SELF-CONTAINED REFRIGERATED
SERVICE / SELF-SERVE UNITS
P/N 54100
SB5766.3923A
Model SB5735………...34 1/2”L* x 33”D** x 58 7/8”H~
Model SB5754.3924……....54”L* x 33”D** x 58 7/8”H~
Model SB5766.3923..….…66”L* x 33”D** x 58 7/8”H~
Model SB5766.3923A….…66”L* x 33”D** x 58 7/8”H~
Model SB5766.4999…...…66”L* x 33”D** x 58 7/8”H~
Model SB5766.5106..….…66”L* x 33”D** x 58 7/8”H~
* With End Panels
** 47 1/8” With Rear Ledge upright
~ With Adjustable Levelers Extended 1 5/8” Below Base Frame
Certification: NSF-7, CRMA, UL/CSA
SB5754.3924
888 E. Porter Road · Muskegon, MI 49441 Phone: 231.798.8888 Fax: 231.798.4960 www.structuralconcepts.com
OVERVIEW / NSF® TYPE / COMPLIANCE / WARNINGS / PRECAUTIONS / WIRING / PLUGS .…..
REFRIGERATION ASS’Y REMOVAL, CASE REMOVAL AND LEVELER ADJUSTMENT …………..
START-UP AND OPERATION …………...…...…..……………………………………………….…………
SECURITY ………….……………...….…………...…...…..…………………………………………………...
MAINTENANCE AND OPERATION ..…………...…...…..……………………………………………..……
ELECTRICAL FUNDAMENTALS ………...…...…..…………………………………….………… …...…….
REFRIGERATION FUNDAMENTALS ..………………...…..……………………………………..…………
HOT GAS CONDENSATE EVAPORATIVE SYSTEM OPERATION………...…..………………...……..
LOAD LEVEL GUIDELINES [APPLICABLE TO ALL MODELS] ………………………………………...
SERIAL LABEL LOCATION & INFORMATION LISTED / TECH INFO & SERVICE …………….…….
ILLUSTRATED PARTS BREAKDOWN FOR MODEL SB5766.3923/3923A (SIMILAR TO OTHER
MODELS) ………………………………...
……………………………..……………………………….....……
PARTS LIST FOR MODEL SB5766.3923/3923A (SIMILAR TO OTHER MODELS) ....…………...……
ILLUSTRATED PARTS BREAKDOWN / PARTS LIST FOR MODEL SB5735 CONDENSER PKG ...
CLEANING SCHEDULE [TO BE PERFORMED BY STORE PERSONNEL] ……………...….….....….
CLEANING SCHEDULE [TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY] ……..
TROUBLESHOOTING [TO BE PERFORMED BY STORE PERSONNEL ……………………………...
TROUBLESHOOTING [TO BE PERFORMED BY TRAINED SERVICE PROVIDERS ONLY] ……….
TROUBLESHOOTING [BY TRAINED SERVICE PROVIDERS ONLY] - CONDENSING SYSTEM
TROUBLESHOOTING [BY TRAINED SERVICE PROVIDERS ONLY] - EVAPORATOR SYSTEM
PREVENTIVE MAINTENANCE - HONEYCOMB AIR DIFFUSERS [TRAINED SERVICE
PROVIDERS ONLY] …………………………………………………………………………………...
CAREL® CONTROLLER - PROGRAMMING THE INSTRUMENT ……………………......……………..
CAREL® CONTROLLER - USER INTERFACE DISPLAY & SUMMARY TABLE OF ALARM AND
SIGNALS: DISPLAY, BUZZER AND RELAY ……………………….………………..…...……….
CAREL® CONTROLLER - SUMMARY TABLE OF OPERATING PARAMETERS (AFTER
you MUST use a GFCI breaker in lieu of a GFCI receptacle.
CAUTION! POWER CORD AND PLUG MAINTENANCE
Risk of electric shock. If cord or plug becomes damaged,
replace only with cord and plug of same type.
WIRING DIAGRAM
Each case has its own wiring diagram folded and in
its own packet.
Wiring diagram placement may vary; it may be
placed near ballast box, field wiring box, raceway
cover, or other related location.
CAUTION
CAUTION! ADVERSE CONDITIONS / SPACING ISSUES
Performance issues caused by adverse conditions are NOT warranted.
End panels must be tightly joined or kept at least 6-inches away from
any structure to prevent condensation.
Unit must be kept at least 15-feet from exterior doors, overhead HVAC
vents or any air curtain disruption to maintain proper temperatures.
Unit must not be exposed to direct sunlight or any heat source
(ovens, fryers, etc.).
Tile floors, low ceilings or small rooms increase noise level. Whisper
Cool compressor blankets or remote units resolve noise level issues.
Keep at least 8-inch clearance above unit for air discharge
(self-contained units only).
CAUTION! CHECK CONDENSATE PAN POSITION & PLUG
Water on flooring can cause extensive damage!
Condensate pan is DIRECTLY UNDER condensate drain.
Condensate pan plug is securely plugged into receptacle.
Overflow pan has plug connected to its box. Units with optional
Before powering up unit, check and confirm that:
Clean Sweep™ MUST HAVE 2 plugs connected.
4
REFRIGERATION ASSEMBLY REMOVAL, CASE REMOVAL AND LEVELER ADJUSTMENT
1. Removing Refrigeration Assembly
Note: Retain screws that are removed from the
CASE shipping brackets (Screws will be used as
Toe-Kick fasteners).
Remove front panel.
Lift front panel upward from the lower edge,
approximately one half inch to detach from the
retainer hooks.
Remove all shipping brackets from units base and
compressor.
Reuse shipping bracket screws for Toe-Kick
mounting.
Note: Make sure all hoses and power cords are
disconnected before completely removing
compressor from unit.
The compressor base is on casters. Roll the
assembly out half way straight out from the front
of the case.
Carefully lower assembly to floor.
After compressor unit is removed, roll out of the
Refrigeration Assembly
Shipping Brackets.
Note: Illustration shown may
differ slightly from your case.
Refrigeration
Assembly
way while locating and setting case.
2. Removing Case from Skid
Slide case halfway off back of skid.
Lower case onto back rear levelers.
Tilt case back enough to free skid.
Slide skid out from front of case, lower case to
floor.
3. Leveling Case
Levelers may need to be adjusted for proper height
Do NOT grab
rear ledge
to move case!
clearance to fully insert unit.
Tools needed: level, pry bar, and adjustable
wrench.
Using a level, find the highest point on the case.
Level the case to that highest point by turning the
levelers up or down to the desired level position.
Pry Bar
5
Leveler
Base
Frame
Toe-Kick
START-UP AND OPERATION
1. Merchandiser Start-Up
Remove rear toe-kick (by removing four screws,
two at each end).
Turn main power on. Switch (220V) is up and
under rear raceway on right side of case.
The Controller display will illuminate.
Coil fans should turn on. From inside case, check
for discharge air from front baffle to confirm that
fans are functioning properly.
When the case is in a start up mode or has been
idle for a long period of time, the unit will require
75 minutes in order to pull-down temperature.
Self-Contained refrigerated cases must maintain
front airflow clearance of approximately twelve
inches and rear airflow clearance of approximately
six inches.
Obstruction / restriction of air voids warranty.
The interior case temperature is to reach 2 °C /
35 °F to 5 °C / 41 °F.
Note: Case temperature is set at the factory, as
determined by the case size. Temperature is
controlled by a thermostat.
If a temperature setting change is required, refer
to the Temperature Controller section of this
operating manual.
Note: According to product displayed, Set point
should be -6 °C / 22 °F to -3 °C / 26° F. This will
maintain the product temperature range. Settings
lower than this can cause product to freeze
.
2. Set Point & Differential Adjustment Guideline
Caution! The Differential MUST be adjusted
either up or down in tandem with the Set point.
For example, if the Set point is raised from 22 °F
to 26 °F (a 4 °F increase), the Differential must
also be raised by 4 °F from (11 °F to 15 °F).
Keeping the Set point and Differential
temperatures ‘in tandem’ will maintain product
temperature and prevent excessive compressor
cycles.
3. See Next Page For Fluorescent Light Guidelines
Controller
Display
Light Switch
Main Power Switch
(access at underside)
Rocker Switch
ON
OFF
Honeycomb Air Diffuser. See PREVENTIVE MAINTENANCE -
HONEYCOMB AIR DIFFUSERS [SERVICE TECHNICIANS
ONLY] section in this manual for cleaning instructions.
6
START-UP AND OPERATION, CONTINUED
Light Switch
ON
3. Fluorescent Light Guidelines
Turn lights on. All of the lights should come on at the
same time. First time lighting may require a short warm
up period for the bulbs. Slightly dim or a flickering of
new bulbs is normal. If lights do not turn on, check that
all of the light plugs are in.
Removal of lamps:
Grasp lamp firmly and carefully pull downward and out
from socket.
See photos at mid-right.
Installation of lamp:
Align pins with slot.
Insert pins into socket and push upward into place.
See photos below.
Standard
Fluorescent
Light Fixtures
OFF
Rocker Switch
7
SECURITY
Anti-Theft Grid Installation (Optional Item only on Model SB5766)
Position Anti-Theft Grid so that the locking rods extend down pointing towards the floor.
Insert grid extensions into the forward air return louver.
With “U” shackle released from the padlock base, insert the locking “U” of the padlocks through the sta-
tionary locking bracket.
Rotate “U” shackle 90 degrees and pull up through grid; secure “U” shackle into padlock base.
Note: Due to possible design modification, actual Anti-Theft Grid construction and positioning may differ
than depicted below.
Anti-Theft
Grid Extensions
Anti-Theft
Grid
Return
Air Grille
8
MAINTENANCE AND OPERATION
1. Crumb Tray
Located in back of case under ledge.
Pull out to empty and clean. Replace
promptly.
Note: Make sure drawer is pushed in tight to
maintain refrigeration efficiency.
2. Removing the Rear Doors
Move the rear doors toward the center of the
case.
Individually lift each door up into the upper
door frame track at the top of the case.
Pivot the bottom of the door out.
Slip out of the upper door frame track.
3. Installing Rear Doors
Doors are not interchangeable, and must be
installed as labeled.
Note: Doors are labeled in the lower
corners to identify their proximity to the
interior of the case (inner or outer door).
Inner door must be installed first in the inner
door track.
Insure that the door pull handle is to the
outside and to the left of the case.
Insert the door into the upper inside track and
lower door onto the inside lower track.
Move inner door to the left.
Install the outer door with the door pull handle
to the right and the chrome door stop to the
inside lower right.
Insert the door into the upper and outer track
and lower door onto the outer lower track.
4. Removing Interior Shelving
Remove any product from the display area.
Remove the ABS shelving.
Turn off light switch prior to unplugging shelf
light.
Unplug shelf light.
Remove the complete shelf assembly
Use even upward pressure to disengage
the shelf assembly support brackets from
the adjustment slots.
Crumb
Tray
Right Hand or Outer Door must
come out first and go back in last.
ABS Shelf
9
Shelf Light Assembly
MAINTENANCE AND OPERATION, CONTINUED
5. Removing and Replacing Toe-Kicks Panels
Front and rear kicks be removed first and
installed last when performing maintenance.
6. Removing Front Toe-Kick
Remove the two screws located on the upper
front of the toe-kick at both ends.
7. Removing rear Toe-Kick
Remove four screws at both ends of the grille.
8. Removing Side Toe-Kicks
Note: Side toe kicks are captive by the rear kick
panel in the back of the unit.
Remove screws to the rear toe-kick.
Remove front kick panel.
Remove screws at front of side toe-kicks.
Front Kick Panel
Side Kick Panel
Side Kick Panel
Screw Location
Front Kick Support
Screw Location
Side Kick
Panels
Rear Kick Panel
Support Screws
Front Kick Panel
10
MAINTENANCE AND OPERATION, CONTINUED
9. Service Area, Ambient / Refrigerated
Note: Illustrations at right may not depict an
exact representation of every particular unit.
Access is through rear doors.
Lift air baffle straight up then rotate 90 degrees
so the arrows on the tag point down and tag is
Air Baffle
(slots down)
to the rear of the case. Lower the baffle, with slots
facing up, back down into the air channel.
To close, reverse the procedure.
Note: Removing the baffle facilitates cleaning
interior by providing easy removal of refuse to the
crumb tray.
Air Baffle
(Suspended)
Air Baffle
(slots up)
11
ELECTRICAL FUNDAMENTALS
1. Electrical: Access and Connections
Connections must be performed by a certified
electrician.
Warning! Disconnect power before providing
maintenance and service to unit.
2. Electrical Leads
Remove rear Toe-Kick panel.
The electrical leads are located inside the 4 x
4 electrical box at the rear lower right hand
base of the case.
3. Light Ballast Access
Remove 6 screws from rear wireway cover to
access electrical connections and ballasts.
4. Evaporator Fans Access
Remove lower decking.
A finger hole is provided to lift up and pull
out decking.
5. Removing Fan Assembly
Unplug the fans.
Remove screws from the fan supports.
Remove fan assembly from the shroud
assembly.
6. Temperature & Defrost Control
The case temperature Set Point is set at the
factory, as determined by the case size and
sensor probe location.
The temperature is controlled by a
thermostat.
If a temperature setting change is required,
follow the Programming Steps in the
Temperature Controller section of this
operating manual.
If service is required to the temperature
control unit, call Structural Concepts. This
maintenance should be performed by a
certified technician.
Rear
Wireway
Light Switch
Electrical
Leads
Temperature
Controller
Ballasts
12
Main Power Switch
Electrical
Leads
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.