• Fluid R 407 C, as opposed to R22, is not a pure fluid but a blend
composed of:
- 23% R 32 + 25% R 125 + 52% R 134 A.
• The compressors approved for operation with this fluid are filled
beforehand with polyalcohol oil.
Contrary to mineral oil, it is very hygroscopic: it absorbs the
humidity of the ambient air very quickly. This can modify its
lubricant properties and lead in time to the destruction of the
compressor.
MAINTENANCE INSTRUCTIONS
1 - Never add oil to the appliance; the compressor is filled with
polyalcohol oil, a special oil which cannot tolerate the presence
of other oils.
2 - The instruments used for:
- filling,
- pressure measurements,
- emptying under vacuum,
- recovering the fluid,
must be compatible and only used for the R 407 C fluid.
3 - The weight of the refrigerant contained in the storage bottle
must be checked constantly. Do not use it from the moment the
remaining weight is less than 10% of the total weight.
4 - In the case of a new charge:
- do not use the charging cylinder,
- use a balance and a dip pipe type R 407 C cylinder,
- charge the weight of R 407 C as per the value indicated on
the unit’s identification plate (for “split systems”, refer to the
installation instructions as the charge must consider the
length of the connecting lines),
- IMPORTANT: see paragraph 3.
5 - The charge must be undertaken in liquid phase.
6 - In case of leakage, do not complete the charge: recover the
remaining refrigerant for recycling and perform a total charge.
Recovery, recycling or the destruction of the fluid must be done
in compliance with the laws in force in the country concerned.
7 - If the refrigerant circuit is opened, you must:
- avoid the entry of air into the circuit as much as possible,
- replace the filter drier.
- perform the “vacuum operation” at a minimum level of 0.3
mbar (static).
The installation must be specially designed in order to respect local noise regulations.
1 - GENERAL
1.1 - GENERAL SUPPLY CONDITIONS
• Generally speaking, the material is transported at the consignee’s risk.
• The consignee must immediately provide the carrier with written reserves if he finds any damage caused during transport.
2
Page 3
1.2 - RECOMMANDATIONS
• Prior to all servicing or other actions on the equipment, installation, commissioning, operation, or maintenance, the personnel
in charge of these operations shall become familiar with the instructions and recommendations provided in the installation manual
of the unit as well as the elements of the project's technical file.
• The personnel responsible for receiving the unit must conduct a visual inspection in order to identify all damage to which the unit
may have been subjected during transport: refrigerating circuit, electrical cabinet, cassis and cabinet.
• The unit must be installed, started, maintained and repaired by qualified servicing personnel in compliance with the requirements
of all directives, laws and regulations and in accordance with standard trade practices.
• During installation, troubleshooting and maintenance operations, the use of pipes as a step: under the stress, the pipe may
rupture and the refrigerant may cause serious burns.
1.3 - VOLTAGE
• Before carrying out any operation, check that the voltage indicated on the unit corresponds to the mains voltage.
1.4 - USE OF EQUIPMENT
• This heat pump is designed for heating/cooling floor type installations.
1.5 - OPERATING CONDITIONS
• Refer to the nominal conditions and operating limitations in the technical manual.
2 - PRESENTATION
2.1 - DESCRIPTION
1 - Sound-proofed hermetic compressor.
2 - Water exchanger with stainless steel plates.
3 - Water outlet connector.
4 - Water inlet connector.
5 - Hole for connecting cables.
6 - Electrical box.
7 - Fan motor.
8 - "Plate-Fin" air heat exchanger.
9 - Microprocessor control unit display keyboard.
10 - Fan protection plastic grille.
Materials:
- Copper piping.
- Painted sheet metal cabinet.
- Copper/aluminium exchanger.
- Plastic grille.
2.2 - DIMENSIONS AND WEIGHT
1Connection 3/4" (male)
-water outlet
2Connection 3/4" (male)
-water inlet
3Holes for electric cables
10
7
8
6
9
5
3
4
12
1
835
PMERV 5
70Weight (kg)
3
2
1 030305
130620
325
28080140
285
3
Page 4
3 - INSTALLATION
600
100
20
100
500
50
• Safety index: IP 24.
• Select the location for the unit on the basis of the following
criteria:
- the unit must be installed outside,
- the unit must not be installed near the following:
. sources of heat,
. combustible materials,
. return/air intake of an adjacent building,
- it is necessary to make sure that the free space around the
unit is provided (see the minimum dimensions on the
drawing opposite),
- installation must be simple and make maintenance work easy,
- the unit must be fixed on a hard base and must be protected
from risks of flooding, (we recommend that the unit be raised approximately 100 mm off the ground to facilitate the installation
of condensate drainage tubing, as required),
- use the anti-vibration mountings supplied, making sure that they are not compressed too much when the fastening screws are
tightened,
- the blown air must not be directed towards surrounding windows,
- vibrations and noise must not be transmitted to a nearby building,
- avoid:
. excessive exposure to salty air or sulfuric gas,
. the proximity of the extractor fan,
. projections of mud (next to a roadway or path, for example),
. areas where there is strong wind blowing against the unit's air exhaust.
Antivibration mountings
DRAINAGE OF CONDENSATES
- If necessary, use the accessory part supplied to connect the condensate
drainage tube.
- The base has 2 drainage holes (one on each side).
- For condensate drainage, place the splined elbow in one of the holes,
depending on the unit's inclination or the preferred side, and plug the other
hole with the plastic cover.
- In this case, the tank and the drain line must be protected against freezing
risks.
4 - CONNECTIONS
4.1 - HYDRAULIC CONNECTION
• Connect the water pipes to the corresponding connections. Refer to Ø and placement page 3.
• Install the hydraulic filter (supplied) on the water intake. Connect it using 2 isolation valves for cleaning purposes.
Note:
Insulated "flexible water pipes" accessories 1 metre in length can be used:
-Ø 3/4" code K 60 L 054 Z.
4.2 - ELECTRICAL CONNECTION
4.2.1 - GENERAL
• The acceptable voltage variation is: ± 10% during operation.
• The electrical connection conduits must be fixed.
• Use the cable clamps located inside the switch box.
• Class 1 unit.
• The electrical installation must comply with the standards and regulations applicable where the unit is being installed (in
particular NF C 15-100
CEI 364).
4.2.2 - POWER SUPPLY
• 230 V / 1 / 50 Hz.
• The power supply must come from an isolation and electric protection device (not supplied) in accordance with existing
regulations. The installation must be protected by a 20A double-pole circuit-breaker (not included).
Note: The unit is designed to be connected to a power supply having a TT neutral regime (neutral to ground) or TN.S regime
(to neutral) as per NF C 15-100.
POWER SUPPLY CABLE
• Section : 3 G 2.5 mm2.
• This section is given as an indication only.
It should be checked and adapted, if necessary, according to installation conditions.
• Make the electrical connections to the terminal board as per the electrical diagrams.
4
Page 5
CURRENT
2
1
3
4
PMERV
COOLING mode
HEATING mode
Nominal currentA
Max. currentA
Starting currentA
7.8
9.6
45
6.4
8
45
4.2.3 - REMOTE CONTROL
• The unit is factory-wired for heating mode operation. Operating control of unit is possible by connecting 2 potential-free, highquality external switches (not included):
-1 for the remote On/Off signal(contact closed = operation authorized, contact open = off),
-1 for change-over of the operating mode (contact closed = heating mode, contact open = cooling mode).
• The On/Off signal is connected to terminals 1 and 2 of the PCB located in the switch box (remove the existing bridge - see
diagram).
• The mode change-over signal is connected to terminals 3 and 4 of the PCB (remove the existing bridge - see diagram).
• The wiring of these contacts must not be routed near power cables in order to avoid electromagnetic disturbances.
• Use shielded cable.
• Max. connection cable length: 20 m.
• Minimum wire size: 0.25 mm
WARNING:
Mode changes (heating/cooling) are to be performed
with the unit shutdown.
2
.
(❋)
Remote control "off"
(❋)
Operating mode
(❋) Jumper to be removed
The "Remote control unit, K 60 D 035 Z" can perform this
function.
PMERV
2
(❋)
1
3
(❋)
4
(❋) Jumper to be removed
6
1
2
5
Remote control
K 60 D 035 Z
Remote control "off"
Operating mode
4.2.4 - MISCELLANEOUS
• Alarm transfer:
Potential-free, closing contact ( 2A - 250 VAC max.) located on the PMERV terminal board (terminals 5 and 6 of the PCB)
for remote signaling. See electrical diagrams.
• Water circulating pump control:
Do not use this contactor for the underfloor "Heating/cooling" application.
4.2.5 - PCB CONNECTION DETAILS
• Note: The terminals are of the "cage with spring" type.
Follow the indications below to connect them.
- These terminals take the following wires:
. rigid,
. flexible (avoid splicing the strands!),
. with ends.
-A single conductor per securing point.
- Make sure that the wires are correctly connected to the terminal board.
Incorrect connection can cause operating problems as well as overheating
which can cause fires.
2
3
1
5
Page 6
5 - OPERATION OF "COMPACT" µCHILLER ELECTRONIC CONTROL
• See wiring diagram page 11.
5.1 - DELIVERY STATE
• The control unit is supplied fitted in the machine and factory pre-set.
• All the connections are made except those concerning the available signals or the options.
5.2 - PRINCIPLE
• The microprocessor controls the operation of the
machine and of the associated alarms.It continuously
compares the water temperature measured by a probe
(S1) and the setpoint temperature value entered via
the keyboard. Each operating request produced by the
control unit is indicated by the light (6) (see below). This
light flashes if a safety delay is in progress. It stays on
when the compressor is operating.
• The control probe S1 is located on the water inlet in
the factory.
Temperature
probe S1
(for control)
Temperature
probe S2
(for anti-freeze
protection)
Temperature
probe S2
(for defrosting and
pressure
adjustment)
DIGITAL INPUTS
CARTE ELECTRONIQUE
A MICROPROCESSEUR
µCHILLER "COMPACT"
ACTUATORS
24 VAC
SUPPLY
TRANSFORMER
5.3 - PRESENTATION
5.3.1 - DISPLAY KEYBOARD
7
8
6
comp
x 100
5.3.2 - CTN TYPE TEMPERATURE PROBE
152
PRG
mute
SEL
1 Key for:
- Return to normal display/validation of parameters,
- Stopping audible alarm.
2 Key for:
- Cooling mode operation ("Summer").
- Incrementation of parameters.
3 Key for:
- Heating mode operation ("Winter").
- Decrementation of parameters.
µchiller
4 Key for access to parameters.
5 LED display.
6 Compressor "ON" light.
7 Cooling light ("Summer").
• The machine is wired in the factory to operate in heating mode.
• The operating mode (heating/cooling) can be switched remotely by connecting one external contact not supplied connected
to the PMERV (see paragraph 4.2.3 for details):
- contact open = cooling,
- contact closed = heating.
Cooling setpoint
6
Cooling
differential
Compressor control
Water temperature
Cooling
Compressor
control
Heating
Heating
differential
Cooling setpoint
Water temperature
Page 7
5.5 - STARTING
PRG
mute
SEL
µ
chiller
5 sec
• Initial condition:
- Machine hydraulically and electrically connected ready to operate.
- Operating mode remote changeover switch is in required position (heating or cooling).
- The remote On/Off contact is open (off).
• Turn the installation on.
• The display comes on and shows the water temperature (read by the control probe S1).
• Close the possible remote on/off contact (not supplied) if it is not connected (see paragraph 4.2.3).
• The indicator lamp corresponding to the selected mode lights up:
- indicator lamp (7): Cooling,
- indicator lamp (8): Heating.
• The compressor "ON" indicator light (6) comes on if necessary (see diagram paragraph 5.4). If the light flashes, it means that
the compressor is starting required but that a safety delay is in progress. This light stays on when the compressor has started.
• To stop the unit, open the remote On/Off contact (in this case, restart is automatic as soon as this contact is closed).
The operating mode indicator lights (7) and (8) and the compressor operation light (6) go off.
•It is possible to stop and restart the current mode (selected remotely) by pressing the
(2) for the cooling mode or the ▼ key (3) for the heating mode.
NOTE:
The controller’s anti-short cycle system requires that the compressor operate for a minimum
amount of time. If the machine should stop, the compressor may continue to function for a certain
amount of time (150 seconds max.).
CAUTION: Changing the operating mode (heating/cooling) must only be done when the machine is stopped.
▲ key
PRG
mute
SEL
5 sec
chiller
µ
5.6 - ADJUSTING AND DISPLAYING THE PARAMETERS
• Parameters accessible by pressing the SEL (4) key for 5 seconds.
• The display displays the code of the 1st parameter on the list ("r1" - see below).
• By pressing the ▲ (2) or ▼ (3) keys, scroll through the parameter codes until you reach the one
you want.
• Press SEL (4) to find out the value of the corresponding parameter.
• The value of the parameter can if necessary be changed using the ▲ (2) and ▼ (3) keys.
• Press SEL (4) to re-display the parameter codes.
• To store the parameters which have been changed and to exit the adjustment procedure, pressthe PRG (1) key. If during the adjustment procedure no key is pressed for 60 seconds (this period is indicated by the display
flashing), the system automatically reverts to normal operation and display without storing the latest parameter changes.
Code
r 1
r 2
r 3
r 4
r 6
r 8
c 9
c C
Parameters
Set point
Cooling ("Summer")
Differential
Cooling
Set point
Heating ("Winter")
Differential
Heating
Water heat exchanger temperature
(Probe S2 for anti-freeze)
Air heat exchanger temperature
(Probe S3)
Compressor hour meter
Pump hour meter
Factory
setting
22 °C
2 k
35°C
2 k
-
-
-
-
Installation
setting
-
-
-
-
Adjustment
range
10 to 30°C
0.3 to 19.9 k
25 to 45°C
0.3 to 19.9 k
-
-
-
-
Remarks
Probe located on water return
Display only
• The hour meters are zeroed by pressing simultaneously on the ▲ (2)
and ▼ (3) keys.
• Note:
The configuration and parameterization of each machine are factory-
set for optimal "Cooling/Heating Floor" operation.
comp
x 100
If light (9) is on,
multiply the time
displayed by 100.
PRG
mute
SEL
µchiller
7
Page 8
5.7 - ALARMS
• When an alarm occurs:
- the bell rings (2 A closing contact - 250 VAC max.),
- the display flashes and the alarm message appears cyclically (see table below),
- the machine stops if necessary (see table below).
• Remedy the fault.
Important note: any work must be done by qualified, experienced person.
• The alarm is cancelled automatically when the fault is cleared.
NOTE: If the circulation pump control is used, the "Water output" alarm may need to be reset manually by simultaneously pressing
the ▲ (2) and ▼ (3) keys.
• At that moment:
- the alarm report is de-activated,
- the display reverts to normal (no flashing),
- the machine can re-start (if it was stopped).
SUMMARY TABLE OF ALARMS
Alarm
Fault on probe 1
Fault on probe 2
Fault on probe 3
Water flow rate
H.P. (unused)
L.P.
Water heat exchanger frozen
Defrosting too long
Compressor maintenance
Memory error
Min. voltage
supply control
Max. voltage
supply control
Interference on
supply control
Message
E1
E2
E3
FL
H1
L1
A1
r1
n1
EE
EP
EU
EO
EL
Inhibition
delay (*)
-
-
-
30" on start-up
10" in operation
-
150" on start-up
-
-
-
-
-
-
-
NOTE:The alarms are not activated when the machine is off (except for probe and memory faults).
Threshold
Pressure switch
Pressure switch
10 mn
10 000 h
(*) Factory settings
Cancellation
(*)
-
-
-
-
2°C
Manual
According
-
seriousness
-
-
-
Auto
Auto
Auto
Auto
Auto
Auto
Auto
Auto
to
of fault
Auto
Auto
Auto
Machine
stop
X
X
X
X
X
X
X
-
According
to
seriousness
of fault
According to
seriousness
of fault
X
-
Pump
stop
X
-
According
to
seriousness
of fault
According to
seriousness
of fault
X
-
ReportRemarks
X
Actuates anti-freeze
X
resistors
X
Alarm enabled if pump
X
running
X
Fan time delay, stopped 1’
X
X
Self-cancellation with
correct defrosting cycle
According
seriousness
of fault
According to
seriousness
of fault
After-sales department
to
operation to renew
parameters or change
the electronics
X
Ventilation
-
on high speed
5.8 - SPECIAL OPERATING FEATURES
5.8.1 - ANTI-FREEZE PROTECTION OF WATER HEAT EXCHANGER
•2 functions performed:
- control of a heating resistor,
- anti-freeze alarm stopping the machine.
Resistor control
Freeze alarm
• Operating diagram (see opposite).
The setting of these thresholds can be changed in the factory on request to suit the machine’s operating conditions.
5.8.2 - REMOTE CONTROL
• Do not use this contactor for the "Heating/cooling floor" application.
5.8.3 - REMOTE CONTROL
• See details in paragraph 4.2.3.
5.8.4 - POWER CUT
• If the power is cut to the control circuits, the electronic control unit returns to the operating mode it was in before the power was
cut and the parameters are still stored in memory when the power is restored.
5.8.5 - HEAD PRESSURE CONTROL
U
Max. voltage
• The PMERV 5 comes with a factory-installed specific voltage control
board, controlled directly by the µCHILLER electronic control device.
• On the basis of temperature information (taken by the probe S3 located on
the condenser), the control unit varies the fan’s supply voltage according
to the diagram opposite.
• This system is operational in cooling mode.
Min.
voltage
22°C 40°C50°C
8
1
1
2°C1°C0°C3°C 4°C0
Condensing
temperature
0
0
0
Page 9
5.8.6 - DEFROSTING (In heating mode only)
• The control is regulated to operate as follows:
- If the temperature detected by probe S3 is less than -3°C (for at least 10 seconds), the machine starts de-icing (switching
of cooling cycle and stopping of fan) until the temperature read by S3 rises to +7°C. (However, the duration of a de-icing phase
is limited to 10 minutes. If de-icing is stopped by this time delay, alarm "r1" appears on the display).
A period of 40 minutes must pass before a new de-icing phase can start.
For special operating conditions, it may be necessary to change these settings. In this case, contact the after sales service.
NOTE: Message "d1" appears on the display during the defrosting phase.
5.8.7 - CYCLE INVERSION VALVE
• The valve is activated in cooling mode.
6 - STARTING
IMPORTANT NOTE
Before carrying out any work on the machine, make sure that it is switched off and that access to it is prevented.
Any work must be carried out by personnel qualified and authorised to work on this type of machine.
6.1 - CHECK:
• That hydraulic connections are properly tight and that the hydraulic circuit functions correctly:
- purge of circuits,
- position of valves,
- hydraulic pressure.
• That there are no leaks.
• That the machine is stable.
• That the power cables are well fixed to their connection terminals. Terminals that are poorly tightened may cause overheating
and malfunctions.
• That the electric cables are well insulated from any sections of sheet metal or metal parts which could damage them.
• That probe, control and power cables are properly separated.
• That the machine is earthed.
•That there are neither tools nor other foreign objects in the units.
6.2 - STARTING-UP THE UNIT
• Turn the water on.
• Power up the unit.
• Start the appliance (see previous paragraph).
6.3 - CHECKS TO BE MADE
• Water flow-rate.
- Note: The PMERV water output must be permanent (particular attention should be paid in the case of control of the terminal
units on 2-way valve).
• Hydraulic circuit pressures.
• Cooling circuit pressures.
• Control system operation.
IMPORTANT:
• If antifreeze is added (monopropylene glycol), a minium rate of 15% to 20% is needed to avoid any risk of corrosion.
• The LP controller (standard, factory installed) cuts off at 0.5 bar (automatic reset).
• The HP controller (accessory, not factory installed) cuts off at 29 bar (manual reset).
9
Page 10
7 - MAINTENANCE INSTRUCTIONS
GENERAL MAINTENANCE:
All equipment must be properly maintained in order to provide optimum performance over time. Faulty maintenance can result in the
cancellation of the product guaranty. Depending on the products, maintenance operations consist in the cleaning of filters (air, water),
internal and external exchangers, casings, and the cleaning and protection of condensate tanks. Treating odours and the disinfection
of room surfaces and volumes also contributes to the cleanliness of the air breathed by users.
TECHNIBEL proposes a wide range of perfectly adapted professional cleaning, maintenance and repair products for complete and
efficient maintenance. For an optimum result, TECHNIBEL air-conditioners must be maintained with TECHNIBEL maintenance
products.
IMPORTANT NOTE
• Before carrying out any work on the machine, make sure that it is switched off and that access to it is prevented.
• Any work must be carried out by personnel qualified and authorised to work on this type of machine.
• Prior to all maintenance and servicing on the refrigerating circuit, one must first shut down the unit then wait a few
minutes before installing temperature or pressure sensors. Certain equipment, such as the compressor and piping,
may reach temperatures above 100
• Carry out the following operations at least once a year (the frequency depends on the installation and operating conditions):
- Check for leaks on the refrigerating circuit.
- Check for traces of corrosion or oil stains around the refrigerating components.
- Inspect the composition and the condition of the coolant and check that it does not contain traces of refrigerating fluid.
- Cleaning the exchangers.
- Checking the wear parts.
- Checking the operating instructions and points.
- Check the safety devices: particularly check that the high and low-pressure controllers are properly connected on the
refrigerating circuit and that they disengage the electrical circuit if triggered.
- De-dusting the electrical equipment cabinet.
- Checking that the electrical connections are secure.
- Checking the earth connection.
- Check the hydraulic circuit (clean the filter, water quality, etc…).
°C and high pressures may lead to serious burns.
8 - TROUBLESHOOTING
•
All maintenance and servicing operations on the refrigerating circuit must be conducted in accordance with standard trade
practices and safety rules: recovery of the refrigerant, inert shielded (nitrogen) brazing, etc…
• All brazing operations must be conducted by qualified welders.
• For equipment loaded with R 407 C, refer to the specific instructions at the beginning of the installation manual.
• This unit is equipped with pressurized equipment, for example piping.
Use only genuine parts listed in the spare parts list for replacing defective refrigeration components.
• Pipes may only be replaced by copper tubing in compliance with standard NF EN 12735-1.
• Leak detection, in the case of pressure testing:
- Never use oxygen or dry air, as the risk of fire or explosion is present.
- Use dehydrated nitrogen or a nitrogen and refrigerant mix indicated on the manufacturer's plate.
- The test pressure, low and high pressure, must not exceed 20 bar and 15 bar in the case where the unit is equipped with
the pressure gauge option.
• For high pressure circuit pipes made with copper tubing having a Ø = or > 1"5/8, the supplier will be requested to submit a
certificate § 2.1 in accordance with standard NF EN 10204, which will be filed in the installation's technical file.
• All part replacement with other than genuine parts, all modifications of the refrigerating circuit, all replacement of refrigerant
by a fluid other than that indicated on the manufacturer's plate, all use of the unit outside the application limits defined in the
documentation, shall result in the cancellation of PED CE marking compliance which shall fall under the liability of the
individual who carried out these modifications.
• The technical information, relative to the safety requirements of the various applicable directives, is indicated on the
manufacturer's plate of the unit and mentioned on the 1st page of this manual.
After any operation on the refrigerating circuit, you must fit a filter dryer: type 53 S.
10
Page 11
M
L
K
J
I
H
G
F
E
D
C
B
A
1234567891011121314151617181920
1 2
3 4
5 6
21 22
(01-18)
(01-18)
(01-18)
(01-13)
(01-12)
1
LOAD
+
-
1
(01-12)
RSC
XB/6
XA
U
XA
N
XA
PE
XB/10
XA
02
XA
01
XB/13
SD1
XB/8
XA
04
XA
03
XB/12
J1
XB/1
XB/11
F1
2A
E3
E2
BPHP
XB/2
XB/7
XB/9
T1
230V
24V
XB/14
XB/3
XC/8
XA
08
XA
07
XC/6
XA
05
XC/9
XC/12
XA
06
XC/7
XC/2
A1
A2
XC/1
XC/4
KM2
21
22
XA
XA
XA
21
XA
22
M1
A1
LN
C1
XB/5 XB/4
M2
KM2
12345
6
C2
R
L1
(N)
(M)
W
L
G
P
M
W
G
G
B
BW
RL
MR
WM
RW
R
R
L1L1
L1
WG
PG
NM
NL
NB
(B)
R
B
B
SD2
SD3
R1
KM2
EV1
9 - PRESSURE CURVES
461610121481820
17
18
19
20
21
22
25
23
24
45°C
35°C
-55010
10
12
14
16
18
-10
20
22
24
15
45°C
35°C
25°C
9.1 - HEATING MODE
5
Water outlet temperature
4.5
4
3.5
45°C
35°C
25°C
3
2.5
2
Low pressure (relative bar)
1.5
-10
-55010
9.2 - COOLING MODE
6.5
Outdoor temperature
6
5.5
5
4.5
Low pressure (relative bar)
4
3.5
461610121481820
45°C
35°C
HIGH PRESSURELOW PRESSURE
Water outlet temperature
High pressure (relative bar)
15
Outside wet bulb temperature (°C)Outside wet bulb temperature (°C)
HIGH PRESSURELOW PRESSURE
Outdoor temperature
High pressure (relative bar)
Water outlet temperature (°C)Water outlet temperature (°C)