that is sending the packet. All unique addresses, except the broadcast address, are equal and can be assigned to individual units. The host computer must also have a unique network address.
7.2.2 Data Packet
The data sub-packet is comprised of six to 32 bytes of information. It is further divided
into seven fields as shown in Figure 7-6. The first six fields comprise the command
preamble while the last field is the actual data.
HEADER
(4 bytes)
DATA
(6-32 bytes)
TRAILER
(1 byte)
Protocol ID
1 Byte
Request ID
1 Byte
COMMAND PREAMBLE
Command
1 Byte
Data Tag
1 Byte
Error Status /
Data Address
1 Byte
Data Length
1 Byte
DATA FIELD
Command
Data Sub
Structure
0 - 26 Bytes
Figure 7-6: Data Sub-Packet
7.2.2.1 Protocol ID
This field provides backward compatibility with older generation equipment protocol. It should normally be set to zero. This field allows the unit to auto-detect other protocol versions, which may exist in the future.
7.2.2.2 Request ID
This is an application specific field. The amplifier will echo this byte back in the response frame without change. This byte serves as a request tracking feature.
7.2.2.3 Command
The RCP2 protocol is a table based protocol. It allows the user to view and modify data tables located on the controlled device. Throughout the remainder of this description, “sender” will refer to the host PC, and “receiver” will refer to the RCP2 unit.
Sender and receiver are limited to two commands and two command responses. The Get Request command issued by a command sender allows monitoring of existing conditions and parameters on the receiver. The Get Request frame should not have any bytes in the Data Filed and be no longer than 11 bytes.
Operations Manual, Redundant System Controllers 209351 REV B 75
The Response frame from the receiver will contain a Get Response designator in the Command field. If the receiver does not detect any errors in the Get Request frame, the requested data will be attached to the response frame. The length of the Get Response frame varies by the amount of attached data bytes. It may contain 11+N bytes where N is the amount of requested data bytes from a particular table, specified in the Data Length field.
The Set Request command allows the sender to actively change parameters for the receiver’s internal configuration. The Set Request frame must contain a number of bytes in the Data Field as specified in the Data length field. The frame size must be 11+N bytes, where N is the length of the attached data structure. The receiver will respond with a frame where the command field will be set to a Set Response designator. The frame length is equal to the Request frame.
The byte value for each command is given in Table 7-1.
Table 7-1: Command Byte Values
Command Name
Command Byte Value
Set Request 0
Get Request 1
Set Response 2
Get Response 3
7.2.2.4 Data Tag
The RCP2 internal structure is organized in several tables, all of which share similar functionality and internal resources. To access the various tables, the data tag must be specified in the request frame. The data associated with certain tags is read only. Therefore only the “Get” command request would be allowed to access these data tags. The RCP2 will return an error on attempts to issue a “Set” request to a read-only table tag. Various tables may contain values formatted either in 1 or 2 bytes format. The Packet Wrapper Tag provides direct access to the RCP2 Local Port and has no
table association. The data tag byte values are given in Table 7-2.
76 209351 REV B Operations Manual, Redundant System Controllers
Tag Name
System Settings Tag
Table 7-2: Data Tag Byte Values
Data
Tag
Byte
Value
0 1 Byte
Minimum
valid
length of
the Data
Field
Description
This tag allows accessing various system settings on remote unit. Host access status: Full Read/Write access. Settings can be modified at any time. Some of the settings may require hardware reset of the remote RCP unit.
System Thresholds Tag
System Conditions Tag
ADC Channels Access Tag
Packet Wrapper 6 1 Byte
Reserved 2 N/A This tag is reserved.
Reserved 5 N/A This tag is reserved for factory use only
1 2 Bytes
3 1 Byte
4 2 Bytes
This tag allows access to the critical unit thresholds. Host access status: Tag have read only status.
This tag allows access to the unit’s internal conditions flags, such as fault status or current system status. Host access status: Read only. This type of the data can not be set or modified remotely.
This tag allows access to the unit’s internal Analog to Digital converter. Host access status: Read only. This type of the data cannot be set or modified remotely.
Bytes in Data fields under this tag will be redirected to a RCP Local Port without any change. Data Address field indicates how many bytes (if any) RCP should return from remote device response. Response frame for this tag is not guaranteed. It will depend on remote device response.
7.2.2.5 Data Address / Error Status / Local Port Frame Length
This field is a tag extension byte and specifies the first table element of the tagged da­ta. If the Data Length is more than 1 byte, then all subsequent data fields must be ac­cessed starting from the specified address. For example, if the requestor wants to ac­cess the amplifier’s unique network address, it should set data tag 0 (System set-
tings tag) and data address 8 (see Table 7-6, System Settings Details table). If the fol-
lowing Data Length field is more than 1, then all subsequent Settings will be accessed after the Unique Network Address.
Important! In the Response Frame Data Address filed replaced with the Error Status information. The various error codes are given in Table 7-3.
Operations Manual, Redundant System Controllers 209351 REV B 77
Table 7-3: Error Status Byte Values
Error Code name
No Errors 0 Normal Condition, no errors detected
Data Frame Too Big 1 Specified Data length is to big for respondent buffer to accept
No Such Data 2 Specified Data Address is out off bounds for this tag data
Bad Value 3 Specified value not suitable for this particular data type
Read Only 4 Originator tried to set a value which has read only status
Bad Checksum 5 Trailer checksum not matched to calculated checksum
Unrecognizable error 6
Byte
Value
Possible Cause
Error presented in originator frame, but respondent failed to recognize it. All data aborted.
In case of Packet Wrapper request frame (Tag 6), data address field used to specify amount of bytes returned by RCP unit in response frame from local port. Byte collecting from local port starts immediately after wrapped frame being send out. There is no time-out and response frame is not being sent back to host PC until specified amount of bytes collected from Local Port. New request sent by PC host will cancel byte collecting and all collected bytes will be discarded.
7.2.2.6 Data Length
This byte value specifies amount of bytes attached in Data Filed. For Get command it specifies the number of data bytes that has to be returned by RCP unit to a host PC in Response frame. For Set command value of this byte specifies number of data fields to be accessed starting from the address specified in the Data Address byte. In general, Data Length value plus Data Address must not exceed the maximum data size particular tag.
7.2.2.7 Data Field
The actual data contained in the packet must be placed in this field. The “Get Request” type of command must not contain any Data Field. “Get Request” will be rejected if any data is present in the Data Field. Generally, the Bad Checksum error code will be add­ed to the response from the unit. In case the data length is 2 bytes, each data word is placed in the frame with its least significant byte first. All data with length of 2 bytes must be represented as integer type with maximum value range from 32767 to (-32767). Formatting of data bytes for the Packet Wrapper frame is not important for the RCP unit. All data bytes will be redirected to the RCP2 local port without any modi­fication.
78 209351 REV B Operations Manual, Redundant System Controllers
7.2.3 Trailer Packet
The trailer component contains only one byte called the Frame Check Sequence. This
field provides a checksum during packet transmission. See Figure 7-7.
HEADER
(4 bytes)
DATA
(6-32 bytes)
TRAILER
(1 byte)
Frame Check
Checksum (1 byte)
Figure 7-7: Trailer Sub-Packet
7.2.3.1 Frame Check Sequence
This value is computed as a function of the content of the destination address, source address and all Command Data Substructure bytes. In general, the sender formats a message frame, calculates the check sequence, appends it to the frame, then transmits the packet. Upon receipt, the destination node recalculates the check sequence and compares it to the check sequence embedded in the frame. If the check sequences are the same, the data was transmitted without error. Otherwise an error has occurred and some form of recovery should take place. In this case the amplifier will return a packet with the “Bad Checksum” error code set. Checksums are generated by summing the value of each byte in the packet while ignoring any carry bits. A simple algorithm is given as:
Chksum=0
FOR byte_index=0 TO byte_index=packet_len-1
Chksum=(chksum+BYTE[byte_index]) MOD 256 NEXT byte_index
Operations Manual, Redundant System Controllers 209351 REV B 79
7.2.4 Timing issues
There is no maximum specification on the inter-character spacing in messages. Bytes in messages to amplifier units may be spaced as far apart as you wish. The amplifier will respond as soon as it has collected enough bytes to determine the message. Generally, there will be no spacing between characters in replies generated by units. The maximum length of the packet sent to the amplifier node should not exceed 64 bytes, including checksum and frame sync bytes. Inter-message spacing, must be provided for good data transmission. The minimum spacing should be 100 ms. This time is required for the controller to detect a “Line Cleared” condition with half duplex communications. Maximum controller respond time is 200 ms.
Host PC
Protocol ID0Request ID
Response Frame A
Request Frame A
J4 Main or J9 Ethernet
P
r
o
p
a
g
a
t
i
o
n
d
e
l
a
y
1
-
5
0
m
S
J5 Local
Request Frame B
Response Frame B
Protocol ID0Request ID
0 to 255
P
r
o
p
a
0 to 255
g
a
t
i
o
Command
Protocol ID0Request ID
n
d
e
l
a
y
1
­5
0
m
S
Command
0 - 1
2 - 3
Header 4 Bytes
Data Tag6Response Length
n = 11 + m
Command
0 to 255
0 - 1
Header 4 Bytes
Data Tag6Error Status
0 to 5
Request Frame A
Command Preamble
6 Bytes
Data Length 11 to 11 + m
Header
4 Bytes
Data Tag
0 - 4
Response Frame A
Command Preamble
6 Bytes
Data Length
11 + m
Header
4 Bytes
Request Frame B 11 to 11 + n Bytes
Data Address
0 to 255
ResponseFrame B
Command Preamble
6 Bytes
11 + n Bytes
Command Preamble
6 Bytes
Request Frame B
Data Length m = 1 to 128
Response Frame B
Trailer Checksum
1 Byte
Data Field
0 to m Bytes
Trailer Checksum
1 Byte
Data Field
m Bytes
Trailer Checksum
1 Byte
Trailer Checksum
1 Byte
SSPA Subsystem
Propagation delay 1 - 10 mS
Figure 7-8: Packet Wrapper access to SSPA subsystem
80 209351 REV B Operations Manual, Redundant System Controllers
Protocol ID0Request ID
0 to 255
Command
2 -3
Data Tag
0 - 4
Error Status
0 to 5
Data Length m = 1 to 128
7.3 Access optional SSPA subsystem with Packet Wrapper technique
Features introduced in firmware version 4.03 allow send requests directly to a remote SSPA subsystem. In this mode, the RCP redirects requests from its Serial Main or
Ethernet port to its Local serial port, connected to the SSPA (see Figure 7-8). Packet
wrapper requests are associated with longer response times, which have to be accounted in the host M&C software. This mode can be useful for advanced remote diagnostic of the attached SSPA subsystem.
All Packet Wrapper request frames must be “Data Set” command requests.
Each frame intended for redirection must be included in request packet Data Fields.
Packet Wrapping frame M&C should follow the same rules as for any other request frames with one exclusion — the Data Address field will represent the number of bytes expected back from the remote SSPA. These bytes will be redirected back to the Host M&C in the Data Field response packet. The response packet will not be sent until the specified number of bytes is collected in the RCP2 buffer.
Maximum length of the data fields in both directions should not exceed 32 bytes.
In the diagram represented in Figure 7-8, Request frame A is the Packet Wrapper
frame. It contains Request frame B, intended to be redirected to the remote SSPA.
Table 7-4: Request Frame Structure
Byte Tag Description
1 0xAA Frame Sync 1 2 0x55 Frame Sync 2 3 Destination Address - // ­4 Source Address -// -
5 Protocol Version Protocol Compatibility Byte, must be set 0 6 Request ID Service Byte
7 Command 0 Set Request; 1 Get Request
0 System Settings; 1 System Thresholds;
8 Data Tag
9 Data Address
10 Data Length Total length of the data, valid values: 1 – 10
11+N Data Actual Data
11+N+1 Checksum
2 Reserved; 3 Conditions; 4 ADC Data;
5 Reserved; 6 Packet Wrapper
Setting number, Sensor command,
EEPROM address
Dest. Address + Source Address + Protocol
Version + Request ID + Command + Data Tag +
Data Address + Data Length + Data
Operations Manual, Redundant System Controllers 209351 REV B 81
Table 7-5:. Response Frame Structure
Byte Tag Description
1 0xAA Frame Sync 1
2 0x55 Frame Sync 2
3 Destination Address - // -
4 Source Address -// -
5 Protocol Version Protocol Compatibility Byte, must be set 0
6 Request ID Service Byte
7 Command 2 Set Response; 3 Get Response
0 System Settings; 1 System Thresholds;
8 Data Tag
9 Error Status
10 Data Length Total length of the data, valid values: 1 – 10
11+N Data Actual Data
2 Reserved; 3 Conditions; 4 ADC Data;
5 Reserved; 6 Packet Wrapper
0 – No Errors, 1- Too Big, 2 No Such Data,
3 Bad Value, 4 Read Only, 5 Bad Checksum; 6
Unrecognized Error
11+N+1 Checksum
Dest. Address + Source Address + Protocol
Version + Request ID + Command + Data Tag +
Data Address + Data Length + Data
82 209351 REV B Operations Manual, Redundant System Controllers
Table 7-6: System Settings Data Values
Data
Address
1 1 System Configuration 2 1 Switching mode Auto Mode = 0; Manual Mode =1
3 1 Control mode Local = 0; Remote = 1 4 1 Reserved N/A 5 1 Priority Select Pol1 = 0; Pol2 = 1 6 1 Communication Protocol* Normal=0; Terminal=1** (version 4.00)
1 Baud Rate* 9600 = 0; 2400 = 1; 4800 = 2; 19200 = 3; 38400 = 4
7
8 1 Unique network address Valid values: 0 – 255 9 1
10 1 Type of fault monitoring LNA only = 1; SSPA only = 0; Both = 2 11 1 Auxiliary fault monitoring Monitor = 0; Ignore = 1 12 1 RF Switch Monitoring Major Fault=0, Alert Only=1, Alternate=2 (version 3.30) 13 1 Fault Latching Latch Enable=0, Latch Disable=1 14 1 Fault Window 20%=0, 8%=1, 12%=2, 15%=3 15 1 Fault Logic Fault on Low=0; Fault on High=1 16 1 User Password Valid Values=0 to 255
17 1 Amplifier Standby Configuration
18 1 Buzzer Enable Buzzer=0; Disable Buzzer=1 19 1 Password Protection Protection Off=0; Protection On=1 20 1 System Type None=0; Compact Outdoor=1; Rack Mount=2; vBUC=4
21 1 RF Power Units 22 1 Reserved N/A
23 1 LNA/LNB PS Output Voltage
24 1 Remote Response Address Valid Values= 0 to 255 25 1 Mute State Mute On=0; Mute Off=255 26 1 Remote SSPA Attenuation Valid Values= 0 to 255 (version 3.10) 27 1 Switch Mute Off=0; Internal=1; External=2; All on=3 (version 3.30)
28 1 Fault Tolerance Disabled=0; One Fault=1; Two Faults=2 (version 3.70) 29-32 4 IP Address (MSB – LSB)* 33-35 4 IP Gateway (MSB – LSB)* 36-40 4 IP Subnet Mask (MSB – LSB)* 41-42 2 Receive IP Port (MSB – LSB)* 43-46 4 IP Lock Address (MSB – LSB)*
47 - 49 3
# Bytes Description Limits and Byte Values
1:2 Controller = 0; 1:1 Controller = 1;
Phase combine 1:1 = 2; Dual 1:1 Controller = 3
Type of serial interface*
Amplifier 3 on Standby=3 (combine in FPRC-1100 mode)
High Power Range 26V, 1.5A = 2 (v4.13 -HP version only)
Settings required for normal operation of IP interface.
Consult network administrator for a proper setup.
All settings physically located on the RCP2-1000 unit.
Changes to these settings effective only after
Individual SSPA Unit Attenuation Offset. Offset value will be added
to Remote SSPA Attenuation value
(Data Address 26) to form SSPA
final value of attenuation
RS232 = 0; RS485 = 1;
IPnet=2; SNMP=3 (version 4.00)
Amplifier 2 on Standby=0 (default)
Amplifier 1 on Standby=1 Amplifier 2 on Standby=2
Measure RF in dBm = 0;
Measure RF in Watts = 1 (version 3.50)
Low range 13V, 900 mA = 0
High range 17V, 900 mA = 1
controller restart. (version 4.00)
Valid Values= 0 to 255 (version 4.20)
* - Requires hardware reset ** - Versions earlier than 4.00 support a different protocol selection:
Auto Select= 0; Extended = 1; Locus = 2; Terminal = 3
Operations Manual, Redundant System Controllers 209351 REV B 83
Table 7-7: System Condition Data Values
Data
Address
1 1 Unit 1 Fault state No Fault = 0; Fault = 1; Ignored = 2
2 1 Unit 2 Fault state No Fault = 0; Fault = 1; Ignored = 2
3 1 Unit 3 Fault state No Fault = 0; Fault =1; Ignored = 2
4 1 Summary Fault No Fault = 0; Fault = 1
5 1 Power Supply 1 Fault State No Fault = 0; Fault = 1
6 1 Power Supply 2 Fault State No Fault = 0; Fault = 1
7 1 Auxiliary input Fault State No Fault = 0; Fault = 1; Ignore = 2
# Bytes Description Limits and valid values
8 1 External Port State
9 1 LNA Faults
10 1 SSPA Faults
11 1 RF Switch 1 position
12 1 RF Switch 2 position
13-14 2
15-16 2
17-18 2
19-20 2
21-22 2
23-24 2
25-26 2
27-28 2
29-30 2
31-32 2
33-34 2
35-36 2
(available only with systems equipped
(available only with systems equipped
(available only with systems with remote
(available only with systems with remote
(available only with systems with remote
(available only with systems equipped
Forward RF Power
with Forward RF power meter)
Ambient Temperature in (oC)
with Forward RF power meter)
Core Temperature of SSPA Unit 1
SSPA control enabled)
Core Temperature of SSPA Unit 2
SSPA control enabled)
Core Temperature of SSPA Unit 3
SSPA control enabled)
Reflected RF Power
with Reflected RF power meter)
DC Current
Unit 1 in Amps
DC Current
Unit 2 in Amps
DC Current
Unit 3 in Amps
Forward RF Power
Unit 1 in dBm
Forward RF Power
Unit 2 in dBm
Forward RF Power
Unit 3 in dBm
Bit 0-2 = SSPA Input lines
Bit 3-8 = Auxiliary Input lines
Bit 0 = 1; Faults enabled; Bit 0 = 0; Faults disabled; Bit 1 =
1; Unit 1 Fault; Bit 2 = 1; Unit 2 Fault; Bit 3 = 1; Unit 3
Fault; Bits 1-3 = 0; No Fault
Bit 0 = 1; Faults enabled; Bit 0 = 0; Faults disabled; Bit 1 =
1; Unit 1 Fault; Bit 2 = 1; Unit 2 Fault; Bit 3 = 1; Unit 3
Fault; Bits 1-3 = 0; No Fault
Switch Fault = 1; Switch Ignore = 2; Position 1 = 3;
Position 2 = 4
Switch Fault = 1; Switch Ignore = 2; Position 1 = 3;
Position 2 = 4
If Setting RF Power Units = 0, Value x 10dBm;
If Setting RF Power Units = 1, Value x 10 W;
(See Table 16, Data Address 21 for details)
(-100 for N/A (0xFF9C); Low Byte First (version 3.10)
Value x 1 °C
N/A=0xFF9C (if parameter is not available at present
time); Low Byte First (version 3.10)
Value x 1 °C
N/A=0xFF9C (if parameter is not available at present
time); Low Byte First (version 3.10)
Value x 1 °C
N/A=0xFF9C (if parameter is not available at present
time); Low Byte First (version 3.10)
Value x 1 °C
N/A=0xFF9C (if parameter is not available at present
time); Low Byte First (version 3.10)
If Setting RF Power Units = 0, Value x 10dBm;
If Setting RF Power Units = 1, Value x 10 W;
(See Table 16, Data Address 21 for details)
(-100 for N/A (0xFF9C); Low Byte First (version 3.30)
Value x 10 Amp
N/A=0XFF9C; Low Byte First (version 3.60)
Value x 10 Amp
N/A=0XFF9C; Low Byte First (version 3.60)
Value x 10 Amp
N/A=0XFF9C; Low Byte First (version 3.60)
Value x 10 dBm
N/A=0XFF9C; Low Byte First (version 3.60)
Value x 10 dBm
N/A=0XFF9C; Low Byte First (version 3.60)
Value x 10 dBm
N/A=0XFF9C; Low Byte First (version 3.60)
84 209351 REV B Operations Manual, Redundant System Controllers
Table 7-8: System Threshold Data Values
Data
Address
1 2 LNA unit 1 calibration Data
2 2 LNA unit 2 calibration Data
3 2 LNA unit 3 calibration Data
# Bytes Description Limits and valid values
Table 7-9: ADC (Analog-Digital Converter) Addressing
Data
Address
0 2
1 2
2 2
3 2
4 2
5 2
6 2
7 2
# Bytes Description Limits and valid values
Current value of ADC channel 0
Current value of ADC channel 1
Current value of ADC channel 2
Current value of ADC channel 3 Current value of ADC channel 4 Current value of ADC channel 5 Current value of ADC channel 6 Current value of ADC channel 7
LNA unit1 cal. Point conversion: 0.57 mA per 1 value increment, maximum value =1023. LNA unit2 cal. Point conversion: 0.57 mA per 1 value increment, maximum value =1023. LNA unit3 cal. Point conversion: 0.57 mA per 1 value increment, maximum value =1023.
LNA unit3 power supply’s current. 0.57 mA per 1 ADC increment, maximum ADC value =1023. LNA unit2 power supply’s current. 0.57 mA per 1 ADC increment, maximum ADC value =1023. LNA unit1 power supply’s current. 0.57 mA per 1 ADC increment, maximum ADC value =1023. Power Supply 2 output voltage. 36 mV per 1 ADC increment, maximum ADC value =1023. Power Supply 1 output voltage. 36 mV per 1 ADC increment, maximum ADC value =1023.
Not Used Not Used Not Used
Operations Manual, Redundant System Controllers 209351 REV B 85
7.4 Examples
This section contains several examples of serial data exchange between a host computer and an RCP2-1200 1:2 Redundant Controller. All byte values are given in hexadecimal format. The following controller and system switch positions are used throughout all examples.
RCP2-1200 Network Address = 0
Host Computer Network Address = 10
Request ID = 0x6F
Amplifier Status
Amplifier #1= OK Amplifier #2= Faulted Amplifier #3= OK
Power Supply Status
Power Supply #1=OK Power Supply #2=OK
Auxiliary Fault Inputs = Faulted RF Switch Status
Switch #1 Position= Position 1 Switch #2 Position = Undetermined or Faulted
7.4.1 Example 1
The host computer requests the RCP2-1200 system conditions. The RCP2-1200 detects no errors in the request frame and issues a response. The PC request string is listed below.
Byte
Position
1 AA Frame Sync Byte 1
2 55 Frame Sync Byte 2 3 0 Destination Address of RCP unit
4 A Source address of Request originating PC Host
5 0 Protocol Version Compatibility Field must always be 0 6 6F Request ID byte is set by originator, will be echoed back by respondent
7 1 Command field for “Get” type request
8 3 “System Conditions” tag indicates which data from respondent required in
9 1 Data Address field indicates the beginning data address inside of the “System
10 C Data Length field indicates how many data bytes of the “System conditions”
11 8A Arithmetic checksum of bytes number 3 through 10
86 209351 REV B Operations Manual, Redundant System Controllers
Byte
Value
(Hex)
response frame
Conditions” data set to 1 (first element)
requested from RCP2 (12 is all available data of “System Conditions” type)
Description
The RCP2-1200 replies with the following response string.
Byte
Position
Byte
Value
Description
(Hex)
1 AA Frame Sync Byte 1 2 55 Frame Sync Byte 2 3 A Destination Address of PC request originator 4 0 Source address of RCP respondent 5 0 Protocol Version Compatibility Field must always be 0 6 6F Echo of the Originator’s Request ID byte 7 3 Command field for “Get” type response
8 3 “System Conditions” tag indicates which data from respondent included in
response frame.
9 0 Data Address field omitted and replaced with Error status code. 0 in this field
indicates absence of errors.
10 C Data Length field indicates how many data bytes of the “System conditions”
requested from RCP (12 is all available data of “System Conditions” type).
11 0 Data field 1 contains data element 1 of “System Conditions” data type, which
is RCP System Unit1 Fault State. 0 Indicates that Unit 1 is not faulted.
12 1 Data field 2 contains data element 2 of “System Conditions” data type, which
is RCP System Unit2 Fault State. 1 Indicates that Unit 2 is in fault condition.
13 0 Data field 3 contains data element 3 of “System Conditions” data type, which
is RCP System Unit3 Fault State. 0 Indicates that Unit 3 is not faulted.
14 1 Data field 4 contains data element 4 of “System Conditions” data type, which
is RCP System Summary Fault State. 1 Indicates presence of faults in the system.
15 0 Data field 5 contains data element 5 of “System Conditions” data type, which
is RCP System Power Supply 1 Fault State. 0 Indicates that Power supply 1 is not faulted and functioning properly.
16 0 Data field 6 contains data element 6 of “System Conditions” data type, which
is RCP System Power Supply 2 Fault State. 0 Indicates that Power supply 2 is not faulted and functioning properly.
17 1 Data field 7 contains data element 7 of “System Conditions” data type, which
is RCP System Auxiliary Fault State. 1 Indicates presence of faults on one of the Auxiliary Inputs.
18 FF Data field 8 contains data element 8 of the “System Conditions” data type.
This data element is reserved for future applications.
19 FF Data field 9 contains data element 9 of the “System Conditions” data type.
This data element is reserved for future applications.
20 FF Data field 10 contains data element 10 of the “System Conditions” data type.
This data element is reserved for future applications.
21 3 Data field 11 contains data element 11 of the “System Conditions” data type,
which is RF Switch 1 state. 3 Indicates that RF Switch 1 is in Position 1.
22 1 Data field 12 contains data element 12 of the “System Conditions” data type,
which is RF Switch 2 state. 1 Indicates that RF Switch 2 is has a fault condi­tion or its position can’t be reliably determined.
23 8F Arithmetic checksum of bytes number 3 through 22
Operations Manual, Redundant System Controllers 209351 REV B 87
7.4.2 Example 2
The host computer requests the RCP2-1200 system thresholds. The PC request string is listed below.
Byte
Position
1 AA Frame Sync Byte 1 2 55 Frame Sync Byte 2 3 0 Destination Address of RCP unit 4 A Source address of Request originating PC Host 5 0 Protocol Version Compatibility Field must always be 0 6 6F Request ID byte is set by originator, will be echoed back by respondent 7 1 Command field for “Get” type request
8 1 “System Thresholds” tag indicates which data from respondent is required in
9 1 Data Address field indicates the beginning data address inside of the “System
10 6 Data Length field indicates how many data bytes of the “System Thresholds”
11 82 Arithmetic checksum of bytes number 3 through 10
Byte Value
(Hex)
Description
response frame
Thresholds” data set to 1 (first element)
requested from RCP (6 is all available data of “System Thresholds” type)
The RCP2-1200 replies with the following response string.
Byte
Position
1 AA Frame Sync Byte 1 2 55 Frame Sync Byte 2 3 A Destination Address of PC request originator 4 0 Source address of RCP respondent 5 0 Protocol Version Compatibility Field must always be 0 6 6F Echo of the Originator’s Request ID byte 7 3 Command field for “Get” type response
8 1 “System Thresholds” indicates which data from respondent is included in response
9 0 Data Address field omitted and replaced with Error status code. 0 in this field indicates
10 6 Data Length field indicates how many data bytes “System Thresholds” requested from
11 D1 Data field 1 contains least significant byte of data element 1 of “System Thresholds”
12 0 Data field 2 contains most significant byte of data element 1 of “System Thresholds”
13 D8 Data field 3 contains least significant byte of data element 2 of “System Thresholds”
14 0 Data field 4 contains most significant byte of data element 2 of “System Thresholds”
15 DC Data field 5 contains least significant byte of data element 3 of “System Thresholds”
16 0 Data field 6 contains most significant byte of data element 2 of “System Thresholds”
17 8 Arithmetic checksum of bytes number 3 through 16
Byte Value
(Hex)
Description
frame
absence of errors.
RCP (6 is all available data of “System Thresholds” type)
data type, which is LNA 1 cal. point
data type, which is LNA 1 cal. point. Data can be normalized to LNA current as follows:
Lna1calpoint * 0.57mA/point=209* 0.57= 119.13 mA
data type, which is LNA 2 cal. point
data type, which is LNA 2 cal. point. Data can be normalized to LNA current as follows:
Lna1 cal point * 0.57mA/point =216* 0.57= 123.12 mA
data type, which is LNA3 cal. Point.
data type, which is LNA 3 cal. Point. Data can be normalized to LNA current as fol-
lows:
Lna1 calpoint * 0.57mA/point=220* 0.57= 125.4 mA
88 209351 REV B Operations Manual, Redundant System Controllers
7.4.3 Example 3
The host computer requests the RCP2-1200 network address. The PC request string is listed below.
Byte
Position
1 AA Frame Sync Byte 1 2 55 Frame Sync Byte 2 3 FF Destination Address is broadcast network address 4 10 Source address of Request originating PC Host 5 0 Protocol Version Compatibility Field must always be 0 6 6F Request ID byte is set by originator, will be echoed back by respondent 7 1 Command field for “Get” type request
8 0 “System Settings” tag indicates which data from respondent required in
9 8 Data Address field indicates the address of the RCP2’s network address
10 1 Data Length field indicates how many data bytes “System Settings” re-
11 82 Arithmetic checksum of bytes number 3 through 10
Byte Value
(Hex)
Description
response frame
inside “System Settings” data set to 8
quested from RCP (1 byte requested)
The RCP2-1200 replies with the following response string.
Byte
Position
1 AA Frame Sync Byte 1 2 55 Frame Sync Byte 2 3 A Destination Address of PC request originator 4 0 Source address of RCP respondent 5 0 Protocol Version Compatibility Field must be always 0 6 6F Echo of the Originator’s Request ID byte 7 3 Command field for “Get” type of the response
8 0 “System Settings” indicates which data from respondent is included in
9 0 Data Address field omitted and replaced with Error status code. 0 in this field
10 1 Data Length field indicates how many data bytes “System Settings”
11 0 Data field 1 contains data element 8 of “System Settings” data type.
12 7D Arithmetic checksum of bytes number 3 through 11
Byte Value
(Hex)
Description
response frame
indicates absence of errors
requested from RCP
“Unique Network Address”=0
Operations Manual, Redundant System Controllers 209351 REV B 89
7.4.4 Example 4
The host computer requests the Priority be set to Polarity #2. The PC request string is listed below.
Byte
Position
1 AA Frame Sync Byte 1 2 55 Frame Sync Byte 2 3 0 Destination Address of RCP unit 4 A Source address of Request originating PC Host 5 0 Protocol Version Compatibility Field must always be 0 6 6F Request ID byte is set by originator, will be echoed back by respondent 7 0 Command field for “Set” type request
8 0 “System Settings” tag indicates which data from respondent is required in
9 5 Data Address field indicates the address of the RCP’s Priority Select data
10 1 Data Length field indicates how many data bytes “System Settings”
11 1 Data Field 1. 1 Indicates that priority must be set to Pol2
12 7F Arithmetic checksum of bytes number 3 through 11
Byte Val-
ue (Hex)
Description
response frame
element inside “System Settings”(data element 5)
requested from RCP (1 byte requested)
The RCP2-1200 replies with the following response string.
Byte
Position
1 AA Frame Sync Byte 1 2 55 Frame Sync Byte 2 3 A Destination Address of PC request originator 4 0 Source address of RCP respondent 5 0 Protocol Version Compatibility Field must always be 0 6 6F Echo of the Originator’s Request ID byte 7 2 Command field for “Set” type response
8 0 “System Settings” indicates which data from respondent is included in
9 2 Data Address field omitted and replaced with Error status code. 2 indicates
10 1 Data Length field indicates how many data bytes “System Settings”
11 0 Data field 1 contains rejected data
Byte Val-
ue (Hex)
Description
response frame
“No such data” error
requested from RCP
12 7E Arithmetic checksum of bytes number 3 through 11
90 209351 REV B Operations Manual, Redundant System Controllers
7.5 Terminal Mode Serial Protocol
The Teledyne Paradise Datacom RCP Redundant System Controller utilizes Terminal Mode Serial Protocol (TMSP) as a secondary serial protocol for Management and Control through a Remote Serial Interface.
TMSP allows the user to access internal RCP functions via a remote ASCII Terminal or its equivalent (such as HyperTerminal for Windows). TMSP is accomplished through either the RS-232 or RS-485, half duplex, serial communication link.
U.S. ASCII encoded character strings are used to represent commands and data massages. A remote terminal or controller initiates a communication session and the RCP takes action and returns a report of requested status. The RCP will not initiate communication and will transmit data only when commanded to do so. Prior to establishing the session with the RCP, this mode must be enabled through the front panel menu.
The remote terminal must be configured with serial settings that match the RCP’s serial port settings. For example, if the RCP is set at 9600 Baud, the remote terminal must be also configured as ASCII terminal at 9600 Baud, no parity, 8 bit data with 1 stop bit serial connection. The RCP will not echo back any incoming characters, so local echo must be enabled on the remote terminal.
To establish a remote control session with the RCP, the user must type “UNIT#XXX” in the terminal window (all letters must be in upper case), where XXX is the RCP’s unique network address or the global call address (255). Press the "Enter" key on Remote Terminal keyboard.
The RCP should answer with words "Unit#XXX OnLine" with the first menu screen on the following lines. After a remote session is successfully established, the unit will stay connected as long as needed. The session interface mimics the RCP's front panel menu. To help the user navigate through the menu, the help string with the list of active keys always follows the menu strings.
For example: "Active Keys:(U)p+Enter;(D)own+Enter;(C)lrearFlt; (M)enu+Enter; (E)
nd+Enter" will be the last transmission string on all informative menu screens. NOTE:
All letters must be in upper case!
To refresh current screen on the Remote Terminal simply press "Enter" key. To end a session, press "E" and then the "Enter" key.
Important! If multiple units are networked on the same serial link, DO NOT
ESTABLISH A SESSION WITH MORE THAN ONE UNIT AT THE SAME TIME. If you do so you will not get a valid response!
Operations Manual, Redundant System Controllers 209351 REV B 91
The following procedure will guide the user through the remote terminal setup, using the Windows 95/98 HyperTerminal software. The RCP must be connected to a PC com port and configured to use TMSP with 9600 Baud rate prior to setting up the PC configurations.
Start the Windows HyperTerminal Program (default Windows location at
Programs — Accessories — HyperTerminal).
Enter the name of your serial connection (“Compact Outdoor SSPA” for
example), and then click “Ok” button. See Figure 7-9.
Figure 7-9: Connection Description
Select direct connection to the PC communication port (Com1 for example),
which meant to be used for communication with RCP unit, and then click
“OK” Button. See Figure 7-10.
Figure 7-10: Communication Port Selection
92 209351 REV B Operations Manual, Redundant System Controllers
In the next window, select the following as shown in Figure 7-11: Bits per
Second: 9600; Data bits: 8; Parity: None; Stop bits: 1; Flow control: none. Click “OK”.
Figure 7-11: Communication Properties
Normally, the RCP will not echo back characters typed by the user in a
Terminal window. For added security and convenience, turn on Local Echo in the HyperTerminal application. To do so, select the following from the Hy­perTerminal menu: File Properties Settings ASCII setup. This will
bring up a window similar to that shown in Figure 7-12. In this window,
check the box marked “Echo typed characters locally” and click “OK”.
NOTE: Due to a software bug on some versions, this feature may not work.
Do not use versions prior to 6.3. Download the latest version of HyperTermi­nal at http://www.hilgraeve.com.
Operations Manual, Redundant System Controllers 209351 REV B 93
Figure 7-12: ASCII Setup
Your PC is now configured to work with the RCP in Terminal mode. To
establish a session with the RCP, type “UNIT#170”
Note: When using a RS-485 connection, avoid using the global address (170).
Instead, use the unique RCP address.
An example of a terminal mode session shown on Figure 7-13.
Figure 7-13: Terminal Mode Example
94 209351 REV B Operations Manual, Redundant System Controllers
7.6 Ethernet Interface
7.6.1 Overview
The RCP2 Ethernet port (J9) supports several IP network protocols to provide a full featured remote M&C interface over an Ethernet LAN.
IPNet protocol — redirection of standard Paradise Datacom LLC serial
protocol over UDP transport layer protocol. This protocol is fully supported in Paradise Datacom LLC’s Universal M&C software.
SNMPv1 protocol — protocol intended for integration into large corporate
NMS architectures.
HTTP Web interface — designed to allow platform independent remote
control function for a single RCP2 unit
In order to utilize either of the protocols listed above, the relevant interface option has
to be turned on. Refer to Section 7.5.2 (Setting IPNet interface), Section 7.5.3 (Configure unit to work with SNMP protocol) and Section 7.5.4 (Web interface).
Of course, standard IP level functions such as ICMP Ping and ARP are supported as well. There is currently no support for dynamic IP parameters settings (DHCP).
7.6.2 IPNet Interface
7.6.2.1 General Concept
Satcom system integrators are recognizing the benefits of an Ethernet IP interface. These benefits include:
Unsurpassed system integration capabilities;
Widely available and inexpensive set of support equipment (network cable;
network hubs);
Ability to control equipment over Internet;
Ease of use
Implementation of the raw Ethernet interface is not practical due to the limitations it places on M&C capabilities by the range of a particular LAN. It is more practical to use an Ethernet interface in conjunction with the standard OSI (Open System Interconnect) model to carry a stack of other protocols. In an OSI layered stack, an Ethernet interface can be represented as a Data Link layer. All upper layers are resolved through a set of IP protocols. In order to keep data bandwidth as low as possible (which is important when M&C functions are provided through a low-bandwidth service channel) the IP/UDP protocol set is used as the Network/Transport layer protocol on Teledyne Paradise Datacom SSPAs.
Operations Manual, Redundant System Controllers 209351 REV B 95
UDP (User Datagram Protocol) was chosen over TCP (Transmission Control Protocol) because it is connectionless; that is, no end-to-end connection is made between the RCP2 unit and controlling workstation when datagrams (packets) are exchanged.
Teledyne Paradise Datacom provides a WindowsTM-based control application to establish UDP-based Ethernet communication with the RCP2. The control application manages the exchange of datagrams to ensure error-free communication. An attractive benefit of UDP is that it requires low overhead resulting in minimal impact to network performance. The control application sends a UDP request to RCP2 unit and waits for response. The length of time the control application waits depends on how it is configured. If the timeout is reached and the control application has not heard back from the agent, it assumes the packet was lost and retransmits the request. The number of the retransmissions is user configurable.
The Teledyne Paradise Datacom RCP2 Ethernet IP interface can use UDP ports from 0 to 65553 for sending and receiving. The receiving port needs to be specified through the front panel menu. For sending, it will use the port from which the UDP request orig­inated. It is up to the user to select an appropriate pair of ports that are not conflicting with standard IP services. Teledyne Paradise Datacom recommends usage of ports 1007, 1038 and 1039. These ports are not assigned to any known application.
As an application layer protocol (which actually carries meaningful data), the standard RCP2 serial protocol was selected. This protocol proves to be extremely flexible and efficient. It is also media independent and can be easily wrapped into another protocol data frame. An example of the UDP frame with encapsulated Teledyne Paradise
Datacom protocol frame is shown on Figure 7-14.
UDP Header
(8 bytes)
SSPA Serial Protocol Frame
(11+N Bytes, 0<N<128)
CRC 16
checksum
Figure 7-14: UDP Redirect Frame Example
This set of Ethernet IP protocols is currently supported by Teledyne Paradise Datacom Universal M&C package (RCP2/FPRC/RCPD selection). The software package is supplied on CD with the controller unit, or can be downloaded by registered users of the company web site, http://www.paradisedata.com.
7.6.2.2 Setting IPNet interface
All IP-related menu items are consolidated under “Main Menu” “2.Com.Setup” “5.IPSetup”.
Prior to enabling the Ethernet IP interface, the following IP parameters need to be set: IP Port address, Default Gateway, Subnet Mask, Receive IP Port and IP lock address. The IP Lock address is a security measure. Setting this parameter either to 0.0.0.0 or
255.255.255.255 will allow any host to control the RCP2. Setting the parameter to the
96 209351 REV B Operations Manual, Redundant System Controllers
Table 7-10: OSI Model for RM SSPA Ethernet IP Interface
OSI Layer Protocol Notes
Application
Paradise Datacom RCP2 Normal serial protocol
Frame structure described in Section 7.2
Connectionless transport service. MTU on
Transport UDP
target PC must be set to accommodate largest SSPA Serial Protocol Frame. Set MTU to a value larger than 127 bytes.
ARP, RARP and ICMP Ping protocols
Network IP
supported by RM SSPA controllers. Static IP Address only, no DHCP support.
Data Link Ethernet 10/100 Base-T Network
Physical
Standard CAT5 (CAT 6) Network Cable
Maximum node length 100 m
specific address of the remote host will lock RCP2 access to this host. Packets received from other hosts will be ignored. For other parameters (IP address, Gateway, Subnet, IP port) contact your network system administrator.
Important! If you are planning to access the RCP2 through the Internet, you must exercise the appropriate security measures. It is strongly recommended to put RCP2 units behind a protective Firewall or set up a VPN link for remote access.
After selecting the IP parameters, you may turn on IP interfaces through front panel: “Main Menu” → “2.Com.Setup” → “4.Interface” “3.IPNet” (Enter).
Ethernet Interface is now the primary remote control interface and the RS232/485 Main port is disabled. You may adjust any IP settings when the IPNet interface is turned on as needed without losing your IP link. All new settings will become effective only after a RCP2 controller hardware reset (“Main Menu” “5.Options” “6.Reset” or cycle power to the unit). To disable the Ethernet port and enable the RS232/485 port: “Main Menu” → “2.Com.Setup” → “4.Interface” → “1.RS232” (Enter).
-OR- “Main Menu” “2.Com.Setup” “4.Interface” “2.RS485” (Enter).
Important! At present, the RCP2 controller supports one remote control protocol selection through its Ethernet interface port. This protocol is referred to as "Normal" on the front panel display (See Section 3.3.2.1). If the protocol selection is set to “Terminal”, the controller will force its protocol selection to "Normal".
The RCP2 Ethernet port can be connected to a network hub through straight through network cable or directly to a work station NIC card through a null-modem or cross­over cable (Rx and Tx lines are crossed). As soon as an Ethernet interface has been
Operations Manual, Redundant System Controllers 209351 REV B 97
selected as the primary interface, you should be able to verify the network connection to the unit by using the Ping command from your host workstation.
To do so on a Windows based PC, open a Command Prompt window and type PING and the dot delimited IP address of the RCP2, then press the Enter key. If the unit is successfully found on the network, the request statistic will be displayed.
PING XXX.XXX.XXX.XXX
If the unit does not answer on the ping command, check all hardware connections and verify that the IP settings on your host workstation and the RCP2 match your network parameters. On a Windows-based PC you may also check ARP table entries. The new IP address of the RCP2 may be set to another PC or network equipment with a different MAC address. Open a Command Prompt window and type "ARP -a”, the press Enter. The current table will be displayed. If you see the RCP2 IP address entry in the table, delete it by issuing the command "ARP -d XXX.XXX.XXX.XXX” and press Enter (XXX.XXX.XXX.XXX is the IP address of the RCP2 unit). Now try the PING command again. More information about how to set up a network connection with the RCP2 can be found in Appendix A.
7.6.3 Using the RCP2 Web Interface
With the Ethernet Interface activated as described in Section 7.6.2.2 and an IP
Address assigned to the unit, launch a Java- (version 1.5 or higher) and Javascript­enabled web browser. Teledyne Paradise Datacom recommends Internet Explorer version 7).
Enter the RCP2 IP address into the Address Bar of your web browser, and the
interface screen will load in the browser window, as shown in Figure 7-15.
98 209351 REV B Operations Manual, Redundant System Controllers
Figure 7-15: Web interface screen
The integrated web server loads a web page and a Java Applet. The activity indicator will be visible until the applet is loaded and running. Once the applet is fully loaded, a
password dialog window will appear. The default password is paradise. This password
may be changed in the Settings section of the web interface, and may comprise up to 15 alpha-numeric characters.
To select another password, enter the following selection on the RCP2 front panel:
Press the Main Menu key; select 2.Com.Setup and press the Enter key; select
3.IPNet and press the Enter key; select 5.IPConfig and press the Enter key; select
6.More and press the Enter key; select 4.WebPassword and press the Enter key.
Use the navigation keys to enter a new password. To erase a character, press and
hold the Up Arrow () and Down Arrow () keys simultaneously. If no password is
selected (all characters erased during password selection through the password select menu), the user will not be prompted with a logon dialog during web page initialization.
The Java Applet uses a UDP socket to communicate with the RCP. If you are using a hardware or software firewall, it will need notification that the Applet is authorized. If the firewall is not notified, the UDP packets will be blocked.
The RCP Monitor and Control is performed via following the links on the web page. These links include Status and Faults, Communication Settings, Settings, and Fault Setup.
Status and Faults: A view of all faults and operational parameters.
Communication Settings: This tab provides access to all communication
related settings. From here, the user can change the IP settings, Interface, Protocol, Baud Rate, Password and SNMP settings.
Settings: Read/Write listing of most adjustable RCP parameters. All options
are selectable. To set a parameter, select the new value and click the “Change” button with the mouse pointer.
Fault Setup: All fault related settings are available under this tab.
Note: Only one web browser should be connected at any time. If a second browser connects to the same RCP Web Interface, service quality cannot be assured.
Important! Make sure to set the IP Port Address to 1007. The Web interface will not function properly with a different port address selection. If the Web interface has to be disabled for any reason, select a port address of any other value.
Operations Manual, Redundant System Controllers 209351 REV B 99
7.6.4 SNMP interface
7.6.4.1 Introduction
SNMP-based management was initially targeted for TCP/IP routers and hosts. However, the SNMP-based management approach is inherently generic so that it can be used to manage many types of systems. This approach has become increasingly popular for remote management and control solutions for various SSPA systems.
Teledyne Paradise Datacom devices with Ethernet interface support the most popular SNMPv1 format (SMIv1, RFC1155), SNMP Get, SNMP GetNext and SNMP Set commands. SNMP Traps are currently unsupported.
In order to utilize SNMP protocol, the user has to enable this feature through the front panel or by remote serial protocol. SNMP uses the UDP fixed port 161 for sending and receiving requests.
The definition of managed objects described in MIB. The MIB file is available for down­load from the Software Downloads section of the Paradise Datacom web site, http:// www.paradisedata.com.
As with the serial protocol, the RCP2 MIB allows access to a remote SSPA (default state) as well as to the RCP unit itself. To switch between those devices’ MIBs, the proper Device Type has to be selected (OID -1.3.6.1.4.1.20712.1.4).
100 209351 REV B Operations Manual, Redundant System Controllers
Loading...