System Sensor RRS-MOD User Manual

WARNING
INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-2203-005
Series
3825 Ohio Avenue, St. Charles, Illinois 60174
SPECIFICATIONS
Operating Voltage Range: 8.5 to 35 VDC Maximum Operating Current: 25mA Relay Contacts: 2A at 35 VDC Operating Temperature Range: 32° to 131° F (0° to 55° C) Operating Humidity Range: 5% to 93% non-condensing Dimensions: 21⁄2˝ x 21⁄2˝ x 1˝ Wire connections: 18 AWG stranded, tinned, 16˝ long
GENERAL DESCRIPTION
The RRS-MOD polarity reversing relay/synchronization module is intended for use with 2-wire and 4-wire i3 series detectors equipped with a built-in sounder, models 2WTA-B, 4WTA-B, 4WTAR-B, and 4WITAR-B. It is designed to allow all the detectors in the same loop to sound when one of the detectors goes into alarm, and to synchronize their audible output. The RRS-MOD also allows the silencing of the detector sounders from the alarm control panel.
The RRS-MOD may be used with an alarm zone that provides coded output for fire and continuous output for burglary. By default the RRS-MOD’s switch is set to “off”. Therefore, the RRS-MOD will only trigger when the alarm output is coded. In this manner, smoke detectors will only sound from the result of a fire, and not from a burglary alarm. In this mode, the detectors will provide a synchronized, coded output. The RRS-MOD contains a relay that is meant for zone applications, per UL 864.
The RRS-MOD can also be set to only trigger on continuous alarm zone sig­nals by selecting the switch to “on”. In this mode, the detectors will provide a synchronized, coded output.
NOTICE: This manual shall be left with the owner/user of this equipment
INSTALLATION
Install in a dry indoor location. Choose a mounting location in the control panel within reach of the provided wire leads. Use a water/isopropyl alcohol mixture (50/50) to clean the mounting surface. Allow surface to dry and re­move paper backing from the Velcro and catch. Stick the Velcro in the panel and the catch on the back of the module, then mount the module inside the control panel. Route terminals to the appropriate terminals as noted below.
WIRING
IMPORTANT: All polarities must be observed!
1. Connect the RRS-MOD module trigger wire to the fire alarm output terminals.
A. Alarm/Bell output: (Figures 1 and 2) Connect the purple wire to the Alarm or Bell output. B. Alarm relay, normally open contact: (Figures 3 and 4)
1. Connect one end of the alarm relay contact output to positive auxiliary or detector power fire alarm output.
2. Connect the purple wire to the other end of the alarm relay contact output.
2. Connect the red and black wires to the panel auxiliary or detector power
(red to positive, black to negative).
3. 2-wire models
Connect the yellow and orange wires to the panel initiating circuit (yel-
low to positive, orange to negative).
4-wire models
Connect the yellow and orange wires to the panel detector power circuit
(yellow to positive, orange to negative).
4. 2-wire models
Connect the brown and white wires to the smoke detector power supply
input (brown to positive, white to negative).
4-wire models
Connect the brown and white wires to the smoke detector power circuit
(brown to positive, white to negative).
NOTE: In an alarm condition, a wiring-fault trouble state may also register at the panel when the RRS-MOD is used.
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
When calculating total current draw of the control panel, remember to add current consumption (25mA) for the polarity reversal relay module (RRS­MOD). IMPORTANT: If the fire alarm output signal is coded, set the switch on the RRS-MOD to “OFF”. If the fire alarm output signal is continuous, set the switch to “ON”.
D500-44-00 1 I56-2203-005
NOTE: Please refer to Figures 5 and 6 for Ademco Vista panels and Figures 7 and 8 for DSC Power 832 panels.
FIGURE 1. 2-WIRE SYSTEM TRIGGERED FROM ALARM/BELL OUTPUT:
UL LISTED
ALARM
CONTROL
PANEL
BELL/
ALARM
CIRCUIT
(positive signal
in alarm state)
2–WIRE
INITIATING
DEVICE
CIRCUIT
AUX POWER
PURPLE
T+
BROWN
YELLOW
+
IN+
ORANGE
IN–
OUT+
WHITE
OUT–
+
RED
+
PWR+
BLACK
PWR–
OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 RA-
+
OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 RA-
FIGURE 2. 4-WIRE SYSTEM TRIGGERED FROM ALARM/BELL OUTPUT:
UL LISTED
ALARM
CONTROL
PANEL
BELL/ALARM
CIRCUIT
(positive signal
in alarm state)
PURPLE
T+
(SHOWN ENERGIZED)
EOL
S0101-01
EOL RELAY
CAUTION
When using the RRS-MOD with model 2WTA-B, do not mix the 2WTA-B with other model smoke detectors and dry contact closure devices, including me­chanical heat detectors, manual pull stations and waterflow switches. Such mixing can cause a direct short on the auxiliary power terminals, damaging the control panel’s internal circuitry and/or damaging devices connected to the initi­ating device circuit.
DETECTOR
POWER
AUX POWER
DETECTOR
POWER
INITIATING
DEVICE CIRCUIT
BROWN
YELLOW
+
IN+
ORANGE
IN–
RED
+
PWR+
OR
BLACK
PWR–
+
OUT+
WHITE
OUT –
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
FIGURE 3. 2-WIRE SYSTEM TRIGGERED FROM ALARM RELAY CONTACT:
UL LISTED
ALARM
CONTROL
PANEL
ALARM RELAY
(NO Contact)
2–WIRE
INITIATING
DEVICE
CIRCUIT
AUX POWER
PURPLE
T+
BROWN
YELLOW
+
IN+
ORANGE
IN–
OUT+
WHITE
OUT–
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 RA-
+
RED
+
PWR+
BLACK
PWR–
OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
+
OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)
EOL
S0102-00
EOL
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 RA-
S0103-01
D500-44-00 2 I56-2203-005