Tait TBA9B1, TBA7C0, TBA9C0, TBA9H0, TBA7B1 Users Manual

...
5 Installation
This chapter describes how to install the TB8100 BSS in a standard 19 inch rack or cabinet. It also provides some general information on safety precautions and site requirements. We recommend that you read the entire chapter before beginning the installation.
5.1 Personal Safety
Warning!! The PMU contains voltages that may be lethal.
The TB8100 BSS must be installed so that the rear of the PMU is located in a service access area.
Refer to the ratings label on the rear of the module.
Disconnect the mains IEC connector and wait for five minutes for the internal voltages to self-discharge before dismantling. The AC power on/off switch does not isolate the PMU from the mains. It breaks only the phase circuit, not the neutral.
The PMU should be serviced only by qualified technicians. All servicing should be carried out only when the PMU is powered through a mains isolating transformer of sufficient rating. We strongly recommend that the mains power to the whole of the repair and test area is supplied via an earth leakage circuit breaker.
Explosive Environments
Warning!! Do not operate TB8100 BSS equipment near
Proximity to RF Transmissions
electrical blasting caps or in an explosive atmos­phere. Operating the equipment in these envi­ronments is a definite safety hazard.
Do not operate the transmitter when someone is standing within 90cm (3ft) of the antenna. Do not operate the transmitter unless you have checked that all RF connectors are secure.
TB8100 Installation and Operation Manual Installation 59 © Tait Electronics Ltd March 2004
High Temperatures
Take care when handling a PMU or PA which has been operating recently. Under extreme operating conditions (+60°C [+140°F] ambient air temperature) or high duty cycles the external surfaces of the PMU and PA can reach temperatures of up to +80°C (+176° F).
5.2 Equipment Safety
ESD Precautions
Important This equipment contains devices which are susceptible to
damage from static charges. You must handle these devices carefully and according to the procedures described in the manufacturers’ data books.
We recommend you purchase an antistatic bench kit from a reputable manufacturer and install and test it according to the manufacturer’s instructions. Figure 5.1 shows a typical antistatic bench set-up.
Aerial Load
You can obtain further information on antistatic precautions and the dangers of electrostatic discharge (ESD) from standards such as ANSI/ESD S20.20-1999 or BS EN 100015-4 1994.
Figure 5.1 Typical Antistatic Bench Set-up
conductive wrist strap dissipative rubber
bench mat
common point ground (building ground or mains ground via 1M ohm series resistor)
The TB8100 BSS equipment has been designed to operate safely under a wide range of aerial loading conditions. However, we strongly recommend that the transmitter should always be operated with a suitable load to prevent damage to the transmitter output power stage.
60 Installation TB8100 Installation and Operation Manual
© Tait Electronics Ltd March 2004
Equipment Grounding
To ensure safe operation the TB8100 BSS equipment must be correctly grounded as described in these installation instructions.
Installation and Servicing Personnel
The TB8100 BSS should be installed and serviced only by qualified personnel.
5.3 Regulatory Information
Distress Frequencies
The 406 to 406.1MHz frequency range is reserved worldwide for use by Distress Beacons. Do not program transmitters to operate in this frequency range.
FCC Compliance
This device complies with part 15 of the FCC Rules. Operation is subject to the condition that this device does not cause harmful interference.
Unauthorised Modifications
Any modifications you make to this equipment which are not authorised by Tait Electronics Ltd may invalidate your compliance authority’s approval to operate the equipment.
5.4 Environmental Conditions
Operating Temperature Range
The operating temperature range of the TB8100 BSS is –30°C to + 60°C (–22°F to +140°F) ambient temperature. Ambient temperature is defined as the temperature of the air at the intake to the cooling fans.
Humidity
The humidity should not exceed 95% relative humidity through the specified operating temperature range.
TB8100 Installation and Operation Manual Installation 61 © Tait Electronics Ltd March 2004
Dust and Dirt
For uncontrolled environments, the level of airborne particulates must not exceed 100µg/m
3
.
5.5 Grounding and Lightning Protection
Electrical Ground
The TB8100 BSS modules are grounded by physical contact between the module case and the subrack. To ensure a good ground connection you must tighten each module retaining clamp securely (refer to “Final
Reassembly” on page 81 for the correct torque setting).
A threaded grounding connector is provided on the rear of the subrack for connection to the site ground point (refer to “Connection” on page 83 for more details).
Lightning Ground
It is extremely important for the security of the site and its equipment that you take adequate precautions against lightning strike. While it is outside the scope of this manual to provide comprehensive information on this subject, the following guidelines apply:
install a suitable lightning rod at the top of the tower and connect it to a
secure ground point with appropriate conductors and connectors
position site buildings and equipment within the cone of protection
provided by the grounded tower
protect all cables entering the site to prevent lightning energy from
entering site buildings.
5.6 Recommended Tools
It is beyond the scope of this manual to list every tool that an installation technician should carry. However, the following tools are specifically required for installing the TB8100 BSS:
Pozidriv PZ3 screwdriver for the M6 screws used to secure the subrack
to the rack or cabinet, and also for the DC input terminals on the PMU
Pozidriv PZ2 screwdriver for the M4 screws used to secure the module
retaining clamps
0.25in or 6mm flat blade screwdriver for the fasteners used to secure the
front panel to the subrack
8mm AF spanner for the SMA connectors.
62 Installation TB8100 Installation and Operation Manual
© Tait Electronics Ltd March 2004
You can also obtain the TBA0ST2 tool kit from your nearest Tait Dealer or Customer Service Organisation. It contains the basic tools needed to install, tune and service the TB8100 BSS.
5.7 Ventilation
Always ensure there is adequate ventilation around the TB8100 BSS. Do not operate it in a sealed cabinet. You must keep the ambient temperature
within the specified range, and we strongly recommended that you ensure that the cooling airflow is not restricted.
Important The cooling fans are mounted on the front panel and will
only operate when the panel is fitted correctly to the front of the subrack. To ensure adequate airflow through the BSS, do not operate it for more than a few minutes with the front panel removed (e.g. for servicing purposes).
Ambient Air Temperature Sensor
The ambient air temperature reading for the TB8100 BSS is provided by the ambient air temperature sensor PCB
b fitted to the PA control PCB.
The sensor PCB is inserted through slots in the control PCB and heatsink to be positioned between the heatsink fins.
b
Important If the sensor PCB is to provide accurate ambient tempera-
ture readings, it must have forced airflow and must not come into contact with the metal of the heatsink fins. Do not stack PAs with the fins together. It is possible for the fins on one heatsink to slide between the fins on the other heatsink. This can damage the sensor PCB, and pos­sibly result in the heatsink fins becoming locked together.
TB8100 Installation and Operation Manual Installation 63 © Tait Electronics Ltd March 2004
Cabinet and Rack Ventilation
Refer to Figure 5.2 on page 65.
The cooling airflow for the TB8100 BSS enters through the front panel and exits at the rear of the subrack. For optimum thermal performance, the heated air that has passed through a BSS must not be allowed to re-enter the air intakes on the front panel. Any space at the front of the cabinet not occupied by equipment should be covered by a blanking panel.
To allow enough cooling airflow through a cabinet-mounted BSS, we recommend the following:
an area of at least 150cm
in front of the air intakes for the fans for each subrack; for example, thirty 6x85 mm (0.25 x 3.3 in) slots will allow the recommended airflow
a vent in the top of the cabinet with an area of approximately 150cm
(23in2) per subrack, or a similar area of ventilation per subrack at the rear of the cabinet behind each subrack
a 2U gap at the top of the cabinet.
Note The ventilation opening must be unrestricted. If the slots or holes
are covered with a filter, mesh or grille, the open area must be increased to allow the same airflow as an unrestricted opening.
2
(23in2) of unrestricted ventilation slots or holes
2
Auxiliary Extractor Fans
The maximum ambient temperature entering the cabinet must not exceed +60°C (+140°F).
If the TB8100 BSS is installed in a rack or cabinet with other equipment with different ventilation requirements, we recommend that the TB8100 be positioned below this equipment.
The TB8100 BSS does not require auxiliary extractor fans mounted in the top of the cabinet. If your cabinet is already fitted with fans, the following procedures apply:
if there are six or more 120mm (4.75in) fans, each capable of extracting
if there are fewer than six fans, you must remove them and ensure the
3
160m
per hour (94.2CFM), they must run continuously
vent in the top of the cabinet has an area of approximately 150cm
2
(23in2) per subrack.
If you have any other configuration, the performance of your system will depend on how closely you comply with the TB8100 BSS airflow requirements described above.
64 Installation TB8100 Installation and Operation Manual
© Tait Electronics Ltd March 2004
Figure 5.2 Typical Cabinet Ventilation Requirements
b
20cm (8in)
top view
side view
t17.5cm (t7in)
front view
2U
c
c
e
d
c
c
ventilation slots
b
blanking panels
c
TB8100 Installation and Operation Manual Installation 65 © Tait Electronics Ltd March 2004
airflow entry
d
airflow exit
e
5.8 Installing the Base Station System
Caution A TB8100 subrack complete with modules can
weigh up to 28 kg (62lb), or up to 30 kg (66 lb) com­plete with packaging. We recommend that, once the equipment is out of the carton, you remove the modules from the subrack before moving the equip­ment again. Otherwise, have another person help you with the lifting. In all cases follow safe lifting practices.
Unpacking the Equipment
Unpacking the TB8100 BSS
Figure 5.3 Unpacking the TB8100 BSS
The TB8100 BSS is packed in a strong corrugated cardboard carton with top and bottom foam cushions. To prevent personal injury and damage to the equipment, we recommend that two people unpack the BSS.
b
e
cd
f
g
1. Cut the tape securing the flaps at the top of the carton and fold them flat against the sides
2. Rotate the carton carefully onto its side ensuring that none of the flaps is trapped underneath.
66 Installation TB8100 Installation and Operation Manual
b.
hi
c and then onto its top d,
© Tait Electronics Ltd March 2004
3. Slide the carton upwards over the foam cushions and lift it away e.
Remove the cushion from the bottom of the BSS
f.
4. Rotate the BSS and cushion carefully over the rear of the BSS
Disposal of Packaging
If you do not need to keep the packaging, we recommend that you recycle it according to your local recycling methods. The foam cushions are CFC­and HCFC-free and may be burnt in a suitable waste-to-energy combustion facility, or compacted in landfill.
Mounting the Subrack
Caution We recommend that you remove the modules from
Figure 5.4 Subrack Mounting Points
that the BSS is the right way up with the cushion on top the cushion from the top of the BSS
the subrack before lifting it (refer to “Replacing
Modules” on page 71), or have another person help
you with the lifting.
i.
g so
h. Remove
front view
b
rear view
c
main mounting holes - front
b
TB8100 Installation and Operation Manual Installation 67 © Tait Electronics Ltd March 2004
auxiliary mounting holes - rear
c
1. Remove the front panel, as described in “Preliminary Disassembly”
on page 71.
2. Fit the subrack into the cabinet or rack and secure it firmly with an M6 screw, flat and spring washer in each of the four main mounting holes
Note If you need extra mounting security, there are additional mount-
Auxiliary Support Bracket
TBA2140 auxiliary support brackets can be fitted to the rear of the TB8100 subrack to provide additional mounting security. Figure 5.5 below shows a standard TBA2140 bracket If you are not using a Tait cabinet, you may have to make your own brackets to suit your installation.
Figure 5.5 Auxiliary Support Bracket
b, as shown in Figure 5.4 on page 67.
ing holes port brackets.
c provided at the rear of the subrack for auxiliary sup-
b fitted in a typical Tait Electronics cabinet c.
b
c
Important Yo u must fit the auxiliary support brackets if you intend to
transport a cabinet fitted with a fully built-up TB8100 BSS.
We also recommend that you fit the brackets under the following conditions:
when the installation is in an area prone to earthquakes
when third party equipment is installed hard up underneath the TB8100
BSS subrack.
68 Installation TB8100 Installation and Operation Manual
© Tait Electronics Ltd March 2004
Optional Slide Mounting Rails
You can also use TBA2141 slide mounting rails b when mounting the TB8100 BSS in a cabinet, as shown in Figure 5.6 below. These rails will support the BSS while you slide it into the cabinet.
However, you must still secure the BSS to the cabinet with four M6 screws through the main mounting holes on the front of the subrack, as shown in
Figure 5.4 on page 67.
Figure 5.6 Optional Slide Mounting Rail - Rear View
c
b
Important The slide mounting rails are not suitable for transporting a
cabinet fitted with a fully built-up TB8100 BSS. In this case, you must also fit the TBA2140 auxiliary support brackets to the upper set of rear mounting holes
Cabling
General We recommend that you try to route all cables to and from the TB8100 BSS
along the side of the cabinet so the cooling airflow is not restricted.
DC Power Cabling DC power cables should be well supported so that the terminals on the
PMU and on the ends of the cables do not have to support the full weight of the cables.
c.
TB8100 Installation and Operation Manual Installation 69 © Tait Electronics Ltd March 2004
Figure 5.7 below shows two recommended methods of securing these cables
to prevent straining either set of terminals.
Figure 5.7 DC Power Cabling
secure the cables to the cabinet to support their weight
70 Installation TB8100 Installation and Operation Manual
© Tait Electronics Ltd March 2004
7 Connection
Once the TB8100 BSS hardware is installed, you need to connect the individual modules to each other, and to any ancillary equipment required in your system. This chapter provides information on all the inputs and outputs available on the TB8100 BSS.
7.1 Overview of Inputs and Outputs
This section identifies the main input and output connections for the TB8100 BSS. Figure 7.1 below identifies the connections at the front of a dual base station, and Figure 7.3 on page 85 identifies those at the rear.
Figure 7.2 on page 84 identifies the connections at the front of a single
100W base station. Figure 7.4 on page 85 and identifies the connections on the control panel. Refer to the following sections in this chapter for more details on these connections.
Figure 7.1 Dual 5 or 50W Base Station Inputs and Outputs - Front View
bcd e ghfgh
ddidiefd
28VDC high current output for PA
b
28VDC low current output for reciter
c
system control bus
d
RF input from reciter
e
PA 1 PA 2 reciter 2PMU
28VDC high current input cable from PMU
f
RF output to PA
g
28VDC low current input from PMU
h
DC output (for optional reciter fan only)
i
reciter 1
TB8100 Installation and Operation Manual Connection 83 © Tait Electronics Ltd March 2004
Figure 7.2 Single 100W Base Station Inputs and Outputs - Front View
bc de
hfgfi
PMU
28VDC high current output for PA
b
28VDC low current output for reciter
c
RF output to PA
d
28VDC low current input from PMU
e
PA re citer
system control bus
f
DC output (for optional reciter fan only)
g
28VDC high current input cable from PMU
h
RF input from reciter
i
84 Connection TB8100 Installation and Operation Manual
© Tait Electronics Ltd March 2004
Figure 7.3 Dual 5 or 50W Base Station Inputs and Outputs - Rear View
bc d fe
1)
system interface connector
b
external reference frequency input
c
RF output
d
–VDC input
e
+VDC input
f
bc
higidjj
PA 1PA 2reciter 1reciter 2 PMU
auxiliary 12VDC output
g
AC mains input
h
RF input
i
auxiliary 12VDC input for system interface
j
subrack ground connector
1)
Figure 7.4 Standard Control Panel Inputs and Outputs
c
b
d
DC outputs for fans mounted on front panel;
b
also used for fan rotation detectors (if fitted)
microphone connector
c
TB8100 Installation and Operation Manual Connection 85 © Tait Electronics Ltd March 2004
RS-232 programming port
d
Figure 7.5 Power Save Control Panel Outputs
b
c
DC outputs for fans mounted on front panel;
b
also used for fan rotation detectors (if fitted)
RS-232 programming port
c
7.2 Power Supply Connections
AC Power The TB8100 PMU is designed to accept a mains input of 88 to 264VAC at
45 to 65Hz. We recommend that a standard 3-wire grounded outlet is used to supply the AC power. The socket-outlet must be installed near the equipment and must be easily accessible. This outlet should be connected to an AC power supply capable of providing a maximum of 600W. The requirements of two typical AC supplies are given in the following table.
Nominal Supply Current Requirement
115VAC 8A 10A
230VAC 4A 6A
Your TB8100 BSS should come supplied with a power supply cord to connect the male IEC connector on the PMU to the local AC supply. The pins of the IEC connector on the PMU are identified at right.
Circuit Breaker/Fuse Rating
neutral
ground
rear view
phase
DC Power The TB8100 PMU is designed to accept a DC input of 10.3 to 15.5VDC
with negative or positive ground. There is a minimum DC start-up threshold to prevent damaging a battery which has little capacity left.
You must connect the DC supply from the battery to the PMU via a fuse or DC-rated circuit breaker with a rating of 60A. The DC input leads should be of a suitable gauge to ensure less than 0.2 V drop at maximum load over the required length of lead.
86 Connection TB8100 Installation and Operation Manual
© Tait Electronics Ltd March 2004
Terminate and insulate the DC input leads so they are protected from accidentally shorting to the subrack if the PMU is removed before the leads are disconnected.
Figure 7.6 Recommended DC Power Connection
Circuit Breaker
or Fuse
PMU
Battery
Reciter Auxiliary DC Input
PMU Auxiliary DC Output
The system interface PCB in the reciter has an auxiliary DC input connector. DC from the auxiliary DC output on the PMU (see “PMU
Auxiliary DC Output” below) can be supplied to the +AUX_V pin on the
system interface connector via this input.
The pin allocations for the auxiliary DC input on the system interface PCB are given in the following table. Note that pins 1 & 3 and pins 2 & 4 on this connector are linked. Refer to “System Connections” on page 89 for the pin allocations for +AUX_V on each system interface PCB.
Pin Description Links
1+V input
123
4
rear view
2 ground
3+V input
4 ground
The DC output from the PMU is 12VDC. Although this power output is isolated, the negative side of the supply is grounded on the system interface PCB to give a +V output.
The PMU can provide an auxiliary DC output when it is fitted with the optional 40W auxiliary power supply PCB. This power supply is current limited to 3A and is available on the auxiliary DC output connector on the rear panel. DC from this output can be supplied to the +AUX_V pin on the system interface connector on the reciter via the auxiliary DC input connector on the system interface PCB (see “Reciter Auxiliary DC Input” above).
The pin allocations for the auxiliary DC output on the PMU are given in the following table. Note that pins 1 to 4 and pins 5 to 8 on this connector are linked.
TB8100 Installation and Operation Manual Connection 87 © Tait Electronics Ltd March 2004
7.3 RF Connections
The RF input to the TB8100 BSS is via the lower BNC connector on the rear panel of the reciter. The RF output is via the N-type connector on the rear panel of the PA (refer to Figure 7.3 on page 85).
We recommend that you use dual-screened coaxial cable such as RG223 for the BNC connections, and RG214 for the N-type connections.
5
rear view
Pin Description Links
1 +V output
2 +V output
1 26 37 48
3 +V output
4 +V output
5ground
6ground
7ground
8ground
88 Connection TB8100 Installation and Operation Manual
© Tait Electronics Ltd March 2004
7.4 System Connections
The reciter can be fitted with an optional system interface PCB which provides the links between the reciter’s internal circuitry and external equipment. This PCB is securely mounted to the reciter’s chassis and is connected to the control PCB with a flexible connector. The system interface PCB is fitted with industry-standard connectors and several standard types are available for different applications.
The circuitry on the system interface PCB provides additional signal processing so that the outputs meet standard system requirements. It also enables the PCB to identify itself to the reciter control circuitry.
The system interface PCB is removable, which makes it possible to change the application of a reciter by removing one type of PCB and fitting another. Only one system interface PCB can be fitted to a reciter at any one time.
This section provides details on the system interface PCBs available at the time of publication. Other types may be developed for future applications.
Figure 7.7 System Interface PCB
system interface PCB*
control PCB
*standard system interface PCB shown
Standard The standard system interface PCB is fitted to reciters bearing the product
code TBA4xxx-0A0x or TBA5xxx-0A0x. If purchased separately, it has the product code TBA10A0. It provides:
non-isolated 600: balanced audio I/O
high impedance unbalanced audio I/O
Tx key
Rx gate
RSSI
Tx relay
TB8100 Installation and Operation Manual Connection 89 © Tait Electronics Ltd March 2004
digital I/O.
It is fitted with a 25-way female D-range connector and an auxiliary DC input connector. The pin allocations are listed in the table below.
Pin Signal Name Signal Type Notes
B C D E F G H I J
1) 1! 1@ 1#
rear view
1$ 1% 1^ 1& 1* 1(
2) 2! 2@ 2# 2$ 2%
1 Rx line out +
2 Rx line out –
3 Rx audio out audio output AC coupled
4 ground ground
5 Tx audio in audio input AC coupled
6 Tx line in +
7 Tx line in –
8 RSSI DC signal
9 Rx gate output open collector
10 Tx key input
11 digital out 1
12 digital out 2
13 +AUX_V power output
14 digital in 1
15 digital in 2
16 digital in 3
17 digital in 4
18 digital in 5
19 digital in 6
20 digital in 7
21 digital in 8
22 digital in 9
23 digital in 10
24 Tx relay output open collector
25 ground ground
audio output
audio input AC coupled line
output open collector
input 5V logic
non-isolated AC coupled line
90 Connection TB8100 Installation and Operation Manual
© Tait Electronics Ltd March 2004
Isolated
This system interface PCB is fitted to reciters bearing the product code TBA4xxx-0B0x or TBA5xxx-0B0x. If purchased separately, it has the product code TBA10B0. It is the same as the standard model, except that the balanced audio interfaces are galvanically isolated.
Isolated E&M This system interface PCB is fitted to reciters bearing the product code
TBA4xxx-0C0x or TBA5xxx-0C0x. If purchased separately, it has the product code TBA10C0. It provides:
isolated balanced audio I/O
opto-isolated keying
opto-isolated gate output.
It is fitted with a 25-way female D-range connector and an auxiliary DC input connector. The pin allocations are listed in the table below.
Pin Signal Name Signal Type Notes
B C D E F G H I J
1) 1! 1@ 1#
rear view
1$ 1% 1^ 1& 1* 1(
2) 2! 2@ 2# 2$ 2%
1 Rx line out +
2 Rx line out –
3 Rx audio out audio output
4 audio ground ground
5 Tx audio in audio input
6 Tx line in +
7 Tx line in –
8 RSSI DC signal
9 Rx gate output open collector
10 Tx key input
11 digital out 1
12 digital out 2
13 +AUX_V power output
14 digital in 1
15 digital in 2
16 digital in 3
17 digital in 4
18 digital in 5
19 digital in 6
20 opto +/–
21 opto –/+
22 relay +/–
23 relay –/+
24 Tx relay output open collector
25 ground ground
audio output transformer isolated line
audio input transformer isolated line
output open collector
input 5V logic
isolated keying input
isolated gate output
TB8100 Installation and Operation Manual Connection 91 © Tait Electronics Ltd March 2004
Tai tN et
This system interface PCB is fitted to reciters bearing the product code TBA4xxx-0T1x or TBA5xxx-0T1x. If purchased separately, it has the product code TBA10T1. It is designed for use with MPT trunking systems. It is fitted with a 15-way female D-range connector and an auxiliary DC input connector. The pin allocations are listed in the table below.
Pin Signal Name Signal Type Notes
1 Rx line out +
2 Rx line out –
3 Rx audio out audio output
B C D E F G H I
rear view
J
1) 1! 1@ 1# 1$ 1%
4 Rx gate output open collector
5 Tx key input
6 Tx audio in audio input
7 Tx line in +
8 Tx line in –
9 +AUX_V power output
10 digital out 3 output open collector
11 no connection
12 digital out 1
13 digital out 2
14 digital in 1 input 5V logic
15 ground ground
7.5 Service Kit Connections
The TB8100 service kit is connected to the BSS via the RS-232 serial port on the control panel. This port is a 9-way female D-range connector. Use a straight through cable, as supplied with the service kit, to connect your programming computer to the BSS. The pin allocations for the serial port are given in the following table. Note that pins 1, 4 & 6 and pins 7 & 8 are linked. This port is also used for remote connection to the Service Kit or Alarm Center software via a modem or radio modem.
audio output AC coupled line
audio input AC coupled line
output open collector
Pin Description Links
1 not connected
2 receive data
3 transmit data
b
cdef
hj
gi
front view
92 Connection TB8100 Installation and Operation Manual
4 not connected
5ground
6 not connected
7 not connected
8 not connected
9 not connected
© Tait Electronics Ltd March 2004
7.6 Microphone Connection
You can connect a microphone to the TB8100 BSS via the standard RJ45 socket on the control panel. If a standard TB8100 microphone has not been supplied with your BSS, you should use an electret microphone. The pin allocations for the microphone socket are given in the following table.
12345678
front view
Pin Description
1not connected
2not connected
3not connected
4 PTT and hookswitch
5 voice band (microphone) input
6 microphone ground
7not connected
8not connected
TB8100 Installation and Operation Manual Connection 93 © Tait Electronics Ltd March 2004
Loading...