WARNING
INSTALLATION AND MAINTENANCE INSTRUCTIONS
I56-2203-005
Series
3825 Ohio Avenue, St. Charles, Illinois 60174
SPECIFICATIONS
Operating Voltage Range: 8.5 to 35 VDC Maximum Operating Current: 25mA Relay Contacts: 2A at 35 VDC Operating Temperature Range: 32° to 131° F (0° to 55° C) Operating Humidity Range: 5% to 93% non-condensing Dimensions: 21⁄2˝ x 21⁄2˝ x 1˝ Wire connections: 18 AWG stranded, tinned, 16˝ long
GENERAL DESCRIPTION
The RRS-MOD polarity reversing relay/synchronization module is intended for use with 2-wire and 4-wire i3 series detectors equipped with a built-in sounder, models 2WTA-B, 4WTA-B, 4WTAR-B, and 4WITAR-B. It is designed to allow all the detectors in the same loop to sound when one of the detectors goes into alarm, and to synchronize their audible output. The RRS-MOD also allows the silencing of the detector sounders from the alarm control panel.
The RRS-MOD may be used with an alarm zone that provides coded output for fire and continuous output for burglary. By default the RRS-MOD’s switch is set to “off”. Therefore, the RRS-MOD will only trigger when the alarm output is coded. In this manner, smoke detectors will only sound from the result of a fire, and not from a burglary alarm. In this mode, the detectors will provide a synchronized, coded output. The RRS-MOD contains a relay that is meant for zone applications, per UL 864.
The RRS-MOD can also be set to only trigger on continuous alarm zone sig­nals by selecting the switch to “on”. In this mode, the detectors will provide a synchronized, coded output.
NOTICE: This manual shall be left with the owner/user of this equipment
INSTALLATION
Install in a dry indoor location. Choose a mounting location in the control panel within reach of the provided wire leads. Use a water/isopropyl alcohol mixture (50/50) to clean the mounting surface. Allow surface to dry and re­move paper backing from the Velcro and catch. Stick the Velcro in the panel and the catch on the back of the module, then mount the module inside the control panel. Route terminals to the appropriate terminals as noted below.
WIRING
IMPORTANT: All polarities must be observed!
1. Connect the RRS-MOD module trigger wire to the fire alarm output terminals.
A. Alarm/Bell output: (Figures 1 and 2) Connect the purple wire to the Alarm or Bell output. B. Alarm relay, normally open contact: (Figures 3 and 4)
1. Connect one end of the alarm relay contact output to positive auxiliary or detector power fire alarm output.
2. Connect the purple wire to the other end of the alarm relay contact output.
2. Connect the red and black wires to the panel auxiliary or detector power
(red to positive, black to negative).
3. 2-wire models
Connect the yellow and orange wires to the panel initiating circuit (yel-
low to positive, orange to negative).
4-wire models
Connect the yellow and orange wires to the panel detector power circuit
(yellow to positive, orange to negative).
4. 2-wire models
Connect the brown and white wires to the smoke detector power supply
input (brown to positive, white to negative).
4-wire models
Connect the brown and white wires to the smoke detector power circuit
(brown to positive, white to negative).
NOTE: In an alarm condition, a wiring-fault trouble state may also register at the panel when the RRS-MOD is used.
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
When calculating total current draw of the control panel, remember to add current consumption (25mA) for the polarity reversal relay module (RRS­MOD). IMPORTANT: If the fire alarm output signal is coded, set the switch on the RRS-MOD to “OFF”. If the fire alarm output signal is continuous, set the switch to “ON”.
D500-44-00 1 I56-2203-005
NOTE: Please refer to Figures 5 and 6 for Ademco Vista panels and Figures 7 and 8 for DSC Power 832 panels.
FIGURE 1. 2-WIRE SYSTEM TRIGGERED FROM ALARM/BELL OUTPUT:
UL LISTED
ALARM
CONTROL
PANEL
BELL/
ALARM
CIRCUIT
(positive signal
in alarm state)
2–WIRE
INITIATING
DEVICE
CIRCUIT
AUX POWER
PURPLE
T+
BROWN
YELLOW
+
IN+
ORANGE
IN–
OUT+
WHITE
OUT–
+
RED
+
PWR+
BLACK
PWR–
OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 RA-
+
OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 RA-
FIGURE 2. 4-WIRE SYSTEM TRIGGERED FROM ALARM/BELL OUTPUT:
UL LISTED
ALARM
CONTROL
PANEL
BELL/ALARM
CIRCUIT
(positive signal
in alarm state)
PURPLE
T+
(SHOWN ENERGIZED)
EOL
S0101-01
EOL RELAY
CAUTION
When using the RRS-MOD with model 2WTA-B, do not mix the 2WTA-B with other model smoke detectors and dry contact closure devices, including me­chanical heat detectors, manual pull stations and waterflow switches. Such mixing can cause a direct short on the auxiliary power terminals, damaging the control panel’s internal circuitry and/or damaging devices connected to the initi­ating device circuit.
DETECTOR
POWER
AUX POWER
DETECTOR
POWER
INITIATING
DEVICE CIRCUIT
BROWN
YELLOW
+
IN+
ORANGE
IN–
RED
+
PWR+
OR
BLACK
PWR–
+
OUT+
WHITE
OUT –
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
FIGURE 3. 2-WIRE SYSTEM TRIGGERED FROM ALARM RELAY CONTACT:
UL LISTED
ALARM
CONTROL
PANEL
ALARM RELAY
(NO Contact)
2–WIRE
INITIATING
DEVICE
CIRCUIT
AUX POWER
PURPLE
T+
BROWN
YELLOW
+
IN+
ORANGE
IN–
OUT+
WHITE
OUT–
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 RA-
+
RED
+
PWR+
BLACK
PWR–
OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
+
OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)
EOL
S0102-00
EOL
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 RA-
S0103-01
D500-44-00 2 I56-2203-005
NOT REQUIRED ON 5110XM
FIGURE 4. 4-WIRE SYSTEM TRIGGERED FROM ALARM RELAY CONTACT:
UL LISTED
ALARM
CONTROL
PANEL
ALARM RELAY (NO Contact)
PURPLE
T+
EOL RELAY
(SHOWN ENERGIZED)
DETECTOR
POWER
AUX POWER
DETECTOR
POWER
INITIATING
DEVICE CIRCUIT
BROWN
YELLOW
+
IN+
ORANGE
IN–
RED
+
PWR+
OR
BLACK
PWR–
OUT+
WHITE
OUT–
+
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
EOL
S0104-00
CONNECTION DIAGRAMS WITH ADEMCO VISTA PANELS
The connection diagrams enclosed show how to connect the 2WTA-B model smoke detector to the Vista panels using the System Sensor polarity reversal relay module (RRS-MOD). Please make sure that the smoke detectors are connected properly to the zones specified in the wiring diagrams for proper operation of the smoke detectors.
FIGURE 5. CONNECTING 2WTA-B SMOKE DETECTORS TO ADEMCO CONTROLS USING RRS-MOD MODULE TRIGGERED FROM BELL/ALARM CIRCUIT:
SYSTEM SENSOR REVERSING
RELAY/SYNCHRONIZATION
MODULE ( RRS-MOD)
(MOUNT INSIDE CONTROL ENCLOSURE)
PURPLE
T+
470 1/2 WATT*
BROWN
WHITE
+
OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)
YELLOW
+
ORANGE
RED
+
BLACK
*4701/2 WATT RESISTOR NEEDED FOR PANEL TO RESET
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
SYSTEM SENSOR 2WTA-B SMOKE DETECTORS (UP TO 16 DETECTORS PER ZONE)
+
OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 C
Programming information:
EOL
2K OHMS
• The supervisory feature for the bell cir­cuit must be turned off. See applicable control manual for procedure.
RRS-MOD Configuration:
• Set switch on RRS-MOD to “OFF”.
S0105-02
ADEMCO
CONTROL
PANEL
APPCLICABLE
CONTROLS:
VISTA-20 VISTA-40
VISTA-50P
VISTA-32FB
VISTA-100
VISTA-128FB
UL LISTED
ALARM
CONTROL
PANEL
BELL/
ALARM
CIRCUIT (positive signal in alarm state)
2 -WIRE
INITIATING
CIRCUIT
AUX POWER
FIGURE 6. CONNECTING 2WTA-B SMOKE DETECTORS TO ADEMCO CONTROLS USING RRS-MOD MODULE TRIGGERED FROM AUXILIARY RELAY:
SYSTEM SENSOR REVERSING
RELAY/SYNCHRONIZATION MODULE (RRS-MOD)
(MOUNT INSIDE CONTROL ENCLOSURE)
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 RA-
+
SYSTEM SENSOR 2WTA-B SMOKE DETECTORS (UP TO 16 DETECTORS PER ZONE)
OPTIONAL REMOTE ANNUNCIATOR (RA400Z/RA100Z)
1 + IN
2 + OUT
3 - IN/OUT
4 RA+
5 RA-
Programming information:
EOL
2K OHMS
• Program Auxiliary relay to activate on alarms
• Assign Auxiliary relay as an output for zones programmed for fire alarm re­sponse only (Types 9, 16, or 17)
RRS-MOD Configuration:
• Set switch on RRS-MOD to “ON”.
S0106-02
ADEMCO
CONTROL
PANEL
APPCLICABLE
CONTROLS:
5110XM 5140XM
VISTA-32FB
VISTA-100
VISTA-128FB
UL LISTED
ALARM
CONTROL
PANEL
AUXILIARY
RELAY
2 – WIRE
SMOKE
ZONE
AUXILIARY
POWER OUTPUT
PURPLE
T +
YELLOW
+
ORANGE
RED
+
BLACK
TAKE POWER FROM CONTROLS AUXILIARY POWER OUTPUT ONLY
WHEN 5100XM JUMPER W3 INTACT
BROWN
WHITE
+
OPTIONAL
470 1/2 WATT*
*4701/2 WATT RESISTOR NEEDED FOR PANEL TO RESET
REMOTE ANNUNCIATOR (RA400Z/RA100Z)
D500-44-00 3 I56-2203-005
UL LISTED
All smoke detectors on the 2-wire fire zone will be synchronized in alarm, and will sound 1 sec ON, 1 sec OFF only from a fire alarm event.
NOTE:
• Program zone section attributes for bell output to be pulsing.
• PGM2 must be programmed for 2-wire smoke zone (04). Jumper J1 on the main board must be removed.
• PGM1 must be programmed as Burglary and Fire Bell Output (01) with ON, ON, OFF attributes.
• RRS-MOD switch must be set to OFF (fac- tory default setting).
CONNECTION DIAGRAMS WITH DSC POWER 832 PANELS
FIGURE 7. CONNECTING 4WTA-B, 4WTAR-B, AND 4WITAR-B SMOKE DETECTORS TO DSC POWER 832 CONTROLS USING RRS-MOD MODULE WITH PGM OUTPUT:
UL LISTED
ALARM
CONTROL
PANEL
DSC POWER 832
AUX (+)
AUX
AUX
ZONE
ZONE (COM)
PURPLE
PGM 1
YELLOW
ORANGE
PGM 2
5.6 K*
RED
+
BLACK
+
*NOTE: 5.6K resistor must be rated for 1/4W or greater. Must be present for panel to reset.
BROWN
WHITE
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
EOL RELAY
(SHOWN ENERGIZED)
EOL
FIGURE 8. CONNECTING 2WTA-B SMOKE DETECTORS TO DSC POWER 832 CONTROLS US­ING RRS-MOD MODULE WITH PGM OUTPUT:
ALARM
CONTROL
PANEL
DSC POWER 832
PGM 1
PURPLE
EOL
All smoke detectors on the 4-wire fire zone will be synchronized in alarm and will sound 1 sec ON, 1 sec OFF only from a fire alarm event.
NOTE:
• Program zone section attributes for bell output to be pulsing.
• PGM2 must be programmed for sensor reset.
• PGM1 must be programmed as Burglary and Fire Bell Output (01) with ON, ON, OFF attributes.
• RRS-MOD switch must be set to OFF (fac­tory default setting).
S0107-02
AUX (+)
PGM 2
AUX
AUX
YELLOW
ORANGE
5.6 KΩ*
RED
+
BLACK
*NOTE: 5.6KΩ resistor must be rated for 1/4W or greater. Must be present for panel to reset.
BROWN
WHITE
TESTING
Before testing, notify the proper authorities that the system is undergoing maintenance and will temporarily be out of service.
Test in accordance with NFPA 72 test methods, inspections, and testing frequency.
1. Confirm that all smoke detectors connected to the RRS-MOD module(s) contain a sounder and the sounders are activated upon power reversal.
2. Initiate an alarm with one of the smoke detectors connected to the RRS­MOD module using any approved test method. In the alarm state, all the detectors connected to the RRS-MOD module must be sounding their sounders.
System Sensor warrants its enclosed product to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for the enclosed product. No agent, representative, dealer, or employee of the Company has the authority to in­crease or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the replacement of any part of the product which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Returns Department, RA
D500-44-00 4 I56-2203-005 © System Sensor 2009
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
3. Reset the system from the control panel. All smoke detector sounders
4. If the fire alarm panel also functions in burglary, initiate a burglary alarm
THREE-YEAR LIMITED WARRANTY
#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
1 + IN
2 + OUT
3 - IN/OUT
4 N.O.
5 C
S0108-02
should be silent.
and ensure the smoke detectors do not sound.