System Sensor OSYEXP User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
CAUTION
OSYEXP Explosion Proof Gate Valve Supervisory Switch
Specifications
Contact Ratings: One SPDT (Form C) Switch 15 A @ 125/250/480 VAC; 1/8 HP @ 125 VAC, 1/4 HP @ 250 VAC 1/2 A @ 125 VDC; 1/4 A @ 250 VDC Dimensions: 7L X 3.125D X 4.875H Maximum Stem Extension: 2.875 Bracket Span: 7 Operating Temperature Range: –40° - 160°F (–40°C – 71°C) Shipping Weight: 2-1/4 lb. Enclosure Rating: UL Listed explosion proof switch enclosure for use in hazardous locations. Class I, Groups C and D; Class II, Groups E. F and G
Important
This manual contains important information about the installation and operation of supervisory switches. These instructions apply to System Sensor switches for outside screw and yoke valves only. Read all instructions carefully before beginning installation.
To prevent ignition of hazardous atmospheres, disconnect supply circuit before opening. Keep assembly tightly closed when in operation. Do NOT leave unused wires exposed.
All supervisory switch installations must comply with local codes and ordinances and the requirements of the author­ity having jurisdiction. Additional information is available in National Fire Protection Association standards NFPA 13, 13D, 13R, 71, and 72.
General Installation Considerations
The OSYEXP Supervisory Switch can be mounted on open yoke valves between 1/2″ and 12″ in diameter. The switch is designed to supervise the open condition of the OS & Y Gate Valve in hazardous locations.
All OSYEXP models are equipped with a ground screw inside the switch housing for those applications where grounding is required.
Narrow Yoke Valves
As Figure 1 suggests, installing the valve with mounting bolts inside the yoke is recommended. However, some valves may have yokes that are too narrow for this arrange­ment. If this is the case, the bolts can be positioned on the outside of the yoke.
Limited Clearance Valves
The OSYEXP mounting bracket fits most of the open yoke valves used in fire protection systems. However, some of these valves, especially those less than 11/2″ in diameter, have irregularly shaped yokes or such limited clearances that the clamping bar cannot be installed properly and/or it causes the valve to bind. If this is the case, the use of the supplied J-bolts is required to attach the OSYEXP to the valve (see J-Bolt Detail, Figure 1).
Installation Procedure
See Figures 2 and 3, as required, while performing the pro­cedure that follows.
Perform step 1 on valves 11/2″ in diameter and smaller only. Proceed directly to step 2 if the switch is being installed on a valve larger than 11/2″ in diameter.
1. Remove and discard the two C-clips and roller from the actuating lever.
2. Set the valve to its fully open position. Remove the OSYEXP Supervisory Switch from the carton and adjust the position of the retaining washers to provide suffi­cient bolt length for the yoke thickness of the valve.
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
D770-27-00 1 I56-1429-002R
Figure 1:
Switch Housing
Actuating Lever
Mounting Bracket
Yoke
Retaining Washer
Nut
Hex Wrench
Clamping Bar
Carriage Bolt
Slide Clamping Bar to remove or install
W0182-00
J-Bolt Detail:
NOTE:
Larger gate valve shown (2 through 12). When install­ing supervisory switch to smaller gate valves (1/2″ through 11/2″), carriage bolts are to be located on outboard side of yoke. On small valves with limited clearance, J-bolts may be used.
W0207-00
D770-27-00 2 I56-1429-002R
Loading...
+ 2 hidden pages