STIEBEL ELTRON SOM6PLUS User Manual

Page 1
ATTENTION: INSTALLING THE CONTROLLER WITH THE
!
DEFAULT SETTINGS IS NOT RECOMMENDED. IN ORDER TO PREVENT OVERHEATING OF THE SYSTEM HEAT EXCHANGER FLUID OR DOMESTIC HOT WATER THE SETTINGS “OCC” AND “OSTC” SHOULD BE SET TO “ON” AND THE SETTING “EM” SHOULD BE RAISED TO 290 °F.
OPERATION AND INSTALLATION
SOLAR CONTROLLER
» SOM 6 PLUS
Page 2
Contents
General .............................................................................2
Overview ...........................................................................3
1. Installation ..................................................................4
1.1 Mounting ..................................................................... 4
1.2 Electrical connection ....................................................4
1.3 Data communication/ Bus ............................................5
1.4 Terminal allocation ......................................................6
2. Operation and function ................................................8
2.1 Push buttons ................................................................ 8
2.2 System monitoring display ........................................... 8
General
Safety advice:
Please read the following information carefully before installing and operating the controller. In this way damage to the solar system caused by wrong installation will be avoided. Please make sure that the mounting is adapted to the characteristics of the building, that the local regulations are respected and is conform with the technical rules.
Please pay attention to the following safety advice in order to avoid danger and damage to people and property.
Subject to technical change. Errors excepted.
2.3 Flashing codes ............................................................. 9
3. Commissioning........................................................... 10
4. Channel overview ......................................................11
4.1 Display channels ........................................................ 11
4.2 Adjustment channels .................................................. 13
5. Troubleshooting ......................................................... 20
5.1 Various ...................................................................... 21
Instructions:
Attention should be paid to
Valid national and local standards and regulations
Respective valid standards and directives
Equipment to be installed and used in accordance with the rules of the National Electrical Code (NEC) or with Canadian Electrical Code (CEC), Part I.
These instructions are exclusively addressed to authorized skilled personnel.
Only qualified electricians should carry out installation and maintenance work.
Initial installation should be carried out by qualified personnel
Description of symbols
WARNING! Warnings are indicated with a warning
triangle!
Î They contain information on how to
avoid the danger described.
Signal words describe the danger that may occur, when it is not avoided.
Warning means that injury, possibly life-threatening injury, can occur.
Attention means that damage to the appliance can occur.
Note
Notes are indicated with an i nformat ion symbol.
Î Arrows indicate instruction steps that should be carried
out.
2
Information about the product
Proper usage
The solar controller is designed for use in solar thermal and heating systems in compliance with the technical data specified in these instructions. Improper use excludes all liability claims.
Note
Strong electromagnetic fields can impair the function of the controller.
Î Make sure the controller as well as the system
are not exposed to strong electromagnetic fields.
Page 3
0.4" / 11 mm
0.5" / 13 mm
Overview
• System-monitoring-display
• Up to 4 Pt1000 temperature sensors
• Semiconductor relay for pump speed control
• Energy metering
®
• VBus
• Function control
• Control of the system by ServiceCenter software possible
• User-friendly operation
• Housing with outstanding design
• Extra-low power consumption
Included with the SOM 6 plus:
1 × SOM 6 plus
1 × accessory bag
1 × spare fuse T4A 2 × screws and wall plugs 4 × strain relief and screws
1 × manual
Additionally enclosed in the full kit:
1 × sensor FKP6 2 × sensor FRP6
Technical data
Housing: plastic, PC-ABS and PMMA
Protection type: IP 20 / EN 60529
Ambient temp.:
32 ... 104 °F [0 ... 40 °C]
Size:
6.8" × 4.3" × 1.9"
172 × 110 × 47 mm
Mounting: wall mounting, mounting into patch-panels is possible
Display: System screen for system visua lization, 16-segment display, 7-segment display, 8 symbols for system status and operating control lamp
2.6"
66 mm
1.1" 28 mm
6.8" 172 mm
4.3"
110 mm
Operation: by 3 push buttons at the front of the housing
Functions: Differential temperature controller with optional add-on system functions. Func ti on con trol, operating hours counter for solar pump, pump speed control, drainback option and energy metering.
Inputs:
for 4 Pt1000 temperature sensors
Output: 1 semiconductor relay
Bus: VBus
®
Power supply: 100 ... 240 V~
6.1" 155 mm
1.9" / 47 mm
Standby power consumption: < 1 W
Switching capacities:
R1: 1 (1) A 100 ... 240 V~ (semiconductor relay)
3
Page 4
1. Installation
104 mm
1.1 Mounting
display
WARNING! Electric shock!
Opening the housing will expose live parts!
Î Switch off power supply and disconnect
the device from power supply before opening the housing!
cover
cable conduits with strain relief
5.1“
130 mm
lower fastening
upper fastening
fuse 4A
4.1“
push button
The unit must only be installed
in a dry interior location
in a non-hazardous location
away from electromagnetic fields
The controller must additionally be supplied from a double­pole switch with contact gap of at least 0.12" [3 mm].
Route sensor cables and power supply cables separately.
Î Unscrew the cross-head screw from the cover and remove
it along with the cover from the housing
Î Mark the upper fastening point on the wall and drill
Î Fasten the enclosed wall plug and screw leaving the head
protruding
Î Hang the housing from the upper fastening point and
mark the lower fastening point through the hole in the terminal box (centers 5.1" [130 mm])
Î Drill and insert the lower wall plug
Î Fasten the housing to the wall with lower fastening screw
and tighten
Î Complete wiring connections in accordance with terminal
allocations, see chap. 1.2 “Electrical connection”
Î Place the cover back onto the housing
Î Fasten the cover by means of the cross-head screw
1.2 Electrical connection
VBus
ground terminal
ATTENTION! ESD damage!
fuse
Electrosta tic discharge can lead to damage to electronic components!
Î Take care to discharge properly
before touching the inside of the device. To do so, touch a grounded surface such as a radiator or tap!
Note:
The minimum pump speed must be set to 100% when
®
load terminalssensor terminal
power supply terminals
Connecting the device to the power supply must always be the last step of the installation!
auxiliary relays or valves are connected.
The power supply to the controller must be carried out via an external power switch (last step!). The supply voltage must be 100 ... 240 V~ (50 ... 60 Hz). Flexible cables must be attached to the housing with the enclosed strain relief and the corresponding screws.
4
Page 5
The controller is equipped with a semiconductor relay, to which a load such as a pump, a valve etc. can be connected:
Relay 1
18 = conductor R1 17 = neutral conductor N 13 = ground conductor
R1
1 (1) A (100 ... 240) V~
Grounding and load terminals
Temp. Sensor
Pt1000
S1 S2 S3
1 2
3 4 5 6
Sensor terminals S1 ... S4
S4
7 8
The power supply is to be carried out at the terminals:
19 = neutral conductor N 20 = conductor L
LNR1N
20191817141312
12 = ground terminal
The temperature sensors (S1 up to S4) are to be connected to the following terminals with either polarity:
1 / 2 = Sensor 1 (e.g. Sensor collector) 3 / 4 = Sensor 2 (e.g. Sensor tank) 5 / 6 = Sensor 3 (e.g. Sensor tank top) 7 / 8 = Sensor 4 (e.g. Sensor return)
All Pt1000 temperature sensors are equipped with a platinum measuring element in their tip. The electrical resistance of the measuring element changes in relation to the temperature (see table in chap. 5).
The difference between FKP and FRP type sensors only lies in the cable insulation material. The insulation material of FKP type sensor cables resists a higher temperature, so that FKP type sensors should be used as collector sensors. FRP type sensors are best used as reference sensors in tanks or pipes.
1.3 Data communication/ Bus
®
VBus
connection terminals
The controller is equipped with a VBus® for data transfer with and energy supply to external modules. The connection is carried out at the terminals marked “VBus” (either polarity). One or more VBus® modules can be connected via this data bus.
By means of a DL2 datalogger or an interface adapter, the controller can be connected to a PC or a computer network.
5
Page 6
1.4 Terminal allocation
The controller calculates the temperature difference between collector sensor S1 and tank sensor S2. If the difference is larger than or identical to the adjusted switch - on temperature difference (DT O), the solar pump will be operated by R1, and the tank will be loaded until the switch-off temperature difference (DT F) or the maximum tank temperature (S MX) is reached.
S1
Sensors S3 and S4 ca n opt i o n a l l y be connected for measurement purposes. If energy metering (OHQM) is activated, sensor S4 has to be connected as return sensor.
R1
S4 / TR
Display Channels
Channel Description Terminal Page
INIT FLL STAB COL x Temperature collector S1 12 TST x Temperature tank S2 12 S3 x Temperature sensor 3 S3 12 S4 x Temperature sensor 4 S4 12 TR x* Temperature return sensor S4 12 n % x Pump speed R1 R1 13 hP x Operating hours R1 R1 13 kWh x* Heat quantity kWh - 13 MWh x* Heat quantity MWh - 13
x*
ODB initialization active - 12
x*
ODB filling time active - 12
x*
ODB stabilization in progress - 12
S3
R1
S4/TR
S2
S1
Drainback system layout
exemplary
S3
S2
6
Page 7
Adjustment Channels
Channel Description Factory setting Page
DT O x Switch-on temperature difference 12.0 °Ra [6.0 K] 14 DT F x Switch-off temperature difference 8.0 °Ra [4.0 K] 14 DT S x Nominal temperature difference 20.0 °Ra [10.0 K] 14 RIS x Rise control 4 °Ra [2 K] 14 nMN x Minimum pump speed 30 % 14 S MX x Maximum tank temperature 140 °F [60 °C] 15
EM x
OCC x Option collector cooling CMX x* Maximum collector temperature
Emergency temperature collector 270 °F [130 °C] 15 Emergency temperature collector if ODB is activated: 200 °F [95 °C] 15
OFF 16
230 °F [110 °C] 16 OSYC x Option system cooling OFF 16 DTCO x* Cooling switch-on temperature difference DTCF x* Cooling switch-off temperature difference
40.0 °Ra [20.0 K]
30.0 °Ra [15.0 K]
16
16 OSTC x Option tank cooling OFF 17 OHOL x* Option holiday cooling OFF 17 THOL x* Holiday cooling temperature 110 °F [40 °C] 17 OCN x Option minimum limitation OFF 17 CMN x* Minimum collector temperature 50 °F [10 °C] 17 OCF x Option antifreeze OFF 17 CFR x* Antifreeze temperature 40.0 °F [4.0 °C] 17 OHQM x Option energy metering OFF 18 FMAX x* Maximum flow 6.0 l 18 MEDT x* Antifreeze type 1 18 MED% x* Antifreeze concentration (only if MEDT = propylene or ethylene) 45 % 18 ODB x Drainback option OFF 19 tDTO x* ODB switch-on condition - time period 60 s 19 tFLL x* ODB filling time 5.0 min 19 tSTB x* ODB stabilization time 2.0 min 19 MAN x Manual operation R1 Auto 20 LANG x Language En 20 UNIT x Temperature unit °C 20 RESE x Reset - back to factory defaults 20
W0020100 Version number
Legend:
Symbol Specification
x Channel is available
x* Channel is available if the corresponding option is activated.
7
Page 8
2. Operation and function
2.1 Push buttons
operating control lamp
backward
2
3
(selection / adjustment mode)
2.2 System monitoring display
SET
The controller is operated via three push buttons below the display.
Button 1 is used for scrolling forward through the indication menu or to increase the adjustment values. Button 2 is used for scrolling backward and reducing values. Button 3 is used for selecting channels and confirming adjustments.
During normal operation, only the display channels are shown.
forward
1
Î Scroll through the display channels by pressing buttons
1 and 2
Accessing the adjustment channels:
Î Scroll down in the display menu and press button 1 for
approx. 2 seconds after you have reached the last display item.
When an adjustment value is shown on the display,
is
indicated to the right of the channel name.
Î Press button 3 in order to access the adjustment mode
starts flashing.
Î Adjust the value using buttons 1 and 2 Î Briefly press button 3,
permanently appears,the
adjusted value will be saved.
The system monitoring display consists of three blocks: channel display, tool bar and system screen.
The channel display consists of 2 lines. The upper line is an alpha-
system monitoring display
numeric 16-segment display (text display) for displaying channel names and menu items. In the lower 7-segment display, the channel values and the adjustment parameters are displayed. Temperatures are either indicated in °F or °C, whereas temperature differences are indicated in K or °Ra respectively.
channel display
The additional symbols of the tool bar indicate the current system status.
Status standard flashing
relay 1 active
maximum tank temperature exceeded
tool bar
8
tank emergency shutdown active
collector emergency shutdown active
collector cooling active
system cooling active
tank cooling active
holiday cooling function activated
holiday cooling function active
collector minimum limitation active
antifreeze function activated
antifreeze function active
manual operation relay 1 ON
manual operation relay 1 OFF
sensor defective
+
+
+
+
Page 9
System screen
The system screen shows the solar system. It consists of several system component symbols, which are – depending on the current status of the system – either flashing or permanently shown.
system screen
collector
pump
collector sensor
tank heat exchanger
Collector
with collector sensor
tank
tank sensor at the top
tank sensor at the bottom
Temperature sensor
2.3 Flashing codes
System screen flashing codes
LED flashing codes
Tank
with heat exchanger
Pump
Pump is flashing when the relay is active
Sensor symbols are flashing if the corresponding sensor
display channel is selected.
Sensors are flashing quickly in the case of a sensor fault.
green: everything OK red/green flashing initialization phase manual operation red flashing: sensor fault
(sensor symbol is flashing quickly)
9
Page 10
3. Commissioning
2
3
1
(SET)
The three push buttons of the BS/2 controller
Î Establish the power supply During a short initialization phase, the operating control lamp flashes red and green.
When the controller is commissioned for the first time or after a reset, it will run a commissioning menu. The commissioning menu leads the user through the most important adjustment channels needed for operating the system.
Operating the commissioning menu:
Î Enter the channel by pressing button 3
The
The
The commissioning menu consists of the following 4 channels:
symbol flashes.
Î Adjust the value by pressing buttons 1 and 2
Î Save the adjustment by pressing button 3 again
symbol stops flashing.
Î Press button 1 or 2 to switch to the next or previous channel
LANG:
Language selection Selection: dE, En Factory setting: En
UNIT:
Temperature unit selection Selection: °F, °C Factory setting: °C
S MX:
Maximum tank temp. Adjustment range: 40 ... 200°F [4 ... 95 °C] in steps of 2 °Ra [1 K] Factory setting:140°F [60 °C]
1. Language
Î Adjust the desired menu language in this channel
dE : German
En : English
2. Unit
Î Adjust the unit in which temperatures and temperature
differences shall be displayed
3. Maximum tank temperature
Î Adjust the desired maximum tank temperature
Note: The controller is also equipped with a non­adjustable emergency shutdown function, which will shut the system down if the tank reaches 200°F [95 °C].
nMN:
Pump speed control Adjustment range: 30 ... 100 in steps of 5 % Factory setting: 30
10
4. Minimum pump speed
Î Adjust a minimum speed for the pump
Note:
If a load which is not speed-controlled is used, the value must be set to 100%.
Page 11
Confirmation enquiry
4. Channel overview
4.1 Display channels
Indication of drainback time periods
Completing the commissioning menu
After the last channel of the commissioning menu has been adjusted and confirmed, the controller asks for confirmation of the adjustments.
Î To confirm the adjustments made in the commissioning
menu, press button 3
Now the controller is ready for operation with typical settings to suit the selected system layout.
The set tings made in the commissioning menu can be changed later on in the corresponding adjustment channels. Additional functions and options can of course be individually adjusted as well (see chap. 4.2).
Note:
The displayed values and adjustment channels depend on which options and functions have been selected. Only values and adjustment channels available for the individual settings selected will appear in the menu.
Initialization
INIT:
ODB initialization active
Filling time
FLL:
ODB filling time active
Stabilization
STAB:
Stabilization
Indication of collector temperature
COL:
Collector temperature Display range: -40 ... +500 °F [-40 ... +260 °C]
Indication of tank temperatures
TST:
Tank temperatures Display range: -40 ... +500 °F [-40 ... +260 °C]
Indicates the time adjusted in tDTO, running backwards.
Indicates the time adjusted in tFLL, running backwards.
Indicates the time adjusted in tSTB, running backwards.
Indicates the current collector temperature.
Indicates the current tank temperature.
11
Page 12
Indication of sensors 3 and 4
S3, S4:
Sensor temperatures Display range: -40 ... +500 °F [-40 ... +260 °C]
Indicates the current temperature of the corresponding ad­ditional sensor (without control function).
S3 : temperature sensor 3
S4 : temperature sensor 4
Note:
S3 and S4 will only be indicated if the temperature sensors are connected.
Indication of return temperature
TR:
Return tempe rature Display range: -40 ... +500 °F [-40 ... +260 °C]
Indication of current pump speed
n %:
Current pump speed Display range: 30 ... 100 %
kWh/MWh: Heat quantity in kWh / MWh Display channel
If energy metering is active, the temperature at sensor4 is indicated as TR.
Indicates the current pump speed of the solar pump.
Indicates the energy gained in heat quantity – only available if energy metering (OHQM) is activated. The flow rate as well as the reference sensors S1 (flow) and S4 (return) are used for calculating the heat quantity supplied. It is shown in kWh in the channel kWh and in MWh in the channel MWh. The overall heat quantity results from the sum of both values. The accumulated heat quantity can be set back to 0. As soon as one of the display channels of the heat quantity is selected, the symbol is permanently shown on the display.
Î Press button 3 for about 2seconds in order to access the
RESET mode of the counter. The display symbol will flash and the heat quantity value will be set to 0.
Î In order to finish this process, press button 3 to confirm. In order to interrupt the RESET-process, do not press a button for about five seconds. The display returns to the display mode.
Operating hours counter
h P:
Operating hours counter Display channel
12
The operating hours counter accumulates the solar operating hours of the relay (h P). Full hours are displayed. The accumulated operating hours can be set back to 0. As soon as one operating hours channel is selected, the symbol
is displayed.
Î In order to access the RESET-mode of the counter, press
button 3 for approx. 2 seconds. The display symbol will flash and the operating hours will be set to 0.
Î Confirm the reset with button 3 in order to finish the reset. In order to interrupt the RESET-process, do not press a button for about five seconds. The display returns to the display mode.
Page 13
4.2 Adjustment channels
T-regulation
DT O:
Switch-on temperature diff. Adjustment range: 2.0 ... 40.0°Ra [1.0 ... 20.0 K] in steps of 1 °Ra [0.5 K] Factory setting: 12.0°Ra [6.0 K]
DT F: Switch-off temperature diff. Adjustment range: 1.0 ... 39.0°Ra [0.5 ... 19.5 K] in steps of 1 °Ra [0.5 K] Factory setting: 8.0°Ra [4.0 K]
Pump speed control
DT S:
Nominal temperature difference Adjustment range: 3.0 ... 60.0 °Ra [1.5 ... 30.0 K] in steps of 1 °Ra [0.5 K] Factory setting: 20.0 °Ra [10.0 K]
RIS: Rise Adjustment range: 2 ... 40 °Ra [1 ... 20 K] in steps of 2 °Ra [1 K] Factory setting: 4 °Ra [2 K]
Minimum pump speed
nMN:
Pump speed control Adjustment range: 30 ... 100 in steps of 5 % Factory setting: 30
The controller works as a standard differential controller. If the switch-on difference is reached, the pump is activated. When the temperature difference falls below the adjusted switch-off temperature difference, the relay switches off.
Note:
The switch-on temperature difference must be at least 1 °Ra [0.5 K] higher than the switch-off tempe rature difference.
Note:
When the drainback option ODB is activated, the temperature differences DTO, DTF and DTS are set to a fixed adjustment: DTO = 20 °Ra [10 K] DTF = 8 °Ra [4 K] DTS = 30 °Ra [15 K] Previous adjustments made in these channels will be overridden and may have to be entered again if ODB is deactivated later on.
Note:
For pump speed control, the operation mode of relay 1 must be set to Auto (adjustment channel MAN)
When the switch-on temperature difference is reached, the pump is activated at full speed for 10 seconds. Then, the speed is reduced to the minimum pump speed value (factory setting = 30%). If the temperature difference reaches the adjusted nominal temperature difference, the pump speed increases by one step (10%). If the difference increases by the adjustable rise value, the pump speed increases by 10% respectively until the maximum pump speed of 100% is reached. The response of the controller can be adapted via the parameter “Rise”.
Note:
The nominal temperature difference must be at least 1 °Ra [0.5 K] higher than the switch-on tempe rature difference.
A relative minimum pump speed can be allocated to the output R1 via the adjustment channel nMN.
Note:
When a load which is not speed-controlled is used, the value must be set to 100% in order to deactivate pump speed control.
13
Page 14
Maximum tank temperature
S MX:
Maximum tank temp. Adjustment range: 40 ... 200°F [4 ... 95 °C] in steps of 2 °Ra [1 K] Factory setting:140°F [60 °C]
Once the adjusted maximum temperature is exceeded, the solar pump is switched off and further loading of the tank is prevented to reduce scald risk or system damage. A fixed hysteresis of 4 °Ra [2 K] is set for the maximum tank temperature. When the temperature at sensor 2 exceeds the adjusted maximum tank temperature, the display.
Note: If the collector cooling or the system cooling function is activated, the adjusted tank temperature may be overridden. In order to prevent system damage, the controller is also equipped with a non-adjustable emergency shutdown if the tank reaches 200°F [95 °C].
symbol is shown on the
Collector temperature limitation Emergency shutdown of the collector
EM:
Collector temperature limitation Adjustment range: 170 ... 390°F [80 ... 200 °C] in steps of 2 °Ra [1 K] Factory setting: 270°F [130 °C]
If the adjusted collector emergency shutdown temperature EM is exceeded, the controller switches off the solar pump (R1) in order to protect the system against overheating (collector emergency shutdown). A hysteresis of 20°Ra [10K] is set for the collector temperature limitation. While the collector is in emergency shutdown,
Note:
If the drainba ck op t i on ODB is ac t ivated , the adj ustment ran ge of EM is changed to 170...250°F [80...120°C]. The factory setting in that case is 200°F [95°C].
WARNING! Danger of injury and system damage
(flashing) is shown on the display.
through pressure surges!
If water is used as a heat transfe r medium in a pressure-less system, the water will start boiling at 212 °F [100 °C].
Î If a pressure-less drainback system
is used with water as a heat transfer medium, do not adjust the collector temperature limitation EM to more than 200 °F [95 °C]!
14
Page 15
Cooling functions
Below, the three cooling functions – collector cooling, system cooling and tank cooling – are described in detail. The following note is valid for all three cooling functions:
Note:
The cooling functions will not become active as long as solar loading is possible.
Collector cooling function
OCC:
Option collector cooling Adjustment range: OFF / ON Factory setting: OFF
CMX:
Maximum collector temp. Adjustment range: 150 ... 320°F [70 ... 160 °C] in steps of 1 °Ra [1 K] Factory setting: 230°F [110 °C]
System cooling function
OSYC:
Option system cooling Adjustment range: OFF / ON Factory setting: OFF
DTCO: Switch-on temperature diff. Adjustment range:
2.0 ... 60.0 °Ra [1.0 ... 30.0 K] in steps of 1 °Ra [0.5 K] Factory setting:
40.0°Ra [20.0 K] DTCF:
Switch-off temperature diff. Adjustment range:
1.0 ... 59.0 °Ra [0.5 ... 29.5 K] in steps of 1 °Ra [0.5 K] Factory setting:
30.0 °Ra [15.0 K]
When the collector cooling function is activated, the controller aims to keep the collector at an operational temperature. When the adjusted maximum tank temperature is reached, solar loading stops. If the collector temperature increases to the adjusted maximum collector temperature, the solar pump is activated until the collector temperature falls at least 10°Ra [5K] below the maximum collector temperature. The tank temperature may increase (subordinate active maximum tank temperature), but only up to 200°F [95°C] (emergency shutdown of the tank). If the collector cooling function is active,
and (flashing)
is shown on the display.
Note:
This function will only be available if the system cooling function (OSYC) is deactivated.
When the system cooling function is activated, the controller aims to keep the solar system operational for a longer time. The function overrides the maximum tank temperature to provide thermal relief of the collector field and the heat transfer fluid on hot days. If the tank temperature is higher than the maximum tank temperature S MX and the switch-on temperature difference DTCO is reached, the solar system remains activated. Solar loading is continued until either the tank temperature reaches 200°F [95°C] (emergency shutdown of the tank), the temperature difference falls below the adjusted value DTCF or the collector emergency shutdown temperature EM is reached. If the system cooling function is active,
and (flashing) is
shown on the display.
Note:
This function will only be available if the collector cooling function (OCC) is deactivated.
15
Page 16
Tank cooling function
OSTC:
Tank cooling option Adjustment range: OFF / ON Factory setting: OFF
OHOL: Holiday cooling option Adjustment range: OFF / ON Factory setting: OFF
THOL: Holiday cooling temperature Adjustment range: 70 ... 175 °F [20 ... 80 °C] in steps of 1 °Ra [1 K] Factory setting: 110 °F [40 °C]
When the tank cooling function is activated, the controller aims to cool down the tank during the night in order to prepare it for solar loading on the following day.
If the adjusted maximum tank temperature S MX is exceeded and the collector temperature falls below the tank temperature, the system will be reactivated in order to cool down the tank. Cooling will continue until the tank temperature has fallen below the adjusted maximum tank temperature S MX again. A fixed hysteresis of 4°Ra [2K] is set for this function. Reference threshold temperature differences for the tank cooling function are DT O and DT F.
If no DHW consumption is expected for a longer period of time, the additional holiday cooling option OHOL can be activated in order to extend the tank cooling function. The adjustable temperature THOL then replaces the maximum tank temperature S MX as a switch-off temperature for the tank cooling function. When the holiday cooling function is activated
, and
(flashing) are shown on the display. While the holiday cooling function is active, , and (flashing) are shown on the display.
Collector minimum limitation option
OCN:
Collector minimum limitation Adjustment range: OFF / ON Factory setting: OFF
CMN:
Collector minimum temp. Adjustment range: 50 ... 190°F [10 ... 90 °C] in steps of 1 °Ra [0.5 K] Factory setting: 50°F [10 °C]
Antifreeze option
OCF:
Antifreeze function Adjustment range: OFF / ON Factory setting: OFF CFR: Antifreeze temperature Adjustment range:
-40.0 ... +50.0°F [-40.0 ... +10.0 °C] in steps of 1 °Ra [0.5 K] Factory setting:
40.0°F [4.0 °C]
If the collector minimum limitation option is activated, the pump (R1) is only switched on if the adjustable collector minimum temperature is exceeded. The minimum temperature prevents the pump from being switched on too often at low collector temperatures. A fixed hysteresis of 10°Ra [5°K] is set for this function If the collector minimum limitation is active,
(flashing) is
shown on the display.
Note:
If OSTC or OCF is active, the collector minimum function will be overridden. In that case, the collector temperature may fall below CMN.
The antifreeze function activates the loading circuit between the collector and the tank when the temperature falls below the adjusted antifreeze temperature. This will protect the fluid against freezing or coagulating. If the adjusted antifreeze temperature is exceeded by 2 °Ra [1 K], the loading circuit will be deactivated. When the antifreeze function is activated,
is shown on the display. If the antifreeze function is active, and (flashing) are shown on the display.
Note:
Since this function uses the limited heat quantity of the tank, the antifreeze function should be used in regions with few days of temperatures around the freezing point. The antifreeze function will be suppressed if the tank temperature falls below 40 °F [5 °C] in order to protect the tank from frost damage.
16
Page 17
Energy metering
OHQM: Energy metering
Adjustment range: OFF / ON Factory setting: OFF
FMAX: Flow rate in l/min Adjustment range: 0.5 ... 100.0 in steps of 0.5 Factory setting: 6.0
If OHQM is activated, the heat quantity gained can be calculated and displayed. Energy metering is possible if a flowmeter is used. To enable energy metering, proceed as follows:
Î Read the flow rate (l/min) from the flowmeter at maximum
pump speed and adjust it in the FMAX channel
Î Adjust the heat transfer fluid and the concentration of the
antifreeze in the channels MEDT and MED%.
MEDT: Heat transfer fluid Adjustment range: 0 ... 3 Factory setting: 1
MED%: Antifreeze ratio in Vol-% (MED% is hidden when MEDT 0 or 3 is used.) Adjustment range: 20 ... 70 in steps of 1% Factory setting: 45
Heat transfer fluid:
0 : Water 1 : Propylene glycol 2 : Ethylene glycol
®
3 : Tyfocor
H-30 L/LS
17
Page 18
Drainback option
Note:
A drainback system layout requires additional components such as a holding tank. The drainback option should only be activated if all components required are properly installed.
ODB:
Drainback option Adjustment range: OFF / ON Factory setting: OFF
Note:
When the drainback option ODB is activated, the cooling functions OCC, OSYC and OSTC as well as the antifreeze function OCF are not available. If OCC, OSYC, OSTC or OCF have already been activated before, they will be deactivated again as soon as ODB is activated. They will remain deactivated, even if ODB is deactivated later on.
Time period - switch-on conditions
tDTO:
Time period - switch-on conditions Adjustment range: 1 ... 100 s in steps of 1 s Factory setting: 60 s
A drainback system permits the heat transfer fluid to drain back into the holding tank when solar energy is not collected. The drainback option will initiate the filling of the system when solar loading begins.
If the drainback option ODB is activated, the pump will operate at 100 % speed for the adjusted filling time tFLL in order to fill the system with fluid from the holding tank. After tFLL, pump speed will go down to the adjusted minimum pump speed nMn. The switch-off conditions will then be ignored for the stabilization time tSTB in order to avoid the system from shutting down prematurely.
If the function is activated, the menu items described in the following (tDTO, tFLL and tSTB) have to be adjusted:
Note:
When the drainback option ODB is activated, the temperature differences DTO, DTF and DTS are set to a fixed adjustment. Additionally, the adjustment range and the factory setting of the collector emergency shutdown temperature EM changes (see the corresponding channel descriptions for further information). Previous adjustments made in these channels will be overridden and have to be entered again if ODB is deactivated later on.
The parameter tDTO is used for adjusting the time period du ring wh ich th e switch-on condition DT O must be permanentely fulfilled.
Filling time
tFLL:
Filling time Adjustment range:
1.0 ... 30.0 min in steps of 0.5 min Factory setting: 5.0 min
Stabilization tSTB:
Stabilization Adjustment range:
1.0 ... 15.0 min in steps of 0.5 min Factory setting: 2.0 min
18
The filling time can be adjusted using the parameter tFLL. During this period, the pump runs at 100% speed.
The parameter tSTB is used for adjusting the time period during which the switch-off condition DT F will be ignored after the filling time has ended.
Page 19
Operating mode MAN:
Operating mode Adjustment range: OFF, Auto, ON Factory setting: Auto
For control and service work, the operating mode of the controller can be manually adjusted. For this purpose, select the adjustment value MAN in which the following adjustments can be made:
Operating mode OFF : relay off
Auto : relay in automatic operation ON : relay on
(flashing) +
(flashing) + +
Note: Always adjust the operating mode back to “Auto” when the control and service work is completed. Normal operation is not possible in manual mode.
Language
LANG:
Language selection Selection: dE, En Factory setting: En
Unit UNIT:
Temperature unit selection Selection: °F, °C Factory setting: °C
Reset RESE
Reset function
The menu language can be adjusted in this channel.
dE : German
En : English
In this adjustment channel, the display unit for temperatures and temperature differences can be chosen. The unit can be switched between °C/K and °F/°Ra during operation. Temperatures and temperature differences in °F and °Ra are displayed without units. If the indication is set to °C, the units are displayed with the values.
By using the reset function, all adjustments will be set back to the factory settings.
Î To initiate a reset, press button 3
Any previous adjustments will be lost. Therefore, initiating the reset function is always followed by a security enquiry.
Only confirm the security enquiry if you are sure that you wish to reset all adjustments to the factory settings!
Security enquiry:
Î To confirm the security enquiry, press button 3
Note: Whenever a reset has been completed, the controller runs the commissioning menu again (see chap.3).
19
Page 20
5. Troubleshooting
VBus® terminals
ground terminals
fuse
In the case of an error, a message is shown on the display of the controller:
Warning symbols
Operating control lamp
load terminalssensor terminals
power supply terminals
Operating control lamp flashes red. On the display the symbols and appear.
Sensor defect. An error code instead of a temperature is displayed in the sensor display channel.
- 88.8888.8
Cable broken. Check cable.
Short circuit. Check cable.
Disconnected Pt1000 temperature sensors can be checked with an ohmmeter. In the following table, the resistance values with the corresponding temperatures are shown.
°C °F Ω °C °F Ω
-10 14 961 55 131 1213
-5 23 980 60 140 1232 0 32 1000 65 149 1252 5 41 1019 70 158 1271
10 50 1039 75 167 1290 15 59 1058 80 176 1309 20 68 1078 85 185 1328 25 77 1097 90 194 1347 30 86 1117 95 203 1366 35 95 1136 100 212 1385 40 104 1155 105 221 1404 45 113 1175 110 230 1423 50 122 1194 115 239 1442
Resistance values of the Pt1000-sensors
Operating control lamp off.
Check the power supply. Is it disconnected?
no
The fuse of the controller could be blown. It can be
Check the supply line and
reconnect it. replace d after th e front cover has been removed (spare fuse is enclosed in the accessory bag).
yes
20
Page 21
5.1 Various
Pump is overheated, but no heat transfer from the collector to the tank, flow and return have the same temperature; perhaps also air / gas bubbles in the lines.
Air in the system?
Air in the system; in crease the system pressure to at
no yes
least static primary pres­sure plus 7. 25 psi (0.5 bar); if necessary continue to increase pressure; switch the pump off and on for a
Is the collector circuit
short time.
blocked at the dirt trap?
yes
Clean the dirt trap
Pump starts up very late
Pump starts for a short moment, switches off, switches on again, etc.
Temperature difference at the controller too small?
Change Ton and Toff
no yes
correspondingly. Problem solved?
no
yes
Wrong position of collector sensors?
no
yes
Mount the collector sensor
o.k.
at solar flow ( w a rmest co lle c tor outp u t); use
Plausibility control of the option tube collector
s e ns o r w e l l o f t h e respective collector.
special function
The temperature difference between tank and collector increases enormously during operation; the collector circuit cannot dissipate the heat.
Switch-on temperature difference Ton to large?
no yes
Non-ideal position of the collector sensor (e.g. flatscrew sensor instead of sensor in sensor wells)?
yes
Change Ton and Toff correspondingly.
Ac ti vate tube co ll e c to r function if necessary.
o.k.
Collector circuit pump defective?
no yes
Heat exchanger calcified?
no
yes
Heat exchanger blocked?
yesno
Heat exchanger too small?
yes
Check / replace it
Decalcify it
Clean it
Replace with correctly sized one.
21
Page 22
Tanks cool down at night
a b
Collector circuit pump runs during the night?
no yes
Collector temperature is at night higher than the out­door temperature
no yes
Sufficient tank insulation?
yes no
Insulation close enough to the tank?
yes no
Are the tank connections insulated?
yes no
Warm water outflow upwards?
no yes
Check controller: Manual operation active? Tube collector function active? Tank cooling or antifreeze function active?
Check the check valve in the flow and the return pipe with regard to the functional efficiency.
Increase insulation.
Re p lace ins u la t ion or increase it.
Insulate the connections.
Change connection and let the water flow hori­zo n t al l y or th r o ug h a siphon (downwards); less tank losses now ?
no yes
Control the non-return va lv e i n wa rm wa t e r circulation - o.k.
yes no
The thermosiphoning in
Further pumps which are
connected to the solar tank
must also be checked.
Clean or replace it the circulation line is too strong; insert a stronger valve in the non-return valve or an electrical 2-port valve behind the circulation pump; the 2-port valve is open when the pump is activated, otherwise it is closed; connect pump and 2-por t valve electrically in parallel; activate the circulation again
The solar circuit pump does not work, although the collector is considerably warmer than the tank.
Is the control lamp (LED) illuminated?
There is no current; check
fuses / replace them and
check power supply.
yes no
Does the pump start up in manual operation?
no
yes
The adjusted temperature
difference for starting the
pump is to high; choose a
value which makes more
sense.
Is the pump current enabled by the controller?
Does the warm water circulation run for a very long time?
no yes
Ci rc u lat i on pum p an d blocking valve should be switched off for one night; less tank losses?
yes no
a
22
o.k.
Use the circulation pump with timer and switch-off thermostat (energy efficient circulation).
Check whether the pumps of the ba cku p he a ti ng circuit run at night; check whether the non-return valve is defective; problem solved ?
no
b
yes
o.k.
no
yes
Are the controller fuses o.k. ?
no yes
Replace fuses.
Is the pump stuck?
yes
Tu r n th e p u m p s ha f t
using a screwdriver; now
passable?
no
Pump is defective - replace
it
Co nt r ol l e r m i g h t b e
defective - replace it or
contact the distributor.
Page 23
Warranty
Make any warranty claim in the country where you purchased the appliance. In such cases, please contact our representation or the importer.
Our warranty applies only if:
— These installation instructions have been observed
— Exclusively accessories designated for this appliance have been
used
— All required steps up to and including commissioning have be
carried out by a qualied contractor
— Maintenance as specied has been carried out
— Exclusively our spare parts have been used for repairs
Environment and recycling
Please help us protect the environment. Dispose of the appliance and its packaging in accordance with national regulations.
23
Page 24
Deutschland
STIEBEL ELTRON GmbH & Co. KG Dr.-Stiebel-Straße | D-37603 Holzminden Tel. 0 55 31 702 0 | Fax 0 55 31 702 480 Email info@stiebel-eltron.de www.stiebel-eltron.de
Verkauf Tel. 0180 3 700705 | Fax 0180 3 702015 | info-center@stiebel-eltron.de Kundendienst Tel. 0180 3 702020 | Fax 0180 3 702025 | kundendienst@stiebel-eltron.de Ersatzteilverkauf Tel. 0180 3 702030 | Fax 0180 3 702035 | ersatzteile@stiebel-eltron.de Vertriebszentren Tel. 0180 3 702010 | Fax 0180 3 702004
STIEBEL ELTRON Inc. 17 West Street | West Hateld MA 01088 Tel. 4 13-247-3380 | Fax 413-247-3369 Email info@stiebel-eltron-usa.com www.stiebel-eltron-usa.com
Austria
STIEBEL ELTRON Ges.m.b.H. Eferdinger Str. 73 | A-4600 Wels Tel. 07242-47367-0 | Fax 07242-47367-42 Email info@stiebel-eltron.at www.stiebel-eltron.at
Belgium
STIEBEL ELTRON Sprl/ Pvba P/A Avenue du Port 104, 5 Etage B-1000 Bruxelles Tel. 02-4232222 | Fax 02-4232212 Email info@stiebel-eltron.be www.stiebel-eltron.be
CCzech Republik
STIEBEL ELTRON spol. s r.o. K Hájům 946 | CZ-15500 Praha 5-Stodůlky Tel. 2-51116111 | Fax 2-35512122 Email info@stiebel-eltron.cz www.stiebel-eltron.cz
Denmark
PETTINAROLI A/S Madal Allé 21 | DK-5500 Middelfart Tel. 63 41 66 66 | Fax 63 41 66 60 Email info@pettinaroli.dk www.pettinaroli.dk
France
STIEBEL ELTRON S.A.S. 7-9, rue des Selliers B.P. 85107 | F-57073 Metz-Cédex 3 Tel. 03 87 74 38 88 | Fax 03 87 74 68 26 Email info@stiebel-eltron.fr www.stiebel-eltron.fr
Finland
Insinööritoimisto Olli Andersson Oy Keskuskatu 8 | FI-04600 Mäntsälä Tel. 020 720 9988 | Fax 020 720 9989 Email info@stiebel-eltron. www.stiebel-eltron.
Great Britain
Stiebel Eltron UK Ltd. Unit 12 Stadium Court Stadium Road Bromborough Wirral CH62 3QP Email: info@stiebel-eltron.co.uk www.stiebel-eltron.co.uk
Hungary
STIEBEL ELTRON Kft. Pacsirtamezo´´ u. 41 | H-1036 Budapest Tel. 01250-6055 | Fax 01368-8097 Email info@stiebel-eltron.hu www.stiebel-eltron.hu
Japan
Nihon Stiebel Co. Ltd. Ebara building 3F | 2-9-3 Hamamatsu-cho Minato-ku | Tokyo 105-0013 Tel. 3 34364662 | Fax 3 34594365 fujiki@nihonstiebel.co.jp
Netherlands
STIEBEL ELTRON Nederland B.V. Daviottenweg 36 | Postbus 2020 NL-5202 CAs-Hertogenbosch Tel. 073-623 0000 | Fax 073-623 1141 Email stiebel@stiebel-eltron.nl www.stiebel-eltron.nl
Poland
STIEBEL ELTRON sp.z. o.o ul. Instalatorów 9 | PL-02-237 Warszawa Tel. 022-846 48 20 | Fax 022-8 46 67 03 Email stiebel@stiebel-eltron.com.pl www.stiebel-eltron.com.pl
Russia
STIEBEL ELTRON RUSSIA Urzhumskaya street, 4. | 129343 Moscow Tel. (495) 775 3889 | Fax (495) 775-3887 Email info@stiebel-eltron.ru www.stiebel-eltron.ru
Switzerland
STIEBEL ELTRON AG Netzibodenstr. 23 c | CH-4133 Pratteln Tel. 061-816 93 33 | Fax 061-8 16 93 44 Email info@stiebel-eltron.ch www.stiebel-eltron.ch
Thailand
STIEBEL ELTRON Asia Ltd. 469 Moo 2, Tambol Klong-Jik Ampur Bangpa-In | Ayutthaya 13160 Tel. 035-22 00 88 | Fax 035-22 11 88 Email stiebel@loxinfo.co.th www.stiebeleltronasia.com
United States of America
STIEBEL ELTRON Inc. 17 West Street | West Hateld MA 01088 Tel. 4 13-247-3380 | Fax 413-247-3369 Email info@stiebel-eltron-usa.com www.stiebel-eltron-usa.com
Irrtum und technische Änderungen vorbehalten | Subject to errors and technical changes! | Sous réserve d‘erreurs et de modifications techniques! · Onder voorbehoud van vergissingen en technische wijzigingen! | Salvo error o modificación técnica! | Rätt till misstag och
4<AMHCMN=jbehig>
tekniska ändringar förbehålls! | Excepto erro ou alteração técnica | Zastrzeżone zmiany techniczne i ewentualne błędy | Omyly a technické změny jsou vyhrazeny! | A muszaki változtatások és vedések jogát fenntartjuk! |
не исключается. Stand 06/09
ВозмоҖность неточностейи технических изменений
A 291478-35631-8540
Loading...