System Sensor MDL, MDLW User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
CAUTION
I56-0983-015R
MDL Module
For use with the following series models: P2RX, P2WX, P4RX, P4WX, SRX, SWX, SCRX, SCWX, HRX, HWX, CHX, CHRX, CHWX, CHSRX, CHSWX, PC2RX, PC2WX, PC4RX, PC4WX, H12/24X, HC12/24X, PA400X, S1224MCX, SC24XX, P1224MCX, PC24XX, SP2C24XX, SP2R1224MCX, SP2W1224MCX, CH24MCX, MHR(A), MHW(A), MHRZA, MHWZA Refer to System Sensor product installation manuals for model specifications. U.S. Patent Nos. 5,850,178 and 5,598,139
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
Specifications
Input Voltage Range: DC or Full Wave Rectified 9 to 33 Volts
When MDL module is used, supply volt­age range at 12 volts: 9 to 17.5 VDC; at 24 volts: 17 to 33 VDC
Maximum Load on Loop: 3 A Current:
Voltage
Average Peak In-rush
DC FWR DC FWR DC FWR
12 V 10mA 12mA 30mA 31mA 87mA 122mA 24 V 12mA 15mA 35mA 37mA 198mA 262mA
Operating Temperature: 0°C to 49°C (32°F to 120°F) Listings: UL S4011, S5512
Note for Strobes – Do not exceed: 1) 9-17.5 or 17-33 voltage range limits when the MDL module is used; 2) Maximum number of strobe lights and/or maximum line impedance specified in the strobe product installation manual; and 3) Max­uimum line impedence as required by the fire alarm control manufacturer.
General Description
The MDL Module is designed to work with the SpectrAlert series of notification appliances to provide a means of synchronizing the temporal-coded horns and chimes, syn­chronizing the one-second flash timing of the strobe, and silencing the horns and chimes of the horn/strobe and chime/strobes combination over a two-wire circuit while leaving the strobes active.
NOTICE: This manual shall be left with the owner/user of this equipment.
Module Configuration
Each MDL module has the capability of connecting two Style Y (Class B) circuits or one Style Z (Class A) circuit.
The zone output(s) from the panel are connected to the zone input(s) of the MDL module and the zone output(s) from the MDL module are connected to the notification loop(s). Supervision is accomplished in the module by a direct con­nection between the zone input and the zone output of each of the two zone circuits connected to the normal end-of-line device. The FACP “sees” the EOL device through the MDL module. When either or both outputs from the module are wired to the SpectrAlert products, the horns or chimes and strobes in both zones will be synchronized.
The MDL module can be configured so that more than two zones can be synchronized by the interconnection of the slave input and output (see Figures 1 and 2).
Zone 1 Input: This input powers the MDL module. This
input must have voltage present from the FACP before anything will work. This also supplies voltage to Zone 1 output.
Zone 2 Input: This input only supplies voltage to Zone 2
output. Note: If Zone 1 input is not powered, the notification devices attached to the Zone 2 output will not be powered.
Horn Control: This input enables the horns on the SpectrAlert
notification appliances. Voltage present means horns are enabled. No voltage present means horns are disabled.
Slave In: Connects to Master MDL Module slave out.
Slave Out: Connects to Slave MDL slave in.
D900-14-00 1 I56-0983-015R
TEMP. JUMPER OFF
NAC2
NAC1
FACP
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
HORN CONTROL
ZONE 1
OUT
ZONE 1 IN
ZONE 2 IN
SLAVE IN
ZONE 2
OUT
SYNC
ERROR
SLAVE
OUT
SEPARATE
MONITORING
INPUT
EOL
TO NEXT
SPECTRALERT
DEVICE OR
EOL
NAC3
NAC2
MASTER MODULE
SLAVE MODULE
NAC1
TO NEXT
SPECTRALERT
DEVICE OR
EOL
All SpectrAlert horns, horn/strobes, and strobes will operate in sync.
NAC2
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
HORNS SILENCED OVER TWO WIRE CIRCUIT
MASTER MODULE HORN CONTROL CONNECTS TO INTERRUPTABLE POWER SOURCE
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
HORN CONTROL
ZONE 1
OUT
ZONE 1 IN
ZONE 2 IN
SLAVE IN
ZONE 2
OUT
SYNC
ERROR
SLAVE
OUT
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
HORN CONTROL
TEMP JUMPER OFF
ZONE 1
OUT
ZONE 1 IN
ZONE 2 IN
SLAVE IN
ZONE 2
OUT
SYNC
ERROR
SLAVE
OUT
TEMP JUMPER OFF
FACP #1
FACP #2
TO NEXT
SPECTRALERT
DEVICE OR
EOL
TO NEXT
SPECTRALERT
DEVICE OR
EOL
NAC1
(+)
(–)
EOL
Synchronize SpectrAlert Horns, Chimes and Strobes
CAUTION
CAUTION
CAUTION
CAUTION
CAUTION
CAUTION
• Each module can power two 3-amp circuits wired in class B or one 3-amp circuit powered as Class A.
• Each module will synchronize 2 zones.
• Additional modules can be added and may be syn­chronized to all other modules by interconnecting the “slave” input and output terminals between modules.
Horn control wiring must be contained within common en­closure of module.
Slave Out – Slave In wiring must be contained within either the common enclosure of modules or enclosures within 20 feet of each other with wiring inside conduit.
If Zone 1 input is not powered or fails during alarm, the notification devices attached to the Zone 2 output will not be powered.
Controlling Sounder On/Off Over 2-Wires Using Mod­ule Horn Control
• Connect the current source to the horn or chime control input. If a zone output is used for the source, you must use an EOL on the horn control input terminal.
• When multiple modules are used, the horn or chime control circuits can be wired in parallel. If wired in par­allel and a zone output is used from panel, use an EOL on the last module for supervision.
Horn/chime control wiring must be contained within com­mon enclosure of module.
Slave Out – Slave In wiring must be contained within either the common enclosure of modules or enclosures within 20 feet of each other with wiring inside conduit.
If Zone 1 input is not powered or fails during alarm, the notification devices attached to the Zone 2 output will not be powered.
Special Considerations
A latching relay contact is provided in case the synchro­nizing signal to the notification devices is interrupted. The output can be wired so that a trouble signal will be annun­ciated at the panel. If the synchronization pulse fails in the MDL module, the strobes will shut off.
D900-14-00 2 I56-0983-015R
Figure 1: Single MDL Using Sync Error (for panels with the capability to check for sync error)
NOTE: If zone 1 output of module is connected to strobes, chime/strobes or horn/strobes, zone 1 input supply power must be continuous for proper operation.
A0262-00
Figure 2:
NOTE: If zone 1 output of module is connected to strobes, chime/strobes or horn/strobes, zone 1 input supply power must be continuous for proper operation.
A0182-00
HORN
POWER
STROBE POWER
MULTI CODE
SOURCE
ANY SPECTRALERT
HORN STROBE
TO NEXT HORN POWER OR EOL
SPECTRALERT
HORN ONLY
}
TO NEXT DEVICE OR EOL
}
MDL
HC
Z1
IN OUT
CAUTION
Horns will be Temporal coded and in sync.
TEMP. JUMPER ON
TO NEXT
DEVICE OR
EOL
TO NEXT
DEVICE OR
EOL
NAC2
NAC1
FACP
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
HORN CONTROL
ZONE 1
OUT
ZONE 1 IN
ZONE 2 IN
SLAVE IN
ZONE 2
OUT
SYNC
ERROR
SLAVE
OUT
MA12/24D OR PA400
HORN
ONLY
MA12/24D OR PA400
HORN
ONLY
NOTE: The MDL Module is factory set with the sync error
MASTER MODULE
SLAVE MODULE
TO NEXT
DEVICE OR
EOL
TO NEXT
DEVICE OR
EOL
All SpectrAlert horns, horn/strobes, and strobe only devices will operate in sync.
NOTE: The panel (or FACP) must be capable of providing Style Z (Class A) notification (or NAC) circuitry. Consult with panel manufacturer.
NAC2
NAC1
FACP
NAC3 OUT
NAC4 RETURN
TO NEXT
DEVICE OR
EOL
TO NEXT
DEVICE OR
EOL
STYLE Z
(CLASS A)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
2 STYLE Y (CLASS B)
1 STYLE Z (CLASS A)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
HORN CONTROL
ZONE 1
OUT
ZONE 1 IN
ZONE 2 IN
SLAVE IN
Temp. Jumper Off
ZONE 2
OUT
SYNC
ERROR
SLAVE
OUT
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
HORN CONTROL
ZONE 1
OUT
ZONE 1 IN
ZONE 2 IN
SLAVE IN
ZONE 2
OUT
SLAVE
OUT
Temp. Jumper Off
SYNC
ERROR
TEMP. JUMPER OFF
NAC2
NAC1
FACP
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
HORN CONTROL
ZONE 1
OUT
ZONE 1 IN
ZONE 2 IN
SLAVE IN
ZONE 2
OUT
SYNC
ERROR
SLAVE
OUT
SEPARATE
MONITORING
INPUT
TEMP. JUMPER OFF
NAC4
NAC3
(+) (–)
(+)
(–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
(+) (–)
HORN CONTROL
ZONE 1
OUT
ZONE 1 IN
ZONE 2 IN
SLAVE IN
ZONE 2
OUT
SYNC
ERROR
SLAVE
OUT
MODULE 1
MODULE 2
EOL
contacts in the open state. These contacts may close during shipping. Approximately two seconds after power-up, these contacts will open.
NOTE: This contact could be wired to a separate monitor­ing input at FACP.
Figure 3:
NOTE: If zone 1 output of module is connected to strobes, chime/strobes or horn/strobes, zone 1 input supply power must be continuous for proper operation.
Figure 5: Wiring for Coded Supplies
A0265-00
NOTE: Horn/chime control must be powered for horn/ strobes to operate the horn portion.
NOTE: SpectrAlert horn-only/chime-only and horn/strobe or chime/strobe devices must be set non-temporal for multi-code sourcing.
Temporal Coding on horns that produce a continuous tone (Non-SpectrAlert Horns)
See Figure 6
• Program module to provide temporal coding by inserting jumper plug per instructions.
• Connect only sounders producing a continuous tone to the module zone output(s).
Figure 4: Multiple Devices Using Sync Error
NOTE: If zone 1 output of module is connected to strobes, chime/strobes or horn/strobes, zone 1 input supply power must be continuous for proper operation.
D900-14-00 3 I56-0983-015R
A0181-00
A0263-00
Strobes cannot be used on a module providing temporal coding to horns. Strobes must be wired for independent operation.
NOTE: Temporal jumper should be inserted across both pins only on non-SpectrAlert products that are to be pow­ered for temporal sound output.
Figure 6:
NOTE: If zone 1 output of module is connected to strobes or horn/strobes, or chime/strobes zone 1 input supply power must be continuous for proper operation.
A0186-00
WARNING
A
A
Figure 6: Mounting Diagram
1. Complete field wiring.
2. Mount unit to 411/16˝ backbox with screws A.
Please refer to insert for the Limitations of Fire Alarm Systems
A0266-00
The Limitations of Sounder/Strobes
The sounder and/or strobe will not work without power. The sounder/strobe gets its power from the fire/security panel monitoring the alarm system. If power is cut off for any reason, the sounder/strobe will not provide the desired audio or visual warning.
The sounder may not be heard. The loudness of the sounder meets (or exceeds) current Underwriters Laboratories’ standards. However, the sounder may not alert a sound sleeper or one who has recently used drugs or has been drinking alcoholic beverages. The sounder may not be heard if it is placed on a different floor from the person in hazard or if placed too far away to be heard over the ambient noise such as traffic, air conditioners, machinery or music appliances that may prevent alert persons from hearing the alarm. The sounder may not be heard by persons who are hearing impaired.
The signal strobe may not be seen. The electronic visual warning signal uses an extremely reliable xenon flash tube. It flashes at least once every three seconds and exceeds current Underwriters Laboratories standards for private mode viewing. The
visual warning signal is suitable for direct viewing and must be installed within an area where it can be seen by building occupants. The strobe must not be installed in direct sunlight or areas of high light intensity (over 60 foot candles) where the visual flash might be disregarded or not seen. The strobe may not be seen by the visually impaired and is not intended to meet American Disabilities Act (ADA) requirements.
The signal strobe may cause seizures. Individuals who have positive photic re­sponse to visual stimuli with seizures, such as persons with epilepsy, should avoid prolonged exposure to environments in which strobe signals, including this strobe, are activated.
The signal strobe cannot operate from coded power supplies. Coded power sup­plies produce interrupted power. The strobe must have an uninterrupted source of dc power in order to operate correctly. System Sensor recommends that the sounder and signal strobe always be used in combination so that the risks from any of the above limitations are minimized.
Three-Year Limited Warranty
Syst em Se nsor warrants its enclosed product to be free from d efects in materi­als and workma nship under normal u se and service for a perio d of t hree years from date of manufac ture. System Sensor makes no o ther express warranty for the encl osed prod uct. No agent , representative, dealer, or employe e of the Company has th e a utho rity to increas e o r a lter the obligation s o r l imitations of this Warranty. The Company’s ob ligation of this Warranty sha ll be limit ed to the rep lacement of any part of the product whic h i s f ound to be def ecti ve in mat erials or workmanship under normal use and se rvice d uring t he three year period commenci ng w ith the date of manu facture. After pho ning Syst em Sensor’s toll free number 800 -SEN SOR2 (736-7672) for a Return Authori zation number, send defecti ve units postag e prepaid to: System Senso r, Retur ns
Department, RA #__________, 3825 Ohio Avenue, St. Cha rles, IL 60174. Please include a note descr ibing the malfunction and suspe cted cause of fai lure. The Co mpany shall not be obligated to repla ce unit s which are f ound to be defective b ecause of damag e, u nreas onab le use, modifica tions, o r a ltera tion s occurring after the date of manufacture. In no case shall the Company be liable for a ny cons equential o r incidental damages for breach of this or any other War ranty, expressed or implie d whatsoever, even if the loss o r damage is caused by the Company’s negligence or f ault. Some states do not allow the excl usion or limitation of incide ntal or co nsequential damages, so the above limitation or exclu sion may not app ly to you. T his Warranty gives you specific legal rights, and you may also have other righ ts which vary from state to state.
D900-14-00 4 I56-0983-015R ©2005 System Sensor
Loading...