Tecumseh AJA9484EXDHS Performance Data Sheet

TECUMSEH OUTDOOR
CONDENSING UNIT
Model AJA9484EXDHS BOM 32L1061-2E*
Air Cooled 1 HP Application Commercial Temp Refrigerant R22
AJA9484EXDHS_REV1
TPC - November 21, 2013
SUCTION 1/2"
Volts-Hz-Ph 208-230/60/1
28.94
LIQUID 3/8"
27.94
23.50
26.55
26.08
2.96
O v e rall Dimensions, inch (mm) Line c onne c tions Pumpdown Air flow
AJA9484EXDHS
Factory charge 20 psig dry air,
Evaporato r
T, °F PSIG BTUH Watts Cond T BTUH Watts Cond T BTU H Watts Cond T BTUH Watts Cond T BTUH Watts Cond T
10 32.8 7700 1210 98 6700 1250 106 6300 1270 110 5900 1280 114 5300 1320 124 15 37.7 8400 1270 99 7500 1320 108 7100 1340 112 6700 1360 117 6000 1400 126
20 43.0 9300 1340 101 8400 1390 110 8000 1420 114 7600 1440 119 6800 1480 128
25 48.8 10200 1400 102 9300 1470 112 8900 1490 116 8500 1520 121 7700 1570 130 30 54.8 11100 1470 104 10300 1540 114 9800 1580 119 9400 1610 123 8600 1660 1 33 35 61.5 12100 1540 106 11300 1620 116 10800 1660 121 10400 1690 12 6 9500 1750 135 40 68.5 13200 1610 108 12400 1700 119 11900 1750 124 11400 1790 12 8 10400 1850 1 37 45 76.0 14400 1680 110 13500 1790 121 13000 1840 126 12500 1880 13 1 11400 1960 1 40
Performance @ 60 Hz, Return gas 40
LWH
26.55 (674) 28.94 (735) 26.08 (662) 18.18 lbs 750
MUST BE EVACUATED
80°F90°F95°F
o
F below 20oF Evaporator and 65oF above 20oF evapor at or, SubC oolin g 5oF
Suction Liquid Oz.
1/2" 3/8" 26
Ambient Temperatures
90% @ 90
o
SCFM
F
100°F 110°F
Oil Ch.
*OPTION CODE: See reverse side for Available Options
Gross weight
Lbs. (kg)
190 (86)
y
AJA9484EXDHS_REV1
TPC - November 21, 2013
Parts/Specifications
STANDARD AVAILABLE OPTIONS
Unit BOM 32L1061-2E Unit MODEL AJA9484EXDHS
Refrigeration Range 10°F to 45°F Fan Motor RLA 0.7 F Fixed Fan Control Design Pressure Low / High 150 / 450 Fan Blade 51568-1 A Adjustable Fan Control Volts - HZ - Ph 208-230V ~ 60HZ Fan Guard 70831 T1 Air Defrost Timer Voltage Range 187 - 253 Shroud 70727-2 T2 Electrical Defrost Timer & Defrost Min. Circuit Ampacity 11.13 Heater Contactor Max. Fuse Size 20 High Pressure switch 84095-1L D Disconnect Switch (nonfused)
Compressor MODEL AJA9484EXD Dual Pressure Conrol Compressor BOM AJ801ET-441-P2 Compressor LRA 54 Head Master Valve 70083-1 Solenoid Valve (supplied loose) KSVC-264 Compressor RLA 8.21 Check Valve 56626 Hail Louver Ass
OverLoad 8300CRTL48 Discharge Valve (Base) 56618 Replacement Kit - O/L K90-35 Liquid Valve (Base) 56500-K06 Receiver Heater (R option) 92124-2 Relay 820ARR3L25 Liquid Valve (Receiver) 31590 Receiver Thermostat (R option) 84102-2 Replacement Kit - Relay K71-16 Suction Valve (Base) 56500-K08 Fixed Fan Control (F option) Run Capacitor 85PR370F20 Suction Valve (Rotolock) 31582-3K Adjustable Fan Control (A option) Run Capacitor Rating 25 MFD, 370 V Start Capacitor 85PS250D84 Condenser 50857-1 Defrost Timer (T1 or T2 option) 84110 Start Capacitor Rating 216-259 MFD, 250 V Receiver 51082-1K Defrost Heater Contactor and 91014B and Contactor 91014B Accumulator TK00014000 Auxiliary Switch (T2 opt.) 91014-AUX
Unit Drawing DGU1893-L112 Sight Glass 70084-S Disconnect (D option) Wiring Diagram WD21-1T2 Suction Filter 704-20001 Wiring Diagram (A or F opt.) CrankCase Heater CH-102-40
Fan Motor 810F050C20 Replacement Fan Motor 50W230 Fan Motor Qty 1 R Heated/Insulated Receiver
Low Pressure Control 84026-2
Process Valve
Liquid Filter 70139
32Lxxxx-2ER(F)ATnD
AVAILABLE ACCESSORIES
REPLACEMENT PARTS
LLPG-101