Sunway NT 6000, NT 4000, NT 2600 User Manual

User Manual for Sunways Solar Inverters NT 2600, NT 4000 and NT 6000
300 mm
510 mm
180 mm
EN
List of Contents
1.1 Safety information
1.2 Sunways Solar Inverters NT 2600, NT 4000 and NT 6000
2.0 Information on installation
2.1 Safety information
2.2 Installation
General safety information Opening the unit
Scope of supply, inspecting the delivery Integration into the PV system Design of the PV generator Standard components of a PV system Protection concept
Electrical safety Mechanical safety Information on cleaning
Requirements on the place of installation Electrical connection and cable entry Grid connection PV generator connection Important Information Communication connections Connecting the sensors
83 84
85 86
87 88
90
91
93 94 95 97
98 100 102
79
2.3 Commissioning
3.0 Information on operation
3.1 Monitoring and diagnosis
3.2 Sunways NT Monitor software
3.3 Fault indications
3.4 Fault diagnosis
3.5 Warranty terms and conditions
Switching the solar inverter on and off Configurations Structure and menu levels for configuration
Display Data memory
General information Initialising the remote modem Connection and circuitry options Configuring the interface cables Sunways NT Monitor data acquisition Operation of Sunways NT Monitor
Screen displays
Indications, causes and remedies
Warranty period Terms and exclusion of liability for solar inverters
104 106 108
111 112
113 114 115 120 122 123
125
127
130
80
EN
4.0 Appendix
4.1 Subject and abbreviation index
4.2 Function and information index
Designation and description
Functional principle and explanations Block diagram Technical data TYCO SOLARLOK connectors Conformity and safety declarations General exclusion of liability, rights, registered trademarks
133
135 138 140 144 146 150
81
82
1.0 General information
General safety information
All safety hints contained in this section and throughout the User Manual must be complied with at all times to guarantee the user's safety. The described product must not be operated if any mechanical or electrical components are defective.
Before commissioning the system, we strongly advise you to carefully read and heed the instructions! Non-compliance can have serious consequences, for exam­ple damage to the unit or other property or physical injuries with possible loss of life.
The solar inverter must be installed by a trained, qualified electrician. The electrici­an must be approved by the competent electricity board (EB).
The relevant tasks to be carried out are identified by an additional adjacent symbol in the respective chapter headings.
83
EN
1.1 Safety information
The User Manual contains safety hints. These are identified by a triangle with an exclamation mark.
!
Opening the unit
Before opening the cabinet, the unit must always be disconnected from the grid and from the PV generator. The unit continues to conduct a hazardous voltage internally and at the connection sockets for ca. five minutes after disconnec­ting from the PV generator. The energy storage capacitors are only fully discharged after this period. After disconnecting the unit from the grid and from the PV generator, you must wait at least five minutes before opening the unit.
84
!
85
EN
1.2 Sunways Solar Inverters NT 2600, NT 4000 and NT 6000
Scope of supply
· Sunways Solar Inverter in the NT series
· Installation frame
· Manual, setup, warranty card, CD-Rom
with software
· 2 pairs of TYCO SOLARLOK connectors
Inspecting the delivery
The condition of our products is checked prior to delivery. Although our products are carefully packed in recyclable packing, transportation damages can still occur. These are generally the transport compa­ny's responsibility.
Please inspect the delivered solar inverter thoroughly!
If you discover any damage to the packing or the solar inverter, please inform the transport company immediately. Your specialist dealer will be glad to assist you if required. Any damages must always be reported to the transport company in wri­ting seven days after receipt of the goods at the latest.
Integration of the solar inverter into the PV system
Design of the PV generator
The technical data of the selected PV generator must be within the specifica­tion of the solar inverter (see Technical Data). The Sunways NT Sundim design program for the PV generator may be helpful. Sunways NT Sundim is available on the enclosed CD or from our web­site, www.sunways.de.
Please take account of the following points before planning your system:
· Pay attention to the skyward alignment of the modules. You will obtain maxi­mum yield in Central Europe with a module inclination of 30° to the hori­zontal and a direct southerly alignment of the generator field.
· The output of the cells decreases as the module temperature increases. Install your PV generator with adequate rear ventilation.
· Check your PV generator for soiling ca. every three years. This occurs particularly at the lower edge of the modules and forms a film, which even heavy rain can­not wash away. Decreases in yield can be prevented by cleaning with a wet cloth or a brush.
· Avoid shading of individual modules or solar cells in your system. This can result in heavy losses in yield.
86
87
EN
Standard components of a PV system
Depending on the recommendations of your electrician, your PV system will con­sist of the following components:
PC
(3)
SUNWAYS
NT
PV
PV
(1)
(2)
(4)
(1) PV generator switch (2) Irradiation sensor with
integrated temperature
sensor (3) Mains fuse (4) Energy meter
Grid
PV generator switch: Designed as DC load break cut-out to cut off the PV generator from the solar inverter. Dimensioning: min. 800 V, 16 A
Grid connection: 3-phase (Feed-in: 1-phase; grid monitoring: 3-phase)
Standard components of the PV system
Protection concept The following parameters are monitored
continuously and in parallel by the micro­controller and displayed on the screen:
· AFI error (ground fault)
· Overheating of the cooling element
· DC overvoltage
· AC undervoltage/overvoltage
In the event of a fault, the conversion is immediately blocked and the grid relay disconnected. In addition, the following protective devi­ces are provided on both grid and PV generator side:
· Grid-side varistors Protect the power semiconductors from high-energy, time-limited voltage spikes on the grid and provide for a reduction of energy in the throttle in the event of grid disconnection.
· Generator-side varistors Thermally monitored varistors provide pro­tection against atmospheric overvoltages (e.g. due to remote strikes during storms).
88
89
2.0 Information on installation
Electrical safety
Before opening the cabinet, the solar inverter must be disconnected from the grid and from the PV generator.
The solar inverter continues to conduct a hazardous voltage internally and at the connection sockets for the PV generator for ca. five minutes after disconnecting from the PV generator. The energy storage capacitors are only fully discharged after this period.
After disconnecting the solar inverter from the grid and PV generator, you must wait at least five minutes before opening the solar inverter.
Mechanical safety
During installation, make sure that the cables or connection lines fitted to the solar inverter are securely laid and that suitable mechanical cable supports (cable ducts etc.) are used.
2.1 Safety information
!
90
91
EN
Information on cleaning
Before cleaning, disconnect the system from the power grid by opening the grid breaker (main fuse) and open the DC switch on the PV generator, in order to exclude the danger of electric shocks.
Use a soft, dry cloth to clean the system. Never use corrosive, solvent-containing or abrasive cleaners or polishes.
!
2.2 Installation
The solar inverter must be installed by a trained, qualified electrician. A special tool is necessary for installation. Please read this chapter very carefully.
92
150 mm
Cool Air
Warm Air
300 mm
300 mm
150 mm
93
EN
If installing the solar inverter in a switch box, ensure adequate heat dissipation.
The ambient temperature must not fall below or exceed –25°C or +40°C.
The solar inverter should not be exposed to direct solar irradiation, so as to protect it from unnecessary external heating.
· Protection from damp and foreign bodies
The IP54 high protection class permits instal­lation both inside and in roofed outdoor areas, but the solar inverter must not be exposed to direct rain.
Make sure that the solar inverter cannot be exposed to foreign bodies (deposits of dust and dirt).
Requirements on the place of installation
· Mechanical bearing capacity
During installation please bear in mind that the solar inverter weighs 26 kg. The installation base must be firm and capable of continuously bearing the weight.
· Thermal interaction
The installation base must consist of flame-retardant material (e.g. no wood or plastic in the base; concrete and brickwork are suitable), as the heat sink emits tempe­ratures up to max. 85°C.
A minimum distance of 300 mm must be maintained above and below the cabinet, and 150 mm on right and left from other units, cabinets, ceilings, cable ducts etc..
The solar inverter must be installed verti­cally, so as not to hinder adequate free convection.
Several solar inverters must not be instal­led on top of each other, so as to prevent reciprocal heating.
Electrical connection and cable entry
For installation, please observe the instructions in the "Setup" leaflet!
94
!
If the solar inverter is fixed to the installa­tion frame, the electrical connection can be led through. The unit may only be ope­ned by a qualified electrician. The cabinet cover must first be released and removed.
The following cable inlets are located on the underside:
–DC +DC
RS 232, RS 485, Irradiation sensor with inte­grated temperature sensor cable
AC wiring loom L1, L2, L3, N, PE
–DC
+DC
Fig.: Inlets on the unit underside
95
EN
Grid connection
The grid connection of the solar inverter must have 5 wires (L1, L2, L3, PE, N). Cable cross-sections of 5 x 4 mm2 are recommen­ded.
The solar inverter is connected to the supply grid via the circuit board terminals inside the unit.
!
As line safety element in the grid feed-in direction, we recommend a 3 x 25 A auto­matic cut-out. No consumption units must be connected to the feed line from the solar inverter to the automatic cut-out. The solar inverter only feeds in via termi­nal L1.
If several solar inverters are operated in parallel, the feed-in phase L1 of the unit must be evenly distributed over grid phases L1, L2 and L3 (see figure below).
L1 N L2 L3 PE
L1 N L2 L3 PE L1 N L2 L3 PE
L1 L2 L3 N PE
Three-phase grid connection distributed over three units
96
You must use adequately dimensioned cable cross-sections in order to avoid a considerable increase in the grid impedan­ce between the domestic distribution and the solar inverter. The terminal range of the AC terminals is 0.5 to 6 mm2 for rigid cables and 0.5 to 10 mm2 for flexible cables. With a high grid impedance, i.e. with a long line or too small a cross­section, the voltage increases at the grid terminal during feed-in.
If the terminal voltage exceeds the per­missible value, the solar inverter is discon­nected from the grid.
Carefully perform the following steps:
· Check that there is no voltage before introducing the supply main into the unit.
· Lead the 5-core AC cable (outer diame­ter 9 – 17 mm) through the M25 threa­ded cable gland.
· Connect cables L1, L2, L3, PE and N to the relevant circuit board terminal with the help of a slot-head screwdriver (see figure below).
· Tighten the M25 screw connection, so
that the cable cannot exert any mechanical force on the circuit board terminal.
97
EN
PV generator connection
· Preparation
Execute the DC cabling according to your electrician's system dimensioning. Check each PV string for correct functioning by performing a no-load voltage current and short-circuit current measurement.
To achieve the necessary protection against hazardous contact voltage during the installation of PV systems, the positi­ve and negative conductors must be kept separate from the ground potential (PE).
Contactable, conductive parts of the PV generator (e.g. metal frame, supporting structure etc.) must be earthed (connec­ted to PE).
Check that the generator is free from ground faults.
Make the electrical connection to the solar inverter.
!
· Connection
The PV generator is connected via the externally accessible, shock-proof TYCO SOLARLOK connectors, which are enclosed with the delivery. The TYCO SOLARLOK connectors are designed for a cable cross­section of 4 mm2 and must be crimped (see data sheet and connector assembly with TYCO crimping tool on page 144).
Connect the two right DC female connectors with «+», the two left DC female connectors with «-» of the PV generator (see figure below).
98
Important information
· The direct PV generator voltage is availa­ble internally after connecting the PV generator to the solar inverter via the DC connectors and switching on the PV generator switch!
· Please note that the input capacitors are still charged even after switching off the PV generator switch or removing the PV generator plug connection!
· After disconnecting the AC and DC side, the solar inverter still conducts voltage for up to ca. five minutes!
· Therefore, wait for at least five minutes until the internal voltage has dissipated. Then you can work on the terminals! Please note the general safety informa­tion on pages 83 and 84!
!
99
EN
· The DC voltage can be up to 750 V. The unit may only be opened by a qualified electrician!
· Always disconnect the PV generator side first by opening the PV generator switch, and then the grid connection by isolating the relevant mains fuse!
· If you do not have a PV generator switch in your PV system, you must disconnect the grid connection first of all by isola­ting the relevant mains fuse. However, a «grid error» will be entered in the error memory of the solar inverter!
· Disconnection of the PV generator by removing the TYCO SOLARLOK DC con­nectors must never be performed under load. In the event of non-compliance, the connectors could be damaged by a strong electric arc. In this case, the relevant con­nectors must be replaced!
Loading...
+ 53 hidden pages