2
SUMMARY
1 - Application - Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2 - Presentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3 - Technical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4 - Physical characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
5 - Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
6 - Heating performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
7 - Cooling performances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
8
- Corrections to be made when using anti-freeze . . . . . . . . . . . . . .9
9 - Curves of available pressures . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
10 - Sound levels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
11 - Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
12 - "ECH" electronic control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
MARKING
This product marked conforms to the essential requirements of the Directives:
- Low voltage no. 2006/95/EC.
- Electromagnetic Compatibility no. 89/336 EEC, modified 92/31 and 93/68 EEC.
1 - APPLICATION - USE
•
Chilled water or hot water generator for air conditioning or heating of rooms for
terminal unit and boiler overhaul
applications.
NOTE : The electronic control parameterization is factory-set for terminal unit and boiler overhaul applications.
R 410 A
• R 410 A is a high-pressure refrigerant (+ 50% in relation to
R 22 and R 407 C).
• The compressors approved for operation with this fluid are
filled beforehand with polyalcohol oil.
Contrary to mineral oil, it is very hygroscopic: it absorbs the
humidity of the ambient air very quickly. This can modify its
lubricant properties and lead in time to the destruction of the
compressor.
MAINTENANCE INSTRUCTIONS
1
-
Never add oil to the appliance; the compressor is filled
with polyalcohol oil, a special oil which cannot tolerate the
presence of other oils.
2 -
The instruments used for:
-
filling,
- pressure measurements,
- emptying under vacuum,
- recovering the fluid,
must be compatible and only used for the R 410 A fluid.
Note: the pressure taps of the refrigerating circuit are
5/16 SAE (1/2 - 20 - UNF)
3 - In the case of a new charge:
- the charge
must be undertaken in liquid phase,
- use a balance and a dip pipe type R 410 A cylinder,
- charge the weight of R 410 A as per the value indicated
on the unit’s identification plate (for “split systems”, refer
to the installation instructions as the charge must
consider the length of the connecting lines).
4 - In case of leakage, do not complete the charge: recover
the remaining refrigerant for recycling and perform a total
charge.
Recovery, recycling or the destruction of the fluid must be
done in compliance with the laws in force in the country
concerned.
5 - If the refrigerant circuit is opened, you must:
-
avoid the entry of air into the circuit as much as
possible,
- replace or install a drier,
- perform the “vacuum operation” at a minimum level of
0.3 mbar (static).
APPLIANCES FILLED WITH R 410 A