Temperature Range:0°C to 49°C (32°F to 120°F)
Under no circumstances can the PS24 voltage exceed 33VDC or be less than 18VDC.
Under no circumstances can the PS12 voltage exceed 18.7VDC or be less than 9.6VDC.
To calculate battery requirements, use current values shown above. However, note that there is an in-rush current associated with
strobe power-up. The information in Figures 3 and 4 is useful when selecting fuse values.
As Figure 3 shows, 12V strobe in-rush current typically peaks at 3A and drops to nominal in 600
current typically peaks at 7.0A and drops to nominal in 800
Figure 3. 12 volt strobe in-rush current:
1A/div
o
C to +60oC (14oF to 140oF)
0°C to 49°C (32°F to 120°F) with strobe added
See Figure 1 for other voltages. 82 dBA minimum measured in UL reverbarant room
(75 dBA minimum with strobe)
Figure 1:Figure 2:
MODEL
µ
S.
92
91
90
89
dBA output
88
87
86
10121416182022
Voltage
µ
S. In a 24V strobe (Figure 4), in-rush
Figure 4. 24 volt strobe in-rush current:
1A/div
200
µ
S/div
General Information
The National Fire Protection Association has published codes,
standards, and recommended practices for the installation and
use of the above appliances. Therefore, the installer must be familiar with these requirements, with local codes, and any special
requirements of the authority having jurisdiction.
Model PA400
The PA400W (white) and PA400R (red) Piezo Alert electronic
sounder and optional supplementary signal strobes are intended
to be connected to the alarm indicating circuit of a UL-listed 12 or
24 VDC fire alarm control panel. The models PS12 and PS24 optional strobe additions to the PA400 require a 12 VDC or 24 VDC
panel, respectively and are able to operate from a full-wave rectified, unfiltered supply.
Installation Notes
The wiring must be in compliance with all codes and must not be
of such length or wire size that would cause the appliance to operate outside of its published specifications. The appliances must
also be tested after installation in accordance with the control
panel manufacturer’s test procedure.
NOTE: Do not loop wires under terminal screws. Wires
connecting the device to the panel must be broken at the
device screw terminal in order to maintain electrical
supervision.
1I56-305-07
Mounting
PA400 Sounders
1. The PA400 is intended for mounting to a standard 2-1/2" deep
single-gang box which allows sufficient clearance for conduit
entrance.
2. The PA400 is compatible with DC line supervision. The Piezo
Alert is polarized and has terminals marked with polarity. Apply positive supply voltage to the (+) terminal and negative
supply voltage to the (–) terminal. (See Figure 5.)
3. Mount the appliance to the electrical outlet box using the two
mounting screws supplied.
4. Field repair of the PA400 should not be attempted. Return to
factory for repair or replacement.
PS12 or PS24 Strobes
These optional strobes are interconnected to the PA400 by first removing the two mounting screws from the sounder. Use a small
screwdriver to punch out the skinned-over areas as indicated in
Figure 6. Install the adapter plate on top of the sounder and screw
the combined sounder and adapter plate to the electrical outlet
box. Make sure field wiring terminals are oriented in the upward
position when mounted in the outlet box. Next, slide the strobe
directly into the slots in the plates. The positive solder lug may be
colored red or marked with a plus sign (+). This lug must be in
the slot closest to the field wiring terminals. Grasp the catch area
on each end of the strobe and squeeze while applying inward
force. Make sure the strobe catches fully engage the slots in the
adapter plate and that no gap appears at the interface between the
strobe and adapter plate.
Figure 5:
From
control
panel
or
previous
To
EOL
or
Next
Device
device*
*NOTE: Shown with control panel in alarm. Panel polarity
reversed in supervisory condition.
A78-1315-00.
Figure 6:
A78-1314-01
The Limitations of Sounders and Strobes
System Sensor’s sounder and signal strobe is designed to provide fire and
security hazard warning.
The strobe is for supplementary signaling use only.
The sounder or sounder/strobe combination will not work without
power. The sounder or sounder/strobe gets its power from the fire or se-
curity panel monitoring the alarm system. If power is cut off for any reason, the sounder or sounder/strobe combination will not provide the
desired audible or visual warning.
The sounder may not be heard. The loudness of the sounder meets or
exceeds current Underwriters Laboratories’ standards. however, the
sounder may not alert a sound sleeper or one who has recently used drugs
or has been drinking alcoholic beverages. The sounder may not be heard if
it is placed in an area which is isolated by a closed door, or if it is located
on a different floor from the person in hazard or if placed too far away to
be heard over the ambient noise such as traffic, air conditioners, machin-
Three-Year Limited Warranty
System Sensor warrants its enclosed sounder/strobe to be free from defects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes no
other express warranty for this sounder/strobe. No agent, representative,
dealer, or employee of the Company has the authority to increase or alter
the obligations or limitations of this Warranty. The Company’s obligation
of this Warranty shall be limited to the repair or replacement of any part of
the sounder/strobe which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll
free number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Repair Depart-
A78-1778-00
WARNING
ery, or music appliances that may prevent alert persons from hearing the
alarm. The sounder may not be heard by persons who are hearing im-
paired.
The signal strobe may not be seen. The electronic visual warning signal
meets or exceeds current Underwriters Laboratories’ standard 1638. The
visual warning signal is suitable for direct viewing and must be installed
within an area where it can be seen by building occupants. The strobe
must not be installed in direct sunlight or areas of high light intensity
where the visual flash might be disregarded or not seen. The strobe may
not be seen by the visually impaired.
The signal strobe may cause seizures. Individuals who have a positive
photic response to visual stimuli with seizures, such as epileptics, should
avoid prolonged exposure to environments in which strobe signals, including this strobe, are activated.
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to repair or replace units which are
found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case
shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to
you. This Warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.
PS12/24ADA Series Strobes with
Mini-sounder for Fire Protective
Signaling Systems
Table 1. PS12/24ADA Series Electrical Ratings
Model
PS24110ADA
PS24110ADAW
PS2475ADA
PS2475ADAW
PS2415ADA
PS2415ADAW
PS1215ADA
PS1215ADAW
PS241575ADA
PS241575ADAW
PS121575ADA
PS121575ADAW
Supply
Voltage
Range
20-30V225
20-30V185
20-30V90
12-17V182
20-30V108
12-17V240
* Horn current is 12mA@12VDC, 15mA@24VDC
Operating Current from Regulated SupplyOperating Current from
Average
Operating
Current
Horn/
Strobe*
Average
Operating
Current
Strobe
Only
210
170
75
170
93
225
Current
Peak
Peak
Inrush
Current
(mA)
10.5V/17V
Current
(mA in
access of
Peak)
(mA)
20/30V
470/500–0
385/400–0
160/180–0
–360/3800
210/220–0
–510/5600
Average
Operating
Current
(mArms)
Horn/Strobe*
260
215
105
212
135
285
3825 Ohio Avenue, St. Charles, Illinois 60174
Full-Wave Rectified Unfiltered Supply
Average
Operating
Current
(mArms)
Strobe Only
245
200
90
220
120
270
Peak Current
Peak Current
(mA)
20Vrms/
30Vrms
400/500–
320/370–
275/290–
275/290–
10.5Vrms/
17Vrms
–330/380
–500/530
(mA)
Inrush Current
(Amps in
excess
of Peak)
0.08
0.04
0.02
0.02
1
0.02
A Division of Pittway
1-800-SENSOR2, FAX: 630-377-6495
NOTE: In-rush current du-
ration is less than
20 microseconds
(0.00002 seconds).
NOTICE: This manual should be left with the owner/user
of this equipment.
General Description
The National Fire Protection Association has published
standards and recommended practices for the installation
and use of the above appliances. It is recommended that
the installer be familiar with these requirements, with local
codes, and any special requirements of the local fire
authority having jurisdiction.
The Piezo electronic sounder and signaling strobe are
intended to be connected to the alarm indicating circuit of a
UL-listed fire alarm control panel. Both are compatible with
DC line supervision. The electronic sounder can be
connected to either 12 or 24 VDC panels. Models
PS2415ADA, PS2475ADA, PS24110ADA, and PS241575ADA
require 24 volt panels. Models PS1215ADA and
PS121575ADA require 12 volt panels. Panels may have full-
Figure 1. Vertical and horizontal light distsribution:
wave rectified, unfiltered power supplies. The strobes
produce one flash per second (nominal) with continuous
nominal voltage applied.
The sounder/strobe strobe is rated for 0° to 49° C and is
NOT suitable for outdoor use.
The rated light output of the PS2415ADA, PS1215ADA,
PS241575ADA, and PS121575ADA is 15 cd (See Figure 1).
The rated light output of the PS2475ADA is 75 cd (See
Figure 1).
The rated light output of the PS24110ADA is 110 cd (See
Figure 1).
NOTE: The 15/75 cd strobe has been measured to be 75 cd
Greater than 90 dBA measured in anechoic room at 10 feet,
24 volts (see Figure 2 for other voltages); 79 dBA minimum
measured in UL reverberant room @ 12V and 82 dBA @
24V.
Figure 2:
90
89
NOTE: All models can be powered using full wave recti-
fied unfiltered supplies. Under no circumstances
can PS24ADA series devices input voltage exceed
33 VDC or be less than 16 VDC (16-33Vrms for fullwave rectified, unfiltered supplies). Under no circumstances can a PS12ADA series device input
voltage exceed 18.7 VDC or be less than 9.6 VDC
(9.6 - 18.7Vrms for full-wave rectified, unfiltered
supplies).
Installation
A. General:
Phillips head screws are used to attach PS12/24ADA to
semi-flush plate or the electrical outlet box. Slotted head
screws are used to attach semi-flush plate to outlet box.
See Figures 3 and 4 for wiring methods.
NOTE: Do not loop wires under the terminal screw. Wires
connecting the device to the panel must be broken
at the device terminal connection in order to
maintain electrical supervision.
The PS12/24ADA is designed for wall mounting ONLY.
It is intended for mounting to a standard 2-1/2" deep
single gang box which allows sufficient clearance for
conduit entrance.
88
87
dBA output
86
85
84
10121416182 022
Voltage
All strobes must be mounted so that the top of the lens is
24 inches (61cm) below ceilings or as required by the
authority having jurisdiction.
B. Sounder/Strobe combination mounting:
1. Surface Mount: (See Figure 5)
2. Semi-Flush Mount: (See Figures 6 and 7)
3. Semi-Flush Mount with Plaster Ring or Double Gang
Box: (See Figure 8)
Installation procedures must conform to all applicable codes
and the requirements of the authority having jurisdiction.
NOTE: The rated output of the sounder is specified at 10
feet. It cannot be assumed that the output will
meet the NFPA standard of 15 dB over ambient
noise at all locations within a room. Additional
sounders may be needed to ensure sound output
level complies with NFPA requirements.
Figure 3. Operating horn and strobe in tandem:
From
Control
Panel
or
Next
Device
Previous
Device
Polarity shown in alarm condition. Polarity is reversed in
supervisory condition.
D900-08-002I56-732-04
EOL
A78-2663-00
Figure 4. Operating horn and strobe independently:
To
or
From
Control
Panel
or
Previous
Device
Blk
Red
Cut and
Remove for
Independent
Operation
Note: Remove paper
shield; cut and
remove red and
black wires between
the horn and strobe.
When finished wiring,
place paper shield
back on unit.
Polarity shown in alarm condition. Polarity is reversed in
supervisory condition.
Figure 8. Semi-flush mount with plaster ring or double
gang box:
1. Screw Semi-Flush Plate to Box with C Screws
A78-2605-00
2. Complete Field Wiring (See Figure 3)
3. Screw PS12/24ADA to Semi-Flush Plate with D Screws
The Limitations of Sounder/Strobes
The Sounder and/or Strobe will not work without power. The sounder/
strobe gets its power from the fire/security panel monitoring the alarm
system. If power is cut off for any reason, the sounder/strobe will not provide the desired audio or visual warning.
The Sounder may not be heard. The loudness of the sounder meets (or
exceeds) current Underwriters Laboratories’ standards. However, the
sounder may not alert a sound sleeper or one who has recently used drugs
or has been drinking alcoholic beverages. The Sounder may not be heard
if it is placed on a different floor from the person in hazard or if placed too
far away to be heard over the ambient noise such as traffic, air conditioners, machinery or music appliances that may prevent alert persons from
hearing the alarm. The Sounder may not be heard by persons who are
hearing impaired.
WARNING
must be installed within an area where it can be seen by building occupants. The strobe must not be installed in direct sunlight or areas of high
light intensity (over 60 foot candles) where the visual flash might be disregarded or not seen. The strobe may not be seen by the visually im-
paired.
The signal strobe may cause seizures. Individuals who have a positive
photic response to visual stimuli with seizures, such as epileptics, should
avoid prolonged exposure to environments in which strobe signals, including this strobe, are activated.
System Sensor recommends that the Multi-Alert Sounder and Signal
Strobe always be used in combination so that the risks from any of the
above limitations are minimized.
The Signal Strobe may not be seen. The electronic visual warning signal
that flashes at least once every three seconds meets or exceeds current Underwriters Laboratories’ standard 1971 and uses an extremely reliable xenon flash tube. The visual warning signal is suitable for direct viewing and
Three-Year Limited Warranty
System Sensor warrants its sounder/strobe to be free from defects in materials and workmanship under normal use and service for a period of three
years from date of manufacture. System Sensor makes no other express
warranty for this sounder/strobe. No agent, representative, dealer, or employee of the Company has the authority to increase or alter the obligations or limitations of this Warranty. The Company’s obligation of this
Warranty shall be limited to the repair or replacement of any part of the
sounder/strobe which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free
number 800-SENSOR2 (736-7672) for a Return Authorization number,
send defective units postage prepaid to: System Sensor, Repair Depart-
The signal strobe cannot operate from coded power supplies. Coded
power supplies produce interrupted power. The strobe must have an uninterrupted source of DC power in order to operate correctly.
ment, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please
include a note describing the malfunction and suspected cause of failure.
The Company shall not be obligated to repair or replace units which are
found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case
shall the Company be liable for any consequential or incidental damages
for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to
you. This Warranty gives you specific legal rights, and you may also have
other rights which vary from state to state.