System Sensor RR1 User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
RR1 Polarity Reversal Relay Module
Specifications
Operating Voltage Range: 9.5 to 32 VDC Maximum Operating Current: 29mA Relay Contacts: 2A at 30 VDC, 0.5A at 120 VAC Operating Temperature Range: 0˚ to 55˚ C (32° to 131° F) Operating Humidity Range: 5% to 95% Dimensions: 1 Wire connections: 18 AWG stranded, tinned, 16 long
General Description
1
/2 x 13/4
2. Connect the outgoing wires of the relay module to the smoke detector power-in terminals (brown to positive, white to negative).
3. Connect the blue and purple wires of the RR1 to any of
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
NOTE: If using a power supervision relay, be aware of the following: In an alarm condition, a wiring-fault trouble state may also register at the panel when the RR1 is used.
The RR1 cannot be used with a coded (or pulsed) power supply. For proper RR1 opera­tion, distinct wiring methods are required. See page 4 for specifics.
wire detectors.
2) Connect the red wire to other end of alarm relay contact output.
A Division of Pittway
the power sources as specified in the applicable wiring NOTICE: This manual shall be left with the owner/user of this equipment.
diagram (see Figures 1-4).
4. 2-wire models: Connect the yellow and orange wires to the positive and
NOTE: If your panel configuration does not match any of the provided wiring diagrams, please contact System Sen­sor technical services at 1-800-SENSOR2 for assistance.
Installation
Choose a mounting location in the control panel within
negative of the initiating loop, respectively. 4-wire models: Connect the yellow and orange wires to the positive and negative of power to detectors, respectively.
5. Connect the smoke detector initiating circuit to the alarm loop.
reach of the provided wire leads. Use a water/isopropyl al­cohol mixture (50/50) to clean the mounting surface. Allow surface to dry and remove paper backing from the Velcro and catch. Stick the Velcro in the panel and the catch on the back of the module, then mount the module inside the control panel. Route terminals to the appropriate terminals
When calculating total current draw of the control panel, remember to add current consumption (29mA) for the power reversal relay module (RR1).
WARNING
as noted below.
Testing
Wiring
1. Connect the relay module trigger wires to the fire alarm output terminals.
Before testing, notify the proper authorities that the system is undergoing maintenance and will temporarily be out of service.
IMPORTANT: Polarity must be observed!
A. Continuous alarm/bell output: (Figures 1 and 2)
Connect red wire to positive and black wire to negative.
Test in accordance with NFPA 72 Chapter 7 test methods, inspections, and testing frequency.
B. Alarm relay, normally open contact output: (Figures 3
and 4)
1) Connect one end of the alarm relay contact output and the black wire to positive and negative of power, respectively. Auxiliary power supply is used as a power source for 2-wire detectors and power to the detectors is used as a power source for 4-
1. To test the RR1 module, confirm that the smoke detec­tors do not sound without an alarm.
2. Initiate an alarm with smoke or approved test method on any detector connected to the control panel via the RR1 module. In alarm, all the detectors that are installed in the corresponding loop shall sound.
3. Reset the detectors by removing power to the loop.
M500-12-00 1 I56-1168-02
NOTE: If your panel configuration does not match any of the following wiring diagrams, please contact System Sensor technical services at 1-800-SENSOR2 for assistance
Figure 1. RR1 module with 2-wire smoke detectors:
The power reversal relay module does not provide supervision.
UL LISTED CONTROL
PANEL
CONTINUOUS
BELL/
ALARM
OUTPUT
INITIATING
LOOP
+
+ –
All supervision is provided by the interconnected control unit. POWER REVERSAL
RELAY MODULE (RR1)
T1RED
BLK
T2
YELLOW
PURPLE
T8
T7
WHITE
T6
T3
BROWN
T4
T5
+
RA400Z
ORG BLUE
+
To auxiliary power/IAC/Bell output or any UL listed regulated power supply listed for fire protective signaling use. (polarity shown with panel in alarm).
EOL
+
P
+
W R
A
+
-
A
Not Used
+
RA400Z
+
P
+
W R
A
+
A
-
Not Used
A78-2336-10
NOTE: If optional Class A wiring is used, second power reversal relay module (RR1) must be added to enable concurrent loop polarity reversal.
Figure 2. RR1 module with 4-wire smoke detectors:
The power reversal relay module does not provide supervision.
UL LISTED CONTROL
PANEL
CONTINUOUS
BELL/
ALARM
OUTPUT
POWER
DETECTORS
TO
INITIATING
LOOP
+
+ –
All supervision is provided by the interconnected control unit. POWER REVERSAL
RELAY MODULE (RR1)
T1RED
BLK
T2 T8
ORG
BLUE
YELLOW
PURPLE
+
To auxiliary power/detector power/IAC/Bell output or any UL listed regulated power supply listed for fire protective signaling use. (polarity shown with panel in alarm).
T7
WHITE T6 T3
BROWN
T4
T5
+
P
W
+
R
A A
NC
A
C
U X
NO
OPTIONAL CLASS A WIRING
A A
NC
NO
+ + –
C
P
W
R
INITIATING
}
LOOP
A U X
EOL POWER SUPERVISION RELAY (SHOWN ENERGIZED) A77-716 12/24V
EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER
A78-2336-09
M500-12-00 2 I56-1168-02
Figure 3. RR1 module with alarm relay and 2-wire smoke detectors:
The power reversal relay module does not provide supervision. All supervision is provided by the interconnected control unit.
UL LISTED CONTROL
PANEL
ALARM RELAY
(N/O contact)
OUTPUT
AUX.
POWER
SUPPLY
INITIATING
LOOP
+
+
POWER REVERSAL RELAY MODULE (RR1)
T1RED
BLK
T2
YELLOW
PURPLE
T8
T7
WHITE
T6
T3
T4
T5
ORG
BLUE
BROWN
RA400Z
EOL
+
P
+
W R
+
A
+
-
A
Not Used
+
RA400Z
+
P
+
W R
A
+
A
-
Not Used
+––
To auxiliary power/IAC/Bell output or any UL listed regulated power supply listed for fire protective signaling use. (polarity shown with panel in alarm).
A78-2336-12
NOTE: If optional Class A wiring is used, second power reversal relay module (RR1) must be added to enable concurrent loop polarity reversal.
Figure 4. RR1 module with alarm relay and 4-wire smoke detectors:
The power reversal relay module does not provide supervision.
UL LISTED
CONTROL
PANEL
ALARM RELAY
(N/O contact)
OUTPUT
POWER
DETECTORS
INITIATING
LOOP
TO
+ –
To auxiliary power/detector power/IAC/Bell output or any UL listed regulated power supply listed for fire protective signaling use. (polarity shown with panel in alarm).
All supervision is provided by the interconnected control unit. POWER REVERSAL
RELAY MODULE (RR1)
T1RED
BLK
T2 T8
ORG
BLUE
YELLOW
PURPLE
+
T7
WHITE T6 T3
BROWN
T4
T5
+
P
W
+
R
A A NC
A
C
U X
NO
OPTIONAL CLASS A WIRING
+ + –
A A NC
C
NO
P
W
R
INITIATING
}
LOOP
A U X
EOL POWER SUPERVISION RELAY (SHOWN ENERGIZED) A77-716 12/24V
EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER
A78-2336-11
M500-12-00 3 I56-1168-02
Minimum Conditions Required for Proper Operation of the RR1 Upon Fire Alarm
For 2-Wire Model Smoke Detectors (Model 2100AT)
Auxiliary power supply for smoke detector sounders upon alarm and one of the following:
1. Bell, alarm, or programmable output exclusive to fire alarm. Output of minimum 30mA @ 9.5 Vdc required
–or–
2. Auxiliary power supply for RR1 and auxiliary relay with normally open contact activated by fire alarm only
For 4-Wire Model Smoke Detectors (Models 2112/24AT, 2112/24ATR, 2112/24AITR)
1. Bell, alarm, or programmable output exclusive to fire alarm. Output of minimum 30mA @ 9.5 Vdc required
–or–
2. Auxiliary relay with normally open contact activated by fire alarm only
NOTE: Outputs must be continuous (non-coded, non-pulsed.) The RR1 will not function properly in panels that provide only single combined burglary and fire alarm output unless the minimum conditions noted above are present.
Three-Year Limited Warranty
System Sensor warrants its enclosed relay module to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for this relay module. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obliga­tions or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the repair or replacement of any part of the relay module which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Repair Depart-
M500-12-00 4 I56-1168-02
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to repair or replace units which are found to be defective because of damage, unreasonable use, modifica­tions, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or conse­quential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
© System Sensor 1998
Loading...