Operating Voltage Range: 8.5 to 35 VDC
Maximum Operating Current: 25mA
Relay Contacts: 2A at 35 VDC
Operating Temperature Range: 32° to 131° F (0° to 55° C)
Operating Humidity Range: 5% to 93% non-condensing
Dimensions: 21⁄2˝ x 21⁄2˝ x 1˝
Wire connections: 18 AWG stranded, tinned, 16˝ long
GENERAL DESCRIPTION
The RRS-MOD polarity reversing relay/synchronization module is intended
for use with 2-wire and 4-wire i3 series detectors equipped with a built-in
sounder, models 2WTA-B, 4WTA-B, 4WTAR-B, and 4WITAR-B. It is designed
to allow all the detectors in the same loop to sound when one of the detectors
goes into alarm, and to synchronize their audible output. The RRS-MOD also
allows the silencing of the detector sounders from the alarm control panel.
The RRS-MOD may be used with an alarm zone that provides coded output for
fire and continuous output for burglary. By default the RRS-MOD’s switch is
set to “off”. Therefore, the RRS-MOD will only trigger when the alarm output
is coded. In this manner, smoke detectors will only sound from the result of a
fire, and not from a burglary alarm. In this mode, the detectors will provide a
synchronized, coded output. The RRS-MOD contains a relay that is meant for
zone applications, per UL 864.
The RRS-MOD can also be set to only trigger on continuous alarm zone signals by selecting the switch to “on”. In this mode, the detectors will provide a
synchronized, coded output.
NOTICE: This manual shall be left with the owner/user of this equipment
INSTALLATION
Install in a dry indoor location. Choose a mounting location in the control
panel within reach of the provided wire leads. Use a water/isopropyl alcohol
mixture (50/50) to clean the mounting surface. Allow surface to dry and remove paper backing from the Velcro and catch. Stick the Velcro in the panel
and the catch on the back of the module, then mount the module inside the
control panel. Route terminals to the appropriate terminals as noted below.
WIRING
IMPORTANT: All polarities must be observed!
1. Connect the RRS-MOD module trigger wire to the fire alarm output terminals.
A. Alarm/Bell output: (Figures 1 and 2)
Connect the purple wire to the Alarm or Bell output.
B. Alarm relay, normally open contact: (Figures 3 and 4)
1. Connect one end of the alarm relay contact output to positive
auxiliary or detector power fire alarm output.
2. Connect the purple wire to the other end of the alarm relay
contact output.
2. Connect the red and black wires to the panel auxiliary or detector power
(red to positive, black to negative).
3. 2-wire models
Connect the yellow and orange wires to the panel initiating circuit (yel-
low to positive, orange to negative).
4-wire models
Connect the yellow and orange wires to the panel detector power circuit
(yellow to positive, orange to negative).
4. 2-wire models
Connect the brown and white wires to the smoke detector power supply
input (brown to positive, white to negative).
4-wire models
Connect the brown and white wires to the smoke detector power circuit
(brown to positive, white to negative).
NOTE: In an alarm condition, a wiring-fault
trouble state may also register at the panel
when the RRS-MOD is used.
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
When calculating total current draw of the control panel, remember to add
current consumption (25mA) for the polarity reversal relay module (RRSMOD). IMPORTANT: If the fire alarm output signal is coded, set the switch on
the RRS-MOD to “OFF”. If the fire alarm output signal is continuous, set the
switch to “ON”.
D500-44-00 1 I56-2203-005
NOTE: Please refer to Figures 5 and 6 for Ademco Vista panels and Figures 7 and 8 for DSC Power 832 panels.
FIGURE 1. 2-WIRE SYSTEM TRIGGERED FROM ALARM/BELL OUTPUT:
UL LISTED
ALARM
CONTROL
PANEL
BELL/
ALARM
CIRCUIT
(positive signal
in alarm state)
2–WIRE
INITIATING
DEVICE
CIRCUIT
AUX POWER
PURPLE
T+
BROWN
YELLOW
+
IN+
ORANGE
–
IN–
OUT+
WHITE
OUT–
+
RED
+
PWR+
BLACK
–
PWR–
–
OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 RA-
+
–
OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 RA-
FIGURE 2. 4-WIRE SYSTEM TRIGGERED FROM ALARM/BELL OUTPUT:
UL LISTED
ALARM
CONTROL
PANEL
BELL/ALARM
CIRCUIT
(positive signal
in alarm state)
PURPLE
T+
(SHOWN ENERGIZED)
EOL
S0101-01
EOL RELAY
CAUTION
When using the RRS-MOD with model
2WTA-B, do not mix the 2WTA-B with
other model smoke detectors and dry
contact closure devices, including mechanical heat detectors, manual pull
stations and waterflow switches. Such
mixing can cause a direct short on the
auxiliary power terminals, damaging the
control panel’s internal circuitry and/or
damaging devices connected to the initiating device circuit.
DETECTOR
POWER
AUX POWER
DETECTOR
POWER
INITIATING
DEVICE
CIRCUIT
BROWN
YELLOW
+
IN+
ORANGE
–
IN–
RED
+
PWR+
OR
BLACK
–
PWR–
+
–
OUT+
WHITE
OUT –
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
FIGURE 3. 2-WIRE SYSTEM TRIGGERED FROM ALARM RELAY CONTACT:
UL LISTED
ALARM
CONTROL
PANEL
ALARM
RELAY
(NO Contact)
2–WIRE
INITIATING
DEVICE
CIRCUIT
AUX POWER
PURPLE
T+
BROWN
YELLOW
+
IN+
ORANGE
–
IN–
OUT+
WHITE
OUT–
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 RA-
+
RED
+
PWR+
BLACK
–
PWR–
–
OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
+
–
OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)
EOL
S0102-00
EOL
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 RA-
S0103-01
D500-44-00 2 I56-2203-005
NOT REQUIRED ON 5110XM
FIGURE 4. 4-WIRE SYSTEM TRIGGERED FROM ALARM RELAY CONTACT:
UL LISTED
ALARM
CONTROL
PANEL
ALARM
RELAY
(NO Contact)
PURPLE
T+
EOL RELAY
(SHOWN ENERGIZED)
DETECTOR
POWER
AUX POWER
DETECTOR
POWER
INITIATING
DEVICE
CIRCUIT
BROWN
YELLOW
+
IN+
ORANGE
–
IN–
RED
+
PWR+
OR
BLACK
–
PWR–
OUT+
WHITE
OUT–
+
–
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
EOL
S0104-00
CONNECTION DIAGRAMS WITH ADEMCO VISTA PANELS
The connection diagrams enclosed show how to connect the 2WTA-B model smoke detector to the Vista panels using the System Sensor polarity reversal relay
module (RRS-MOD). Please make sure that the smoke detectors are connected properly to the zones specified in the wiring diagrams for proper operation of the
smoke detectors.
FIGURE 5. CONNECTING 2WTA-B SMOKE DETECTORS TO ADEMCO CONTROLS USING RRS-MOD MODULE TRIGGERED FROM BELL/ALARM CIRCUIT:
SYSTEM SENSOR REVERSING
RELAY/SYNCHRONIZATION
MODULE ( RRS-MOD)
(MOUNT INSIDE CONTROL ENCLOSURE)
PURPLE
T+
470
1/2 WATT*
BROWN
WHITE
+
–
OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)
YELLOW
+
ORANGE
–
RED
+
BLACK
–
*470Ω 1/2 WATT RESISTOR NEEDED FOR PANEL TO RESET
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
SYSTEM SENSOR
2WTA-B SMOKE
DETECTORS
(UP TO 16 DETECTORS
PER ZONE)
+
–
OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 C
Programming information:
EOL
2K OHMS
• The supervisory feature for the bell circuit must be turned off. See applicable
control manual for procedure.
RRS-MOD Configuration:
• Set switch on RRS-MOD to “OFF”.
S0105-02
ADEMCO
CONTROL
PANEL
APPCLICABLE
CONTROLS:
VISTA-20
VISTA-40
VISTA-50P
VISTA-32FB
VISTA-100
VISTA-128FB
UL LISTED
ALARM
CONTROL
PANEL
BELL/
ALARM
CIRCUIT
(positive signal
in alarm state)
2 -WIRE
INITIATING
CIRCUIT
AUX POWER
FIGURE 6. CONNECTING 2WTA-B SMOKE DETECTORS TO ADEMCO CONTROLS USING RRS-MOD MODULE TRIGGERED FROM AUXILIARY RELAY:
SYSTEM SENSOR REVERSING
RELAY/SYNCHRONIZATION MODULE (RRS-MOD)
(MOUNT INSIDE CONTROL ENCLOSURE)
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 RA-
+
SYSTEM SENSOR
2WTA-B SMOKE
DETECTORS
(UP TO 16 DETECTORS
PER ZONE)
–
OPTIONAL
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 RA-
Programming information:
EOL
2K OHMS
• Program Auxiliary relay to activate on
alarms
• Assign Auxiliary relay as an output for
zones programmed for fire alarm response only (Types 9, 16, or 17)
RRS-MOD Configuration:
• Set switch on RRS-MOD to “ON”.
S0106-02
ADEMCO
CONTROL
PANEL
APPCLICABLE
CONTROLS:
5110XM
5140XM
VISTA-32FB
VISTA-100
VISTA-128FB
UL LISTED
ALARM
CONTROL
PANEL
AUXILIARY
RELAY
2 – WIRE
SMOKE
ZONE
AUXILIARY
POWER
OUTPUT
PURPLE
T +
YELLOW
+
ORANGE
–
RED
+
BLACK
–
TAKE POWER FROM CONTROLS
AUXILIARY POWER OUTPUT ONLY
WHEN 5100XM JUMPER W3 INTACT
BROWN
WHITE
+
–
OPTIONAL
470
1/2 WATT*
*470Ω 1/2 WATT RESISTOR NEEDED FOR PANEL TO RESET
REMOTE
ANNUNCIATOR
(RA400Z/RA100Z)
D500-44-00 3 I56-2203-005
UL LISTED
All smoke detectors on the 2-wire fire zone will be synchronized in alarm, and will sound 1 sec ON, 1 sec OFF only from a fire alarm event.
NOTE:
•Program zone section attributes for bell output to be pulsing.
•PGM2 must be programmed for 2-wire smoke zone (04). Jumper J1 on the main board must be removed.
•PGM1 must be programmed as Burglary and Fire Bell Output (01) with ON, ON, OFF attributes.
•RRS-MOD switch must be set to OFF (fac-tory default setting).
CONNECTION DIAGRAMS WITH DSC POWER 832 PANELS
FIGURE 7. CONNECTING 4WTA-B, 4WTAR-B, AND 4WITAR-B SMOKE DETECTORS TO DSC
POWER 832 CONTROLS USING RRS-MOD MODULE WITH PGM OUTPUT:
UL LISTED
ALARM
CONTROL
PANEL
DSC POWER 832
AUX (+)
AUX
AUX
ZONE
ZONE (COM)
PURPLE
PGM 1
YELLOW
ORANGE
PGM 2
5.6
K� *
RED
+
BLACK
–
+
–
*NOTE: 5.6K� resistor must be rated for 1/4W or greater. Must be present for panel to reset.
BROWN
WHITE
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
EOL RELAY
(SHOWN ENERGIZED)
EOL
FIGURE 8. CONNECTING 2WTA-B SMOKE DETECTORS TO DSC POWER 832 CONTROLS USING RRS-MOD MODULE WITH PGM OUTPUT:
ALARM
CONTROL
PANEL
DSC POWER 832
PGM 1
PURPLE
EOL
All smoke detectors on the 4-wire fire zone will
be synchronized in alarm and will sound 1 sec
ON, 1 sec OFF only from a fire alarm event.
NOTE:
• Program zone section attributes for bell
output to be pulsing.
• PGM2 must be programmed for sensor
reset.
• PGM1 must be programmed as Burglary
and Fire Bell Output (01) with ON, ON,
OFF attributes.
• RRS-MOD switch must be set to OFF (factory default setting).
S0107-02
AUX (+)
PGM 2
AUX
AUX
YELLOW
ORANGE
5.6
KΩ*
RED
+
BLACK
–
*NOTE: 5.6KΩ resistor must be rated for 1/4W or greater. Must be present for panel to reset.
BROWN
WHITE
TESTING
Before testing, notify the proper authorities that the system is undergoing
maintenance and will temporarily be out of service.
Test in accordance with NFPA 72 test methods, inspections, and testing frequency.
1. Confirm that all smoke detectors connected to the RRS-MOD module(s)
contain a sounder and the sounders are activated upon power reversal.
2. Initiate an alarm with one of the smoke detectors connected to the RRSMOD module using any approved test method. In the alarm state, all the
detectors connected to the RRS-MOD module must be sounding their
sounders.
System Sensor warrants its enclosed product to be free from defects in materials and
workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for the enclosed product.
No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the replacement of any part of the product which
is found to be defective in materials or workmanship under normal use and service
during the three year period commencing with the date of manufacture. After phoning
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Returns Department, RA
3. Reset the system from the control panel. All smoke detector sounders
4. If the fire alarm panel also functions in burglary, initiate a burglary alarm
THREE-YEAR LIMITED WARRANTY
#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing
the malfunction and suspected cause of failure. The Company shall not be obligated to
replace units which are found to be defective because of damage, unreasonable use,
modifications, or alterations occurring after the date of manufacture. In no case shall the
Company be liable for any consequential or incidental damages for breach of this or any
other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by
the Company’s negligence or fault. Some states do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitation or exclusion may not apply
to you. This Warranty gives you specific legal rights, and you may also have other rights
which vary from state to state.
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
S0108-02
should be silent.
and ensure the smoke detectors do not sound.