TEC AP160N Series 1000VA, AP160N Series 2000VA, AP160N Series 3000VA User Manual

USER MANUAL
On-Line UPS
Model AP160N
1000VA/2000VA/3000VA
Uninterruptible Power Supply System
CONTENT
1. Safety and EMC Instructions..............................................................4
1.1 Installation.............................................................................................4
1.1.4 EBM Installation (Optional)................................................................5
1.2 Operation..............................................................................................9
1.3 Maintenance, servicing and faults......................................................10
1.4 Transport.............................................................................................13
1.5 Storage...............................................................................................13
1.6 Standards............................................................................................14
2. Description of Commonly Used Symbols.......................................15
3. Introduction.........................................................................................16
4. Panel Description...............................................................................17
5. Connection and Operation................................................................19
5.1 Inspection:..........................................................................................19
5.2 Connection:.........................................................................................19
5.3 Battery charge:...................................................................................21
5.4 Turn on the UPS:................................................................................21
5.5 Test function:.......................................................................................21
5.6 Turn off the UPS:................................................................................22
5.7 Audible alarm mute function:..............................................................22
5.8 Operation procedure of external battery for long backup time model
(“S” model)................................................................................................22
6. Operating Mode for All Models.........................................................24
6.1 Line mode...........................................................................................24
6.2 Battery mode......................................................................................25
6.3 Bypass mode......................................................................................25
6.4 NO output mode.................................................................................26
6.5 EPO (Emergency Power Off).............................................................26
6.6 ECO mode (Economy mode).............................................................26
6.7 Converter mode..................................................................................27
6.8 Abnormal mode..................................................................................27
7. Setting by LCD Module......................................................................28
8. Trouble Shooting................................................................................30
9. Maintenance........................................................................................32
9.1 Operation............................................................................................32
9.2 Storage...............................................................................................32
9.3 Battery Replace..................................................................................32
10. Technical Data...................................................................................33
10.1 Electrical specifications....................................................................33
10.2 Operating Environment.....................................................................33
10.3 Typical backup time (Typical values at 25°C in minutes:)....................33
10.4 Dimensions and weights....................................................................34
11. Communication Port........................................................................34
11.1 RS-232 and USB communication ports............................................34
11.2 RS-232 port.......................................................................................35
11.3 USB port...........................................................................................35
11.4 Installing a Serial Network Management Card (optional).................35
12. Software.............................................................................................37
Appendix: Rear panel.............................................................................38
4
1. Safety and EMC Instructions
1.1 Installation
See installation instructions before connecting to the supply. Condensation may occur if the UPS is moved directly from a cold to a
warm environment. The UPS must be absolutely dry before being installed. Please allow an acclimatization time of at least two hours.
Do not install the UPS near water or in damp environment. Do not install the UPS where it would be exposed to direct sunlight or
near heat.
Do not connect appliances or items of equipment which would overload
the UPS (e.g. laser printers, etc) to the UPS output.
Place cables in such a way that no one can step on or trip over them. Assure to connect with the earth reliably. Assure external battery source must be earthed. Connect the UPS only to an earthed shockproof socket outlet. The building wiring socket outlet (shockproof socket outlet) must be
easily accessible to close to the UPS.
With the installation of the equipment, the sum of the leakage current of
the UPS and the connected load does not exceed 1,5mA.
Do not block ventilation openings in the UPS’s housing. Ensure the air
vents on the front and rear of the UPS are not blocked. Allow at least 25cm of space on each side.
UPS has provided earthed terminal, in the final installed system
configuration, equipotential earth bonding to the external UPS battery cabinets.
An appropriate disconnect device as short-circuit backup protection
should be provided in the building wiring installation. Please see the disconnect device specification in chapter 5.2.
The equipment is powered by more than one source.
1.1.1 Inspection of Unit
Inspect the UPS upon receiving. If the UPS is apparently damaged during the shipment, please keep the box and packing material in original form for the carrier and notify the carrier and dealer immediately.
Please read carefully the following user manual and the safety instructions before installing the unit or using the unit!
5
1.1.2 Unpacking the Cabinet
To unpack the system:
1. Open the outer carton and remove the accessories packaged with the cabinet.
2. Carefully lift the cabinet out of the outer carton and set it on a flat, stable surface.
3. Discard or recycle the packaging in a responsible manner, or store it for future use.
1.1.3 UPS Setup
All model series are designed for tower and rack purpose. They can be installed into a 19 inches equipment rack. Please follow the instruction for Tower Setup and Rack-Mount Setup.
l Tower setup This series of UPS can be placed horizontally and vertically. As a tower
configuration, it is provided with the optional UPS stands to stabilize the UPS when the UPS is positioned in vertical. The UPS stand must be attached to the bottom of the tower. Use the following procedure to install UPS in UPS stands.
1. Slide down the UPS vertically and put two UPS stands at the end of the
tower.
2. Place down the UPS into two stands carefully.
3. Pull out the LCD box and rotate it in a clockwise direction to 90 degree and
then push it back in the front panel.
5
l Rack-mount setup The series can be installed in 19 inches racks. Both the UPS and external
battery enclosure need 2U of valuable rack space. Use the following procedure to install UPS in a rack.
1. Align the mounting ears with screw holes on the side of the UPS, and tighten the screw.
2. Assemble the rack rails with the rack-mounting.
3. Slide in the UPS into the rack rail and lock it in the rack enclosure.
4. Tighten the screw, and the load can then be connect
1.1.4 EBM Installation (Optional)
l Connecting the EBM in Tower form:
1. Slide down the UPS and EBM vertically and place two UPS stands with the extend part at the end of the tower.
2. Tighten the screw on the metal sheet for stabilization
3. Connect the Earth line from UPS (port A ) to EBM (port B)
4. Take off the front panel, and connect the battery terminal (A) from UPS to EBM terminal (B) shown as below. Users need to remove the small gate(C)
6
on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel.
B
A
C
B
A
7
l Connecting the EBM in a rack form
1. Using the same method as assembling UPS in a rack form, assemble EBM into the rack-mounting on the top or bottom of the UPS.
2. Connect the earth line from UPS (port A ) to EBM (port B )
3. Take off the LCD box, and unscrew the internal screws.
4. Take off the front panel, and connect the battery terminal (A) from UPS to EBM terminal (B) shown as below. Users need to remove the small gate(C) on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel.
5. After installing the UPS into rack, the load can then be connected to UPS. Please make sure the load equipment is turned off before plugging all loads into the output receptacle
l Connecting the Multiple EBMs
1KVA / 2KVA and 3KVA UPS include external battery port that allows users to connect multiple EBM in order to provide additional backup time. Follow the procedure to install multiple EBM as below.
A
B
B
A
C
Unscrew
Unscrew
5
8
Connecting multiple EBMs in Tower form
1. Connect Earth line between UPS and the first EBM, and then connect Earth Line between the first EBM and the second EBM.
2. Take off the front panel, and connect the battery terminal (A) from UPS to EBM terminal (B) shown as below. And then connect the battery terminal (D) from the first EBM to the battery terminal (E) from the second EBM. Users need to remove the small gate(C) on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel.
Connecting the Multiple EBMs in rack form
1. Connect Earth line between UPS and the first EBM, and then connect Earth Line between the first EBM and the second EBM.
2. Take off the front panel, and connect the battery terminal (A) from UPS to EBM terminal (B) shown as below. And then connect the battery terminal (D) from the first EBM to the battery terminal (E) from the second EBM. Users need to remove the small gate(C) on side of the front panel to allow the outlet wire of the EBM to pass through the gate and then reassemble front panel.
B
C
A
D
E
9
Note: Three or more EBMs can be connected to the UPS in the same way as shown above. Note: After connect the EBMs, please do not forget to set the number of EBMs on LCD, please refer to chapter 7 “Setting by LCD module” for setting method. If use the nonstandard EBMs, please call local dealer or distributor for setting
method.
1.2 Operation
Do not disconnect the mains cable on the UPS or the building wiring
socket (grounded shockproof socket) during operation as this would remove the ground to the UPS and of all connected loads.
The UPS features its own, internal current source (batteries). You may be
electric shock when you touch the UPS output sockets or output terminal block even if the UPS is not connected to the building wiring socket.
In order to fully disconnect the UPS, first press the OFF button to turn off
the UPS, then disconnect the mains lead.
Ensure that no liquid or other foreign objects can enter the UPS. Do not remove the enclosure. This system is to be serviced by qualified
service personnel only.
Remove the protective panel only after disconnecting the terminal
connections.
Use No. 12 AWG (for 3K-KS input wire), 90°C copper wire and 4.4 lb-in
E B
C
A
D
10
Torque force when connecting to terminal block.
Use No. 10AWG (for all models battery wire), 90°C copper wire and
Anderson PP45 connectors for user’s external battery cabinet.
1.3 Maintenance, servicing and faults
The UPS operates with hazardous voltages. Repairs may be carried out
only by qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the
mains power supply (building wiring socket), components inside the UPS are still connected to the battery which are potentially dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the
batteries. Verify that no current is present and no hazardous voltage exists in the capacitor or BUS capacitor terminals.
Batteries must be replaced only by qualified personnel. Caution - risk of electric shock. The battery circuit is not isolated from the
input voltage. Hazardous voltages may occur between the battery terminals and the ground. Verify that no voltage is present before servicing!
Batteries have a high short-circuit current and pose a risk of shock. Take
all precautionary measures specified below and any other measures necessary when working with batteries:
★ - remove all jewellery, wristwatches, rings and other metal objects ★ - use only tools with insulated grips and handles. When changing batteries, replace with the same quantity and the same
type of batteries.
Do not attempt to dispose of batteries by burning them. It could cause
explosion.
Do not open or destroy batteries. Effluent electrolyte can cause injury to
the skin and eyes. It may be toxic.
Please replace the fuse only by a fuse of the same type and of the same
amperage in order to avoid fire hazards.
Do not dismantle the UPS, except the qualified maintenance personnel.
1.3.1 UPS and Battery Care
For the best preventive maintenance, keep the area around the UPS clean and dust-free. If the atmosphere is very dusty, clean the outside of the system
11
with a vacuum cleaner. For long battery life, keep the UPS at an ambient temperature of 25°C (77°F)
1.3.2 Storing the UPS and Batteries
When the UPS is intended to store for a long period, recharge the battery every 6 months by connecting the UPS to utility power. The batteries charge to 90% capacity in approximately 4 hours. However, it is recommended that the batteries charge for 48 hours after long-term storage.
1.3.3 Time to Replace Batteries
When the discharging time is less than 50% of specified after full charged, the battery may need to be replaced. Please check the battery connection or contact your local dealer to order new battery.
WARNING:
l Turn off the UPS and disconnect the utility power cord from the wall outlet. l Servicing should be performed by qualified service personnel
knowledgeable of batteries and required precautions. Keep unauthorized personnel away from batteries
l Batteries can present a risk of electrical shock or burn from high short
circuit current. The following precautions should be observed:
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
3. Do not lay tools or metal parts on top of batteries.
4. Wear rubber gloves and boots.
5. Disconnect the charging source prior to connecting or disconnecting battery terminal.
l When replacing batteries, replace with the same type and number of
batteries or battery packs. Contact your service representative to order new batteries.
l Do not dispose of battery in a fire. Batteries may explode when exposed to
flame.
l Proper disposal of batteries is required. Refer to your local codes for
disposal requirements.
l Do not open or mutilate the battery. Released toxic electrolyte is harmful to
skin and eyes.
12
1.3.4 Replacing UPS Internal Batteries
Follow the steps and Charts as below to replace batteries:
1. Take off the LCD box, and remove the screws.
2. Slide and Pull the front panel leftward and then take it off.
3. Disconnect the cable from the UPS and battery pack.
4. Remove the right inner battery bracket.
5. Pull the battery pack out onto flat area.
6. Install new battery pack into UPS.
7. Screw up the battery bracket and reconnect the battery cable A and B
8. Re-install the front panel back to UPS.
Note: If you are not qualified service personnel to replace the battery, do not attempt to open the battery cabin. Please call local dealer or distributor
immediately.
5
7
13
1.3.5 Testing New Batteries
For a battery test, please check:
l The batteries must be fully charged. l The UPS must be in Normal mode with no active alarms. l Don’t take on/off the load.
To test batteries:
1. Connect the UPS to utility power for at least 48 hours to charge the batteries.
2. Press and hold the “I” button 1 second to start the battery test on line mode or HE mode. The status display string shows “TEST”
1.3.6 Recycling the Used Battery:
To recycle properly the used battery, please do not discard the UPS, battery pack and batteries into the trash bin. Please follow your local laws and regulations; you may contact your local recycling waste management center for further information to dispose properly of the used UPS, battery pack, and batteries.
1.4 Transport
Please transport the UPS only in the original packaging (to protect against
shock and impact).
1.5 Storage
The UPS must be stockpiled in the room where it is ventilated and dry.
Warning:
l Never dispose the batteries in a fire. It may explode. l Do not open or mutilate the batteries. Released electrolyte is harmful
to the skins and eyes. It may be toxic. A battery can present a risk of
electrical shock and high short circuit current.
14
1.6 Standards
* Safety
IEC/EN 62040-1-1
* EMI
Conducted Emission..........................:IEC/EN 62040-2 Category C1
Radiated Emission.............................:IEC/EN 62040-2 Category C1
Harmonic Current...............................:IEC/EN 61000-3-2
Voltage Fluctuation and Flicker..........:IEC/EN 61000-3-3
*EMS
ESD...................................................:IEC/EN 61000-4-2 Level 3
RS.....................................................:IEC/EN 61000-4-3 Level 3
EFT....................................................:IEC/EN 61000-4-4 Level 4
SURGE.............................................:IEC/EN 61000-4-5 Level 4
CS……………………………………...:IEC/EN 61000-4-6 Level 3 MS……………………………………..: IEC/EN 61000-4-8 Level 3 Voltage Dips………………………….: IEC/EN 61000-4-11
Low Frequency Signals.....................:IEC/EN 61000-2-2
15
2. Description of Commonly Used Symbols
Some or all of the following symbols may be used in this manual. It is advisable to familiarize yourself with them and understand their meaning:
16
3. Introduction
This On-Line-Series is an uninterruptible power supply incorporating double-converter technology. It provides perfect protection specifically for Novell, Windows NT and UNIX servers.
The double-converter principle eliminates all mains power disturbances. A rectifier converts the alternating current from the socket outlet to direct current. This direct current charges the batteries and powers the inverter. On the basis of this DC voltage, the inverter generates a sinusoidal AC voltage, which permanently supplies the loads.
Computers and periphery are thus powered entirely by the mains voltage. In the event of power failure, the maintenance-free batteries power the inverter.
This manual covers the UPS listed as follows. Please confirm whether it is the model you intend to purchase by performing a visual inspection of the Model No. on the rear panel of the UPS.
“KS” Model: Extended backup time
Model No. Type Model No. Type
1K 1K-KS 2K 2K-KS 3K
Standard
3K-KS
Extended backup
time
17
4. Panel Description
The Display Panel
Switch Function ON
Button
Turn on UPS system: By pressing the ON-Button “I” the UPS system is turned on. Deactivate acoustic alarm: By pressing this Button an acoustic alarm can be deactivated in the battery mode. By short touch this Button all acoustic alarms can be deactivated in all mode. Do the battery test: By pressing this Button the UPS can do the battery test in the Line mode or ECO mode or Converter mode.
OFF Button
When mains power is normal, the UPS system switches to No output or Bypass mode by pressing OFF-Button “ “, and the inverter is off. At this moment, if Bypass is enabled, then the output sockets are supplied with voltage via the bypass if the mains power is available. Deactivate acoustic alarm: By pressing this Button an acoustic alarm can be deactivated in the bypass mode. Release the UPS from fault mode and EPO status.
Select Button
Enter Button
The output voltage, frequency, Bypass disable/enable and operating mode in No output or Bypass mode, Two Load segments in output mode, Battery string in all mode, could be selected by pressing Select-Button, and confirmed by pressing Enter-Button.
18
The LCD Display
Display Function Display Function
Input Information Output Information
It indicates input
voltage/frequency value, which are displayed alternately.
It indicates output
voltage/frequency value, which are displayed alternately.
It indicates the input is
connected with mains, and the input power is supplied from the mains.
It indicates the Output plug.
It indicates the Number of the
input supplied from the mains.
It indicates the Number of the
output connected with load.
Battery Information Load Information
It indicates the battery capacity. Every grid represents the capacity of 20%.
It indicates the load level. Every grid represents the level of 20%.
Mode/Fault/Warning Information Else
It indicates the UPS is in setting mode.
It Indicates the operating mode or Fault kind or Warning kind, several warning kinds at the same time could be displayed alternately.
It indicates the UPS is in Fault mode or has some warnings.
19
5. Connection and Operation
5.1 Inspection:
Inspect the packaging carton and its contents for damage. Please inform the transport agency immediately should you find signs of damage.
Please keep the packaging in a safe place for future use. Note: Please ensure that the incoming feeder is isolated and secured to
prevent it from being switched back on again.
5.2 Connection:
(1) UPS Input Connection
If the UPS is connected via the power cord, please use a proper socket with protection against electric current, the user can refer to below table. If the UPS is connected via wires, it is recommended to select the 2.5mm2 wire, and the “GND” terminal should be grounded first.
The UPS System has no input breaker on the standard cabinet. When installing the UPS, the user needs to connect the external breakers and protective components in the input terminals. It is recommended to select the NFB(Non-Fuse Breaker) instead of the traditional combination kit including breaker and fuse.
When selecting the NFB, the user can refer to below table.
UPS INPUT NFB & Power Cord & Socket
Model No.
VOLTAGE CURRENT 1K & 1K-KS 300Vac 10A 2K & 1K-KS 300Vac 16A 3K & 1K-KS 300Vac 20A
The system may be installed and wired only by qualified electricians
in accordance with a
pplicable safety regulations!
When installing the electrical wiring, please note the nominal
amperage of your incoming feeder
.
20
(2) UPS Output Connection
The output of the UPS is IEC socket-types. Simply plug the load power cord to the output sockets to complete connection. Use one cord for every 5A load.
Model No. Output Socket (pcs)
1K, 1K-KS, 2K, 2K-KS 8 * IEC320 C13
3K, 3K-KS 8 * IEC320 C13 + 1 * C19
The wiring configuration ( 3K-KS only) is shown as the following procedure:
a) Remove the small cover of the terminal block b) Use 2.5mm2 wires for wiring configuration c) Upon completion of the wiring configuration,
please check whether the wires are securely affixed
d) Put the small cover back to the rear panel
(3) EPO Connection:
The polarity of EPO is NC (Normally closed) as default setting.
Normally the EPO connector is closed with a wire on the rear panel. Once the connector is open, the UPS would stop the output until the EPO status is disabled.
Enable the EPO status Disable the EPO status
( UPS output is OFF ) ( normal status )
Connection diagram
Caution:
Do not connect equipment which would overload the UPS system (e.g. laser printers)
21
5.3 Battery charge:
Fully charge the batteries of the UPS system by leaving the UPS system connected to the mains for 1-2 hours. You may use the UPS system directly without charging it but the stored energy time may be shorter than the nominal value specified.
5.4 Turn on the UPS:
(1) With utility power connecting:
Press “I” button continuously for more than 1 second to turn on the UPS, the UPS will get into the inverter mode, the LCD screen will indicate the state of the UPS.
(2) Without utility power connecting:
If UPS is cold start without utility power connecting, user need to push “I” button twice, first pushing “I” button is for UPS to get power, LCD screen show ‘INIT’. And second pushing “I” button continuously for more than 1 second is for UPS to turns on, the UPS will get into the inverter mode. In fact, the two pushing “I” button is to make further sure user operation for turning on UPS, the LCD screen will indicate the state of the UPS.
Note: The default setting for bypass mode is no output after UPS is connecting utility power and breaker is turned on. This can be configured by monitoring the LCD panel or firmware.
5.5 Test function:
(1)Real time detection
UPS could do real-time detection when battery connected or disconnected. If the battery connection status is changed, in floating mode, UPS will detect the change within 30 seconds; in resting mode, UPS will detect the change within 3 minutes;
(2) Manual test
Test the function of the UPS system by pressing the On-Switch “I” for more than 1 second, the UPS would detect whether the battery is connected or the battery is low immediately. Also the UPS could do the test automatically and periodically, the period time could be set by user, the default value is 7 days.
22
5.6 Turn off the UPS:
(1) In Inverter Mode:
Press “ ” button continuously for more than 1 second to turn off the UPS, the UPS will get into no output or bypass mode. At this time, the UPS might has output if bypass is enabled. Disconnect the utility power to turn off the output.
(2) In Battery Mode:
Press “ ” button continuously for more than 1 second to turn off the UPS, the UPS will be turned off completely.
5.7 Audible alarm mute function:
If the alarm is too annoying in battery mode, you may press “I” button continuously for more than 1 second to clear it. Moreover, the alarm will be enabled when the battery is low to remind you to shutdown the load soon. If the alarm is too annoying in bypass mode, you may press “ “button continuously for more than 1 second to clear it. The action doesn’t affect the warning and fault alarm. If all alarm is too annoying, you can short touch “I” button, all alarms are disable, if alarms need to be resumed, short touch “I” button again.
5.8 Operation procedure of external battery for long backup time model (“S” model)
(1) Use the battery pack with voltage: 36VDC for 1KVA (12V×3 batteries),
48VDC for 2KVA 2V×4 batteries), 72VDC for 3KVA 2V×6 batteries). Connection of batteries more than or less than required will cause abnormality or permanent damage.
(2) One hard wiring type battery terminal on the rear panel is used for
connecting the battery pack.
(3) The battery connection procedure is very important. Any incompliance
may result in the risk of electric shock. Therefore, the following steps must be strictly complied with.
(4) Make sure the mains input is cut off, if there is a battery breaker then turn
it off first.
(5) Remove front panel, connect the battery via Anderson PP45 connectors.
Prepare the battery cable which should be able to carry the current of >50A for all models, the cross section area should be great than 4 mm2 for
23
all model. And battery wire color is recommended as following:
GND
Red wire Green/Yellow wire Black wire
(6) The red wire is connected to the "+" terminal of the battery. The black wire
is connected to the "-" terminal of the battery. (Note: the green/yellow wire is grounded for protection purpose.)
(7) Make sure the wires are fasten, install the terminal block cover on the rear
panel of the UPS.
(8) Connect the UPS to the load. Then, turn on the mains switch or connect
the power cord of the UPS to utility power supply, the battery would start to be charged.
Caution:
A DC breaker must be connected between the UPS and external battery.
Caution:
The output sockets of the UPS system may still be electrically live even if the power supply system has been disconnected or the Bypass switch is on “OFF” position.
24
6. Operating Mode for All Models
The different string could be displayed on the LCD screen corresponding to their own operating modes, and they are illustrated as the following table. At any time, only one normal operating string or fault string is presented. But the warning, even several warnings could appear in a certain normal operating mode at one time. And the normal operating mode string and the warning string would be shown circularly. Once one fault is come forth, then all previous warnings would not be shown again but only the fault string is presented.
Normal operating mode Code
No output mode STbY Bypass mode bYPA Line mode LINE Battery mode bATT
Battery test mode TEST ECO mode ECO Converter mode CVCF
6.1 Line mode
The LCD display in Line mode is shown in the following diagram. The information about the utility power, the battery level, the UPS output and the load level could be displayed. The “LINE” string indicates the UPS is working in Line mode.
The Line mode
If output overloaded, alarm will keep twice every second. You should get rid of some unnecessary loads one by one to decrease the loads connected to the UPS less than 90% of its nominal power capacity.
25
Note: Please follow the following steps to connect the generator l Activate the generator and wait until the operation is stable before
supplying power of the generator to the UPS (be sure that the UPS is in idle mode). Then turn on the UPS according to the start-up procedure. After the UPS is turned on, then the loads can be connected to the UPS one by one.
l The power capacity of the AC generator should be at least twice of the
UPS capacity.
6.2 Battery mode
The LCD display in battery mode is shown in the following diagram. The information about the utility power, the battery level, the UPS output and the load level could be displayed. The “bATT” string indicates the UPS is working in the battery mode. When the UPS is running in battery mode, the buzzer beeps once every 4 seconds. If the “ON” button on the front panel is pressed for more than 1 second again, the buzzer will stop beeping (in silence mode). Press the “ON” button once again for more than 1 second to resume the alarm function.
The Battery mode
6.3 Bypass mode
The LCD display in bypass mode is shown in the following diagram. The information about the utility power, the battery level, the UPS output and the load level could be displayed. The UPS will beep once every 2 minutes in bypass mode. The “bYPA” string indicate the UPS is working in the bypass mode.
The Bypass mode
26
The UPS does not have the backup function when it is in bypass mode. The power used by the load is supplied from the utility power via internal filter.
6.4 NO output mode
The LCD display in No output mode is shown in the following diagram. The information about the utility power, the battery level, the UPS output and the load level could be displayed. The “STbY” string indicates the UPS is working in the No output mode.
The No output mode
6.5 EPO (Emergency Power Off)
It is also called RPO (Remote Power Off). On LCD display, the mode string is “EPO”. It is a special status in which the UPS would shut the output off and alarm. The UPS could not be turned off by pressing “OFF” button on the panel, only after releasing EPO status by turning off the EPO switch.
6.6 ECO mode (Economy mode)
It is also called high efficiency mode. In ECO mode, on LCD display, the mode sting is “ECO”. After the UPS is turned on, the power used by the load is supplied from the utility power via internal filter while the utility power is in normal range, so the high efficiency could be gained in the ECO mode. Once the mains is loss or abnormal, the UPS would transfer to battery mode and the load is supplied continuously by the battery.
1) It could be enabled through the LCD setting or the software (Winpower,
etc.).
2) It is attention that the transfer time of UPS output from ECO mode to
battery mode is less than 10ms. But it is still too long for some sensitive load.
27
6.7 Converter mode
In converter mode, on LCD display, the mode string is “CVCF”. The UPS would free run with fixed output frequency (50Hz or 60Hz) in converter mode. Once the mains is loss or abnormal, the UPS would transfer to battery mode and the load is supplied continuously by the battery.
1) It could be enabled through the LCD setting or the software (Winpower, etc.).
2) The load should be derating to 70% in converter mode.
6.8 Abnormal mode
In abnormal mode such as Bus fault etc., the corresponding fault string would be shown to indicate the operating mode of the UPS, and the background light become red. For example “SHOR” would be shown when the load or the UPS output is short. The LCD display is shown in the following diagram.
28
7. Setting by LCD Module
The output voltage, frequency, Bypass status and operating mode in No output mode or Bypass mode, Two Load segments in output mode, Battery string in all mode could be set directly through LCD module. The output voltage could be set to 208V, 220V, 230V and 240V. The output frequency could be set to 50Hz and 60Hz. The bypass state could be set to enable and disable. The operating mode of UPS could be set between the Line mode, ECO mode and Converter mode. Battery string could be set to one to night groups. Two Load segments could be set to on and off.
In bypass or no output mode, pressing the “Enter” button on the LCD panel for more than one second to enter setting mode. The LCD display is shown in the following diagram. The string “OPV” indicates that the current setting is output voltage. “230Vac” indicates the current default output voltage is 230Vac. if you want to set output voltage, press the “Enter” button for more than one second, a flickering string “208” would be shown, if the “Enter” button is pressed again, the string “208” turn to flickerless, the output volt is changed to 208V; if the “Select” button is pressed for more than one second, the next flickering string “220” appear, the order of flickering string is 208 – 220 – 230 – 240 – 208, Press “Enter” button to confirm the output volt what you want.
Exit the setting mode to short touch the “Enter” button; continue setting to press “Select” button. if no any pressing on the “Select” or “Enter” button lasting for more than 10 seconds, the setting mode exit automatically. The output frequency string “OPF”, Bypass status string ” bYPA”, operating mode string “MOdE”, Battery string “bSTR”, Load segment string “LS1” and “LS2” would be presented circularly. The only one voltage value could be selected in “208V”, “220V”, “230V”, “240V” at any time; The only one frequency value could be selected in “50Hz”, “60Hz” at any time; Bypass status could be selected in “000” or “001”(Here 000 means Bypass Disable,001 means Bypass Enable),The UPS would turn to bypass mode in
29
several seconds after “Bypass Enable” is selected, and turn to no output mode in several seconds after “Bypass Disable” is selected; Operating mode could be selected in “UPS”, “ECO”, “CVF”(Here “UPS” means the normal inverter mode, “ECO” means the high efficiency mode, and “CVF” means the converter mode), The mode change would be active only after the UPS is turned on; Battery string could be selected in “001” to “009”(Here “001” means one group battery). Load segment 1 could be selected in “000” or “001”(Here 000 means load segment 1 off, 001 means load segment 1 on); Load segment 2 is the same as Load segment 1.
Here is a example for changing the Operating mode from normal mode to
converter mode through the LCD panel.
Step 1: “OPV” after pressing the “Enter” button; Step 2: “OPF” after pressing the “Select” button.
Step 3: “bYPA” after pressing the “Select” button; Step 4: “MOdE” after pressing the “Select” button,
press the “Enter” button to set mode, then “UPS” flickering;
Step 5: “ECO” flickering after pressing the “Select” button; Step 6: “CVF” flickering after pressing the
“Select” button again. Press the “Enter” button to make sure to change the mode. Short touch “Enter” button to exit setting mode.
30
8. Trouble Shooting
If the UPS system does not operate correctly, check the operating status on the LCD display.
Warning String Fault String
Site fail SITE Inverter short SHOR Fan fail FANF Overload fault OVLD Battery over voltage (over charged) HIGH Inverter soft start fail ISFT Battery low bLOW Bus soft start fail bSFT Charge fail CHGF Over temperature fault OVTP Inverter temperature high TEPH Inverter Volt Low INVL Ambient temperature high AMbH Inverter Volt High INVH Battery open bOPN Bus volt over bUSH Overload OVLD Bus volt Low bUSL EPO EPO Bus Unbalance bUSE Inverter NTC open NTCO
If the UPS system does not operate correctly, please attempt to solve the problem using the table below.
Problem Pzle cause Remedy
No indication, no warning tone even though system is connected to mains power supply
No input voltage Check building wiring socket outlet
and input cable.
Display Mode string ”STbY” in LCD, even though the power supply is available
Inverter not switched on Press On-Switch “I”.
Display Mode string ”bATT” in LCD, and audible alarm sounding every 1 beep in every 4 seconds
Mains power supply has failed, or Input power and/or frequency are out of tolerance
Switching to battery mode automatically. Check input power source and inform dealer if necessary.
Emergency supply period shorter than nominal value
Batteries not fully charged / batteries defect
Charge the batteries for at least 5 - 8 hours and then check capacity. If the problem still persists, consult
your dealer. Fan fail Fan abnormal Check if the fan is running Battery over voltage Battery is over charged Stop charging to battery
automatically, and after the battery
voltage is normal and the mains is
normal, charge automatically again. Battery low Battery voltage is low When audible alarm sounding every
second, battery is almost empty.
31
Charge fail The charge is broken Notify dealer. Inverter temperature high Inside temperature of the UPS
is too high
Check the ventilation of the UPS, check the ambient temperature.
Ambient temperature high The ambient temperature is
too high
Check the environment ventilation.
Battery open Battery pack is not connected
correctly
Check the battery bank is connected to the UPS. Check the battery breaker is turn on.
Overload Overload Check the loads and remove some
non-critical loads. Check whether some loads are failed.
Site fail Phase and neutral conductor
at input of UPS system are reversed
Rotate mains power socket by 180° or connect UPS system.
EPO active EPO function is enabled Turn off the EPO switch. Bus fault(Low/high/ Unbalance/soft start)
UPS internal fault Notify dealer
Inverter fault(Low/high/soft start)
UPS internal fault Notify dealer
Over temperature fault Over temperature Check the ventilation of the UPS,
check the ambient temperature and ventilation.
Inverter short Output short circuit Remove all the loads. Turn off the
UPS. Check whether the output of UPS and loads is short circuit. Make sure the short circuit is removed, and the UPS has no internal faults before turning on again.
Please have the following information at hand before calling the After-Sales
Service Department:
1. Model number, serial number
2. Date on which the problem occurred
3. LCD display status, Buzzer alarm status
4. Utility power condition, load type and capacity, environment temperature, ventilation condition
5. The information (battery capacity, quantity) of external battery pack if the UPS is “S” model
6. Other information for complete description of the problem
32
9. Maintenance
9.1 Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case please contact your dealer.
9.2 Storage
If the batteries are stored in temperate climatic zones, they should be charged every three months for 1~2 hours. You should shorten the charging intervals to two months at locations subject to high temperatures.
9.3 Battery Replace
If the battery service life has been exceeded, the batteries must be replaced.
Battery replacement should be performed only by qualified personnel.
It recommends to shut off the UPS completely before the replacement. If there is a battery breaker then turn it off first. Disconnect the battery cable carefully and make sure no any exposed wires can be touched. Reconnect the new batteries to the UPS by following section 5.8. Then turn on the battery breaker and start the UPS. If it needs to replace the batteries while the UPS is running, make sure the UPS would not shut down during the replacement. If there is a battery breaker then turn it off first. Disconnect the battery cable carefully and make sure no any exposed wires can be touched. Reconnect the new batteries to the UPS by following section 5.8. Then turn on the battery breaker and press the ON switch to make the UPS do the battery test, check whether the battery information is normal.
33
10. Technical Data
10.1 Electrical specifications
INPUT
Model No. 1K & 1K-KS 2K & 2K-KS 3K & 3K-KS
Phase 1
Frequency (45~55)/(54~66) Hz
Max Current(A) 7.5 13.5 20
OUTPUT
Model No. 1K& 1K-KS 2K& 2K-KS 3K & 3K-KS
Power rating 1KVA/0.9KW 2KVA/1.8KW 3KVA/2.7KW
Voltage 208/220/230/240×1 1%VAC
Frequency 50/60±0.2Hz (Battery mode)
Wave form sinusoidal
BATTERIES
Model No. 1K 2K 3K
Number and type 3×12V 7Ah 4×12V 9Ah 6×12V 9Ah
10.2 Operating Environment
Ambient Temperature 0 oC to 40 oC
Operating humidity < 95%
Altitude < 1000m
Storage temperature 0 oC to 45 oC
10.3 Typical backup time (Typical values at 25°C in minutes:)
Model No. 100 % Load 50 % Load
1K 5 15 2K 3 10 3K 3 10
34
10.4 Dimensions and weights
Model 1K 1K-KS 2K 2K-KS 3K 3K-KS
Net weight (kg) 16,2 8,4 19,7 9,3 28,6 13,2
UPS
Cabinet
Dimension (mm)
(W x H x D)
Dimension (mm)
(W x H x D)
438x86,5x436 438x86,5x608
Net weight (kg) 22,2 27,5 40,5
Battery
Cabinet
Type 36V 48V 72V
11. Communication Port
11.1 RS-232 and USB communication ports
To establish communication between the UPS and a computer, connect a computer to one of the UPS communication ports by using an applicable communication cable.
NOTE:
Only one of the communication ports can be active at one time. The USB port has priority over the RS-232 port. When a communication cable is installed, the power management software can exchange data with the UPS. The software polls the UPS for detailed information on the status of the power environment. If a power emergency occurs, the software initiates the saving of all data and an orderly shutdown of the equipment
35
11.2 RS-232 port
The RS-232 port is available for UPS monitoring, control, and firmware updates. To establish communication between the UPS and a computer, connect one end of the serial communication cable that comes with the UPS to the RS-232 port on the UPS. Connect the other end of the serial cable to the RS-232 port on a computer. The cable pins for the RS-232 communication port are identified in the following illustration. RS-232 communication port pin assignments
Pin Signal name Function
Direction from the UPS
1 Unused Not applicable 2 Tx Transmit to external device Out 3 Rx Receive from external device In 4 Unused Not applicable
5 GND
Signal common (tied to chassis)
Not applicable
6 Unused Not applicable 7 Unused Not applicable 8 Unused Not applicable 9 Unused Not applicable
11.3 USB port
The UPS can communicate with a USB-compliant computer by using HID-compatible power management software. To establish communication between the UPS and a computer, connect the USB cable that comes with the UPS to the USB port on the UPS. Connect the other end of the USB cable to the USB port on a computer.
11.4 Installing a Serial Network Management Card (optional)
Each UPS has one available communication bay, which supports the optional Serial Network Management Card. After you install a Serial Network Management Card, you can connect an environmental monitoring probe to the UPS.
36
Note: You do not have to shut down the UPS before you install a communication card.
To install the Network Management Card, complete the following steps:
1. Locate the UPS communication bay.
2. Remove the two screws that secure the communication bay cover to the UPS and save the screws.
3. Insert the Serial Network Management Card into the slot on the UPS.
4. Secure the Serial Network Management Card to the UPS with both screws.
For more information about the Serial Network Management Card, see the Serial Network Management Card User's Guide.
37
12. Software
Free Software Download – WinPower
WinPower is a brand new UPS monitoring software, which provides user-friendly interface to monitor and control your UPS. This unique software provides safely auto shutdown for multi-computer systems while power failure. With this software, users can monitor and control any UPS on the same LAN no matter how far from the UPSs.
Installation procedure:
1. Go to the website: http://www.ups-software-download.com/winpower.htm
2. Choose the operation system you need and follow the instruction described on the website to download the software.
3. When downloading all required files from the internet, enter the serial No: 511C1-01220-0100-478DF2A to install the software.
When your computer restarts, the WinPower software will appear as a green plug icon located in the system tray, near the clock.
38
Appendix: Rear panel
The UPS rear panel description table and pictures are shown as below:
1K, 2K Standard & 1K-KS
rear panel
2K-KS rear panel
No. Function(1KVA – 2KVA – 3KVA)
1 AC Output 2 EPO / Dry input Communication Port 3 USB Port 4 AC Input 5 Dry out 6 SNMP slot 7 RS232 8 Modem/Network Surge Protection 9 Earth Line connection
39
1
1
3K Standard model rear panel
3K-KS model rear panel
The EBM rear panel description table and picture are shown as below:
36V &48V&72V EBM rear panel
614-03804-00
No. Function(36V & 48V & 72V EBM)
1 Earth Line Port
Loading...