INSTALLATION AND MAINTENANCE INSTRUCTIONS
MDL3 Series Sync Module
For use with the following series models:
UL & ULC listed models: CHRX, CHWX, CHSRX, CHSWX, HRX, HWX, MHR(A), MHW(A), P2RX, P2WX, P4RX, P4WX,
PC2WX, PC4RX, PC4WX, PC24XX, PC2RX, SCRX, SCWX, SC24XX, SRX, SWX, B200S(A), B200SR(A)
UL listed: SP2C24XX, SPSX, SPSCX, SEP-SW, SEP-SPSW
ULC listed models: HC12/24X, SPSX (V models only), SPSCX (V models only), MHRZA, MHWZA, SEP-SW(A), SEP-SPSW(A)
Obsolete models (for reverse compatibility reference):
CHX, CH24MCX, H12/24X, PA400X, S1224MCX, SP2R1224MCX, SP2W1224MCX
Refer to System Sensor product installation manuals for model specifications.
SPECIFICATIONS
Input Voltage Range: Regulated: 12VDC/FWR (8.0 to 17.5V); or 24VDC/FWR (16.0 to 33V)
Maximum Load on Loop: 3 A
Current Draw:
Voltage
DC FWR DC FWR
NAC Slave Input (3)
12 V 10mA 12mA 3.5mA 4mA
24 V 12mA 15mA 4.5mA 5mA
Operating Temperature: 32°F to 120°F (0°C to 49°C)
Listings: UL464, UL1971, ULC S525, ULC S526
NOTE: 1) For maximum number of strobes and/or maximum line impedance, refer to the voltage drop calculator found at Systemsensor.com; and 2) Maximum
line impedance as required by the fire alarm control manufacturer. 3) Current draw of NAC Slave input when connected as in figure 3.
GENERAL DESCRIPTION
The MDL3 Module is designed to work with the SpectrAlert Advance series
of notification appliances to provide a means of synchronizing the temporalcoded horns and chimes, synchronizing the one-second flash timing of the
strobe, and silencing the horns and chimes of the horn/strobe and chime/
strobes combination over a two-wire circuit while leaving the strobes active.
MDL3 is intended to connect to UL or ULC listed FACP or its NAC accessories
(e.g. a boost module, etc.)
NOTICE: This manual shall be left with the owner/user of this equipment.
MODULE CONFIGURATION
Each MDL3 module has the capability of connecting two Style Y (Class B)
circuits or one Style Z (Class A) circuit.
The zone output(s) from the panel are connected to the zone input(s) of the
MDL3 module and the zone output(s) from the MDL3 module are connected
to the notification loop(s). Supervision is accomplished in the module by a
direct connection between the zone input and the zone output of each of the
two zone circuits connected to the normal end-of-line device. The FACP “sees”
the EOL device through the MDL3 module. When either or both outputs
from the module are wired to the SpectrAlert Advance products, the horns or
The MDL3 module can be configured so that more than two zones can
be synchronized by the interconnection of the slave input and output
(see Figures 1, 2, and 3).
SYNCHRONIZE SPECTRALERT ADVANCE HORNS, CHIMES AND STROBES
• Each module can power two 3-amp circuits wired in class B or one
3-amp circuit powered as Class A.
• Each module will synchronize 2 zones.
• Additional modules can be added and may be synchronized to all other
modules by interconnecting the “slave” input and output terminals
between modules.
CONTROLLING SOUNDER ON/OFF OVER 2-WIRES USING MODULE
HORN CONTROL
• Connect the current source to the horn control input. If a zone output
is used for the source, you must use an EOL on the horn control input
terminal, see Figure 1.
• When multiple modules are used, the horn control circuits can be wired
in parallel. If wired in parallel and a zone output is used from panel, use
an EOL on the last module for supervision.
chimes and strobes in both zones will be synchronized.
3825 Ohio Avenue, St. Charles, Illinois 60174
1.800.SENSOR2; Fax: 630.377.6495
www.systemsensor.com
When Strobes are connected to sync module, MDL3 input voltage range at 12V: 8.5 to
17.5VDC/FWR; at 24V 16.5 to 33VDC/FWR
I56-3157-004R
This input powers the MDL3 module. This input must
Zone 1 Input
have voltage present from the FACP before anything
will work. This also supplies voltage to Zone 1 output.
This input only supplies voltage to Zone 2 output.
Zone 2 Input
Note: If Zone 1 input is not powered, the notification
devices attached to the Zone 2 output will be out of
synch.
This input enables the horns on the SpectrAlert
Horn Control
Advance notification appliances. Voltage present
means horns are enabled. No voltage present means
horns are disabled.
Connects to Master MDL3 Module slave out.
Slave In
mum of 11 slave MDL3 modules can be connected to a
Master MDL3.
Slave Out Connects to Slave MDL3 slave in.
NAC Slave In
Connects to slave MDL3 from NAC. A dedicated NAC
should be used for slaving purposes.
A maxi-
mon enclosure of FACP
Slave Out – Slave In wiring must be contained within either the common
enclosure of modules or enclosures within 20 feet of each other with wiring
inside conduit. Reverse wiring will cause this input to malfunction.
If Zone 1 input is not powered or fails during alarm, the notification devices
attached to the Zone 2 output will not be synchronized.
NOTE: Ground fault on a module’s two wire loop can be indicated at the
control panel if the control panel is capable of ground fault detection on the
power supply to the module and meets UL 864 9th Edition ground fault indication requirements for initiating device circuits. The installer must verify
that capability.
Zone 1 – NAC slave wiring must be dedicated to sync purposes. No devices
shall be attached. EOL must be used on the last MDL3 for supervision.
(1) The value of EOL should refer to FACP specification or installation instruction.
SS-110-000 1 I56-3157-004R
Unless it’s supervised, Horn Control wiring must be contained within com-
FIGURE 1. HORNS SILENCED OVER TWO WIRE CIRCUIT:
NOTE: If zone 1 output of module is connected to strobes, chime/strobes or horn/
strobes, zone 1 input supply power must be continuous for proper operation.
MASTER MODULE HORN CONTROL CONNECTS TO INTERRUPTABLE POWER SOURCE
FACP #1
NAC 1
NAC 2
NAC 3
FACP #2
NAC 1
+
B+
}
–
B–
+
B+
}
–
B–
+
B+
}
–
B–
B+
+
}
B–
–
A+
+
}
A–
–
EOL
(1)
+
–
+
–
+
–
+
–
+
–
+
–
+
–
+
–
HORN
CONTROL
}
ZONE 1
IN
}
ZONE 2
IN
}
SLAVE
IN
}
HORN
CONTROL
}
ZONE 1
IN
}
ZONE 2
IN
}
SLAVE
IN
}
MASTER
SLAVE IN
TEMP JUMP OFF
SLAVE
SLAVE IN
TEMP JUMP OFF
ZONE 1
OUT
ZONE 2
OUT
NAC
SLAVE
OUT
ZONE 1
OUT
ZONE 2
OUT
NAC
SLAVE
OUT
+
}
–
+
}
–
+
}
–
+
}
–
+
}
–
+
}
–
+
}
–
+
}
–
TO NEXT
SPECTRALERT
ADVANCE DEVICE
OR EOL (1)
2 STYLE Y ZONES
(CLASS B)
TO NEXT
SPECTRALERT
ADVANCE DEVICE
OR EOL (1)
WIRING MUST BE
CONTAINED WITH EITHER
THE COMMON ENCLOSURE
OF MODULES OR
ENCLOSURES WITHIN 20
FEET OF EACH OTHER WITH
WIRING INSIDE CONDUIT
TO NEXT
SPECTRALERT
ADVANCE DEVICE
TO NEXT
SPECTRALERT
ADVANCE DEVICE
STYLE Z ZONES
(CLASS A)
A0414-01
FIGURE 2 MASTER-SLAVE MODE:
NOTE: If zone 1 output of module is connected to strobes, chime/strobes or horn/
strobes, zone 1 input supply power must be continuous for proper operation.
FACP
B+
NAC 1
}
B–
B+
NAC 2
}
B–
(STYLE Z CLASS A)
B+
NAC 3
}
B–
A+
}
A–
+
–
+
–
+
–
+
–
+
}
–
+
}
–
+
}
–
+
}
–
+
}
–
+
}
–
+
}
–
+
}
–
HORN
CONTROL
ZONE 1
IN
ZONE 2
IN
SLAVE
IN
HORN
CONTROL
ZONE 1
IN
ZONE 2
IN
SLAVE
IN
MASTER
SLAVE IN
TEMP JUMP OFF
SLAVE
SLAVE IN
TEMP JUMP OFF
ZONE 1
OUT
ZONE 2
OUT
NAC
SLAVE
OUT
ZONE 1
OUT
ZONE 2
OUT
NAC
SLAVE
OUT
+
}
–
+
}
–
+
}
–
+
}
–
+
}
–
+
}
–
+
}
–
+
}
–
TO NEXT
SPECTRALERT
ADVANCE DEVICE
OR EOL (1)
2 STYLE Y ZONES
(CLASS B)
TO NEXT
SPECTRALERT
ADVANCE DEVICE
OR EOL (1)
WIRING MUST BE
CONTAINED WITH EITHER
THE COMMON ENCLOSURE
OF MODULES OR
ENCLOSURES WITHIN 20
FEET OF EACH OTHER WITH
WIRING INSIDE CONDUIT
TO NEXT
SPECTRALERT
ADVANCE DEVICE
TO NEXT
SPECTRALERT
ADVANCE DEVICE
STYLE Z ZONES
(CLASS A)
A0415-01
FIGURE 3. MASTER-SLAVE USING NAC-SLAVE INPUT:
NOTE: If zone 1 is connected to synchronize other MDL3 no devices shall be
attached to this zone. Zone 1 input supply power must be continous to be
operational.
TO NEXT
SPECTRALERT
ADVANCE DEVICE
OR EOL (1)
TO NEXT
SPECTRALERT
ADVANCE DEVICE
OR EOL (1)
TO NEXT MDL3 NAC
SLAVE IN OR EOL (1)
2 STYLE Y ZONES
(CLASS B)
FACP
NAC 1
NAC 2
FACP
B+
NAC 1
}
B–
B+
NAC 2
}
B–
B+
+
}
B–
–
B+
+
}
B–
–
+
–
+
–
+
–
+
–
+
–
+
–
HORN
CONTROL
}
ZONE 1
IN
}
ZONE 2
IN
}
SLAVE
IN
}
+
}
–
+
}
–
+
}
–
+
}
–
MASTER
SLAVE IN
TEMP JUMP OFF
HORN
CONTROL
ZONE 1
IN
SLAVE
ZONE 2
IN
SLAVE
IN
TEMP JUMP OFF
ZONE 1
OUT
ZONE 2
OUT
NAC
SLAVE
OUT
+
ZONE 1
OUT
}
–
+
ZONE 2
OUT
}
–
+
NAC
SLAVE IN
}
–
+
SLAVE
OUT
}
–
+
}
–
+
}
–
+
}
–
+
}
–
TO NEXT SPECTRALERT
ADVANCE DEVICE OR EOL (1)
A0416-01
FIGURE 4. WIRING FOR CODED SUPPLIES:
MULTI CODE
SOURCE
MDL
HC
Z1
IN OUT
SPECTRALERT
HORN STROBE
HORN
POWER
STROBE
POWER
SPECTRALERT
HORN ONLY
TO NEXT
}
DEVICE
OR EOL (1)
TO NEXT
}
HORN
POWER
OR
EOL (1)
A0265-01
NOTE: Horn control must be powered for horn/strobes to operate the horn portion.
NOTE: SpectrAlert Advance horn-only/chime-only and horn/strobe or chime/
strobe devices must be set to coded for multi-code sourcing.
FIGURES 5 & 6. MOUNTING DIAGRAM:
BARRIER STRIPS
A0423-00
1. Fold barrier strip flat and complete field wiring. Input terminal wire
gauge: 12 to 18 AWG.
2. Fold barrier strips toward terminal block and mount unit to back box with
screws provided. Back box must be 4-11/16˝ x 4-11/16˝ x 2-1/8˝ deep.
Please refer to insert for the Limitations of Fire Alarm Systems
The sounder and/or strobe will not work without power. The sounder/strobe gets its power from the
fire/security panel monitoring the alarm system. If power is cut off for any reason, the sounder/strobe
will not provide the desired audio or visual warning.
The sounder may not be heard. The loudness of the sounder meets (or exceeds) current Underwriters
Laboratories’ standards. However, the sounder may not alert a sound sleeper or one who has recently
used drugs or has been drinking alcoholic beverages. The sounder may not be heard if it is placed on
a different floor from the person in hazard or if placed too far away to be heard over the ambient noise
such as traffic, air conditioners, machinery or music appliances that may prevent alert persons from
hearing the alarm. The sounder may not be heard by persons who are hearing impaired.
The signal strobe may not be seen. The electronic visual warning signal uses an extremely reliable
xenon flash tube. It flashes at least once every three seconds and exceeds current Underwriters
Laboratories standards for private mode viewing. The visual warning signal is suitable for direct view-
System Sensor warrants its enclosed product to be free from defects in materials and workmanship under normal use and service for a period of three years from date of manufacture. System Sensor makes
no other express warranty for the enclosed product. No agent, representative, dealer, or employee of
the Company has the authority to increase or alter the obligations or limitations of this Warranty. The
Company’s obligation of this Warranty shall be limited to the replacement of any part of the product
which is found to be defective in materials or workmanship under normal use and service during the
three year period commencing with the date of manufacture. After phoning System Sensor’s toll free
number 800-SENSOR2 (736-7672) for a Return Authorization number, send defective units postage prepaid to: System Sensor, Returns Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.
SS-110-000 2 I56-3157-004R
©2012 System Sensor
THE LIMITATIONS OF SOUNDER/STROBES
ing and must be installed within an area where it can be seen by building occupants. The strobe must
not be installed in direct sunlight or areas of high light intensity (over 60 foot candles) where the visual
flash might be disregarded or not seen. The strobe may not be seen by the visually impaired and is not
intended to meet American Disabilities Act (ADA) requirements.
The signal strobe may cause seizures. Individuals who have positive photic response to visual stimuli
with seizures, such as persons with epilepsy, should avoid prolonged exposure to environments in
which strobe signals, including this strobe, are activated.
The signal strobe cannot operate from coded power supplies. Coded power supplies produce interrupted
power. The strobe must have an uninterrupted source of dc power in order to operate correctly. System
Sensor recommends that the sounder and signal strobe always be used in combination so that the risks
from any of the above limitations are minimized.
THREE-YEAR LIMITED WARRANTY
Please include a note describing the malfunction and suspected cause of failure. The Company shall not
be obligated to replace units which are found to be defective because of damage, unreasonable use,
modifications, or alterations occurring after the date of manufacture. In no case shall the Company be
liable for any consequential or incidental damages for breach of this or any other Warranty, expressed
or implied whatsoever, even if the loss or damage is caused by the Company’s negligence or fault. Some
states do not allow the exclusion or limitation of incidental or consequential damages, so the above
limitation or exclusion may not apply to you. This Warranty gives you specific legal rights, and you may
also have other rights which vary from state to state.