System Sensor 1412, 2400, 2400TH, 2400AT, 2424AT Installation And Maintenance Instructions Manual

...
INSTALLATION AND MAINTENANCE INSTRUCTIONS
1412 and 1424 Direct Wire
3825 Ohio Avenue, St. Charles, Illinois 60174
Ionization Smoke Detectors
Specifications
Diameter: 5.5 inches (14 cm) Height: 3.12 inches (8.0 cm) Weight: 0.7 lb (310 gm) Operating Temperature: 0° to +49°C (32° to 120°F) Operating Humidity: 10% to 93% Relative Humidity Non-condensing Locking Alarm: Reset by momentary power interruption.
Relay Contact Ratings
Resistive or Inductive (60% power factor) load Form A: 2.0A @ 30VAC/DC Form C:* 0.6A @ 110VDC, 2.0A @ 30VDC
1.0A @ 125VAC, 2.0A @ 30VAC
*For Canadian installations, relay contact rating is 2.0A @ 30VAC/DC
Electrical Ratings: 1412 1424
System Voltage: 12 24 DC (4V Maximum Ripple) Supply Voltages: 11.3 20 VDC Minimum
17.3 29 VDC Maximum Reset Voltages: .73 .8 VDC Minimum Standby Current: 100 100 Alarm Currents: 35.2 21.3 mA Minimum
77.0 40.6 mA Maximum The alarm and auxiliary relay operate within the specified voltage ratings. Reset Time: 0.3 0.3 Seconds Start-up Time: 30 30 Seconds
1-800-SENSOR2, FAX: 630-377-6495
µ
A Maximum
A Division of Pittway
Before Installing
General Description
System Sensor 1412 and 1424 dual-chamber ionization smoke detectors utilize state-of-the-art, unipolar sensing chambers. These detectors are designed to provide open area protection, and to be used with UL-listed 4-wire con­trol panels. The 1412 for 12 volt panels operates at 12VDC, and the 1424 for 24 volt panels operates at 24VDC. The de­tectors’ operation and sensitivity can be tested in place. These detectors are listed to UL 268 and are latching type system detectors. When latched in alarm, the detectors must be reset by a momentary power interruption.
D400-08-00 1 I56-280-03
Technical Manuals Online! - http://www.tech-man.com
An LED on the detector provides a local indication of the detector’s status. If power is applied to the detector, and the detector is functioning properly in standby, the status LED will blink every 10 seconds. In alarm, the LED will be latched on continuously until the detector is reset.
Each detector contains one Form A (SPST-NO) contact for connection to the alarm-initiating circuit, and one Form C (SPDT-NO/NC) set of auxiliary contacts. Supervision of de­tector power is accomplished by installing a Power Supervi­sory End-of-Line Relay Module (A77-716) at the end of the detector power loop. When power is applied to and through the detectors, the EOL Power Supervisory Module is energized. Its relay contacts close and provide a closed series circuit in the control panel’s alarm-initiating loop. A power failure or a break in the detector power loop de-ener­gizes the EOL Module. The relay contacts open and trigger a trouble signal at the control panel.
CAUTION
Figure 1. Flush mounting of detector on 4 inch octagonal box:
Figure 2. Detector mounting bracket:
TAMPER
RESISTANT
TAB
A78-1554-02 A78-534-00
Mounting
Each 1412 and 1424 detector is supplied with a mounting bracket kit that permits the detector to be mounted:
1. Directly to a 3-1/2 inch or 4 inch octagonal, 1-1/2 inch deep electrical box, or
2. To a 4 inch square electrical box by using a plaster ring with the supplied mounting bracket kit.
Spacing
Spacing of 30 ft. on a smooth ceiling as per NFPA 72E. Where conditions or response requirements vary, other spacing may apply.
Wiring Installation Guidelines
All wiring must be installed in compliance with the Na­tional Electrical Code and the applicable local codes, and any special requirements of the local authority having juris­diction. Proper wire gauges should be used. The conduc­tors used to connect smoke detectors to control panels and accessory devices should be color-coded to prevent wiring mistakes. Improper connections can prevent a system from responding properly in the event of a fire.
TO MAKE DETECTOR TAMPER RESISTANT,
BREAK OFF TAB EXTENSION
AT SCRIBED LINE
NOTE: Refer to releasing device manufacturer’s installa-
tion instruction for proper connections.
NOTE: Contacts are shown in stand-by mode and will
transfer in alarm condition.
For system supervision: for terminals 1, 2, 7, and 8, do not use looped wire under terminals. Break wire run to provide system supervision of connections.
For signal wiring (the wiring between interconnected de­tectors), it is recommended that the wire be no smaller than 18 gauge. Wire sizes up to 12 gauge wire may be used. For best system performance, the power (+) and (–) loop wires should be twisted pair and installed in separate grounded conduit to protect the loop from extraneous elec­trical interference.
Smoke detectors and alarm system control panels have specifications for allowable loop resistance. Consult the control panel manufacturer’s specifications for the total loop resistance allowed for the particular model control panel being used before wiring the detector loops.
Figure 3. Wiring diagram for models 1412 and 1424 detectors used with Class A or Class B four-wire control panels.
POWER
+
-
2
1
AUXILIARY
CONTACTS
FORM C
COMMON N/O N/C
A78-1811-00
8
7
4
5
6
ALARM
CONTACTS
FORM A
N/O
D400-08-00 2 I56-280-03
POWER
TO
DETECTORS
UL LISTED
CONTROL
PANEL
INITIATING
LOOP
+
-
(OPTIONAL) RELEASING
DEVICE
COMMON N/O N/C
4
+
-
2
1
(OPTIONAL) RELEASING
8
7
5
6
DEVICE
COMMON N/O N/C
4
+
-
2
1
8
7
5
6
+
-
CLASS A OPTIONAL WIRING
Technical Manuals Online! - http://www.tech-man.com
EOL POWER SUPERVISION RELAY MODULE
SUGGESTED EOL RESISTOR
A78-1554-01
Loading...
+ 2 hidden pages