System Sensor MOD2W User Manual

I56-4001-000
i3 Series Loop Test/Maintenance Module MOD2W
*For use with 2-Wire i3 series smoke detectors 2W-B, 2WT-B, and (one) 2WTR-B
SPECIFICATIONS
Electrical Specifications
Power Supply Voltage: Resettable power; Min. 8.5 Volts DC (Power limited); Max. 35 Volts DC (Power limited); Device Power-up Time: 200 milliseconds Max. Standby Current: 60mA Max. Alarm Current: 185mA Nom. Standby Current: 38mA@12V, 20mA@24V Alarm Contact Rating: 100 mA @ 36 Volts DC, resistive, 25 ohms Maintenance Contact Rating: 100 mA @ 36 Volts DC, resistive, 25 ohms Max. IDC Loop Wiring Resistance: 50 Ohms Min. Reset Time: 300 milliseconds Initial Communication Cycle: 6 minutes EZ Walk Test Availability: 6 minutes after power up or panel reset
Physical Specifications
Operating Temperature Range: 0 - 50° C (32 - 122° F) Operating Humidity Range: 5 - 95% RH Storage Temperature Range: -20 - 70° C (-4 - 158° F) Height: 6.04 inches Width: 6.04 inches Depth: 1.16 inches Shipping Weight: 0.6 lbs Wire Gauge Acceptance: Min: 22 AWG; Max: 14 AWG
2-wire Compatibility Requirements
Min. Loop Voltage: 12.6 Volts DC Max. Loop Voltage: 14.52 Volts DC Max. Loop Resistance: 50 Ohms Max. Loop Ripple: 240 mVpp Max. Loading Capacitance: 0.01 mF Max. Alarm Current: 43.5 mA Max. Reset Voltage: 0.30 Volts DC Alarm Delay: n/a Min. Alarm Reset Time: 0.3 seconds Max. Normal Load Current: 1.2 mA Zone Type: Standard EOL Device: 3.9k Ohms (+-5%) Loop Style: B and D Compatibility Zone Identifier: A Detector Zone Identifier: A Max. Detectors Per Zone: (12) 2-wire i3 series model #2W-B, 2WT-B, (one) 2WTR-B
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6583
www.systemsensor.com
BEFORE INSTALLATION
This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the module will be installed in an existing operational system, inform the operator and local authority that the system will be temporarily out of service. Discon­nect power to the control panel before installing the module.
Notice: This manual should be left with the owner/user of this equipment. This product is intended for use in ordinary indoor locations.
GENERAL DESCRIPTION
The MOD2W allows a control panel to receive a “need for maintenance” sig­nal from two–wire i3 series smoke detectors, model numbers 2W–B, 2WT–B and one 2WTR-B. The module uses a form C zone relay to initiate “out of sen­sitivity” and “freeze trouble”, a form A zone alarm relay and a second form A zone relay to indicate loop fault. An EZ Walk Test puts all detectors on the loop into a Walk Test mode for easy verification of detector loop wiring. The module allows 2-wire smoke detectors to be used on any compatible 4-wire control panel and provides Style D wiring on the detector loop.
VISIBLE ANNUNCIATON
The MOD2W has three visible LED’s: The green LED is a supervisory LED; it blinks during power on, reset, and during normal operation. The yellow LED
SS-560-000 1 I56-4001-000
is used to indicate a loop wiring fault and will blink when it is in EZ Walk test mode. The red LED signals smoke events; it blinks during smoke maintenance events and lights constantly during smoke alarm events.
FIGURE 1: MODULE FRONT VIEW
Green LED
Yellow LED
Red LED
EZ Walk Test Switch
S0331-02
TABLE 1: OPERATION MODES
HOLE FOR MOUNTING
OPERATION MODE
Normal (standby) Blink 5 Sec. OFF OFF
No power/Non-operational OFF OFF OFF
Loop wiring fault Blink 5 Sec. ON OFF
EZ Walk Test Mode Blink 5 Sec. Blink 5 Sec. OFF
Alarm Smoke Blink 5 Sec. OFF ON
Maintenance Blink 5 Sec. OFF Blink 5 Sec.
Freeze Trouble Blink 5 Sec. OFF Blink 10 Sec.
GREEN
LED
YELLOW
LED
RED LED
NORMAL (STANDBY)
The module is powered and detectors on the loop are operating normally.
NO POWER/NON-OPERATIONAL
Power is not applied to the module or communication between the module and the detectors on the loop is unsuccessful.
LOOP WIRING FAULT
If an open circuit occurs on the loop, the module will indicate the condition by illuminating the yellow LED. 2-wire units will then power the style-D ter­minals. When the wiring issue on the loop has been resolved, the module will turn the yellow LED off.
EZ WALK TEST MODE
This indicates the module and detectors are in EZ Walk Test Mode. See “EZ Walk Test” section for instructions on how to initiate and perform the EZ Walk test.
ALARM SMOKE
A smoke alarm will be indicated by the red LED.
A smoke alarm is not self-restoring. Once a smoke alarm has been signaled, the red LED will illuminate until the module is reset by removal of power.
MAINTENANCE
This condition means one or more detectors on the loop have a smoke main­tenance issue. See “Smoke Maintenance Inquiry” section for further details.
FREEZE TROUBLE
This condition means one or more detectors on the loop are measuring the ambient temperature is near the freezing point. See “Freeze Trouble Inquiry” section for further details.
INSTALLATION MOUNTING
The module can be mounted to a 4-11/16 inch back box or inside a listed, dedi- cated enclosure. When mounting inside an enclosure with pre-stamped holes, it may be easier to align the bottom screw hole first. It is not necessary to use the module cover when mounting inside an enclosure.
FIGURE 2: MOUNTING
TO VISTA ENCLOSURE
(No. 6x3/4 Type AB)
WIRING GUIDELINES
All wiring must be installed in compliance with the NFPA 70 standards, Na­tional Electrical Code, applicable state and local codes, and any special re­quirements at the local Authority Having Jurisdiction (AHJ).
The screw terminals in the mounting base will accept 14-22 gauge wire. Wire connections are made by stripping approximately ¼” of insulation from the end of the feed wire, inserting it into the proper base terminal, and tightening the screw to secure the wire in place. Do not put wires more than 2 gauge apart under the same clamping plate.
WARNING
Remove power from alarm control unit or initiating device circuits before in­stalling detectors.
WIRING DIAGRAMS
Install module wiring in accordance with appropriate wiring diagrams. (Figure 3)
The module relays have a maximum ON resistance of 25 ohms. This resis­tance plus the wiring resistance to the panel must be less than the maximum zone wiring resistance stated in the panel manual.
NOTE: If 2–wire i3 detectors are used in conjunction with a style D initiat­ing circuit, the MOD2W must be used to provide that capability. Ground fault on a module’s 2-wire loop can be indicated at a control panel if the control panel is capable of ground fault detection on the power supply to the module and meets NFPA 72 ground fault indication requirements for initiating device circuits. The installer must verify that capability.
TABLE 2: DIP SWITCH CONFIGURATIONS
DIP SWITCH # 1 DIP SWITCH # 2 DIP SWITCH # 3
ON
(DEFAULT)
OFF
Unused
Unused
Smoke Maint on
Smoke Trouble and
Form-B Maint Relay
Smoke Maint on
Form-B Smoke main-
tenance Relay only
Unused
Unused
POWER UP AND COMMUNICATIONS COMMUNICATIONS CHECK
Upon power up, the module will send a request for communication check. All compatible detectors on the loop that understand the communication protocol will respond. If all detectors respond correctly, the green LED will blink once every 5 seconds. If the module does not get a response, it will turn off the green LED and continue to try every 2 minutes until a response is received.
SMOKE MAINTENANCE INQUIRY
The module sends a smoke maintenance inquiry to the detectors every 24 hours. If a response indicating a maintenance problem is received, the red LED on the module will blink once every 5 seconds and a smoke maintenance condition will be indicated to the panel. It is likely that the detector needs to be cleaned or replaced, refer to the detector instruction manual for mainte­nance instructions.
FREEZE TROUBLE INQUIRY
The module sends a freeze trouble inquiry to the detectors every four hours. If a response indicating a freeze problem is received, the red LED on the module will blink once every 10 seconds and a smoke maintenance condition will be indicated to the panel.
SLOT FOR MOUNTING TO VISTA ENCLOSURE
(No. 6x5/16Type AB or Type F)
SLOTS FOR MOUNTING
TO 4-11/16 JUNCTION BOX
S0332-00
SS-560-000 2 I56-4001-000
OR
FIGURE 3: MOD2W WIRING DIAGRAM
SMOKE
AUXPOWER
(resettable)
SMOKE
ZONE
ALL CIRCUITS ARE SUPERVISED
AND MUST BE POWER LIMITED
Note: See Table 2 for dip switch configurations
Panel
EOL
Resistor
3.9K EOL
RESIST
MAINT.
ZONE
Panel
EOL
Resistor
FIGURE 4: MODULE TERMINALS
POWER IN + POWER IN –
SMOKE ALARM CONTACT
MAINTENANCE TROUBLE RELAY CONTACT
UNUSED
UNUSED
MOD2W
(
1 )
+ IN
2W-B or 2WT-B
RA100Z
(
(
(
(
5
4
3
2
)
)
)
)
RA –
RA +
– IN/OUT
+ OUT
LOOP STYLE D / CLASS A WIRING
RA100Z
(
(
(
(
(
1 )
+ IN
2 )
+ OUT
4
3
)
)
RA +
– IN/OUT
5 )
RA –
2W-B or 2WT-B
SMOKE ZONE EOL RESISTOR (VALUE DEFINED BY PANEL)
UNUSED
IDC + IDC –
STYLE D + /CLASS A
STYLE D – /CLASS A
UNUSED
S0335-00
S0334-03
SS-560-000 3 I56-4001-000
TESTING
Modules must be tested after installation and following periodic maintenance. Testing should be performed at least once per year.
NOTE: Before testing, notify the proper authorities that the system will be temporarily out of service. Disable the zone or system to prevent any un­wanted alarms.
EZ WALK TEST
The communication loop between the module and detectors can be manually tested by putting the module and detectors into EZ Walk test mode.
The EZ Walk loop test verifies the initiating loop wiring and provides visual status indication at each detector:
1. Ensure proper wiring and power is applied. Wait approximately 5 min­utes from power-up before performing the EZ Walk test. The green LED on the module must be blinking indicating the module is in ready/ standby mode to start the EZ Walk mode.
2. Locate the EZ Walk recessed test switch located behind the module cover (See Figure 1). Depress the test switch with a small screwdriver. The yellow LED will blink showing that the module and detectors are in EZ Walk mode for 5 minutes.
3. Observe the LEDs at each detector to make sure the green LED is double blinking every 5 seconds as listed in Table 3.
4. At the end of the five minute period, the module will terminate EZ Walk and the yellow LED will stop blinking. The EZ Walk test period can be extended by pressing the test switch multiple times. Each press will add 5 minutes of additional time.
If a module or detector fails the test, its wiring should be checked. If the module still fails, it should be replaced. Notify the proper authorities when all testing has been completed.
NOTE: The EZ Walk loop test should not be used in lieu of functional testing (alarm, trouble and other functional tests) of the system.
TABLE 3: EZ WALK TEST DETECTOR MODES
DETECTOR
GREEN LED
PROPER OPERATION
OUT OF SENSITIVIY
FREEZE CONDITION
Double Blink 5 Seconds OFF
OFF Double Blink 5 Seconds
OFF Double Blink 10 Seconds
DETECTOR
RED LED
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installa­tion. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures: – Reorient or relocate the receiving antenna. – Increase the separation between the equipment and receiver. – Connect the equipment into an outlet on a circuit different from that to which the receiver is connected. – Consult the dealer or an experienced radio/TV technician for help.
System Sensor warrants its enclosed product to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes no other express warranty for the enclosed product. No agent, representative, dealer, or employee of the Company has the authority to in­crease or alter the obligations or limitations of this Warranty. The Company’s obligation of this Warranty shall be limited to the replacement of any part of the product which is found to be defective in materials or workmanship under normal use and service during the three year period commencing with the date of manufacture. After phoning System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Returns Department, RA
FCC STATEMENT
THREE-YEAR LIMITED WARRANTY
#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing the malfunction and suspected cause of failure. The Company shall not be obligated to replace units which are found to be defective because of damage, unreasonable use, modifications, or alterations occurring after the date of manufacture. In no case shall the Company be liable for any consequential or incidental damages for breach of this or any other Warranty, expressed or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
SS-560-000 4 I56-4001-000 ©2013 System Sensor