NOTE: All -R models are specifically designed for use with the WTP Series of Weatherproof plates
NOTE: When replacing outdoor units; device and back box must be replaced
NOTE: Models SBHK, SBK-R are UL listed for General Signaling
PRODUCT SPECIFICATIONS
Operating Temperature:Standard Products32°F to 120°F (0°C to 49°C)
K Series–40°F to 151°F
Humidity Range:Standard Products10 to 93% Non-condensing
K SeriesMeets NEMA 4X requirements
Strobe Flash Rate:1 flash per second
Nominal Voltage:Regulated 12VDC/FWR or regulated 24DC/FWR
Operating Voltage Range (includes fire alarm panels with built in sync):8 to 17.5V (12V nominal) or 16 to 33V (24V nominal)
Operating Voltage with MDL3 Sync Module:8.5 to 17.5V (12V nominal) or 16.5 to 33V (24V nominal)
Input terminal wire gauge:12 to 18 AWG
NOTE : Strobes will operate at 12 V nominal for 15 & 15/75 candela settings only. Switching between ranges is automatic.
NOTE: SA-WBB, SA-WBBW, SA-WBBC and SA-WBBCW dimensions
do not include the two mounting tabs
800/736-7672, FAX: 630/377-6495
www.systemsensor.com
6.8"2.5"
7.1"2.2"
180 mm51 mm
6.9"5.3"
175 mm135 mm
I56-2769-020R
NOTICE: This manual shall be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The SpectrAlert Advance series of notification appliances offers a wide range
of horns, strobes, and horn/strobes, for wall and ceiling applications, indoors
and outdoors. They are designed to be used on 12 or 24 volt, DC or FWR
(full wave rectified) systems. These products are electrically backward compatible with the previous generation of SpectrAlert notification appliances. Horn/
strobe products are available in two versions. The 2-wire products fit systems
where a single NAC controls both horn and strobe. The 4-wire products are intended for systems which have separate wiring circuits for the horn and strobe.
All SpectrAlert Advance products are suitable for use in synchronized systems.
The System Sensor MDL3 module may be used to provide synchronization.
K Series products are designed to be used over a wider range of temperatures
and are suitable for use in wet environments with outdoor backbox supplied
with product.
Wall and ceiling products may be used interchangeably (wall products
may be used on the ceiling and ceiling products may be used on the wall.)
FIRE ALARM SYSTEM CONSIDERATIONS
The National Fire Alarm Code, NFPA 72, requires that all horns, used for
building evacuation produce temporal coded signals. Signals other than those
used for evacuation purposes do not have to produce the temporal coded signal. System Sensor recommends spacing notification appliances in compliance with NFPA 72.
1 I56-2769-020R
06-10
LOOP DESIGN AND WIRING
The system designer must make sure that the total current drawn by the devices on the loop does not exceed the current capability of the panel supply,
and that the last device on the circuit is operated within its rated voltage. The
current draw information for making these calculations can be found in the
tables within this manual. For convenience and accuracy, use the voltage drop
calculator on the System Sensor website (www.systemsensor.com).
When calculating the voltage available to the last device, it is necessary to
consider the voltage drop due to the resistance of the wire. The thicker the
wire, the smaller the voltage drop. Wire resistance tables can be obtained
from electrical handbooks. Note that if Class A wiring is installed, the wire
length may be up to twice as long as it would be for circuits that are not
fault tolerant.
NOTE: The total number of strobes on a single NAC must not exceed 40 for
24 volt applications or 12 for 12 volt applications. Loop resistance on a single
NAC should not exceed 120 ohms for 24 volt and 30 ohms for 12 volt systems.
CANDELA SELECTION
Thisisgeneratedtextforfigtxt.
Adjust the slide switch on the rear of the product to the desired candela setting in the small window on the front of the unit. All products meet the light
output profiles specified in the appropriate UL Standards. See Figures 1-3.
Use Table 1 to determine the current draw for each candela setting. For K
series products used outdoors at low temperatures, listed candela ratings must
be reduced in accordance with Table 2.
NOTE: SpectrAlert products set at 15 and 15/75 candela automatically work
on either 12V or 24V power supplies. The products are not listed for 12V operating voltages when set to any other candela settings. For 4-Wire products,
total current draw may be determined by adding current draw for the specific
candela selection and the current draw for the specific horn selection use
Table 1 and Table 3.
FIGURE 1. LIGHT OUTPUT - VERTICAL DISPERSION, CEILING TO WALLS
TABLE 1. STROBE CURRENT DRAW (mA) FOR S, SC, P4 & PC4 SERIES:
Candela
8–17.5 Volts16–33 Volts
DCFWRDCFWR
151231286671
15/751421487781
30NANA9496
Standard Candela Range
75NANA158153
95NANA181176
110NANA202195
11 5NANA210205
135NANA228207
High Candela Range
150NANA246220
177NANA281251
185NANA286258
TO FLOOR
Degrees*
Percent of
Rating
0100
5-2590
30-4575
5055
6045
6535
7035
7530
8030
8525
9025
Figures 1-3 list the minimum light output requirements per UL1971.
FIGURE 2. LIGHT OUTPUT -
HORIZONTAL DISPERSION
Degrees*
Percent of
Rating
0100
5-2590
30-4575
5055
5545
6040
6535
7035
7530
8030
8525
9025
Compound 45
to the right
Compound 45
to the right
24
24
FIGURE 3. LIGHT OUTPUT - VERTICAL DISPERSION, WALL TO FLOOR
Degrees*
Percent of
Rating
TABLE 2. CANDELA DERATING:
Listed Candela
Candela rating at –40°F
(K Series Outdoor Applications Only)
15
Do not use below 32°F15/75
30
7544
9570
110110
11 511 5
135135
150150
177177
185185
HORN SELECTION
Turn the rotary switch on the back of the product to the desired setting. For
horn and 4-wire horn/strobe products, the current draw for each setting is
listed in Table 3. For 2-wire horn/strobe products (P2 series), current draws
are listed in Tables 4 and 5. The sound output measurement for each horn
setting is shown in Table 6.
TABLE 3. HORN CURRENT DRAW (mA) FOR H, P4 & PC4 SERIES:
NOTE: In positions 7, 8, and 9, temporal coding must be provided by the NAC.
If the NAC voltage is held constant, the horn output will remain constantly on.
Positions 7, 8, and 9 are not available on 2-wire horn/strobe products.
0100
5-3090
3565
4046
4534
5027
5522
6018
6516
7015
*Tolerance of ±1 degree is permitted.
7513
8012
8512
9012
2 I56-2769-020R
06-10
TABLE 4. 2-WIRE HORN/STROBE CURRENT DRAW ( ) FOR P2 AND PC2 STANDARD CANDELA SERIES:
INPUT
FROM
F
PRIOR
STROBE
INPUT
FACP OR PRIOR HORN
HORN OR EOL
DC Input
8–17.5 Volts16–33 Volts
15 cd15/75 cd15 cd15/75 cd30 cd75 cd95 cd110 cd115 cd
*Horn & 4-wire Horn/Strobe only. ** Minimum dB rating for Operational Voltage Range as per UL 464.
FIGURE 4. WIRING 2-WIRE PRODUCTS:
INPUT
FROM
FACP
OR
PRIOR
DEVICE
+
–
OUTPUT
TO
NEXT
DEVICE
OR EOL
+
–
FIGURE 6. SHORTING SPRING:
FIGURE 5. WIRING 4-WIRE PRODUCTS:
3 I56-2769-020R
06-10
ACP OR
+
–
+
–
FROM
A0367-01
OUTPUT
TO NEXT
STROBE
OR EOL
+
–
+
–
OUTPUT TO NEXT
A0366-00
SHORTING SPRING
A0368-00
For 4-Wire installations, terminals 1, 2, and 3 connect to the strobe; terminals
4 and 5 connect to the horn. The horn and strobe circuits must be wired independently, and each circuit must be terminated with the appropriate EOL
device. Removal of a notification device will result in an open circuit indication on the strobe loop.
NOTE: A shorting spring is provided between terminals 2 and 3 of the mounting plate to enable wiring checks after the system has been wired, but prior
to installation of the final product. This spring will automatically disengage
when the product is installed, to enable supervision of the final system. Only
available on indoor products(non K-series).
MOUNTING INDOOR WALL OR CEILING PRODUCTS
1. Attach mounting plate to junction box as shown in Figure 7. The mounting plate is compatible with 4-inch square, double gang, and 4-inch octagon junction boxes (2-wire products may be used with a single gang box).
2. Connect field wiring to terminals, as shown in Figures 4 or 5.
3. If the product is not to be installed at this point, use the paint cover to
prevent contamination of the mounting plate. (For indoor models only)
4. To attach product to mounting plate, remove the paint cover, then hook
tabs on the product housing into the grooves on mounting plate.
5. Swing product into position to engage the pins on the product with the
terminals on the mounting plate. Make sure that the tabs on the back of
the product housing fully engage with the mounting plate.
6. Secure product by tightening the single mounting screw in the front
of the product housing. For tamper resistance, the standard captivated
mounting screw may be replaced with the enclosed Torx screw.
SURFACE MOUNT BACK BOX MOUNTING
1. The surface mount back box may be secured directly to the wall or ceiling. Grounding bracket provided if needed.
2. The wall mount box must be mounted with the up arrow pointing up.
3. Threaded knockout holes are provided for the sides of the box for ¾ inch
and ½ inch conduit adapter. Knockout holes in the back of the box can
be used for ¾ inch and ½ inch rear entry.
4. To remove the ½ inch knockout, we recommend you use a flat head screwdriver ,place the blade of the flat head screwdriver in the inner edge of the
knockout. Strike the screwdriver as you work you way around as shown in
Figure 9.
To remove the ¾ inch knockout place the blade of the screwdriver along
the outer edge and work your way around the knockout as you strike the
screwdriver, as shown in Figure 9.
NOTE: For both ½ in. and ¾ in. installation, use caution not to strike the
knockout near the top edge of the wall version of the surface mount back box.
5. V500 and V700 raceway knockouts are also provided. Use V500 for low
profile applications and V700 for high profile applications.
6. To remove the knockout turn pliers up, as shown in Figure 9.
7. Attach the mounting plate to the surface mount back box using the four
unpainted screws, as shown in Figure 8.
8. Follow steps 2-6 of the mounting indoor wall or ceiling products to wire
and attach the product.
NOTE: For Outdoor Mounting Installation see included Outdoor Mount-
ing Installation Document (I56-3222).
FIGURE 7. MOUNTING:
2-wire mounting plate
A0348-00
4-wire mounting plate
A0369-00
FIGURE 8. SURFACE MOUNT BACK BOX MOUNTING:
WALL
CEILING
A0462-00
A0463-00
FIGURE 9. KNOCKOUT REMOVAL FOR SURFACE MOUNT BACK BOX:
A0465-01
½ INCH
¾ INCH
wire mold removal
A0466-00
Please refer to insert for the Limitations of Fire Alarm Systems
WARNING
THE LIMITATIONS OF HORN/STROBES
The horn and/or strobe will not work without power. The horn/strobe gets its power
from the fire/security panel monitoring the alarm system. If power is cut off for any rea
son, the horn/strobe will not provide the desired audio or visual warning.
The horn may not be heard. The loudness of the horn meets (or exceeds) current
Underwriters Laboratories’ standards. However, the horn may not alert a sound sleeper or
one who has recently used drugs or has been drinking alcoholic beverages. The horn may
not be heard if it is placed on a different floor from the person in hazard or if placed too
far away to be heard over the ambient noise such as traffic, air conditioners, machinery
or music appliances that may prevent alert persons from hearing the alarm. The horn
may not be heard by persons who are hearing impaired.
NOTE: Strobes must be powered continuously for horn operation.
THREE-YEAR LIMITED WARRANTY
System Sensor warrants its enclosed product to be free from defects in materials and
workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for this product. No
agent, representative, dealer, or employee of the Company has the authority to increase
or alter the obligations or limitations of this Warranty. The Company’s obligation of this
Warranty shall be limited to the replacement of any part of the product which is found to
be defective in materials or workmanship under normal use and service during the three
year period commencing with the date of manufacture. After phoning System Sensor’s
toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send
defective units postage prepaid to: Honeywell, 12220 Rojas Drive, Suite 700, El Paso TX
SpectrAlert Strobes and Horn/Strobes have been tested and found to comply with the
limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference when the equip
ment is operated in a commercial environment. This equipment generates, uses, and
The signal strobe may not be seen. The electronic visual warning signal uses an extremely
reliable xenon flash tube. It flashes at least once every second. The strobe must not be
installed in direct sunlight or areas of high light intensity (over 60 foot candles) where the
visual flash might be disregarded or not seen. The strobe may not be seen by the visually
impaired.
The signal strobe may cause seizures. Individuals who have positive photoic response to
visual stimuli with seizures, such as persons with epilepsy, should avoid prolonged exposure
to environments in which strobe signals, including this strobe, are activated.
The signal strobe cannot operate from coded power supplies. Coded power supplies
produce interrupted power. The strobe must have an uninterrupted source of power in or
der to operate correctly. System Sensor recommends that the horn and signal strobe always
be used in combination so that the risks from any of the above limitations are minimized.
79936, USA. Please include a note describing the malfunction and suspected cause of
failure. The Company shall not be obligated to replace units which are found to be defec
tive because of damage, unreasonable use, modifications, or alterations occurring after
the date of manufacture. In no case shall the Company be liable for any consequential
or incidental damages for breach of this or any other Warranty, expressed or implied
whatsoever, even if the loss or damage is caused by the Company’s negligence or fault.
Some states do not allow the exclusion or limitation of incidental or consequential dam
ages, so the above limitation or exclusion may not apply to you. This Warranty gives you
specific legal rights, and you may also have other rights which vary from state to state.
can radiate radio frequency energy and, if not installed and used in accordance with the
instruction manual, may cause harmful interference to radio communications. Operation
of this equipment in a residential area is likely to cause harmful interference in which
case the user will be required to correct the interference at his own expense.
-
-
-
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.