System Sensor P2RK, P2WH, P2W, P4R, P4RH Installation And Maintenance Instructions Manual

...
INSTALLATION AND MAINTENANCE INSTRUCTIONS
3825 Ohio Avenue, St. Charles, Illinois 60174
Selectable Output Strobes, Horns, and Horn/Strobes
For use with the following models: P2R, P2RH, P2RK, P2RHK, P2W, P2WK, P2WH, P2WHK, P4R, P4RH, P4RK, P4W, P4WK, SR, SRH, SRK, SRHK, SW, SWK, SWH, SWHK, SW-CLR­ALERT, PC2R, PC2RH,PC2RK, PC2RHK, PC2W, PC2WK, PC2WH, PC2WHK, PC4R, PC4RH, PC4W, PC4WK, PC4WHK, SCR, SCRH, SCRK, SCRHK, SCW, SCWK, SCWH, SCWHK, SCW­CLR-ALERT, HR, HRK, HW, SR-P, SW-P, SRH-P, SWH-P,P2R-P, P2W-P, P2WH-P, P4R-P, P4W-P, SCW-P, PC2R-P, PC2W-P, PC2WH-P, SRK-P, SRHK-P, P2RK-P, P2RHK-P, SWK-P, SWHK-P,
P2WK-P, P2WHK-P, SR-SP, P2R-SP, PC2W-SP, SRK-R, SWK-R, SRHK-R, SWHK-R, P2RK-R, P2WK-R, P2RHK-R, P2WHK-R, SBHK, SBK-R
NOTE: All -R models are specifically designed for use with the WTP Series of Weatherproof plates NOTE: When replacing outdoor units; device and back box must be replaced NOTE: Models SBHK, SBK-R are UL listed for General Signaling
PRODUCT SPECIFICATIONS
Operating Temperature: Standard Products 32°F to 120°F (0°C to 49°C)
K Series –40°F to 151°F
Humidity Range: Standard Products 10 to 93% Non-condensing
K Series Meets NEMA 4X requirements
Strobe Flash Rate: 1 flash per second
Nominal Voltage: Regulated 12VDC/FWR or regulated 24DC/FWR
Operating Voltage Range (includes fire alarm panels with built in sync): 8 to 17.5V (12V nominal) or 16 to 33V (24V nominal)
Operating Voltage with MDL3 Sync Module: 8.5 to 17.5V (12V nominal) or 16.5 to 33V (24V nominal)
Input terminal wire gauge: 12 to 18 AWG
NOTE : Strobes will operate at 12 V nominal for 15 & 15/75 candela settings only. Switching between ranges is automatic.
DIMENSIONS FOR PRODUCTS AND ACCESSORIES
WALL PRODUCTS Length Width Depth CEILING PRODUCTS DIAMETER DEPTH
Strobe and Horn/Strobes (including lens)
Horns
SA-WBB Red Weatherproof Back Box
SA-WBBW White Weatherproof Back Box
SBBR Red Surface Mount Box
SBBW White Surface Mount Box
MOUNTING BOX OPTIONS
2-Wire Indoor Products 4-Wire Indoor Products K Series Products
4 × 4 × 11/2, Single Gang, Double Gang, 4˝ Octagon
SBBR/W (wall), SBBCR/W (ceiling)
5.6" 4.7" 2.5"
142 mm 119 mm 64 mm 173 mm 64 mm
5.6" 4.7" 1.3"
142 mm 119 mm 33 mm
5.7" 5.1" 2.0"
145 mm 130 mm 51 mm
5.6" 4.7" 4.3"
142 mm 119 mm 109 mm
4 × 4 × 11/2, Double Gang, 4˝ Octagon SA-WBB/W (wall), SA-WBBC/CW (ceiling)
Strobes and Horn/Strobes (including lens)
SA-WBBC Red Weatherproof Back Box
SA-WBBCW White Weatherproof Back Box
SBBCR Red Surface Mount Box
SBBCW White Surface Mount Box
NOTE: SA-WBB, SA-WBBW, SA-WBBC and SA-WBBCW dimensions do not include the two mounting tabs
800/736-7672, FAX: 630/377-6495
www.systemsensor.com
6.8" 2.5"
7.1" 2.2"
180 mm 51 mm
6.9" 5.3"
175 mm 135 mm
I56-2769-020R
NOTICE: This manual shall be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The SpectrAlert Advance series of notification appliances offers a wide range of horns, strobes, and horn/strobes, for wall and ceiling applications, indoors and outdoors. They are designed to be used on 12 or 24 volt, DC or FWR (full wave rectified) systems. These products are electrically backward compat­ible with the previous generation of SpectrAlert notification appliances. Horn/ strobe products are available in two versions. The 2-wire products fit systems where a single NAC controls both horn and strobe. The 4-wire products are in­tended for systems which have separate wiring circuits for the horn and strobe. All SpectrAlert Advance products are suitable for use in synchronized systems. The System Sensor MDL3 module may be used to provide synchronization.
K Series products are designed to be used over a wider range of temperatures and are suitable for use in wet environments with outdoor backbox supplied with product.
Wall and ceiling products may be used interchangeably (wall products may be used on the ceiling and ceiling products may be used on the wall.)
FIRE ALARM SYSTEM CONSIDERATIONS
The National Fire Alarm Code, NFPA 72, requires that all horns, used for building evacuation produce temporal coded signals. Signals other than those used for evacuation purposes do not have to produce the temporal coded sig­nal. System Sensor recommends spacing notification appliances in compli­ance with NFPA 72.
1 I56-2769-020R 06-10
LOOP DESIGN AND WIRING
The system designer must make sure that the total current drawn by the de­vices on the loop does not exceed the current capability of the panel supply, and that the last device on the circuit is operated within its rated voltage. The current draw information for making these calculations can be found in the tables within this manual. For convenience and accuracy, use the voltage drop calculator on the System Sensor website (www.systemsensor.com).
When calculating the voltage available to the last device, it is necessary to consider the voltage drop due to the resistance of the wire. The thicker the wire, the smaller the voltage drop. Wire resistance tables can be obtained from electrical handbooks. Note that if Class A wiring is installed, the wire length may be up to twice as long as it would be for circuits that are not fault tolerant.
NOTE: The total number of strobes on a single NAC must not exceed 40 for 24 volt applications or 12 for 12 volt applications. Loop resistance on a single NAC should not exceed 120 ohms for 24 volt and 30 ohms for 12 volt systems.
CANDELA SELECTION
Thisisgeneratedtextforfigtxt.
Adjust the slide switch on the rear of the product to the desired candela set­ting in the small window on the front of the unit. All products meet the light output profiles specified in the appropriate UL Standards. See Figures 1-3. Use Table 1 to determine the current draw for each candela setting. For K series products used outdoors at low temperatures, listed candela ratings must be reduced in accordance with Table 2.
NOTE: SpectrAlert products set at 15 and 15/75 candela automatically work on either 12V or 24V power supplies. The products are not listed for 12V op­erating voltages when set to any other candela settings. For 4-Wire products, total current draw may be determined by adding current draw for the specific candela selection and the current draw for the specific horn selection use Table 1 and Table 3.
FIGURE 1. LIGHT OUTPUT - VERTICAL DISPERSION, CEILING TO WALLS
TABLE 1. STROBE CURRENT DRAW (mA) FOR S, SC, P4 & PC4 SERIES:
Candela
8–17.5 Volts 16–33 Volts
DC FWR DC FWR
15 123 128 66 71
15/75 142 148 77 81
30 NA NA 94 96
Standard Candela Range
75 NA NA 158 153
95 NA NA 181 176 110 NA NA 202 195 11 5 NA NA 210 205
135 NA NA 228 207
High Candela Range
150 NA NA 246 220 177 NA NA 281 251 185 NA NA 286 258
TO FLOOR
Degrees*
Percent of
Rating
0 100
5-25 90
30-45 75
50 55 60 45 65 35 70 35 75 30 80 30 85 25 90 25
Figures 1-3 list the minimum light output requirements per UL1971.
FIGURE 2. LIGHT OUTPUT -
HORIZONTAL DISPERSION
Degrees*
Percent of
Rating
0 100
5-25 90
30-45 75
50 55 55 45 60 40 65 35 70 35 75 30 80 30 85 25 90 25
Compound 45
to the right
Compound 45
to the right
24
24
FIGURE 3. LIGHT OUTPUT - VERTICAL DISPERSION, WALL TO FLOOR
Degrees*
Percent of
Rating
TABLE 2. CANDELA DERATING:
Listed Candela
Candela rating at –40°F
(K Series Outdoor Applications Only)
15
Do not use below 32°F15/75 30 75 44 95 70
110 110
11 5 11 5 135 135 150 150 177 177 185 185
HORN SELECTION
Turn the rotary switch on the back of the product to the desired setting. For horn and 4-wire horn/strobe products, the current draw for each setting is listed in Table 3. For 2-wire horn/strobe products (P2 series), current draws are listed in Tables 4 and 5. The sound output measurement for each horn setting is shown in Table 6.
TABLE 3. HORN CURRENT DRAW (mA) FOR H, P4 & PC4 SERIES:
Pos Sound Pattern dA Out
8–17.5 Volts 16–33 Volts
DC FWR DC FWR 1 Temporal High 57 55 69 75 2 Temporal Medium 44 49 58 69 3 Temporal Low 38 44 44 48 4 Non-temporal High 57 56 69 75 5 Non-temporal Medium 42 50 60 69 6 Non-temporal Low 41 44 50 50 7 Coded High 57 55 69 75 8 Coded Medium 44 51 56 69 9 Coded Low 40 46 52 50
NOTE: In positions 7, 8, and 9, temporal coding must be provided by the NAC. If the NAC voltage is held constant, the horn output will remain constantly on. Positions 7, 8, and 9 are not available on 2-wire horn/strobe products.
0 100
5-30 90
35 65 40 46 45 34 50 27 55 22 60 18 65 16 70 15
*Tolerance of ±1 degree is permitted.
75 13 80 12 85 12 90 12
2 I56-2769-020R 06-10
Loading...
+ 2 hidden pages