System Sensor 2451A Installation And Maintenance Instructions Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
2451A Photoelectronic Plug-in Smoke Detectors
Specifications
Size Height: 2.4 inches (61 mm) Add 0.5 inches (13 cm) for thermal model 2451THA Diameter: 4.0 inches (101 cm) Weight: 0.5 lb. (277 g) Operating Temperature Range: 0° to 49°C (32° to 120°F) Operating Humidity Range: 10% to 93% Relative Humidity Maximum Air Velocity: 3000 Ft./Min. (15 M/S) Locking Alarm: Reset by momentary power interruption Fixed Temperature Thermal: 135°F (57°C)
Before Installing
Please thoroughly read the System Sensor publication, I56-407, Applications Guide for System Smoke Detectors, which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Cop­ies of this guide are available at no charge from System Sensor. Please also refer to CAN/ULC-S524, Standard for the Installation of Fire Alarm Systems and CEC Part 1, Sec. 32..
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: This sensor must be tested and maintained regularly following CAN/ULC-S536 requirements. This sensor should be cleaned at least once a year.
General Description
The 2451A photoelectronic detector utilize state-of-the-art, optical sensing chambers. This detector is designed to pro­vide open area protection, and to be used with compatible ULC-listed control panels only. The capability of plugging this detector into a variety of special bases makes it more versatile than equivalent direct-wired models. Two LEDs on each detector light to provide a local 360° visible alarm indication. They ash every ten seconds indi­cating that power is applied and the detector is operating properly. The LEDs light continuously in alarm. Remote LED annunciator capability is available as an optional ac-
Base Selection and Wiring Guide
Refer to the installation instructions for the Plug-in Detector Bases for base selection and wiring instructions. System Sensor has a variety of detector bases available for this smoke detector. This includes 2-wire applications with and without relays and/or current limiting resistors, 4-wire and 120VAC applications.
All bases are provided with screw terminals for power, ground, remote annunciator connections and relay contact connections, if applicable. The electrical ratings for each detector-base combination are also included in the base installation instructions.
Installation
NOTE: Wiring must conform to applicable local codes,
NOTE: Verify that all detector bases are installed, that the
6581 Kitimat Rd., Unit #6, Mississauga, Ontario, L5N 3T5
ordinances, and regulations.
initiating-device circuits have been tested, and that the wiring is correct. (Refer to detector base manual for testing procedure.)
1-800-SENSOR2, FAX: 905-812-0771
www.systemsensor.ca
D400-02-01 REV#-002 1 I56-1020-000
Disconnect power from initiating-device circuits before in-
PAINTED
SURFACE
TEST
MAGNET
LED
LED
TEST MODULE
SOCKET
TEST
MAGNET
stalling detectors.
1. Install detectors: a. Place the detector into the detector base b. Turn the detector clockwise until the detector drops
into place.
c. Continue turning detector clockwise to lock it in
place.
2. Tamper-proof Feature The detector bases include a feature that, when acti-
vated, prevents removal of the detector without the use of a tool. See the installation instruction manual of the detector base for details in using this feature.
4. Test the detector using the magnet or the test card as described under TESTING.
5. Reset the detector at the system control panel.
Dust covers can be used to help limit dust entry to the detector, but they are not a substitute for removing the detector during building construction. Remove any dust covers before placing system in service.
Testing
Before testing, notify the proper authorities that the smoke detector system is undergoing maintenance and will tem­porarily be out of service. Disable the zone or system un­dergoing maintenance to prevent unwanted alarms.
Detectors must be tested after installation and periodic maintenance. To test the 2451A:
NOTE: Before testing the detector, check to ensure that
the LEDs are blinking. If they are not, the detector has lost power (check the wiring) or it is defective (return for repair).
A. Test Magnet (System Sensor model no. M02-04-00)
6. Notify the proper authorities that the system is back on line.
Figure 1. Bottom and side views showing position of test magnet:
D400-02-01 REV#-002 2 I56-1020-000
A78-1213-00
1. Place the magnet against the cover opposite the test
REMOVABLE HEAD COVER
CLEANABLE SCREEN
HEAD COVER REMOVAL SLOT
VANED CHAMBER
TEST SLOT
P/N RS24 (W/O THERMAL)
module slot to activate the test feature (see Figure
1).
Detectors that fail these tests should be cleaned as de­scribed under MAINTENANCE and retested. If the detec­tors still fail these tests they should be returned for repair.
B. Calibrated Test Card (System Sensor no. R59-18-00)
1. Remove the detector cover by placing a small blad­ed screwdriver in the side slot of the detector cover, twisting it slightly until the cover can be turned coun­terclockwise for removal.
2. Insert the NO ALARM end of the test card fully into the test slot (see Figure 2) then slide it counterclockwise until it stops.
3. Wait for at least 20 seconds. The detector should NOT alarm.
4. Remove the test card by sliding it clockwise before removing, then insert the ALARM end.
5. The LEDs should latch on within 20 seconds indi­cating alarm and annunciating the panel.
6. Put the cover back by gently rotating it clockwise until it locks in place.
C. Test Module (System Sensor no. MOD400R) The MOD400R is used with your DMM or voltmeter
to check the detector sensitivity as described in the MOD400R’s manual.
D. Aerosol Generator (Gemini 501) Set the generator to represent 4% to 5%/Ft. obscuration
as described in the Gemini 501 Manual. Using the bowl shaped applicator, apply aerosol until the unit alarms.
Figure 2:
A78-1213-01
Notify the proper authorities that the detection system is back on line.
Maintenance
It is recommended that the detector be removed from its mounting base to facilitate easier cleaning. The detector is cleaned as follows: NOTE: Before removing the detector, notify the proper
1. Remove the detector cover by placing a small bladed
D400-02-01 REV#-002 3 I56-1020-000
authorities that the smoke detector system is un­dergoing maintenance and will temporarily be out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.
screwdriver in the side slot of the detector cover, twisting it slightly until the cover can be turned counterclockwise for removal.
2. Vacuum the screen carefully without removing it. If fur­ther cleaning is required continue with Step 3, otherwise skip to Step 6.
3. Remove the screen by pulling it straight out (see Figure
2). Vacuum the inside.
4. Clean the vaned chamber piece by vacuuming or blow­ing out dust and particles.
5. To replace the screen, orient it so that the arrow on top aligns with the test module socket of the detector. Care-
fully push the screen onto the base making sure it ts
tightly to the chamber.
6. Replace the cover by gently rotating it clockwise until it locks in place.
7. Reinstall the detector.
8. Notify the proper authorities that the system is back on line.
Please refer to insert for the Limitations of Fire Alarm Systems
System Sensor warrants its enclosed smoke detector to be free from defects in ma-
terials and workmanship under normal use and service for a period of three years
from date of manufacture. System Sensor makes no other express warranty for this
smoke detector. No agent, representative, dealer, or employee of the Company has
the authority to increase or alter the obligations or limitations of this Warranty. The
Company’s obligation of this Warranty shall be limited to the repair or replacement
of any part of the smoke detector which is found to be defective in materials or work-
manship under normal use and service during the three year period commencing
with the date of manufacture. After phoning System Sensor’s toll free number 1-
800-SENSOR2 (736-7672) for a Return Authorization number, send defective units
postage prepaid to: System Sensor, Repair Department, RA #__________, 6581
Kitimat Rd., Unit #6, Mississauga, Ontario, L5N 3T5. Please include a note describ-
ing the malfunction and suspected cause of failure. The Company shall not be obli-
D400-02-01 REV#-002 4 I56-1020-000 © System Sensor 2004
Three-Year Limited Warranty
gated to repair or replace units which are found to be defective because of damage,
unreasonable use, modications, or alterations occurring after the date of manu-
facture. In no case shall the Company be liable for any consequential or incidental
damages for breach of this or any other Warranty, expressed or implied whatsoever,
even if the loss or damage is caused by the Company’s negligence or fault. Some
states do not allow the exclusion or limitation of incidental or consequential dam-
ages, so the above limitation or exclusion may not apply to you. This Warranty gives
you specic legal rights, and you may also have other rights under common law.
Loading...