System Sensor 2400AT, 2400AIT User Manual

INSTALLATION AND MAINTENANCE INSTRUCTIONS
2400AT and 2400AIT Direct Wire Photoelectronic with Fixed Heat
3825 Ohio Avenue, St. Charles, Illinois 60174
Smoke Detectors
Size: Diameter: 5.5 inches (140 mm) Height: 3.19 inches (81 mm); add 0.5 inches (13 mm) for thermal units Weight: 0.7 lb. (310 g) Air Velocity: 3000 ft/min (15 M/s) Operating Temperature: 0°C to 38°C (0° to 100°F) Operating Humidity: 10% to 93% Relative Humidity, noncondensing Visual Indicator: Solid State LED Latching Alarm: Reset by Momentary Power Interruption Audible Signal: 85dBA minimum interrupted tone when in alarm or supply voltage polarity is reversed Fixed Temperature Thermal: 135°F (57°C)
Electrical Ratings
System Voltage: 24 VDC Maximum Ripple Voltage: 4 Volts peak-to-peak Start-up Capacitance: .02 µF Maximum Start-up Time: 36 Sec. Maximum Voltage Limits: 10 – 32 VDC Current Limits
Standby: 120 µA Maximum; 100 µA Nominal
Alarm Current: 15mA at 10V; 67mA at 32V; 48mA at 24V Reversed Supply: 5mA at 10V; 19mA at 32V; 15mA at 24V (Detector not in Alarm) Alarm Impedance: 666 ohms Maximum; 478 ohms Minimum Alarm Signal: 15mA Minimum in Alarm
1-800-SENSOR2, FAX: 630-377-6495
A Division of Pittway
Before Installing
Please thoroughly read the System Sensor manual I56-407­XX, Guide for Proper Use of System Smoke Detectors. This manual provides detailed information on detector spacing, placement, zoning, wiring, and special applications. It is available at no charge from System Sensor. (For installa­tions in Canada refer to CAN/ULC4-S524, Standard for the Installation of Fire Alarm Systems and CEC Part 1, Sec. 32.)
General Description
System Sensor 2400AT and 2400AIT photoelectronic smoke detectors, listed to UL 268, provide open area protection and are intended for use with UL-listed, compatible, 2-wire control panels. The sensor in this detector operates on the light scattering principle and features a unique photo-optic sensing chamber that optimizes smoke entry while mini­mizing the effects of ambient light.
These detectors also provide restorable, 135°F fixed-tem­perature heat detection. The 2400AT heat detection unit is integrated with the photoelectronic sensor while the 2400AIT’s heat detection unit is isolated from the photo­electronic smoke sensor and can be monitored separately. In addition, a piezoelectric horn in each detector produces
D400-03-00 1 I56-287-02
an interrupted, 85 dBA tone when the individual detector alarms or when the supply voltage polarity is reversed.
An LED on each detector lights to provide a local alarm in­dication and will remain on until the supply polarity is re­versed. A screw terminal is provided for a remote LED annunciator optional accessory (RA400Z). These detectors also have the latching feature. The alarm can be reset only by momentary power interruption.
Mounting
Each 2400 Series detector is supplied with a mounting bracket kit to permit mounting in either of two ways:
1. Directly to a 3- or 4-inch octagonal, 11/2-inch deep elec­trical box (See Figures 1 and 2).
2. To a 4-inch square electrical box by using a plaster ring with the mounting bracket kit supplied.
Spacing
NFPA 72E defines the spacing requirements for smoke de­tectors. Typically, this is 30 feet when the detectors are in­stalled on a smooth ceiling. However, ALL installations must comply with NFPA 72E and/or special requirements of the authority having jurisdiction.
CAUTION
Figure 1. Flush mounting of detector on 4-inch octagonal box:
Figure 2. Detector mounting bracket:
TAMPER
RESISTANT
TAB
A78-1394-00
Installation Wiring Guidelines
All wiring must comply with the National Electrical Code and the applicable local codes, and any special require­ments of the authority having jurisdiction, using the proper wire gauges. The conductors used to connect smoke detec­tors to control panels and accessory devices should be color-coded to reduce the likelihood of wiring errors. Im­proper connections can prevent a system from responding properly in the event of a fire.
For signal wiring (wiring between interconnected detec­tors), wiring no smaller than AWG 18 is recommended. The clamping plates in the base can accept wire sizes up to AWG 12. For best system performance, the power (+and –) loop wires should be twisted pair and installed in separate grounded conduit or shielded cable to protect the loop from extraneous electrical interference. If a cable shield is pro­vided, the shield connection to and from the detector must be made continuous by using wire nuts, crimping, or sol­dering, as appropriate for a reliable connection.
Wire connections are made by stripping about 3/8” insula­tion from the end of the wire, sliding the bare end of the wire under the clamping plate, and tightening the clamping plate screw. Do NOT loop the wire under the terminals. System Sensor smoke detectors are marked with a compat­ibility identifier located as the last digit of a five-digit code stamped on the back of the product. Connect detectors only to compatible control units as indicated in System Sensor’s compatibility chart. This chart contains a current list of UL-
TO MAKE DETECTOR TAMPER RESISTANT,
BREAK OFF TAB EXTENSION
AT SCRIBED LINE
A78-534-00
listed control units and detector combinations and is avail­able from System Sensor upon request.
Dust covers provide limited protection against airborne dust particles during shipping. Dust covers MUST be re­moved before the smoke detectors can sense smoke. Re­move sensors before beginning remodeling or heavy construction.
Tamper-resistance Feature
The Tamper Resistant Tab, in the detector mounting bracket, can make the detector tamper-resistant by making it necessary to use a pocket screwdriver, or similar tool, to detach the detector from the bracket. To make the detector tamper-resistant, use needle-nose pli­ers to break the smaller tab at the scribed line on the Tamper Resistant Tab. Figure 2 shows the location of this tab on the detector mounting bracket. To remove a detector from the bracket after it has been made tamper-resistant, use a pocket screwdriver, or other similar tool, to depress the Tamper Resistant Tab, in the slot on the mounting bracket, and rotate the detector counter­clockwise.
Testing
NOTE: Before testing, notify the proper authorities that the
smoke detector system is undergoing maintenance and, therefore, the system will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent unwanted alarms.
Figure 3. Wiring diagram for 2400AT detector with two-wire control panel:
D400-03-00 2 I56-287-02
Loading...
+ 2 hidden pages