System Sensor RR2 User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
WARNING
RR2 Polarity Reversal Relay Module
Specifications
Operating Voltage Range: 8.5 to 35 VDC Maximum Operating Current: 25mA Relay Contacts: 2A at 35 VDC Operating Temperature Range: 0° to 55° C (32° to 131° F) Operating Humidity Range: 5% to 95% non-condensing Dimensions: 21⁄2″ x 21⁄2″ x 1″ Wire connections: 18 AWG stranded, tinned, 16 long
General Description
The RR2 may be used with an alarm zone that provides coded output for fire and continuous output for burglary. By default the RR2 will only trigger when the alarm output is coded. In this manner, smoke detectors will only sound from the result of a fire, and not from a burglary alarm. When the RR2 is used in this mode, the smoke detectors must provide for coded alarm signals if required by the specification.
The RR2 can also be set to only trigger on continuous alarm zone signals. When used in this mode, it will not trigger from a coded fire alarm signal.
NOTICE: This manual shall be left with the owner/user of this equipment.
NOTE: If your panel configuration does not match any of the provided wiring diagrams, please contact System Sensor technical services at 1-800-SENSOR2 for assistance.
Installation
Choose a mounting location in the control panel within reach of the provided wire leads. Use a water/isopropyl alcohol mixture (50/50) to clean the mounting surface. Allow surface to dry and remove paper backing from the Velcro and catch. Stick the Velcro in the panel and the catch on the back of the module, then mount the module inside the control panel. Route terminals to the appropriate termi­nals as noted below.
When calculating total current draw of the control panel, remember to add current consumption (25mA) for the power reversal relay module (RR2). IMPORTANT: If the fire alarm output signal is coded, set the switch on the RR2 to “OFF”. If the fire alarm output signal is continuous, set the switch to “ON”.
Wiring
IMPORTANT: All polarities must be observed!
1. Connect the RR2 module trigger wire to the fire alarm output terminals. A. Alarm/Bell output: (Figures 1 and 2) Connect the purple wire to the Alarm or Bell output. B. Alarm relay, normally open contact: (Figures 3 and 4)
1. Connect one end of the alarm relay contact output
2. Connect the red and black wires to the panel auxiliary or detector power (red to positive, black to negative).
3. 2-wire models
Connect the yellow and orange wires to the panel initiat-
ing circuit (yellow to positive, orange to negative).
4-wire models Connect the yellow and orange wires to the panel detec-
tor power circuit (yellow to positive, orange to nega­tive).
4. 2-wire models
Connect the brown and white wires to the smoke detector
initiating circuit (brown to positive, white to negative).
4-wire models Connect the brown and white wires to the smoke detec-
tor power circuit (brown to positive, white to negative).
NOTE: In an alarm condition, a wiring-fault trouble state may also register at the panel when the RR2 is used.
to positive auxiliary or detector power fire alarm output.
alarm relay contact output.
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
D500-44-00 1 I56-1683-02
NOTE: If your panel configuration does not match any of the following wiring diagrams, please contact System Sensor
EOL
+ +
A
+
RA400Z
A
-
+
BELL/
ALARM
CIRCUIT (positive signal in alarm state)
UL LISTED
ALARM
CONTROL
PANEL
INITIATING
CIRCUIT
PURPLE
T+
+
+
AUX POWER
YELLOW
IN
+
ORANGE
IN
RE
D
PWR+
BLAC
K
PWR–
BROWN
OUT
+
WHITE
OUT–
Power
Not Used
+ +
A
+
RA400Z
A
-
+
Power
Not Used
EOL
+ +
A A
UL LISTED
ALARM
CONTROL
PANEL
DETECTOR
POWER
+
+
AUX POWER
OR
DETECTOR
POWER
Power
INITIATING
CIRCUIT
+
+ +
Power
NC
NO
C
Aux
A A
NC
NO
C
Aux
BELL/ALARM
CIRCUIT
(positive signal
in alarm state)
PURPLE
T+
YELLOW
IN+
ORANGE
IN–
RED
PWR+
BLACK
PWR–
BROWN
OUT+
WHITE
OUT–
EOL
+ +
A
+
RA400Z
A
-
+
ALARM RELAY
(NO Contact)
UL LISTED
ALARM
CONTROL
PANEL
INITIATING
CIRCUIT
+
+
AUX POWER
Power
Not Used
+ +
A
+
RA400Z
A
-
+
Power
Not Used
PURPLE
T+
YELLOW
IN+
ORANGE
IN–
RED
PWR+
BLACK
PWR–
BROWN
OUT+
WHITE
OUT–
technical services at 1-800-SENSOR2 for assistance. Please refer to Figures 5 and 6 for Ademco Vista panels and Figure 7 for DSC Power 832 panels.
Figure 1. 2-Wire system triggered from IAC/bell circuit:
S0124-00
NOTE: If optional Style A (Class B) wiring is used, a second RR2 module must be added to enable concurrent loop polarity reversal.
Figure 2. 4-Wire system triggered from IAC/bell circuit:
S0125-00
Figure 3. 2-Wire system triggered from alarm relay contact:
S0126-00
NOTE: If optional Style A (Class B) wiring is used, a second RR2 module must be added to enable concurrent loop polarity reversal.
D500-44-00 2 I56-1683-02
Loading...
+ 2 hidden pages