Tecumseh Hermetic
Condensing Units
September 17, 2002
REV 2,2000
Model: AJA7465YXAXW |
R134a |
3/4 HP |
WATERCOOLED |
Note: Dimensioning = Inches [mm]
Model |
|
Dimensions, inches |
|
Line Connection* |
|
Oil Ch |
Gr. Wt. |
|||
L |
|
W |
H |
CH |
Suction |
Liquid |
|
CC |
Lbs. |
|
|
|
|
||||||||
AJA7465YXAXW |
24.0 |
|
17.0 |
9.0 |
12.0 |
5/8’F |
3/8’F |
|
782 |
95 |
Use 3/8” min. pipe size. Water valve inlet 3/8” NPT
Performance: Ambient 90°F—Return Gas 65°F—Condenser Water In 75° F—Head 135 PSIG
Evaporator Temp °F |
|
-10 |
0 |
+10 |
+20 |
+30 |
|
|
|
|
|
|
|
BTU/HR |
|
2029 |
3490 |
5372 |
7580 |
10013 |
|
|
|
|
|
|
|
Water Usage-gpm |
|
0.41 |
0.70 |
1.07 |
1.52 |
2.00 |
|
|
|
|
|
|
|
Watts |
|
588 |
770 |
930 |
1074 |
1207 |
|
|
|
|
|
|
|
The water valve should be adjusted to maintain a maximum of 95°F water outlet temperature in order to minimize water scaling within the condenser.
Return gas temp. 40°F, 5°F sub cooling